1.1.4 SOW Fire NETC.docx
DOCX document 23 KB Posted
- Solicitation number
- 02848
About this file
This Statement of Work (SOW) details a fire suppression system tie-in project for Frederick MERS at the National Emergency Training Center (NETC) in Emmitsburg, MD. The project requires the vendor to provide and install a Monaco BT-X system with electrical materials, including antenna installation, wiring to two Fire Alarm Control Panels (FACPs), and programming to enable alarm reporting to campus security dispatch. The system utilizes a portable, waterless, and chemical-free fire suppression approach that minimizes residue and potential water damage.
The project has a 30 business day performance period, with all work to be completed at the NETC facility in buildings I2 and I3, located at 16825 S Seton Ave, Emmitsburg, MD 21727. Work hours are restricted to 0730-1500 ET. The solicitation is issued by the Federal Emergency Management Agency (FEMA) National Community Section, with solicitation number 02848, and interested vendors are encouraged to contact Dustin Johnson to arrange potential site visits prior to proposal submission.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2.4.1 Amendment 1 - RFP_Fire Suppression Tie-In.doc | DOC document | |
| 2.2.1 RFP_Fire Suppression Tie-In.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work NETC Fire Suppression System Tie In Background:
Frederick MERS has a CEASE FIRE portable, waterless, and chemical formless system. Because of our mission and the computer and radio systems we need to have a fire suppression system that uses gas not water or form. This system will leave little to residue to clean, no water damage, and since this system doesn’t have chemicals there is little to no health effect. Frederick MERS needs to tie this system into the NETC (National Emergency Training Center) fire control system.
The vendor will be responsible for the following work.
· Provide Monaco BT-X and electrical material.
· Installation and testing of antenna, wiring of BT-XF to power and two FACPs, so alarms can be reported back to D-21 at the campus security dispatch.
· Once installed, the programming of Monaco BT-X.
· Finally, the testing of the tied in fire suppression system.
Period of Performance:
The period of performance will be 30 business days from the date of award.
Place of Performance:
All work will take place at the Frederick MERS facility on the NETC Campus in building I2, and I3. The address is 16825 S Seton Ave, Emmitsburg, MD 21727 between the hours of 0730 and 1500 ET.