SPECIFICATIONS
CUMMINS 275KW TRAILER MOUNTED DIESEL GENERATOR,
PART NO. C275D2RE (BRAND NAME OR EQUAL TO)
ENGINE
· Cummins (or approved equal) QSL9-G9 - turbocharged, diesel engine
· Alternator HCI434E (208/240/480) (or approved equal)
· Battery Capacity 2 X 760 cca
· 70 amps battery charging alternator
· 6 cylinder in-line, cast iron
· 8.9 L displacement
· Interim Tier IV approved
· 24 Volt, negative ground starting voltage
· Direct Injection HPCR fuel system
· Spin on fuel filter with water separator
· 2-stage, dry replaceable element with dust ejector air cleaner
· Single spin-on, full flow lube oil filter
· Standard cooling system, 122 deg F ambient radiator
ALTERNATOR
· Brushless, 4-pole, drip proof, revolving field
· Single bearing, flexible disc rotor
· Class H per NEMA MG1-1.65 (208/240/480 VAC) insulation system
· Permanent Magnet Generator (PMG) exciter
· Alternator Cooling - Direct drive centrifugal blower fan
CONTROL SYSTEM
· Power Command 3.3 (or approved equal)
· Simplified display for Rental operators - simplified display tailored for Rental equipment operations for ease of use
· Masterless Load Demand (MLD) - The controller is capable of smartly managing power from paralleled generators to match varying load patterns.
· Power management - Control function provides battery monitoring and testing features and smart starting control system.
· Advanced control methodology - Three phase sensing, full wave rectified voltage regulation, with a PWM output for stable operation with all load types.
· Regulation compliant - Prototype tested: UL, CSA and CE compliant.
· Service - InPower™ PC-based service tool available for detailed diagnostics, setup, data logging and fault simulation
· Easily upgradeable - PowerCommand controls are designed with common control interfaces
· Reliable design - The control system is designed for reliable operation in harsh environment.
· Operator Panel Features
· Operator/display functions
· Displays paralleling breaker status
· Provides direct control of the paralleling breaker
· 320 x 240 pixels graphic LED backlight LCD
· Auto, manual, start, stop, fault reset and lamp test/panel lamp switches
· Alpha-numeric display with pushbuttons
· Heated HMI
· LED lamps indicating genset running, remote start, not in auto, common shutdown, common warning, manual run mode, auto mode and stop
· Paralleling Control Functions
· First Start Sensor System selects first genset to close to bus
· Phase lock loop synchronizer with voltage matching
· Sync check relay
· Isochronous KW and kVAR load sharing
· Enhanced Safety Features for paralleling generators
· Alternator Data
· Line to Neutral and Line to Line AC volts
· 3 phase AC current
· Frequency
· kW,kVar, power factor kVA (three phase and total)
· Engine Data
· DC Voltage
· Lube Oil Pressure
· Coolant Temperature
· Comprehensive FAE data (where applicable)
· Other Data
· Fault History
· Data logging and fault simulation (requires InPower)
· Standard Control Functions
· Digital Voltage Regulation
· Integrated digital electronic voltage regulator
· 3 phase, 4 wire line to line sensing
· Configurable torque matching
· Digital Governing
· Integrated digital electronic isochronous governor
· Temperature dynamic governing
· AmpSentry AC Protection
· AmpSentry protective relay
· Over current and short circuit shutdown
· Over current warning
· Single and three phase fault regulation
· Over and under voltage shutdown
· Over and under frequency shutdown
· Overload warning with alarm contact
· Reverse power and reverse VAR shutdown
· Field overload shutdown
· Engine Protection
· Battery voltage monitoring, protection and testing
· Overspeed shutdown
· Low oil pressure warning and shutdown
· High coolant temperature warning and shutdown
· Low coolant level warning or shutdown
· Low coolant temperature warning
· Fail to start (overcrank) shutdown
· Fail to crank shutdown
· Cranking lockout
· Sensor failure indication
· Full authority electronic engine protection
· Control Functions
· Time delay start and cool down
· Real time clock for fault and event time stamping
· Cycle cranking
· Load shed
· Remote emergency stop
ENCLOSURE
· Camlock distribution panel
· Sound attenuated, white powder coated lockable enclosure
· 24 hour fuel tank (75% prime) with gauge
· Roof mounted, single point lift
· Cooling system rated for 122 deg. F at 100% standby ambient
· Complete engine fluid containment reservoir
· 4 position voltage selector switch
· Shore power (15A/120V) for coolant heater and battery charger
· Conveniently located analog gauges and heated Human Machine Interface display
TRAILER
· DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch.
· ST235/85R16 radial tires, a total of 6 tires, lug pattern 8 x 6.5
WEIGHTS & DIMENSIONS
Trailer mounted
· Dry weight: 13,285 lbs
· Operating weight: 16,140 lbs
· 241 x 84 x 115 in
WARRANTY
· Genset Warranty – Industrial Mobile Base, Prime 3 years / 3000 hours