Refurbish Circuit Breaker (Eaton Corp) for Generator at Detroit Dam, Oregon
Added: Sep 24, 2016 1:58 pm PERFORMANCE WORK STATEMENTRefurbish Detroit Circuit Breaker XJ2PR 161T0121 General Description1.1 Background The Eaton type 150VCP-WG63 circuit breaker is the circuit breaker for generator 2 at Detroit Dam, Oregon. During maintenance in May, 2012 the wipe measurement for phases A and C was observed to be unsatisfactory per the factory operation and maintenance manual. The breaker was removed from service and is in need of repair.1.2 Scope This scope of work (SOW) covers repair, refurbishment and testing of an Eaton type VCP-W vacuum circuit breaker for the Willamette Valley Project Office. In addition, a closure test tool shall be supplied with the refurbished breaker. Satisfactory completion of this work requires that parts be furnished and installed per factory procedures to restore the breaker to original factory performance standards as verified by testing performed in accordance with the factory's operation and maintenance manual (I.B. 32-255-1G - Eaton "Instructions for Installation, Operation and Maintenance of Type VCP-W Vacuum Circuit Breakers"). The full set of requirements is described in detail in section 3.1.3 Technical Point of Contact:Name/title: Steve Tanner, Electrical EngineerMailing Address: Foster DamPO Box 807Foster, OR 97345Email: steven.a.tanner@usace.army.milOffice Phone: 541-367-5124, X 362 Applicable Documents2.1 ANSI/IEEE C37.04 - Standard Rating Structure for AC HV Circuit Breakers2.2 ANSI/IEEE C37.06 - Preferred Ratings for AC HV Circuit Breakers2.3 ANSI/IEEE C37.09 - Standard Test Procedure for AC HV Circuit Breakers2.4 I.B. 32-255-1G - Eaton "Instructions for Installation, Operation and Maintenance ofType VCP-W Vacuum Circuit Breakers".3 Requirements3.1 Repair and Reconditioning Services 3.1.1 Replace all tee vacuum pole assemblies with new assemblies of the same or superseding type meeting IEEE/ANSI C37.04 and C37.06 standards.3.1.2 Install X-Washers kit per figure 6-1b of I.B. 32-255-1G.3.1.3 Class 2 reconditioning service per Eaton services brochure3.2 Supplied Equipment3.2.1 Closure test tool, part #: (6352C58G01)3.3 Nameplate Information All parts and repairs must be compatible with the Eaton type VCP-WG63 circuit breaker. Parts shall be rated to meet or exceed the performance ratings specified on the breaker nameplate, given as:Type: 150VCP-WG63Maximum Voltage (V): 15 kV rmsVoltage Range Factor (K): 1.0Power Frequency: 60 HzContinuous Current: 3000 A rmsLightning Imp. Withstand Voltage: 95 kV peakPeak Standard Operating Duty: O-0.3s-CO-3m-CO Interrupting Time: 83 ms Short-Circuit Current (I): 63 kA rms -dc Component: 75 % -Close & Latch Current: 173 kA Peak -Duration of Short-Time Current: 3 Sec Out of Phase Switching Current: 31.5kA rmsYear / Serial Number: 02060877Weight: 525 Lbs.Instruction Book Number: 32-255-1FParts List (Style) Number: 4A35145G26Option Number: 20210200010000000000Wiring Diagram Number: 691C386H44Motor Voltage Range: 125 Vdc/acClose Control Voltage Range: 100-140 VdcClose Current 6.6 A Trip #1 Control Voltage Range: 70-140 Vdc Trip #1 Current: 6.6 A Trip #2 Control Voltage Range: N.A.Trip #2 Current: N.A.Undervoltage Trip Voltage: N.A.3.4 Breaker Testing Following all repairs and reconditioning, the circuit breaker shall be tested and certified by the manufacturer. Testing shall follow ANSI/IEEE C37.09 test procedures and include, at a minimum, insulation resistance, contact resistance, timing and over-potential tests. A report with the test results and certification that the breaker meets Eaton's performance specifications and that it is suitable for safe operation shall be submitted to the Government.3.5 Warranty A 12 month warranty will be provided to the Government.3.6 Shipping The circuit breaker shall be picked up at Detroit Dam, 40990 Hwy 22, Mill City, OR 97360. The Government shall pack and crate the VCP-W breaker prior to pick-up. The Government shall be provided at least two-week notice prior to the scheduled date of pick-up. After repairs are complete and satisfactory test results are submitted to the Government, the breaker shall be delivered free on board (FOB) to Detroit Dam. The Government shall not be responsible for the cost of shipping back to Detroit Dam. The Government shall not be responsible for damage or loss of the VCP-W breaker during shipping or while being stored away from Detroit Dam. W66QKZ53131641 Department of the Army Corps of Engineers Engineering District Portland
Award Notice 1/1 9/24/16, 1:58 PM