1-SMTMA Pump Station No 4 Upgrade - Bid Documents drawings.pdf
PDF 11 MB Posted
- Solicitation number
- Not on record
- Issued by
- Cumberland County, Pennsylvania
About this file
These documents are bid documents for the South Middleton Township Municipal Authority's Pump Station No. 4 Upgrade project located in Cumberland County, Pennsylvania. The project consists of three primary contracts: Contract 1 for General Construction Forcemain, Contract 2 for General Construction Pump Station, and Contract 3 for Electrical Construction Pump Station. The bid documents, dated November 2025, outline a comprehensive upgrade to an existing wastewater pump station, involving demolition of current infrastructure, installation of new force mains, a precast concrete wet well, valve vault, and associated electrical systems. The project site is situated on Meals Drive, a private road in Carlisle, PA, and includes detailed plans for site preparation, piping, electrical work, and equipment installation.
The project involves upgrading an existing pump station with new infrastructure, including two submersible wastewater pumps, a grinder, generator, control panels, and associated electrical systems. The electrical components include a 200A service entrance rated main circuit breaker, automatic transfer switch, 40kW diesel generator, and a power panelboard. The documents provide extensive technical specifications for civil, structural, process, and electrical components, with detailed drawings covering site demolition, piping, electrical layouts, and equipment mounting. The project appears to be funded through municipal infrastructure investment, with precise funding sources not explicitly detailed in the provided documents. The comprehensive design suggests a significant municipal investment in modernizing and improving wastewater infrastructure for the South Middleton Township area.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: G:\564\12637903\Digital_Design\ACAD\Sheets\General\12637903-GHD-00-DRG-00-GN-001.dwgPlotted By: Mike Wiestling5 November 2025 - 2:15 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
COVER SHEET
GN-001AS SHOWN
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
AREA MAP LOCATION MAP PROJECT
LOCATION
SITE ADDRESS:
MEALS DRIVE (PRIVATE ROAD)
CARLISLE, PA 17015
CALL BEFORE YOU DIG
PENNSYLVANIA LAW REQUIRES 3 WORKING DAYS NOTICE
FOR CONSTRUCTION PHASE AND 10 WORKING
DAYS IN DESIGN STAGE - STOP CALL
PENNSYLVANIA ONE CALL SYSTEM, INC.
1-800-242-1776 OR 811
POCS SERIAL NUMBER: 20252953906
UNDERGROUND UTILITIES ACT:
THE CONTRACTOR SHALL COMPLY WITH THE PROVISIONS OF THE PENNSYLVANIA GENERAL ASSEMBLY UNDERGROUND UTILITY LINE PROTECTION ACT, PA ACT 287 OF 1974, AS AMENDED BY ACT 50 OF 2017, 73 P.S. § 176 ET SEQ., FOR NOTIFICATION OF UTILITIES BEFORE EXCAVATION IN THE CONTRACT AREA. THE ONE UNDERGROUND UTILITIES CALL NUMBER IS 800-242-1776 OR 811.
INDIVIDUAL LOCAL UTILITIES ARE AS FOLLOWS:
COMPANY: BRIGHTSPEED
ADDRESS: 1120 S TRYON STREET SUITE 700
CHARLOTTE, NC. 28203
CONTACT: CASE WELLS
EMAIL: case.wells@brightspeed.com
PHONE: 704-314-2503
COMPANY: SOUTH MIDDLETON TWP MUNI AUTH
ADDRESS: 345 LEAR LN PO BOX 8
BOILING SPRINGS, PA. 17007
CONTACT: JOSEPHINE HALL
EMAIL: jhall@smtma.net
PHONE: 717-258-6476 EXT. 225
COMPANY: FIRSTENERGY CORPORATION
ADDRESS: 21 S MAIN ST
AKRON, OH. 44308
CONTACT: MELLYSSA ADAMS
EMAIL: madams@firstenergycorp.com
PHONE: 330-604-4073
COMPANY: PPL ELECTRIC UTILITIES CORPORATION
ADDRESS: 437 BLUE CHURCH RD
PAXINOS, PA. 17860
CONTACT: DOUG HAUPT
EMAIL: dlhaupt@pplweb.com
PHONE: 570-490-5684
COMPANY: COMCAST CABLE COMMUNICATIONS INC
ADDRESS: C/O USIC LOCATING SERVICES INC
13085 HAMILTON CROSSING BLVD STE 200
CARMEL, IN. 46032
CONTACT: USIC OFFICE PERSONNEL
PHONE: 800-811-7981
COMPANY: U S I C LOCATING SERVICES
ADDRESS: 9045 N RIVER RD SUITE 300
INDIANAPOLIS, IN. 46240
CONTACT: JEFFREY TRUMBOWER
EMAIL: jefftrumbower@usicllc.com
PHONE: 317-810-8254
COMPANY: UGI UTILITIES INC
ADDRESS: 1301 AIP DR
MIDDLETOWN, PA. 17057-5987
CONTACT: GEOFFREY FERGUSON
EMAIL: gferguson@ugi.com
PHONE: 610-807-3118HARRISBURG
YORK
LANCASTER
PHILADELPHIA
PITTSBURGH
ERIE
STATE COLLEGE
WILLIAMSPORT
SCRANTON
CHAMBERSBURG
PROJECT
LOCATION
SOUTH MIDDLETON TOWNSHIP
MUNICIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
SOUTH MIDDLETON TOWNSHIP, CUMBERLAND COUNTY, PA
CONTRACT 1 - GENERAL CONSTRUCTION FORCEMAIN
CONTRACT 2 - GENERAL CONSTRUCTION PUMP STATION
CONTRACT 3 - ELECTRICAL CONSTRUCTION PUMP STATION
BID DOCUMENTS
NOVEMBER 2025
N http://www.ghd.com http://www.ghd.com/
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: G:\564\12637903\Digital_Design\ACAD\Sheets\General\12637903-GHD-00-DRG-00-GN-002.dwgPlotted By: Mike Wiestling8 November 2025 - 10:10 AM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
1. EXISTING FACILITIES AND PIPING SHOWN LIGHT. NEW FACILITIES AND PIPING SHOWN DARK.
2. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL EXISTING PIPING ELEVATIONS, LOCATIONS, SIZE AND TYPE OF MATERIAL WITH NEW PIPING PRIOR TO CONSTRUCTION. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL EXISTING EQUIPMENT DIMENSIONS AND ELEVATIONS, AS REQUIRED, PRIOR TO
ORDERING NEW EQUIPMENT.
3. CONTRACTOR SHALL COORDINATE ALL PIPING AND OTHER CONNECTIONS WITH THE APPROVED EQUIPMENT
SHOP DRAWINGS.
4. ALL BURIED PIPING TO BE MIN. 4' BELOW GRADE, UNLESS OTHERWISE NOTED.
5. THE CONTRACTOR SHALL BE REQUIRED TO VERIFY ALL CONDITIONS AND DIMENSIONS ON THE JOB SITE BEFORE PROCEEDING WITH THE WORK AND SHALL MAKE MINOR ADJUSTMENTS AS REQUIRED ON THE JOB.
SUCH ADJUSTMENTS ARE TO BE APPROVED BY THE ENGINEER AND THE OWNER.
6. THE CONTRACTOR SHALL MAINTAIN A RECORD SET OF "AS BUILT" DRAWINGS ON THE PROJECT SITE. AT THE COMPLETION OF THE PROJECT, THESE DRAWINGS SHALL BE TURNED OVER TO THE ENGINEER AND OWNER.
THESE DRAWINGS SHALL INDICATE, BUT NOT BE LIMITED TO, CHANGES IN PIPING, INSTALLATIONS, VALVES, EQUIPMENT CHANGES, ELECTRICAL WORK, ETC.
7. DEMOLITION OF EXISTING PIPING AND EQUIPMENT MAY REQUIRE TEMPORARY SYSTEM SHUTDOWNS.
CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL SHUTDOWN PROCEDURES WITH ENGINEER AND OWNER PRIOR TO ANY DEMOLITION WORK. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL TEMPORARY EQUIPMENT, MATERIAL AND CONTROLS TO MAINTAIN SYSTEM OPERATIONS DURING CONSTRUCTION AS REQUIRED. ALL SHUTDOWNS AND STARTUPS TO BE COORDINATED WITH OWNER / OPERATOR DURING CONSTRUCTION. ONLY BOROUGH OF CARLISLE PERSONNEL SHALL PERFORM SYSTEM OPERATIONS, INCLUDING OPERATIONS OF VALVES AND PUMPS.
GENERAL NOTES (APPLY TO ALL DRAWINGS
DETAIL NUMBER
(NUMERICAL ON EACH SHEET
BEGINNING WITH DETAIL 1)
DETAIL NUMBER
SHEET WHERE DETAIL IS SHOWN
(IF ON DIFFERENT SHEET) DEPICTION BOUNDARY
TYPICAL SECTION MARKS (FOR PLANS)
TYPICAL DETAIL TITLE
TYPICAL DETAIL CALLOUT
OR
D-101
DETAIL NAME
NO SCALE
A-501
A-501
SECTION INDICATORA
X-301
SECTION LETTER
SHEET WHERE SECTION IS SHOWN
(IF SHOWN ON DIFFERENT SHEET)
A D-101
SECTION
SCALE: 1/4" = 1'-0"
SECTION LETTER
(ALPHABETICAL FOR
EACH STRUCTURE)
0 8'4'2'
SHEET WHERE SECTION
IS REFERENCED
SHEET WHERE DETAIL
IS REFERENCED
NEW GRAPHICS; EQUIPMENT, STRUCTURES,
ETC., ARE SHOWN AS BOLD LINEWORK AND
IN THIS TEXT FORMAT.
TRUE NORTH
NORTH INDICATOR
N
XXX
EQUIPMENT TAG
TYPE
NUMBER
GENERAL LEGEND
KEYNOTE INDICATOR
KEYNOTE NUMBER
ADD'L ADDITIONAL
AFF ABOVE FINISHED FLOOR
ADJ ADJUSTABLE
AGGR AGGREGATE
ALLOW ALLOWANCE
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECT OR ARCHITECTURAL
ASSY ASSEMBLY
APPROX APPROXIMATE
BLDG BUILDING
BLK BLOCK
BOT or B BOTTOM
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CIP CAST IRON PIPE
CMP CORRUGATED METAL PIPE
CO CLEANOUT
CONN CONNECTION
CY CUBIC YARD
CL CLEAR
℄ CENTER LINE
CONC CONCRETE
CONT CONTINUOUS
CPVC CHLORINATED POLYVINYL CHLORIDE
CL JT CONTROL JOINT
DL DEAD LOAD
DIA, Ø DIAMETER
DIP DUCTILE IRON PIPE
DWL DOWEL
EF EACH FACE
EA EACH
EL or ELEV ELEVATION
ELEC ELECTRIC
EQ EQUAL
EX, EXIST EXISTING
EXT EXTERIOR
FF FAR FACE/ FINISHED FLOOR
FM FORCE MAIN
FLR FLOOR
FT FEET
FTG FOOTING
G NATURAL GAS
GPM GALLONS PER MINUTE
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
HDPE HIGH-DENSITY POLYURETHYLENE
HWL HIGH WATER LEVEL
HP HORSEPOWER
ID INSIDE DIAMETER
IF INSIDE FACE
INV INVERT
I/O INPUT / OUTPUT
LF LINEAR FEET
LL LIVE LOAD
LWL LOW WATER LEVEL
M MOTOR
MGD MILLION GALLONS PER DAY
MH MANHOLE
MJ MECHANICAL JOINT
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
POLY / PE POLYETHYLENE
⅊ PLATE, PROPERTY LINE
R RADIUS
REINF REINFORCING
REQD REQUIRED
SF SQUARE FOOT
SS STAINLESS STEEL
SCH SCHEDULE
SPEC SPECIFICATION
SQ SQUARE
STL STEEL
STD STANDARD
SYM SYMBOL
TEL TELEPHONE
TEMP TEMPERATURE
TYP TYPICAL
UV ULTRAVIOLET
W WATER
WL WATER LEVEL
W/O WITHOUT
WWF WELDED WIRE FABRIC
ABBREVIATIONS:
SINGLE LINE
90° BEND
45° BEND
TEE
LATERAL WYE
REDUCER
PLUG VALVE
GATE VALVE
PIPING LEGEND
WELDED JOINT (STEEL / STAINLESS
STEEL PIPE & FITTINGS)
UNION
ITEM DOUBLE LINE
ROTAMETER
UNION
PRESSURE REDUCING VALVE
SOLENOID VALVE
PRESSURE RELIEF VALVE
Y STRAINER
CALIBRATION COLUMN
PULSATION DAMPENER
FLEXIBLE TUBING
QUICK CONNECT (FEMALE)
SCHEMATIC SYMBOLS LEGEND
PLUG VALVE
GATE VALVE
VALVE
ULTRASONIC LEVEL SENSOR
RUPTURE DISK
PRESSURE GAUGE
VACUUM REGULATOR
MOTOR OPERATOR
POLYMER FLOW METER
REDUCER
SOLENOID OPERATOR
PNEUMATIC OPERATOR
TEMPERATURE GAUGE
FLOW CONTROL VALVE
FLOW METER
COALESCING FILTER
PROCESS FLOW DIRECTION
SHEET INDEX, GENERAL NOTES
AND LEGENDS
GN-002AS SHOWN
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
SHEET INDEX
SHEET
NUMBER SHEET TITLE CONTRACT NO 1
FORCEMAIN
CONTRACT NO 2
GC PUMP STATION
CONTRACT NO 3
EC PUMP STATION
GENERAL
GN-001 COVERSHEET X X X
GN-002 SHEET INDEX, GENERAL NOTES AND LEGENDS X X X
CIVIL
C-101 KEYPLAN, LEGEND AND GENERAL NOTES - CIVIL X
C-102 PLAN AND PROFILE - CIVIL X
C-103 PLAN AND PROFILE - CIVIL X
C-104 PLAN AND PROFILE - CIVIL X
C-105 PUMP STATION SITE DEMOLITION PLAN X
C-106 PUMP STATION SITE PLAN X
C-107 PAVING PLAN X
C-108 DETOUR PLAN X
C-501 SANITARY SEWER DETAILS - CIVIL X
C-502 CIVIL DETAILS X X
CE-001 EROSION AND SEDIMENT CONTROL - NOTES X X
CE-501 EROSION AND SEDIMENT CONTROL AND RESTORATION PLAN - DETAILS X X
CE-502 EROSION AND SEDIMENT CONTROL AND RESTORATION PLAN - DETAILS X X
STRUCTURAL
ST-001 GENERAL CONCRETE NOTES AND DETAILS X X
ST-501 KIOSK ELEVATION, SECTION, AND DETAILS X
PROCESS
MPD-101 PUMP STATION DEMOLITION PLAN AND SECTION X
MP-101 PUMP STATION PLANS X
MP-301 PUMP STATION SECTIONS X
MP-501 PUMP STATION DETAILS X
ELECTRICAL
EL-001 ABBREVIATIONS AND SYMBOLOGY X
EL-101 PUMP STATION ELECTRICAL SITE PLAN X
EL-501 PUMP STATION KIOSK LAYOUT AND AIR GAP JUNCTION BOX DETAIL X
EL-502 PUMP STATION ELECTRICAL DETAILS X
EL-601 PUMP STATION SINGLE LINE DIAGRAM AND INTERCONNECTION DIAGRAM X
http://www.ghd.com http://www.ghd.com/
U/C U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C U/C DuB
DuC
Pt DuC
HdF
HdD
DuC
DuC DuC
DuB
Ub
DuC
DuB
Ub
DuC
DuC
X
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-101.dwgPlotted By: Shawn Matthews7 November 2025 - 1:15 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
KEYPLAN, LEGEND AND GENERAL
NOTES - CIVIL
C-101AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
KEYPLAN
SCALE 1" = 100' 0 200'100'
ROAD CENTERLINE
PROPERTY LINE
UTILITY POLE
BUILDINGS AND STRUCTURES OHW
U/E U/E
EXISTING OVERHEAD WIRES
EXISTING UNDERGROUND ELECTRIC
EXISTING STORM SEWER
EXISTING SANITARY SEWER
EXISTING WATER VALVE
EXISTING HYDRANT
W W EXISTING WATER LINE
STORM INLET
EXISTING SPOT ELEVATION
SOIL TYPE (TYP.)
SOIL TYPE BOUNDARY
(APPROXIMATE)
INLET PROTECTION (TYP.)
EXISTING GAS LINEG G
LEGEND:
ROAD RIGHT OF WAY LINE
X X
TREES/TREELINE
FENCEINDEX CONTOUR
INTERMEDIATE CONTOUR
EXISTING EASEMENT
NEW FORCE MAIN
LIMIT OF DISTURBANCE
SURVEY NOTES:
1. EXISTING BOUNDARY AND TOPOGRAPHIC CONDITIONS ON THIS PLAN HAVE BEEN ESTABLISHED THROUGH FIELD SURVEY BY HONOR ENGINEER CO. PERFORMED IN APRIL AND MAY 2024.
2. THIS SURVEY HORIZONTALLY REFERENCES THE NORTH AMERICAN DATUM OF 1983 (NAD 83-2011)(EPOCH:2010:0000) PENNSYLVANIA STATE PLANE COORDINATE SYSTEM, SOUTH ZONE (3702) GRID, ESTABLISHED VIA KEYNETGPS VRS (VIRTUAL REFERENCE STATION SYSTEM). THIS SURVEY VERTICALLY REFERENCES THE NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD 88).
3. THIS PLAN WAS PREPARED WITHOUT THE BENEFIT OF A TITLE REPORT AND MAY BE SUBJECT TO EASEMENTS AND OTHER RESTRICTIONS, EITHER RECORDED OR UNRECORDED. THE SURVEYOR HAS MADE NO INVESTIGATION OR INDEPENDENT SEARCH FOR EASEMENTS OF RECORD, ENCUMBRANCES, RESTRICTIVE COVENANTS, OWNERSHIP TITLE EVIDENCE OR ANY OTHER FACTS THAT AN ACCURATE AND CURRENT TITLE SEARCH MAY DISCLOSE OTHER THAN WHAT IS SHOWN ON THIS PLAN.
4. THE LOCATIONS OF UTILITIES AS SHOWN HEREON ARE BASED ON ABOVEGROUND FEATURES, FIELD OBSERVATIONS/SURVEY, AND RECORD DRAWINGS PROVIDED BY UTILITY COMPANIES.
LOCATIONS OF UNDERGROUND UTILITIES/STRUCTURES MAY VARY FROM LOCATIONS SHOWN HEREON. ADDITIONAL BURIED UTILITIES/STRUCTURES MAY BE ENCOUNTERED. NO EXCAVATIONS WERE MADE DURING THE PROCESS OF THIS SURVEY TO LOCATE BURIED UTILITIES/STRUCTURES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE EXACT LOCATION AND
DEPTH OF ALL UTILITY LINES PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITIES.
5. IN COMPLIANCE WITH PENNSYLVANIA ACT 50 OF 2017 (EFFECTIVE APRIL 28, 2018) ALL UNDERGROUND UTILITIES SHOWN ON THIS PLAN ARE A COMPILATION OF ACTUAL FIELD LOCATIONS AND DATA FURNISHED FROM INFORMATION SUPPLIED BY OTHERS. HONOR ENGINEER CO. ASSUMES NO RESPONSIBILITY FOR THE LOCATIONS OF ANY UNDERGROUND UTILITIES AS DEPICTED ON THIS DRAWING. ANY REQUESTS FOR ADDITIONAL UNDERGROUND UTILITY INFORMATION SHOULD BE DIRECTED TO THAT RESPECTIVE UTILITY COMPANY. A PA ONE CALL WAS PERFORMED PRIOR TO
FIELD SURVEYING, SERIAL #20240871977 WEST YORK STREET.
6. FORCE MAIN, WATER, AND SANITARY SEWER LINES SHOWN ARE BASED UPON A COMBINATION OF INFORMATION PROVIDED BY GHD AND FIELD LOCATIONS OF VISIBLE UTILITIES.
7. THE EASEMENT DOCUMENT PROVIDED BY SOUTH MIDDLETON TOWNSHIP MUNICIPAL AUTHORITY WAS UNABLE TO BE LOCATED OR VERIFIED IN THE RECORDER OF DEEDS OF CUMBERLAND COUNTY AND IS OF THE OPINION OF HONOR ENGINEER COMPANY TO BE AN UNRECORDED DOCUMENT. A RECORD SEARCH BY HONOR WAS PERFORMED AND UNABLE TO FIND ANY DOCUMENTS
PERTAINING TO ADDITIONAL UTILITY EASEMENTS.
8. A BOUNDARY SURVEY WAS NOT PERFORMED BY HONOR ENGINEER CO. THE LINES SHOWN HEREON ARE BASED UPON DEEDS OF RECORD AND THE BEST AVAILABLE FIELD EVIDENCE.
GENERAL NOTES:
1. THE CONTRACTOR SHALL COMPLY WITH THE PROVISIONS OF THE PENNSYLVANIA GENERAL
ASSEMBLY UNDERGROUND UTILITY LINE PROTECTION ACT, PA ACT 287 OF 1974 AS AMENDED
BY ACT 121 OF 2008 73P.S. § 176 ET. SEQ. NOTIFICATION OF UTILITIES BEFORE EXCAVATION IN
CONTRACT AREA THE ONE UNDERGROUND UTILITIES CALL NUMBER IS 800-242-1776 OR 811.
2. PRIOR TO THE START OF WORK, CONTRACTOR TO COORDINATE AND HOLD EXISTING UTILITY
PRECONSTRUCTION MEETING TO BE ATTENDED BY: OWNER, ENGINEER, CONTRACTOR, AND
ALL UTILITY OWNERS WITHIN THE PROJECT AREA.
3. IMPLEMENT EROSION AND SEDIMENTATION CONTROLS SHOWN ON DRAWINGS BEFORE
STARTING CONSTRUCTION.
4. CONTRACTOR SHALL ABIDE BY TRAFFIC CONTROL PLAN. MAINTENANCE OF TRAFFIC SHALL
COMPLY WITH PENNSYLVANIA DEPARTMENT OF TRANSPORTATION PUBLICATIONS 213 AND
408, SECTIONS 107.11 AND 900 RESPECTIVELY.
5. THE LOCATION, DEPTH, SIZE, AND TYPE OF EXISTING UTILITIES (ELECTRIC, GAS, TELEPHONE, TV CABLE, WATER, SANITARY SEWERS, STORM SEWERS, ETC.) SHOWN ON THE DRAWINGS
MAY NOT BE ACCURATE. IN MANY CASES, THE ACTUAL LOCATION AND INVERT OF THESE
UTILITIES IS NOT KNOWN. INDIVIDUAL UTILITY SERVICES FOR HOUSES AND BUILDINGS ARE
NOT SHOWN. EXACT LOCATIONS AND DEPTHS ARE TO BE VERIFIED IN THE FIELD BY THE
CONTRACTOR. THE CONTRACTOR SHALL TEST PIT, AS REQUIRED, TO ESTABLISH THE
LOCATION OF THESE FACILITIES SO APPROPRIATE ADJUSTMENT TO THE PROPOSED SANITARY
SEWER AND/OR WATER DESIGN MAY BE MADE, IF NECESSARY.
6. CONTRACTOR SHALL MAINTAIN ACCESS TO ALL DRIVEWAYS AND MAILBOXES DURING THE
COURSE OF THE WORK.
7. LENGTHS AND SLOPE(GRADE) OF PIPE SHOWN ARE CALCULATED FROM MANHOLE INSIDE
EDGE TO MANHOLE INSIDE EDGE USING THE INVERTS FROM OUTSIDE OF MANHOLE.
8. CONTRACTOR TO ADJUST ACTUAL GRADES ACCORDINGLY TO ALLOW FOR DISTANCE FROM MH
CENTERS TO INSIDE OF MH WALLS.
9. MANHOLE TOP ELEVATIONS SHOWN ARE APPROXIMATE. MANHOLES ARE TO BE SET AT GRADE
IN IMPROVED AREAS AND PRIVATE YARDS, UNLESS OTHERWISE NOTED. MANHOLES IN
WOODED AND/OR SECLUDED AREAS SHALL BE SET AT THE ELEVATION SHOWN ON THE
PROFILES OR AS DIRECTED BY THE OWNER.
10. TERMINAL MANHOLE LOCATIONS SHALL BE ADJUSTED TO SUIT LATERAL LOCATIONS AND FIELD
CONDITIONS. CONTRACTOR TO VERIFY BEFORE ORDERING MATERIALS.
11. NO TREES SHALL BE REMOVED/CLEARED FROM OUTSIDE OF THE PERMANENT SANITARY
SEWER EASEMENT UNLESS OTHERWISE NOTED.
12. AT THE END OF EACH WORK DAY, THE EXCAVATED TRENCHES SHALL BE COMPLETELY
BACKFILLED AND/OR STEEL PLATES SHALL BE PLACED OVER THE EXCAVATION.
13. TRENCH RESTORATION SHALL INCLUDE BUT NOT LIMITED TO; STREETS, MISCELLANEOUS
DRIVEWAY RESTORATION, SEEDING, SHOULDER RESTORATION, SHRUBBERY, MAIL BOXES,
FENCES, PLANTERS, GUARD RAILS, HEAD AND END WALLS, LAWN ORNAMENTS,
MISCELLANEOUS LANDSCAPING DECOR, ETC.
14. CONTRACTOR RESPONSIBLE FOR BYPASS PUMPING OF SEWERAGE WHEN REPLACING AND/OR
CONNECTING EXISTING SANITARY SEWER SYSTEMS. CONTRACTOR SHALL PROVIDE DIESEL
POWERED AUTOMATIC SELF-PRIMING UNITS, PIPING, VALVING, AND ALL NECESSARY
APPURTENANCES. A STAND-BY UNIT SHALL ALSO BE PROVIDED FOR EACH SETUP.
15. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING SURFACE OF THE STREET FROM
CONTRACTOR'S EQUIPMENT.
16. ALL MATERIALS USED AND CONSTRUCTION METHODS EMPLOYED ARE TO BE IN ACCORDANCE
WITH THE LATEST STANDARDS.
17. CONTRACTOR SHALL TEST PIT ALL KNOWN EXISTING UTILITY CROSSINGS PRIOR TO
INSTALLING ANY SANITARY SEWER AND/OR WATER PIPE TO VERIFY EXISTING HORIZONTAL
AND VERTICAL ELEVATIONS TO ASSURE NO CONFLICT.
18. SOIL TYPES SHOWN ARE FROM U.S. DEPARTMENT OF ASCS. THEY ARE SHOWN FOR GENERAL
INFORMATION PURPOSES ONLY. SOIL TYPES ENCOUNTERED MAY BE DIFFERENT.
19. PRIOR TO THE CONNECTION INTO AN EXISTING MANHOLE, CONTRACTOR TO VERIFY ALL
EXISTING ELEVATIONS.
20. ALL PROPERTY SURVEY PINS, MARKERS, AND/OR STAKES REMOVED DURING CONSTRUCTION
SHALL BE REPLACED BY CONTRACTOR'S PROFESSIONAL SURVEYOR.
21. HORIZONTAL AND VERTICAL SEPARATION BETWEEN NEW SANITARY SEWERS AND EXISTING
WATER MAINS SHALL CONFORM WITH SECTION 28.3 OF DEP'S "DOMESTIC WASTEWATER
FACILITIES MANUAL." IF POSSIBLE, SEWERS CROSSING WATER MAINS SHALL BE
CONSTRUCTED SO THAT THE SEWER JOINTS WILL BE EQUIDISTANT AND AS FAR AS POSSIBLE
FROM THE WATER MAIN JOINTS. WHERE A WATER MAIN CROSSES UNDER A SEWER,
ADEQUATE STRUCTURAL SUPPORT SHALL BE PROVIDED FOR THE SEWER TO PREVENT
DAMAGE TO THE WATER MAIN.
22. ALL SERVICE LATERALS TO BE INSTALLED AT 1% FROM MAIN TO CLEANOUT.
23. BRACING/SHORING OF EXISTING UTILITY POLES IS THE RESPONSIBILITY OF THE CONTRACTOR.
CONTRACTOR IS TO COORDINATE AND PAY FOR BRACING/SHORING OF UTILITY POLES WITH
UTILITY OWNER.
24. GATE VALVES TO BE INSTALLED DIRECTLY TO CROSSES AND TEES WITH FOSTER ADAPTORS.
25. ALL PAVEMENT MARKINGS THAT ARE DISTURBED TO BE REPLACED BY CONTRACTOR.
26. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF RELOCATING ANY
CONFLICTING UTILITIES WHICH ARE A RESULT OF THESE IMPROVEMENTS.
27. ROLLED ASPHALT CURBING DAMAGED OR REMOVED DURING CONSTRUCTION SHALL BE
REPLACED/REPAIRED AT THE END OF THE WORK DAY.
28. SIX (6) INCHES OF SIFTED TOPSOIL SHALL BE PLACED ON ALL DISTURBED LAWN AND GRASS
AREAS PRIOR TO PLACEMENT OF SEED AND MULCH FOR PERMANENT RESTORATION.
DISTURBED AREAS ARE DEFINED AS ANY AREA WHERE THE CONTRACTOR EXCAVATED FOR
MAIN LINES, SERVICE LINES OR ANY OTHER EXCAVATED AREAS AS PART OF THE PROJECT.
DISTURBED AREAS ARE ALSO WHERE CONTRACTOR HAS PLACED OR STOCKPILED DIRT FROM
EXCAVATIONS ON GRASS OR LAWN AREAS REGARDLESS OF THE AMOUNT OF TIME THE
STOCKPILED OR STORED MATERIAL WAS PLACED.
29. TP-XX TEST PIT LOCATIONS DUG BY OWNER.
INVERT OUT - INVERT IN
HORIZONTAL LENGTH (FROM MH INSIDE EDGE TO MH INSIDE EDGE)
S
U/C U/C EXISTING UNDERGROUND COMMUNICATION
FMFM EXISTING FORCE MAIN
ABANDONED FORCE MAINABFM ABFM
SS SS
FLOODWAY
100-YR FLOOD PLAIN
EXISTING SANITARY SEWER MANHOLE
EXISTING COMMUNICATION MANHOLEC
COMPOST FILTER SOCKCFS CFS
NEW PERMANENT EASEMENT
NEW TEMPORARY EASEMENT
NPDES BOUNDARY
C-102 C-103 C-104
LIMIT OF DISTURBANCE
NEW 4" PVC FORCE MAIN NEW 5'Ø MANHOLE
EXISTING ELECTRICAL JUNCTION BOX
EXISTING COMMUNICATION JUNCTION BOX
TEST PIT
REPLACE EXISTING AND/OR NEW 4" PVC FORCE MAIN
(2) NEW 4" BENDS
NEW FORCE MAIN LOCATOR ASSEMBLY
1 NEW GATE VALVE
NEW VALVE
VAULT
0+00 1+00
CONTRACT
CONTRACT
BYPASS PUMP CONNECTION
NEW 4"x4" WYE
S
S
W W
W W
W W
W W
W W W W
W
W
W
W
W
W
W
W W W W W W W W W W W W W W W W W W W W W W W W W W
W W W W W W W W W W W W W W W W W W
FM
FM FM FM FM FM FM FM FM
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS SS SS SS SS
SS
SS
SS
SS
SS
SS
XXXXXXXXXXXXXXXX
SS SS SS SS
SS SS SS SS
SS SS SS SS SS SS
S
U/C U/C U/C U/C
U/ C
U/C U/C U/C
U/C
U/C
U/C U/C U/C U/C U/C U/C U/C U/C
U/C U/C
M
AT
C H
LI
N E
A A
NEW 4" PVC FORCE MAIN
NEW BEND (TYP.)
0+
1+00
NEW FORCE MAIN LOCATOR ASSEMBLY
C-502
BYPASS PUMP CONNECTION
CFS
CFSCFSCFS
CF
S
CF
S
12" CFS
12" CFS
X
X X
X
X
TP-1
FMU/E
FM
FM
FM
FM
FM FM FM FM FM
SS SS SS SS SS SS SS SS SS SS
SS
SS
SS SS SS
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C U/C U/C
U/C U/C U/C U/C U/C U/C
CF
S
CFS
CFSCFSCFSCFSCFSCFSCFS
CFS
CF
S
CF
S
CF
S
CF
S
CF
S
CF
S
CFS
X X
X
X X X X X X
X X
X X
XXX
SS
SS
U/E
U/E
U/E
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-102.dwgPlotted By: Shawn Matthews7 November 2025 - 1:17 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PLAN AND PROFILE
CIVIL
C-102AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
PLAN
SCALE 1" = 30' 0 60'30'
PROFILE
SCALE: H:1" = 30', V: 1" = 10' 0 60'30'
0 20'10'
(TO BE REPLACED)
N
LARGE SCALE PLAN
SCALE 1" = 10' 0 20'10'
(TO BE REPLACED)
EXISTING FORCE MAIN TO BE CAPPED AFTER
NEW PUMP STATION IS IN SERVICE (CONTRACT 2)
(2) NEW 4" VALVES
(1) MJ RESTRAINED PLUG
RECONNECT TO EXISTING FORCE MAIN (CONTRACT 1)
NEW FORCE MAIN LOCATOR ASSEMBLY
BYPASS PUMP CONNECTION
CONTRACT
CONTRACT
4" DI BY CONTRACT 2
2+00 3+00 4+00 5+00 6+00 7+00 8+00 9+00 10+00
REPLACE EXISTING AND/OR NEW 4" PVC FORCE MAIN
NEW FORCE MAIN LOCATOR ASSEMBLY (TYP.)
M
AT
E
B B
M
AT
E
A A
REPLACE EXISTING AND/OR NEW 4" PVC FORCE MAIN
2+00 3+00
4+00 5+00
6+00 7+00
8+00 9+00
NEW FORCE MAIN LOCATOR ASSEMBLY (TYP.)
C-502
CFS
12" CFS
S
W W W W W W W W W W W W W W W W W W W W W W W
W W
W
W W
W
W W
W
W W
W W
W W
W W
W W
W W
W W
W W
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
W W W W W W W W W W W W W W W W W W W W W W
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
S
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-103.dwgPlotted By: Shawn Matthews7 November 2025 - 1:18 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PLAN AND PROFILE
CIVIL
C-103AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
PLAN
SCALE 1" = 30' 0 60'30'
PROFILE
SCALE: H:1" = 30', V: 1" = 10' 0 60'30'
0 20'10'
TP-2
TP-3
TP-4
TP-5
TP-2
TP-3
TP-4
TP-5
10+00 11+00 12+00 13+00 14+00 15+00 16+00
INV IN
INV OUT
STATION
RIM EL. ±
REPLACE EXISTING AND/OR NEW 4" PVC FORCE MAIN NEW 4" BENDS (TYP.)
EX. MANHOLE
(TO BE REPLACED W/ 5' ∅ MH
AND BE COATED)
512.00 (4" FM)
511.07(S) 510.97(N) 15+78.18
521.4
INV IN
NEW FORCE MAIN LOCATOR ASSEMBLY (TYP.)
18" (MIN.)
W W
W W
W W
W
W W
W
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
W
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
S
X X
XXX
XXXXXXXXX
XX
XXXXXXXXXXXXXX
W W W W W W W W W W W
W W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
W
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C
S
U/ C
U/ C
U/C U/C
B B
M
AT
E
REPLACE EXISTING AND/OR NEW 4" PVC FORCE MAIN
10+00 11+00
12+00
13+00
14+00
15+00
15+78
NEW FORCE MAIN LOCATOR ASSEMBLY (TYP.)
C-502
CFS
12" CFS
TP-8 TP-9
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-104.dwgPlotted By: Shawn Matthews7 November 2025 - 1:19 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PLAN AND PROFILE
CIVIL
C-104AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
PLAN
SCALE 1" = 30' 0 60'30'
PROFILE
SCALE: H:1" = 30', V: 1" = 10' 0 60'30'
0 20'10'
TP-6
TP-7
EX. MANHOLE TO BE REPLACED WITH
NEW 5' Ø MANHOLE AND TO BE COATED
EX. MANHOLE
TO BE COATED
NEW 4" BENDS
TP-6
TP-7
FM FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM
XXXXXXXXXXXXXXXX
X X
X X
X X
X X
X X
X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X X
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
SS
SS
SS
SS
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/ C
U/ C
U/ C
U/ C
U/ C
U/ C
U/C
U/C
U/C
U/C
U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C U/C U/C U/C U/C U/C U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-105.dwgPlotted By: Shawn Matthews7 November 2025 - 1:20 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PUMP STATION
SITE DEMOLITION PLAN
C-105AS SHOWN
S. MATTHEWS
J. HAMSHER
B. ANDERSON
N
PLAN
SCALE 1" = 5' 0 10'5'
EXISTING
COMMINUTOR
CHAMBER
(TO BE DEMOLISHED) EXISTING
WET WELL
(TO BE DEMOLISHED)
EXISTING
VALVE PIT
(TO BE DEMOLISHED)
EXISTING
GENERATOR
(TO BE REMOVED)
EXISTING
FENCING
(TO BE REMOVED)
EXISTING
CONTROL CABINET
(TO BE REMOVED)
EXISTING
CONCRETE PAD
(TO BE REMOVED)
EXISTING
FORCEMAIN
(TO BE REMOVED)
EXISTING
MACADAM
(TO BE REMOVED)
E E E
SS SS SS
W W W
U/E U/E U/E
LEGEND
EXISTING CONTOUR MAJOR
EXISTING CONTOUR MINOR
EXISTING RIGHT-OF-WAY
EXISTING OVERHEAD ELECTRIC
EXISTING SANITARY SEWER
EXISTING SEWER FORCEMAIN
EXISTING PROPERTY LINE
EXISTING UILITY POLE
EXISTING STORM PIPE
ITEM TO BE REMOVED
CONCRETE / MASONRY TO BE REMOVED
EXISTING WATER PIPE
EXISTING EDGE OF GRAVEL
EXISTING UNDERGROUND ELECTRIC
EXISTING VEGETATION / TREE LINE
U/C U/C U/C EXISTING UNDERGROUND CABLE
X X X X X EXISTING FENCE
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
SS
SS
SS
SS
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/ C
U/ C
U/ C
U/ C
U/ C
U/ C
U/C
U/C
U/C
U/C
U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C
U/C U/C U/C U/C U/C U/C U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
X X
X X
X X
X
X X X X X X X X X X X X
X X
X X
X X
X
XXXXXXX
XX X X
SS
SS
SS
SS
SS
WET WELL VALVE VAULT
GENERATOR
GENERATOR
PAD
PUMP STATION
CONTROLS
FENCE
NEW 4" PVC
FORCEMAIN
FM
FM
FM
FM
FM
FM
FM FM FM
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-106.dwgPlotted By: Shawn Matthews7 November 2025 - 1:21 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PUMP STATION
SITE PLAN
CI-106AS SHOWN
S. MATTHEWS
J. HAMSHER
B. ANDERSON
N
PLAN
SCALE 1" = 5' 0 10'5'
E E E
SS SS SS
W W W
U/E U/E U/E
LEGEND
EXISTING CONTOUR MAJOR
EXISTING CONTOUR MINOR
EXISTING RIGHT-OF-WAY
EXISTING OVERHEAD ELECTRIC
EXISTING SANITARY SEWER
EXISTING SEWER FORCEMAIN
EXISTING PROPERTY LINE
EXISTING UILITY POLE
EXISTING STORM PIPE
EXISTING WATER PIPE
EXISTING EDGE OF GRAVEL
EXISTING UNDERGROUND ELECTRIC
EXISTING VEGETATION / TREE LINE
U/C U/C U/C EXISTING UNDERGROUND CABLE
X X X X X EXISTING FENCE
PROPOSED FORCEMAIN
X X X X PROPOSED FENCE
PROPOSED STRUCTURE
PROPOSED MACADAM PAVING
S
S
W W
W W
W W
W W
W W
W
W W W W W W W W W W W W W W W W W W W W W W
W W
W W
W W
W W
W W
W W
W W
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
S
XX
X
X X
X X
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
X
X
X
X
SS SS SS SS SS SS SS SS SS SS SS SS
SS SS
SS SS SS
W W W W W W W W W W W W W W W W W W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
U/C U/C U/C U/C
U/C
U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C U/C
U/C U/C U/C U/C U/C U/C U/C
S
S
U/ C
U/C
U/C
CFSCFS
CF
S
BASE PAVING WITH 6.5" OF
BASE. MILL 1.5" AND OVERLAY
SECTION OF ROAD.
REBUILD MEALS DRIVE AND
ENTRANCE TO PETERSBURG
ROAD. 5" BASE PAVING AND
1.5" OF WEARING COURSE.
GRAVEL SHOULDER
(BACKFILL WITH 2A FLUSH)
TRENCH PAVING ONLY,
BASE FLUSH
CI-502
CI-50210
CI-502
Project
Client
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-107.dwgPlotted By: Shawn Matthews7 November 2025 - 1:23 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
PAVING PLAN
C-107AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
PLAN
SCALE 1" = 50' 0 100'50'
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-108.dwgPlotted By: Shawn Matthews7 November 2025 - 1:23 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
DETOUR PLAN
C-108AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
N
PLAN
SCALE 1" = 150' 0 300'150'
W/O DETOURCLOSED
R7-10 TEMPORARY7
M4-9S
R11-2
ROAD
DETOUR
REGULATION
POLICE
W20-2
M4-8A
W30-1
END
DETOUR
PARKING
NO
AHEAD
DETOUR
OR
M4-9R
M4-9L
OR
M4-9SL
M4-9SR
DETOUR
DETOUR
DETOUR
W20-3 W30-1
R11-4
OR
M4-10R
M4-10L2
DETOUR
THRU TRAFFIC
CLOSED
DETOUR
ROAD
AHEAD
CLOSED
LOCATION SERIES LEGEND
TYPE B OR
TYPE III
TYPE B OR
BARRICADE
SANDBAG48" X 30"
30" X 24"
30" X 12"
TYPE III
BARRICADE
TYPE III
BARRICADE
TYPE B OR
24" X 18"
36" X 36"
TYPE III
TYPE B OR
BARRICADE
TYPE III
BARRICADE
TYPE B OR30" X 12"
30" X 24"
30" X 24"
30" X 12"
TYPE B OR
BARRICADE
TYPE III
TYPE III
BARRICADE
48" X 18" 48" X 30"
36" X 36" 20" X 6"
MOUNTINGSIZE
24" X 18"
TYPE III
BARRICADE
SPECIAL
SPECIAL
TRAFFIC CONTROL SIGN LEGEND
NO SCALE
CONSTRUCTION CLOSURE AREA
DETOUR DIRECTIONS:
South on Petersburg Rd. Detour Left (East) on Westminster Dr.
Right (South) on Forge Rd.
Right (West) on W Hunter Rd.
Right (West) On Limestone Rd.
Left (South) back onto Petersburg Rd.
End Detour
North on Petersburg Rd. Detour Right (East) on Limestone Rd.
Left (East) on W. Hunter Rd.
Left (North) on Forge Rd.
Left (West) on Westminster Dr.
Right (North) back onto Petersburg Rd.
End Detour
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: G:\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-501.dwgPlotted By: Mike Wiestling8 November 2025 - 10:07 AM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
SANITARY SEWER DETAILS
CIVIL
C-501AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
1"
1"
SEWER
SANITARY
MANHOLE STEPS
NO SCALE
SECTION
TO BE USED ONLY IN ROW AREAS. NOT TO BE USED IN PAVED AREAS.
NOTES:
1.
MANHOLE
SECTIONAL ELEVATION
REINFORCED PLASTIC
PLAN
MI
N.
1/2" (TYPICAL)
10"
6 3/4"
#3 DEFORMED
STEEL BAR
INSIDE FACE OF MANHOLE
1 3 /4"
1"
6" MAXIMUM
ALLOWABLE
LEVELING RING
ADJUSTMENT
3/4" DIA. STAINLESS STEEL
STUD W/NUT AND WASHER:
4" MIN. (4 BOLTS REQ'D)
WHOLE PRECAST CONCRETE
OR RUBBER LEVELING RINGS
(VARIED THICKNESS)THREADED INSERT
CAST INTO TOP SECTION
DOUBLE APPLICATION OF
PREFORMED FLEXIBLE
PLASTIC JOINT SEALANT
MANHOLE
GASKETRUBBER WEDGE
PIPE
END VIEW
PLAN SECTIONTYPE 1
PLAN
SECTION
END VIEW
FLEXIBLE
CONNECTOR
PIPE
STAINLESS STEEL PIPE CLAMP
(TWO)
TYPE 2
FLEXIBLE CONNECTOR WITH KORBAND AND TWO STAINLESS STEEL CLAMPS
RUBBER GASKET CAST INTO PRECAST PIPE OPENINGS
MANHOLE
(4) 7/8" DIA. HOLES ON
28" DIA. BOLT CIRCLE SECTION
PLAN
MANHOLE FRAME DETAIL
31 1/2" 25 7/8" 21 1/2"
24 1/16" 25 1/8"
3"
7 1 /16
1/2
"3/8"
1/2"
2" LETTERS
(RAISED LETTERS)
(2) CLOSED
PICKHOLES
(2) PICKBARS
1 1/2"
PLAN
PICKHOLE DETAIL
2 1/4" 1 3/8"
7/1 6"
1/4 "1"
23 3/4"
3"
1/4" DIA. NEOPRENE GASKET
3"
DIA.
5/8
1 1/2" SPH. R
SECTION PICKBAR DETAIL
SECTION
PREFORMED FLEXIBLE
PLASTIC JOINT SEALANT
TONGUE
GROOVE6" MIN.
5" MIN.
VA
RI
ES
MI
N.6"
(TYP.)
VA
RI
ES
R=1'-0"
3/4
12" TO 18"
VARIES
CENTERS
SPACED ON
NO. 8 OR NO. 57 COARSE
O.
D.
AGGREGATE, TAMPED
BASE WITH RISER SECTION
PRECAST REINFORCED CONCRETE
(SEE MANHOLE GASKET DETAIL)
JOINTS SEALED WATERTIGHT
SECTION
CAST INTO TOP
THREADED INSERT
VA
RI
ES
STANDARD ASPHALT
WITH ONE COAT OF
WASHER, AND NUT COATED
STAINLESS STEEL STUD,
MATCH PAVEMENT/GRADE
AND SLOPE AS DIRECTED
BOLTED FRAME DETAIL)
(SEE LEVELING RINGS AND
3 1/2" MIN. TO 4" MAX.
MANHOLE STEPS
SEALED WATERTIGHT
FRAME AND LEVELING RINGS
2'-0"
18" MAX. TO TOP STEP
CONCRETE
PLAN
SECTION
EMBEDMENT
CHANNEL
4" MIN. 3/4" DIA.
INSTALLATION
ANTI-FLOTATION
COLLAR ON MANHOLES
(6" MIN.)(TYP.)
ALL STONE GRADATIONS ARE AASHTO
PIPES SHALL PROTRUDE 2" INSIDE
MANHOLE WALL.
CLASSIFICATION.
BOLTING OF MANHOLE FRAME AND
NOTES:
1.
2.
3.
COVER IS REQUIRED FOR ALL MANHOLES.
02605 FOR ANTI-FLOATATION
REFERENCE SPECIFICATION SECTION4.
REQUIREMENTS.
WITH PREFORMED PLASTIC GASKET
MANHOLE FRAMES SHALL BE SET
RESTORATION TO PREVENT
5.
WATER INFILTRATION.
(RUB-R-NEK) PRIOR TO
VA
RI
ES
GASKETS DETAIL)
WITH RUBBER GASKET.
(SEE MANHOLE PIPE
PIPE CONNECTION MADE
VA
RI
ES
5" MIN. (TYP.)
SECTION
6" MIN.
NO. 8 OR NO. 57 COARSE
AGGREGATE, TAMPED
BASE WITH RISER SECTION
PRECAST REINFORCED CONCRETE
JOINTS SEALED WATERTIGHT
(SEE MANHOLE GASKET DETAIL)
CENTERS
12" TO 18"
SPACED ON
VARIES
3 5/8"
INTO TOP SECTION
THREADED INSERT CAST
VA
RI
ES
MATCH PAVEMENT/GRADE
AND SLOPE AS DIRECTED
COATED WITH ONE COAT
OF STANDARD ASPHALT AFTER
STEEL STUD, WASHER, AND NUT
4" MIN. 3/4" DIA. STAINLESS
INSTALLATION
(SEE LEVELING RINGS AND
BOLTED FRAME DETAIL)
3 1/2" MIN. TO 4" MAX. EMBEDMENT
SEALED WATERTIGHT
MANHOLE STEPS
FRAME AND LEVELING RINGS
2'-0"
ANTI-FLOTATION
COLLAR ON MANHOLES
(6" MIN.)(TYP.)
10" 13-3/4"
1-1/2"
3-3/4"
6" MI
N.
(TYP.)
(TYP.)
1/2"/FT.
PLAN
6 MANHOLE PIPE GASKETS
NO SCALE
5 HEAVY DUTY MANHOLE FRAME AND COVER
NO SCALE
PRECAST CONCRETE MANHOLE
WITH PRECAST CONCRETE BASE
NO SCALE
PRECAST CONCRETE MANHOLE
WITH PRECAST CONCRETE BASE
NO SCALE
3 MANHOLE STEPS
NO SCALE
4 MANHOLE GASKET DETAIL
NO SCALE
LEVELING RINGS AND
BOLTED FRAME DETAILS
NO SCALE
GASKETS DETAIL)
WITH RUBBER GASKET.
(SEE MANHOLE PIPE
PIPE CONNECTION MADE
PIPE COUPLING
STAINLESS STEEL
ANCHORS
TEE
90° PVC BEND
FLUSH TO MANHOLE
CHANNEL
EXPANSION
BAND W/ S.S.
STAINLESS STEEL
ANCHORS BANDS
TO BE SPACED
EVERY 16"
SECTION
FLANGED SCH.40
REFERENCE SECTION
02605 - MANHOLE
THREADED
END CAP
7 FORCEMAIN CONNECTION TO MANHOLE
NO SCALE
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-CI-502.dwgPlotted By: Shawn Matthews7 November 2025 - 1:24 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
CIVIL
DETAILS
C-502AS NOTED
S. MATTHEWS
J. HAMSHER
B. ANDERSON
T. PARTHEMORE
6" MI
N.
6"
MIN.
6"
MIN.O.D.
DE
PT
H
AS
RE
QU
IR
ED
REFERENCE APPROPRIATE
TRENCH DETAIL
AASHTO NO. 8 OR NO. 57
AGGREGATE BEDDING
FORCE MAIN
R-3 BEDDING
UNDISTURBED EARTH OR ROCK
4'
MI
NI
MU
M
OF
C
OV
ER
DETECTION TAPE
1'-0" 1'-0"O.D.
" M
IN
AG
GR
EG
AT
E O.
D.
6" MI
N.
SURFACE RESTORATION AND
TRENCH BACKFILL AS PER
APPROPRIATE DETAIL
SECURE PIPE USING NO. 5 STEEL
REINFORCING BARS WITH WIRE,
SPACED AS REQUIRED TO
PREVENT PIPE FLOTATION
TYPE B FLOWABLE FILL
PROVIDE MASONRY SUPPORTS
AS REQUIRED TO PREVENT
PIPE MOVEMENT
FORCEMAIN
NOTE:
1. CONCRETE ENCASEMENT TO BE USED WHERE MINIMUM CLEARANCE CANNONT
BE OBTAINED BETWEEN WATERLINE AND SANITARY SEWERS AND STORM SEWER.
ENCASEMENT WILL BE INSTALLED AS DIRECTED BY THE ENGINEER IN THE FEILD.
12"
MIN.
(TYP.)
1'
MI
N.
BE
DD
IN
G
LIM
IT
O F
PI
PE
TRENCH
WIDTH
6"6" O.D.
AG
GR
EG
AT
E
DE
PT
H
VA
RI
ES
5'
MI
NI
MU
M
1'
MI
N.
MIN.
O.
D.
6" (MIN.)
MIN.
DETECTION TAPE
AASHTO NO. 8 OR NO. 57
AGGREGATE BEDDING
PA NO. 2A COARSE AGG. TRENCH BACKFILL MACHINE
TAMPED IN 8" LAYERS TO 100% MIN. COMPACTION PER
ASTM D-698 (STD.) (SEE NOTE)
NOTES:
1. USE MECHANICAL TAMPERS OR OTHER COMPACTION EQUIPMENTACCEPTABLE TO PENNDOT.
2. CONTRACTOR TO REPAIR AND/OR REPLACE EXISTING UNDERDRAIN DAMAGED AS A RESULT OF
THE SANITARY SEWER REPLACEMENT.
PAVING RESTORATION AS
PER APPROPRIATE DETAIL,
FORCE MAIN
UNDISTURBED
EARTH OR ROCK
TO
DE
TE
CT
ION
TA
PE
DETECTION TAPE
LIM
IT
O F
PI
PE
BE
DD
IN
G O.D.
1'- 0"
MIN.
6" O.D.
DE
PT
H
VA
RI
ES
4'
MI
NI
MU
M
MIN.
6"
3' MIN.
5' MAX.
UNDISTURBED
EARTH OR ROCK
FORCE MAIN
AASHTO NO. 8 COARSE
AGGREGATE BEDDING MATERIAL.6" EARTH
8" ROCK
SUITABLE ONSITE SOILS
TRENCH BACKFILL MACHINE
TAMPED BACK- FILL IN 8"
LAYERS
ENTIRE DISTURBED AREA
EXISTING GRADEEXISTING GRADE
6" SIFTED TOPSOIL
1 CONCRETE ENCASEMENT DETAIL
NO SCALE
2 UNSUITABLE MATERIAL EXCAVATION
NO SCALE
TRENCH DETAIL IN LAWN, GRASS
AND RIGHT OF WAY AREAS
NO SCALE
TRENCH DETAIL IN TOWNSHIP
AND PRIVATE ROADS
NO SCALE
REFER TO APPROPRIATE
TRENCH DETAIL
EXISTING GROUND
AND/OR PAVEMENT
6" COMPACTED SUBBASE
2A COARSE AGGREGATE
TRENCH WIDTH
3" (COMPACTED) 2P OR 3P PAVING
MATERIAL (COLD PATCH) OR
SUPERPAVE ASPHALT MIXTURE DESIGN,
WMA BASE COURSE, PG64S-22, 0.3
MILLION TO < 3 MILLION ESAL'S 19mm, 3" DEPTH
TEMPORARY PAVING DETAIL FOR
AND PRIVATE TOWNSHIP ROADS
NO SCALE
SUPERPAVE ASPHALT MIXTURE DESIGN,
5" OF WMA BASE COURSE 25mm, PG64S-22, 0.3 MILLION TO < 3 MILLION ESAL'S
INITIAL SAWCUT
FOR TRENCHING FINAL SAWCUT FOR 1' CUT BACK
NO. 2A COARSE AGGREGATE BACKFILL
FULL DEPTH SAWCUT,
SEAL WITH PG64-22
SEALANT MATERIAL
NOTES:
1. ROAD RESTORATION SHALL CONFORM TO ALL TOWNSHIP REQUIREMENTS.
1'-0"
MIN. WIDTH VARIES
1'-0"
MIN. SUPERPAVE ASPHALT MIXTURE DESIGN,
1-1/2" OF WMA WEARING COURSE 9.5mm, PG64S-22 0.3 MILLION TO < 3 MILLION ESAL'S, SRL-LFULL WIDTH OVERLAY
MEALS DRIVE (PRIVATE ROAD) FULL
DEPTH PAVEMENT RESTORATION DETAIL
NO SCALE
TRENCH
6" MIN. COMPACTED 2A
COARSE AGGREGATE
TRENCH BACKFILL AS PER
TRENCH DETAIL FOR PAVED
OR GRAVEL AREAS
COMPACT AND ADD
SUBBASE (2A) IF
REQUIRED (TYPICAL)
EXISTING GRAVEL
ROAD/DRIVEWAY
5 GRAVEL ROAD/DRIVEWAY RESTORATION DETAIL
NO SCALE
9 SNAKEPIT® ACCESS POINT DETAIL
NO SCALE
PETERSBURG ROAD FULL DEPTH
PAVEMENT RESTORATION DETAIL
NO SCALE
SUPERPAVE ASPHALT MIXTURE DESIGN,
6.5" OF WMA BASE COURSE 25mm, PG64S-22, 0.3 MILLION TO < 3 MILLION ESAL'S
INITIAL SAWCUT
FOR TRENCHING FINAL SAWCUT FOR 1' CUT BACK
NO. 2A COARSE AGGREGATE BACKFILL
FULL DEPTH SAWCUT,
SEAL WITH PG64-22
SEALANT MATERIAL
NOTES:
1. ROAD RESTORATION SHALL CONFORM TO ALL TOWNSHIP REQUIREMENTS.
1'-0"
MIN. WIDTH VARIES
1'-0"
MIN. SUPERPAVE ASPHALT MIXTURE DESIGN,
2" OF WMA WEARING COURSE 12.5mm, PG64S-22 0.3 MILLION TO < 3 MILLION ESAL'S, SRL-MFULL WIDTH OVERLAY
AT-GRADE SNAKEPIT® ACCESS
POINT TO BE INSTALLED
DIRECTLY OVER MAINLINE
#12 AWG COPPERHEAD®
COPPER-CLAD STEEL-RED,
FACTORY CONNECTED TO
GROUND ROD.
DRIVE-IN MAGNESIUM
GROUND ROD
MAINLINE
WIRE CONTINUES
WITH MAINLINE
#12 AWG COPPERHEAD®
COPPER-CLAD STEEL-GREEN (TYP.)
COIL UP TO 1' OF EXTRA RED AND GREEN
WIRE IN ACCESS POINT. RED WIRE IS
FROM GROUND ROD AND GREEN WIRE IS
TRACER WIRE ON MAINLINE.
EXISTING GROUND
AND/OR PAVEMENT
5" OF 25mm BASE FLUSH
TRENCH WIDTH
10 TRENCH PAVING DETAIL
NO SCALE
LOCATION CABLE
LOCATION CABLE
MEALS DRIVE (PRIVATE ROAD)
TRENCH RESTORATION DETAIL
NO SCALE
2A SHOULDER
TACK COAT
12 PUMP STATION PAVING RESTORATION
NO SCALE
SUPERPAVE ASPHALT MIXTURE DESIGN,
5" OF WMA BASE COURSE 25mm, PG64S-22, 0.3 MILLION TO < 3 MILLION ESAL'S
SPAV, WMA, BASE COURSE,
PG 64S-22, 10.0 TO < 30.0 MILLION
ESALS, 25mm, 5" DEPTH
SUPERPAVE ASPHALT MIXTURE DESIGN,
1-1/2" OF WMA WEARING COURSE 9.5mm, PG64S-22 0.3 MILLION TO < 3 MILLION ESAL'S, SRL-L
6" COMPACTED SUBBASE
2A COARSE AGGREGATE
LOCATION CABLE
LOCATION CABLE
0 1"
Bar is one inch on original size sheet
IssueNo. Checked Approved Date
Author Drafting Check
Designer Design Check
Project Manager
Project Director
Project No. Date ScaleThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.
www.ghd.com
Conditions of Use
Title
ARCH D
Size
Plot Date: Path and Filename: \\ghdnet\ghd\US\Harrisburg\Projects\564\12637903\Digital_Design\ACAD\Sheets\Civil\12637903-GHD-00-DRG-00-ES-001.dwgPlotted By: Shawn Matthews7 November 2025 - 1:25 PM
Sheet No.
SOUTH MIDDLETON TOWNSHIP
MUNCIPAL AUTHORITY
PUMP STATION NO. 4 UPGRADE
M. PICKERING
E. CHEESEMAN 12637903 November 7, 2025
GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS HB MP NOV-7-2025
EROSION AND SEDIMENT
CONTROL AND RESTORATION
PLAN - NOTES
CE-001AS NOTED
S. MATTHEWS
A. CHRISTENSEN
B. ANDERSON
H. MYERS
Soil Description The project involves earthmoving in an area of karst geology. The development of a sinkhole during or after construction activities has the potential to cause pollution. Please see Standard Erosion and Sediment Control Plan Note 37 and the Sinkhole Repair Details included on the plan drawings.
Approximate boundaries of the soil-mapping units are shown on the plan drawings. This information is obtained from the United States Department of Agriculture Natural Resource Conservation Service online Web Soil Survey (http://websoilsurvey.nrcs.usda.gov/app/). Soils found within the project area are classified as follows:
Soil limitation resolutions:
· Depth to saturated zone and flooding will be addressed by use of a pumped water filter bag if necessary. Pumped water filter bags must be placed at least 50 feet from any stream banks in well vegetated, flat areas.
· Contractor is required by law to follow OSHA requirements; this will address any limitations associated with unstable excavation walls.
· Dusty/droughty limitations for landscaping will be addressed by supplemental watering if necessary.
· Slope limitations will be addressed by limiting the amount of the soil that is exposed. All areas disturbed during construction shall be stabilized using temporary seeding. An erosion control blanket will be used on all slopes 3H:1V or greater.
Standard Erosion and Sediment (E&S) Control Plan Notes
1. All earth disturbances, including clearing and grubbing as well as cuts and fills shall be done in accordance with the approved E&S plan. A copy of the approved E&S plan drawings must be available at the project site at all times.
2. At least 7 days prior to starting any earth disturbance activities, including clearing and grubbing, the owner and/or operator shall invite all contractors, the landowner, appropriate municipal officials, the E&S plan preparer, and a representative from the local conservation district to an on-site preconstruction meeting.
3. At least 3 days before starting any earth disturbance activities, all contractors involved in those activities shall notify the Pennsylvania One Call System Incorporated at 1-800-242-1776 or 811 for buried utilities locations.
4. All earth disturbance activities shall proceed in accordance with the sequence provided on the plan drawings.
5. The Contractor is responsible for installation and maintenance of all erosion and sediment best management practices (BMPs) and shall assure that the E&S Plan is properly and completely implemented.
6. Areas to be filled are to be cleared, grubbed, and stripped of topsoil to remove trees, vegetation, roots, and other objectionable material.
7.…