0172-0544 TRC Investigation Report Groton Maintenance Salt Shed June 2026.pdf

PDF 4 MB Posted

Attached to
Construction of Maintenance Facility in the Towns of Stonington and Groton
Solicitation number
0172-0544
Issued by
New London County, Connecticut

About this file

This is a pre-demolition investigative survey report prepared by TRC for the Connecticut Department of Transportation regarding hazardous building materials at the Groton Maintenance Facility Salt Shed located at 150 Welles Road, Groton, Connecticut (Project No. 172-544). The survey was conducted on May 22, 2026 and June 4, 2026 by licensed asbestos inspectors Andrew Smith (License #1137) and Tyler Noll (License #1053), with lead paint inspections performed by Andrew Smith (License #2316) and Alexa Knight. The facility has no historic significance designation. The investigation focused on identifying asbestos-containing materials, lead paint, and other hazardous building materials present at the salt shed facility prior to any demolition activities. The report includes comprehensive sampling and analysis across multiple tables documenting bulk samples of suspect materials, identified and confirmed non-asbestos-containing materials, lead paint XRF measurements, and composite building material waste characterization.

The survey findings indicate that no asbestos-containing materials were identified in the subject area, and lead paint testing results were all below one percent thresholds. The report documents general building material hazardous waste present at the facility and provides detailed laboratory analysis data, site photographs, site sketches, inspector certifications, and laboratory accreditations as supporting documentation. The investigation was conducted under TRC Project No. 501871.8360.0710, with the Connecticut Department of Transportation project manager Benjamin Silverman overseeing the assignment. The report was issued in June 2026 and includes inventory of additional hazardous and regulated materials identified during the site inspection.

View the file

Other files

File Type Posted
FD_CP_ELE_0172-0544_E-600.dgn —
SV_D2_0170_3421_Stonington_New Facilty Construction_321 Liberty Street_Hydraulic Data.dxf DXF file
S-009.dgn —
FD_CP_ELE_0172-0544_E-201.dgn —
Stonington Facility.dgn —
SV_D2_0170_3421_Stonington_New Facilty Construction_321 Liberty Street_Utilities.dxf DXF file
FD_CP_ELE_0172-0544_E-401.dgn —
SV_D2_0170_3421_Stonington_New Facilty Construction_321 Liberty Street_Annotation.dxf DXF file
EED_Design_Contours.dxf DXF file
S-010.dgn —
FD_CP_ELE_0172-0544_E-301.dgn —
OBD_FD_ARC_0172_0544_A200.dgn —
Design.dxf DXF file
FD_CP_ELE_0172-0544_E-540.dgn —
FD_CP_ELE_0172-0544_E-202.dgn —
FD_CP_ELE_0172-0544_E-300.dgn —
FD_CP_ELE_0172-0544_E-303.dgn —
S-012.dgn —
SV_D2_058_0337_Groton_Maintenance Facilty_Welles Road LABELS_ORD.dgn —
S-005.dgn —
SV_D2_0170_3421_Stonington_New Facilty Construction_321 Liberty Street.dxf DXF file
OBD_FD_ARC_0172_0544_A100-104.dgn —
S-011.dgn —
OBD_FD_ARC_0172_0544_NORTH STONINGTON.dgn —
Online Q and A Instruction.pdf PDF
S-003.dgn —
FT_CP_CIV_0173_0544_EF-C001 (Groton Demo).dgn —
FD_CP_ELE_0172_0544_EF-E-100.dgn —
FD_CP_ELE_0172-0544_E-200.dgn —
Groton Temp Facility.dgn —
FD_CP_ELE_0172_0544_EF-E-210.dgn —
S-002.dgn —
S-004.dgn —
0172-0544_Nov_11_26_solicitation_doc.pdf PDF
EED_Design Groton_Contours.dxf DXF file
Design_Contours.dxf DXF file
FT_CP_CIV_0172_0544_C004 (Site Plan).dgn —
FD_CP_ELE_0172-0544_E-500.dgn —
Design Groton.dgn —
Bidders Checklist - Rev September 2026.pdf PDF
FD_CP_ELE_0172-0544_E-302.dgn —
FT_CP_CIV_0172_0544_C003 (Demo).dgn —
FD_CP_ELE_0172-0544_E-402.dgn —
FT_CP_CIV_0173_0544_EF-C002 (Groton Site).dgn —
OBD_FD_ARC_0172_0544_A111.dgn —
FD_OBD_0172_0544_P000 Final DGN.dgn —
EED_Design Groton Contours.dxf DXF file
SV_D2_058_0337_Groton_Maintenance Facilty_Welles Road_ORD.dgn —
0172-0544 Invitation to Bid.pdf PDF
FD_CP_ELE_0172_0544_EF-E-200.dgn —
Show 40 more

Latest 50 of 87 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SURVEY REPORT

PRE-DEMOLITION

INVESTIGATIVE SURVEY FOR HAZARDOUS

BUILDING MATERIALS

GROTON MAINTENANCE FACILITY

SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Project No.172-544

Prepared for

State of Connecticut Department of Transportation

Newington, Connecticut

Prepared by

TRC

Windsor, Connecticut

Issued

June 2026

PRE-DEMOLITION

INVESTIGATIVE SURVEY FOR

HAZARDOUS BUILDING MATERIALS

GROTON MAINTENANCE FACILITY

SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Project No.172-544

Prepared for

Department of Transportation Newington, Connecticut

Prepared by

TRC

Windsor, Connecticut

Stephen R. Arienti, CHMM SIH New England Regional Area Leader – Engineer in Charge

Erik R. Plimpton, P.E., CHMM, CMC Vice President SIH – Engineer in Charge

TRC Project No. 501871.8360.0710

Issued-June 2026

TRC

21 Griffin Road North Windsor, Connecticut 06095 Telephone (860) 298-9692

TABLE OF CONTENTS

PROJECT OUTLINE

TABLES

1 BULK SAMPLE SUMMARY OF SUSPECT ASBESTOS CONTAINING

MATERIALS

2 IDENTIFIED ASBESTOS CONTAINING MATERIALS

3 CONFIRMED NON-ASBESTOS CONTAINING MATERIALS

4 SUMMARY OF LEAD PAINT XRF MEASUREMENTS

5 SUMMARY OF COMPOSITE BUILDING MATERIAL WASTE CHARACTERIZATION

6 INVENTORY OF ADDITIONAL HAZARDOUS/REGULATED MATERIALS, WASTES

AND ITEMS IDENTIFIED

APPENDICES

A SITE PHOTOS

B SITE SKETCH

C CONNECTICUT STATE HISTORICAL PRESERVATION OFFICE SITE REVIEW

D TRC INSPECTORS LICENSES/CERTIFICATIONS

E LABORATORY ACCREDITATIONS

F ASBESTOS PLM LABORATORY ANALYSIS DATA

G ASBESTOS TEM LABORATORY ANALYSIS DATA

H LEAD PAINT XRF MEASUREMENT TABLE

I CTDEEP/EPA MEMO OF JANUARY 26, 2004

J RELATED CORRESPONDENCE

PROJECT OUTLINE

DOT Project No.:

Assignment No.:

DOT Project Manager:

Site Address:

TRC Project No.:

Asbestos Inspector(s):

Lead Inspector:

Date(s) of Inspection:

Historic Significance:

Asbestos Identified:

Lead Paint Identified:

Gen. Bldg. Mat. Haz Waste:

172-544

524-8360

Benjamin Silverman

150 Welles Road Groton, Connecticut 06355

501871.8360.0710

Andrew Smith (LIC #1137) Tyler Noll (LIC #1053) Alexa Knight

Andrew Smith (LIC #2316)/Alexa Knight

May 22, 2026 & June 4, 2026

None

None

Yes, however all XRF readings tested <1.0 mg/cm2

No, per EPA/CTDEEP memo dated January 26, 2004

Add’l Haz./Reg. Mat./Waste/Items: Yes (See Table 6)

Additional Notes:

The salt shed building is located at the Groton Maintenance Facility, 150 Welles Road in Groton, Connecticut. The building is scheduled for future demolition as part of site-wide renovations.

TABLES

ND Asbestos was not detected Trace Asbestos was observed at a level of 1% or less NA/PS Not Analyzed/Positive Stop + Although found to be negative by analysis, material is homogeneous to a determined ACM and therefore must be considered positive 1 NOB Result confirmed by TEM analyses

* Quantified by EPA 400 Point Count Method

TABLE 1

BULK SAMPLE SUMMARY OF SUSPECT ASBESTOS CONTAINING MATERIALS

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Sample No. Sample Location Type of Homogeneous Material % and Type Asbestos

1 A side electrical panel conduit EP 1 - Black electrical puddy on conduit penetrations

ND1

2 A side electrical panel conduit EP 1 - Black electrical puddy on conduit penetrations

ND

3 A side interior VB1 - Black vapor barrier behind interior plywood panels

ND1

4 B side interior VB1 - Black vapor barrier behind interior plywood panels

ND

5 B side exterior C1 - Grey exterior caulk ND1

6 D side exterior C1 - Grey exterior caulk ND

7 C side exterior C2 - Red louvre caulk ND1

8 C side exterior C2 - Red louvre caulk ND

9 C side exterior VB2 - Black vapor barrier under exterior shakes

ND1

10 B side exterior VB2 - Black vapor barrier under exterior shakes

ND

11 B side interior C3 - Black support beam base caulk ND1

12 D side interior C3 - Black support beam base caulk ND

13 D side roof RS1 - Grey rubber roof membrane sealant

ND1

14 B side roof RS1 - Grey rubber roof membrane sealant

ND

15 D side roof G1 - Yellow rubber membrane glue on gypsum roof boards

ND1

16 B side roof G1 - Yellow rubber membrane glue on gypsum roof boards

ND

17 D side roof SHR1 - Grey gypsum roof board ND

18 B side roof SHR1 - Grey gypsum roof board ND

19 D side roof VB3 - Blue vapor barrier paper between gypsum roof board and plywood roof deck

ND1

20 B side roof VB3 - Blue vapor barrier paper between gypsum roof board and plywood roof deck

ND

ND Asbestos was not detected Trace Asbestos was observed at a level of 1% or less NA/PS Not Analyzed/Positive Stop + Although found to be negative by analysis, material is homogeneous to a determined ACM and therefore must be considered positive 1 NOB Result confirmed by TEM analyses

* Quantified by EPA 400 Point Count Method

TABLE 1

BULK SAMPLE SUMMARY OF SUSPECT ASBESTOS CONTAINING MATERIALS

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Sample No. Sample Location Type of Homogeneous Material % and Type Asbestos

21 D side roof IN1 - White roof insulation under rubber room membrane

ND

22 B side roof IN1 - White roof insulation under rubber room membrane

ND

AHERA Categories = thermal system insulation (TSI), surfacing material or miscellaneous NESHAP Categories = friable, category I non-friable or category II non-friable Friable = crumbled, pulverized or reduced to powder by hand pressure when dry Category I Non-friable = packings, gaskets, resilient floor covering and asphalt roofing Category II Non-friable = all non-friable that is not Category I

TABLE 2

IDENTIFIED ASBESTOS CONTAINING MATERIALS (>1%)

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Material Sampled/ Assumed (mo/yr)

General Location NESHAP Category

AHERA

Category

Estimated Quantity

No asbestos-containing materials were identified in the subject area.

TABLE 3

CONFIRMED NON-ASBESTOS CONTAINING MATERIALS (<1%)

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Material General Location

EP1 - Black electrical puddy on conduit penetrations A side electrical panel conduit VB1 - Black vapor barrier behind interior plywood panels Behind plywood panels on interior

C1 - Grey exterior caulk B & D side exterior C2 - Red louvre caulk C side exterior VB2 - Black vapor barrier under exterior shakes Under exterior shakes C3 - Black support beam base caulk Interior around base of beam supports RS1 - Grey rubber roof membrane sealant Roof G1 - Yellow rubber membrane glue on gypsum roof boards On gypsum roof boards

SHR1 - Grey gypsum roof board Roof VB3 - Blue vapor barrier paper between gypsum roof board and plywood roof deck Between gypsum roof board and plywood roof deck

IN1 - White roof insulation under rubber roof membrane Under rubber roof membrane

TABLE 4

SUMMARY OF LEAD PAINT XRF MEASUREMENTS

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Structure No. of Measurements Calibrations Void Lead

Detected No Lead Detected

Groton MF Salt Shed 30 7 3 3 17

See Lead Paint XRF Measurement Table in Appendix H.

TABLE 5

SUMMARY OF COMPOSITE BUILDING MATERIAL WASTE CHARACTERIZATION

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Waste Stream Metal mg/L Leachate Hazardous/Non-Hazardous

Salt Shed Bldg. Material

Composite (Excluding metal substrates and clean concrete/brick)

No TCLP sample for Lead warranted as XRF readings on non-metallic components were all below 1.0 mg/cm2 and therefore the debris is presumed as non-hazardous per

CTDEEP/USEPA clarification memo of January 26, 2004.

Note: Any metal components should be recycled to promote waste minimization efforts, rather than disposed of, and the recycling operation is exempt from the USEPA RCRA and CTDEEP Hazardous Waste regulations.

See Appendix I for CTDEEP/USEPA clarification memo of January 26, 2004.

CRW- Connecticut Regulated Waste – PCBs (CR01), Oils (CR02/CR03), waste chemical liquids - antifreeze, latex & solvent paints, sludges, etc. (CR04), waste chemical solids (CR05)

UW- Universal Waste (batteries, thermostat ampoules, fluorescent lamps, used electronics) IH- Inhalation hazard (silicas, etc.)

I- Ignitable - may contain ingredients which are ignitable (materials which have a flashpoint <140oF) (D001) C- Corrosive - may contain ingredients which are alkaline or acidic (materials with a PH<2 or >12.5) (D002) T- Toxic - may contain ingredients which are harmful if swallowed or which release vapors that can cause irritation R- Reactive – may contain ingredients which are unstable, react violently with water or are explosive (D003)

TABLE 6

INVENTORY OF ADDITIONAL HAZARDOUS/REGULATED

MATERIALS, WASTES AND ITEMS IDENTIFIED

GROTON MF SALT SHED

150 WELLES ROAD

GROTON, CONNECTICUT

Quantity Size Material/Item General Location Potential Hazard

1 Motion Sensors/Heat Sensors Salt shed UW - Circuit boards 1 Magnesium chloride tank Salt shed CRW - Waste Chemical Liquid

APPENDIX A

SITE PHOTOS

CTDOT

Groton MF Salt Shed

TRC# 501871-8360-0710

PHOTO 1

Salt Shed Exterior

PHOTO 2

PHOTO 3

PHOTO 4

Salt Shed Interior

PHOTO 5

Salt Shed Interior

PHOTO 6

Salt Shed Roof

APPENDIX B

SITE SKETCH

APPENDIX C

CONNECTICUT STATE HISTORICAL

PRESERVATION OFFICE SITE REVIEW

APPENDIX D

TRC INSPECTORS LICENSES/CERTIFICATIONS

Lookup Detail View Name

Name

ANDREW J SMITH

License Information lookup

License Type License Number

Expiration Date

Granted Date

License Name

License Status

Licensure Actions or Pending Charges

Asbestos Consultant- Inspector

1137 08/31/2026 11/22/2022 ANDREW

J SMITH

ACTIVE CURRENT None

Generated on: 12/19/2025 12:46:10 PM

12/19/25, 12:46 PM Print Lookup Details https://www.elicense.ct.gov/Lookup/PrintLicenseDetails.aspx?cred=2425922&contact=2746664 1/1

Lookup Detail View Name

TYLER J NOLL

License Information lookup

6/8/2026 10:05:20 AM

License Type Asbestos Consultant-Inspector

License Number

Expiration Date 05/31/2027

Granted Date 10/18/2019

License Name

TYLER J NOLL

License Status

ACTIVE

CURRENT

Licensure Actions or Pending Charges None

APPENDIX E

LABORATORY ACCREDITATIONS

State of Connecticut, Department of Public Health Approved Environmental Laboratory

THIS IS TO CERTIFY THAT THE LABORATORY DESCRIBED BELOW HAS BEEN APPROVED BY THE STATE DEPARTMENT OF PUBLIC HEALTH PURSUANT TO APPLICABLE PROVISIONS OF THE PUBLIC HEALTH CODE AND GENERAL STATUTES OF CONNECTICUT, FOR MAKING THE EXAMINATIONS, DETERMINATIONS OR TESTS SPECIFIED BELOW WHICH HAVE BEEN AUTHORIZED IN WRITING BY THAT DEPARTMENT.

TRC ENVIRONMENTAL CORPORATION

LOCATED AT 21 Griffin Road North IN Windsor, CT 06095 AND REGISTERED IN THE NAME OF Stephen Arienti THIS CERTIFICATE IS ISSUED IN THE NAME OF Kathleen Williamson WHO HAS BEEN DESIGNATED BY THE REGISTERED OWNER/AUTHORIZED AGENT TO BE IN CHARGE OF THE LABORATORY WORK COVERED BY THIS CERTIFICATE OF

APPROVAL AS FOLLOWS:

Examination For:

ASBESTOS FIBERS – PCM

ASBESTOS IN BULK – PLM

SEE CERTIFIED PARAMETER LIST FOR SPECIFIC TESTS APPROVED

EFFECTIVE RENEWAL DATE April 1, 2026 THIS CERTIFICATE EXPIRES March 31, 2028 AND IS REVOCABLE FOR CAUSE BY THE STATE DEPARTMENT OF PUBLIC HEALTH

DATED AT HARTFORD, CONNECTICUT, THIS 4th DAY OF March, 2026

Registration No.

PH–0426 Lisa Michelle Morrissey, MPH Deputy Commissioner

Rev. Feb. 2023

STATE OF CONNECTICUT

DEPARTMENT OF PUBLIC HEALTH

ENVIRONMENTAL LAB CERTIFICATION PROGRAM

(ELCP)

CERTIFIED ANALYTES REPORT FOR ALL MATRICES

TRC-Environmental Corporation

PH-0426

21 GRIFFIN ROAD NORTH

ANY QUESTIONS CONCERNING THIS DOCUMENT SHOULD BE ADDRESSED TO THE

ENVIRONMENTAL LABORATORY CERTIFICATION PROGRAM AT (860) 509-7389

REVIEWED BY 2/13/2026 9:46:46 AM

LABORATORY REGISTRATION EXPIRATION DATE :

LABORATORY STATUS :

03/31/2028

APPROVED

WINDSOR, CT 06095

Dawn Shaban

PHONE :

REGISTERED OWNER / AUTHORIZED AGENT :

DIRECTOR :

CO DIRECTOR(S) :

(860) 298-6308

Stephen Arienti

Kathleen Williamson

LABORATORY REGISTRATION EFFECTIVE DATE : 04/01/2026

CT REGISTRATION NUMBER :

APPROVED BY

Lisa Michelle Morrissey, MPH Deputy Commissioner

Connecticut Department of Public Health

Laboratory Consultant

Report Printed on: 2/13/2026 9:46:46 AM Page 1 of 4 TRC-Environmental Corporation

3/4/2026

AIR

STATUS REPORTED ON 2/13/2026

ANALYTE NAME

ASBESTOS

Asbestos Fibers (PCM) NIOSH 7400

Report Printed on: 2/13/2026 9:46:46 AM Page 2 of 4

CONSTRUCTION, RENOVATION & DEMO BLDG

MATERIALS

STATUS REPORTED ON 2/13/2026

ANALYTE NAME

ASBESTOS

Asbestos in Bulk Materials (PLM) 40 CFR Part 763, Subpart E, Appendix E Asbestos in Bulk Materials (PLM) EPA-600-R-93-116

Report Printed on: 2/13/2026 9:46:46 AM Page 3 of 4

THIS IS THE LAST PAGE OF THE REPORT

Report Profile: Lab Name : TRC-Environmental Corporation

Test Name : *

Matrix Name : *

Matrix Selection = ALL OR SOME MATRICES SELECTED

Certifications approved or provisional on 2/13/2026

Report Printed on: 2/13/2026 9:46:46 AM Page 4 of 4

United States Department of Commerce National Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2017

NVLAP LAB CODE: 101424-0

TRC Environmental Corporation Windsor, CT is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:

Asbestos Fiber Analysis

2025-07-01 through 2026-06-30 Effective Dates For the National Voluntary Laboratory Accreditation Program

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.

This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique on ISO/IEC 17025).

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017

For the National Voluntary Laboratory Accreditation Program

Effective

National Voluntary Laboratory Accreditation Program

2025-07-01 through 2026-06-30

TRC Environmental Corporation 21 Griffin Road North Windsor, CT 06095

Ms. Kathleen Williamson Phone: 860-298-6392 Fax: 860-298-6214

Email: kwilliamson@trccompanies.com www.trccompanies.com/

ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 101424-0

Bulk Asbestos Analysis

Code Description 18/A01 EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of

Asbestos in Bulk Insulation Samples

18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials

State of Connecticut, Department of Public Health Approved Environmental Laboratory

THIS IS TO CERTIFY THAT THE LABORATORY DESCRIBED BELOW HAS BEEN APPROVED BY THE STATE DEPARTMENT OF PUBLIC HEALTH PURSUANT TO APPLICABLE PROVISIONS OF THE PUBLIC HEALTH CODE AND GENERAL STATUTES OF CONNECTICUT, FOR MAKING THE EXAMINATIONS, DETERMINATIONS OR TESTS SPECIFIED BELOW WHICH HAVE BEEN AUTHORIZED IN WRITING BY THAT DEPARTMENT.

EMSL ANALYTICAL, INC. – CARLE PLACE

LOCATED AT 528 Mineola Avenue IN Carle Place, NY 11514

AND REGISTERED IN THE NAME OF Nicholas Straccione

THIS CERTIFICATE IS ISSUED IN THE NAME OF Daniel Clarke WHO HAS BEEN DESIGNATED BY THE REGISTERED OWNER/AUTHORIZED AGENT TO BE IN CHARGE OF THE LABORATORY WORK COVERED BY THIS CERTIFICATE OF

APPROVAL AS FOLLOWS:

DRINKING WATER, NON-POTABLE WATER/

ASBESTOS

ENVIRONMENTAL HEALTH & HOUSING

WASTEWATER

Examination For:

BACTERIA & LEGIONELLA

LEAD

Examination For:

FIBERS – PCM, TEM

BULK – PLM, TEM

DRINKING WATER - TEM

Examination For:

LEAD IN PAINT CHIPS

LEAD IN DUST WIPES

LEAD IN SOIL

SEE CERTIFIED PARAMETER LIST FOR SPECIFIC TESTS APPROVED

EFFECTIVE RENEWAL DATE April 1, 2025

THIS CERTIFICATE EXPIRES March 31, 2027

AND IS REVOCABLE FOR CAUSE BT THE STATE DEPT OF PUBLIC HEALTH

DATED AT HARTFORD, CONNECTICUT, THIS 26th DAY OF February, 2025

Registration

PH–0249

Lisa Michelle Morrissey, MPH Deputy Commissioner

REV. FEB 2023

STATE OF CONNECTICUT

DEPARTMENT OF PUBLIC HEALTH

ENVIRONMENT LAB CERTIFICATION PROGRAM (ELCP)

CERTIFIED ANALYTES REPORT FOR ALL MATRICES

EMSL Analytical, Inc.-Carle Place

PH-0249

528 MINEOLA AVE.

ANY QUESTIONS CONCERNING THIS DOCUMENT SHOULD BE ADDRESSED TO THE

ENVIRONMENTAL LABORATORY CERTIFICATION PROGRAM AT (860) 509-7389

REVIEWED BY 2/26/2025 2:07:43 PM

LABORATORY REGISTRATION EXPIRATION DATE :

LABORATORY STATUS :

03/31/2027

APPROVED

CARLE PLACE, NY 11514

Mike Mitchell

PHONE :

REGISTERED OWNER / AUTHORIZED AGENT :

DIRECTOR :

CO DIRECTOR(S) :

(516) 997-7251

Nicholas Straccione

Daniel Clarke

LABORATORY REGISTRATION EFFECTIVE DATE : 04/01/2025

CT REGISTRATION NUMBER :

APPROVED BY

Lisa Michelle Morrissey, MPH Deputy Commissioner

Connecticut Department of Public Health

Laboratory Consultant

Report Printed on: 2/26/2025 2:07:43 PM Page 1 of 6 EMSL Analytical, Inc.-Carle Place

AIR

STATUS REPORTED ON 2/26/2025

ANALYTE NAME

ASBESTOS

ASBESTOS FIBERS (PCM) NIOSH 7400 ASBESTOS FIBERS (TEM) 40 CFR Part 763, Subpart E, Appendix A

Report Printed on: 2/26/2025 2:07:44 PM Page 2 of 6

CONSTRUCTION, RENOVATION & DEMO BLDG

MATERIALS

STATUS REPORTED ON 2/26/2025

ANALYTE NAME

ASBESTOS

ASBESTOS IN BULK MATERIALS (PLM) EPA-600-R-

93-116

ASBESTOS IN BULK MATERIALS (TEM) EPA-600-R-

93-116

Report Printed on: 2/26/2025 2:07:44 PM Page 3 of 6

DRINKING WATER (SDWA)

ANALYTE NAME

MICROBIOLOGY/BACTERIA

Heterotrophic plate count SM9215B Legionella CDC ELITE

METALS

Lead EPA 200.8

ASBESTOS

ASBESTOS IN WATER (TEM) EPA 100.2

Report Printed on: 2/26/2025 2:07:44 PM Page 4 of 6

NON-POTABLE WATER/ WASTEWATER (CWA)

ANALYTE NAME

MICROBIOLOGY/BACTERIA

Heterotrophic plate count SM9215B Legionella CDC ELITE

Report Printed on: 2/26/2025 2:07:44 PM Page 5 of 6

THIS IS THE LAST PAGE OF THE REPORT

Report Profile: Lab Name : EMSL Analytical, Inc.-Carle Place

Test Name : *

Matrix Name : *

Matrix Selection = ALL OR SOME MATRICES SELECTED

Certifications approved or provisional on 2/26/2025

Report Printed on: 2/26/2025 2:07:44 PM Page 6 of 6

United States Department of Commerce National Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2017 is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:

Effective Dates For the National Voluntary Laboratory Accreditation Program

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.

This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique on ISO/IEC 17025).

APPENDIX F

ASBESTOS PLM LABORATORY ANALYSIS DATA

Industrial Hygiene Laboratory 21 Griffin Road North Windsor, CT 06095

(860) 298-6308

69664.CT-DOT.doc

Lab Log #: 0069664

Maintenance Facility Salt Shed, 150 Welles Road, Groton, CT

CLIENT: CT Department of Transportation

Site:

Date Analyzed:

Date Received:

05/26/2026

05/22/2026

Project #: 501871.8360.0710

BULK ASBESTOS ANALYSIS REPORT

Asbestos Type

Other Matrix MaterialsSample No.

Asbestos

POLARIZED LIGHT MICROSCOPY by EPA 600/R-93/116

Sample Location Homogeneous

Material Description

A side electrical panel conduits - - - None1 NDBlack EP 1 - electrical puddy on conduit penetrations

A side electrical panel conduits - - - None2 NDBlack EP 1 - electrical puddy on conduit penetrations

A side interior - - - None3 NDBlack VB1 - vapor barrier behind interior plywood panels

B side interior - - - None4 NDBlack VB1 - vapor barrier behind interior plywood panels

B side exterior - - - None5 NDGrey C1 - exterior caulk

D side exterior - - - None6 NDGrey C1 - exterior caulk

C side exterior - - - None7 NDRed C2 - louvre caulk

C side exterior - - - None8 NDRed C2 - louvre caulk

C side exterior cellulose None9 ND80%Black VB2 - vapor barrier under exterior shakes

B side exterior cellulose None10 ND80%Black VB2 - vapor barrier under exterior shakes

B side interior - - - None11 NDBlack C3 - support beam base caulk

D side interior - - - None12 NDBlack C3 - support beam base caulk

TRC LABORATORY ASBESTOS ANALYTICAL ACCREDITATIONS

NVLAP Lab Code 101424-0

RI #PLM00007 TX #300354

CO# AL-21772

AIHA LAP #100122

VT #An-000020

LA#05011

CT #PH-0426

VA #3333 000283

PA#68-03387

NY #10980

NV #CT00004

WA #C1071

WV #000622

CA #2907

ME LB-0071

AZ #AZ0944

PHIL#ALL-461

MA #AA000052

HI #L-09-004

21 Griffin Road North Windsor, CT 06095

(860) 298-6308

69664.CT-DOT.doc

Asbestos Type

Other Matrix MaterialsSample No.

Asbestos

POLARIZED LIGHT MICROSCOPY by EPA 600/R-93/116

Sample Location Homogeneous

Material Description

Trace - asbestos was observed at level of 1% or less - This is the reporting limit NA/PS - Not Analyzed / Positive Stop SNA - Sample Not Analyzed- See Chain of Custody for details Notes: Asbestos-Containing Material (ACM) is any material containing more than 1% asbestos

The Laboratory at TRC follows 18/01A EPA -- 40 CFR Appendix E to subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples and 18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials which utilize polarized light microscopy (PLM). Our analysts have completed an accredited course in asbestos identification. TRC's Laboratory is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), for Bulk Asbestos Fiber Analysis, NVLAP Code 101424-01. TRC is accredited by the AIHA Laboratory Accreditation Programs AIHA LAP (ID: LAP-100122) in the Industrial Hygiene Program (IHLAP) for PLM. Asbestos content is determined by visual estimate unless otherwise indicated. Quality Control is performed in-house on at least 10% of samples and QC data related to the samples is available upon written request from client.

This report shall not be reproduced, except in full, without the written approval of TRC. This report must not be used by the client to claim product endorsement by NVLAP or any agency of the U.S. Government. This report relates only to the items tested, as received by the laboratory.

ND - asbestos was not detected

Note: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. In those cases, EPA recommends, and certain states (e.g. NY) require, that negative results be confirmed by quantitative transmission electron microscopy.

Analyzed by: Reviewed by Date Issued

05/26/2026Najaat Bhura, Approved SignatoryKathleen Williamson, Laboratory Manager

TRC LABORATORY ASBESTOS ANALYTICAL ACCREDITATIONS

NVLAP Lab Code 101424-0

RI #PLM00007 TX #300354

CO# AL-21772

AIHA LAP #100122

VT #An-000020

LA#05011

CT #PH-0426

VA #3333 000283

PA#68-03387

NY #10980

NV #CT00004

WA #C1071

WV #000622

CA #2907

ME LB-0071

AZ #AZ0944

PHIL#ALL-461

EMSL

528 Mineola Ave, Carle Place, NY 11514 TEM Bulk Chain of Custody Record

Date: 05/26/2026

PO#: C501871 Analysis Type: TEM EPA N.O.B Client: CT DOT Client Job#: 501871.8360.0710 Client Job Ref./Loc. Maintenance Salt Shed, Groton, CT Relinquished by: K. Williamson Received by:

Report to: KWilliamson@trccompanies.com; SArienti@trccompanies.com EPlimpton@trccompanies.com

DCarillo@trccompanies.com KGraff@trccompanies.com NBhura@trccompanies.com GKaczynski@trccompanies.com Sampler’s Name: A. Smith

Turnaround Time: <12 Hour <24 Hour <48 Hour <3 Day 5 Day Other:

For Lab Use Only

Client ID # Lab ID# Description Location Acceptable on Receipt

Comments

1 69664 Puddy See COC 3 69664 Vapor Barrier 5 69664 Caulk 7 69664 Caulk 9 69664 Vapor Barrier 11 69664 Caulk

For Lab Use Only # Spies Total Client # Batch # Results Reported Comments mailto:KWilliamson@trccompanies.com mailto:SArienti@trccompanies.com mailto:EPlimpton@trccompanies.com mailto:DCarillo@trccompanies.com mailto:KGraff@trccompanies.com mailto:NBhura@trccompanies.com mailto:GKaczynski@trccompanies.com

21 Griffin Road North Windsor, CT 06095

(860) 298-6308

69742.CT-DOT.doc

Lab Log #: 0069742

Maintenance Facility Salt Shed, 150 Welles Road, Groton, CT

CLIENT: CT Department of Transportation

Site:

Date Analyzed:

Date Received:

06/04/2026

06/04/2026

Project #: 501871.8360.0710

BULK ASBESTOS ANALYSIS REPORT

Asbestos Type

Other Matrix MaterialsSample No.

Asbestos

POLARIZED LIGHT MICROSCOPY by EPA 600/R-93/116

Sample Location Homogeneous

Material Description

D side roof - - - None13 NDGrey RS1 - rubber roof membrane sealant

B side roof - - - None14 NDGrey RS1 - rubber roof membrane sealant

D side roof - - - None15 NDYellow G1 - rubber membrane glue on gypsum roof boards

B side roof - - - None16 NDYellow G1 - rubber membrane glue on gypsum roof boards

D side roof cellulose None17 ND5%Grey SHR1 - gypsum roof board

B side roof cellulose None18 ND5%Grey SHR1 - gypsum roof board

D side roof - - - None19 NDBlue VB3 - vapor barrier paper between gypsum roof board and plywood roof deck

B side roof - - - None20 NDBlue VB3 - vapor barrier paper between gypsum roof board and plywood roof deck

D side roof synthetic fiber None21 ND90%White IN1 - roof insulation under rubber room membrane

B side roof synthetic fiber None22 ND90%White IN1 - roof insulation under rubber room membrane

TRC LABORATORY ASBESTOS ANALYTICAL ACCREDITATIONS

NVLAP Lab Code 101424-0

RI #PLM00007 TX #300354

CO# AL-21772

AIHA LAP #100122

VT #An-000020

LA#05011

CT #PH-0426

VA #3333 000283

PA#68-03387

NY #10980

NV #CT00004

WA #C1071

WV #000622

CA #2907

ME LB-0071

AZ #AZ0944

PHIL#ALL-461

21 Griffin Road North Windsor, CT 06095

(860) 298-6308

69742.CT-DOT.doc

Asbestos Type

Other Matrix MaterialsSample No.

Asbestos

POLARIZED LIGHT MICROSCOPY by EPA 600/R-93/116

Sample Location Homogeneous

Material Description

Trace - asbestos was observed at level of 1% or less - This is the reporting limit NA/PS - Not Analyzed / Positive Stop SNA - Sample Not Analyzed- See Chain of Custody for details Notes: Asbestos-Containing Material (ACM) is any material containing more than 1% asbestos

The Laboratory at TRC follows 18/01A EPA -- 40 CFR Appendix E to subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples and 18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials which utilize polarized light microscopy (PLM). Our analysts have completed an accredited course in asbestos identification. TRC's Laboratory is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), for Bulk Asbestos Fiber Analysis, NVLAP Code 101424-01. TRC is accredited by the AIHA Laboratory Accreditation Programs AIHA LAP (ID: LAP-100122) in the Industrial Hygiene Program (IHLAP) for PLM. Asbestos content is determined by visual estimate unless otherwise indicated. Quality Control is performed in-house on at least 10% of samples and QC data related to the samples is available upon written request from client.

This report shall not be reproduced, except in full, without the written approval of TRC. This report must not be used by the client to claim product endorsement by NVLAP or any agency of the U.S. Government. This report relates only to the items tested, as received by the laboratory.

ND - asbestos was not detected

Note: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. In those cases, EPA recommends, and certain states (e.g. NY) require, that negative results be confirmed by quantitative transmission electron microscopy.

Analyzed by: Reviewed by Date Issued

06/04/2026Najaat Bhura, Approved SignatoryKathleen Williamson, Laboratory Manager

TRC LABORATORY ASBESTOS ANALYTICAL ACCREDITATIONS

NVLAP Lab Code 101424-0

RI #PLM00007 TX #300354

CO# AL-21772

AIHA LAP #100122

VT #An-000020

LA#05011

CT #PH-0426

VA #3333 000283

PA#68-03387

NY #10980

NV #CT00004

WA #C1071

WV #000622

CA #2907

ME LB-0071

AZ #AZ0944

PHIL#ALL-461

EMSL

528 Mineola Ave, Carle Place, NY 11514 TEM Bulk Chain of Custody Record

Date: 06/04/2026

PO#: C501871 Analysis Type: TEM EPA N.O.B Client: CT DOT Client Job#: 501871.8360.0710 Client Job Ref./Loc. Maintenance Facility Salt Shed, Groton, CT Relinquished by: K. Williamson Received by:

Report to: KWilliamson@trccompanies.com; SArienti@trccompanies.com EPlimpton@trccompanies.com

DCarillo@trccompanies.com KGraff@trccompanies.com NBhura@trccompanies.com GKaczynski@trccompanies.com Sampler’s Name: T. Noll

Turnaround Time: <12 Hour <24 Hour <48 Hour <3 Day 5 Day Other:

For Lab Use Only

Client ID # Lab ID# Description Location Acceptable on Receipt

Comments

13 69742 Roof Membrane Sealant See COC 15 69742 Roof Membrane Glue 19 69742 Vapor Barrier

For Lab Use Only # Spies Total Client # Batch # Results Reported Comments mailto:KWilliamson@trccompanies.com mailto:EPlimpton@trccompanies.com mailto:DCarillo@trccompanies.com mailto:KGraff@trccompanies.com mailto:NBhura@trccompanies.com mailto:GKaczynski@trccompanies.com

APPENDIX G

ASBESTOS TEM LABORATORY ANALYSIS DATA

EMSL Analytical, Inc.

528 Mineola Avenue Carle Place, NY 11514

Tel/Fax: (516) 997-7251 / (516) 997-7528 http://www.EMSL.com / carleplacelab@emsl.com

EMSL Order: 062605633

Customer ID: TRC51

Customer PO: C501871

Project ID:

Attention: Kathleen Williamson Phone: (860) 298-9692

TRC Environmental Consultants Fax: (860) 298-6399

21 Griffin Road North Received Date: 05/27/2026 10:05 AM

Windsor, CT 06095 Analysis Date: 05/29/2026

Collected Date: 05/22/2026

501871.8360.0710, ConnDOT- Groton Maintenance, Facility Salt Shed, 150 Welles Rd, Groton CTProject:

Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via

EPA/600/R-93/116 Section 2.5.5.1

Sample ID Description Appearance % Matrix Material % Non-Asbestos Fibers Asbestos Types

062605633-0001

A Side Electrical Panel

Conduits - EP 1- Black

Electrical Puddy on

Conduit Penetrations

Brown/Black

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605633-0002

A Side Interior - VB1-

Black Vapor Barrier

Behind Interior Plywood

Panels

Black

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605633-0003

B Side Exterior - C1- Grey

Exterior Caulk

Gray

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605633-0004

C Side Exterior - C2 - Red

Louvre Caulk

Brown

Non-Fibrous

Homogeneous

100.0 None No Asbestos DetectedOther

062605633-0005

C Side Exterior - VB2 -

Black Vapor Berrier

Under Exterior Shakes

Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605633-0006

B Side Interior - C3 -

Black Support Beam

Base Caulk

Black

Non-Fibrous

Homogeneous

100.0 None No Asbestos DetectedOther

Analyst(s)

Cristhian Granda (6) Daniel Clarke, Asbestos Laboratory Manager or other approved signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. EMSL recommends that samples reported as none detected or < 1% undergo additional analysis via PLM to avoid the possibility of false negatives.

Samples analyzed by EMSL Analytical, Inc. Carle Place, NY

Initial report from: 05/30/2026 10:37:24

ASB_PLMEPANOB_0012_0002 Printed 5/30/2026 10:38:50AM Page 1 of 1

OrderID: 062605633

OrderID: 062605633

EMSL Analytical, Inc.

528 Mineola Avenue Carle Place, NY 11514

Tel/Fax: (516) 997-7251 / (516) 997-7528 http://www.EMSL.com / carleplacelab@emsl.com

EMSL Order: 062605992

Customer ID: TRC51

Customer PO: 501871.8360.07

Project ID:

Attention: Kathleen Williamson Phone: (860) 298-9692

TRC Environmental Consultants Fax: (860) 298-6399

21 Griffin Road North Received Date: 06/05/2026 10:54 AM

Windsor, CT 06095 Analysis Date: 06/06/2026

Collected Date: 06/04/2026

501871.8360.0710; ConnDOT - Groton Maintenance Facility Salt Shed, 150 Welles Rd, Groton, CTProject:

Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via

EPA/600/R-93/116 Section 2.5.5.1

Sample ID Description Appearance % Matrix Material % Non-Asbestos Fibers Asbestos Types

062605992-0001

D Side Roof - RS1 - Grey

Rubber Roof Membrane

Sealant

White/Black

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605992-0002

D Side Roof - G1 - Yellow

Rubber Membrane Glue on Gypsum Roof Boards

Green/Beige

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

062605992-0003

D Side Roof - VB3 - Blue

Vapor Barrier Paper

Gypsum Roof Board and

Plywood Roof Deck

White/Blue

Non-Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

Analyst(s)

Luisa Vargas (3) Daniel Clarke, Asbestos Laboratory Manager or other approved signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. EMSL recommends that samples reported as none detected or < 1% undergo additional analysis via PLM to avoid the possibility of false negatives.

Samples analyzed by EMSL Analytical, Inc. Carle Place, NY

Initial report from: 06/06/2026 13:03:50

ASB_PLMEPANOB_0012_0002 Printed 6/6/2026 1:05:22PM Page 1 of 1

APPENDIX H

LEAD PAINT XRF MEASUREMENT TABLE

Device(s) : Niton XLP301-A (Serial #22323) X Ray Fluorescence (XRF) Spectrum Analyzer Client : ConnDOT Site : Groton MF Salt Shed Project # : 501871.8360.0710 Date(s) : 5/22/2026 Inspector : Andrew Smith (LIC#2316)/Alexa Knight

1 Shutter Calibration 1.6 0.0 230.4 5/22/2026 9:28 2 0.0 Calibration 0.0 0.0 1.0 1.8 5/22/2026 9:32 3 1.6 Calibration 1.6 0.2 1.2 4.4 5/22/2026 9:33 4 0.7 Calibration 0.7 0.1 1.1 12.2 5/22/2026 9:34 5 Exterior A Pillar Metal Yellow 0.5 0.3 10.0 25.8 5/22/2026 9:38 6 Exterior A Pillar Metal Yellow 0.4 0.4 10.0 30.4 5/22/2026 9:40 7 Exterior A Siding Wood Brown 0.0 0.0 1.0 1.4 5/22/2026 9:44 8 Exterior A Siding Wood Brown 0.0 0.0 1.0 2.4 5/22/2026 9:44 9 Exterior A Electrical Box Metal Brown 0.0 0.0 1.0 2.5 5/22/2026 9:45 10 Exterior A Door Casing Wood White 0.0 0.0 1.0 1.6 5/22/2026 9:46 11 Exterior A Door Casing Wood White 0.0 0.0 1.0 0.4 5/22/2026 9:46 12 Exterior A Door Casing Wood White 0.0 0.0 1.0 1.4 5/22/2026 9:47 13 Exterior B Siding Shakes Brown 0.0 0.0 1.0 2.2 5/22/2026 9:48 14 Exterior B Siding Shakes Brown 0.0 0.0 1.0 2.5 5/22/2026 9:48 15 Exterior B Soffit Wood Brown 0.0 0.0 1.0 2.4 5/22/2026 9:50 16 Exterior B Soffit Wood Brown 0.0 0.0 1.0 1.3 5/22/2026 9:50 17 Exterior C Soffit Wood Brown 0.0 0.1 1.0 0.3 5/22/2026 9:52 18 Exterior C Soffit Wood Brown 0.0 0.0 1.0 1.3 5/22/2026 9:52 19 Exterior C Siding Shakes Brown 0.0 0.0 1.0 2.2 5/22/2026 9:53 20 Exterior D Siding Shakes Brown 0.0 0.0 1.0 2.2 5/22/2026 9:54 21 Exterior D Soffit Shakes Brown 0.0 0.0 1.0 2.0 5/22/2026 9:55 22 Exterior D Light Fixture Metal Black 0.0 0.1 1.4 0.3 5/22/2026 9:57 23 Exterior D Light Fixture Metal Black 0.1 0.3 2.7 0.4 5/22/2026 9:57

Lead Based Paint Measurement Summary Table

Date/TimeColor Reading (mg/cm2)

Precision (mg/cm2)

Depth Index

Duration (sec)Number Floor Side Structure Feature Material

Lead paint includes paint found to contain any detectable amount of lead by Atomic Absorption Spectrophotometry (AAS) or X-Ray Fluorescence (XRF). Side A = Street side; Sides B,C,D follow clockwise

Device(s) : Niton XLP301-A (Serial #22323) X Ray Fluorescence (XRF) Spectrum Analyzer Client : ConnDOT Site : Groton MF Salt Shed Project # : 501871.8360.0710 Date(s) : 5/22/2026 Inspector : Andrew Smith (LIC#2316)/Alexa Knight

Lead Based Paint Measurement Summary Table

Date/TimeColor Reading (mg/cm2)

Precision (mg/cm2)

Depth Index

Duration (sec)Number Floor Side Structure Feature Material

24 Void 25 Exterior D Light Fixture Metal Black 0.0 0.1 4.4 2.5 5/22/2026 9:58 26 Void 27 Void 28 0.0 Calibration 0.0 0.0 1.0 1.4 5/22/2026 10:54 29 1.6 Calibration 1.5 0.3 1.1 2.7 5/22/2026 10:54 30 0.7 Calibration 0.6 0.1 1.0 6.6 5/22/2026 10:55

Lead paint includes paint found to contain any detectable amount of lead by Atomic Absorption Spectrophotometry (AAS) or X-Ray Fluorescence (XRF). Side A = Street side; Sides B,C,D follow clockwise

APPENDIX I

COMPOSITE BUILDING MATERIAL

WASTE CHARACTERIZATION DATA

APPENDIX J

RELATED CORRESPONDENCE

This is an External email. Do not click links or open attachments unless you validate the sender and know the content is safe.

ALWAYS hover over the link to preview the actual URL/site and confirm its legitimacy.

From: Arienti, Stephen To: Imig, Daniel R.

Cc: Plimpton, Erik; Gentile, Jonathan; Kaczynski, Gregory; Silverman, Benjamin L.

Subject: RE: [EXTERNAL] Scope Change for 0172-0544 Groton/Stonington Maintenance Facility Date: Tuesday, May 26, 2026 8:53:39 AM Attachments: image001.png image002.png image003.png

Morning Dan, All went well.

No issues.

We held off on touching the roof which sounds like was the right move according to Mike Strong.

We will get the other samples in for now.

Thank you, SIH New England Regional Area Leader Environmental, Health, Safety, and Sustainability (EHS&S)

21 Griffin Road North, Windsor, CT 06095 T 860.298.9692 | C 860.508.9240 | sarienti@trccompanies.com LinkedIn | Instagram | TRCcompanies.com

From: Imig, Daniel R. <Daniel.Imig@ct.gov> Sent: Tuesday, May 26, 2026 8:51 AM To: Arienti, Stephen <SArienti@trccompanies.com> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <JGentile@trccompanies.com>; Kaczynski, Gregory <GKaczynski@trccompanies.com>; Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Subject: RE: [EXTERNAL] Scope Change for 0172-0544 Groton/Stonington Maintenance Facility

Good morning - How did it go on Friday?

Daniel Imig, P.E.

Supervising Engineer Environmental Compliance Section Connecticut Department Of Transportation 2800 Berlin Turnpike Newington, CT 06131 P: 860.594.3455 mailto:Daniel.Imig@ct.gov mailto:EPlimpton@trccompanies.com mailto:JGentile@trccompanies.com mailto:GKaczynski@trccompanies.com mailto:Benjamin.Silverman@ct.gov mailto:sarienti@trccompanies.com http://www.linkedin.com/company/trc-companies-inc https://www.instagram.com/trc_companies/ http://www.trccompanies.com/

This is an External email. Do not click links or open attachments unless you validate the sender and know the

ALWAYS hover over the link to preview the actual URL/site and confirm its legitimacy.

From: Arienti, Stephen <SArienti@trccompanies.com> Sent: Thursday, May 21, 2026 4:09 PM To: Imig, Daniel R. <Daniel.Imig@ct.gov>; Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <jgentile@trccompanies.com>; Kaczynski, Gregory <gkaczynski@trccompanies.com>

EXTERNAL EMAIL: This email originated from outside of the organization. Do not click any links or open any attachments unless you trust the sender and know the content is safe.

Sounds good.

Yeah we would want to get destructive to see all the layers. I was just thinking the edges since the roof looks to be homogeneous and the edges might be a better spot since it wouldn’t be over the salt.

Sent: Thursday, May 21, 2026 4:01 PM To: Arienti, Stephen <SArienti@trccompanies.com>; Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <JGentile@trccompanies.com>; Kaczynski, Gregory <GKaczynski@trccompanies.com>

Assume you are doing the destructive testing near the edges. Not sure how long the salt shed will stay up. I will do some reaching out and be in touch if we want to back off and not do it.

Environmental Compliance Section Connecticut Department Of Transportation 2800 Berlin Turnpike

From: Arienti, Stephen <SArienti@trccompanies.com> Sent: Thursday, May 21, 2026 3:44 PM To: Imig, Daniel R. <Daniel.Imig@ct.gov>; Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> mailto:SArienti@trccompanies.com mailto:Daniel.Imig@ct.gov mailto:Benjamin.Silverman@ct.gov mailto:EPlimpton@trccompanies.com mailto:jgentile@trccompanies.com mailto:gkaczynski@trccompanies.com mailto:sarienti@trccompanies.com https://urldefense.com/v3/__http:/www.linkedin.com/company/trc-companies-inc__;!!EAPaXxOOW7smCwU!ksHtIJJRbZH4RqY8ebCHwr1PerqY-Yy8qvrSIdZmw6LavDWe7zKuXRtY9NxZHomtXVawKlAs2Zoe6DF5BgD8ErY$ https://urldefense.com/v3/__https:/www.instagram.com/trc_companies/__;!!EAPaXxOOW7smCwU!ksHtIJJRbZH4RqY8ebCHwr1PerqY-Yy8qvrSIdZmw6LavDWe7zKuXRtY9NxZHomtXVawKlAs2Zoe6DF5_fo3VFI$ https://urldefense.com/v3/__http:/www.trccompanies.com/__;!!EAPaXxOOW7smCwU!ksHtIJJRbZH4RqY8ebCHwr1PerqY-Yy8qvrSIdZmw6LavDWe7zKuXRtY9NxZHomtXVawKlAs2Zoe6DF5bTt7aWc$ mailto:Daniel.Imig@ct.gov mailto:SArienti@trccompanies.com mailto:Benjamin.Silverman@ct.gov mailto:EPlimpton@trccompanies.com mailto:JGentile@trccompanies.com mailto:GKaczynski@trccompanies.com mailto:SArienti@trccompanies.com mailto:Benjamin.Silverman@ct.gov

This is an External email. Do not click links or open attachments unless you validate the sender and know the

ALWAYS hover over the link to preview the actual URL/site and confirm its legitimacy.

Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <jgentile@trccompanies.com>; Kaczynski, Gregory <gkaczynski@trccompanies.com>

EXTERNAL EMAIL: This email originated from outside of the organization. Do not click any links or open any attachments unless you trust the sender

Thank you.

Lastly, I wanted to ask about sampling the roof for asbestos. The report indicts that a new roof was put on the salt shed back in 2019 and has a warranty on it. I know we get no asbestos letters for the products when they do those projects too. We can cut into the roof near the edges to inspect for suspect materials and try our best to patch those areas, but just wanted to run it by Ben and you.

I know eventually it is going to be demolished but I assume it might not be for a while.

Sent: Thursday, May 21, 2026 3:27 PM To: Arienti, Stephen <SArienti@trccompanies.com>; Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <JGentile@trccompanies.com>; Kaczynski, Gregory <GKaczynski@trccompanies.com>

Should be fine. I sent an email to the GS and left him a vm so he knows you are coming.

Environmental Compliance Section Connecticut Department Of Transportation 2800 Berlin Turnpike

Sent: Thursday, May 21, 2026 2:47 PM To: Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> mailto:EPlimpton@trccompanies.com mailto:jgentile@trccompanies.com mailto:gkaczynski@trccompanies.com mailto:sarienti@trccompanies.com https://urldefense.com/v3/__http:/www.linkedin.com/company/trc-companies-inc__;!!EAPaXxOOW7smCwU!hQ2lfrrkDNMsXmD6q17VF0vjHdBCCESfotUyiQyp64mHWgIV5-wILtqr00DeSrs3s1zORKhBFXKhGIFsaANrbJ4$ https://urldefense.com/v3/__https:/www.instagram.com/trc_companies/__;!!EAPaXxOOW7smCwU!hQ2lfrrkDNMsXmD6q17VF0vjHdBCCESfotUyiQyp64mHWgIV5-wILtqr00DeSrs3s1zORKhBFXKhGIFsNLP2-hY$ https://urldefense.com/v3/__http:/www.trccompanies.com/__;!!EAPaXxOOW7smCwU!hQ2lfrrkDNMsXmD6q17VF0vjHdBCCESfotUyiQyp64mHWgIV5-wILtqr00DeSrs3s1zORKhBFXKhGIFsTog_67U$ mailto:Daniel.Imig@ct.gov mailto:SArienti@trccompanies.com mailto:Benjamin.Silverman@ct.gov mailto:EPlimpton@trccompanies.com mailto:JGentile@trccompanies.com mailto:GKaczynski@trccompanies.com mailto:Benjamin.Silverman@ct.gov

This is an External email. Do not click links or open attachments unless you validate the sender and know the

ALWAYS hover over the link to preview the actual URL/site and confirm its legitimacy.

Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <jgentile@trccompanies.com>; Kaczynski, Gregory <gkaczynski@trccompanies.com>; Imig, Daniel R. <Daniel.Imig@ct.gov>

EXTERNAL EMAIL: This email originated from outside of the organization. Do not click any links or open any attachments unless you trust the sender

Afternoon Ben, We plan to send a crew out tomorrow to the Groton Salt Shed, if that works for everyone.

Let us know.

From: Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Sent: Wednesday, May 20, 2026 11:00 AM To: Arienti, Stephen <SArienti@trccompanies.com> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <JGentile@trccompanies.com>; Kaczynski, Gregory <GKaczynski@trccompanies.com>; Imig, Daniel R. <Daniel.Imig@ct.gov>

Good morning, Please see the attached plan showing the final condition after the salt shed is demolished. I’ve also attached the most recent inspection report for the building. That’s all we have. Is this enough for you to complete the inspection?

Ben Silverman Transportation Engineer 2 Connecticut Department of Transportation Environmental Compliance Unit Office: 860-594-2763 Cell: 774-249-1753 benjamin.silverman@ct.gov

Sent: Tuesday, May 19, 2026 11:18 AM To: Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <jgentile@trccompanies.com>; Kaczynski, Gregory <gkaczynski@trccompanies.com>; Imig, Daniel R. <Daniel.Imig@ct.gov> Subject: RE: [EXTERNAL] Scope Change for 0172-0544 Groton/Stonington Maintenance Facility mailto:EPlimpton@trccompanies.com mailto:jgentile@trccompanies.com mailto:gkaczynski@trccompanies.com mailto:Daniel.Imig@ct.gov mailto:sarienti@trccompanies.com https://urldefense.com/v3/__http:/www.linkedin.com/company/trc-companies-inc__;!!EAPaXxOOW7smCwU!iOqQAvIGqUnuzlsvk7NKm0P0DXCbBQwH1VoF_HGWvO6fVXP1WplATqqq89xXbwDueAJNuJCa1CrXKGJxeD7cQvQ$ https://urldefense.com/v3/__https:/www.instagram.com/trc_companies/__;!!EAPaXxOOW7smCwU!iOqQAvIGqUnuzlsvk7NKm0P0DXCbBQwH1VoF_HGWvO6fVXP1WplATqqq89xXbwDueAJNuJCa1CrXKGJx4Rj69bE$ https://urldefense.com/v3/__http:/www.trccompanies.com/__;!!EAPaXxOOW7smCwU!iOqQAvIGqUnuzlsvk7NKm0P0DXCbBQwH1VoF_HGWvO6fVXP1WplATqqq89xXbwDueAJNuJCa1CrXKGJxwbUnqpM$ mailto:Benjamin.Silverman@ct.gov mailto:SArienti@trccompanies.com mailto:EPlimpton@trccompanies.com mailto:JGentile@trccompanies.com mailto:GKaczynski@trccompanies.com mailto:Daniel.Imig@ct.gov mailto:benjamin.silverman@ct.gov mailto:SArienti@trccompanies.com mailto:Benjamin.Silverman@ct.gov mailto:EPlimpton@trccompanies.com mailto:jgentile@trccompanies.com mailto:gkaczynski@trccompanies.com

This is an External email. Do not click links or open attachments unless you validate the sender and know the

ALWAYS hover over the link to preview the actual URL/site and confirm its legitimacy.

EXTERNAL EMAIL: This email originated from outside of the organization. Do not click any links or open any attachments unless you trust the sender

No problem. We still have some funds left under 524-8360 for Task 710/720 that we should be able to make work.

I tried to get into Compass for the project and it says no access. Anything you can find will be helpful.

Thanks, From: Silverman, Benjamin L. <Benjamin.Silverman@ct.gov> Sent: Tuesday, May 19, 2026 10:56 AM To: Arienti, Stephen <SArienti@trccompanies.com> Cc: Plimpton, Erik <EPlimpton@trccompanies.com>; Gentile, Jonathan <JGentile@trccompanies.com>; Kaczynski, Gregory <GKaczynski@trccompanies.com>; Imig, Daniel R. <Daniel.Imig@ct.gov> Subject: [EXTERNAL] Scope Change for 0172-0544 Groton/Stonington Maintenance Facility Importance: High

Hi Steve, Busy times… I was just informed the project has added the demolition of the salt shed in Groton to their scope. They’ve asked for the supporting inspection to be completed ASAP. I have reached out for any helpful, tangible information (such as plans) and if I get anything I will forward it to you. Do you need a Mod for this effort? Please let me know.

Thanks, Ben Silverman Transportation Engineer 2 Connecticut Department of Transportation Environmental Compliance Unit Office: 860-594-2763 Cell: 774-249-1753 benjamin.silverman@ct.gov mailto:sarienti@trccompanies.com https://urldefense.com/v3/__http:/www.linkedin.com/company/trc-companies-inc__;!!EAPaXxOOW7smCwU!kw8fQwhZ-ebItjabj3K9FZRfMH__7CwJTpy-83UWZyQSx4ALoBo5WuDu-JP6BGNPiMENqKDF6oKbH-m9IF4IYZD78Rhe$ https://urldefense.com/v3/__https:/www.instagram.com/trc_companies/__;!!EAPaXxOOW7smCwU!kw8fQwhZ-ebItjabj3K9FZRfMH__7CwJTpy-83UWZyQSx4ALoBo5WuDu-JP6BGNPiMENqKDF6oKbH-m9IF4IYaXsaUy4$ https://urldefense.com/v3/__http:/www.trccompanies.com/__;!!EAPaXxOOW7smCwU!kw8fQwhZ-ebItjabj3K9FZRfMH__7CwJTpy-83UWZyQSx4ALoBo5WuDu-JP6BGNPiMENqKDF6oKbH-m9IF4IYZ2Qiez0$ mailto:Benjamin.Silverman@ct.gov mailto:SArienti@trccompanies.com mailto:EPlimpton@trccompanies.com mailto:JGentile@trccompanies.com mailto:GKaczynski@trccompanies.com mailto:benjamin.silverman@ct.gov

SIH - WinSIH HBM Survey ConnDOT, Groton Maintenance Facility Salt Shed, 150 Welles Rd Groton CT

6/4/2026, 6:38:49 PM UTC

CREATED

5/22/2026, 1:09:43 PM UTC

by Andrew Smith

UPDATED

6/4/2026, 6:38:49 PM UTC

by Kathleen Williamson

STATUS

Complete

ASSIGNED TO

No Assignment

JOB INFORMATION

Site Name Groton Maintenance Facility Salt Shed

Address 150 Welles Rd Groton CT

TRC Project Number 501871.8360.0710

Project Manager Stephen Arienti, Erik Plimpton

Inspector(s) Andrew Smith, Tyler Noll

Client ConnDOT

Type of Asbestos Survey Reno/Demo

Site Sketch Diagrams

Additional Analysis for NOB Materials (Calc)

TEM NY NOB 198.4

PLM Turnaround Time (TAT) 3-day

TEM Turnaround Time (TAT) 3-day

Date May 22, 2026

General Notes Post at front of shed have metal jacket around concrete. Unable to verify if concrete is painted.

Overview Photo

Options & Other Settings

Use auto-numbering? No

Auto-fill gaps? Yes

Alert user about missing site sketch? Yes

SURVEYS PERFORMED Asbestos, LCP, Hazardous Materials Inventory, Demolition Items

Asbestos Survey

Materials & Samples (11 Items)

Materials & Samples - 1. (2) Samples #1–2: EP 1–Black electrical puddy on conduit penetrations

Sample Information

Asbestos Samples (2 Items)

Asbestos Samples - 1. Sample #1: EP 1…A side electrical panel conduits

Sample Number 1

Sample Location A side electrical panel conduits

Asbestos Bulk Analysis PLM EPA 600/R93/116

Grab or Composite Grab

Date May 22, 2026

Time 10:14

Sample Location Photo

Asbestos Samples - 2. Sample #2: EP 1…A side electrical panel conduits

Sample Number 2

Sample Location A side electrical panel conduits

Asbestos Bulk Analysis PLM EPA 600/R93/116

Grab or Composite Grab

Date May 22, 2026

Time 10:14

Sample Location Photo

Material Information

Sampled or Assumed? Sampled

Material Acronym EP 1

Material Description Black electrical puddy on conduit penetrations

Material Color Black

Representative Photos

Analyze by layer? No

Is material non-friable organically bound (NOB)?

Yes

Homogeneous Area

Total Approximate Quantity

Notes

Materials & Samples - 2. (2) Samples #3–4: VB1–Black vapor barrier behind interior plywood panels

Sample Information

Asbestos Samples (2 Items)

Asbestos Samples - 1. Sample #3: VB1…A side interior

Sample Number 3

Sample Location A side interior

Asbestos Bulk…