11436_-_AVCRAD_Plans.pdf
PDF 18 MB Posted
- Solicitation number
- 0000031570
- Issued by
- Fresno County, Kern County, Fresno City, Kernville CDP, California
About this file
This document is an advertisement for bids for the California Military Department's (CMD) Electric Vehicle Supply Equipment (EVSE) project at the Madera Armory and AVCRAD facilities in Madera/Fresno County, California. The project involves the labor, materials, and services necessary to install and electrically connect EVSE infrastructure, including wiring devices and all required associated items for a complete and operational system. The scope also includes saw cutting, trenching, backfilling, and finishing of the affected lot surface to restore it to original condition. The project is being bid in accordance with Government Code 14838.7 and is open only to Small Business and Micro Business contractors certified through the California Department of General Services, Office of Small Business and DVBE Services. Bids are due by 2:00 PM on June 25, 2024, and a mandatory pre-bid site inspection tour will be held on June 11, 2024.
The estimated cost of the project is $212,200.00, with a contract term of 60 calendar days. The successful bidder will be required to furnish payment and performance bonds, each in the amount of 100 percent of the contract price. Contractors and subcontractors must abide by all federal, state, and local health and safety mandates, and costs associated with adhering to these mandates are the responsibility of the contractor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 11436_-_Madera_Plans.pdf | ||
| 11436_-_Complete_Project_Manual.pdf | ||
| 11436_-_Bid_Package_Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E DAKOTA AVEE DAKOTA AVE
E AIRW
AYS BLVD
N P
E A C
H A
V E
N C
H E S T N
U T A
V E
E SHIELDS AVE
E CLINTON AVE
E McKINLEY AVE
E McKINLEY AVE
N C
L O
V
IS
A V E
E ASHLAN AVE
PROJECT LOCATION
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D ti .d w g T .0
T it le
S h e e t B C
F .c tb P lo t b y s c h h in a
F e b
:1 a m
Date Signed:
02-07-2023
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
TITLE SHEET
T1.0
SHEET INDEX
SHEET NO. TITLE
T1.0 TITLE SHEET
C1.0 OVERALL SITE PLAN
C2.0 DEMOLITION PLAN
C3.0 SITE PLAN
C4.0 DETAILS
E1.0 ELECTRICAL CONDUIT PLAN
E2.0 CONDUIT SECTIONS & DETAILS
E2.1 CONDUIT SECTIONS & DETAILS
E3.0 ELECTRICAL SCHEDULE & CIRCUITS
R1.0 REFERENCE DRAWINGS
R2.0 TITLE 24 DOCUMENTS
TOTAL NUMBER OF SHEETS = 11
LOCATION MAP
NOT TO SCALE
ANCHORAGE NOTES:
1. ANCHOR SYSTEMS:
A. EPOXY ANCHORS: COMPLYING WITH ICC ESR-2508, OR ICC ESR-3187, OR ICC ESR-3298.
B. MECHANICAL ANCHORS: COMPLYING WITH ICC ESR-4266, OR ICC ESR-2502
2. INSTALLATION: SEE MANUFACTURER'S WRITTEN INSTRUCTIONS AND REFERENCED ICC ES
REPORT.
A. MATERIALS NOT TO BE PENETRATED BY FASTENERS OR ANCHORS: POST-TENSIONED
CONCRETE AND PRECAST CONCRETE, PRESTRESSED CONCRETE UNLESS SPECIFICALLY
DETAILED HEREIN OR AS ACCEPTED IN WRITING BY ARCHITECT (STRUCTURAL ENGINEER).
WHEN INSTALLATION IS PERMITTED, LOCATE PRESTRESSING AND POST-TENSIONED
TENDONS ACCURATELY PRIOR TO INSTALLATION.
B. DRILLING HOLES IN EXISTING CONCRETE FOR ANCHORS: USE NON-PNEUMATIC, ROTARY
HAMMER TOOLS WITH ANSI COMPLIANT NON-REBAR CUTTING DRILL BITS TO DRILL HOLES
TO PROPER TOLERANCE. LOCATE EXISTING REBAR INCLUDING PRESTRESSING AND
POST-TENSIONING TENDONS USING NON-HAZARDOUS, NON-DESTRUCTIVE METHODS
WITH ACCURATE LOCATION TOLERANCES (PLUS OR MINUS ONE INCH PRIOR TO DRILLING
HOLES TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING OR
PRESTRESSING/POST-TENSIONING TENDONS. HOLES SHALL BE THOROUGHLY CLEANED
PER THE MANUFACTURERS WRITTEN RECOMMENDATIONS PRIOR TO INSTALLATION OF
ANCHORS.
C. DELETERIOUS MATERIALS: KEEP ANCHORS, INCLUDING HOLES FOR DRILL AND EPOXY
ANCHORS AND MECHANICAL ANCHORS FREE OF DUST, GREASE, AND OTHER MATERIALS
THAT IMPAIR CHEMICAL AND MECHANICAL BOND.
3. TESTING FOR EXPANSION ANCHORS:
A. SPECIAL INSPECTION: SPECIAL INSPECTOR WILL PERFORM CONTINUOUS SPECIAL
INSPECTION DURING INSTALLATION.
B. TEST QUANTITY: INSPECTOR SHALL TEST 50% OF ANCHORS USED FOR
EQUIPMENT/NON-STRUCTURAL COMPONENT ANCHORAGE.
C. TEST LOADS FOR:
A. 3/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 3/8" EXPANSION ANCHOR: 25 FT-LBS
B. 1/2"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 1/2" EXPANSION ANCHOR: 40 FT-LBS
C. 5/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 5/8" EXPANSION ANCHOR: 60 FT-LBS
D. HIGH-STRENGTH EPOXY ADHESIVE COMPLYING WITH ICC ESR-2508, ICC ESR-3298 OR
ICC ESR-3187
D. TESTING METHOD:
A. HYDRAULIC RAM METHOD: THE ANCHORS SHALL BE TESTED BY DIRECT PULL WITH A
HYDRAULIC JACK. DURING THE TEST, THE ANCHORS SHALL HAVE NO OBSERVABLE
MOVEMENT.
B. TORQUE WRENCH METHOD: THE ANCHORS SHALL BE TESTED BY THE USE OF A
CALIBRATED WRENCH. THE APPLICABLE TEST LOAD SHALL BE REACHED WITHIN
ONE-HALF TURN OF THE NUT.
E. FAILED ANCHORS: IF ANY ANCHOR(S) FAIL IN TESTING, TESTING OF REMAINING ANCHORS
OF THE SAME SIZE AND CATEGORY NOT PREVIOUSLY TESTED SHALL BE COMPLETED.
4. POST-INSTALLED ANCHORAGE: CONTRACTOR SHALL INSTALL ANCHORAGE AT ALL LOCATIONS
ILLUSTRATED IN THE CONSTRUCTION DOCUMENTS. POST-INSTALLED ANCHORS SHALL
CONFORM TO CBC REQUIREMENTS, AND BE INSPECTED BY A SPECIAL INSPECTOR.
CONCRETE NOTES:
1. CONCRETE COMPRESSIVE STRENGTH: ALL CONCRETE SHALL ATTAIN A MINIMUM
COMPRESSIVE STRENGTH AS SHOWN IN THE CONCRETE STRENGTH TABLE BELOW AT 28
DAYS, U.N.O. ON PLANS. SEE ALSO SULFATE CONTENT NOTES
2. AGGREGATES IN CONCRETE: SHALL BE NATURAL SAND AND ROCK (150 LB/CU. FT)
CONFORMING TO ASTM C33. AGGREGATE SHALL HAVE PROVEN SHRINKAGE
CHARACTERISTICS OF LESS THAN 0.04% PER ASTM C157. DO NOT CHANGE SOURCE OF
AGGREGATE DURING COURSE OF WORK WITHOUT WRITTEN CONSENT OF ENGINEER.
3. CEMENT: SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C150. CEMENT SHALL BE
TYPE II OR AS REQUIRED TO SATISFY SITE SOIL CONDITIONS. REFER TO TABLE 4 OF ASTM
C150 FOR CONCRETE CEMENT REQUIREMENTS ON SOIL CONTAINING SULFATE. REFER TO
THE CONCRETE STRENGTH TABLE FOR MAXIMUM WATER TO CEMENT RATIO. USE A MINIMUM
OF (6) SACK OF CEMENT FOR EACH CUBIC YARD OF CONCRETE.
CONCRETE STRENGTH
CONDITION
MIN 28-DAY
COMPRESSIVE
STRENGTH,
F'C
CONCRETE
TYPE*
MAXIMUM
AGGREGATE
SIZE
WATER TO
CEMENT
RATIO
MAX
SLUMP**
SLAB ON
GRADE/
CONC PADS
4,000 PSI
NORMAL-WEIGHT
CONCRETE
(NWC)
3/4" 0.50 4"
* MAXIMUM DRY WEIGHT OF LIGHTWEIGHT CONCRETE SHALL BE 115 PCF.
** SLUMP SHALL BE MEASURED PRIOR TO THE ADDITION OF SUPERPLASTICIZER (IF USED.)
REBAR CLEAR COVER IN CONCRETE: THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN
REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHER
WISE:
REBAR CLEAR COVER FOR CAST-IN-PLACE CONCRETE
CONDITION COVER
SLAB ON GRADE CENTER OF SLAB OR 2" MIN
4. VIBRATION: VIBRATION OF CONCRETE SHALL BE IN ACCORDANCE WITH GENERAL
PROVISIONS OUTLINED IN PORTLAND CEMENT ASSOCIATION SPECIFICATION ST26.
5. CURING: CONCRETE SHALL BE MAINTAINED AT IN A MOIST CONDITION FOR A MINIMUM OF
FIVE DAYS AFTER IS PLACEMENT. FOR CONCRETE OTHER THAN SLAB ON GRADE, APPROVED
CURING COMPOUNDS MAY BE USED IN LIEU OF MOIST CURING. ONLY IF APPROVED BY THE
ENGINEER OR ARCHITECT.
6. INSPECTIONS, TESTING & QUALITY ASSURANCE: REFER TO SHEET SN1 FOR DEPUTY SPECIAL
INSPECTION, TESTING & STRUCTURAL OBSERVATION REQUIREMENT. A MINIMUM OF ONE
COMPRESSION TEST AT 7 DAYS AND 2 TESTS AT 28 DAYS FOR ALL CONCRETE SAMPLES.
TAKE TEST AT A FREQUENCY OF ONCE EVERY 150 CU. YDS OR 5,000 SQ. FT MINIMUM.
7. DOWELS, INSERTS: SHALL BE TIED IN PLACE PRIOR TO POURING CONCRETE.
8. ANCHOR BOLTS: SHALL BE WEDGE ANCHORS.
9. CONSTRUCTION AND POUR JOINTS: LOCATIONS SHALL BE APPROVED BY ENGINEER PRIOR
TO POURING CONCRETE.
10. FORMWORK: FORMWORK TOLERANCE SHALL BE IN ACCORDANCE WITH THE C.B.C. AND A.C.I
STANDARDS.
11. PIPES IN CONCRETE: PIPES MAY PASS THROUGH STRUCTURAL CONCRETE IN SLEEVES, BUT
SHALL NOT BE EMBEDDED THEREIN. PIPES OR DUCTS EXCEEDING ONE-THIRD THE SLAB OR
WALL THICKNESS SHALL NOT BE PLACED IN THE STRUCTURAL CONCRETE UNLESS
SPECIFICALLY DETAILED.
12. EXPOSED CORNERS: PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS.
13. DRYPACK OR GROUT: SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI AND BE
COMPOSED OF ONE PART PORTLAND CEMENT TO NOT MORE THAN THREE PARTS SAND.
14. FLY ASH: NOT PERMITTED.
DESIGN INFORMATION & PARAMETERS:
1. BASIC WIND SPEED (101 MPH) AND WIND EXPOSURE CATEGORY C.
2. LATITUDE = 36.785672N, LONGITUDE = -119.720518W
3. S1 = 0.22 G
, SD1 = 0.4
G
, SS = 0.67
G
, SDS = 0.63
G
(SITE CLASS D ASSUMED)
NOTE:
1. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE
WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE
AUTHORITIES HAVING JURISDICTION (AHJ) AND THEIR LATEST ADOPTED EDITIONS (IN
EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING
PUBLICATIONS:
- CALIFORNIA CODE OF REGULATIONS TITLE 24:
· 2022 CALIFORNIA ELECTRICAL CODE (CEC)
· 2022 CALIFORNIA FIRE CODE (CFC)
· 2022 CALIFORNIA BUILDING CODE (CBC)
· 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)
· 2022 CALIFORNIA REFERENCED STANDARDS CODE (CRSC)
· 2020 NATIONAL ELECTRICAL CODE (NEC)
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
· AMERICANS WITH DISABILITIES ACT (ADA)
· TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
· APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE
2. PRIOR TO MAKING REVISIONS TO THE EXISTING PHASE SERVICE, VERIFY EXISTING
SEQUENCE OF THE CIRCUITS AND MAKE CERTAIN THAT EVERY ITEM IS THOROUGHLY
PREPARED. PRIOR TO SCHEDULED OUTAGES MAKE CERTAIN THAT EVERY ITEM IS
THOROUGHLY PREPARED, THAT ALL REQUIRED MATERIALS ARE ON-SITE 7 DAYS PRIOR
TO THE SCHEDULED OUTAGE, THAT SPARE MATERIALS ARE AVAILABLE IN THE EVENT
OF DAMAGE OR DEFECTS, AND THAT THE REQUIRED PERSONNEL ARE AVAILABLE TO
COMPLETE THE WORK DURING THE SCHEDULED OUTAGE. DO THE ACTUAL WORK AT AN
OFF-PEAK TIME, OR OVERTIME, AS ARRANGED WITH THE STATE'S PROJECT DIRECTOR
OR AS HEREINAFTER SPECIFIED. ONCE THE WORK IS STARTED, VIGOROUSLY
PROSECUTE IT TO COMPLETION TO KEEP DOWNTIME TO A MINIMUM. ENSURE THAT
EXISTING ELECTRICAL PHASE SEQUENCE (ELECTRICAL PHASE ROTATION) OF THE
SYSTEM IS MAINTAINED. BE PREPARED TO TEMPORARILY SERVE THE EXISTING SERVICE
OR DISCONTINUE THE NECESSARY REVISIONS IN THE EVENT OF AN EMERGENCY OR
OTHER CONDITION WHICH MAKES IT IMPOSSIBLE TO FINISH THE SCHEDULED WORK ON
TIME.
3. NAMEPLATES:
A. PROVIDE NAMEPLATES ON EQUIPMENT, DEVICES, PANELS AND FIELD MOUNTED
INSTRUMENTS (PRESSURE SWITCHES, LIMIT SWITCHES, ETC.) TO IDENTIFY EACH ITEM
WITH ITS RESPECTIVE SERVICE OR FUNCTION. USE BLACK-ON-WHITE LAMINATED
PLASTIC (WHITE LETTERING ON BLACK BACKGROUND), WITH BEVELED EDGES AND
ENGRAVED LETTERING NOT LESS THAN 1/4 INCH HIGH UNLESS OTHERWISE NOTED.
ATTACH WITH 1/4-INCH-LONG NO. 4 PHILLIPS, ROUND HEAD, COARSE THREAD, TYPE
410 STAINLESS STEEL, THREAD-CUTTING SCREWS WITH BLUNT POINT UNLESS
OTHERWISE SPECIFIED. FOR EXTERIOR NAMEPLATES, PROVIDE SILICON SEAL FOR
SCREW PENETRATIONS. FOR CAST IRON ENCLOSURES MOUNT NAMEPLATES WITH
SETON TUFF-BOND #TB2 ADHESIVE.
B. PROVIDE NAMEPLATES FOR INTERNAL DEVICES OF EQUIPMENT (CONTROL RELAYS,
CONTACTORS, TIMERS, TERMINAL BLOCKS, ETC.). MOUNT NAMEPLATES ADJACENT
TO, NOT ON, THE DEVICE.
C. PROVIDE SINGLE, DEDICATED NAMEPLATES FOR DEVICES MOUNTED WITHIN AND ON
EQUIPMENT. PROVIDE AS A MINIMUM A SINGLE DEDICATED NAMEPLATE FOR EACH
DEVICE (RELAY, SWITCH, TERMINAL BLOCK, METER, ETC.). NAMEPLATE SHALL AGREE
WITH IDENTIFICATION ON MANUFACTURER'S DRAWING. ON DEVICES MOUNTED IN
FRONT COMPARTMENT DOORS, PROVIDE EACH DEVICE WITH TWO NAMEPLATES, ONE
ON THE FRONT AND ONE ON THE BACK OF THE FRONT COMPARTMENT DOOR. THE
NAMEPLATES MOUNTED ON THE BACK OF THE DOOR SHALL BE STICK-ON TYPE.
FIRE SAFETY NOTES:
1. FIRE DEPARTMENT ACCESS ROAD SHALL BE MAINTAINED AT ALL TIMES, AND
SHALL BE PROVIDED TO BE WITHIN 100 FEET OF TEMPORARY FIRE
DEPARTMENT CONNECTIONS. (2019 CFC SECTION 3310)
2. FIRE SAFETY DURING DEMOLITION AND CONSTRUCTION SHALL COMPLY
WITH CBC CHAPTER 33 AND CFC CHAPTER 33.
FLOOD ZONE NOTES:
1. PROJECT SITE LOCATED WITHIN FLOOD HAZARD ZONE X; AREA OF MINIMAL
FLOOD HAZARD.
2. FIRM PANEL: 06019C1590H.
3. MAP EFFECTIVE DATE; 02 18, 2009.
4. MAP IS COUNTYWIDE, PANEL PRINTED.
GENERAL CONTRACT NOTES:
1. CONTRACTOR SHALL PROVIDE ALL MATERIALS SUCH AS TOOLS, EQUIPMENT, LABOR, AND
INCIDENTALS REQUIRED INCLUDING THE CONSTRUCTION OF ALL PROPOSED IMPROVEMENTS
SHOWN ON THE PLANS AND AS SPECIFIED BY THE GOVERNING STANDARDS AND/OR THE
CIVIL AND ELECTRICAL ENGINEERS.
2. CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL EXISTING UTILITIES PRIOR TO
CONSTRUCTION OF THE PROPOSED IMPROVEMENTS.
3. IF DAMAGED DURING CONSTRUCTION, THE CONTRACTOR SHALL REPLACE IN KIND ALL
EXISTING STRUCTURES, WALKWAYS, CURB & GUTTER, LANDSCAPING, AND/OR OTHER
IMPROVEMENTS TO AN EXISTING OR BETTER CONDITION.
4. CONTRACTOR SHALL REPLACE ALL EXISTING STRIPING, SIGNAGE AND MARKINGS DAMAGED
DUE TO PROJECT CONSTRUCTION ACTIVITIES. CONTRACTOR TO REMOVE EXISTING
STRIPING BEFORE PLACING PROPOSED STRIPING PATTERNS.
5. ALL WORK SHALL BE CONFINED WITHIN THE EASEMENTS AND/OR CONSTRUCTION LIMITS AS
SHOWN ON THE PLANS.
6. APPROVAL OF THESE PLANS BY THE AUTHORITIES HAVING JURISDICTION DOES NOT
AUTHORIZE ANY WORK TO BE PERFORMED UNTIL A PERMIT OR NOTICE TO PROCEED HAS
BEEN ISSUED.
7. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL NOTIFY ALL UTILITY AUTHORITIES
OR UTILITY COMPANIES HAVING POSSIBLE INTEREST IN THE WORK OF THE CONTRACTOR'S
INTENTION TO EXCAVATE PROXIMATE TO EXISTING FACILITIES AND THE CONTRACTOR SHALL
VERIFY THE LOCATION OF ANY UTILITIES IN THE WORK AREA. THE CONTRACTOR SHALL
NOTIFY UNDERGROUND SERVICE ALERT (U.S.A.) TWO (2) DAYS PRIOR TO BEGINNING ANY
EXCAVATION.
8. THE CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION FROM ANY PROPERTY OWNER
GIVING HIM PERMISSION TO ENTER HIS PROPERTY FOR THE PURPOSE OF CONSTRUCTING
THE IMPROVEMENTS DELINEATED ON THE PLANS AND TRANSITION THERETO.
9. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL BE PROVIDED AS SPECIFIED WITHIN THIS
SET OR APPROVED EQUAL. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL MATCH THE
SAME QUALITY AND CAPACITY AS INDICATED HEREIN.
10. CONTRACTOR MUST IMMEDIATELY NOTIFY THE ENGINEER OF RECORD, IDENTIFIED BY THE
PROFESSIONAL ENGINEERING SEAL AND SIGNATURE ON THESE PLANS, OF ANY SITE
CONDITION(S) AND/OR DESIGN INFORMATION THAT PREVENTS THE CONTRACTOR FROM
COMPLYING WITH THE LAWS, REGULATIONS AND/OR BUILDING CODES.
11. ALL CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH DGS STANDARD
CONSTRUCTION SPECIFICATIONS.
PROJECT LOCATION:
PROJECT IS LOCATED AT:
5168 EAST DAKOTA AVENUE,
FRESNO, CA 93727
APN: 494-020-21T
SCOPE OF EV IMPROVEMENT WORK:
1. SITE AND ELECTRICAL INFRASTRUCTURE IMPROVEMENTS FOR INSTALLATION OF EV
CHARGERS.
2. IMPACTED EXISTING PARKING = 11 TOTAL SPACES; 11 STANDARD SPACES
PROPOSED FLEET EV CHARGER TABULATION
EV CHARGER NO. OF EVCS(S) NO. OF PORT(S)
DUAL (LEVEL 2) 5 10
TOTAL TOTAL EVCS(S) = 5 TOTAL PORT(S) = 10
CBC 11B-228.3.2 EXCEPTION #1: EVCS NOT AVAILABLE TO THE GENERAL PUBLIC AND INTENDED
FOR USE BY A DESIGNATED VEHICLE OR DRIVER SHALL NOT BE REQUIRED TO COMPLY WITH
SECTION 11B-228.3.2
LIST OF CONSULTANTS:
STRUCTURAL: ELECTRICAL:
BRIAN BROOKS
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
BRIAN DUFFY
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
PROJECT DIRECTOR:
JANELLE GOULDING
DEPARTMENT OF GENERAL
SERVICES (DGS)
DIRECT: (916) 441-9205
CELL: (916) 823-7059
FAX: (916) 376-6216
OWNER/REPRESENTATIVE
INFORMATION:
FRESNO AVCRAD
5168 EAST DAKOTA AVENUE,
FRESNO, CA 93727
EMAIL: ANDREW.HERNANDEZ@CMD.CA.GOV
CONTACT: CAPTAIN ANDREW HERNANDEZ
UTILITY NOTE:
UTILITY INFORMATION SHOWN HEREON IS BASED ON OBSERVATION OF VISIBLE EVIDENCE BY
A FIELD SURVEY. THE ENGINEER CAN MAKE NO GUARANTEE AS TO THE ACCURACY OR
COMPLETENESS OF THE UNDERGROUND UTILITY FACILITIES SHOWN. PRIOR TO ANY SITE
EXCAVATIONS, THE CONTRACTOR SHALL CONTACT THE OWNER AND UNDERGROUND
SERVICE ALERT (U.S.A.) AND REQUEST THAT THEY IDENTIFY THE LOCATION OF ALL
UNDERGROUND UTILITIES AT THE SITE. SEE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
DESIGN CRITERIA:
CALIFORNIA ADMINISTRATIVE CODE (CAC) 2022
CALIFORNIA BUILDING CODE (CBC) 2022
CALIFORNIA ELECTRICAL CODE (CEC) 2022
CALIFORNIA FIRE CODE (CFC) 2022
CALIFORNIA REFERENCED STANDARDS CODE (CRSC) 2022
NATIONAL ELECTRICAL CODE (NEC) 2020
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
ARC-FLASH NOTE:
1. ALL NEW ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANELBOARDS SHALL BE
PROVIDED WITH AN ARC-FLASH HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL
CONTRACTOR, IN COMPLIANCE TO THE THE REQUIREMENTS OF THE LATEST CEC 110.16. AN
ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE LATEST NFPA 70E - 130.5,
SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD WARNING
LABEL/MARKING TEMPLATE/S SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEER OF
RECORD (EEOR) FOR REVIEW AND APPROVAL.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
Issue date May 24, 2024 000000000000011436
LP
BO
BO
BO
BO
BO
LP
LP
WV
WV
CO
BO BO BO BO
BOBO
BOBO
BOBO
BOBO
BOBO
LP
WHM
LP
PROJECT LOCATION:
SEE DEMOLITION PLAN ON
SHEET C2.0, SITE PLAN ON
SHEET C3.0, AND ELECTRICAL
CONDUIT PLAN ON SHEET E1.0
E DAKOTA AVE E DAKOTA AVE
N P
E A C
H A
V E
E A
IR
W
A Y S B
L V D
OWNER: FRESNO CITY OF
APN: 494-020-21T
O W
N E R C A D
IG
A N P
A L M
L A K E S L
L C
A P N -0
-4
S
OWNER: CADIGAN PALM
LAKES LLC
APN: 493-063-39S
OWNER: KELLER
FRESNO LLC
APN: 493-063-38S
OWNER: FRESNO SUPREME INC
APN: 493-020-27S OWNER: PONTIAC 2 LLC
APN: 493-070-70S
OWNER: FRESNO CITY OF
APN: 494-020-22T
OWNER: FRESNO CITY OF
APN: 494-020-23T
OWNER: FRESNO CITY OF
APN: 494-020-32T
OWNER: BRH-JR LLC
APN: 493-063-20S
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D s i0
.d w g C
.0
O v e ra ll S it e P la n B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
OVERALL SITE PLAN
C1.0
0 25 50 100 150 200
SCALE IN FEET
SCALE: 1"=100'
SYMBOL LEGEND:
EXISTING PROPERTY LINE
AREA OF WORK
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
AREA REQUIRING PERMISSIONS
AND GUARD CHECK-IN TO ENTER;
NOT OPEN TO THE GENERAL
PUBLIC
LP
BO
BO
BO
BO
LP
LP
WV
WV
CO
WHM
LP
EXISTING GAS VALVE
EXISTING MAIN SWITCH BOARD
"MSB", 2000A, 480/277V, 3P, 4W
E DAKOTA AVE
EJB
(TYP)
11 1111
14 14
(TYP)
(TYP)
(TYP)
(TYP) (TYP)
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D d e .d w g C .0
D e m o lit io n P la n B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
DEMOLITION PLAN
C2.0
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
EXISTING SYMBOL LEGEND:
BOLLARD
CLEANOUT
DOOR/GATE
ELECTRICAL CABINET
ELECTRICAL JUNCTION BOX
ELECTRICAL TRANSFORMER
INTERNATIONAL SYMBOL OF
ACCESSIBILITY
LIGHT POST
WATER MANHOLE
ROLL GATE
SIGN
STREET LIGHT
STREET LIGHT
WATER MANHOLE
WATER VALVE
WHEELSTOP
EXISTING ASPHALT CONCRETE
PAVEMENT
EXISTING BUILDING
EXISTING CONCRETE
EXISTING CONCRETE BLOCK WALL
EXISTING GRAVEL
BUILDING OVERHANG
CHAIN LINK FENCE
IRON FENCE
STRIPING
ELECTRICAL LINE
WATER LINE
BO
CO
ECA
EJB
ET
LP
WMH
WMH
WV
DEMOLITION NOTES:
1. THE "LIMIT OF DEMOLITION" SHOWN IS
APPROXIMATE AND IS GENERALLY CONSIDERED TO
BE THE MINIMUM REMOVAL REQUIREMENTS.
CONTRACTOR MUST COORDINATE AS NOTED IN THE
LEGEND.
2. CONTRACTOR SHALL LEGALLY DISPOSE OF ALL
DEMOLISHED MATERIALS OFF SITE.
3. CONTRACTOR SHALL PROTECT ALL EXISTING
UTILITY IMPROVEMENTS NOT SPECIFICALLY
DESIGNATED FOR REMOVAL.
4. THE ON-SITE UNDERGROUND UTILITIES SHOWN ON
THIS SHEET ARE AT AN APPROXIMATE LOCATION.
THE EXTENT, LOCATIONS AND SIZES ARE UNKNOWN.
THE CONTRACTOR SHALL POTHOLE TO LOCATE AND
VERIFY THE UNDERGROUND UTILITY LINES PRIOR
TO REMOVAL.
5. CONTRACTOR TO PROTECT AND PRESERVE IN
PLACE ANY FOUND SURVEY MONUMENTS. ANY
MONUMENTS DISTURBED SHALL BE RESET BY A
LICENSED SURVEYOR AND THE APPROPRIATE
PAPERWORK FILED WITH THE CITY OR COUNTY.
6. ALL HAZARDOUS MATERIALS ENCOUNTERED
DURING SITE DEMOLITION SHALL BE REMEDIATED
AND DISPOSED OF PER STATE AND EPA
REQUIREMENTS.
7. CONTRACTOR SHALL CONTACT AND COORDINATE
WITH ALL UTILITY AGENCIES PRIOR TO THE START
OF ANY DEMOLITION OR CONSTRUCTION.
8. ANY EXISTING UTILITIES AND/OR IMPROVEMENTS
THAT BECOME DAMAGED DURING CONSTRUCTION
SHALL BE COMPLETELY RESTORED TO THE
SATISFACTION OF THE OWNER AND AGENCY
HAVING AUTHORITY, AT THE CONTRACTOR'S SOLE
EXPENSE.
DEMOLITION LEGEND:
PROTECT EXISTING ASPHALT CONCRETE PAVEMENT
TO REMAIN
PROTECT EXISTING BLOCK WALL TO REMAIN
PROTECT EXISTING BOLLARD TO REMAIN
PROTECT EXISTING BUILDING TO REMAIN
PROTECT EXISTING CHAIN LINK FENCE TO REMAIN
PROTECT EXISTING CONCRETE TO REMAIN
PROTECT EXISTING CONCRETE SIDEWALK TO REMAIN
PROTECT EXISTING SIGN TO REMAIN
PROTECT EXISTING SWING GATE TO REMAIN
PROTECT EXISTING UTILITY TO REMAIN
REMOVE AND LAWFULLY DISPOSE OF ASPHALT
CONCRETE PAVEMENT: 439 S.F.
REMOVE AND LAWFULLY DISPOSE OF GRAVEL: 25 S.F.
SAWCUT
H-20 TRAFFIC RATED TRENCH PLATING
LIMIT OF STRIPING REMOVAL
REMOVE EXISTING IMPROVEMENTS AS NECESSARY TO
CONSTRUCT NEW IMPROVEMENTS SHOWN ON THESE
PLANS UNLESS OTHERWISE NOTED ON THE PLAN. THE
REMOVAL OF IMPROVEMENTS MUST BE COORDINATED
WITH ALL PLAN SHEETS. CONTRACTOR MUST ALSO
COORDINATE REMOVAL OF IMPROVEMENTS WITH
UTILITY AGENCIES. PROTECT ALL IMPROVEMENTS NOT
DESIGNATED FOR REMOVAL. SEE NOTE 1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BOBO
BO
BO
BO BOBO
BO
LP
BO
BO
BO
BO
BO
WV
WV
CO
WHM
EXISTING GAS VALVE
EXISTING MAIN SWITCH BOARD
"MSB", 2000A, 480/277V, 3P, 4W
E DAKOTA AVE
EJB
PB
PB-1 PB-2 PB-3
(T
Y P
(T
Y P
T Y P
( T Y P
T Y P
9'9' 9' 9' 9' 9'
6'-9"
(TYP)
4'-6"
(TYP)
A
A
B
(TYP)
I
D
(TYP)
D
(TYP)
E
G (TYP)
H
H
BO
BO
BO
BO
BO
BOBO
BO BO
BO
8" 3'-1" 7"
4'4' 6" 6"
A
A
B
(TYP)
C
F
H
H
1'-3" 3'-5"
8"1'-3" 3'-1" 7"
6" 2'-3" 1'-7"
9"6" 6"
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D s i0
.d w g C
.0
S it e P la n B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
SITE PLAN
C3.0
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
A
C3.0
ENLARGED BOLLARD AND EQUIPMENT SPACING
SCALE: 1"=2'
CONSTRUCTION LEGEND:
2' WIDE ELECTRICAL UTILITY TRENCH. TRENCH,
BACKFILL AND RESURFACING PER DETAIL [C/E2.1]
FURNISH AND INSTALL FIXED BOLLARDS PER DETAIL
[A/C4.0]
PAINT 4" WIDE GREEN PERIMETER LINE WITH 4"
WIDE GREEN DIAGONAL LINES AT 3' ON CENTER
PAINT 4" WIDE GREEN STRIPE
REPAINT STRIPING REMOVED DURING TRENCHING
TO MATCH EXISTING
CONSTRUCT EQUIPMENT PAD PER DETAIL [B/C4.0]
CONSTRUCT CONCRETE PAD PER DETAIL [B/E2.0]
FOR MAKE READY INSTALLATION WITH STUB & CAP
SEE ELECTRICAL CONDUIT PLAN FOR ADDITIONAL
ELECTRICAL IMPROVEMENTS
SEE ENLARGED BOLLARD AND EQUIPMENT SPACING
PER DETAIL [A/C3.0]
PROPOSED BTC POWER [MODEL NUMBER
L2P-30-240-15] DUAL CHARGE PORT STYLE
CHARGERS TO BE INSTALLED BY OTHERS. SEE
DETAIL [A/R1.0] AND [B/R1.0] (SHOWN FOR
REFERENCE ONLY)
PROPOSED WHITE STRIPING IMPROVEMENTS
LIMITS OF ASPHALT CONCRETE PAVEMENT
IMPROVEMENTS
LIMITS OF CONCRETE IMPROVEMENTS
A
B
C
D
E
F
G
H
I
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
NOTES:
1. LOCATE FIXED BOLLARDS SO THAT THEY DO NOT INTERFERE
WITH THE OPENING OF EQUIPMENT DOORS.
2. CLEAR ALL DIRT AND DEBRIS IN THE GENERAL LOCATIONS
INDICATED FOR INSTALLATION.
3. SUPPORT AND BRACE BOLLARDS IN POSITION UNTIL
CONCRETE HAS CURED.
16"
(M
IN
(M
IN
PAINT SAFETY
YELLOW
4" GALVANIZED SCH.40
STEEL POST (WEIGHT
= 9.1 LBS/FT) SEE PLAN
FOR LOCATION
3" WIDE REFLECTING
TAPE
PROVIDE GALVANIZED
4" POST CAP FITTING
SECURED TO POST
FINISHED
SURFACE
CLASS "B"
CONCRETE
FOOTING
FILL BOLLARDS
SOLIDLY WITH
CONCRETE
10'-3"
3" CLR.
(TYP)
1'
(TYP)
C
L R
(T
Y P
(T Y P
C L R
(T
Y P
3" CLR.
(TYP)
10'-3"
PLAN VIEW
#4 @ 12" O.C.
BOTH WAYS
EQUIPMENT CONCRETE PAD MINIMUM CONCRETE
COMPRESSIVE STRENGTH OF 4,000 PSI REQUIRED
EQUIPMENT CONCRETE PAD MINIMUM CONCRETE
COMPRESSIVE STRENGTH OF 4,000 PSI REQUIRED
3" CLR.
(TYP)
3" CLR.
(TYP)
C
L R
(M
IN
10'-3"
FINISHED
SURFACE
COMPACT 12" OF NATIVE SOIL MATERIAL TO MINIMUM
95% RELATIVE COMPACTION PER ASTM D1557
SECTION A-A
A A
#4 @ 12" O.C.
BOTH WAYS
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D d t0
.d w g C
.0
D e ta ils B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
DETAILS
C4.0
A
C4.0
FIXED BOLLARD
NOT TO SCALE
B
C4.0
EQUIPMENT PAD
NOT TO SCALE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BO
BOBO
BO
BO
BO BOBO
BO
LP
BO
BO
BO
BO
BO
WV
WV
CO
WHM
EXISTING GAS VALVE
EXISTING MAIN SWITCH BOARD
"MSB", 2000A, 480/277V, 3P, 4W
E DAKOTA AVE
EJB
PB
PB-1 PB-2 PB-3
(P1)
(P1)
(P1)
(P1)
(K1-K5)
(K3-K5) (K5, AND
C1)
EVCS-1
(CHARGE
PORT 1 & 2)
EVCS-3
(CHARGE
PORT 5 & 6)
EVCS-5
(CHARGE
PORT 9 &
10)
EVCS-2
(CHARGE
PORT 3 & 4)
EVCS-4
(CHARGE
PORT 7 & 8)
C
F
F
F
G H (TYP)
D E E
K
L
BO
BO
BO
BO
BO
BOBO
BO BO
BO
6" 2'-3" 1'-7" 3'-5"1'-3"
4'-4"
8"1'-3" 3'-1" 7"
4'-4"
(P1)
(P2)
(K1-K5)
A
B
F
F
F
I
I
T Y P
1'-9" 4'-4" 3'-11"
10' (TYP)
J
J
J
J
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n st ru c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D e l0
.d w g E .0
E le c tr ic a l C o n d u it P la n B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
Date Signed:
02-07-2023
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
ELECTRICAL CONDUIT PLAN
E1.0
A
E1.0
ENLARGED EQUIPMENT LAYOUT
SCALE: 1"=2'
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
ELECTRICAL LEGEND:
FURNISH AND INSTALL 208Y/120V, 400 AMP BUS, 250
AMP MAIN, 3Ø, 4W, SERVICE CT METER AND MAIN
SWITCHBOARD "EV" PER DETAILS [A/E2.0] AND [C/E3.0]
FURNISH AND INSTALL75kVA STEP DOWN
TRANSFORMER "TX-EV" PER DETAILS [A/E2.0] AND
[B/E3.0]
FURNISH AND INSTALL 17"x30"x12"D OPEN BOTTOM
FLAT WALL PULL BOX WITH TRAFFIC RATED SECURITY
BOLTED MARKED "ELECTRIC" COVER. GROUT SEAL
CONDUIT PENETRATIONS AND SEAL CONDUITS WITH
DUCT SEAL OR EQUAL TO PREVENT WATER ENTRY.
SEE DETAIL [B/E2.1]
FURNISH AND INSTALL 17"x30"x12"D OPEN BOTTOM
FLAT WALL PULL BOX WITH TRAFFIC RATED SECURITY
BOLTED MARKED "ELECTRIC" COVER. GROUT SEAL
CONDUIT PENETRATIONS AND SEAL CONDUITS WITH
DUCT SEAL OR EQUAL TO PREVENT WATER ENTRY.
SEE DETAIL [B/E2.0] & [B/E2.1], AND NOTE 12
FURNISH AND INSTALL 17"x30"x12"D OPEN BOTTOM
FLAT WALL PULL BOX WITH TRAFFIC RATED SECURITY
BOLTED MARKED "ELECTRIC" COVER. GROUT SEAL
CONDUIT PENETRATIONS AND SEAL CONDUITS WITH
DUCT SEAL OR EQUAL TO PREVENT WATER ENTRY.
SEE DETAIL [A/E2.1] & [B/E2.1], AND NOTE 12
SEE DETAIL [C/E2.1] FOR THE FURNISHING AND
INSTALLATION OF BELOW GRADE PVC CONDUIT. SEE
CONDUIT SCHEDULE FOR COUNT AND CONDUIT SIZE
FURNISH AND INSTALL MAKE READY INSTALLATION
WITH STUB & CAP. CONSTRUCT PER DETAIL [B/E2.0],
[A/E2.1], AND NOTE 12
CONSTRUCT CHARGER CONCRETE PAD PER DETAIL
[A/R1.0]
#2 BARE COPPER GROUND WIRE GROUNDING RING
3/4" X 10' COPPER CLAD GROUND ROD
SEE ENLARGED EQUIPMENT LAYOUT PER DETAIL
[A/E1.0]
FURNISH AND INSTALL 480V, 125A, 3P CIRCUIT
BREAKER, AS SHOWN IN SINGLE LINE DIAGRAM ON
SHEET E3.0. FIELD FIT BREAKER MAKE AND MODEL, TO
ENSURE COMPATIBILITY WITH EXISTING MAIN
SWITCHBOARD "MSB", AND INCLUDE BREAKER CUT
SHEETS WITH EQUIPMENT SUBMITTAL FOR
ENGINEERING REVIEW AND APPROVAL
PROPOSED SERVICE CT METER AND MAIN
SWITCHBOARD "EV"
PROPOSED 75KVA STEP DOWN TRANSFORMER "TX-EV"
PROPOSED PULL BOX
3/4" X 10' COPPER CLAD GROUND ROD
PROPOSED BTC POWER [MODEL NUMBER
L2P-30-240-15] DUAL CHARGE PORT STYLE CHARGERS
TO BE INSTALLED BY OTHERS. SEE DETAIL [A/R1.0] AND
[B/R1.0] (SHOWN FOR REFERENCE ONLY)
2/0 AWG BURIED BARE COPPER GROUND WIRE
ELECTRICAL CONDUIT; SIZE AND COUNT AS NOTED
A
B
C
D
E
F
G
H
I
J
K
L
PB
CONDUIT SCHEDULE
CONDUIT
NUMBER
FROM TO
CONDUCTORS ALL 90°C THWN-2 OR
SIMILAR UNLESS NOTED OTHERWISE
CONDUIT
SIZE & TYPE
COMMENTS
P1
EXISTING 2000A MAIN SWITCH
BOARD "MSB"
PROPOSED 75kVA STEP DOWN
TRANSFORMER "TX-EV"
(3) #1 AWG Cu, (1) #6 AWG Cu GND 3" PVC
EXISTING UTILITY POWER TO STEP
DOWN TRANSFORMER
P2 PROPOSED 75kVA STEP DOWN
TRANSFORMER "TX-EV"
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
(4) 250 MCM Cu, (1) #2 AWG Cu GND 3" PVC
K1
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
PB-1
(4) #8 AWG Cu, (1) #8 AWG Cu GND, TAGGED
(EVCS-1, L1, L2, GROUND)
1" PVC
K2
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
PB-1
(4) #8 AWG Cu, (1) #8 AWG Cu GND, TAGGED
(EVCS-2, L1, L2, GROUND)
1" PVC
K3
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
PB-2
(4) #8 AWG Cu, (1) #8 AWG Cu GND, TAGGED
(EVCS-3, L1, L2, GROUND)
1" PVC
K4
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
PB-2
(4) #8 AWG Cu, (1) #8 AWG Cu GND, TAGGED
(EVCS-4, L1, L2, GROUND)
1" PVC
K5
PROPOSED 400A SERVICE CT
METER AND MAIN
SWITCHBOARD "EV"
PB-3
(4) #8 AWG Cu, (1) #8 AWG Cu GND, TAGGED
(EVCS-5, L1, L2, GROUND)
1" PVC
C1 PB-2 PB-3 (1) CAT6 DATA CABLE 1" PVC
B
E1.0
CONDUIT SCHEDULE
ELECTRICAL NOTES:
1. ELECTRICAL UTILITY LINE TO BE PROTECTED IN PLACE WHEN POSSIBLE. IF EXISTING LINES INTRODUCE EXCESSIVE CONSTRAINTS DURING THE INSTALLATION OF THE
ELECTRICAL EQUIPMENT, REMOVE AND RELOCATE EXISTING LINES AS NEEDED, USING THE PROPOSED UTILITY TRENCH. IF THE ELECTRICAL LINE CANNOT BE SALVAGED THE
CONTRACTOR MUST LAWFULLY DISPOSE OF THE ELECTRICAL LINE AND REPLACE WITH LIKE-IN-KIND.
2. ALL ELECTRICAL POWER IN CLOSE PROXIMITY TO THE INSTALLATION OF THE ELECTRICAL EQUIPMENT MUST BE POWERED OFF PRIOR TO THE START OF CONSTRUCTION, TO
PREVENT ANY ELECTRICAL INJURIES.
3. HAND DIG ALL UTILITIES IN CLOSE PROXIMITY TO THE INSTALLATION OF THE ELECTRICAL EQUIPMENT TO AVOID DAMAGING ANY UTILITY LINE.
4. SEE SINGLE LINE DIAGRAM ON SHEET E3.0.
5. SEE CONDUIT SCHEDULE FOR WIRE SIZE, CONDUIT FILL AND WIRE TAGS.
6. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH GROUNDING AND BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING CONDUCTIVE MATERIALS, ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT THAT ENCLOSES OR CARRIES ELECTRICAL CONDUCTOR OR
EQUIPMENT THAT IS LIKELY TO BECOME ENERGIZED. SEE CEC/NEC 250.4(A)(1) THROUGH (5) FOR FURTHER DESCRIPTION.
7. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION SHALL BE 6' PER CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
8. MINIMUM CONDUIT BURIAL DEPTH SHALL BE 24".
9. PER CEC/NEC 110.26 "ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION
AND MAINTENANCE OF SUCH EQUIPMENT."
10. CONDUIT BODIES SHALL BE USED AS NEEDED TO MAINTAIN LESS THAN 360° OF CONDUIT BENDS BETWEEN PULL POINTS.
11. STEP DOWN TRANSFORMER AND SERVICE CT METER TO SHARE GROUND RODS.
12. EACH CHARGER SHALL HAVE A 1-1/2" PVC CONDUIT STUBBED AND CAPPED FROM ITS ADJACENT PULL BOX. THESE CONDUITS SHALL PROVIDE ENTRY INTO THE EQUIPMENT
FOR BOTH POWER AND CAT-6 CABLING.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
BILL OF MATERIALS
REFERENCE
NUMBER
ITEM QUANTITY
STEPDOWN TRANSFORMER, CASE STYLE NEMA TYPE 3R,
480-208/120V, 3Ø, 75 KVA
1 UNIT
SERVICE CT METER AND MAIN SWITCHBOARD, NEMA TYPE 3R,
208/120V, 3Ø, 4W, 400 AMP, 42 KAIC FULLY RATED
1 UNIT
3 MAIN BREAKER, 240 VOLT, 250 AMP TRIP, 65 KAIC AT 240V, 3 POLE 1 EA
4 BRANCH BREAKER, 240 VOLT, 40 AMP, 65 KAIC AT 240V, 2 POLE 10 EA
5 3/4" PVC BELL END 2 EA
6 1" PVC BELL END 5 EA
7 3" PVC BELL END 3 EA
8 3/4" SCH. 40 PVC, 24" RADIUS 2 EA
9 1" SCH. 40 PVC, 18" RADIUS 5 EA
10 3" SCH. 40 PVC, 24" RADIUS 3 EA
11 3/4" SCH. 40 PVC AR
12 1" SCH. 40 PVC AR
13 3" SCH. 40 PVC AR
14 3/4" PVC COUPLING AR
15 1" PVC COUPLING AR
16 3" PVC COUPLING AR
17 GROUND BUS BAR KIT 1 EA
18 3/4" X 10' COPPER CLAD GROUND ROD, INSTALLED VERTICALLY 2 EA
19 GROUND TAP COMPRESSION FITTING, #2 TO 3/4" ROD 2 EA
20 #8 CONDUCTOR THWN-2 AR
21 #8 CONDUCTOR GRN INSULATION THWN-2 AR
22 #6 CONDUCTOR GRN INSULATION THWN-2 AR
23 #2 CONDUCTOR GRN INSULATION THWN-2 AR
24 #1 CONDUCTOR THWN-2 AR
25 250 MCM CONDUCTOR THWN-2 AR
26 2/0 AWG BARE COPPER CONDUCTOR AR
27 1/2" BOLT WITH 3-1/4" EFFECTIVE EMBEDMENT AR
PLAN
SECTION A-A
WEIGHT = 590 LBS
WEIGHT = 1480± LBS
7" 2'-4" 1' 5'-10" 6"
10'-3"
6'-5"1'-9" 2'-1"
(P1)
(P2)
(K1-K5)
A A
18 2619
26 19 18
1 2
7" 2'-4" 1' 5'-10" 6"
7 75
5 6(TYP)27
(TYP)
(P1)
10 13
24 22
10 13
(TYP)
(TYP)
23 25
(P2)
(TYP)
(K1-K5)9
(TYP)
12 (TYP)
20 21 (TYP)15
SEE NOTES 7SEE NOTES 7
SEE NOTES 8
SEE NOTES 9
13'
(TYP)
(TYP)
SEE NOTES 9
SEE NOTES 10
SEE NOTES 10
C
E2.0
1'-3" 1'-3" 1'-3" 1'-3"
2'-6" 2'-6"
1'-10"
S E E N
O T E
PROPOSED 17x30x12D
PULL BOX PER DETAIL
#4 @ 12" O.C.
EACH WAY
CONCRETE
PAD
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT (TYP).
SEE NOTE 4
SCH. 40 PVC
CONDUIT
(AS NEEDED)
SCH. 40 PVC COUPLER
RIGID METALLIC
THREADED
CONDUIT
COUPLER
FINISHED
GRADE
RIGID METALLIC
CONDUIT
THREADED PLUG
SCH. 40 PVC
THREADED
MALE
ADAPTER
SCH. 40 PVC CONDUIT SWEEP,
SEE NOTE 2 AND 4
SEE NOTE 5
(K3-K5)
(K1-K2)
PROPOSED PVC FROM
DISTRIBUTION PANEL TO
EVCS CHARGER
PROPOSED PVC FROM
DISTRIBUTION PANEL TO
EVCS CHARGER
DUAL AND SINGLE EV CHARGER DUAL AND SINGLE EV CHARGER
PVC
ELECTRICAL
CONDUIT STUB
AND CAP
1'-3"1'-3" 1'-3" 1'-3" 1'-10"
2'-6"2'-6"
PLAN
AA
LINETYPE LEGEND
POWER AND GROUND
WIRES FOR EV
CHARGER (SEE
ELECTRICAL CONDUIT
PLAN ON SHEET [E1.0]
AND SINGLE LINE
DIAGRAM ON SHEET
[E3.0] FOR EXACT
WIRE SIZE)
PULL CORD FOR CAT6
CABLE. BTC POWER
TO INSTALL CAT6
CABLE DURING EV
CHARGER
INSTALLATION
PULL CORD FOR
POWER AND GROUND
WIRES. BTC POWER
TO PULL WIRES
THROUGH DURING EV
CHARGER
INSTALLATION
NOTES:
1. MATERIAL FOR SERVICE CONDUIT SHALL
BE LISTED AS ELECTRICAL CONDUIT.
ACCEPTABLE MATERIAL SHALL BE PVC
RIGID CONDUIT AND WHEN SPECIFIED,
IMC OR RIGID METALLIC CONDUIT TAPED
OR COATED FOR DIRECT BURIAL.
2. CONDUIT SWEEP SHALL BE PVC AND
HAVE A RADIUS OF 6" (MIN). RADIUS
SHALL BE INCREASED WHERE REQUIRED
PER NEC CHAPTER 9 .
3. MINIMUM CONDUIT COVER
REQUIREMENTS SHALL FOLLOW NEC
300.5 UNLESS OTHERWISE SPECIFIED.
4. EXACT CONDUIT TYPE AND SIZE MAY
VARY, REFER TO ELECTRICAL CONDUIT
SCHEDULE AND PLAN
5. CONTRACTOR TO LEAVE AN EXCESS OF
15 L.F. OF POWER AND GROUND WIRES
TO ENSURE BTC POWER HAS THE
REQUIRED LENGTH TO REACH THE
PROPOSED EV CHARGER CONNECTIONS.
SECTION A-A
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D d t0
.d w g E .0
C o n d u it S e c ti o n s
D e ta ils B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
Date Signed:
02-07-2023
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
CONDUIT SECTIONS & DETAILS
E2.0
A
E2.0
75kVA STEP DOWN TRANSFORMER "TX-EV" & DISTRIBUTION PANEL "EV"
NOT TO SCALE
B
E2.0
MAKE READY INSTALLATION WITH STUB & CAP - SELECTION 1
NOT TO SCALE
NOTES:
1. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH GROUNDING AND
BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING CONDUCTIVE MATERIALS, ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT THAT ENCLOSES OR CARRIES ELECTRICAL CONDUCTOR OR EQUIPMENT THAT IS LIKELY TO BECOME ENERGIZED. SEE CEC/NEC 250.4(A)(1) THROUGH (5) FOR FURTHER
DESCRIPTION.
2. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION SHALL BE 6' PER
CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
3. MINIMUM CONDUIT BURIAL DEPTH SHALL BE 24".
4. PER CEC/NEC 110.26 "ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT."
5. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED FOR TERMINATION OF ELECTRICAL CONDUCTORS RATED 75°C
OR HIGHER.
6. CONTRACTOR TO SCAN FOR REBAR OR OTHER STRUCTURAL SUPPORT PRIOR TO CORE DRILLING OR WALL
MOUNTING EQUIPMENT.
7. UNDERGROUND GROUNDING CONDUCTORS TO BE BURIED AT A MINIMUM OF 30 INCHES BELOW GRADE.
8. GROUNDING BUS TO BE INSTALLED IN ELECTRICAL EQUIPMENT ROOMS, IN ROOMS HOUSING SERVICE EQUIPMENT, AND ELSEWHERE AS INDICATED. INSTALL BUS HORIZONTALLY, ON INSULATED SPACERS 2 INCH MINIMUM FROM WALL, 6 INCH MINIMUM ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.
9. DRIVE GROUND RODS UNTIL TOPS ARE 2 INCHES BELOW FINISHED FLOOR OR FINAL GRADE UNLESS
OTHERWISE INDICATED.
A. INTERCONNECTED GROUND RODS WITH GROUNDING ELECTRODE CONDUCTOR
BELOW GRADE AND AS OTHERWISE INDICATED. MAKE CONNECTIONS WITHOUT
EXPOSING STEEL OR DAMAGING COATING IF ANY.
B. USE EXOTHERMIC WELDS FOR ALL BELOW GRADE CONNECTIONS.
10. GROUND RING: INSTALL A GROUNDING CONDUCTOR, ELECTRICALLY CONNECTED TO EACH INDICATED ITEM, EXTENDING AROUND THE PERIMETER OF THE ITEM INDICATED.
A. BURY GROUND RING NOT LESS THAN 24 INCH FROM BUILDING'S FOUNDATION.
B. FOR GROUND RING SYSTEM, INSTALL AT LEAST THREE RODS SPACED AT LEAST ONE-ROD LENGTH FROM
EACH OTHER AND LOCATED AT LEAST THE SAME DISTANCE FROM OTHER GROUNDING ELECTRODES, AND
CONNECT TO THE EQUIPMENT GROUNDING BUS.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
PULL BOX
TO BE OF
COMPOSITE
TYPE
PULL BOX LID TO
BE SECURELY
BONDED TO
GROUND ROD IF
METALLIC
CRUSHED ROCK
ROOFING
PAPER LAYER
5/8 x 8' COPPER
GROUND ROD. IF
BOX IS COMPOSITE
WITH COMPOSITE
LID, GROUND ROD
IS NOT NEEDED
*V A R
IE
S
VARIES
(WIDTH TO MATCH
PULL BOX)
COMPACT 12"
OF NATIVE SOIL
MATERIAL TO
MINIMUM 95%
RELATIVE
COMPACTION
PER ASTM D1557
FLUSH
BOLTDOWN HOLES
WITH BOLTS (TYP)
1/2" THICK STEEL
DIAMOND PLATE
COVER FOR H-20
TRAFFIC LOADING,
MARKED "ELECTRIC"
*VARIES
CONCRETE
AREAS
ASPHALT CONCRETE
PAVEMENT AREAS
FLUSH
NOTES:
1. SEE SHEET E1.0 FOR PULL
BOX SIZE AND LOCATION.
2. CONTRACTOR TO CUT
HOLES REQUIRED FOR
CONDUIT AND GROUND
ROD.
3. PULL BOX TO COMPLY
WITH ASTM C858 FOR
DESIGN AND
MANUFACTURING
PROCESS.
4. RECAST CONCRETE PULL
BOX SHALL COMPLY WITH
THE SPECIFICATION
SECTION 26 05 43,
UNDERGROUND DUCTS
AND RACEWAYS FOR
ELECTRICAL SYSTEMS
(M
IN
(M
IN
2"
VARIES
(SEE PLAN)
7-INCH OF 3/4-INCH MEDIUM, TYPE B ASPHALT CONCRETE
SAWCUT T-SECTION AND MATCH ADJACENT
ASPHALT CONCRETE
METALLIC WARNING TAPE
95% MINIMUM RELATIVE
COMPACTED NATIVE
BACKFILL UNDER CONCRETE
AND ASPHALT AREAS, PER
ASTM D1557. 90% MINIMUM
RELATIVE COMPACTED
NATIVE BACKFILL UNDER
LANDSCAPE AREAS, PER
ASTM D1556 AND ASTM
D1557. SEE NOTE 3 ELECTRICAL CONDUIT,
SEE ELECTRICAL PLANS
FOR SIZE AND COUNT
(TYP). SEE NOTE 3
24" (MAX) DEPTH, AT LEAST 12" ABOVE
CONDUIT (SEE NOTE 1)
EXISTING ELECTRICAL CONDUIT WHERE
APPLICABLE
EXISTING ELECTRICAL
CONDUIT CROSSING
WHERE APPLICABLE
MINIMUM CONDUIT
BURIAL DEPTH
SHALL BE 24".
TRENCH RESURFACING
IN CONCRETE AREA
TRENCH RESURFACING
IN ASPHALT AREA
95% MINIMUM RELATIVE
COMPACTED NATIVE
MATERIAL IN TOP 2' OF
TRENCH
SAWCUT AND
MATCH
ADJACENT
CONCRETE
6"
(MIN)
CALTRANS CLASS 3
CONCRETE
EXISTING CONCRETE
6"
EXISTING ASPHALT CONCRETE PAVEMENT
EXISTING
CURB
6"
SEE NOTE 2
NOTES:
1. PER NEC 300.5 (D)(3), UNDERGROUND
SERVICE CONDUCTORS THAT ARE
NOT ENCASED IN CONCRETE AND
THAT ARE BURIED 450MM (18") OR
MORE BELOW GRADE SHALL HAVE
THEIR LOCATION IDENTIFIED BY A
WARNING RIBBON THAT IS PLACED IN
THE TRENCH AT LEAST 300MM (12")
ABOVE THE UNDERGROUND
INSTALLATION.
2. APPLY SLURRY COAT IN A UNIFORM
THICKNESS IN ACCORDANCE WITH
ASTM D3910 AND ALLOW TO CURE
FOR A MINIMUM OF 5 DAYS. ROLL
SLURRY SEAL TO REMOVE RIDGES
AND PROVIDE A UNIFORM, SMOOTH
SURFACE.
3. DIRECT BURIED UTILITY TRENCH
BACKFILL SHALL COMPLY WITH THE
FOLLOWING SPECIFICATIONS:
- SECTION 31 20 00, EARTH MOVING
- SECTION 26 05 43, UNDERGROUND
DUCTS AND RACEWAYS FOR
ELECTRICAL SYSTEMS
- SECTION 32 12 16, ASPHALT PAVING
- SECTION 03 30 00, CAST-IN-PLACE
CONCRETE
3" CLEAN SAND BEDDING
TO BE PLACED BELOW
AND ABOVE CONDUIT
PER ASTM C33/C33M;
FINE AGGREGATE
EMERGENCY SHUT-OFF
EVCS-#
LOCATED IN/AT
(PANEL EV)
5"
1 2
4 "
(T Y P
4 "(T Y P
7 8
1 4
1 4
1 4
1 4
1 4
1 4
1 4
7 8
3 4
3 4
" 43
" 3
SEE NOTES 1, 4 & 6
SEE NOTES 1, 2, 3 & 5. TEXT TO BE PRINTED
IN THE COLOR WHITE NOT BLACK
SEE NOTE 1
NOTES:
1. ELECTRICAL VEHICLE CHARGING
STATION SHUT-OFF LABEL TO HAVE
WHITE LETTERS ON RED FIELD. WITH
RED AND WHITE DIAGONAL STRIPED
BORDER.
2. EMERGENCY SHUT-OFF LABEL SHALL
READ THE EVCS-# THAT IS CORRELATED
WITH ONE ANOTHER. SEE BELOW FOR
EXAMPLE:
EMERGENCY SHUT-OFF
EVCS-1
LOCATED IN/AT
(PANEL EV)
3. FOR EVCS-# AND LABELING, SEE
ELECTRICAL SCHEDULE & CIRCUITS ON
SHEET E3.0.
4. EMERGENCY SHUT-OFF LABEL TO BE
SELF-ADHESIVE: VINYL, THERMAL,
TRANSFER-PRINTED, 5.5-MIL-THICK,
MULTICOLOR, WEATHER AND
UV-RESISTANT, PRESSURE-SENSITIVE
ADHESIVE LABELS, CONFIGURED FOR
INTENDED USE AND LOCATION.
5. THE TEXT HEIGHT SHALL BE 1/4" HIGH
WITH WHITE LETTERING.
6. EMERGENCY -SHUT-OFF LABEL SHALL
COMPLY WITH THE FOLLOWING
SPECIFICATION:
- SECTION 26 05 53, IDENTIFICATION FOR
ELECTRICAL SYSTEMS
7. PLACE EMERGENCY SHUT-OFF LABEL
ON EACH EVCS CHARGER.
PROPOSED PVC FROM
DISTRIBUTION PANEL TO
EVCS CHARGER
PROPOSED PVC FROM
DISTRIBUTION PANEL TO
EVCS CHARGER
C
E2.0
1'-3" 1'-3" 1'-3" 1'-3"
2'-6" 2'-6"
1'-10"
S E E N
O T E
PROPOSED 17x30x12D
PULL BOX PER DETAIL
#4 @ 12" O.C.
EACH WAY
CONCRETE
PAD
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT (TYP).
SEE NOTE 4
SCH. 40 PVC
CONDUIT
(AS NEEDED)
SCH. 40 PVC COUPLER
RIGID METALLIC
THREADED
CONDUIT
COUPLER
FINISHED
GRADE
RIGID METALLIC
CONDUIT
THREADED PLUG
SCH. 40 PVC
THREADED
MALE
ADAPTER
SCH. 40 PVC CONDUIT SWEEP,
SEE NOTE 2 AND 4
SEE NOTE 5
(K5)
(K3-K4)
(C1)
SEE NOTE 5
1'-3" 1'-3"
2'-6"
1'-10"
RIGID METALLIC
CONDUIT
THREADED PLUG
SCH. 40 PVC
THREADED
MALE
ADAPTER
RIGID METALLIC
THREADED
CONDUIT
COUPLER
#4 @ 12" O.C.
EACH WAY
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT (TYP).
SEE NOTE 4
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT SWEEP,
SEE NOTE 2 AND 4
DUAL AND SINGLE EV CHARGER
PLAN
DUAL AND SINGLE EV CHARGER DUAL AND SINGLE EV CHARGER
AA
PVC
ELECTRICAL
CONDUIT STUB
AND CAP
PVC
ELECTRICAL
CONDUIT STUB
AND CAP
1'-3" 1'-3" 1'-3" 1'-3" 1'-10"
2'-6" 2'-6"
1'-3"1'-3" 1'-10"
2'-6"
SECTION A-A
LINETYPE LEGEND
POWER AND GROUND
WIRES FOR EV
CHARGER (SEE
ELECTRICAL CONDUIT
PLAN ON SHEET [E1.0]
AND SINGLE LINE
DIAGRAM ON SHEET
[E3.0] FOR EXACT
WIRE SIZE)
PULL CORD FOR CAT6
CABLE. BTC POWER
TO INSTALL CAT6
CABLE DURING EV
CHARGER
INSTALLATION
PULL CORD FOR
POWER AND GROUND
WIRES. BTC POWER
TO PULL WIRES
THROUGH DURING EV
CHARGER
INSTALLATION
NOTES:
1. MATERIAL FOR SERVICE CONDUIT SHALL
BE LISTED AS ELECTRICAL CONDUIT.
ACCEPTABLE MATERIAL SHALL BE PVC
RIGID CONDUIT AND WHEN SPECIFIED,
IMC OR RIGID METALLIC CONDUIT TAPED
OR COATED FOR DIRECT BURIAL.
2. CONDUIT SWEEP SHALL BE PVC AND
HAVE A RADIUS OF 6" (MIN). RADIUS
SHALL BE INCREASED WHERE REQUIRED
PER NEC CHAPTER 9 .
3. MINIMUM CONDUIT COVER
REQUIREMENTS SHALL FOLLOW NEC
300.5 UNLESS OTHERWISE SPECIFIED.
4. EXACT CONDUIT TYPE AND SIZE MAY
VARY, REFER TO ELECTRICAL CONDUIT
SCHEDULE AND PLAN
5. CONTRACTOR TO LEAVE AN EXCESS OF
15 L.F. OF POWER AND GROUND WIRES
TO ENSURE BTC POWER HAS THE
REQUIRED LENGTH TO REACH THE
PROPOSED EV CHARGER CONNECTIONS.
Date Signed:
02-07-2023
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D d t0
.d w g E .1
C o n d u it S e c ti o n s
D e ta ils B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
Date Signed:
02-07-2023
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
CONDUIT SECTIONS & DETAILS
E2.1
B
E2.1
TRAFFIC RATED PULL BOX
NOT TO SCALE
C
E2.1
DIRECT BURIED ELECTRICAL UTILITY TRENCH
NOT TO SCALE
D
E2.1
EMERGENCY SHUT-OFF LABEL
NOT TO SCALE
A
E2.1
MAKE READY INSTALLATION WITH STUB & CAP - SELECTION 2
NOT TO SCALE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0628
V3
M
EXISTING MAIN SWITCH BOARD "MSB",
2000 AMP BUS, 2000 AMP MAIN, 480Y/277V, 3Ø, 4W
PULL SECTION CT METERING SECTION
LANDING
LUGS (TYP)
MAIN
2000A 3P
FROM
UTILITY
TRANSFORMER
125A
PROPOSED
3P
TO EXISTING
CIRCUIT
TO EXISTING
CIRCUIT
YΔ
75kVA, 480-208Y/120V
3Ø, 4W (NEMA 3R)
NEW STEP DOWN
TRANSFORMER "TX-EV"
SERVICE CT METER AND MAIN SWITCHBOARD "EV", 400 AMP BUS, 250 AMP MAIN
208Y/120V, 3Ø, 4W, 22 kAIC MINIMUM
(NEMA 3R)
3" U.G. PVC TO
TRANSITION TO
3" A.G. RMC WITH
(4) 250 MCM Cu AND
(1) #2 Cu GND
1 2
40A 2P
40A 2P
3 4
40A 2P
40A 2P
3" U.G. RMC TO TRANSITION
TO 3" A.G. PVC WITH
(3) #1 Cu AND
(1) #6 Cu GND
5 6
40A 2P
40A 2P
7 8
40A 2P
40A 2P
9 10
40A 2P
40A 2P
MODEM 1 WITHIN
EVCS-1
(MODEM 1 TO SERVE
EVCS-1 THROUGH
EVCS-2)
PB-1
TO EVCS-1
CHARGE PORTS 1 & 2
(30 FLA + 30 FLA)
TO EVCS-2
CHARGE PORTS 3 & 4
(30 FLA + 30 FLA)
EVCS-2
COMMUNICATION
CONNECTION
PB-2 PB-3
TO EVCS-3
CHARGE PORTS 5 & 6
(30 FLA + 30 FLA)
TO EVCS-4
CHARGE PORTS 7 & 8
(30 FLA + 30 FLA)
MODEM 2 WITHIN
EVCS-3
(MODEM 2 TO SERVE
EVCS-3 THROUGH
EVCS-5)
EVCS-4
COMMUNICATION
CONNECTION
EVCS-5
COMMUNICATION
CONNECTION
TO EVCS-5
CHARGE PORTS 9 & 10
(30 FLA + 30 FLA)
1" U.G. PVC WITH
(4) #8 Cu AND
(1) #8 Cu GND
(TYP FOR EVCS-1
THROUGH EVCS-5)
1-1/2" U.G. PVC WITH
(4) #8 Cu AND
(1) #8 Cu GND
(TYP FOR EVCS-1
THROUGH EVCS-5)
(1) CAT6 DATA CABLE
TO ENTER THROUGH THE SAME
1-1/2" PVC CONDUIT USED FOR
THE POWER AND GROUND WIRES
(TYP FOR EVCS-1 THROUGH
EVCS-2)
(1) CAT6 DATA CABLE
TO ENTER THROUGH THE
SAME 1-1/2" PVC CONDUIT
USED FOR THE POWER
AND GROUND WIRES
(TYP FOR EVCS-3
THROUGH EVCS-5)
M
PULL SECTION CT METERING SECTION
LANDING
LUGS (TYP)
MAIN
250A 3P
PROPOSED SERVICE CT METER AND MAIN SWITCHBOARD "EV"
BUS AMPS: 400 NEMA: 3R MFR: TBD LOC: FRESNO AVCRAD MTG: PEDESTAL MAIN AMPS: 250
PHASE: 3 WIRES: 4 VOLTS: 208Y/120V
FEEDER: (4) 250 MCM Cu AND
(1) #2 AWG Cu GND
FEEDER ENTRY AT: BOTTOM AIC RATING: 22,000A SYM.
DESCRIPTION
VOLT-AMPS
BKR TRIP CKT
L1 L2 L3
CKT BKR TRIP
VOLT-AMPS
DESCRIPTION
L1 L2 L3 L1 L2 L3
EVCS-1
CHARGE PORT 1
3120.0 0.0 0.0
1 2
3120.0 0.0 0.0 EVCS-1
CHARGE PORT 20.0 3120.0 0.0 3 4 0.0 3120.0 0.0
EVCS-2
CHARGE PORT 3
0.0 0.0 3120.0
5 6
0.0 0.0 3120.0 EVCS-2
CHARGE PORT 43120.0 0.0 0.0 7 8 3120.0 0.0 0.0
EVCS-3
CHARGE PORT 5
0.0 3120.0 0.0
9 10
0.0 3120.0 0.0 EVCS-3
CHARGE PORT 60.0 0.0 3120.0 11 12 0.0 0.0 3120.0
EVCS-4
CHARGE PORT 7
3120.0 0.0 0.0
13 14
3120.0 0.0 0.0 EVCS-4
CHARGE PORT 80.0 3120.0 0.0 15 16 0.0 3120.0 0.0
EVCS-5
CHARGE PORT 9
0.0 0.0 3120.0
17 18
0.0 0.0 3120.0 EVCS-5
CHARGE PORTS 103120.0 0.0 0.0 19 20 3120.0 0.0 0.0
- 0.0 0.0 0.0 - 21 22 - 0.0 0.0 0.0 -
- 0.0 0.0 0.0 - 23 24 - 0.0 0.0 0.0 -
CONNECTED LOAD > 12480.0 9360.0 9360.0 ESTIMATED TOTAL VOLT-AMPERES 12480.0 9360.0 9360.0 < CONNECTED LOAD
LINE 1 AMP: 208.0A L1 L2 L3 REMARKS:
LINE 2 AMP: 156.0A
24960.0 VA 18720.0 VA 18720.0 VA
65.7KVA TOTAL ESTIMATED CONNECTED LOAD: 227.9A @ 3PH, 208V
(AT 125% CONTINUOUS LOAD, 0.95 POWER FACTOR)LINE 3 AMP: 156.0A
EXISTING MAIN SWITCH BOARD "MSB"
BUS AMPS: 2,000 NEMA: 3R MFR: SQUARE D LOC: FRESNO AVCRAD MTG: PEDESTAL MAIN AMPS: 2,000
PHASE: 3 WIRES: 4 VOLTS: 480Y/277V FEEDER: UTILITY FEED FEEDER ENTRY AT: BOTTOM AIC RATING: 65,000A SYM.
DESCRIPTION
VOLT-AMPS
BKR TRIP CKT
L1 L2 L3
CKT BKR TRIP
VOLT-AMPS
DESCRIPTION
L1 L2 L3 L1 L2 L3
- - - - 1 2
EETF TRAILER POWER SUPPLY
- - - - 3 4 - - -
- - - - 5 6
METTS POWER SUPPLY
- - - - 7 8 - - -
- - - - 9 10
WATER BOOSTER PUMP
- - - - 11 12 - - -
- - - - 13 14
XFMER T2
- - - - 15 16 - - -
- - - - 17 18
XFMER T1
- - - - 19 20 - - -
- - - - 21 22
PANEL HA
- - - - 23 24 - - -
- - - - 25 26
HANEL
- - - - 27 28 - - -
- - - - 29 30
XFORMER FOR PORTABLES WEST
- - - - 31 32 - - -
DISTRIBUTION PANEL DP
33 34
- 24960.0 -
PROPOSED STEP DOWN TRANSFORMER "TX-EV"- - - 35 36 - - 18720.0
- - - 37 38 18720.0 - -
- - - 39 40 - - - - -
- - - 41 42 - - - - -
- - - 43 44 - - - - -
- - - - 45 46 - - - - -
- - - - 47 48 - - - - -
- - - - 49 50 - - - - -
- - - - 51 52 - - - - -
- - - - - 53 54 - - - - -
CONNECTED LOAD > - - - ESTIMATED TOTAL VOLT-AMPERES 18720.0 24960.0 18720.0 < CONNECTED LOAD
LINE 1 AMP: - L1 L2 L3 REMARKS:
LINE 2 AMP: -
18720.0 VA 24960.0 VA 18720.0 VA - KVA TOTAL ESTIMATED CONNECTED LOAD: 2000A @ 3PH, 480V
LINE 3 AMP: -
A B A B A B
X0
H1 H2 H3
PRIMARY
A
B
C
FROM
EXISTING
2000A MAIN
SWITCH
BOARD
X1 X2 X3
SECONDARY
H2
H1 H3
X1
X2
X0
X3
G
A
B
C
G
N
TO
PROPOSED
DISTRIBUTION
PANEL "EV"
#1/0 Cu
SYSTEM
BONDING
JUMPER
#2 BARE Cu
GROUND
ELECTRODE
CONDUCTOR
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
02-07-2023 11
RF
DHELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
FRESNO AVCRAD
CALIFORNIA MILITARY DEPARTMENT
D ra w in g P -0
\S it e \f re s n o A v c ra d \c o n st ru c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \F re s n o A
V C
R A D d t0
.d w g E .0
E le c tr ic a l S c h e d u le
C ir c u it s B
C F .c tb P lo t b y s c h h in a
F e b
:1 a m
Date Signed:
02-07-2023
5168 EAST DAKOTA AVE., FRESNO, CA 93727 PROJECT #: 000000000010704
V1
ELECTRICAL SCHEDULE & CIRCUITS
E3.0
A
E3.0
SINGLE LINE DIAGRAM
NOT TO SCALE
C
E3.0
PROPOSED DISTRIBUTION PANEL "EV" LOAD SCHEDULE
NOT TO SCALE
D
E3.0
EXISTING MAIN SWITCH BOARD "MSB" LOAD SCHEDULE
NOT TO SCALE
B
E3.0
PROPOSED 75kVA STEP DOWN
TRANSFORMER "TX-EV" WIRING DIAGRAM
NOT TO SCALE
17. CONTRACTOR TO MATCH MANUFACTURER SPECIFICATIONS AND KAIC RATING FOR NEW BREAKERS.
18. CONTRACTOR TO VERIFY THE EXISTING LOAD DRAWN BY EXISTING PANEL "MSB" AND VERIFY THAT THE
EXISTING PANEL WILL HAVE THE CAPACITY TO SUPPORT THE PROPOSED LOADS.
19. COLOR-CODING FOR PHASE- AND VOLTAGE-LEVEL IDENTIFICATION, 600V OR LESS: USE COLORS LISTED
BELOW FOR UNDERGROUND SERVICE, FEEDER, AND BRANCH-CIRCUIT CONDUCTORS.
COLORS FOR 208/120-V CIRCUITS:
A. PHASE A: BLACK
B. PHASE B: RED
C. PHASE C: BLUE
20. METER PHYSICAL CHARACTERISTICS:
1. DISPLAY: BACKLIT LCD WITH ANTIGLARE AND SCRATCH-RESISTANT LENS.
2. DISPLAY OF METERED VALUES: ONE SCREEN TO SHOW AT LEAST FOUR LINES OF USER-SELECTED
VALUES ON ONE SCREEN AT THE SAME TIME. PROVIDE GRAPHICAL REPRESENTATION OF
USER-SELECTED VALUES. THE SCREEN SELECTIONS AVAILABLE AT THE DISPLAY MUST INCLUDE THE
FOLLOWING:
A. METERS, INCLUDING THOSE LISTED UNDER THE FOLLOWING:
1) MEASUREMENTS.
2) THD.
3) ENERGY.
4) DEMAND.
5) MINIMUM AND MAXIMUM VALUES.
6) POWER DEMAND.
3. ELECTRICAL POWER MONITORING TO COMPLY WITH SECTION 26 09 13