Text version

SPECIFICATIONS

CUMMINS 275KW TRAILER MOUNTED DIESEL GENERATOR,

PART NO. C275D2RE (BRAND NAME OR EQUAL TO)

ENGINE

· Cummins (or approved equal) QSL9-G9 - turbocharged, diesel engine

· Alternator HCI434E (208/240/480) (or approved equal)

· Battery Capacity 2 X 760 cca

· 70 amps battery charging alternator

· 6 cylinder in-line, cast iron

· 8.9 L displacement

· Interim Tier IV approved

· 24 Volt, negative ground starting voltage

· Direct Injection HPCR fuel system

· Spin on fuel filter with water separator

· 2-stage, dry replaceable element with dust ejector air cleaner

· Single spin-on, full flow lube oil filter

· Standard cooling system, 122 deg F ambient radiator

ALTERNATOR

· Brushless, 4-pole, drip proof, revolving field

· Single bearing, flexible disc rotor

· Class H per NEMA MG1-1.65 (208/240/480 VAC) insulation system

· Permanent Magnet Generator (PMG) exciter

· Alternator Cooling - Direct drive centrifugal blower fan

CONTROL SYSTEM

· Power Command 3.3 (or approved equal)

· Simplified display for Rental operators - simplified display tailored for Rental equipment operations for ease of use

· Masterless Load Demand (MLD) - The controller is capable of smartly managing power from paralleled generators to match varying load patterns.

· Power management - Control function provides battery monitoring and testing features and smart starting control system.

· Advanced control methodology - Three phase sensing, full wave rectified voltage regulation, with a PWM output for stable operation with all load types.

· Regulation compliant - Prototype tested: UL, CSA and CE compliant.

· Service - InPower™ PC-based service tool available for detailed diagnostics, setup, data logging and fault simulation

· Easily upgradeable - PowerCommand controls are designed with common control interfaces

· Reliable design - The control system is designed for reliable operation in harsh environment.

· Operator Panel Features

· Operator/display functions

· Displays paralleling breaker status

· Provides direct control of the paralleling breaker

· 320 x 240 pixels graphic LED backlight LCD

· Auto, manual, start, stop, fault reset and lamp test/panel lamp switches

· Alpha-numeric display with pushbuttons

· Heated HMI

· LED lamps indicating genset running, remote start, not in auto, common shutdown, common warning, manual run mode, auto mode and stop

· Paralleling Control Functions

· First Start Sensor System selects first genset to close to bus

· Phase lock loop synchronizer with voltage matching

· Sync check relay

· Isochronous KW and kVAR load sharing

· Enhanced Safety Features for paralleling generators

· Alternator Data

· Line to Neutral and Line to Line AC volts

· 3 phase AC current

· Frequency

· kW,kVar, power factor kVA (three phase and total)

· Engine Data

· DC Voltage

· Lube Oil Pressure

· Coolant Temperature

· Comprehensive FAE data (where applicable)

· Other Data

· Fault History

· Data logging and fault simulation (requires InPower)

· Standard Control Functions

· Digital Voltage Regulation

· Integrated digital electronic voltage regulator

· 3 phase, 4 wire line to line sensing

· Configurable torque matching

· Digital Governing

· Integrated digital electronic isochronous governor

· Temperature dynamic governing

· AmpSentry AC Protection

· AmpSentry protective relay

· Over current and short circuit shutdown

· Over current warning

· Single and three phase fault regulation

· Over and under voltage shutdown

· Over and under frequency shutdown

· Overload warning with alarm contact

· Reverse power and reverse VAR shutdown

· Field overload shutdown

· Engine Protection

· Battery voltage monitoring, protection and testing

· Overspeed shutdown

· Low oil pressure warning and shutdown

· High coolant temperature warning and shutdown

· Low coolant level warning or shutdown

· Low coolant temperature warning

· Fail to start (overcrank) shutdown

· Fail to crank shutdown

· Cranking lockout

· Sensor failure indication

· Full authority electronic engine protection

· Control Functions

· Time delay start and cool down

· Real time clock for fault and event time stamping

· Cycle cranking

· Load shed

· Remote emergency stop

ENCLOSURE

· Camlock distribution panel

· Sound attenuated, white powder coated lockable enclosure

· 24 hour fuel tank (75% prime) with gauge

· Roof mounted, single point lift

· Cooling system rated for 122 deg. F at 100% standby ambient

· Complete engine fluid containment reservoir

· 4 position voltage selector switch

· Shore power (15A/120V) for coolant heater and battery charger

· Conveniently located analog gauges and heated Human Machine Interface display

TRAILER

· DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch.

· ST235/85R16 radial tires, a total of 6 tires, lug pattern 8 x 6.5

WEIGHTS & DIMENSIONS

Trailer mounted

· Dry weight: 13,285 lbs

· Operating weight: 16,140 lbs

· 241 x 84 x 115 in

WARRANTY

· Genset Warranty – Industrial Mobile Base, Prime 3 years / 3000 hours