02 82 11.1 - Asbestos Report for Reference.pdf

PDF 3 MB Posted

Attached to
F999--NRM - CONST 528-811 | AIR MONITOR FOR CONSOLIDATE PRIMARY CARE PHASE 1
Solicitation number
36C24225Q0380
Issued by

About this file

This is an asbestos survey report from 2011 (updated with drawings in 2020) for Building 1 at the Albany VA Medical Center, performed by Mabbett & Associates. The report documents a comprehensive asbestos inspection of 11 buildings at the medical center, with 904 samples collected and analyzed. Eight of the surveyed buildings contained asbestos-containing materials (ACM), including approximately 173,663 square feet of asbestos flooring, 4,132 linear feet of pipe/fitting insulation, 290 square feet of caulking, and 432 square feet of boiler/tank/refrigeration insulation. The total estimated abatement liability was over $1.5M.

The report includes detailed sampling results, risk hazard categorizations (1-4 scale), floor plans showing ACM locations, and an Operations & Maintenance Plan. Some areas requiring immediate attention included 88 linear feet of damaged pipe insulation. The survey followed EPA AHERA protocols and New York State requirements, with samples analyzed by America Science, Inc. The report is structured in four volumes covering: Executive Summary & Introduction, Individual Building Reports, Supporting Documentation/Lab Results, and the O&M Plan. The included floor plans show locations of various ACM materials including floor tiles, pipe insulation, transite materials, and other building components containing asbestos.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VOLUME I

ASBESTOS SURVEY

EXECUTIVE SUMMARY & INTRODUCTION

WITH SUPPORTING DOCUMENTATION

VISN 2

Albany Medical Center

113 Holland Avenue Albany, NY 12208

Project No. 2010009.003

April 15, 2011

5 Alfred Circle Bedford, MA 01730-2318

Telephone: (781) 275-6050 Toll Free: (800) 877-6050 Facsimile: (781) 275-5651 info@mabbett.com www.mabbett.com

© 2011, Mabbett & Associates, Inc.

mailto:info@mabbett.com http://www.mabbett.com/ Shannon Text Box Summary and tables pertaining to Building 1 (report 2011 updated w/ drawings in 2020) Included for reference

©2011, Mabbett & Associates, Inc. ii VOLUME I Exec Summary and Intro 1 4-15-2011.doc.doc

ACKNOWLEDGMENT

This Asbestos Containing Materials (ACM) Building Survey Report was prepared for the Veterans Integrated Network System (VISN 2) in accordance with an established scope of work as defined in Contract Number VA528-P-0738. The information presented herein is based on the facts and information conveyed to or received by Mabbett & Associates, Inc.

(M&A) during the preparation of this report. If the information provided to M&A that was used in preparing this report is incorrect, incomplete, or subject to change, M&A would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to M&A as of the date of this report and considered applicable to this report.

This report was prepared by the following Mabbett & Associates, Inc. personnel:

MABBETT & ASSOCIATES, INC.

BY:

Michael F. Delaney Project Manager New York State Asbestos Building Inspector 02-16232 New York State Management Planner 02-16232

This report has been reviewed and approved by:

MABBETT & ASSOCIATES, INC.

Robert K. McKinley, MPH, CIH, LIH Director of Industrial Hygiene Services

©2011, Mabbett & Associates, Inc. iii VOLUME I Exec Summary and Intro 1 4-15-2011.doc

REPORT TABLE OF CONTENTS

Volume I - General

Chapter 1 - Executive Summary and Introduction with Supporting Documentation Chapter 2 - Summary of ACM Building Results Tables

Volume II – Individual Building Reports

Individual Building Report Chapters including:

• Introduction and Executive Summary

• Building Description Summary

• Asbestos Survey Methodology

• Relevant Asbestos Findings for the Building

(Including Summary Tables and Floor Plans Identifying ACM Locations)

Volume III – Appendices and Supporting Data

Appendix A - Asbestos Laboratory Analysis Reports and Laboratory Certifications Appendix B - Personnel Certifications & Licenses

Volume IV – Asbestos Operations & Maintenance (O&M) Plan

Asbestos Operations & Maintenance (O&M) Plan Master Positive Table and Quantification and Liability Tables

©2011, Mabbett & Associates, Inc. iv VOLUME I Exec Summary and Intro 1 4-15-2011.doc

TABLE OF CONTENTS

CHAPTER 1

Description Page

EXECUTIVE SUMMARY

INTRODUCTION AND SUMMARY

Introduction Purpose Summary of Findings Abatement Action Recommendations Asbestos Survey Methodology Summary Previous Report Summary O&M Plan Quarterly Liability Report Conclusions and Limitations

LIST OF TABLES

Table 1 List of Surveyed Buildings Table 2 List of Building Not Surveyed Table 3 Buildings Surveyed Where ACM was Not Identified Table 4 Buildings Surveyed Where ACM was identified Table 5 Summary of Damaged ACM Table 6 Previous Report Summary Table 7 VAMC Summary for Liability Report

ATTACHMENTS

Appendix A Supporting Documentation

CHAPTER 2

Description Page

SUMMARY OF RESULTS TABLE

CHAPTER 1

EXECUTIVE SUMMARY & INTRODUCTION

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 1 of 8 VOLUME I Exec Summary and Intro 1 4-15-2011.doc

EXECUTIVE SUMMARY

Mabbett and Associates, Inc. (M&A) performed the following at Albany VAMC in accordance with the VISN 2 scope of work:

• Completed comprehensive asbestos inspections by New York State licensed asbestos inspectors in accessible areas of 11 buildings.

• Performed labeling of asbestos containing thermal system insulation such as piping and boiler insulation and provided CADD plans showing asbestos locations for posting and notification purposes by the VAMC.

• Prepared building reports with results, tables, and CADD building plans showing asbestos locations.

• Prepared an Asbestos Operations & Maintenance Plan in accordance with the August 2010 VHA Asbestos Management Directive.

Visual inspections and sampling were performed in general accordance with U.S.

Environmental Protection Agency (EPA) Asbestos Hazard and Emergency Response Act (AHERA) protocols. This report is not intended to be used to generate bid documents, specifications, etc. for asbestos abatement projects or renovation or demolition projects.

Significant findings from the asbestos inspections included:

• A total of 904 samples were collected for asbestos analysis. Materials sampled included floor tiles, mastics, ceiling tiles, thermal insulation, caulking, and other miscellaneous suspect asbestos containing materials.

• 8 of the 11 buildings surveyed had asbestos containing materials. (See Table 4)

• Approximately 88 linear feet of pipe insulation containing asbestos was identified which is in need of repair or abatement by properly trained/licensed contractors in the near term if not already corrected due to damaged condition. (See Table 5)

• The total estimated current liability if the VAMC was to abate all the asbestos containing materials identified is over $1.5M. The VAMC is required to report the asbestos liability estimate quarterly. (See Table 7)

This asbestos assessment report consisting of four volumes is considered a living document that will require on-going, periodic revisions and updates to ensure accuracy as the status of the asbestos and building conditions change over time.

The assessment should serve as a cornerstone for a facility asbestos program that should be carefully maintained to comply with Federal Regulations, protect human health and serve as a useful tool when evaluating planned or unplanned building material disturbance.

Implementation and effective on-going management of the asbestos program requires a team approach and involvement from senior management, Safety, Engineering, Facilities, Housekeeping and others. It is recommended that Medical Center Directors assign qualified individuals, including Asbestos Program Managers, to coordinate and oversee asbestos impacting activities to ensure effective management of on-going revisions of this facility asbestos survey, asbestos removal and maintenance activities.

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 2 of 8

INTRODUCTION AND SUMMARY

Introduction

Mabbett and Associates, Inc. (M&A), performed surveys for suspect asbestos containing building materials (ACBM) at the Albany VA Medical Center (VAMC) located at 113 Holland Avenue in Albany, New York, under Contract VA528-P-0738 as part of a VISN 2 wide asbestos inspection program. Site survey work was performed during September 2010, by appropriately credentialed personnel. A list of buildings provided by the VAMC and surveyed is in Table 1.

Any building not surveyed and the reason is listed in Table 2.

Table 1- List of Surveyed Buildings - Albany, VAMC

Bldg No Function Title Year Built No. of Floors

Estimated Gross Square

Footage (ft2) 1 Main Hosp. 1947 14 715,000 2 Utilities Wing 1947 2 12,283 3 Animal Research 1947 3 33,385 4 Boiler Plant 1947 1 11,680 5 Adult Daycare 1951 3 7,806

14 Generator Room 1960 1 1,418 25 Maintenance Garage 1981 1 4,828 26 Radiation Therapy 1983 2 10,115 51 EMS Trailer 1991 1 2,739 54 Chiller Plant 1987 1 6,625 56 Fisher House 1994 2 5,120

Table 2 - List of Buildings Not Surveyed – Albany, VAMC

Bldg.

No. Function Title Year

Built Total Gross

Square Footage (ft2)

Reason for not screening or surveying

60 Projects Trailer 2009 3,749 Deleted from scope due to age.

61 Salt Storage Shed 2009 600 Deleted from scope due to age.

62 Warehouse Storage 2009 2,780 Deleted from scope due to age.

67 New VISN Bldg 2010 37,592 Deleted from scope due to age.

In addition to performing the initial asbestos inspection survey, identified thermal system insulation (i.e. pipe insulation and boiler insulation containing asbestos) was subsequently labeled as part of the project. Building plans showing locations of identified ACM were also prepared and provided for posting by VAMC to meet employee notification requirements. The project also included the preparation of an asbestos O&M Plan prepared by a state licensed asbestos management planner which is available in Volume IV.

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 3 of 8

This comprehensive report, including individual Building Reports (Volume II), is the product of the M&A’s effort. The Report consists of four volumes: Volume I – Executive Summary & Introduction; Volume II - Individual Building Reports, containing floor plans indicating ACM sample locations with findings information, and survey findings for the specific surveyed building;

Volume III – Appendices/Supporting Data, including laboratory results and certifications; and Volume IV - the ACM O&M Plan.

Purpose

Visual inspections and sampling were performed in general accordance with US Environmental Protection Agency (EPA) Asbestos Hazard and Emergency Response Act (AHERA) protocols. The purpose of this AHERA type asbestos inspection survey was to identify asbestos containing materials in areas that were accessible to the survey team. This inspection report and associated individual building reports are not intended to be used to generate bid documents, specifications, etc. for asbestos abatement project or renovation or demolition projects since samples were not collected behind walls, above hard ceilings, etc. and therefore additional sampling of suspected ACM in locations scheduled for demolition/ renovation may be required.

Summary of Findings

A total of 904 samples were collected for analysis. Materials sampled included floor tiles, mastics, ceiling tiles, thermal insulation, caulking, and other miscellaneous suspect ACM. Of the buildings surveyed for ACM, the buildings listed in Table 3 had no ACM identified based on the results of the surveys of accessible locations and analytical results for samples collected which were all reported by the laboratory as “No Asbestos Detected” (NAD) for these buildings.

See individual building reports for specific sample locations, building drawings, and results or Volume I – Chapter 2 for a table of all samples collected during this survey and any presumed ACM (PACM). PACM’s are materials identified as ACM in previous surveys or VISN 2 directed assumed materials which include original TSI in older buildings and 9”x9” floor tile and mastics.

A summary of all positive ACM and PACM identified during this survey is provided in the Volume IV:

Table 3 - Buildings Surveyed Where ACM was Not Identified

Albany, VAMC 51 54

The buildings listed in Table 4 below had ACM identified during the survey based on the analytical results provided by the laboratory. See individual building reports for specific sample locations, building drawings, and results:

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 4 of 8

Table 4 - Buildings Surveyed Where

ACM was Identified Albany, VAMC

1 5 2 14 3 25 4 26

Abatement Action Recommendations

Based on the visual observations of this survey, the items listed in Table 5 were identified to VAMC staff as posing a potentially serious condition and required immediate abatement or other corrective action to reduce the risk. The materials were assigned a Risk Hazard Category 1 rating:

Table 5 Summary of Damaged Friable Asbestos Containing Materials Albany, VAMC

Bldg.

No. Floor Wing

ACM

Sample

No.

ACM

Locations Description of Material

Percent and Type of

Asbestos Estimated Quantity Condition

VISN 2

Risk

Hazard Category

1-4*

1 11 B 8A

Exterior Firebox, SW4 Pipe Chase

Pipe Insulation

57.1% Chrysotile NA 25 LF Damaged 1

1 11 B 23A Exterior Firebox

Canvas Pipe Wrap

66.7% Chrysotile NA 11 LF Damaged 1

1 11 C 8A

SW9 Pipe Chase, Exterior Firebox

Pipe Insulation

57.1% Chrysotile NA 22 LF Damaged 1

1 11 C 23A Exterior Firebox

Canvas Pipe Wrap

66.7% Chrysotile NA 10 LF Damaged 1

1 12 Core 5B Stairwell Pipe Fitting 36.4% Chrysotile NA 4 LF Damaged 1

1 12 Core 8A Stairwell Pipe Insulation

57.1% Chrysotile NA 6 LF Damaged 1

3 1 NA 42A U21B 6” Pipe Fitting

50% Chrysotile NA 10 LF Damaged 1

Footnotes:

SF – Square Feet LF – Linear Feet CF– Cubic Feet

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 5 of 8

All identified ACM was assigned a risk hazard category ranging from 1 (worst) to 4 (best). The ratings takes into account: condition, friable vs. non-friable, accessibility, occupancy (e.g.

continuous, intermittent or occasional and patients/staff/visitors), potential for air erosion, potential for vibration damage, potential for disturbance/damage (e.g. exposed and in an accessible location), and potential for water damage. Individual building reports and Volume 1

– Chapter 2 includes all of the associated risk hazard category ratings based on the following criteria:

Category 1: represents significantly damaged friable ACM in locations with moderate to high occupancy by staff and/or patients. A significantly damaged condition is a condition with damage greater than or equal to 10% of the total surface area or 25% localized damage. Category 1 ACM should be abated or repaired as soon as possible to minimize any potential hazards posed by the asbestos.

Category 2: represents significantly damaged or damaged friable ACM in locations not frequently occupied. Category 2 ACM should be abated or repaired as soon as possible to minimize any potential hazards posed by the asbestos.

Category 3: represents ACM in at least good condition (friable or non-friable ACM that could become friable). A good condition is a condition with damage less than or equal to 1% of its total area or less than or equal to 1% localized damage. Category 3 should be visually surveyed semi-annually as part of the routine O&M program and should be considered for abatement or corrective action if conditions deteriorate or circumstances allow.

Category 4: represents non-friable ACM in good or excellent condition but should be regularly inspected as part of the O&M Plan.

Asbestos Survey Methodology Summary

A visual inspection was conducted by New York State Licensed Asbestos Inspectors to determine the locations of suspect building materials in the buildings listed in Table 1.

Sampling and inspections were performed in general accordance with AHERA protocols. Only areas that were accessible during the field work phase were surveyed. Areas which were inaccessible were identified in the individual building reports. Suspect ACM material that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, that was not sampled should be assumed to contain asbestos if discovered during any renovation process or until otherwise verified. To avoid impacting any existing roof warranties, no destructive sampling of roofing materials was included in this survey, and suspect roofing material should be assumed to be ACM until sample results prove otherwise.

The bulk samples collected as part of this effort were submitted under chain of custody procedures to America Science, Inc. (Amerisci) of New York, NY for polarized light microscopy (PLM) and transmission electron microscopy (TEM) analysis as required by the New York State Environmental Laboratory Approval Program (ELAP). PLM analysis of friable materials was performed using NYS ELAP Method 198.1. Samples of Non-friable Organically Bound (NOB) materials were analyzed by PLM (NYS ELAP Method 198.6) subsequent to matrix

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 6 of 8 reduction. NOB samples that were identified as non-ACM by PLM methods were re-analyzed by TEM (NYS ELAP Method 198.4) for confirmation purposes.

The PLM analytical protocol requires each layer of the sample to be analyzed separately. The quantity of analyses will vary based on the number of layers in a sample and whether a "positive stop" is employed. A positive stop (PS) is used when one sample of a homogeneous area is positive, the remainder of the samples were not be analyzed because the entire homogeneous area is considered positive as indicated on the results tables and drawings.

Amerisci is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program (NVLAP Lab Code 200546-0).

Copies of the laboratory accreditations are included in Volume III of the Comprehensive VAMC Asbestos Survey Report.

Previous Report Summary

The VAMC was asked to provide previous asbestos survey reports/laboratory results (Table 6). If provided, M&A reviewed reports during the survey, and used the information to identify locations where ACM materials were previously noted. By building upon the existing information, M&A attempted to improve the total number of samples collected.

Table 6 - Previous Report Summary Albany, VA Medical Center

Building Date Firm Title

4 May-10 Albany VA Medical Center

In-House Asbestos Survey Summary, No Formal Title was Provided

Supporting documentation is provided in Appendix A.

O&M Plan

The Asbestos O&M Plan prepared by a New York State Licensed Asbestos Management Planner found in Volume IV of the Project Report satisfies the Occupational Safety and Health Administration (OSHA) and VHA Asbestos Management Program Directive compliance requirements for employee safety and for management of asbestos identified at the facility. This O&M Plan contains the asbestos survey results, background information on asbestos, an introduction to the O&M program, information on implementing the O&M program, O&M work practices, O&M incident and emergency work practices, and O&M surveillance and documentation practices.

During preparation for renovation activities, the VAMC should review the Asbestos O&M Plan and specific building reports to determine if asbestos-containing materials may potentially be disturbed by the proposed renovations. The VAMC should also assume materials not previously sampled due to inaccessibility and which will be impacted by renovation activities to be ACM unless otherwise determined. If ACM must be abated as a part of the renovations, ACMs must be removed by a New York State Licensed Asbestos Abatement Contractor and proper notification to the New York State, Department of Labor, Asbestos Bureau must be

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 7 of 8 made as required.

If any ACM is damaged or becomes damaged it should be repaired, if possible, or removed entirely. Materials classified with a high potential for disturbance (Category 1 and 2) should be removed or repaired immediately upon discovering damage to the material especially when located in occupied areas. Additional information regarding the O&M program for in-place ACM is available in Volume IV – O&M Plan.

Quarterly Liability Report

The VAMC must submit a quarterly ACM liability report. At the time of the survey, identified quantities of ACM were estimated/quantified and cost estimates for abatement were developed.

Identified ACM should be included and accounted for in the liability report until removed from the building. As outlined in the O&M Plan as abatements occur or other changes to the amount or condition of ACM are identified, the liability tables and associated building reports and CADD plans should be updated to reflect the current conditions and available information including current abatement market rates. Table 7 is a consolidated summary of the estimated liability for the VAMC based on identified ACM at the time of the survey. The estimated liability table by building and ACM type can be found in the Volume IV – O&M Plan Appendix F.

Table 7 – VAMC Summary for Liability Report Albany VA Medical Center

General Description of Material Estimated Quantity

Estimated Remediation

Costs

Asbestos Flooring 173,663 SF $1,302,473 Pipe/Fitting Insulation 4,132 LF $206,600.00

Caulking 290 SF $2,900.00 Boiler/Tank/Refrigeration

Insulation 432 SF $15,120.00

Walls & Ceilings 0 SF $0.00 Total $1,527,093 LF – Linear Feet SF – Square Feet

Notes: Miscellaneous materials identified which do not fall into one of the categories above are not included in the liability estimate. Any ACM not accessible to the survey teams is not included since it could not be quantified. The estimated abatement and disposal unit costs provided are based on RS Means Building Construction Cost Data 2010 and other current industry unit rate estimates provided by abatement contractors and are intended to be inclusive of all abatement contractor costs. They do not include costs for design, monitoring, sampling, and other consultant fees.

© 2011, Mabbett & Associates, Inc. Vol I, Chapter 1 – Page 8 of 8

Conclusions and Limitations

M&A greatly appreciates all of the support provided by the VAMC to complete this survey and the opportunity to support Albany’s Asbestos Management Program. Based on the information provided in this complete report and consistent with the VHA directive and other regulatory requirements the VAMC should continue to implement an asbestos management program for the protection of employees, patients and visitors. Most importantly ACM which is damaged and poses a risk should be addressed as soon as possible to minimize the risk.

Implementation and effective on-going management of the asbestos program requires a team approach and involvement from senior management, Safety, Engineering, Facilities, Housekeeping and others. It is recommended that Medical Center Directors assign qualified individuals, including Asbestos Program Managers, to coordinate and oversee asbestos impacting activities to ensure effective management of on-going revisions of this facility asbestos survey, asbestos removal and maintenance activities.

Information in the project documentation provided relating to ACM and conditions although believed to be inclusive and accurate, was based on limited assessments and representative field sampling. Limiting conditions included limited sampling and inaccessible areas such as between walls and floors of the structures as indicated in this report.

APPENDIX A

SUPPORTING DOCUMENTATION

CHAPTER 2

Summary of Results Tables

PLM TEM Amount Units

1 1A 14 Duct 8 Duct Sealant (White) NAD NAD - - - -

1 1B 14 Duct 8 Duct Sealant (White) NAD NAD - - - -

1 1C 14 Duct 8 Duct Sealant (White) NAD NAD - - - -

1 2A 14 HVAC

Ducts Foam Sealant NAD NA - - - -

1 2B 14 HVAC

Ducts Foam Sealant NAD NA - - - -

1 2C 14 HVAC

Ducts Foam Sealant NAD NA - - - -

1 3A 14 HVAC

Ducts

Duct Sealant (Red) NAD NAD - - - -

1 3B 14 HVAC

Ducts

Duct Sealant (Red) NAD NAD - - - -

1 3C 14 HVAC

Ducts

Duct Sealant (Red) NAD NAD - - - -

1 4A 13 Adj. Office New Canvas Pipe Wrap NAD NA - - - -

1 4B 13 Adj. Office New Canvas Pipe Wrap NAD NA - - - -

1 4C 13 Adj. Office New Canvas Pipe Wrap NAD NA - - - -

1 5A 13 Adj. Office Pipe Fitting NAD NA - - - -

1 5B 12 12th Floor Stairwell Pipe Fitting 36.4%

Chrysotile NA 334 LF Good 3

1 5C 11 1113 Pipe Fitting NA/PS NA - - - -

1 6A 13 Elevator Room Red Fire Stop NAD NAD - - - -

1 6B 8 D815A Red Fire Stop NAD NAD - - - -

1 6C 5 B- Wing Hallway Red Fire Stop NAD NAD - - - -

1 7A 13 Air Supply Duct Sealant (Gray) NAD NAD - - - -

1 7B 12 HVAC

Ducts

Duct Sealant (Gray) NAD NAD - - - -

1 7C 5 B530 Duct Sealant (Gray) NAD NAD - - - -

1 8A 12 12th Floor Stairwell Pipe Insulation 57.1%

Chrysotile NA 2,447 LF Good 3

1 9A 12 HVAC

Ducts

Duct Sealant (Brown) NAD NAD - - - -

1 9B 3 C312 Duct Sealant (Brown) NAD NAD - - - -

1 9C 3 C312 Duct Sealant (Brown) NAD NAD - - - -

1 10A 12 HVAC

Ducts

Canvas Duct Wrap NAD NA - - - -

1 10B 12 HVAC

Ducts

Canvas Duct Wrap NAD NA - - - -

1 11A 11 1113 Drywall NAD NA - - - -

1 11B 10 1010 Drywall NAD NA - - - -

1 11C 9 A900 Drywall NAD NA - - - -

1 11D 8 D815A Drywall NAD NA - - - -

1 11E 6 D614 Drywall NAD NA - - - -

1 11F 2 C224 Drywall NAD NA - - - -

Chapter 2 - Summary of ACM Building Results Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

(c) 2011, Mabbett & Associates

Albany - Vol I - Chapter 2 Summary of Lab Analysis Results (4-15-11).doc

Chapter 2 - Summary of ACM Building Results Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 11G Basement B40-3 Drywall NAD NA - - - -

1 12A 11 1113 Drywall Tape and Joint Compound

NAD NA - - - -

1 12B 10 1010 Drywall Tape and Joint Compound

NAD NA - - - -

1 12C 9 A900 Drywall Tape and Joint Compound

NAD NA - - - -

1 12D 8 D815A Drywall Tape and Joint Compound

NAD NA - - - -

1 12E 6 D614 Drywall Tape and Joint Compound

NAD NA - - - -

1 12F 2 C224 Drywall Tape and Joint Compound

NAD NA - - - -

1 12G Basement B40-3 Drywall Tape and Joint Compound

NAD NA - - - -

1 13A 11 1113 4” Covebase Mastic NAD NAD - - - -

1 13B 5 D500A 4” Covebase Mastic NAD NAD - - - -

1 13C 5 D500A 4” Covebase Mastic NAD NAD - - - -

1 14A 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor

Tile

NAD NAD - - - -

1 14B 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor

Tile

NAD NAD - - - -

1 14C 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor

Tile

NAD NAD - - - -

1 15A 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor Tile Mastic

NAD NAD - - - -

1 15B 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor Tile Mastic

NAD NAD - - - -

1 15C 11 Hall Adj.

12”x12” Tan with Brown Fleck Floor Tile Mastic

NAD NAD - - - -

1 16A 11 D1109 Spray Applied Fire Proofing NAD NA - - - -

1 16B 8 D815A Spray Applied Fire Proofing NAD NA - - - -

1 16C 2 C224 Spray Applied Fire Proofing NAD NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 17A 11 D1110 Black Cork Pipe Insulation

11.2% Chrysotile NA 101 LF Good 3

1 17B 11 D1110 Black Cork Pipe Insulation NA/PS NA - - - -

1 17C 11 D1110 Black Cork Pipe Insulation NA/PS NA - - - -

1 18A 11 D1109 Plaster Wall (Base) NAD NA - - - -

1 18B 10 B1029 Plaster Wall (Base) NAD NA - - - -

1 18C 8 A841 Plaster Wall (Base) NAD NA - - - -

1 18D 6 C606 Plaster Wall (Base) NAD NA - - - -

1 18E 5 512 Plaster Wall (Base) NAD NA - - - -

1 18F 4 B414 Plaster Wall (Base) NAD NA - - - -

1 18G 3 A324 Plaster Wall (Base) NAD NA - - - -

1 19A 11 D1109 Plaster Wall (Skim) NAD NA - - - -

1 19B 10 B1029 Plaster Wall (Skim) NAD NA - - - -

1 19C 8 AB41 Plaster Wall (Skim) NAD NA - - - -

1 19D 6 C606 Plaster Wall (Skim) NAD NA - - - -

1 19E 5 512 Plaster Wall (Skim) NAD NA - - - -

1 19F 4 B414 Plaster Wall (Skim) NAD NA - - - -

1 19G 3 A324 Plaster Wall (Skim) NAD NA - - - -

1 20A 11 D1104B Plaster Ceiling (Base) NAD NA - - - -

1 20B 6 D617 Plaster Ceiling (Base) NAD NA - - - -

1 20C 5 C500 Plaster Ceiling (Base) NAD NA - - - -

1 20D 4 B423 Plaster Ceiling (Base) NAD NA - - - -

1 20E 3 B328 Plaster Ceiling (Base) NAD NA - - - -

1 20F 2 B209 Plaster Ceiling (Base) NAD NA - - - -

1 20G Basement D1-3 Plaster Ceiling (Base) NAD NA - - - -

1 21A 11 D1104B Plaster Ceiling (Skim) NAD NA - - - -

1 21B 6 D617 Plaster Ceiling (Skim) NAD NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 21C 5 C500 Plaster Ceiling (Skim) NAD NA - - - -

1 21D 4 B423 Plaster Ceiling (Skim) NAD NA - - - -

1 21E 3 B328 Plaster Ceiling (Skim) NAD NA - - - -

1 21F 2 B209 Plaster Ceiling (Skim) NAD NA - - - -

1 21G Basement D1-3 Plaster Ceiling (Skim) NAD NA - - - -

1 22A 11 D1104B 2’x 4’ Ceiling Tile with Tan

Stripe

NAD NA - - - -

1 22B 11 D1104B 2’x 4’ Ceiling Tile with Tan

Stripe

NAD NA - - - -

1 22C 11 D1104B 2’x 4’ Ceiling Tile with Tan

Stripe

NAD NA - - - -

1 23A 11 Rooftop Stairwell

Canvas Pipe Wrap

66.7% Chrysotile NA 35 SF Damaged 2

1 23B 11 Rooftop Stairwell

Canvas Pipe Wrap NA/PS NA - - - -

1 24A 11 A1104

12”x12” Tan with Brown

Streak Floor Tile

1.6% Chrysotile NA 26,056 SF Good 4

1 24B Basement A25

12”x12” Tan with Brown

Streak Floor Tile

NA/PS NA - - - -

1 24C Basement A25

12”x12” Tan with Brown

Streak Floor Tile

NA/PS NA - - - -

1 25A 11 A1104

12”x12” Tan with Brown

Streak Floor Tile Mastic

<.025% Chrysotile

1.5% Chrysotile 26,056 SF Good 4

1 25B Basement A25

12”x12” Tan with Brown

Streak Floor Tile Mastic

NAD NA/PS - - - -

1 25C Basement A25

12”x12” Tan with Brown

Streak Floor Tile Mastic

NAD NA/PS - - - -

1 26A 11 A1106 White with Blue Speck

Sheet Flooring

NAD NAD - - - -

1 26B 11 A1106 White with Blue Speck

Sheet Flooring

NAD NAD - - - -

1 26C 11 A1106 White with Blue Speck

Sheet Flooring

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 27A 11 A1106

White with Blue Speck

Sheet Flooring Mastic

NAD NAD - - - -

1 27B 11 A1106

White with Blue Speck

Sheet Flooring Mastic

NAD NAD - - - -

1 27C 11 A1106

White with Blue Speck

Sheet Flooring Mastic

NAD NAD - - - -

1 28A 11 A1106B Duct Sealant (White) NAD NAD - - - -

1 28B 11 A1106B Duct Sealant (White) NAD NAD - - - -

1 28C 11 A1106B Duct Sealant (White) NAD NAD - - - -

1 29A 11 A1106B Sink Coating (Black) NAD NA - - - -

1 29B 4 402 Sink Coating (Black) NAD NA - - - -

1 29C 3 A306 Sink Coating (Black)

2.6% Chrysotile NA 99 SF Good 4

1 30A 11 1104C 6” Covebase Mastic NAD NAD - - - -

1 30B 5 514 6” Covebase Mastic NAD NAD - - - -

1 30C Basement B40-1 6” Covebase Mastic NAD NAD - - - -

1 31A 11 B1101 12”x12” White with Black Dot

Floor Tile

NAD NA - - - -

1 31B 5 C500 12”x12” White with Black Dot

Floor Tile

1.7% Chrysotile NA 8,888 SF Good 4

1 31C 5 D524 12”x12” White with Black Dot

Floor Tile

NA/PS NA - - - -

1 32A 11 B1101

12”x12” White with Black Dot

Floor Tile Mastic

NAD NAD - - - -

1 32B 5 C500

12”x12” White with Black Dot

Floor Tile Mastic

NAD NAD - - - -

1 32C 5 D524

12”x12” White with Black Dot

Floor Tile Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 33A 11 B1103 2’x 4’ Fissured Ceiling Tile NAD NA - - - -

1 33B 6 Hall Adj.

D621

2’x 4’ Fissured Ceiling Tile NAD NA - - - -

1 33C 6 Hall Adj.

D621

2’x 4’ Fissured Ceiling Tile NAD NA - - - -

1 34A 11 C1101 Sink Coating (White) NAD NAD - - - -

1 34B 3 307E Sink Coating (White) NAD NAD - - - -

1 34C 2 D241 Sink Coating (White) NAD NAD - - - -

1 35A 10 1011 12”x12” Brown Marbled Floor

Tile

NAD NAD - - - -

1 35B 10 1011 12”x12” Brown Marbled Floor

Tile

NAD NAD - - - -

1 35C 10 1011 12”x12” Brown Marbled Floor

Tile

NAD NAD - - - -

1 36A 10 1011 12”x12” Brown Marbled Floor

Tile Mastic

NAD NAD - - - -

1 36B 10 1011 12”x12” Brown Marbled Floor

Tile Mastic

NAD NAD - - - -

1 36C 10 1011 12”x12” Brown Marbled Floor

Tile Mastic

NAD NAD - - - -

1 37A 10 D1001 Carpet Mastic (Green) NAD NAD - - - -

1 37B 9 D927 Carpet Mastic (Green) NAD NAD - - - -

1 37C 9 D927 Carpet Mastic (Green) NAD NAD - - - -

1 38A 10 A1000 Tan Sheet Flooring NAD NAD - - - -

1 38B 5 510A Tan Sheet Flooring NAD NAD - - - -

1 38C 10 A1000 Tan Sheet Flooring NAD NAD - - - -

1 39A 10 A1000 Tan Sheet Flooring Mastic

NAD NAD - - - -

1 39B 5 510A Tan Sheet Flooring Mastic

NAD NAD - - - -

1 39C 10 A1000 Tan Sheet Flooring Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 40A 9 A924 12”x12”

Cream Floor Tile

NAD NAD - - - -

1 40B 9 A924 12”x12”

Cream Floor Tile

NAD NAD - - - -

1 40C 9 A924 12”x12”

Cream Floor Tile

NAD NAD - - - -

1 41A 9 A924 12”x12”

Cream Floor Tile Mastic

NAD NAD - - - -

1 41B 9 A924 12”x12”

Cream Floor Tile Mastic

NAD NAD - - - -

1 41C 9 A924 12”x12”

Cream Floor Tile Mastic

NAD NAD - - - -

1 42A 8 811 Duct Sealant (Green) NAD NAD - - - -

1 42B 8 811 Duct Sealant (Green) NAD NAD - - - -

1 42C 8 811 Duct Sealant (Green) NAD NAD - - - -

1 43A 8 806 Leaf Pattern Sheet Flooring NAD NAD - - - -

1 43B 7 C701 Leaf Pattern Sheet Flooring NAD NAD - - - -

1 43C 2 A223A Leaf Pattern Sheet Flooring NAD NAD - - - -

1 44A 8 806 Leaf Pattern

Sheet Flooring Mastic

NAD NAD - - - -

1 44B 7 C701 Leaf Pattern

Sheet Flooring Mastic

NAD NAD - - - -

1 44C 2 A223A Leaf Pattern

Sheet Flooring Mastic

NAD NAD - - - -

1 45A 8 803B Sink Coating (Gray) NAD NAD - - - -

1 45B 8 803B Sink Coating (Gray) NAD NAD - - - -

1 45C 5 A521 Sink Coating (Gray) NAD NAD - - - -

1 46A 8 803 2’x 2’ Flat Ceiling Tile NAD NA - - - -

1 46B 5 512 2’x 2’ Flat Ceiling Tile NAD NA - - - -

1 46C 2 C265 2’x 2’ Flat Ceiling Tile NAD NA - - - -

1 47A 6 D609 Blue Sheet Flooring NAD NAD - - - -

1 47B 6 D609 Blue Sheet Flooring NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 47C 6 D609 Blue Sheet Flooring NAD NAD - - - -

1 48A 6 D609 Blue Sheet

Flooring Mastic

NAD NAD - - - -

1 48B 6 D609 Blue Sheet

Flooring Mastic

NAD NAD - - - -

1 48C 6 D609 Blue Sheet

Flooring Mastic

NAD NAD - - - -

1 49A 6 D612 White Fire Stop NAD NA - - - -

1 49B 6 D612 White Fire Stop NAD NA - - - -

1 49C 6 D612 White Fire Stop NAD NA - - - -

1 50A 6 D612 Computer Post Mastic NAD NAD - - - -

1 50B 6 D612 Computer Post Mastic NAD NAD - - - -

1 50C 6 D612 Computer Post Mastic NAD NAD - - - -

1 51A 6 D612 12”x12” White Marble Floor

Tile

NAD NA - - - -

1 51B 6 C605 12”x12” White Marble Floor

Tile

NAD NA - - - -

1 51C 5 C511 12”x12” White Marble Floor

Tile

1.8% Chrysotile NA 19,615 SF Good 4

1 52A 6 D612 12”x12” White Marble Floor Tile Mastic

NAD NAD - - - -

1 52B 6 C605 12”x12” White Marble Floor Tile Mastic

NAD NAD - - - -

1 52C 5 C511 12”x12” White Marble Floor Tile Mastic

<0.25% Chrysotile

Chrysotile Trace - - - -

1 53A 6 D617 Ceiling Tile Mastic NAD NAD - - - -

1 53B 6 D617 Ceiling Tile Mastic NAD NAD - - - -

1 53C 6 D617 Ceiling Tile Mastic NAD NAD - - - -

1 54A 6 D617 1’x 1’ Ceiling Tile NAD NA - - - -

1 54B 5 D538 1’x 1’ Ceiling Tile NAD NA - - - -

1 54C 6 D617 1’x 1’ Ceiling Tile NAD NA - - - -

1 55A 6 607

Pneumatic Tubing

Insulation (Wall)

NAD NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 55B 6 607

Pneumatic Tubing

Insulation (Wall)

NAD NA - - - -

1 55C 6 607

Pneumatic Tubing

Insulation (Wall)

NAD NA - - - -

1 56A 6 C608 12”x12” Gray with Olive Floor Tile

8.3% Chrysotile NA 6,106 SF Good 4

1 56B 5 D515 12”x12” Gray with Olive Floor Tile

NA/PS NA - - - -

1 56C 4 A405 12”x12” Gray with Olive Floor Tile

NA/PS NA - - - -

1 57A 6 C608

12”x12” Gray with Olive Floor Tile

Mastic

5.0% Chrysotile NA 6,106 SF Good 4

1 57B 5 D515

12”x12” Gray with Olive Floor Tile

Mastic

NA/PS NA - - - -

1 57C 4 A405

12”x12” Gray with Olive Floor Tile

Mastic

NA/PS NA - - - -

1 58A 6 B631 12”x12” Rust Floor Tile NAD NAD - - - -

1 58B 6 B631 12”x12” Rust Floor Tile NAD NAD - - - -

1 58C 6 B631 12”x12” Rust Floor Tile NAD NAD - - - -

1 59A 6 B631 12”x12” Rust

Floor Tile Mastic

NAD NAD - - - -

1 59B 6 B631 12”x12” Rust

Floor Tile Mastic

NAD NAD - - - -

1 59C 6 B631 12”x12” Rust

Floor Tile Mastic

NAD NAD - - - -

1 60A 6 B631 Floor Leveling Compound NAD NA - - - -

1 60B 6 B631 Floor Leveling Compound NAD NA - - - -

1 60C 6 B631 Floor Leveling Compound NAD NA - - - -

1 61A 5 C506 12”x12” Tan with Rust Floor Tile

15.6% Chrysotile NA 1,513 SF Good 4

1 61B 4 B403 12”x12” Tan with Rust Floor Tile

NA/PS NA - - - -

1 61C 3 Hall Adj.

C308-1

12”x12” Tan with Rust Floor Tile

NA/PS NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 62A 5 C506

12”x12” Tan with Rust Floor Tile

Mastic

<0.25% Chrysotile

<1.0% Chrysotile - - - -

1 62B 4 B403

12”x12” Tan with Rust Floor Tile

Mastic

<0.25% Chrysotile

Chrysotile Trace - - - -

1 62C 3 C308-1

12”x12” Tan with Rust Floor Tile

Mastic

NAD NAD - - - -

1 63A 5 D519 12”x12” Blue Floor Tile NAD NAD - - - -

1 63B 4 B404 12”x12” Blue Floor Tile NAD NAD - - - -

1 63C 5 D519 12”x12” Blue Floor Tile NAD NAD - - - -

1 64A 5 D519 12”x12” Blue

Floor Tile Mastic

NAD NAD - - - -

1 64B 4 B404 12”x12” Blue

Floor Tile Mastic

NAD NAD - - - -

1 64C 5 D519 12”x12” Blue

Floor Tile Mastic

NAD NAD - - - -

1 65A 5 508A 12”x12” Tan Multicolor Floor Tile

NAD NAD - - - -

1 65B 5 508C 12”x12” Tan Multicolor Floor Tile

NAD NAD - - - -

1 65C 5 508E 12”x12” Tan Multicolor Floor Tile

NAD NAD - - - -

1 66A 5 508A

12”x12” Tan Multicolor Floor Tile

Mastic

NAD NAD - - - -

1 66B 5 508C

12”x12” Tan Multicolor Floor Tile

Mastic

NAD NAD - - - -

1 66C 5 508E

12”x12” Tan Multicolor Floor Tile

Mastic

NAD NAD - - - -

1 67A 5 511A Brown Sheet Flooring NAD NAD - - - -

1 67B 5 511D Brown Sheet Flooring NAD NAD - - - -

1 67C 5 511D Brown Sheet Flooring NAD NAD - - - -

1 68A 5 511A Brown Sheet

Flooring Mastic

NAD NAD - - - -

1 68B 5 511D Brown Sheet

Flooring Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 68C 5 511D Brown Sheet

Flooring Mastic

NA NA - - - -

1 69A 5 510 Brown Duct Covering NAD NA - - - -

1 69B 5 510 Brown Duct Covering NAD NA - - - -

1 69C 5 510 Brown Duct Covering NAD NA - - - -

1 70A 4 B401 Black Damp Proofing

3% Chrysotile NA 1,695 SF Good 4

1 70B 3 A315 Black Damp Proofing NA/PS NA - - - -

1 70C 3 A315 Black Damp Proofing NA/PS NA - - - -

1 71A 4 Hall Adj.

SW3

Tan Mosaic Sheet Flooring

4.5% Chrysotile NA 16,130 SF Good 4

1 71B 3 C303-1 Tan Mosaic Sheet Flooring NA/PS NA - - - -

1 71C 3 C303-1 Tan Mosaic Sheet Flooring NA/PS NA - - - -

1 72A 4 Hall Adj.

SW3

Tan Mosaic Sheet Flooring

Mastic

NA/PS NA - - - -

1 72B 3 C303-1 Tan Mosaic

Sheet Flooring Mastic

2% Chrysotile NA 16,130 SF Good 4

1 72C 3 C303-1 Tan Mosaic

Sheet Flooring Mastic

NA/PS NA - - - -

1 73A 4 D402 Black

Computer Post Mastic

NAD NAD - - - -

1 73B 4 D405 Black

Computer Post Mastic

NAD NAD - - - -

1 73C 4 D407 Black

Computer Post Mastic

NAD NAD - - - -

1 74A 4 C403 Green Sheet Flooring NAD NAD - - - -

1 74B 4 C403 Green Sheet Flooring NAD NAD - - - -

1 74C 4 C403 Green Sheet Flooring NAD NAD - - - -

1 75A 4 C403 Green Sheet

Flooring Mastic

NAD NAD - - - -

1 75B 4 C403 Green Sheet

Flooring Mastic

NAD NAD - - - -

1 75C 4 C403 Green Sheet

Flooring Mastic

NAD NAD - - - -

1 76A 3 D314 2’x 4’ Ceiling Tile NAD NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 76B 3 D314 2’x 4’ Ceiling Tile NAD NA - - - -

1 76C 3 D314 2’x 4’ Ceiling Tile NAD NA - - - -

1 77A 3 B320 Light Green Sheet Flooring NAD NAD - - - -

1 77B 3 B320 Light Green Sheet Flooring NAD NAD - - - -

1 77C 3 B320 Light Green Sheet Flooring NAD NAD - - - -

1 78A 3 B320 Light Green

Sheet Flooring Mastic

NAD NAD - - - -

1 78B 3 B320 Light Green

Sheet Flooring Mastic

NAD NAD - - - -

1 78C 3 B320 Light Green

Sheet Flooring Mastic

NAD NAD - - - -

1 79A 2 C208 12”x12” Blue Marble Floor

Tile

NAD NAD - - - -

1 79B 2 C208 12”x12” Blue Marble Floor

Tile

NAD NAD - - - -

1 79C 2 C208 12”x12” Blue Marble Floor

Tile

NAD NAD - - - -

1 80A 2 C208 12”x12” Blue Marble Floor Tile Mastic

NAD NAD - - - -

1 80B 2 C208 12”x12” Blue Marble Floor Tile Mastic

NAD NAD - - - -

1 80C 2 C208 12”x12” Blue Marble Floor Tile Mastic

NAD NAD - - - -

1 81A 2 C265 12”x12” Gray Marble Floor

Tile

NAD NAD - - - -

1 81B 2 C265 12”x12” Gray Marble Floor

Tile

NAD NAD - - - -

1 81C 2 C265 12”x12” Gray Marble Floor

Tile

NAD NAD - - - -

1 82A 2 C265 12”x12” Gray Marble Floor Tile Mastic

NAD NAD - - - -

1 82B 2 C265 12”x12” Gray Marble Floor Tile Mastic

NAD NAD - - - -

1 82C 2 C265 12”x12” Gray Marble Floor Tile Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 83A 2 D230 Rust Sheet Flooring NAD NAD - - - -

1 83B 2 D230 Rust Sheet Flooring NAD NAD - - - -

1 83C 2 D230 Rust Sheet Flooring NAD NAD - - - -

1 84A 2 D230 Rust Sheet

Flooring Mastic

NAD NAD - - - -

1 84B 2 D230 Rust Sheet

Flooring Mastic

NAD NAD - - - -

1 84C 2 D230 Rust Sheet

Flooring Mastic

NAD NAD - - - -

1 85A 2 D203 12”x12”

Cream Marble Floor Tile

NAD NAD - - - -

1 85B 2 D203 12”x12”

Cream Marble Floor Tile

NAD NAD - - - -

1 85C 2 D203 12”x12”

Cream Marble Floor Tile

NAD NAD - - - -

1 86A 2 D203

12”x12” Cream Marble

Floor Tile Mastic

NAD NAD - - - -

1 86B 2 D203

12”x12” Cream Marble

Floor Tile Mastic

NAD NAD - - - -

1 86C 2 D203

12”x12” Cream Marble

Floor Tile Mastic

NAD NAD - - - -

1 87A 2 A202 12”x12” Pink Floor Tile NAD NAD - - - -

1 87B 2 A202 12”x12” Pink Floor Tile NAD NAD - - - -

1 87C 2 A202 12”x12” Pink Floor Tile NA NAD - - - -

1 88A 2 A202 12”x12” Pink

Floor Tile Mastic

NAD Chrysotile Trace - - - -

1 88B 2 A202 12”x12” Pink

Floor Tile Mastic

NAD Chrysotile Trace - - - -

1 88C 2 A202 12”x12” Pink

Floor Tile Mastic

NAD Chrysotile Trace - - - -

1 89A 2 A214 Gray Sheet Flooring NAD NAD - - - -

1 89B 2 A214 Gray Sheet Flooring NAD NAD - - - -

1 89C 2 A214 Gray Sheet Flooring NAD NAD - - - -

1 90A 2 A214 Gray Sheet

Flooring Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 90B 2 A214 Gray Sheet

Flooring Mastic

NAD NAD - - - -

1 90C 2 A214 Gray Sheet

Flooring Mastic

NAD NAD - - - -

1 91A 2 A214 Bottom Layer Sheet Flooring NAD NAD - - - -

1 91B 2 A214 Bottom Layer Sheet Flooring NAD NAD - - - -

1 91C 2 A214 Bottom Layer Sheet Flooring NAD NAD - - - -

1 92A 2 A214 Bottom Layer

Sheet Flooring Mastic

NAD NAD - - - -

1 92B 2 A214 Bottom Layer

Sheet Flooring Mastic

NAD NAD - - - -

1 92C 2 A214 Bottom Layer

Sheet Flooring Mastic

NAD NAD - - - -

1 93A 1 C107 12”x12” Green Floor Tile NAD NAD - - - -

1 93B 1 C108 12”x12” Green Floor Tile NAD NAD - - - -

1 93C 1 C109 12”x12” Green Floor Tile NAD NAD - - - -

1 94A 1 C107 12”x12” Green

Floor Tile Mastic

NAD NAD - - - -

1 94B 1 C108 12”x12” Green

Floor Tile Mastic

NAD NAD - - - -

1 94C 1 C109 12”x12” Green

Floor Tile Mastic

NAD NAD - - - -

1 95A 1 C112 Black Tape Pipe Insulation

2.7% Chrysotile NA 10 LF Good 4

1 95B 1 C112 Black Tape Pipe Insulation NA/PS NA - - - -

1 95C 1 C112 Black Tape Pipe Insulation NA/PS NA - - - -

1 96A Basement C51-3 Walk-In

Cooler Ceiling Insulation

NAD NAD - - - -

1 96B Basement C51-3 Walk-In

Cooler Ceiling Insulation

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 96C Basement C51-3 Walk-In

Cooler Ceiling Insulation

NAD NAD - - - -

1 97A Basement C51-3

Walk-In Cooler Ceiling

Insulation Covering

9.1% Chrysotile NA 432 SF Good 3

1 97B Basement C51-3

Walk-In Cooler Ceiling

Insulation Covering

NA/PS NA - - - -

1 97C Basement C51-3

Walk-In Cooler Ceiling

Insulation Covering

NA/PS NA - - - -

1 98 Basement C51-2 Safe Door Insulation NAD NA

1 99A Basement C52 Stone Sheet Flooring

8.5% Chrysotile NA 445 SF Good 4

1 99B Basement C52 Stone Sheet Flooring NA/PS NA - - - -

1 99C Basement C52 Stone Sheet Flooring NA/PS NA - - - -

1 100A Basement C52 Stone Sheet

Flooring Mastic

3.5% Chrysotile NA 445 SF Good 4

1 100B Basement C52 Stone Sheet

Flooring Mastic

NA/PS NA - - - -

1 100C Basement C52 Stone Sheet

Flooring Mastic

NA/PS NA - - - -

1 101A Basement D3C 2’x 4’ Pinhole Ceiling Tile NAD NA - - - -

1 101B Basement D3C 2’x 4’ Pinhole Ceiling Tile NAD NA - - - -

1 101C Basement D3C 2’x 4’ Pinhole Ceiling Tile NAD NA - - - -

1 102A Basement D3 Interior Window Caulking

NAD NAD - - - -

1 102B Basement D3 Interior Window Caulking

NAD NAD - - - -

1 102C Basement D3 Interior Window Caulking

NAD NAD - - - -

1 103A Basement D13 12”x12” White Floor Tile NAD NAD - - - -

1 103B Basement D13 12”x12” White Floor Tile NAD NAD - - - -

1 103C Basement D13 12”x12” White Floor Tile NAD NAD - - - -

1 104A Basement D13 12”x12” White

Floor Tile Mastic

NAD NAD - - - -

1 104B Basement D13 12”x12” White

Floor Tile Mastic

NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 104C Basement D13 12”x12” White

Floor Tile Mastic

NAD NAD - - - -

1 105A Sub- Basement D-Wing

Black Canvas Damp-

Proofing

NAD NAD - - - -

1 105B Sub- Basement D-Wing

Black Canvas Damp-

Proofing

NAD NAD - - - -

1 105C Sub- Basement Core

Black Canvas Damp-

Proofing

NAD NAD - - - -

1 106A Sub- Basement A-Wing Stick Pin Duct

Adhesive NAD NAD - - - -

1 106B Sub- Basement A-Wing Stick Pin Duct

Adhesive NAD NAD - - - -

1 106C Sub- Basement A-Wing Stick Pin Duct

Adhesive NAD NAD - - - -

1 107A 3 A326 Carpet Mastic NAD NAD - - - -

1 107B 3 A326 Carpet Mastic NAD NAD - - - -

1 107C 3 A326 Carpet Mastic NAD NAD - - - -

1 108A Exterior 1-D Exterior Exterior Window Caulk NAD NAD - - - -

1 108B Exterior 1-D Exterior Exterior Window Caulk NAD NAD - - - -

1 108C Exterior 1-C Exterior Exterior Window Caulk NAD NAD - - - -

1 109A Exterior 1-C Exterior Building Flashing Mastic

NAD NAD - - - -

1 109B Exterior 1-C Exterior Building Flashing Mastic

NAD NAD - - - -

1 110A Exterior 1-Core Exterior

Exterior Door Caulk NAD NAD - - - -

1 110B Exterior 1-D Exterior Exterior Door Caulk NAD NAD - - - -

1 110C Exterior 1C Exterior Exterior Door Caulk NAD NAD - - - -

1 111A Exterior 1-A Exterior Damp- Proofing NAD NAD - - - -

1 112A Exterior 1-B Exterior Building Caulk NAD NAD - - - -

1 112B Exterior 1-A Exterior Building Caulk NAD NAD - - - -

1 112C Exterior 1-D Exterior Building Caulk NAD NAD - - - -

1 112D Exterior 1-C Exterior Building Caulk NAD NAD - - - -

1 112E Exterior 1-D Exterior Building Caulk NAD NAD - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

1 NA

Sub- Basement

Basement , 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, NA Fire Panel Insulation PACM NA 275 SF Good 3

1 NA

Basement , 1, 2, 3, 6, 11 NA Transite Board

Tabletops PACM NA 1,847 SF Good 4

1 NA

Basement , 1, 2, 3, 4, 5, 6, 11, NA

9"x9" Floor

Tile and Mastic

PACM NA 22,540 SF Good 4

1 NA Basement , 2 NA Transite Fume

Hood PACM NA 22 SF Good 4

1 NA 6, 11 NA 9"x9" Mastic PACM NA 2,627 SF Damaged 3

1 NA

Sub-

Basement , 6, 12

NA Canvas Vibration Cloth PACM NA 37 SF Damaged 2

1 NA 9 NA

Calcium

Carbonate Pipe

PACM NA 3 LF Good 3

1 NA 9 NA 8" Transite Pipe PACM NA 12 LF Good 4

1 NA 9, 10 NA 10" Transite Pipe PACM NA 20 LF Good 4

1 NA 12, 13, 14 NA

Labeled Encapsualted

ACM Duct Insulation

PACM NA 376 SF Good 3

2 1A Basement C53-1 Drywall NAD NA - - - -

2 1B Basement C53-1 Drywall NAD NA - - - -

2 1C Basement C53-1 Drywall NAD NA - - - -

2 2A Basement C53-1 Joint Compound NAD NA - - - -

2 2B Basement C53-1 Joint Compound NAD NA - - - -

2 2C Basement C53-1 Joint Compound NAD NA - - - -

2 3A Basement C53-1 1’x1’ Ceiling Tile NAD NA - - - -

2 3B Basement C53-1 1’x1’ Ceiling Tile NAD NA - - - -

2 3C Basement C53-1 1’x1’ Ceiling Tile NAD NA - - - -

2 4A Basement C53-1 1’x1’ Ceiling Tile Mastic NAD NAD - - - -

2 4B Basement C53-1 1’x1’ Ceiling Tile Mastic NAD NAD - - - -

2 4C Basement C53-1 1’x1’ Ceiling Tile Mastic NAD NAD - - - -

2 5A Basement C53-1 Ceiling Plaster

– Skim Coat NAD NA - - - -

2 5B Basement C54 Ceiling Plaster

– Skim Coat NAD NA - - - -

(c) 2011, Mabbett & Associates

Albany VA Medical Center

Building No.

Sample No. Floor

Sample Location (Rm # or location)

Description of Material

Percent and Type of Asbestos Estimated Quantity

Condition

VISN 2

Risk

Hazard Category

1-4*

56 7C 2 2nd Floor Stairwell

Drywall (Ceiling) NAD NA - - - -

56 8A 1 Exterior Damp- Proofing NAD NAD - - - -

56 8B 1 Exterior Damp- Proofing NAD NAD - - - -

56 9A 1 Exterior Window Caulk (Exterior) NAD NAD - - - -

56 9B 1 Exterior Window Caulk (Exterior) NAD NAD - - - -

56 9C 1 Exterior Window Caulk (Exterior) NAD NAD - - - -

56 10A 1 Exterior Door Caulk (Exterior) NAD NAD - - - -

56 10B 1 Exterior Door Caulk (Exterior) NAD NAD - - - -

56 10C 1 Exterior Door Caulk (Exterior) NAD NAD - - - -

TR - Trace SF - Square Feet LF - Linear Feet EA - Each CF - Cubic Feet

* - The VISN 2 risk hazard assessment scale 1 – 4 is a relative indicator of the risk and need for response/remediation. (1) represents the highest priority (e.g. removal or encapsulation) whereas a (4) represents the lowest priority (monitor as part of 6 month O&M program). The rating, assigned by an Asbestos Management Planner, takes into account the following criteria: condition, friable vs. non-friable, accessibility, occupancy (e.g. continuous, intermittent or occasional, patients/staff/visitors), potential for air erosion, potential for vibration damage, potential for disturbance/damage (e.g. exposed and in an accessible location), and potential for water damage.

Footnotes:

NAD - No Asbestos Detected (PLM) ND - None Detected (TEM) NA/PS - Positive Stop

(c) 2011, Mabbett & Associates

ASBESTOS SURVEY SUMMARY PLAN

NOTES:

NORTH

25** 25*

LEGEND

SNK

T

D

I

D

Cvc

FP

NO ASBESTOS ABATED IN THIS AREA

SINCE 2011 SURVEY

UPDATED 08/2020

ASBESTOS SURVEY SUMMARY PLAN

NOTES:

NORTH

25** 25*

LEGEND

SNK

T

D

I

D

Cvc

FP

ASBESTOS ABATED AFTER 2011 SURVEY

1. 1.All known asbestos abated during full renovation as part of project 528A8-09-850 Renovate Dental

Clinic

F

P

FP

FP

ASBESTOS SURVEY SUMMARY PLAN

NOTES:

NORTH

25** 25*

LEGEND

SNK

T

D

I

D

Cvc

FP

NO ASBESTOS ABATED IN THIS AREA

FP

F

P

ASBESTOS SURVEY SUMMARY PLAN

NOTES:

NORTH

25…

This is the start of the file's text. The full file is on GovTribe.