1-PTSA Brush Run WPCF MCC Replacement Bid Documents Drawings.pdf

PDF 1 MB Posted

Attached to
BRUSH RUN WATER POLLUTION CONTROL PLANT MCC REPLACEMENT
Solicitation number
US.263735
Issued by
Washington County, Pennsylvania

About this file

These are bid documents and electrical drawings for the Brush Run Water Pollution Control Plant Motor Control Center (MCC) Replacement project submitted by Peters Township Sanitary Authority in Washington County, Pennsylvania. The project involves the complete replacement of the motor control center and associated electrical work at the facility located at 111 West Valley Brook Road, McMurray, Pennsylvania. The scope includes demolition of the existing MCC, installation of new electrical distribution equipment (service entrance rated switchboard SWDB-1 at 1600A, 480VAC; distribution panelboard DP-1 at 800A, 480VAC; and multiple new motor starters), new conduit and wiring, grounding systems, and related electrical infrastructure as detailed in the accompanying electrical drawings and specifications. A mandatory pre-bid meeting is scheduled for 2:00 PM on December 17, 2026, at the Brush Run Water Pollution Control Plant, with failure to attend resulting in disqualification. Sealed bids are due by 2:00 PM on Thursday, January 21, 2027, via the PennBid online portal, with opening to follow at the Authority office at 111 Bell Drive, McMurray, Pennsylvania.

Each bid must be accompanied by a certified check or bid bond equal to not less than ten percent of the total bid amount payable to Peters Township Sanitary Authority. The contract documents, including drawings, specifications, and additional solicitation details, are available at no cost through the PennBid website (https://pennbid.bonfirehub.com) as of November 23, 2026. The electrical drawings provided include details on conduit routing, equipment specifications, grounding requirements, and installation standards in accordance with the National Electrical Code Article 501 for Class I, Division 1, Group D areas. The Authority reserves the right to reject any and all bids and to accept the bid deemed most favorable to its interests. No set-asides or specific funding sources are identified in the solicitation documents.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PITTSBURGH

CHAMBERSBURG

WASHINGTON

GREENE FAYETTE

WESTMORELAND

BEAVER

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Gen\Sheets\12680111-GHD-00-00-DRG-G-001.dwgJulie Davenport

No. Checked Date

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

J. DAVENPORT

A. KARAFFA

S. PIKE

S. BOCHNOWICZ AS SHOWN

COVER SHEET

GN-00001

BRUSH RUN WATER POLLUTION CONTROL PLANT

MCC REPLACEMENT

PETERS TOWNSHIP SANITARY AUTHORITY

WASHINGTON COUNTY, PENNSYLVANIA

NOVEMBER 16, 2026

ISSUED FOR CLIENT BIDDING

AREA MAP LOCATION MAP

N N

PROJECT LOCATION

COUNTY LOCATION

NO SCALE NO SCALE

0 ISSUED FOR BIDDING RE RE NOV-16-2026

SHEET INDEX

GN-00001 - COVER SHEET

E-00001 ELECTRICAL LEGEND SHEET

ED-00601 ELECTRICAL DEMOLITION ONE-LINE DIAGRAM

ED-01101 CONTROL BUILDING DEMOLITION PLAN

E-00501 ELECTRICAL DETAILS

E-00502 NEW MOTOR STARTER LAYOUR ELEVATION

E-00601 ELECTRICAL ONE-LINE DIAGRAM

E-01101 CONTROL BUILDING NEW POWER PLAN

http://www.ghd.com

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 E-00001.dwgJulie Davenport

No. Checked Date

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

MCP

SA

CR

M

ETM

TR

TDR

S

ADDITIONAL SYMBOLS AND ABBREVIATIONS.

SEE THE LISTINGS IN OTHER SECTIONS OF THIS DOCUMENT FOR

PORTION OF THEM WILL NECESSARILY APPLY TO ANY GIVEN PROJECT.

OF THIS OFFICE AND APPLY TO A VARIETY OF PROJECTS. ONLY A

THE ABBREVIATIONS AND SYMBOLS LISTED HEREIN ARE STANDARDS

OXOO

S

XOOO

F A

O

OOOX

XOO

OOX

H AO

START

STOP

T

MMS

(CIR. NO.)

L6-30R

M

X

NP

MSSOR

LS

FS

PS

CS

M

GROUND

VS

ORM

S

M

MOD MOTOR OPERATED DAMPER

LOUVERLV

C

ALARM HORN/AMBER BEACON

HAZARDOUS GAS DETECTION

INTRUSION SYSTEM

DOOR CONTACT

STOP/LOCKOUT PB STATIONSLO

GENERAL NOTES:

1. LIGHTING CIRCUITS ARE SHOWN DIAGRAMMATICALLY; EXACT LOCATION OF CONDUIT RUNS

SHALL BE DETERMINED BY THE ELECTRICAL SUBCONTRACTOR IN THE FIELD, UNLESS

SPECIFICALLY DIMENSIONED ON THE PLANS. CONDUIT AND WIRE INFORMATION CAN BE

FOUND ON THE PLANS, EQUIPMENT SCHEDULES AND SCHEMATICS.

2. EXACT EQUIPMENT CONDUIT CONNECTIONS ARE TO BE DETERMINED BY THE ELECTRICAL

SUBCONTRACTOR BASED UPON THE ACTUAL FIELD LOCATION OF EQUIPMENT. INSTALL

CONDUIT IN ACCORDANCE WITH SPEC. SEC. 16110.

3. ALL PENETRATIONS THROUGH NON-FIRE RATED WALLS, CORE HOLE AND SEAL AROUND

CONDUIT WITH NON-SHRINK GROUT. THROUGH EXTERIOR WALL SEAL WATER TIGHT WITH

SILICONE MASONRY SEALANT. THRU FIRE RATED WALLS PROVIDE FIRE STOPPING PER

DETAILS ON CONTRACT DRAWINGS.

4. EVERY EFFORT HAS BEEN MADE TO IDENTIFY REMOTE ITEMS TO BE CONNECTED EITHER IN

THE ELEMENTARIES OR IN THE SCHEDULES. HOWEVER, NOT ALL OF THE REMOTE DEVICES

MAY HAVE BEEN SHOWN ON THE ELECTRICAL PLAN DRAWINGS. SEE THE DRAWINGS OF

RESPECTIVE DISCIPLINES TO LOCATE OR CONFIRM THEIR LOCATION.

5. ALL ELECTRICAL WORK IN CLASS I, DIVISION 1, GROUP D AREAS SHALL BE IN STRICT

ACCORDANCE WITH THE NFPA 70 NATIONAL ELECTRICAL CODE ARTICLE 501, APPLICABLE

COMMONWEALTH OF PENNSYLVANIA LAW AND THE CONTRACT SPECIFICATIONS. ALL

MATERIALS PROVIDED IN SUCH AREAS SHALL BE LISTED AS SUITABLE FOR THE

ENVIRONMENT IN WHICH THEY ARE INSTALLED. REFER TO DRAWING G-00002 FOR AREA

CLASSIFICATION REQUIREMENTS.

6. FASTENERS ON THE UNDERSIDE OF PRECAST/PRESTRESSED CONCRETE MEMBERS

(PLANKS OR DOUBLE TEEs) WHICH SERVE FOR DIRECT ATTACHMENT OR FOR HANGERS OF

ELECTRICAL EQUIPMENT, CONDUIT, CHANNEL, ETC., MAY NOT BE DRILLED OR SHOT IN THE

VICINITY OF THE PRESTRESSING TENDONS. THIS MEANS THAT FASTENERS AT CONCRETE

PLANKS CAN ONLY BE PLACED AT THE JOINTS BETWEEN UNITS. CONTRACTOR SHALL

PROVIDE AN INTERMEDIATE SUPPORTS NEEDED TO ACCOMPLISH THIS.

7. CONDUIT RUN ON EXTERIOR OF STRUCTURES SHALL BE EITHER WALL OR HANDRAIL

MOUNTED. ALL SUCH MOUNTING SHALL BE VIA ELECTRICAL CHANNEL

ABBREVIATIONS

A or AMP AMPERE, AMPS

AC ALTERNATING CURRENT

AE ANALYZER SENSOR

AF AMPERE FRAME SIZE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPS INTERRUPTING CURRENT

AIT ANALYZER INDICATING TRANSMITTER

ALT ALTERNATOR

AM AMMETER

ANN ANNUNCIATOR

AS AMMETER SWITCH

AT AMPERE TRIP RATING

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BKR BREAKER

BTS BEARING TEMPERATURE SENSOR

C or COND CONDUIT

CA CABLE

CB CIRCUIT BREAKER

CBDH CIRCUIT BREAKER DISCONNECT HANDLE

CGD COMBUSTIBLE GAS DETECTOR

CGM COMBUSTIBLE GAS MONITOR

CMD COMMAND

CIRC or CKT CIRCUIT

CLF CURRENT LIMITING FUSE

COMP COMPARTMENT

COR CORROSION RESISTANT

CP CONTROL PANEL

CS CONTROL STATION

CPT CONTROL POWER TRANSFORMER

CR CONTROL RELAY

CT CURRENT TRANSFORMER

DC DIRECT CURRENT

DM DAMPER MOTOR

DS DISCONNECT SWITCH

EA EACH

EJ EXPANSION JOINTS

EMH ELECTRICAL MANHOLE

EMT ELECTRICAL METALLIC TUBING

EMTP EMBEDDED MOTOR THERMAL PROTECTOR

EP EQUIPMENT PANEL

ES EMERGENCY SWITCH

ESTOP EMERGENCY STOP

ETM ELAPSED TIME METER

EWC ELECTRIC WATER COOLER

F & I FURNISHED AND INSTALLED

FDBK FEEDBACK

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FE FLOW ELEMENT

FIT FLOW INDICATING TRANSMITTER

FLEX FLEXIBLE

FOS FAST-OFF-SLOW

FS FLOW SWITCH

FSW FUSED SWITCH

FVNR FULL VOLTAGE NON REVERSING

FVR FULL VOLTAGE REVERSING

FVTS FULL VOLTAGE TWO SPEED

GC GENERAL CONTRACTOR

GEN GENERATOR

GENSET EMERGENCY POWER GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GRD or G GROUND

HMI HUMAN MACHINE INTERFACE

HOA HAND-OFF-AUTO SELECTOR SWITCH

HOR HAND-OFF-REMOTE SELECTOR SWITCH

HP HORSE POWER

IB/OB INBOARD/OUTBOARD

IL INDICATING LIGHT

IMH INSTRUMENTATION MANHOLE

IPC INDUSTRIAL PANEL COMPUTER

I/O INPUT/OUTPUT

ISB INTRINSICALLY SAFE BARRIER

ISR INTRINSICALLY SAFE RELAY

JB JUNCTION BOX

JIC JOINT INDUSTRIAL COUNCIL

KCMIL THOUSAND CIRCULAR MILS

KSU KEY SERVICE UNIT

KVA KILOVOLT AMPERES

KW KILOWATT

LA LIGHTNING ARRESTOR

LC LIGHTING CIRCUIT

LE LEVEL TRANSDUCER

LIC LEVEL INDICATING CONTROLLER

LIT LEVEL INDICATING TRANSMITTER

LP LIGHTING PANEL

LO LOCKOUT

LS LIMIT SWITCH

mA MILLIAMPS

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MCS/ MOLDED CASE SWITCH

T-THERMAL ONLY

M-MAGNETIC ONLY

AUTO- AUTOMATIC ONLY

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MIN MINIMUM

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOD MOTOR OPERATED DAMPER

SYMBOLS

MSS MOTOR STARTING SWITCH

MTR MOTOR TIMING RELAY

MWTP MOTOR WINDING THERMAL PROTECTION

Mx MOTOR CONTACTOR AUXILIARY CONTACT

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOC.

NO NORMALLY OPEN

NP NAMEPLATE

NTS NOT TO SCALE

OH/E OVERHEAD ELECTRIC

OH/L OVERHEAD TELEPHONE

OIU OPERATOR INTERFACE UNIT

OL OVERLOAD RELAY

Ø PHASE

P POLE

PB PUSHBUTTON

PBx PULL BOX

PDSL PRESSURE DIFFERENTIAL SWITCH LOW

PDSH PRESSURE DIFFERENTIAL SWITCH HIGH

PE PRESSURE SENSOR

PF PULLING FITTING

PFC POWER FACTOR CORRECTION

PIT PRESSURE INDICATING TRANSMITTER

PLC PROGRAMMABLE LOGIC CONTROLLER

PNL PANEL

POT POTENTIOMETER

PR PAIR

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

R&R REMOVE & REPLACE

RECEP RECEPTACLE

RGS RIGID GALVANIZED STEEL CONDUIT

ROS REMOTE OPERATING STATION

RV-AT REDUCED VOLTAGE AUTO TRANSFORMER

SA SURGE ARRESTOR

SCADA SUPERVISORY CONTROL AND DATA ACQUISITION

SCR SILICON CONTROLLED RECTIFIER

SEC SECOND

SEL or SEL SW SELECTOR SWITCH

SHLD SHIELDED

S/L STOP/LOCKOUT SWITCH

SN SOLID NEUTRAL

SOL SOLENOID

SPD SPEED

SS STAINLESS STEEL

SSRVS SOLID STATE REDUCED VOLTAGE STARTER

SSW SAFETY SWITCH

S/S STOP/START PUSH BUTTON

STR STRANDED

SV SOLENOID VALVE

SW SWITCH

SWD SWITCHING DUTY

SWSV SEALWATER SOLENOID VALVE

TC TERMINAL CABINET OR TIMED CLOSED

TDR TIME DELAY RELAY

TEL TELEPHONE

TERM TERMINAL

TI TEMPERATURE SENSOR

TIT TEMPERATURE INDICATING TRANSMITTER

TR TIMER

TR.SW. TRANSFER SWITCH

TR24 24-HOUR TIMER

TRANS TRANSFORMER

TS TORQUE SWITCH

TSP TWISTED SHIELDED PAIR

TST TWISTED SHIELDED TRIAD

TYP TYPICAL

UG/E UNDERGROUND ELECTRIC

UG/T UNDERGROUND TELEPHONE

UNK. UNKNOWN

UPS UNINTERRUPTIBLE POWER SUPPLY

VA VOLT-AMPERES

VFD VARIABLE FREQUENCY DRIVE

VM VOLTMETER

VS VOLTMETER SWITCH

VSC VARIABLE SPEED CONTROL

W/ WITH

WE WEIGHT SENSOR

WIT WEIGHT INDICATING TRANSMITTER

WP WEATHER PROOF, WATER PROOF

XP EXPLOSION PROOF

2S1W 2 SPEED, 1 WINDING

2SP2W 2 SPEED, 2 WINDING

XFMR TRANSFORMER

SINGLE POLE SWITCH (P) PILOT LIGHT

THREE-WAY SWITCH

FOUR-WAY SWITCH

MOTOR STARTING SWITCH

MANUAL MOTOR STARTER WITH

OVERLOAD PROTECTION

QUAD RECEPTACLE

SINGLE RECEPTACLE

SPECIAL RECEPTACLE WITH

DESIGNATION

THERMOSTAT

CONTINUOUS RATING

MOTOR CIRCUIT PROTECTOR-TRIP

RANGE SETTING BASED ON ACTUAL

MOTOR FULL LOAD AMPS

CONTACTOR TYPE AND NEMA SIZE

AS REQUIRED FOR MOTOR FULL

LOAD AND CHARACTERISTICS

OVERLOAD HEATERS OR RELAY

MOMENTARY OPEN PUSHBUTTON

(NORMALLY OPEN)

MOMENTARY CLOSED PUSHBUTTON

(NORMALLY CLOSED)

MAINTAINED CONTACT PUSHBUTTON

WITH MECHANICAL INTERLOCK

THREE POSITION MAINTAINED CONTACT

SELECTOR SWITCH

FOUR POSITION MAINTAINED

CONTACT SELECTOR SWITCH

NORMALLY OPEN

NORMALLY CLOSED

TIME DELAY AFTER

COIL ENERGIZED

TIME DELAY AFTER

COIL DE-ENERGIZED

NORMALLY OPEN CONTACT

NORMALLY CLOSED

NORMALLY OPEN

NORMALLY CLOSED CONTACT

TEMPERATURE SWITCH

LIMIT SWITCH

FLOAT SWITCH

PRESSURE SWITCH

SOLENOID VALVE COIL

MOTOR OPERATED VALVE

INDICATING LIGHT *=COLOR

R - RED W - WHITE

G - GREEN A - AMBER

PUSH-TO-TEST INDICATING LIGHT

NAME PLATE

RED MUSHROOM HEAD PUSHBUTTON

(MAINTAINED)

MOUNTING STAND

CONTROL RELAY

TIMER

TIME DELAY RELAY

MOTOR STARTER CONTACTOR COIL OTHER

COIL DESIGNATIONS:

SL- SLOW O - OPEN

FS- FAST C - CLOSED

F - FORWARD L - LOW

R - REVERSE H - HIGH

LIMIT SWITCH

FLOW SWITCH

PRESSURE SWITCH

VIBRATION SENSOR

MOTOR OPERATED DAMPER

CONTROL STATION

UTILITY POLE

UTILITY POLE W/STREET LIGHT

ELAPSED TIME METER

FLEXIBLE CONDUIT

WIRES CONNECTED

WIRES NOT CONNECTED

CURRENT LIMITING FUSE

SWITCH WITH CURRENT LIMITING FUSE

MOLDED CASE CIRCUIT BREAKER

DISCONNECT SWITCH

SQUIRREL CAGE INDUCTION MOTOR AND

X= HORSEPOWER (HP)

RESISTANCE LOAD

DRAW OUT FEATURE

TRANSFORMER

GROUNDING NOTES:

1. THE GROUNDING SYSTEM IS SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF CABLE

GROUND RODS AND CONNECTIONS SHALL BE DETERMINED IN THE FIELD.

2. ALL BURIED GROUNDING CABLE CONNECTIONS SHALL BE CADWELD OR THERMOWELD. THE

WELDED CONNECTIONS SHALL BE LEFT EXPOSED FOR INSPECTION BY ENGINEER PRIOR TO

BACKFILLING.

3. WHERE EXPOSED TO MECHANICAL INJURY, THE GROUNDING CONDUCTOR SHALL BE

SUITABLY PROTECTED BY PIPE OR OTHER MECHANICAL PROTECTION. EACH END OF

PROTECTING CONDUIT (IF METALLIC) SHOULD BE GROUNDED TO THE BARE CABLE.

4. ALL EXPOSED CABLE LUGS AND CONNECTORS SHALL BE OF THE COMPRESSION TYPE

UNLESS OTHERWISE NOTED.

5. STEEL MUST BE CLEANED THOROUGHLY AND CABLE MUST BE COMPLETELY DRY BEFORE

MAKING WELD CONNECTIONS.

6. THE GROUNDING SYSTEM SHALL BE CONNECTED TO A METALLIC WATERLINE WITH A

MINIMUM OF 10 FEET LENGTH UNDERGROUND AND TO THE GROUNDING ELECTRODES.

7. REMOVE PAINT FROM UNDER ALL GROUNDING LUGS, INCLUDING SHOP FABRICATED

PANELS.

AIR TERMINAL

EARTH TERMINAL

CABLE TURNING DOWN

TWISTED SHIELDED PAIR

GROUND PLATE

HEAT TRACING

NEW EQUIPMENT/WORK.

NEW WORK/EQUIPMENT IS SHOWN IN THIS TEXT FORMAT

REFERENCE TO DRAWING NOTE

BRANCH CIRCUIT WIRING, WHEN SHOWN, PROVIDE QUANTITIES OF

CONDUCTORS REQUIRED FOR CIRCUITING AND SWITCHING

INDICATED. WIRE SIZE SHALL MATCH ASSOCIATED CIRCUIT HOME.

ON BRANCH CIRCUITRY WHERE ONLY THE CIRCUIT NUMBER IS

SHOWN, CIRCUIT RECEPTACLES WITH THE SAME NUMBER TO

THE CIRCUIT INDICATED WITH A HOMERUN TO EACH

NUMBERED GROUP. CONNECT TO A 20A-1P CIRCUIT BREAKER,

OR AS NOTED FOR SPECIAL PURPOSE RECEPTACLES.

ON BRANCH CIRCUITRY WHERE ONLY THE CIRCUIT NUMBER IS

SHOWN, CIRCUIT LUMINAIRES WITH THE SAME NUMBER TO THE

CIRCUIT INDICATED WITH A HOMERUN TO EACH NUMBERED GROUP.

CONNECT TO A 20A-1P CIRCUIT BREAKER, OR AS NOTED.

114 22

POWER FEEDER CIRCUIT DESIGNATION,

SOME NOT SHOWN.2

J JUNCTION BOX

LIGHTING CONTROL SWITCH. LIGHTING WALL SWITCHES,

1 POLE IF NO NOTATION. 3=3 WAY, 4=4 WAY, LV=LOW VOLTAGE

LOWER CASE LETTER INDICATES CONTROL DESIGNATION.

D DIMMER SWITCH

OCCUPANCY SENSOR, CEILING MOUNTED.

OS OCCUPANCY SENSOR, WALL MOUNTED.

NUMBER INDICATES SUPPLY CIRCUIT.

3 INDICATION OF GANGED DEVICES

EM LIGHTING FIXTURE WITH EMERGENCY POWER UNIT

SITE LIGHTING FIXTURE, POLE MOUNTED; QUANTITY AND

ORIENTATION OF LUMINAIRES AS INDICATED

EMERGENCY LIGHTING FIXTURE, INTEGRAL BATTERY

EXIT LIGHT FIXTURE

EXIT LIGHT FIXTURE, WALL MOUNTED

COMBINATION MAGNETIC MOTOR STARTER WITH INTEGRAL

DISCONNECT.

PUSHBUTTON STATION

LIGHTING FIXTURE GENERAL NOTES:

1. UPPER CASE LETTERS INDICATE FIXTURE TYPE. REFER TO

SPECIFICATIONS.

2. LOWER CASE LETTERS INDICATE SWITCHING DESIGNATION.

OR

LIGHTING FIXTURE - TYPE AS SUBSCRIPTED

DUPLEX RECEPTACLE

TELEPHONE OUTLET, UTILITY COMPANY SYSTEM

WORKSTATION OUTLET. NUMBER INDICATES BRANCH CIRCUIT

NUMBER. REFER TO DETAIL ON E004.

FLOOR BOXFB

TERMINAL STRIP CONNECTION

HAND DRYERHD

DEDICATED PLC NETWORK DATA PORT. NUMBER INDICATES

NUMBER OF DATA PORTS AVAILABLE FROM WALL BOX.

BUILDING SECURITY DOOR CONTACT OR LOCKDC

LOCAL CONTROL STATIONAUX

STOP

HAND - OFF - AUTO (H-O-A)

ABOVE GROUND CIRCUIT RUN

UNDERGROUND CIRCUIT RUN

COPPER GROUND ROD

COPPERWELD 3/4" DIA. X 10' LONG

GROUND WIRE CONDUIT STUB-UP

FROM BELOW GRADE

GROUND WIRE CONNECTOR

MECHANICAL TYPE

GROUND CONNECTION

EXOTHERMIC WELD TYPE

COPPER GROUND ROD, COPPERWELD

3/4" DIA. X 10' LONG (INSPECTION TYPE)

LEFT1

LEFT2

RIGHT1

RIGHT2 AREA DIVIDER

- 11

S

S

S

S

PORTABLE GENERATOR RECEPTACLE

HARMONIC FILTER

VFD

HOMERUN

PHOTOCELL

TO BE DEMOLISHED

X

MWTP MOTOR WINDING TEMPERATURE (MWTP)

SEAL LEAK SENSOR (SEAL)SEAL

JUNCTION BOX

PC

T THERMOSTAT

C-xxx

P-xxx

CONTROL CIRCUIT TAG

POWER CIRCUIT TAG

F-xxx FIBER CIRCUIT TAG

U-xxx UTILITY CIRCUIT TAG

SEAL OFF

CONCRETE ENCASED

GRAVEL ENCASED

FLOOD LIGHTF

OS

ALARM LIGHT/HORN

DATA PORT

DISCONNECT SWITCH

E-STOP

UTILITY POLE

CEILING MOUNTED LIGHT

WALL MOUNTED LIGHT

NORMALLY OPEN SWITCH

POLE MOUNTED LIGHT

G

GROUNDING SYMBOLS

J. DAVENPORT

A. KARAFFA

S. PIKE

S. BOCHNOWICZ

ELECTRICAL LEGEND,

ABBREVIATIONS, AND SYMBOLS

E-00001 AS SHOWN

0 ISSUED FOR BID AK SB NOV -16-2026

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 E-00501.dwgJulie Davenport

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

EXTERIOR

OF BUILDING

INTERIOR OF

BUILDING

WHEN WALL THICKNESS EXCEEDS

15 INCHES, INSTALL SEALS ON BOTH

SIDES OF WALLSTAINLESS STEEL

AND NEOPRENE

MECHANICAL SEAL

SEAL PER SECTION 16110 CORE DRILL AND

MECHANICAL SEAL, NO

SLEEVE REQUIRED

NEW OR EXISTING CONCRETE

MASONRY WALL

WALL THICKNESS

COORDINATE CORE SIZE &

O.D. OF CONDUIT WITH

MECHANICAL SEAL MFR.

5 CONDUIT THROUGH CONCRETE WALL

NO SCALE

PULL FITTING

SILICONE MASONRY

SEALANT CORE DRILL

FILL VOID WITH

NON-SHRINK GROUT

FILL BOTTOM OF BLOCK

EXISTING INTERIOR OR

ACCESSIBLE WALL

WALL THICKNESS

CONDUIT PENETRATION

THROUGH MASONRY WALL

NO SCALE

NEW CONDUIT

SUPPORT 4'-0" OC

NEW CONDUIT &

CONDUIT STRAP

ANCHOR BOLT

EXISTING CONC WALL

COORDINATE CORE SIZE &

O.D. OF CONDUIT WITH

MECHANICAL SEAL MFG

STAINLESS STEEL AND

NEOPRENE MECHANICAL

LINK TYPE SEAL

STAINLESS STEEL AND NEOPRENE

MECHANICAL LINK TYPE SEAL

WHEN FLOOR THICKNESS EXCEEDS 15 INCHES. INSTALL SEALS

AT TOP & BOTTOM SIDES OF FLOOR

SLAB THICKNESS

VERTICAL WALL MOUNT

CONDUIT SUPPORT DETAIL

NO SCALE

1/4"THICK ALUM. PLATE AT LEAST

2" LARGER ON EACH SIDE THEN

THE DEVICE TO BE MOUNTED.

1 5/8" ELECTRICAL CHANNEL

(2 REQUIRED IF MORE THEN

12" IN WIDE)

HEAVY DUTY ALUM. STRAP

CLAMPS WITH S.S. BOLTS (TYP.)

#6 GROUND CONDUCTOR

3/8" S.S.

FASTENERS (TYP.)

TOP AND BOTTOM

HAND RAIL

4'-6" MIN. ABOVE

WALKWAY

NOTE: GRIND SMOOTH ALL

EDGES AND CORNERS OF

FABRICATED PARTS

2 RAILING MOUNTING STAND DETAIL

NO SCALE

1/2"

EXTERIOR WALL

NON-SHRINK GROUT

CONDUIT

CONDUIT PENETRATION

THROUGH CONCRETE FLOOR

NO SCALE

CORE DRILL AND MECHANICAL

SEAL, NO SLEEVE REQUIRED

NEW FLOOR

TOP OF FLOOR

BOTTOM OF FLOOR

ELECTRICAL DETAILS

E-00501 AS SHOWN

FROST FREE EXTERIOR EQUIPMENT PAD DETAIL

NO SCALE

OVERALL LENGTH AND WIDTH PER EQUIPMENT SIZE

CREATE HIGHPOINT IN CENTER OF SLAB AND SLOPE 14" PER FOOT TO EDGES

2" CLR

2" CLR

3" CLR

10" (UNO)

2"

1'- 0"

(M

IN

GRADE GRADE

6" (M

IN

1'-0"

(TYP)

3'-0" MIN

(TYP PAST EDGE)

NOTE:

1. FOR EQUIPMENT WEIGHING LESS THAN 1,000 lbs. PROVIDE 8" MIN SLAB

THICKNESS AT CENTER WITH (1) ONE LAYER OF #5 @ 12" TOP EW.

COMPACTED UNDISTURBED SOIL

2" EXTRUDED POLYSTYRENE

INSULATION (ASTM C578, TYPE VII)

COMPACTED

STRUCTURAL FILL

#5 @ 12" T & B

DUCTBANK NOTES:

1. IF EXISTING OR NEW GROUNDS ARE NOT AVAILABLE AT DUCTBANK ENDS, PROVIDE ONE

3/4"x10' GROUND ROD, OFFSET TO SIDE OF DUCTBANK, FOR TERMINATION OF DUCTBANK

GROUNDING CONDUCTORS.

2. SEE NATIONAL GRID DRAWINGS FOR ADDITIONAL DUCTBANK REQUIREMENTS.

CONCRETE SHALL BE PER SPECIFICATION SECTION

03300. EXTEND FROM EDGES OF PAVED AREA 5'

INTO UNPAVED AREA UNLESS OTHERWISE SHOWN

LONGER

MIN. 3" CONC. (PAVED)

BOTH SIDES OF CONDUIT

30" TO

TOP OF

SHALLOWEST

CONDUIT

3" THICK CONC.

BLOCKS AT 5' O.C.

#6 GRD.; CONNECT TO

BLDG. GRD., MH, PBx

AND HANDHOLE GRDS.

(NOTE 1)

3" MIN.

6" TOP AND BOTTOM

3" MIN

MIN. 6" CONC.

TOP & BOTTOM

OF CONDUITS

CONTINUOUS MARKER TAPE

12" STAIN TOP OF CONC. WITH RED IRON OXIDE

#4@6" LENGTHWISE, #4@18" ACROSS

TOP AND BOTTOM. REBAR REQUIRED

ONLY UNDER PAVEMENT.

6 DUCTBANK DETAIL

NOT TO SCALE

NOTE: GROUNDING CONDUCTOR SIZE SHALL

BE AS PER THE SPECIFICATIONS AND THE NEC.

4"

NON-METALLIC BUSHING

TO GROUND BAR

OR SYSTEM

GROUND CABLE TO RUN IN

SLAB (SIZE AS REQUIRED)

TOP OF FINISHED SLAB

1" PVC CONDUIT BEND

GROUND CABLE TO EQUIPMENT, ETC.

NON-METALLIC

BUSHING

7 DUCTBANK DETAIL

NOT TO SCALE

MOTOR

STARTER

MS-CD1

JB-P-1

JB-CEX

CONTINUED TO

DISTRIBUTION

PANELBOARD DP-1

EXISTING CONDUIT AND

WIRE TO MOTOR LOADS

AND RTUS

MOTOR STARTER RISER DIAGRAM

NO SCALE

(TYPICAL TO ALL NEW MOTOR STARTERS)

NOTE:

1. CONTRACTOR SHALL PROVIDE NEW CONDUIT AND WIRE AS SHOWN ON

THIS DIAGRAM AND E-601 BETWEEN NEW MOTOR STARTERS AND NEW

JUNCTION BOXES SHOWN.

2. TYPICAL TO ALL NEW MOTOR STARTERS BEING INSTALLED

P-108

C-EX

1"C

14 #14 AWG

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 E-00502.dwgJulie Davenport

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

NEW MOTOR STARTER LAYOUT

ELEVATION

E-00502 AS SHOWN

A

E-01101

NEW MOTOR STARTER ELEVATION

SCALE: 1 1/2"=1'-0"

NOTES:

1. CIRCUIT ROUTING SHOWN IS DIAGRAMMATIC IN NATURE. ALL EQUIPMENT SHOWN SHALL BE INSTALLED AS DETAILED IN THE RECOMMENDED SEQUENCE ON CONSTRUCTION. CONTRACTOR SHALL PROVIDE HANGERS AND SUPPORTS TO STACK CONDUITS WHERE REQUIRED FOR NEW MOTOR STARTER INSTALLATION.

2. CONTRACTOR SHALL REFER TO MOTOR STARTER RISER DIAGRAM ON DRAWING E-501 FOR ADDITIONAL INFORMATION ON CONTROL CIRCUITS TO BE INSTALLED FROM NEW MOTOR STARTERS TO NEW CONTROL

JUNCTION BOX, JB-C-EX.

0 1 1/2'1/2' 1'

MS-CD1

MS-SDP1

MS-CD2

MS-SDP2

MS-SDP3

MS-AM2

MS-GSP1

MS-AC1

MS-GSP2

MS-AC2

JB-P-1 JB-C-EX

DISTRIBUTION PANELBOARD DP-1

P-107

P-121

P-122

P-126

P-109

P-111

P-113

P-110

P-112

P-116

P-117

P-118

P-115

P-128

P-102

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 ED-00601.dwgJulie Davenport

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

ELECTRICAL DEMOLITION

ONE-LINE DIAGRAM

ED-00601 AS SHOWN

SHEET GENERAL NOTES

1. CONTRACTOR SHALL PROTECT AND CONDUIT AND WIRE FOR RECONNECTION TO EXISTING

LOADS. EXTEND CONDUIT AND WIRE AS REQUIRED FOR CONNECTION TO NEW DISTRIBUTION

EQUIPMENT.

2. FOR NEW WORK ELECTRICAL ONE-LINE DIAGRAM, SEE DWG. E-601.

3. CONTRACTOR SHALL DISCONNECT AND COIL ALL CONTROL CIRCUITS REQUIRED FOR

RECONNECTION TO NEW MOTOR STARTERS.

SHEET KEYNOTES

1. SPARE STARTERS SHALL BE TURNED OVER TO THE OWNER AFTER MCC DEMOLITION HAS

BEEN COMPLETED.

ELECTRICAL DEMOLITION ONE-LINE DIAGRAM

NO SCALE

1 1

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 E-00601.dwgJulie Davenport

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

ELECTRICAL ONE-LINE DIAGRAM

E-00601 AS SHOWN

SERVICE ENTRANCE RATED SWITCHBOARD, SWDB-1, 1600A, 480VAC, 3Ø, 4W, 3P, 65 KAIC, NEMA 12

1600AF

1600AT

3P

LSIG

UTILITY

WEATHERHEAD

UTILITY POLE WITH

POLE MOUNTED

TRANSFORMERS

600AF

600AT

3P

(3) SETS OF 750 KCMIL,

TRIPLEX OVERHEAD

WIRE

400AF

350AT

3P

300AF

250A 3P

200AF

200AT

3P

DISTRIBUTION PANELBOARD, DP-1, 800A, 480VAC, 3Ø, 4W, 3P, 65 KAIC, NEMA 12

600AF

600AT

3P

125AF

30A 3P

125AF

20A 3P

P-101

(2) 4"C

(3) #600KCMIL

#1 GND

P-102 4"C

(3) #300KCMIL

#3 GND

P-103 4"C

(4) #500KCMIL

#3 GND

P-104 4"C

(4) #300KCMIL

#3 GND

P-105 4"C

(4) #300KCMIL

#300 KCMIL GND

P-106 4"C

(4) #250KCMIL

#6 GND

400AF

400AT

3P

300AF

250A 3P

2:1 2:2 2:3 2:4 2:5 2:6

SHEET GENERAL NOTES

1. CONTRACTOR SHALL EXTEND CONDUIT AND WIRE AS REQUIRED FOR CONNECTION TO NEW

DISTRIBUTION EQUIPMENT. CONDUIT AND CONDUCTOR SIZES ARE SHOWN FOR CLARITY.

SHEET KEYNOTES

1. CONTRACTOR SHALL EXTEND AND CONNECT THE OVERHEAD WIRE INSTALLED TO THE NEW

MAIN CIRCUIT BREAKER LOCATION. REFER TO PLAN DRAWING E-1101 FOR ADDITIONAL

INFORMATION.

2. FOR ELECTRICAL DEMOLITION ONE-LINE DIAGRAM, SEE DWG. ED-601.

3. CONTRACTOR SHALL PROVIDE NEW LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE RATED

FOR 480VAC. CONTRACTOR SHALL PROVIDE SQUARE D LIGHTING CONTACTOR OR

APPROVED EQUAL.

125AF

40A 3P

125AF

20A 3P

125AF

40A 3P

125AF

40A 3P

125AF

30A 3P

125AF

30A 3P

125AF

60A 3P

125AF

20A 3P

125AF

20A 3P

125AF

20A 3P

225AF

225A 3P

125AF

20A 3P

125AF

80A 3P

125AF

110A 3P

125AF

40A 3P

125AF

40A 3P

125AF

40A 3P

125AF

40A 3P

125AF

40A 3P

125AF

40A 3P

MS-CD1

NEMA 12

SIZE 1

MS-SDP1

NEMA 12

SIZE 2

MS-CD2

NEMA 12

SIZE 1

MS-SDP2

NEMA 12

SIZE 2

MS-SDP3

NEMA 12

SIZE 2

MS-AC1

NEMA 12

SIZE 2

MS-GSP1

NEMA 12

SIZE 1

MS-GSP2

NEMA 12

SIZE 1

MS-AM2

NEMA 12

SIZE 1

P-107 1"C

(3) #10 AWG

#10 GND

P-120

(3) #12 AWG

#12 GND

P-121 1"C

(3) #3 AWG

#8 GND

P-122 1"C

(3) #2 AWG

#6 GND

P-123 1"C

(4) #8 AWG

#10 GND

P-124 1"C

(4) #8 AWG

#10 GND

P-125 1"C

(3) #8 AWG

#10 GND

P-126 1"C

(4) #8 AWG

#10 GND

P-127 1"C

(3) #8 AWG

#10 GND

ELECTRICAL ONE-LINE DIAGRAM

NO SCALE

MS-AC2

NEMA 12

SIZE 2

U-100

U-101

(3) 5"C

(3) #750 KCMIL

JB-P-1 JB-P-1 JB-P-1 JB-P-1

P-108 1"C

(3) #12 AWG

#12 GND

P-109 1"C

(3) #8 AWG

#10 GND

P-110 1"C

(3) #12 AWG

#12 GND

P-111 1"C

(3) #8 AWG

#10 GND

P-112 1"C

(3) #8 AWG

#10 GND

P-113 1"C

(3) #10 AWG

#10 GND

P-114 1"C

(4) #10 AWG

#10 GND

P-115 1"C

(3) #4 AWG

#10 GND

P-116 1"C

(3) #12 AWG

#12 GND

P-117 1"C

(3) #12 AWG

#12 GND

P-118 1"C

(3) #12 AWG

#12 GND

P-119

4"C

(4) #4/0 AWG

#4 GND

125AF

20AT

3P

LIGHTING

CONTACTOR

P-128 1"C

(3) #4 AWG

#10 GND

P-129 1"C

(3) #12 AWG

#12 GND

JB-P-1

OE

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 ED-01101.dwgJulie Davenport

No. Checked Date

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

SHEET KEYNOTES

0 8'4'2'

PLAN

NORTH

CONTROL BUILDING DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

1 2

CONTROL BUILDING

DEMOLITION PLAN

ED-01101 AS SHOWN

A

1. EXISTING MCC AND MCC PAD TO BE DEMOLISHED AS A PART OF THIS PROJECT. CONTRACTOR

SHALL PROTECT ALL CONDUIT AND WIRE FOR RECONNECTION TO NEW DISTRIBUTION

EQUIPMENT BEING INSTALLED AS A PART OF THIS PROJECT.

2. REFER TO RECOMMENDED SEQUENCE OF CONSTRUCTION FOR MCC DEMOLITION SEQUENCE.

CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO KEEP THE PLANT OPERATIONAL FOR

THE DURATION OF THIS UPGRADE.

MCC-1 FRONT ELEVATION

NO SCALE

OE

23 November 2026 - 10:32 AM C:\ADSK\ACCDocs\GHD Services Pty Ltd\12680111-PTSA MCC Replacement\Project Files\01 WIP\Elec\Sheets\12680111 E-01101.dwgJulie Davenport

No. Checked Date

Project No. Scale

Title Size Bar is 1" on original size sheet

Sheet No.

Project

Client

Plot Date: Plotted By:

Issue Approved Drafting Check

Designer Design Check

Project Manager

Project Director

Date

Path and Filename:

1"

Author

This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Conditions of Use

GHD

T

Inc.

4068 Mt. Royal Boulevard, Gamma Building, Suite 201 Allison Park, Pennsylvania 15101, USA

412.684.9060

ANSI D

R. EVANS

PETERS TOWNSHIP SANITARY

AUTHORITY

J. KOSTELAC

PTSA MCC REPLACEMENT

12680111 NOVEMBER, 2026

SHEET KEYNOTES

CONTROL BUILDING NEW POWER PLAN

SCALE: 1/4" = 1'-0" 0 8'4'2'

PLAN

NORTH

CONTROL BUILDING POWER PLAN

E-01101 AS SHOWN

LIGHTING

CONTACTOR

AERATION TANK #2 MIXER STARTER (ABOVE)

DIGESTER SLUDGE/DRAIN PUMP #3 STARTER (BELOW)

I-LINE PANELBOARD

DP-1

SWDB-1

DISTRIBUTION

SECTION

MAIN CIRCUIT BREAKER,

MCB AND UTILITY METERING

GALLERY SUMP PUMP #2 STARTER (ABOVE)

AIR COMPRESSOR #2 STARTER (BELOW)

GALLERY SUMP PUMP #1 STARTER (ABOVE)

AIR COMPRESSOR #1 STARTER (BELOW)

CLARIFIER DRIVE #2 (ABOVE)

DIGESTER SLUDGE/DRAIN PUMP #2 STARTER (BELOW)

CLARIFIER DRIVE #1 (ABOVE)

DIGESTER SLUDGE/DRAIN PUMP #1 STARTER (BELOW)

A

B

1 2

DUCTBANK SECTION A

NTS

4" SPAREA:1

W/PULLSTRING

4" SPAREA:2

W/PULLSTRING

P-101B:1 P-101B:2

A

NEMA 4X

JUNCTION BOX

UTILITY

WEATHERHEAD

U-100

U-101

2 3

2 3

2 3

P-107

P-121

P-122

P-129

P-101

P-119

P-120

P-123

P-124

P-103

P-127

P-106

P-104

P-105

1. CONTRACTOR SHALL COORDINATE THE DISCONNECTION AND RECONNECTION OF THE UTILITY

SERVICE TO THE NEW SERVICE ENTRANCE RATED EQUIPMENT. ALL WORK PERFORMED ON

THE ELECTRICAL SERVICE SHALL BE COORDINATED WITH THE UTILITY COMPANY PRIOR TO

ANY WORK BEING PERFORMED.

2. CONTRACTOR SHALL PROVIDE JUNCTION BOXES BELOW THE NEWLY INSTALLED STARTERS.

CONTRACTOR SHALL EXTEND ALL CONDUIT AND WIRE REQUIRED FROM THE JUNCTION BOXES

TO THE NEW WALL MOUNTED STARTERS. REFER TO DRAWING E-601 FOR NEW WORK LAYOUT

AND CONDUIT AND WIRE REQUIREMENTS.

3. CONTRACTOR SHALL PROVIDE JUNCTION BOXES BELOW THE NEWLY INSTALLED STARTERS

FOR RECONNECTION OF EXISTING CONTROL CIRCUITS. CONTRACTOR SHALL REFER TO

MOTOR STARTER DIAGRAM ON E-501 FOR ADDITIONAL INFORMATION.

P-125

P-114

E-00502 P-102

P-113

P-126

CONCRETE EQUIPMENT PAD

http://www.ghd.com

Sheets and Views
12680111-GHD-00-00-DRG-G-001-ANSI D - BOTTOM
12680111 E-00001-Layout1
12680111 E-00501-Layout1
12680111 E-00502-Layout1
12680111 ED-00601-Layout1
12680111 E-00601-Layout1
12680111 ED-01101-Layout1
12680111 E-01101-Layout1

File details come from the government source that posted it. Updated .