1-2026-10-26 STP Roof Replacement Plans.pdf

PDF 11 MB Posted

Attached to
Piney Fork Sewage Treatment Plant Roof Replacement
Solicitation number
US.261372
Issued by
Allegheny County, Pennsylvania

About this file

This document is a set of architectural and engineering plans prepared by Gateway Engineers, Inc. for the Municipality of Bethel Park, Pennsylvania, for the Piney Fork Sewage Treatment Plant Roof Replacement project. The project involves the removal and replacement of existing roof systems at two buildings (Building A: approximately 1,900 square feet; Building B: approximately 1,400 square feet) with new TPO (thermoplastic polyolefin) membrane roofing systems. Building A currently has an existing ballasted roof system to be removed down to deck, while Building B has an existing membrane roof to be similarly removed. Both buildings will receive replacement roofs consisting of new TPO roofing systems per the provided drawings and specifications. The project is designed in accordance with the 2021 International Building Code (IBC), 2021 International Existing Building Code (IEBC), and applicable Pennsylvania prevailing wage requirements. Sealed proposals are due by 2:00 P.M. on Wednesday, November 18, 2026, via PennBid, with anticipated work commencement in Fall 2026. Proposals must remain firm for sixty days and be accompanied by certified checks or bid bonds, performance and labor/material payment bonds, and certificates of insurance and workers' compensation.

The plans establish specific design loading requirements including roof live loads of 20 PSF on flat roofs, base ground snow loads of 30 PSF with a flat roof snow load of 21 PSF, and minimum R-30 continuous insulation above the roof deck per the 2021 International Energy Conservation Code. The construction is classified as Type IIB with a minimum roof covering classification of Class C. All materials and workmanship must conform to the drawings, specifications, and applicable building codes, with the contractor responsible for verifying all dimensions prior to construction and notifying the engineer of any discrepancies. The plans include detailed specifications for TPO membrane installation, flashing details, roof penetration treatments, walkpad installation, and parapet construction, with references to Johns Manville manufacturer specifications and installation instructions. An alternate scope option for pipe rail systems fabricated from 1.5-inch diameter passivated stainless steel with 48-inch on-center post spacing is included for contractor consideration.

View the file

Other files

File Type Posted
2-2026-10-26 STP Roof Replacement Specs.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C O

M

P

IT

TS

BU

RG

H

B

U

TL

ER

, P

1-

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. CS

KMN

KMN

AAS

10/26/2026

AS NOTED

C-90064

COVER SHEET

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

PINEY FORK SEWAGE TREATMENT PLANT

ROOF REPLACEMENT

PREPARED FOR:

3100 PINEY FORK ROAD

MUNICIPALITY OF BETHEL PARK

5100 WEST LIBRARY AVENUE

BETHEL PARK, PA 15102

SOUTH PARK TOWNSHIP, PA 15129

SITE LOCATION MAP

NOT TO SCALE

SHEET INDEX

NO. TITLE

CS COVER SHEET

S000 GENERAL NOTES, CODE SUMMARY

S100 BUILDING A ROOF PLAN

S101 BUILDING B ROOF PLAN

S200 BUILDING A AND B DETAILS

S201 TYPICAL DETAILS

S202 TYPICAL DETAILS

S203 TYPICAL DETAILS

BUILDING B

BUILDING A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S000

KMN

KMN

AAS

10/26/2026

C-90064

GENERAL NOTES,

CODE SUMMARY

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

AB - ANCHOR BOLT

ADDL - ADDITIONAL

AI - AUXILIARY IRON

ALT - ALTERNATE

ALU - ALUMINUM

AR - ANCHOR ROD

ARCH - ARCHITECTURAL

BLDG - BUILDING

BLK (G) - BLOCK(ING)

BM(S) - BEAM(S)

BTM/ xxx - BOTTOM OF xxx

BTM - BOTTOM

BP - BASE PLATE

BRG - BEARING

BS - BOTH SIDES

BTW - BETWEEN

CHAN - CHANNEL

CIP - CAST IN PLACE

CJT - CONTRACTION/

CONSTRUCTION JOINT

CL - CENTERLINE

CLR - CLEAR(ANCE)

CMU - CONCRETE MASONRY UNIT

COL - COLUMN

CONC - CONCRETE

CONN - CONNECTION

CONST - CONSTRUCTION

CONT - CONTINUOUS

CONTR - CONTRACTOR

COORD - COORDINATE

CP - COMPLETE PENETRATION

CTR - CENTER(ED)

D - DEPTH or DEEP

DBL - DOUBLE

DEG - DEGREE

DEM - DEMOLITION

DET - DETAIL

DIA - DIAMETER

DIAG - DIAGONAL

DIM - DIMENSION

DIST - DISTANCE

DN - DOWN

DWG - DRAWING

EA - EACH

EF - EACH FACE

EJT - EXPANSION JOINT

EL - ELEVATION

ELEC - ELECTRICAL

ELEV - ELEVATOR

EMBED - EMBEDMENT

ENGR - ENGINEER

EOSL - EDGE OF SLAB

EQ - EQUAL

EQUIP - EQUIPMENT

EW - EACH WAY

EXIST - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FDN - FOUNDATION

FIN - FINISH(ED)

FLG - FLANGE

FLR - FLOOR

FO xxx - FACE OF xxx

FOC - FACE OF CONCRETE

FOF - FACE OF FINISH

FOS - FACE OF STEEL

FS - FAR SIDE

FT - FOOT or FEET

FTG - FOOTING

GA - GAGE

GALV - GALVANIZED

GEN - GENERAL

GL - GLUE LAMINATED BEAM

GR - GRADE

GWB - GYPSUM WALLBOARD

H - HIGH

HAS - HEADED ANCHOR STUD

HDR - HEADER

HGR - HANGER

HORIZ - HORIZONTAL

HSS - HOLLOW STRUCTURAL

SECTIONS

HT - HEIGHT

HVAC - HEATING, VENTILATING/

AIR CONDITIONING

ID - INSIDE DIAMETER

IF - INSIDE FACE

IN - INCHES

INFO - INFORMATION

INSUL - INSULATE or INSULATION

JST - JOIST

JT - JOINT

L - LENGTH

LED - LEDGER

LLH - LONG LEG HORIZONTAL

LLV - LONG LEG VERTICAL

LOC - LOCATION

LT - LIGHT

LSH - LONG SLOTTED HOLE/

LONG SIDE HORIZONTAL

MAS - MASONRY

MAX - MAXIMUM

MECH - MECHANICAL

MEZZ - MEZZANINE

MFR - MANUFACTURE(R/D)

MIN - MINIMUM

MISC - MISCELLANEOUS

MSE - MECHANICALLY STABALIZED

EARTH

NA - NOT APPLICABLE

NIC - NOT IN CONTRACT

NIP - NOT IN PERMIT

A. - NUMBER

NS - NEAR SIDE

NTS - NOT TO SCALE

OC - ON CENTER

OD - OUTSIDE DIAMETER

OF - OUTSIDE FACE

OH - OPPOSITE HAND

OPNG - OPENING

OPP - OPPOSITE

OVS - OVERSIZED

PAF - POWDER ACTUATED

FASTENER

PC - PRECAST

PIL - PILASTER

PCAP - PILE CAP

PL - PLATE

PLCS - PLACES

PLWD - PLYWOOD

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PT - POINT

RAD or R - RADIUS

REF - REFERENCE

REINF - REINFORCING

REQD - REQUIRED

RO - ROUGH OPENING

SCHED - SCHEDULE

SECT - SECTION

SHT - SHEET

SHTG - SHEATHING

SIM - SIMILAR

SOG - SLAB ON GRADE

SL - SLOPE

SPEC - SPECIFICATION

SPCS - SPACES

SQ - SQUARE

SSH - SHORT SLOTTED HOLE

STD - STANDARD

STIF - STIFFENER

STL - STEEL

STRUCT - STRUCTURAL

SYM - SYMMETRICAL

TBC - THREADED BAR COUPLER

TBR - TO BE REMOVED

THRD - THREAD(ED)

THK - THICK(NESS)

TO xxx - TOP OF xxx

TOC - TOP OF CONCRETE

TOF - TOP OF FOOTING

TOGB - TOP OF GRADE BEAM

TOS - TOP OF STEEL

TOSL - TOP OF SLAB

TYP - TYPICAL

T/C - TENSION/COMPRESSION

UNO - UNLESS NOTED OTHERWISE

VERT - VERTICAL

W - WIDTH

WT - WEIGHT

WWF - WELDED WIRE FABRIC

WP - WORK POINT

W/ - WITH

W/O - WITHOUT

ABBREVIATIONS

1. ALL CONSTRUCTION MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF THE

DRAWINGS, SPECIFICATIONS, AND THE CODES, RULES AND REGULATIONS OF THE INTERNATIONAL BUILDING

CODE, 2021 EDITION, AND ALL OTHER APPLICABLE BUILDING CODES.

2. SPECIFICATIONS, CODES, AND STANDARDS NOTED IN THE CONTRACT DOCUMENTS SHALL BE OF THE LATEST APPROVED ISSUE, INCLUDING SUPPLEMENTS, UNLESS OTHERWISE NOTED. MATERIAL SPECIFICATIONS ARE

ASTM LATEST EDITION.

3. THESE DRAWINGS HAVE BEEN PRODUCED ON THE GATEWAY ENGINEERS, INC. CADD SYSTEM. ANY OTHER MARKS AFFIXED TO THE DRAWINGS, OTHER THAN PROFESSIONAL STAMPS AND SIGNATURES, HAVE BEEN MADE WITHOUT THE THE AUTHORIZATION OF GATEWAY ENGINEERS AND ARE THEREFORE INVALID.

4. IF ANY ERRORS OR OMISSIONS APPEAR IN THESE DRAWINGS, SPECIFICATIONS, OR OTHER DOCUMENTS; THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OR ARCHITECT IN WRITING OF SUCH OMISSION OR

ERROR BEFORE PROCEEDING WITH THE WORK.

5. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE OWNER AND ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES. THE STRUCTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL STRUCTURAL FEATURES, U.N.O. THE ARCHITECTURAL DRAWINGS SHALL GOVERN THE WORK RELATED TO DIMENSIONS. SCALING OF DRAWINGS TO OBTAIN DIMENSIONS SHALL NOT BE DONE AT ANY TIME. IF A REQUIRED DIMENSION IS NOT PROVIDED, THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION TO THE ENGINEER FOR CLARIFICATION. U.N.O. CONTRACTOR SHALL PROVIDE EQUAL SPACING OF STRUCTURAL COMPONENTS BETWEEN OVERALL DIMENSIONS PROVIDED ON THE

DRAWINGS.

6. NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NOTES AND DETAILS ON DRAWINGS AND THESE GENERAL NOTES AND TYPICAL DETAILS ARE IN CONFLICT WITH THE PROJECT SPECIFICATIONS, CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD. CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED AS SHOWN FOR SIMILAR WORK, SUBJECT TO REVIEW BY

THE ARCHITECT AND STRUCTURAL ENGINEER.

7. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE; THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE

STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE ITEMS.

8. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE EXISTING AND NEW STRUCTURE AND ALL STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH

THE STRUCTURAL DOCUMENTS.

9. MANUFACTURED MATERIALS SHALL BE APPROVED BY THE CHECKING AGENCY PRIOR TO THEIR USE. ALL

REQUIREMENTS OF THOSE APPROVALS SHALL BE FOLLOWED.

10. ALL STRUCTURAL SYSTEMS THAT ARE TO BE COMPOSED OF MANUFACTURED COMPONENTS TO BE FIELD ERECTED SHALL BE APPROVED BY THE CHECKING AGENCY PRIOR TO THEIR USE AND SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION IN

ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER.

11. STRUCTURAL WORK SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS AND THE GENERAL NOTES. THE OWNER SHALL ENGAGE AN EXPERIENCED AND QUALIFIED TESTING AGENCY, EXPERIENCED IN THE TESTING TO BE PERFORMED, TO REVIEW AND TEST ALL NECESSARY

ELEMENTS.

12. THE CONTRACTOR SHALL DESIGN AND SUBMIT SHOP DRAWINGS ALONG WITH CALCULATIONS, SIGNED AND

SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF PENNSYLVANIA, FOR ALL

PRE-FABRICATED STAIRS, PLATFORMS, HANDRAILS, GUARDS AND/OR LADDERS. DESIGN OF THESE ELEMENTS

SHALL MEET ALL RELEVANT REQUIREMENTS OF THE DESIGN BUILDING CODE.

- CONTRACTOR SHALL SUBMIT ELECTRONIC COPIES (OF SHOP DRAWINGS, IN PDF FORM, FOR REVIEW OF GATEWAY ENGINEERS, INC. SHOP DRAWINGS SHOULD PROVIDE A COMPLETE COMPLETE INFORMATION FOR THE PRODUCTS AND/OR COMPONENTS BEING SUBMITTED. INCLUDING BUT NOT LIMITED TO: MEMBER SIZES AND LOCATIONS, GRADES OF MATERIALS, MATERIAL FINISH/COATING, CONNECTIONS, AND ANY SPECIAL

REQUIREMENTS FOR INSTALLATION/ERECTION.

13. THE CONTRACTOR SHALL NOT DIRECTLY INCORPORATE THE STRUCTURAL DRAWINGS OR ANY PORTIONS THEREOF INTO THE SHOP DRAWINGS WITHOUT WRITTEN PERMISSION OF GATEWAY ENGINEERS, INC.

14. THE REVIEW OF SHOP DRAWINGS AND OTHER SUBMITTALS FOR THIS PROJECT IS FOR GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS. ANY COMMENTS EXPRESSED AS PART OF THE REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THEIR CONTRACTUAL OBLIGATION TO PROVIDE THE OWNER WITH THE PROJECT OUTLINED IN THE CONTRACT DOCUMENTS. ANY SUBMITTALS REVISED AND RESUBMITTED FOR REVIEW OR RECORD PURPOSES SHALL HAVE THE SUBSEQUENT REVISIONS

CLOUDED ON THE RESUBMITTED SHEETS.

15. ANY EXISTING ROOF PIPE PENETRATIONS, EQUIPMENT, FANS, DUCTS, ETC. EXTENDING ABOVE THE ROOF SHALL BE RAISED TO REMAIN ABOVE ROOF LEVEL AS REQUIRED BY ROOFING MANUFACTURE PER PLAN. THIS

INCLUDES NEW CURBS, ADJUSTMENTS TO PIPING DUCTING OR ELECTRIC, NEW FLASHINGS AND

TERMINATIONS, ETC. AS REQUIRED.

GENERAL NOTES DESIGN LOADING

1. ALL STRUCTURAL ELEMENTS WERE DESIGNED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING

CODE (2021 IBC).

2. FLOOR/ROOF DEAD LOADS:

- HAVE BEEN CALCULATED VIA RELEVANT ENGINEERING SELF-WEIGHT INFORMATION

3. ROOF LIVE LOADS:

- FLAT ROOF 20 PSF

4. SNOW LOADS:

- BASE GROUND SNOW LOAD 30 PSF

- IMPORTANCE FACTOR (SNOW LOAD) 1.0

- EXPOSURE FACTOR 1.0

- THERMAL FACTOR 1.0

- FLAT ROOF SNOW LOAD 21 PSF

6. WIND LOADS: [WIND EXPOSURE AREA HAS NOT SIGNIFICANTLY CHANGED AND IS NOT REQUIRED TO BE

REVIEWED PER INTERNATIONAL EXISTING BUILDING CODE - SECTION 3404.4]

7. SEISMIC LOADS: [SEISMIC MASS HAS NOT SIGNIFICANTLY CHANGED AND IS NOT REQUIRED TO BE REVIEWED

PER INTERNATIONAL EXISTING BUILDING CODE - SECTION 3404.4]

PROJECT & CODE SUMMARY

PROJECT DESCRIPTION: THE PROJECT INCLUDES TWO ROOF REPLACEMENTS. BUILDING A CONSISTS OF AN EXISTING BALLASTED ROOF SYSTEM, WHICH SHALL BE REMOVED DOWN TO DECK. BUILDING B CONSISTS OF AN EXISTING MEMBRANE ROOF, WHICH SHALL BE REMOVED DOWN TO DECK. BOTH BUILDINGS SHALL HAVE REPLACEMENT ROOFS CONSISTING OF NEW TPO ROOFING SYSTEMS PER DRAWINGS AND SPECIFICATIONS.

BUILDING INFORMATION:

CONSTRUCTION TYPE: IIB

BUILDING AREA: EXISTING, NO CHANGE

BUILDING A: APPROXIMATELY 1900SF

BUILDING B: APPROXIMATELY 1400SF

BUILDING HEIGHT: EXISTING, NO CHANGE

BUILDING A: APPROXIMATELY 16FT, NO CHANGE

BUILDING B: APPROXIMATELY 22FT, NO CHANGE

APPLICABLE CODES:

2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

2021 INTERNATIONAL BUILDING CODE (IBC) FOR NEW ELEMENTS

2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2021 INTERNATIONAL PLUMBING CODE (IPC)

2021 INTERNATIONAL EXISTING BUILDING CODE - LEVEL 1 ALTERATIONS

705.1 MATERIALS AND METHODS OF APPLICATION USED FOR RECOVERING OR REPLACING AN EXISTING ROOF

COVERING SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 15 OF THE IBC.

EXCEPTIONS: 1. ROOF REPLACEMENT OR ROOF RECOVER OF EXISTING LOW-SLOPE ROOF COVERINGS SHALL NOT BE REQUIRED TO MEET THE MINIMUM DESIGN SLOPE REQUIREMENT OF 1/4 UNIT VERTICAL IN 12 UNITS HORIZONTAL

(2% SLOPE) IN SECTION 1507 OF THE IBC FOR ROOFS THAT PROVIDE POSITIVE DRAINAGE.

2. RECOVERING OR REPLACING AN EXISTING ROOF COVERING SHALL NOT BE REQUIRED TO MEET THE REQUIREMENT FOR SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS IN SECTION 1502 OF THE IBC FOR ROOFS THAT PROVIDE POSITIVE DRAINAGE. EXISTING SECONDARY DRAINAGE OR SCUPPERS SHALL NOT BE

REMOVED UNLESS THEY ARE REPLACED IN ACCORDANCE WITH SECTION 1502 OF THE IBC.

705.2 ROOF REPLACEMENT SHALL INCLUDE THE REMOVAL OF ALL EXISTING LAYERS OF ROOF COVERINGS DOWN

TO THE ROOF DECK.

EXCEPTION: WHERE THE EXISTING ASSEMBLY INCLUDES AN ADHERED ICE BARRIER, THE EXISTING ICE BARRIER SHALL BE PERMITTED TO REMAIN IN PLACE AND COVERED WITH AN ADDITIONAL LAYER OF ICE BARRIER MEMBRANE

IN ACCORDANCE WITH SECTION 1507 OF THE IBC.

705.5 FLASHINGS SHALL BE RECONSTRUCTED IN ACCORDANCE WITH APPROVED MANUFACTURER'S INSTALLATION INSTRUCTIONS. METAL FLASHING TO WHICH BITUMINOUS MATERIALS ARE TO BE ADHERED SHALL BE PRIMED PRIOR

TO INSTALLATION.

706.2 ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT

ANY EXISTING GRAVITY LOAD-CARRYING STRUCTURAL ELEMENT FOR WHICH AN ALTERATION CAUSES AN INCREASE IN DESIGN DEAD, LIVE, OR SNOW LOAD, INCLUDING SNOW DRIFT EFFECTS, OR MORE THAN 5% SHALL BE REPLACED OR ALTERED AS NEEDED TO CARRY THE GRAVITY LOADS REQUIRED BY THE IBC FOR NEW STRUCTURES.

PROVISION: BUILDING A DEAD LOAD IS ANTICIPATED TO BE REDUCED WITH THE REMOVAL OF THE BALLAST SYSTEM. BUILDING A AND BUILDING B LOADS ARE NOT ANTICIPATED TO INCREASE MORE THAN 5%. THE PLANNED ROOFTOP EQUIPMENT REPLACEMENT IS TO BE UNDER A SEPARATE COVER. HOWEVER, THE EQUIPMENT IS

ANTICIPATED TO BE REPLACED IN-KIND (CAPACITY, WEIGHT, SIZE, ETC.)

708.1 LEVEL 1 ALTERATIONS TO EXISTING BUILDINGS OR STRUCTURES DO NOT REQUIRE THE ENTIRE BUILDING OR STRUCTURE TO COMPLY WITH THE ENERGY REQUIREMENTS OF THE IECC. ALTERATIONS SHALL CONFORM TO THE

ENERGY REQUIREMENTS OF THE IECC AS THEY RELATE TO NEW CONSTRUCTION ONLY.

2021 INTERNATIONAL BUILDING CODE

1502.1 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL COMPLY WITH THIS SECTION, SECTION 1611

OF THIS CODE, AND CHAPTER 11 OF THE IPC.

1503.1 ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED IN ACCORDANCE WITH THIS CODE, AND INSTALLED IN ACCORDANCE WITH THIS CODE AND THE MANUFACTURER'S

APPROVED INSTRUCTIONS.

1503.2 FLASHING SHALL BE INSTALLED IN A MANNER SO AS TO PREVENT WATER FROM ENTERING THE WALL AND ROOF THROUGH JOINTS IN COPINGS, THROUGH MOISTURE-PERMEABLE MATERIALS AND AT INTERSECTIONS WITH

PARAPET WALLS AND OTHER PENETRATIONS THROUGH THE ROOF PLANE.

1503.2.1 FLASHING SHALL BE INSTALLED AT WALL AND ROOF INTERSECTIONS, AT GUTTERS, WHEREVER THERE IS A CHANGE IN ROOF SLOPE OF DIRECTION AND AROUND ROOF OPENINGS. WHERE FLASHING IS OF METAL, THE METAL SHALL BE CORROSION RESISTANT WITH A THICKNESS OF NOT LESS THAN 0.019 INCH (0.483 MM) (NO.26 GALVANIZED

SHEET)

1503.3 PARAPET WALLS SHALL BE COPED OR COVERED IN ACCORDANCE WITH SECTIONS 1503.1 AND 1503.2. THE

TOP SURFACE OF THE PARAPET WALL SHALL PROVIDE POSITIVE DRAINAGE.

1503.5 A CRICKET OR SADDLE SHALL BE INSTALLED ON THE RIDGE OF ANY CHIMNEY OR PENETRATION GREATER THAN 30 INCHES WIDE AS MEASURED PERPENDICULAR TO THE SLOPE. CRICKET OR SADDLE COVERINGS SHALL BE

SHEET METAL OR THE SAME MATERIAL AS THE ROOF COVERING.

1504.4 ROOF COVERINGS INSTALLED ON ROOFS IN ACCORDANCE WITH SECTION 1507 THAT ARE MECHANICALLY ATTACHED OR ADHERED TO THE ROOF DECK SHALL BE DESIGNED TO RESIST THE DESIGN WIND LOAD PRESSURES FOR COMPONENTS AND CLADDING IN ACCORDANCE WITH SECTION 1609.5.2. THE WIND LOAD ON THE ROOF

COVERING SHALL NOT BE PERMITTED TO BE DETERMINED USING ALLOWABLE STRESS DESIGN.

1504.4.1 BUILT-UP, MODIFIED BITUMEN, FULLY ADHERED OR MECHANICALLY ATTACHED SINGLE-PLY ROOF SYSTEMS AND OTHER TYPES OF MEMBRANE ROOF COVERINGS SHALL BE TESTED IN ACCORDANCE WITH FM4474, UL580, OR

UL1897.

1504.6 METAL EDGE SYSTEMS, EXCEPT GUTTERS AND COUNTERFLASHING, INSTALLED ON BUILT-UP, MODIFIED BITUMEN AND SINGLE-PLY ROOFS, SHALL BE DESIGNED, CONSTRUCTED AND INSTALLED TO RESIST WIND LOADS IN ACCORDANCE WITH SECTION 1609 AND SHALL BE TESTED IN ACCORDANCE WITH METHODS G-1 AND G-2 OF

SPRIGT-1.

1504.7 ROOF COVERINGS INSTALLED ON LOW-SLOPE ROOFS IN ACCORDANCE WITH SECTION 1507 SHALL DEMONSTRATE PHYSICAL INTEGRITY OVER THE WORKING LIFE OF THE ROOF BASED ON 2,000 HOURS OF EXPOSURE TO ACCELERATED WEATHERING TESTS CONDUCTED IN ACCORDANCE WITH ASTM G152, ASTM G154 OR ASTM G155. THOSE ROOF COVERINGS THAT ARE SUBJECT TO CYCLICAL FLEXURAL RESPONSE DUE TO WIND LOADS SHALL NOT DEMONSTRATE ANY SIGNIFICANT LOSS OF TENSILE STRENGTH FOR UNREINFORCED MEMBRANES OR

BREAKING STRENGTH FOR REINFORCED MEMBRANES WHEN TESTED AS REQUIRED.

1504.8 ROOF COVERINGS INSTALLED ON LOWSLOPE ROOFS IN ACCORDANCE WITH SECTION 1507 SHALL RESIST IMPACT DAMAGE BASED ON THE RESULTS OF TESTS CONDUCTED IN ACCORDANCE WITH ASTM D3746, ASTM D4272

OR FM 4470 RESISTANCE TO FOOT TRAFFIC TEST.

1505.1 MINIMUM ROOF COVERING CLASSIFICATION FOR TYPES OF CONSTRUCTION: IIB = CLASS C

2021 INTERNATIONAL ENERGY CONSERVATION CODE

402.1.3 OPAQUE THERMAL ENVELOPE INSULATION COMPONENT MINIMUM REQUIREMENTS, R-VALUE METHOD

ROOF - INSULATION ABOVE ROOF DECK - ZONE 5: R-30 CONTINUOUS INSULATION

402.1.4.1.3 CONTINUOUS INSULATION BOARD SHALL BE INSTALLED IN NOT LESSS THAN TWO LAYERS, AND THE EDGE JOINTS BETWEEN EACH LAYER OF INSULATION SHALL BE STAGGERED, EXCEPT WHERE INSULATION TAPERS TO

THE ROOF DECK AT A GUTTER EDGE, ROOF DRAIN, OR SCUPPER.

402.2.1.2 THE MINIMUM THICKNESS OF ABOVE-DECK ROOF INSULATION AT ITS LOWEST POINT, GUTTER EDGE, ROOF

DRAIN, OR SCUPPER SHALL BE NOT LESS THAN 1 INCH.

1. REFER TO JOHNS MANVILLE WEBSITE (www.jm2. PLEASE SEE SINGLE PLY FLASHING SPECIFICA INSTRUCTIONS AND REQUIREMENTS WHICH A3. ANY CARPENTRY OR METAL WORK SHOULD BEWITH LOCAL CODE REQUIREMENTS AND/OR PROJBE REVIEWED AND APPROVED BY A LICENSED DE4. IF GAP OR CUT IN MEMBRANE IS GREATER THTHAT EXTENDS OUT ONTO THE MEMBRANE A MIN("L" PATCH SHOWN AT RIGHT WITHOUT TPO UNIV5. JM TPO EDGE SEALANT IS REQUIRED ON ALL CMEMBRANE. THIS INCULDES FACTORY CUT MEMB1. REFER TO JOHNS MANVILLE WEBSITE (www2. PLEASE SEE SINGLE PLY FLASHING SPECIFIREQUIREMENTS WHICH ARE CONSIDERED A P3. ANY CARPENTRY OR METAL WORK SHOULD 4. JM TPO EDGE SEALANT IS REQUIRED ON ALMEMBRANE. THIS INCLUDES FACTORY CUT ED

AND/OR PROJECT SPECS. THESE COMPONENT

JM SINGLE PLY LVOC CAULK (AT

OF CLAMP - SLOPED TO SHED WREFER TO JOHNS MANVILLE WEBSITE (wwPLEASE SEE JM TPO APPLICATION GUIDE F

INSTRUCTIONS AND REQUIREMENTS WHI

ANY CARPENTRY OR METAL WORK SHOUL

WITH LOCAL CODE REQUIREMENTS AND/O

SHOULD BE REVIEWED AND APPROVED BY

JM APPROVED FASTENERS & PLA

PENETRATION DEPENDANT ON D

SEE SPECIFICATIONS FOR FURTH

JM TPO MEMBRANE ADHERED TO

WITH JM APPROVED MEMBRANE

JM TPO 6" REINFORCED TERMINA

CONTINUOUS WELD AROU

SLOPE

1/4 :12

SL

O

PE

1/

:1

SLOPE

1/4 :12

SLOPE

1/4 :12

SLOPE

1/4 :12

SL

O

PE

1/

:1

SL

O

PE

1/

:1

ROOF DRAIN CLAMP AND STRAINER

TO BE REPLACED; CONTRACTOR TO

ENSURE PRODUCTS ARE

COMPATIBLE WITH, AND COVERED

BY ROOF WARRANTY. CLEAN ROOF

DRAIN LEADER PER ROOF

MANUFACTURER GUIDELINES.

ROOF DRAIN CLAMP AND STRAINER

TO BE REPLACED; CONTRACTOR TO

ENSURE PRODUCTS ARE

COMPATIBLE WITH, AND COVERED

BY ROOF WARRANTY. CLEAN ROOF

DRAIN LEADER PER ROOF

MANUFACTURER GUIDELINES.

EXISTING RTU TO BE REPLACED

IN-KIND UNDER SEPARATE

PERMIT / COVER.

PRE-FABRICATED CURB TO BE

COORDINATED WITH ROOFING

SCOPE OF WORK. ALL CURB

FLASHINGS TO BE PER PROVIDED

MANUFACTURER STANDARD

DETAILS HEREIN.

PROVIDE ROOF CRICKET AT

MECHANICAL CURB LOCATION.

EXISTING EXTERIOR WALL BELOW;

NO SOFFIT CONDITION.

EXISTING EXTERIOR WALL

PARAPET TO BE EXTENDED

PER TYPICAL DETAIL,

TYPICAL FULL PERIMETER.

EXISTING COPING TO BE

REPLACED PER PROVIDED

MANUFACTURER

STANDARD DETAIL,

TYPICAL FULL PERIMETER.

EXISTING WALKWAY PAVERS TO

BE REMOVED AND REPLACED

WITH NEW ADHERED AND HEAT

WELDED TPO WALKPADS PER

PROVIDED MANUFACTURER

STANDARD DETAIL. WALKWAY

PATH LAYOUT SHALL MATCH

EXISTING.

EXISTING ROOF LADDER ACCESS

AND CAGE STRUCTURE TO REMAIN.

ADD ALTERNATE SCOPE - ADD ALTERNATE NO. 1

PIPE RAIL SYSTEM:

· 1-1/2" DIA. PASSIVATED STAINLESS STEEL PIPE POSTS

AND RAILS

· POST SPACING ASSUMED TO BE 48" O.C. MAXIMUM

· GUARDRAIL SHALL RESIST LATERAL FORCES OF 200LBS

· INCLUDE PASSIVATED STAINLESS STEEL RAIL CORNER

TUBE, MID RAIL SUPPORTS, ELBOWS, TEES, CROSS, POST

CAPS, OTHER ACCESSORIES AND CONNECTIONS AS

REQUIRED TO COMPLETE GUARD

EXISTING MEMBRANE ROOF, INSULATION, AND

VAPOR BARRIER TO BE REMOVED. COMPLETE

REPLACEMENT PER TYPICAL DETAILS 1/S200

THROUGH 3/S203.

S200

S200

SIM

S2

SI

M

S2

SI

M

S2

S201

S20

S202

FLASH AROUND EXISTING ROOF

PENETRATIONS PER ROOFING

MANUFACTURER STANDARD DETAILS,

TYPICAL. EXTENSION OF PIPING MAY

BE REQUIRED TO ACHIEVE ADEQUATE

LENGTH BEYOND ROOF AND/OR

MANUFACTURER TYPICAL PIPE

FLASHING AS REQUIRED PER ROOFING

MANUFACTURER WARRANTY

REQUIREMENTS. ALL LOCATIONS NOT

SHOWN, CONTRACTOR TO FIELD

VERIFY ALL LOCATIONS.

S2

SI

M

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S100

KMN

KMN

AAS

10/26/2026

AS NOTED

C-90064

BUILDING A

ROOF PLAN

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

BUILDING A ROOF PLANS100

1/4" = 1'-0"

NOTES:

1. ALL OPENINGS MUST BE PROTECTED FROM DUST AND DEBRIS DURING ALL WORK. THIS

INCLUDES PROTECTING OR COVERING ANY OPENINGS NEAR THE WORK AREA AS WELL

AS PROVIDING FILTERS FOR VENTS AND AIR INTAKES.

2. ALL EXTERIOR FIXTURES AND ITEMS MUST BE PROTECTED FOR THE DURATION OF THE

PROJECT. CONTRACTOR MAY ELECT TO REMOVE AND REINSTALL ITEMS AT NO

ADDITIONAL COST TO THE OWNER.

3. EXTERIOR LIGHTS, CAMERAS, SIGNAGE AND OTHER APPARATUSES ARE NOT SHOWN

FOR CLARITY. CONTRACTOR TO REMOVE AND REPLACE AS REQUIRED TO COMPLETE

WORK (WITH OWNER APPROVAL) AND/OR PROTECT FOR DURATION OF THE PROJECT.

SLOPE

1/4 :12

SLOPE

1/4 :12

SL

O

PE

1/

:1

SL

O

PE

1/

:1

ROOF DRAIN CLAMP AND STRAINER TO BE

REPLACED; CONTRACTOR TO ENSURE

PRODUCTS ARE COMPATIBLE WITH AND

COVERED BY ROOF WARRANTY. CLEAN

ROOF DRAIN LEADER PER ROOF

MANUFACTURER GUIDELINES.

PROVIDE ROOF CRICKET PER

ROOFING MANUFACTURER

INSTALLATION INSTRUCTIONS

EXISTING ROOF BLOWER DUCTING AND

EQUIPMENT TO REMAIN (SHOWN DASHED),

TYPICAL OF (3). FLASH AROUND ALL

ROOFTOP MOUNTS, EQUIPMENT, ETC. PER

ROOFING MANUFACTURER DETAILS.

EXISTING EXTERIOR WALL BELOW;

NO SOFFIT CONDITION.

EXISTING EXTERIOR WALL PARAPET

TO BE EXTENDED PER TYPICAL

DETAIL, TYPICAL FULL PERIMETER.

EXISTING ROOF LADDER

ACCESS WITH HARNESS

ARREST SYSTEM TO REMAIN

EXISTING COPING TO BE REPLACED PER

PROVIDED MANUFACTURER STANDARD

DETAIL, TYPICAL FULL PERIMETER.

EXISTING WALKWAY PAVERS TO BE

REMOVED AND REPLACED WITH NEW

ADHERED AND HEAT WELDED TPO

WALKPADS PER MANUFACTURER

PROVIDED STANDARD DETAIL.

WALKWAY PATH LAYOUT SHALL

MATCH EXISTING.

FLASH AROUND EXISTING ROOF PENETRATIONS

PER ROOFING MANUFACTURER STANDARD

DETAILS, TYPICAL. EXTENSION OF PIPING MAY

BE REQUIRED TO ACHIEVE ADEQUATE LENGTH

BEYOND ROOF AND/OR MANUFACTURER

TYPICAL PIPE FLASHING AS REQUIRED PER

ROOFING MANUFACTURER WARRANTY

REQUIREMENTS. ALL LOCATIONS NOT SHOWN,

CONTRACTOR TO FIELD VERIFY ALL LOCATIONS.

EXISTING FACE-MOUNTED RAIL SYSTEM

TO REMAIN. PROTECT DURING

DEMOLITION AND CONSTRUCTION.

TUBE, MID RAIL SUPPORTS, ELBOWS, TEES, CROSS, PO

EXISTING MEMBRANE

ROOF, INSULATION, AND

VAPOR BARRIER TO BE

REMOVED. COMPLETE

REPLACEMENT PER

TYPICAL DETAILS 1/S200

THROUGH 3/S203.

S200

S200

SIM

S2

SI

M

SI

M

S2

S201

S2

S200

S2

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S101

KMN

KMN

AAS

10/26/2026

AS NOTED

C-90064

BUILDING B

ROOF PLAN

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

BUILDING B ROOF PLANS101

1/4" = 1'-0"

NOTES:

1. ALL OPENINGS MUST BE PROTECTED FROM DUST AND DEBRIS DURING ALL WORK. THIS

INCLUDES PROTECTING OR COVERING ANY OPENINGS NEAR THE WORK AREA AS WELL

AS PROVIDING FILTERS FOR VENTS AND AIR INTAKES.

2. ALL EXTERIOR FIXTURES AND ITEMS MUST BE PROTECTED FOR THE DURATION OF THE

PROJECT. CONTRACTOR MAY ELECT TO REMOVE AND REINSTALL ITEMS AT NO

ADDITIONAL COST TO THE OWNER.

3. EXTERIOR LIGHTS, CAMERAS, SIGNAGE AND OTHER APPARATUSES ARE NOT SHOWN

FOR CLARITY. CONTRACTOR TO REMOVE AND REPLACE AS REQUIRED TO COMPLETE

WORK (WITH OWNER APPROVAL) AND/OR PROTECT FOR DURATION OF THE PROJECT.

GUARDRAIL TO BE MINIMUM 42" ABOVE WALK

SURFACE, TYPICAL PERIMETER OF ROOF

TAPERED RIGID INSULATION ACHIEVING MINIMUM

R-30 SYSTEM OVER EXISTING ROOF DECK.

ASSUMED 1.5" MINIMUM TAPERED START AT LOW

POINTS, ROOF DRAINS. SLOPE PER PLAN.

APPROXIMATE EXISTING TOP OF PARAPET

EXISTING ROOF TO REMAIN; METAL DECK AND CONCRETE

EXISTING WALL

EXISTING BRICK MASONRY TO REMAIN

L4x4x1 4 LEDGER ANGLE WITH 12" DIAMETER ADHESIVE ANCHORS x4.5"

MINIMUM EMBEDMENT INTO MASONRY WALL AT 16" O.C. MAXIMUM

ADD ALTERNATE SCOPE - ADD ALTERNATE NO. 1

PIPE RAIL SYSTEM:

· 1-1/2" DIA. PASSIVATED STAINLESS STEEL PIPE POSTS AND RAILS

· POST SPACING ASSUMED TO BE 48" O.C. MAXIMUM

· GUARDRAIL SHALL RESIST LATERAL FORCES OF 200LBS

· INCLUDE PASSIVATED STAINLESS STEEL RAIL CORNER TUBE, MID RAIL

SUPPORTS, ELBOWS, TEES, CROSS, POST CAPS, OTHER ACCESSORIES

AND CONNECTIONS AS REQUIRED TO COMPLETE GUARD

ADD ALTERNATE SCOPE - ADD ALTERNATE NO. 1

PIPE RAIL SYSTEM; STAINLESS STEEL RAIL MOUNT BASE;

FASTEN PER MANUFACTURER INSTALLATION INSTRUCTIONS

NEW TPO ROOFING MEMBRANE

BASIS OF DESIGN: JOHNS MANVILLE GRAY TPO

MEMBRANE-COMPATIBLE ICE AND WATER SHIELD

TURN MEMBRANE OVER PARAPET WALL PER

MANUFACTURER STANDARD INSTALLATION DETAILS,

INSTRUCTIONS. TERMINATE WITH ROUT-IN TERM BAR

AT MASONRY. ANCHOR, SEAL AND SEAM AT

TERMINATIONS AND TRANSITIONS PER

MANUFACTURER INSTALLATION INSTRUCTIONS

FIRE RATED WOOD BLOCKING AND PARAPET EXTENSION TO

ACHIEVE HEIGHT REQUIRED FOR NEW INSULATION AND

MEMBRANE INSTALLATION.

5/8" DIAMETER ADHESIVE ANCHORS AT 48" O.C. MAXIMUM

WITH MINIMUM 6" EFFECTIVE EMBEDMENT

GALVANIZED CLEAT, 20 GA CONTINUOUS ALONG PARAPET

NEW GRAVEL STOP WITH DRIP EDGE PER DETAIL 3/S201

6" M

IN

O R

AS

R

EQ

D

BY

M

FR

EXISTING PIPE RAIL SYSTEM TO REMAIN

NEW TPO ROOFING MEMBRANE

BASIS OF DESIGN: JOHNS MANVILLE GRAY TPO

MEMBRANE-COMPATIBLE ICE AND WATER SHIELD

TAPERED RIGID INSULATION ACHIEVING MINIMUM R-30

SYSTEM OVER EXISTING ROOF DECK. ASSUMED 2.5"

BASE LAYER AND 0.5" MINIMUM TAPERED START AT

LOW POINTS, ROOF DRAINS. SLOPE PER PLAN.

TURN MEMBRANE OVER PARAPET WALL PER

MANUFACTURER STANDARD INSTALLATION DETAILS,

INSTRUCTIONS. TERMINATE WITH ROUT-IN TERM BAR

AT MASONRY. ANCHOR, SEAL AND SEAM AT

TERMINATIONS AND TRANSITIONS PER

MANUFACTURER INSTALLATION INSTRUCTIONS

EXISTING ROOF TO REMAIN; METAL DECK AND CONCRETE

FIRE RATED WOOD BLOCKING AND PARAPET EXTENSION TO

ACHIEVE HEIGHT REQUIRED FOR NEW INSULATION AND

MEMBRANE INSTALLATION.

5/8" DIAMETER ADHESIVE ANCHORS AT 48" O.C. MAXIMUM

WITH MINIMUM 6" EFFECTIVE EMBEDMENT

GALVANIZED CLEAT, 20 GA CONTINUOUS ALONG PARAPET

EXISTING WALL

EXISTING BRICK MASONRY TO REMAIN

NEW GRAVEL STOP WITH DRIP EDGE PER DETAIL 3/S201

6" M

IN

O R

AS

R

EQ

D

BY

M

FR

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S200

KMN

KMN

AAS

10/26/2026

AS NOTED

C-90064

BUILDING A

AND B DETAILS

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

BUILDING A TYPICAL SECTION

AT PARAPETS200

1-1/2" = 1'-0" SCALE:

BUILDING B TYPICAL SECTION

AT PARAPETS200

1-1/2" = 1'-0"

APPROVED DECK

JM INSULATION / COVER BOARD

1" (25 mm)

3" (76 mm) LAP

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

REPLACES TA-5-ADH JM TPO

N.T.S 7-14-17 30 YEAR

T-MS-07 MEMBRANE SIDE LAP

JM TPO MEMBRANE ADHESIVE

(FOR ADHERED

SPECIFICATIONS ONLY)

1 1/2" (38 mm)

MIN. WELD

(CONTINUOUS)

JM TPO EDGE SEALANT

IF REQUIRED

JM TPO

MEMBRANE

JM TPO MEMBRANE

ADHERED OR

MECHANICALLY FASTENED

(END LAP

CONDITION ONLY)

NOTES:

1.

2.

3.

4.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS

SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON-ENCAPSULATED EDGES OF REINFORCED

MEMBRANE. THIS INCLUDES FACTORY CUT MEMBRANE (SEE DETAIL T-MS-01).

1" (25 mm)

6"

OF WALKPAD

JM TPO WALKPAD

JM TPO ADHERED

30" WIDTH

LENGTH OF T

PO

WALKPAD

DETERMINED BY SEAMS

OF T

PO

FIE

LD MEMBRANE

HEAT WELDED - PERIMETER

JM TPO WALKPAD

HEAT WELDED - PERIMETER

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

REPLACES TM-93A JM TPO

N.T.S 7-14-17 20 YEAR

T-PT-05 TPO WALKPADS OVER ADHERED TPO MEMBRANE

LENGTH OF T

PO

WALKPAD

DETERMINED BY SEAMS

OF T

PO

FIE

LD MEMBRANE

1 1/2" (40 mm) MINIMUM

CONTINUOUS WELD AROUND

EDGE OF WALKPAD (MUST

BE WATERTIGHT)

TPO HEAT WELDED SEAM

HOLD ADHESIVE

BACK 2" (51 mm) FROM

WALKPAD EDGES

ADHERE WALKPADS

WITH JM MEMBRANE

ADHESIVE-SEE NOTE 7

NOTES:

1.

2.

3.

4.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS

SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON-ENCAPSULATED EDGES OF REINFORCED

MEMBRANE. THIS INCLUDES FACTORY CUT MEMBRANE (SEE DETAIL T-MS-01).

5. CLEAN MEMBRANE SURFACE PRIOR TO WALKPAD INSTALLATION WITH TPO MEMBRANE CLEANER.

(152 mm)

6. DO NOT INSTALL WALKPADS OVER MEMBRANE SEAMS.

JM TPO ADHERED

(MAX. LE

NGTH 10' W

ITH

MIN. 2" G

AP B

ETWEEN

WALKPAD LE

NGTHS)

(MAX. LE

NGTH 10' W

ITH

MIN. 2" G

AP B

ETWEEN

WALKPAD LE

NGTHS)

7. JM APPROVED ADHESIVES FOR ADHERING TPO WALKPADS ARE JM LVOC MEMBRANE ADHESIVE (TPO & EPDM), JM MEMBRANE BONDING ADHESIVE (TPO & EPDM) AND JM TPO WATER BASED MEMBRANE ADHESIVE.

APPROVED DECK

JM INSULATION / COVER BOARD

PRESTO-TITE ANCHOR BAR

JM SINGLE PLY SEALING MASTIC

WOOD NAILER SECURELY

ANCHORED TO DECK-RE: DETAIL T-FE-V1

PRESTO-TITE FASCIA COVER

JM TPO MEMBRANE

ADHERED OR

MECHANICALLY FASTENED

JM TPO MEMBRANE ADHESIVE

(FOR ADHERED

SPECIFICATIONS ONLY)

STAINLESS STEEL

FASTENERS 12" (304 mm)

O.C. MIN. PROVIDED BY JM

MEMBRANE FASTENED ON BACK

SIDE OF WALL 12" (304 mm) O.C. MAX.

JM SINGLE PLY LVOC CAULK, OPTIONAL

1/

4" (3 m m m m

FA

SC

IA

C O

VE

R

H

EI

G H

T

NOTES:

1.

2.

3.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS

SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

4. JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON-ENCAPSULATED EDGES OF REINFORCED

MEMBRANE. THIS INCLUDES FACTORY CUT MEMBRANE (SEE DETAIL T-MS-01)

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S201

KMN

KMN

AAS

10/26/2026 N.T.S.

C-90064

TYPICAL DETAILS

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

MEMBRANE SIDE LAP

MANUFACTURER DETAILS201

NOT TO SCALE SCALE:

TPO WALKPADS OVER TPO MEMBRANE

MANUFACTURER DETAILS201

NOT TO SCALE

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

FLASHING EDGE JM TPO

N.T.S 12-06-19 30 YEAR

T-FE-P2 JM PRESTO TITE FASCIA SYSTEM FOR SINGLE PLY SYSTEMS

SCALE:

TPO TERMINATION WITH GRAVEL STOP DETAILS201

NOT TO SCALE

STRAINER

ISSUE DATEDRAWING NO.

SCALE

MEMBRANE TYPE:

MAXIMUM GUARANTEE TERM:

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy for general educational purposes only. This complimentary assistance is not to be either used or relied upon by anyone as a substitute for professional engineering design and documentation required by any building code, contract, or applicable law. By accepting the general conceptual information, you agree it does not constitute any representations, endorsements of, or an assumption by Johns Manville of any duty or liability for either the adequacy of the design of a building, any of its components or the sufficiency of any construction.REPLACES TF-55 30 YEAR

JM TPO

N.T.S

7-17-17T-DV-07

PRIMARY DRAIN SUMP (LOW SLOPE) UP TO 3:12 SLOPE

TAPERED DRAIN

JM SINGLE PLY SEALING MASTIC

CLAMP RING

JM INSULATION / COVER BOARD

CLEAN OUT EXISTING

DRAIN PIPE AND LEADER

AS REQUIRED

JM TPO MEMBRANE

ADHERED OR

MECHANICALLY FASTENED

NOTES:

1.

2.

3.

4.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS

SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON-ENCAPSULATED EDGES OF

REINFORCED MEMBRANE. THIS INCLUDES FACTORY CUT MEMBRANE (SEE DETAIL T-MS-01).

INSULATION TAPERED

TO DRAIN

JM TPO MEMBRANE

ADHESIVE (FOR ADHERED

SPECIFICATIONS ONLY)

JM TPO FIELD MEMBRANE

ADHERED INTO DRAIN BOWL

APPROVED DECK

CUT HOLE THROUGH MEMBRANE AT LEAST THE

SAME DIAMETER AS THE ROOF DRAIN PIPE-TYP.

5. REPLACE ANY BROKEN COMPONENTS (DRAINS, RINGS, BOLTS, ETC.)

1/2" (13 mm) MIN.

6. SUMP AREA MUST BE PROPERLY TAPERED SO THAT THE DRAIN FLASHING IS NOT INSTALLED UNDER TENSION.

APPROVED DECK

JM INSULATION / COVER BOARD

JM APPROVED FASTENERS & PLATES 12" (304 mm) O.C. MAX.

PENETRATION DEPENDANT ON DECK MATERIAL(S).

SEE SPECIFICATIONS FOR FURTHER INFORMATION

PEEL & STICK

SECTION OF RTS

ISSUE DATEDRAWING NO.

SCALE

MEMBRANE TYPE:

MAXIMUM GUARANTEE TERM:

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy for general educational purposes only. This complimentary assistance is not to be either used or relied upon by anyone as a substitute for professional engineering design and documentation required by any building code, contract, or applicable law. By accepting the general conceptual information, you agree it does not constitute any representations, endorsements of, or an assumption by Johns Manville of any duty or liability for either the adequacy of the design of a building, any of its components or the sufficiency of any construction.FLASHING WALL 20 YEAR

JM TPO

N.T.S

11-28-22T-FW-B1

BASE FLASHING WITH HORIZONTAL REINFORCED TERMINATION STRIP - RTS

JM TPO MEMBRANE ADHERED TO WALL

WITH JM APPROVED MEMBRANE ADHESIVE (SEE DETAIL T-FW-M1)

JM TPO MEMBRANE MECHANICALLY

FASTENED OR ADHERED

NOTES:

JM MEMBRANE PRIMER (SEE NOTE 4)

JM TPO 6" REINFORCED TERMINATION STRIP (RTS)

JM TPO MEMBRANE ADHESIVE FOR

ADHERED SPECIFICATIONS ONLY

APPROVED

WALL / SUBSTRATE

1.

2.

3.

4.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION INSTRUCTIONS AND

REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

PRIME UNDERSIDE OF FIELD MEMBRANE AT PEEL & STICK SECTION WITH JM TPO MEMBRANE PRIMER OR JM SINGLE PLY MEMBRANE PRIMER (LOW VOC). ROLL TPO MEMBRANE WITH ROLLER UNDER PRESSURE AT PEEL & STICK SECTION OF RTS.

5. THIS DETAIL IS NOT COMPATIBLE OR ELIGIBLE FOR GUARANTEE WITH JM SELF ADHERED TPO MEMBRANE.

ISSUE DATEDRAWING NO.

SCALE

MEMBRANE TYPE:

MAXIMUM GUARANTEE TERM:

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy for general educational purposes only. This complimentary assistance is not to be either used or relied upon by anyone as a substitute for professional engineering design and documentation required by any building code, contract, or applicable law. By accepting the general conceptual information, you agree it does not constitute any representations, endorsements of, or an assumption by Johns Manville of any duty or liability for either the adequacy of the design of a building, any of its components or the sufficiency of any construction.NEW DETAIL 30 YEAR

JM TPO

N.T.S

1-2-15T-MS-01

CUT EDGE SEALANT

NOTES:

JM TPO MEMBRANE

JM TPO CUT EDGE (SEE NOTES 4 & 5)

JM TPO MEMBRANE

JM TPO EDGE SEALANT

IF REQUIRED

1.

2.

3.

4.

5.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION INSTRUCTIONS AND

REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS SHOULD BE REVIEWED AND APPROVED BY A

LICENSED DESIGN PROFESSIONAL.

JM TPO EDGE SEALANT IS A ONE-PART POLYMERIC MATERIAL USED TO SEAL CUT EDGES OF JM TPO MEMBRANES WHERE THE POLYESTER REINFORCEMENT IS EXPOSED AFTER WELDING. A 1/8" (3.18 MM) BEAD IS APPLIED FROM A PLASTIC

SQUEEZE BOTTLE TO THE CUT EDGE OF THE TPO MEMBRANE.

JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON ENCAPSULATED EDGES OF REINFORCED MEMBRANE.

THIS INCLUDES FACTORY CUT MEMBRANE.

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S202

KMN

KMN

AAS

10/26/2026 N.T.S.

C-90064

TYPICAL DETAILS

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

BASE FLASHING WITH HORIZONTAL REINFORCED TERMINATION STRIP

MANUFACTURER DETAILS202

NOT TO SCALE SCALE:

CUT EDGE SEALANT

MANUFACTURER DETAILS202

NOT TO SCALE

SCALE:

PRIMARY DRAIN SUMP (LOW SLOPE)

MANUFACTURER DETAILS202

CURB

JM TPO

MEMBRANE

1. REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

2. PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

3. ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS SHOULD

BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

4. IF GAP OR CUT IN MEMBRANE IS GREATER THAN 1" UNDER TPO UNIVERSAL CORNER, AN "L" PATCH THAT EXTENDS OUT ONTO THE MEMBRANE A MINIMUM OF 2" MUST BE INSTALLED AT OUTSIDE CORNER.

("L" PATCH SHOWN AT RIGHT WITHOUT TPO UNIVERSAL CORNER)

5. JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON ENCAPSULATED EDGES OF REINFORCED

MEMBRANE. THIS INCULDES FACTORY CUT MEMBRANE (SEE DETAIL T-MS-01).

1 1/2" (40 mm)

MINIMUM

CONTINUOS WELD

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

REPLACES TF-62A JM TPO

N.T.S 1-2-15 30 YEAR

T-FC-03 OUTSIDE CORNER

1 1/2" (40 mm)

MINIMUM

CONTINUOUS

WELD

JM TPO

MEMBRANE

MECHANICALLY

FA

STENED

AT PE

RIMETER OF C

URB

IF GAP IS GREATER

THAN 1" (25 mm)

SEE NOTE 4

JM TPO UNIVERSAL

CORNER WELDED TO

FLASHING SHEET &

FIELD MEMBRANE

'L' PATCH UNDER FLASHING,

WELDED SOLID

NOTES:

JM TPO EDGE SEALANT

IF REQUIRED

OPTIONAL "L" PATCH

UNDER UNIVERSAL

COVER

JM APPROVED FASTENER

AND PLATE 12" (304 mm) O.C. MAX.

PENETRATION DEPENDANT

ON DECK MATERIAL(S).

SEE SPECIFICATIONS FOR

FURTHER INFORMATION

JM TPO FLASHING

"A"

JM TPO FLASHING

"B"

JM TPO

MEMBRANE

MECHANICALLY

ATTACHED

AT PE

RIMETER

COPIN

G

COPIN

G

FLA

SHING

"A"

"B" FLASHING

FIELD

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

CURB & CORNER JM TPO

N.T.S 03-15-19 30 YEAR

T-FC-04 INSIDE CORNER

90° BEND IN FLASHING

90° BEND IN FLASHING

APPROPRIATE VERTICAL

JM FASTENERS

12" (304 mm) O.C. MAX.

REQUIRED FOR WALLS

GREATER THAN

5 FT. IN HEIGHT

INCISE & CUT OUT

TPO FLASHING AND

POSITION AS SHOWN

1 1/2" (38 mm)

MINIMUM CONTINUOUS WELD

JM TPO

MEMBRANE

MECHANICALLY

FA

STENED

AT PE

RIMETER

FOLD AND WELD

SIMILAR TO THIS

FOLD LINE

(VISIBLE)

JM TPO UNIVERSAL CORNER

WELDED TO FLASHING SHEET

(FOLDED AS SHOWN)

JM IN

SULATION / C

OVER BOARD

APPR

OVED DECK

TPO MEMBRANE ADHESIVE

BETWEEN OVERLAP (NOT SHOWN)

JM IN

SULATION / C

OVER BOARD

APPR

OVED DECK

1. REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

2. PLEASE SEE SINGLE PLY FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION INSTRUCTIONS AND

REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

3. ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS

4. JM TPO EDGE SEALANT IS REQUIRED ON ALL CUT OR NON ENCAPSULATED EDGES OF REINFORCED

MEMBRANE. THIS INCLUDES FACTORY CUT EDGES (SEE DETAIL T-MS-01).

INCISE & CUT OUT

TPO FLASHING AND

POSITION AS SHOWN

NOTES:

JM APPROVED FASTENER AND PLATE

PENETRATION DEPENDANT ON DECK

MATERIAL(S). SEE SPECIFICATIONS

FOR FURTHER INFORMATION

JM TPO EDGE

SEALANT IF

REQUIRED

PLAN VIEW OF FLASHING

"B" STEP 2

PLAN VIEW OF FLASHING

"A"

STEP 1

STEP 3 AT INSIDE

CORNER

AND/OR PROJECT SPECS. THESE COMPONENTS SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

APPROVED

WALL / SUBSTRATE

APPROVED

WALL / SUBSTRATE

APPROPRIATE

JM FASTENERS

12" (304 mm)

O.C. MAX.

JM INSULATION

DRAWING NO.

Johns Manville is a manufacturer of commercial roofing products and offers this general conceptual information to you as a courtesy. This complimentary assistance is not to be used or relied upon by anyone as a substitute for professional engineering design and documentation required by building code, contract, or applicable law. By accepting these comments you agree they do not constitute any representations, endorsements of, or an assumption by Johns Manville of any liability for either the adequacy of the design of this building or any other material not supplied by Johns Manville.

MAXIMUM GUARANTEE TERM:ISSUE DATESCALE

MEMBRANE TYPE:

PENETRATION JM TPO

N.T.S 08-09-22 30 YEAR

T-FP-01 TPO PIPE BOOT

APPROVED DECK

JM TPO

MEMBRANE

JM APPROVED FASTENER AND PLATE

MIN. 4 AROUND PIPE

PENETRATION DEPENDANT ON DECK

MATERIAL(S). SEE SPECIFICATIONS

FOR FURTHER INFORMATION

PIPE PENETRATION

JM SINGLE PLY LVOC CAULK (AT TOP

OF CLAMP - SLOPED TO SHED WATER)

STAINLESS STEEL CLAMP AND SCREW

JM SEALING MASTIC

(BETWEEN PIPE AND NECK OF BOOT)

PRE-MOLDED JM TPO PIPE BOOT

1 1/2" (38 mm) MIN. WELD

(CONTINUOUS AROUND

BOOT PERIMETER)

NOTES:

1.

2.

3.

REFER TO JOHNS MANVILLE WEBSITE (www.jm.com) FOR MOST UP-TO-DATE INFORMATION.

PLEASE SEE JM TPO APPLICATION GUIDE FOR A FULL DESCRIPTION OF INSTALLATION

INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL.

ANY CARPENTRY OR METAL WORK SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS

SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL.

COVER BOARD

A

FU

LL

-S

ER

VI

CE

C

IV

IL

E

NG

IN

EE

RI

NG

F

IR

M

W W

W .G

AT

EW

AY

EN

G

IN

EE

RS

.C

TS

BU

RG

H

B

U

TL

ER

5-

4-

PR

EP

AR

ED

F O

R

R

EV

IS

IO

N R

EC

O

R D

N o

D at e

Pa th

F ile na m e=

G :\P ro je ct s\

Be th el

P ar k\

ST

P

R oo fs \D w g\

-S he et

\C -9

B et he l P ar k

- S

TP

R oo fs .d w g

Pl ot

D at e=

/2 6/

2:

P

M A sh le y A.

S w ee ne y Sa ve D at e=

/2

6/

1:

A M

Project Number:

Drawing Scale:

Date Issued:

Index Number:

Drawn By:

Checked By:

Project Manager:

22.0

G at ew ay E ng in ee rs

In c.

A ll

R ig ht s

R es er ve d

THE GATEWAY ENGINEERS, INC. RETAINS OWNERSHIP RIGHTS OF ALL DATA WITHIN THE PLANS. DATA CONTAINED WITHIN IS ONLY TO BE USED FOR ITS INTENDED PURPOSE BY ITS RESPONSIBLE PARTY. THE USE, REPLICATION, REPRODUCTION, OR REDISTRIBUTION OF DATA CONTAINED WITHIN IS STRICTLY PROHIBITED AND SUBJECT TO LEGAL ACTION. S203

KMN

KMN

AAS

10/26/2026 N.T.S.

C-90064

TYPICAL DETAILS

BE

TH

EL

P

AR

K, P A

SO

U

TH

P

AR

K

TO

W

N

SH

IP

, P

A

W

ES

T

LI

BR

AR

Y

AV

EN

U

E

P

IN

EY

F

O R

K R

O

AD

M U

N

IC

IP

AL

IT

Y

O F

BE

TH

EL

P

AR

K

R O

O F

R

EP

LA

C

EM

EN

T

SCALE:

OUTSIDE CORNER

MANUFACTURER DETAILS203

NOT TO SCALE SCALE:

INSIDE CORNER

MANUFACTURER DETAILS203

NOT TO SCALE SCALE:

TPO PIPE BOOT

MANUFACTURER…