100KVA Portable Generator - PWS 20250806.docx

DOCX document 24 KB Posted

Attached to
100 KVA Portable Generator
Solicitation number
2025-PZI-1635
Issued by

About this file

This Performance Work Statement (PWS) details the Department of the Air Force Materiel Command's requirement for purchasing a 100KVA Portable Generator for Hanscom AFB. The specific procurement calls for a GENERAC Portable GenSet MDG100DF4-STD3 or equivalent diesel-powered trailer-mountedGenerator with precise technical specifications, including EPA Tier 4 compliance, a 165-gallon double-wall fuel tank, and multiple power output configuration options (9 Sign Phase, Three Phase 120/208 Low Wye, and Three Phase 277/480 High Wye).

Key technical requirements include a Selective Catalytic Reduction (SCR) and Diesel Oxidation Catalyst (DOC) exhaust system, 32-hour fuel max run time at 75% load, CSA listed AC distribution, powder-coated aluminum enclosure, and a Deep Sea Electronics 7310 MKII Controller. The vendor must provide manufacturer's warranty covering 1-year unlimited hours and 2-year/2,000 hours, with delivery specifications mandating Monday-Friday delivery between 0700-1700 hours, subject to military vehicle inspection. The point of contact for this opportunity is Joshua Guerra, Operations Engineering Chief, reachable at (781) 225-2864.

View the file

Other files

File Type Posted
Bid Schedule 1635.xlsx XLSX spreadsheet
100KVA Updated Combo Synopsis Solicitation (1635) SAM.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Performance Work Statement 08 August 2025

Work Task: 160002TEMP Project Title: Purchase 100KVA Portable Generator

1. General Information

0. The Vender shall provide all labor, materials, equipment, testing, transportation, and services required to purchase and delivery a 100KVA Portable Generator to Hanscom AFB, additional generator information provided below.

0. Only items incorporated into this document from the accepted proposal shall be considered part of this performance work statement.

0. The Vender shall delivery the generator Monday thru Friday from 0700-1700. The delivery will require a vehicle inspection by military personnel. The delivery vehicle and personnel shall expect to wait several hours to get their vehicle inspected.

0. Delivery drivers shall have a clean criminal record, no pending court decisions, vehicle registration, vehicle insurance, and a real I.D. driver’s license.

0. Delivery location: Building 1810, 120 Grenier Street, Hanscom AFB, MA 01731

1. Product Requirements

1. The Vender shall purchase and deliver a GENERAC Portable GenSet MDG100DF4-STD3 or equivalent generator to Hanscom AFB.

1. The flowing are the salient characteristics of the required Generator:

1. Engine must meet EPA Tier 4 or greater.

1. Generator must run/ operate on diesel fuel.

1. Must have a Selective catalytic reduction (SCR) and Diesel Oxidation Catalyst (DOC) exhaust after-treatment that limits harmful emissions and minimizes soot. buildup.

1. Double Wall Fuel Tank with a capacity of 165 gallons or 625 liters

1. Fuel Consumption rate at Prime 100% of 8.7 gallons per hour or 33 liters per hour.

1. A Deisel Exhaust Fluid (DEF) tank capacity of 12 gallons or 45.4 liters.

1. DEF Consumption Rate at Standy 100% of 0.34 gallons per hour or 1.3 liters per hour.

1. Fuel Max Run Time of 32 hours at 75% load.

1. Shall have single to three-phase selector switch and parallel capability to provide ultimate flexibility and scalable power.

1. The 3 position selector must have outputs of:

9. Sign Phase – 120/240 Zig Zag, 78KVA Prime Power

9. Three Phase – 120/208 Low Wye, 100KVA Prime Power

9. Three Phase – 277/480 High Wye, 100 KVA Prime Power

1. The portable generator shall be trailer mounted.

1. The generator shall have CSA listed AC distribution.

1. The generator shall have a powder-coated aluminum enclosure.

1. The generator shall have Deep Sea Electronics 7310 MKII Controller/

1. The generator shall have a lockable external fuel access.

1. The Generator shall have an external remote shutdown (e-stop) located near the power output connection.

1. Warranty:

2. The vender shall provide a manufacturer’s warranty that includes 1-year unlimited hours and a 2-year 2,000 hours warranty.

5.0 Point of Contact:

Joshua Guerra Operations Engineering Chief

(781) 225-2864

File details come from the government source that posted it. Updated .