03_VGLZ232034_SelfridgeANG-MV-Termina_SW 1-2 to 1-3_Dwgs.pdf

PDF 1 MB Posted

Attached to
VGLZ232034 - Repair Electrical MV Terminations SW 1-2 to 1-3”
Solicitation number
W50S8523B0008
Issued by

View the file

Other files

File Type Posted
OF_1419 23B0008.pdf PDF
23B0008 Bid Opening Sign in Sheet.pdf PDF
OF_1419A23B0008.pdf PDF
Amendment 2 W50S8523B0008.pdf PDF
W50S8523B0008 Pre-Bid Conference_Site Visit.pdf PDF
Pre-Bid Conference sign in sheet.pdf PDF
Amendment 1 W50S8523B0008.pdf PDF
W50S8523B0008.pdf PDF
04_VGLZ_232034_Form_AF_66_3_14_23.xls XLS spreadsheet
02_General Contract Spec (1).pdf PDF
127 SFS Vetted Form.xlsx XLSX spreadsheet
Source ID Docs SANGB MI.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

1098710775C Line

0.1Test Frequency

NANO

FARADS

NANO

FARADS

SYSTEM VOLTAGE

TAN DELTA

R. DESJARDINS A. SHERWOODTested By:Tested By: 13090, REVISED 12/14/2021

TOOLS USED: VLF #UIS1444

PAGE

USER

Address

CUSTOMER

TAN DELTA CABLE TESTUtilities Instrumentation Service, Inc.

Dexter, Michigan

(734) 424-1200 Centerville, Ohio

(937) 439-9660

OWNER REPRESENTATIVE TELEPHONE

Selfridge Air National Guard Base; 43200 Maple Street; 127 MSC. Bldg 105; Selfridge ANG Base MI 48045 Scott Stawinski

40950 Woodward Ave; Suite 130; Bloomfield Hills MI 48304 CAVU/Roncelli

JOB # CAVR227900

DATE

SUBSTATION SWITCH 01-02 TO 01-03POSITION

12/11/2022 SWITCH 1-2

LOOP 1

35 °F EQPT. LOCATION%HUMIDITY 85TEMPERATURE

PHASE A, B, C

5kV

CABLE

15 kV

CABLE

---1.4

---7.0

4.2

2.8

TEST VOLTAGE

kV

DEFICIENCIES: THE RESULTS OF THE TAN DELTA TEST ARE OUTSIDE OF THE ACCEPTABLE RANGE FOR THIS CABLE ACCORDING TO IEEE 400.2 FOR

VLF TESTING. SEE RECOMMENDATION ON COVER LETTER AND IN FIELD SERVICE REPORT.

COMMENTS:

ACCEPTABLE NON - ACCEPTABLE ( THIS FORM IS NOT TO BE REPRODUCED EXCEPT IN FULL)

PHASE B

TAN DELTA

PHASE C

TAN DELTA

MICRO

AMPS

PHASE A OR

YES

0.7 188 330

0.7 188 165

1.7 188 495

8.3 188 827

9.2 188 165

17.0 188 331

40.6 188 497

54.2 188 829

0.7 187 165

0.7 187 329

0.8 187 494

0.9 187 827

NANO

FARADS

0.01

0.01 0.66

0.01 2.86

1.30 1.73

PHASE B

SINE Other

TEST TYPE

MICRO

AMPS

PHASE A

BREAKDOWN NO WAVE SHAPE

DIAGNOSTICPASS / FAIL

MICRO

AMPS

0.01

0.02

PHASE C

0.01

0.01

STANDARD

DEVIATION

kV kV kV kV

2.8

4.2

7.0

1.4 0.01

SIZE

MANUFACTURER

OPERATING VOLTAGE

INSULATION TYPE---

NO. OF CONDUCTORS---

--- INSULATION THICKNESS

CONDUCTOR MATERIAL

LENGTH

SWITCH 1-3CABLE SOURCE CABLE TERMINATION POINT SWITCH 1-2

kV FT °CCABLE TEMPERATURE 1.7

NONE Y NISOLATE CABLE

4.8 INSTALLED IN CONDUIT TRAY

CONNECTED EQUIPMENT

CU ALMCM

SHIELDED UNSHIELDED CONCENTRIC NEUTRAL AGEBELTED (PILC) ---

RATED VOLTAGE kV

NAMEPLATE DATA:

MILS

7.0

Hz kV