This design guide outlines construction requirements for renovating and relocating offices for the U.S. Commodity Futures Trading Commission. It specifies 38 space types including chairman, commissioner, director, and other offices as well as conference rooms, training rooms, and shared workspaces. Requirements cover walls, ceilings, floors, doors, furniture, fixtures, equipment, finishes, electrical and mechanical systems. Audiovisual specifications and IT infrastructure guidelines are included in appendices. Space sketches illustrate example layouts. The document provides detailed product and construction standards to ensure consistency across the agency's headquarters and regional office renovations and relocations.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROPERTY OF THE UNITED STATES GOVERNMENT FOR OFFICIAL USE ONLY
Do not remove this notice Properly destroy documents when no longer needed
U.S. COMMODITY FUTURES
TRADING COMMISSION
(CFTC)
DESIGN GUIDE
April 2023
FOR REFERENCE ONLY
Contact DCHQRelo@cftc.gov for information mailto:DCHQRelo@cftc.gov
Page Purposely Left B lank
Page i
Table of Contents
CFTC GENERAL REQUIREMENTS
Type 1 CHAIRMAN OFFICE
Type 2 COMMISSIONER OFFICE
Type 3 DIRECTOR OFFICE
Type 4 SUPERVISORY OFFICE
Type 5 SUPERVISORY OFFICE
Type 6 NON-SUPERVISORY OFFICE
Type 7 WORKSTATION
Type 8 VISITOR’S OFFICE
Type 9 CONFERENCE ROOM
Type 9A CHAIRMAN’S CONFERENCE ROOM
Type 10 TRAINING ROOM
Type 11 TEAMING ROOM
Type 12 DEPOSITION ROOM
Type 13 NON-NETWORK PC & BLOOMBERG
Type 14 PANTRY
Type 14A CHAIRMAN’S PANTRY
Type 15 EMPLOYEE LOUNGE
Type 16 LEADERSHIP RECEPTION AREA
Type 17 RECEPTION AREA
Type 18 FILE ROOM
Type 19 STORAGE (HQ)
Type 20 STORAGE (Regions)
Type 21 MAIL, SUPPLY & PIV
Type 22 MOTHER’S ROOM
Type 22A GENDER NEUTRAL RESTROOM
Type 23 MAIL ROOM (HQ)
Type 24 PRINT / COPY
Type 25 ADP SERVER ROOM
Type 26 IDF SERVER CLOSET
Type 27 CONFERENCE CENTER ANTE ROOM
Type 27 CONFERENCE CENTER MAIN ROOM
Type 27 CONFERENCE CENTER AV CONTROL BOOTH
Type 27 CONFERENCE CENTER KITCHENETTE
Type 27 CONFERENCE CENTER STORAGE
Type 27 CONFERENCE CENTER MULTI-PURPOSE MEETING
Type 28 BADGING OFFICE
Type 29 PERSONNEL SECURITY OFFICE
Type 30 SECURITY GUARD ROOM
Type 31 AUDIO VISUAL STUDIO
Page ii
Type 32 LIBRARY PUBLIC READING ROOM
Type 33 DA IT CUSTOMER SERVICE CENTER HELP DESK
Type 34 CAA – See Separate “DESIGN GUIDE – SECURE SPACE”
Type 35 USER OPERATIONS TEST / DEPLOYMENT LAB
Type 36 NOT USED
Type 37 FORENSICS TRANSACTIONAL MEETING SPACE
Type 37A FORENSICS LAB
Type 38 NOT USED
APPENDIX 1 - IT REQUIREMENTS PROVIDED BY AGENCY
Specification 27 05 00 - INFORMATION TRANSPORT SYSTEMS INFRASTRUCTURE DESIGN
PART 1 GENERAL
PART 2 PRODUCTS
PART 3 EXECUTION
Specification 11 52 00 - AUDIO VISUAL EQUIPMENT
PART 1 TYPICAL ROOM SYSTEM REQUIREMENTS
1. Audio System
2. Video System
3. Control System
4. Rack Mounting System
APPENDIX 2 - FINISHES MATERIAL REFERENCE LIST
APPENDIX 3 - EQUIPMENT / APPLIANCE REFERENCE LIST
APPENDIX 4 – CFTC SIGNAGE STANDARD
ALL
CFTC GENERAL REQUIREMENTS
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 1 of 209 April 2023 - 2023-04-20 CFTC Design Guide
SUMMARY Relocation of CFTC existing regional and headquarters locations to new federal building assignment or lease locations.
LOCATIONS ▪ Headquarters – Washington, DC
▪ Eastern – New York, NY
▪ Central – Chicago, IL
▪ Southwestern – Kansas City, MO
ADJACENCIES
(GENERAL)
▪ Main Reception and the Gender-Neutral Restroom (GNR) should be adjacent to the public entrance / corridor
▪ Chairman, Commissioners, Directors, Leadership Reception should all be adjacent to each other
▪ The Visitor Office, Deposition Room and one (1) Conference Room and should be adjacent to the main Reception Area
▪ All other Conference Rooms, Teaming Rooms, Print Copy Areas and Pantries should be distributed throughout the overall space
▪ The Mail Room (HQ) or Mail – Supply – PIV (Regions), Supply and Storage Rooms should be adjacent to the service entrance and / or freight elevator.
DOORS /
FRAMES
▪ Full height, solid core, building standard wood doors, stained and varnished finish
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system specified. Recommended manufacturer Infinium Wall Systems Refine Series or equal
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
HARDWARE All locking doors to be electric lock controlled by a remote card reader (coordinate system requirements with agency). Locking doors to be keyed to CFTC master key as fail safe in event of power outage
Lockset Types
▪ Mortise - Mortised or recessed into the edge of the door
▪ Cylindrical - Often called key-in-knob or key-in-lever locks
▪ Dead-Bolt – may also include Occupied / Vacant indicator
▪ Keypad – has numeric keypad requiring a number code to be entered
Lockset Functions
▪ Passage Function Both interior and exterior levers are always unlocked and free
▪ Office Function Interior push button, exterior key core. Interior push button locks door. Door unlocked with key on exterior or lever is turned on interior
▪ Privacy Function Interior push button locks door. Door unlocked when lever is turned on interior or with narrow tool from outside in case of emergency
▪ Storeroom Function Interior lever, exterior key core, always locked / fixed. Interior level always unlocked and free. Door unlocked only with key on exterior.
▪ Classroom Function Interior lever, exterior key core. Interior level always unlocked and free. Door locked or unlocked with key on exterior.
▪ Institutional Function Interior and exterior levers both fixed with key core. Interior and exterior both must use key to unlock.
FIRE Automatic sprinkler systems in accordance with all required and advisory provisions of NFPA 13 latest edition, by hydraulic calculations for light hazard occupancy with uniform water distribution
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 2 of 209
SUPPRESSION over the design area
ENVIRONMENTAL Separate zones (Variable Air Volume (VAV) with thermostat control), building standard distribution
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, mounted at standard height unless otherwise noted on drawings
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R receptacle configuration
▪ Outlets near water source shall have Ground Fault Circuit Interrupter (GFCI) device
▪ Depending upon the space, dedicated circuits for equipment may be necessary, coordinate with CFTC Commission representative to confirm requirements
▪ Coordinate with CFTC Information Technology requirements in APPENDIX 1
LIGHTING ▪ Building standard LED, dimmable lighting as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.) over desk area or alternate, approved for same foot-candles
▪ In accordance with federal, state and local codes, lighting control to include ability to adjust or power lights in response to occupancy, power consumption and daylight available.
▪ Customize lighting layout and switching and review with Commission
▪ Match building standard lighting color temperature, unless otherwise noted on drawings
▪ Dimmable LED downlights over conference area with supplementary LED wall wash lighting
SECURITY ▪ Coordinate with CFTC Security for building entry and screening at each location
▪ Monitoring cameras will be located throughout the general tenant space
▪ If necessary, specific Space Types requiring additional cameras will be noted in that section
▪ See Table below for Access Control:
COMMUNICATION ▪ Refer to IT requirements chart; APPENDIX 1
▪ Communication Data Outlets and Wireless Access Points (WAPs) locations shall be coordinated with the Commission by the Architect / Engineer (A/E) in the final design
▪ CFTC internal Paging System will be furnished and installed by contractor and locations shall be coordinated with the Commission by the Architect / Engineer (A/E) in the final design
FINISHES
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 3 of 209
WALLS, FLOORS,
DOORS, FRAMES,
MILLWORK,
CEILINGS
Refer to Commission standard finishes in APPENDIX 2 for types and locations
FURNITURE FIXTURES & EQUIPMENT
EQUIPMENT (AGENCY PROVIDED) Refer to each Space Type for recommended equipment
FURNITURE (AGENCY PROVIDED) Refer to each Space Type for recommended furniture
SIGNAGE Refer to Commission standard signage in APPENDIX 4 for types and locations
SKETCHES ▪ Sketches for each space type are for illustration purposes only and are not drawn to scale.
They do not represent final configurations.
▪ Power and data connections and General Contractor provided items are noted in red text
▪ Furniture and equipment furnished by the Commission are noted in blue text
END OF GENERAL REQUIREMENTS
LOCATION: HQ
ROOM NAME: CHAIRMAN OFFICE SQUARE FT: 600
SPACE TYPE: Type 1 OCCUPANTS: 10 maximum ADJACENCIES: Executive Team
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 4 of 209
Type 1 CHAIRMAN OFFICE
CONSTRUCTION INFORMATION
MILLWORK N/A
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and varnished finish
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system specified. Recommended manufacturer Infinium Wall Systems Refine Series or equal
▪ Color(s) to be reviewed and approved by the Commission
HARDWARE Office Commercial grade hardware to match building standard style and finish. Final hardware to confirmed with Commission and meeting the following minimum requirements:
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader (coordinate system requirements with Commission)
▪ two coat hooks, one installed at standard height, one installed at accessible height
Toilet Room Commercial grade hardware to match building standard style and finish. Final hardware to confirmed with Commission and meeting the following minimum requirements:
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, privacy function lockset with interior push button, lever handles
▪ two coat hooks, one installed at standard height, one installed at accessible height
WALLS ▪ Partitioning shall be one layer of ⅝” gypsum board to slab above on each side of 2 ½”, 25-gauge (or equivalent) metal studs at 24” On Center (O.C.)
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Provide translucent film at glass in pattern and translucence selected by the Commission, 3M Matt Crystal1 (70-0709-0293-0) or approved equal
CEILING Office Tile
▪ Lay-in acoustic ceiling tiles, building standard size
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 5 of 209
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
▪ USG Fineline Tegular or equal
▪ Minimum ¾” thick with white enameled metal grid to match building standard
Toilet Room ▪ Gypsum board ceiling, with ⅝” thick gypsum board attached to metal drywall suspension system
▪ Paint ceiling in ceiling white color with low VOC content paint for gypsum board substrates: flat acrylic finish, minimum of two finish coats over primer
ACCESSORIES Toilet room accessories include:
▪ Grab Bars (near both toilet and inside shower)
▪ Toilet Tissue Dispenser
▪ Wall Mirror
▪ Towel Dispenser / Waste Receptacle Unit
▪ Seat Cover Dispenser
▪ Sanitary Napkin Dispenser
▪ Sanitary Napkin Waste Receptacle
Assume upgrade from building standard. All to be maintained by landlord. See APPENDIX 3 for recommended
PLUMBING Assume upgrade from building standard and selected by Commission
▪ One (1) Sink / Lavatory
▪ One (1) Faucet – Automatic
▪ One (1) Soap Dispenser – Automatic
▪ One (1) Toilet – Automatic Flush
▪ One (1) Shower stall with frosted, tempered glass door
All to be maintained by landlord. See APPENDIX 3 for recommended
ENVIRONMENTAL ▪ Separate zone (VAV with thermostat control), building standard distribution
▪ Switched exhaust fan for toilet room
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout,
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration.
▪ Coordinate infrastructure and pathways with CFTC Information Technology requirements in
APPENDIX 1
▪ Outlets near water source shall have Ground Fault Circuit Interrupter (GFCI) device
LIGHTING ▪ Building standard LED dimmable lighting as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.) over desk area or alternate approved LED lighting to provide same foot-candles
▪ Dimmable LED downlights over seating and conference area with supplementary LED wall wash lighting
▪ Customize layout and review lighting layout and switching with Commission
▪ Match building standard color temperature
COMMUNICATION ▪ Refer to IT requirements in APPENDIX 1
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 6 of 209
WALLS Office ▪ Low VOC content paint for gypsum board substrates, eggshell finish, minimum of two finish coats over primer
▪ Color per Commission specifications
Toilet Room ▪ Porcelain or ceramic wall tile to height of four (4) feet with profile trim; tile to be selected by Commission
▪ Paint above tile with low VOC content paint for gypsum board substrates, eggshell finish, minimum of two finish coats over primer
▪ Color including accent paint or wallcovering, per Commission specifications
FLOOR / BASE Office ▪ Modular carpet tile
▪ Resilient base to be rubber, top set, ⅛” x 4”, with field formed external and internal corners – coved at hard floor finishes, straight at carpet floor finishes
Toilet Room ▪ Porcelain or ceramic floor tile, 12” x 12” or larger format, thin set, latex grout
▪ Matching porcelain or ceramic base; 4” minimum height
EQUIPMENT (AGENCY PROVIDED)
▪ PC or docking station, flat screen monitor(s), telephone handset and printer at desk
▪ Speaker telephone at conference table
▪ Television monitor, verify location and provide blocking as necessary
▪ Coordinate power and telecommunications connections per requirements in APPENDIX 1
FURNITURE (AGENCY PROVIDED)
▪ Desk, credenza and return, return to be height adjustable
▪ Dual monitor arm on the height adjustable table
▪ Laptop cable lock anchor
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Two (2) Guest chairs
▪ Four (4) upholstered chairs with occasional table
▪ Conference table with ten (10) chairs
▪ All files and storage shall be lockable
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 7 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 1
Four (4) upholstered chairs with occasional table
Conference table with ten (10) chairs
Two (2) guest chairs
Desk, height adjustable return with dual monitor arm and credenza Task chair
Bench and wardrobe cabinet Paper towel dispenser and waste receptacle
Automatic flush toilet, toilet tissue dispenser and toilet seat cover dispenser Grab Bars
Sink with automatic faucet and automatic soap dispenser
Shower stall with grab bars and frosted, tempered glass door
Television Monitor
Table Top Outlets
ROOM NAME: COMMISSIONER OFFICE SQUARE FT: 475
SPACE TYPE: Type 2 OCCUPANTS: 10 maximum
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 8 of 209
Type 2 COMMISSIONER OFFICE
MILLWORK: N/A
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
HARDWARE Office Commercial grade hardware to match building standard style and finish. Final hardware to confirmed with Commission and meeting the following minimum requirements:
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader (coordinate system requirements with
Commission)
▪ two coat hooks, one installed at standard height, one installed at accessible height
Toilet Room Commercial grade hardware to match building standard style and finish. Final hardware to confirmed with Commission and meeting the following minimum requirements:
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, privacy function lockset with interior push button, lever handles
▪ two coat hooks, one installed at standard height, one installed at accessible height
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
CEILING Office Tile
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 9 of 209
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
▪ USG Fineline Tegular or equal
▪ Minimum ¾” thick with white enameled metal grid to match building standard
Toilet Room ▪ Gypsum board ceiling, with ⅝” thick gypsum board attached to metal drywall suspension system
▪ Paint ceiling in ceiling white color with low VOC content paint for gypsum board substrates: flat acrylic finish, minimum of two finish coats over primer
ACCESSORIES Assume upgrade from building standard. Toilet room accessories include:
▪ Grab Bars (near both toilet and inside shower)
▪ Toilet Tissue Dispenser
▪ Wall Mirror
▪ Towel Dispenser / Waste Receptacle Unit
▪ Seat Cover Dispenser
▪ Sanitary Napkin Dispenser and
▪ Sanitary Napkin Waste Receptacle
PLUMBING Assume upgrade from building standard and selected by Commission
▪ One (1) Sink / Lavatory
▪ One (1) Faucet – Automatic
▪ One (1) Soap Dispenser – Automatic
▪ One (1) Toilet – Automatic Flush
▪ One (1) Shower stall with frosted, tempered glass door
ENVIRONMENTAL ▪ Separate zone (VAV with thermostat control), standard distribution
▪ Switched exhaust fan for toilet room
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout,
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration.
▪ Coordinate infrastructure and pathways with CFTC Information Technology requirements in
▪ Outlets near water source shall have Ground Fault Circuit Interrupter (GFCI) device
LIGHTING ▪ Dimmable building standard LED lighting as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.) over desk area or alternate approved LED lighting to provide same foot-candles
▪ Dimmable LED downlights over seating and conference area with supplementary LED wall wash lighting
▪ Communication outlet locations shall be coordinated with the Commission by the Architect /
Engineer in the final design
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 10 of 209
WALLS Office ▪ Low VOC content paint for gypsum board substrates, eggshell finish, minimum of two finish coats over primer
▪ Color per Commission specifications
Toilet Room ▪ Porcelain or ceramic wall tile to height of 4 feet with profile trim; tile to be selected by Commission
▪ Paint above tile with low VOC content paint for gypsum board substrates, eggshell finish, minimum of two finish coats over primer
▪ Color including accent paint or wallcovering, per Commission specifications
FLOOR / BASE Office ▪ Modular carpet tile
▪ Resilient base to be rubber, top set, 1/8” x 4”, with field formed external and internal corners – coved at hard floor finishes, straight at carpet floor finishes
▪ Stained and varnished wood base is optional if approved by Commission
Toilet Room ▪ Porcelain or ceramic floor tile, 12” x 12” or larger format, thin set, latex grout
▪ Matching porcelain or ceramic base; 4” minimum height
▪ Speaker telephone at conference table
▪ Dual monitor arm on the height adjustable table
▪ Laptop cable lock anchor
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Two (2) Guest chairs
▪ All files and storage shall be lockable
▪ Two (2) upholstered chairs and one (1) sofa
▪ Conference table with eight (8) chairs
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 11 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 2
One (1) upholstered sofa and two (2) upholstered chairs
Conference table with eight (8) chairs
Two (2) guest chairs
Desk, height adjustable return with dual monitor arm and credenza
Task chair
Bench and wardrobe cabinet Paper towel dispenser and waste receptacle
Automatic flush toilet, toilet tissue dispenser and toilet seat cover dispenser Grab Bars
Sink with automatic faucet and automatic soap dispenser
Shower stall with grab bars and frosted, tempered glass door
ROOM NAME: DIRECTOR OFFICE SQUARE FT: 275
SPACE TYPE: Type 3 OCCUPANTS: 8 maximum
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 12 of 209
Type 3 DIRECTOR OFFICE
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
HARDWARE Commercial grade hardware to match building standard style and finish. Final hardware to confirmed with Commission and meeting the following minimum requirements:
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
(coordinate system requirements with Commission)
▪ two coat hooks, one installed at standard height, one installed at accessible height
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
CEILING Tile
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
▪ USG Fineline Tegular or equal
▪ Minimum ¾” thick with white enameled metal grid to match building standard
ACCESSORIES N/A
ENVIRONMENTAL Separate zone (VAV with thermostat control), building standard distribution
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 13 of 209
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration
▪ Coordinate infrastructure and pathways with CFTC Information Technology requirements in
LIGHTING ▪ Building standard 24”x24” LED Dimmable lighting as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.) over desk area or alternate approved LED lighting to provide same foot-candles
▪ Dimmable LED downlights over conference area with supplementary LED wall wash lighting
WALLS ▪ Low VOC content paint for gypsum board substrates, eggshell finish, minimum of two finish coats over primer
▪ Color per Commission specifications
FLOOR / BASE ▪ Modular carpet tile
▪ Resilient base to be rubber, top set, 1/8” x 4”, with field formed external and internal corners
– coved at hard floor finishes, straight at carpet floor finishes
▪ Stained and varnished wood base is optional if approved by Commission
▪ Speaker telephone at conference table
▪ Dual monitor arm on the height adjustable table
▪ Laptop cable lock anchor
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Two (2) Guest chairs
▪ All files and storage shall be lockable
▪ Conference table with four (4) chairs
▪ Two (2) upholstered chairs with occasional table
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 14 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 3
Two (2) upholstered chairs with occasional table
Conference table with four (4) chairs
Two (2) guest chairs
Desk, height adjustable return with dual monitor arm and credenza Task chair
Television Monitor
LOCATION: ALL
ROOM NAME: SUPERVISORY OFFICE CT 16 - 17 SQUARE FT: 150
SPACE TYPE: Type 4 OCCUPANTS: 5 maximum
ADJACENCIES:
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 15 of 209
Type 4 SUPERVISORY OFFICE
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ENVIRONMENTAL Code required, building standard distribution
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 16 of 209 plug configuration
LIGHTING Building standard (LED preferred) lighting as required to meet a minimum of 40 foot-candles at
30” Above Finished Floor (A.F.F.)
Match building standard color temperature
- coved at hard floor finishes, straight at carpet floor finishes
▪ Speaker telephone at conference table
▪ Desk and return, wood laminate finish, return to be height adjustable
▪ Dual monitor arm on the height adjustable table
▪ Laptop cable lock anchor
▪ Metal lockable lateral file & shelf combo located at the front of the desk
▪ Metal lockable, movable box / file
▪ All files to be lockable
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Desk top power / USB charging module
▪ Four (4) guest chairs
▪ One (1) 36” diameter meeting table (wood laminate finish)
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 17 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 4
Two (2) guest chairs with occasional table
Two (2) guest chairs
Desk, height adjustable return with dual monitor arm
Task chair
Bookcase File
Cabinet combination unit
Television
Monitor
ROOM NAME: SUPERVISORY OFFICE CT 15 and below SQUARE FT: 120 SPACE TYPE: Type 5 OCCUPANTS: 1 each
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 18 of 209
Type 5 SUPERVISORY OFFICE
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
PLUMBING N/A
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 19 of 209 plug configuration
LIGHTING ▪ Building standard (LED preferred) lighting as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.)
▪ Dual monitor arm on the height adjustable table and
▪ Laptop cable lock anchor
▪ Metal lockable lateral file & shelf combo located at the front of the desk
▪ Metal lockable, movable box / file
▪ All files to be lockable
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Desk top power / USB charging module
▪ Two (2) guest chairs
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 20 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 5
Two (2) guest chairs
Desk, height adjustable return with dual monitor arm Task chair
Bookcase File
Cabinet combination unit
ROOM NAME: NON-SUPERVISORY OFFICE CT 9 - 18 SQUARE FT: 100
SPACE TYPE: Type 6 OCCUPANTS: 1 each
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 21 of 209
Type 6 NON-SUPERVISORY OFFICE
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 22 of 209 plug configuration
LIGHTING ▪ Building standard (LED preferred) lighting as required to meet a minimum of 40 foot-candles
▪ PC or docking station, flat screen monitor(s) and telephone handset
▪ Dual monitor arm on the height adjustable table and
▪ Laptop cable lock anchor
▪ Metal lockable lateral file & shelf combo located at the front of the desk
▪ Metal lockable, movable box / file
▪ All files to be lockable
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ One (1) guest chair
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 23 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 6
One (1) guest chair
Desk, height adjustable return with dual monitor arm Task chair
Bookcase File
LOCATION ALL
ROOM NAME: WORKSTATION SQUARE FT: 48
SPACE TYPE: Type 7 OCCUPANTS: 1 each
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 24 of 209
Type 7 WORKSTATION
DOORS / FRAMES N/A
HARDWARE N/A
WALLS N/A
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ELECTRICAL ▪ Systems Furniture to be powered by hard wire connection to panels in a circuit configuration requirement to be provide by Systems Furniture manufacturer.
▪ Outlets mounted in Systems Furniture to be furnished and installed by Systems Furniture installer.
▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, mounted at standard height unless otherwise noted on drawings
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration
LIGHTING ▪ Building standard (LED preferred) lighting as required to meet a minimum of 40 foot-candles
WALLS N/A
LOCATION ALL
ROOM NAME: WORKSTATION SQUARE FT: 48
SPACE TYPE: Type 7 OCCUPANTS: 1 each
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 25 of 209
▪ Solid color systems furniture with low panels & height adjustable desk
▪ Dual monitor arm on the height adjustable table
▪ Laptop cable lock anchor
▪ Desk top power / USB charging module
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ Narrow Wardrobe (Approximately 9” wide), (Height range: 48” – 54”)
▪ Metal Storage and lockable files as the space allows
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 7
Desk, height adjustable return with dual monitor arm
Task chair
Locker, Bookcase
& File Cabinet
ROOM NAME: VISITOR’S OFFICE SQUARE FT: 100
SPACE TYPE: Type 8 OCCUPANTS: 1 each ADJACENCIES: Main Entrance
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 26 of 209
Type 8 VISITOR’S OFFICE
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height. Brace partition to structure above with black iron or misc.
metal at 4’-0” O.C.
▪ Provide sound attenuating batt insulation between studs.
▪ Sound Transmission Class (STC) rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
▪ Office front walls to be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 27 of 209 plug configuration
LIGHTING ▪ Building standard (LED preferred) lighting as required to meet a minimum of 40 foot-candles
▪ Dual monitor arm on the height adjustable table and
▪ Laptop cable lock anchor
▪ Metal lockable lateral file & shelf combo located at the front of the desk
▪ Metal lockable, movable box / file
▪ All files to be lockable
▪ Task chair (ergonomic with adjustable arms & seat height, mesh back and seat)
▪ One (1) guest chair
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 28 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 8
One (1) guest chair
Desk, height adjustable return with dual monitor arm Task chair
Bookcase File
ROOM NAME: CONFERENCE ROOM SQUARE FT: 500
SPACE TYPE: Type 9 OCCUPANTS: 14 - 20 ADJACENCIES: Reception, Working Zone
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 29 of 209
Type 9 CONFERENCE ROOM
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ provide automatic door bottom and perimeter gasketing as necessary to achieve STC rating
WALLS ▪ Partitioning shall be one layer of ⅝” gypsum board full height to slab above on each side of
2 ½”, 25-gauge (or equivalent) metal studs at 24” O.C.
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height.
▪ Provide sound attenuating batt insulation between studs
▪ STC rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ENVIRONMENTAL Separate zone and controls (separate VAV and thermostat) with code-required ventilation and building distribution designed for occupant load
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout,
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration
▪ Coordinate floor outlet locations with furniture and connect to tabletop as required. Quantity located in table to be confirmed by Commission
▪ Coordinate infrastructure and pathways with CFTC audiovisual requirements, wiring and connections per Commission specifications in APPENDIX 1
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 30 of 209
LIGHTING ▪ Building standard (LED preferred) dimmable lighting or alternate downlights as required to meet a minimum of 40 foot-candles at 30” Above Finished Floor (A.F.F.)
▪ All lighting shall be dimmable to 1% with a simple control
COMMUNICATION Refer to IT requirements chart; APPENDIX 1
Engineer in the final design
▪ For floor receptacles one receptacle is required for every 215 square feet of floor space in meeting rooms that are at least 12 feet wide
▪ Coordinate floor outlet locations with furniture and connect to tabletop module if required.
Verify requirements at each location
▪ Area shall be equipped with sound masking system
▪ Color including accent paint, and one wall of wallcovering, per Commission specifications
▪ Conference telephone handset
▪ Three (3) wall mounted flat screen monitors (controlled from table), provide blocking as necessary
▪ Video conference equipment
▪ One (1) wood laminate conference table sized to fit the dimensions and configuration of the room (power and data outlets mounted on the table shall be non-obtrusive)
▪ White board
▪ Minimum sixteen (16) ergonomic chairs (with fixed arms & height adjustable seat, mesh back and upholstered seat)
▪ Credenza with 30" depth to store IT / AV equipment adequately (with exhaust fan or vent if required) and top surface for serving
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 31 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 9
Credenza
Television Monitors Conference
Room Chairs
Marker Board
Table Top Outlets
Television Monitor
Room Scheduler Conference
Table
ROOM NAME: CHAIRMAN’S CONFERENCE ROOM SQUARE FT: 500
SPACE TYPE: Type 9A OCCUPANTS: 14 - 20 ADJACENCIES: Leadership Reception Area, Chairman and Commissioner Offices
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 32 of 209
Type 9A CHAIRMAN’S CONFERENCE ROOM
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height.
▪ Provide sound attenuating batt insulation between studs
▪ STC rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ENVIRONMENTAL Separate zone and controls (separate VAV and thermostat) with code-required ventilation and
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout,
▪ Outlets to be commercial grade, 20Amp, 125Volt, 2 Pole, 3 Wire Grounding, NEMA 5-20R plug configuration
▪ Coordinate floor outlet locations with furniture and connect to tabletop as required. Quantity located in table to be confirmed by Commission
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 33 of 209
LIGHTING ▪ Building standard (LED preferred) dimmable lighting or alternate downlights as required to
Engineer in the final design
▪ For floor receptacles one receptacle is required for every 215 square feet of floor space in meeting rooms that are at least 12 feet wide
▪ Coordinate floor outlet locations with furniture and connect to tabletop module if required.
Verify requirements at each location
▪ Area shall be equipped with sound masking system
▪ Public Broadcasts and Webcasting Events: the space must accommodate in room participation as well as broadcast capabilities for both in house webcasting services and public broadcasting
▪ Conference telephone handset
▪ Three (3) wall mounted flat screen monitors (controlled from Secretariat Technical Table), provide blocking as necessary
▪ Video conference equipment
▪ Secretariat Technical Table with controls for A/V systems
▪ One (1) wood laminate conference table sized to fit the dimensions and configuration of the room (power and data outlets mounted on the table shall be non-obtrusive)
▪ White board
▪ Minimum sixteen (16) ergonomic chairs (with fixed arms & height adjustable seat, mesh back and upholstered seat)
▪ Credenza with 30" depth to store IT / AV equipment adequately (with exhaust fan or vent if required) and top surface for serving
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 34 of 209
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
Sketches are for illustration purposes only and are not drawn to scale. They do not represent final configurations.
END OF SPACE Type 9A
Television Monitors
Conference Room Chairs
Marker Board
Table Top Outlets
Television Monitor
Room Scheduler
Conference Table
Audio Visual Equipment
Racks
Secretariat Technical
Table
LOCATION: HQ and Kansas City
ROOM NAME: TRAINING ROOM SQUARE FT: 500
SPACE TYPE: Type 10 OCCUPANTS: 30 maximum ADJACENCIES: Entrance, Reception
REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 35 of 209
Type 10 TRAINING ROOM
DOORS / FRAMES ▪ Full height, single leaf, solid core, 36” wide, building standard wood door, stained and
▪ Manufacturer’s standard aluminum horizontal and vertical framing members for type system
▪ heavyweight minimum 1 ½ pair butt hinges of quantities recommended by manufacturer for size and weight of door
▪ doorstop; commercial grade
▪ mortise lockset style, office function lockset with interior push button and exterior key core, keyed to CFTC master, lever handles, electric lock controlled by a remote card reader
▪ Adjust stud gauge, spacing and width to meet minimum deflection requirements in spaces with ceilings over 14’-0” in height.
▪ Provide sound attenuating batt insulation between studs
▪ STC rating of 50 is required, Architect of Record to design or modify wall composition as necessary to meet
▪ Manufacturer’s standard anchors, seals and miscellaneous trim necessary to complete all work and achieve the specified acoustical performance
If Applicable
▪ One wall may be full-height, interior, unitized, double-glazed movable glass as shown and specified
▪ For side light windows and frames, recommended manufacturer Infinium Wall Systems
Refine Series or equal
▪ Insert material to be ¼” clear, tempered glass, verify the extent of glass with Commission
▪ Light Reflectance Coefficient: 0.90
▪ Noise Reduction Coefficient: 0.75
▪ Ceiling Attenuation Coefficient: 3
Grid
ENVIRONMENTAL Separate zone and controls (separate VAV and thermostat) with code-required ventilation and
ELECTRICAL ▪ Power outlets, whether wall or floor mounted, should be placed according to space layout, REQUIREMENTS for: U.S. Commodity Futures Trading Commission (CFTC) Page 36 of 209 plug configuration
▪ Coordinate floor outlet locations with furniture and connect to tabletop as required. Quantity located in table to be confirmed by Commission
▪ Coordinate infrastructure and pathways with CFTC audiovisual requirements, wiring and
▪ Coordinate with Commission requirements for lectern
LIGHTING ▪ Building standard (LED preferred) dimmable lighting or alternate downlights as required to
Engineer in the final design
▪ Coordinate floor outlet locations with furniture and connect to tabletop module if required.
Verify requirements at each location
▪ Area shall be equipped with sound masking system
▪ Specialized Network availability to be provided (Separated from working zone network system)
▪ Conference telephone handset and video tele-conference equipment
▪ Two (2) wall mounted flat screen monitors (control from table), provide…