SOUTHSIDE ELECTRIC COOPERATIVE
SEC Construction Specifications and Drawings Prepared by Southside Electric Engineering Utilizing:
Page # Pole Assembly Units 1 Costruction Specifications for Poles and Crossarms 2 Conductor Assembly Units 5 Conductor Installation Specifications 6 Clearence Diagrams 8 Tying Guides 11 Construction Specifications for Pole Top Assembly Units 19 Single Phase Primary Pole Top Assembly Units 21
VA1.01 Single Support - Miscellaneous 22 VA1.011 Single Support - Miscellaneous 22 VA1.1 Single Support (Tangent) 23 VA1.1 - AC Tangent Aerial Cable 24 VA1.11 Single Support (Tangent) on Crossarm 25 VA2.021 Double Support - Miscellaneous 26 VA2.1 Double Support (Shallow Angle) 27 VA2.1 - AC Angle Aerial Cable 28 VA2.21 Double Support - Miscellaneous 29 VA3.1 Suspension Angle 30 VA4.1 Dead End Angle (90°-150°) 31 VA4.2 Dead End Angle (20°-90°) 32 VA5.1 Single Dead End 33 VA5.1 - AC Dead End Aerial Cable 34 VA5.3 Single Dead End - Miscellaneous 35 VA5.4 Single Dead End - Miscellaneous 36 VA5.21 Single Dead End on Crossarms 37 VA5.31 Single Dead End on Crossarms 37 VA6.1 Double Dead End (Straight) 38 VA6.2 Double Dead End (Feed Through) 39 VA6.21 Double Dead End on Crossarms 40 VA1.12G Single Phase Junction Guide 41 VA5.5G Single Phase Tap Guide 42
Two Phase Primary Pole Top Assembly Units 43 VB1.11L Single Support on Crossarm (Tangent) 44 VB1.14L Single Support, Neutral on Crossarm 45 VB2.21L Double Support on Crossarms (Shallow Angle) 46 VB2.22L Double Support Neutral on Crossarms (Shallow Angle) 47 VB3.1 Suspension Angle 48 VB4.1 Deadend Angle (90°-150°) 49 VB5.1 Single Deadend -Vertical 50 VB5.21 Single Deadend on Crossarms 51 VB5.31 Single Deadend on Crossarms 51 VB6.21 Double Deadend on Crossarms 52
Overhead Construction i
Three Phase Primary Pole Top Assembly Units 53 VC1.11 Single Support on Crossarm (Tangent) 54 VC1.11L Single Support on Crossarm (Tangent) (Large Conductors) 55 VC1.41 Single Support, Neutral on Crossarm 56 VC1.41L Single Support, Neutral on Crossarm (Large Conductors) 57 VC2.21 Double Support on Crossarms (Shallow Angle) 58 VC2.21L Double Support on Crossarms (Large Conductors) 59 VC2.51 Double Support Neutral on Crossarms 60 VC2.51L Double Support Neutral on Crossarms (Large Conductors) 61 VC2.52 Double Support on 10ft Crossarms 62 VC2.52L Double Support on 10ft Crossarms (Large Conductors) 63 VC3.1 Suspension Angle 64 VC3.2L Suspension Angle (Large Conductors 65 VC4.2L Deadend Angle (Large Conductors) 66 VC5.2L Single Deadend -Vertical - (Large Cond.) 67 VC5.21 Single Deadend on 2 Crossarms 68 VC5.31 Single Deadend on 3 Crossarms 68 VC5.51-XF Single Deadend on 10ft Fiberglass X-arm 69 VC5.71-XF Single Deadend on 1 Fiberglass X-arm 70 VC5.91-XF Single Deadend on 12ft Fiberglass X-arm 71 VC6.21 Double Deadend on 2 Crossarms 72 VC6.31 Double Deadend on 3 Crossarms 72 VC6.31-XF Double Deadend on 1 Fiberglass X-arm 73 VC6.51 Double Deadend on 10ft Crossarms 74 VC6.51-XF Double Deadend on 10ft Fiberglass X-arm 75 VC6.91-XF Double Deadend on 12ft Fiberglass X-arm 76 VC1.81G Three Phase Junction Guide 77 VC5.11G Single Phase Tap Guide 78 VC5.82G Three Phase Horizontal Tap "Buckarm" Guide 79
Double Circuit Primary Pole Top Assembly Units 80 VD1.83L Single Support on Crossarms (Tangent) 81 VD2.91L Double Support on Crossarms (Shallow Angle) 82 VD6.91 Double Deadend on Crossarms 83 VD3.1G Double Ckt Suspension Angle Guide 84 VD4.2LG Double Ckt Deadend Guide 85 VD5.91G Double Ckt Three Phase Tap Guide 86 ii
Guying Assembly Units 87 Construction Specifications for Guying Assembly Units 88
E1.01 Single Overhead Guy 89 E2.01 Single Overhead Guy - Heavy Duty 89 E2.01X Single Overhead Guy w/ Guy Strain Insulator 90 E2.1 Single Down Guy - Heavy Duty 91 E2.1X Single Down Guy w/ Guy Strain Insulator 92 E3.10X Guy Marker 93 E5.1X Guy Strain Insulator 94 E2.3G Three Down Guy Guide 95 E2.4G Four Down Guy Guide 96
Anchor Assembly Units 97 Construction Specifications for Anchoring 98
F1.8 Expanding Anchor 5/8" x 7'0" Rod 99 F1.12 Expanding Anchor 3/4" x 8'0" Rod 99 F2.12 Screw Anchor (Power Installed) 100 F2.X Multihelix Power Installed Screw Anchor 101 F5.3 Rock Anchor 102 F6.8 Swamp Anchor (Power Installed) 103
Transformer Assembly Units 104 Construction Specifications for Transformer Connections 105
VG1.4 Single Phase Transformer, Multi-Phase Pole, Cutout Protection 106 VG1.5 Single Phase Transformer, Single Phase Pole, Cutout Protection 106 VG1.6 Single Phase Transformer, Single Phase Pole, Cutout Protection 107 VG1.7 Single Phase Transformer Tangent 108 VG1.8 Single Phase Transformer Deadend 109 VG1G Single Phase Transformer Guide 110 VG2.1 Two-Phase Transformer Bank - Open Delta 111 VG2.1G Two-Phase Transformer Bank - Open Delta Guide 112 VG3.1 Three-Phase Transformer Bank - Delta 113 VG3.1G Three-Phase Transformer Bank - Delta Guide 114 VG3.2 Three-Phase Transformer Bank - Corner Grounded Delta 115 VG3.2G Three-Phase Transformer Bank - Corner Grounded Delta Guide 116 VG3.3 Three-Phase Transformer Bank - Wye 117 VG3.3G Three-Phase Transformer Bank - Wye Guide 118
Grounding Assembly Units 119 Construction Specifications for Grounding 120
H1.1 Grounding Assembly - Ground Rod Type 121 H3.1 Grounding Assembly - Ground Rod Type (For Airbreak Switch) 122 H4.1 Grounding Assembly - Platform Type (For Airbreak Switch) 123 iii
Secondary Assembly Units 124 Construction Specifications for Secondaries and Service Drops 125
J1.2 Secondary Assembly - Double Upset Bolt (Small Angle) 126 J1.2-C Transfer of Tangent Communication Attachment 127 J3.1 Secondary Assembly - Swinging Clevis (Deadend) 128 J9.1X Secondary Assembly - Dead End Shoe 129 J9.1X-C Transfer of Dead End Communication Attachment 130 K1.1 Service Assembly - Stationary Clevis (Pole Mounted) 131 K1.3 Service Assembly - Swinging Clevis (House Mounted) 132 K2.1 Service Assembly - House Knob 133 K3.1 Service Assembly - Mast Pole 134 K4.3 Service Assembly - Overhead Feed Underground Load 135 K4.4 Service Assembly - Overhead Feed Overhead Load (Loop) 136 M265.1 100W HPS Security Light 137 M265.2 150W HPS Security Light 137 M265.3 200W HPS Security Light 137 M265.4 175W MV Security Light 137 M265.5 150W Darksky Compliant HPS Security Light 137 M264.6 200W Darksky Compliant HPS Security Light 137
Protection Assembly Units 138 N1.1 Neutral Assembly - Tangent 139 N1.11 Neutral Supports on Crossarms 140 N2.21 Neutral Supports on Crossarms 140 N2.1 Neutral Assembly - Small Angle 141 N3.1 Neutral Assembly - Large Angle 141 N5.1 Neutral Assembly (Single Deadend) 142 N5.2 Neutral Assembly (Single Deadend) 142 N6.1 Neutral Assembly - Double Deadend 143 N6.21 Neutral Assembly - Double Deadend on Crossarm 144
Protection Assembly Units 145 P2.1 Pole Protection Assembly - Plate Type 146 VP1.01 Surge Arrester - Single Phase 147 VP1.1 Surge Arrester - Single Phase 147 VP1.2 Surge Arrester - Two Phase 148 VP1.3 Surge Arrester - Three Phase 148 iv
Metering Assembly Units 149 Q1.1 Secondary Metering - Single Phase 120/240V 150 Q3.1 Secondary Metering - Three Phase Delta 151 Q3.2 Secondary Metering - Three Phase Corner Grounded Delta 152 Q3.3 Secondary Metering - Three Phase Wye 153 VQ4.1 Primary Metering - Three Phase Wye 154
Recloser Assembly Units 155 VR1.2 Oil Circuit Recloser (with Bypass Cutout) 156 VR1.2-VT Vacuum Circuit Recloser (with Bypass Cutout) 157 VR2.2 (Two) Oil Circuit Reclosers (with Bypass Switches) 158 VR3.2 (Three) Oil Circuit Reclosers (with Bypass Switches) 158 VR3.2-TS Three Phase Vacuum Circuit Recloser (with Bypass Switches) 159 VR3.1 (Three) Oil Circuit Reclosers 160
Sectionalizing Assembly Units 161 VS1.01 Cutout 162 VS1.01X Cutout with Solid Barrel 163 VS1.1 Single Phase Cutout on Bracket 164
VS1.1S Single Phase Cutout with Electronic Sectionalizer Barrel 165 VS1.1X Single Phase Cutout on Bracket with Solid Barrel 166 VS1-T Single Target 167 VS2.21 600A Disconnect Switches (Two Single-Phase) 168 VS2.31 600A Disconnect Switches (Three Single-Phase) 169 VS2.31-X 600A Disconnect Switches (Cutout Style Mounting) 170 VS2.32 Group-Operated Airbreak Switch (Three Phase) 171
Voltage Alteration Equipment Assembly Units 172 VY1.1 Voltage Regulator, Pole Mounted (One Single-Phase) 173 VY1.3 Voltage Regulators, Platform Mounted (Three Singe-Phase) 174 VY2.1 Autotransformer, Pole Mounted (Step-Down) 175 VY2.3 Autotransformer, Platform Mounted (3 Step-Downs) 176 VY3.3 Three Phase Capacitor Bank 177 VY3.4 Three Phase Capacitor Switch Bank 178 v
VS1.01S Single Phase Cutout with Electronic Sectionalizer Barrel 165
General Requirements for Underground Construction 179 Cable Assembly Units 188 Underground Cable Clearence Diagrams 189 Underground Primary Terminal Pole Assembly Units 191
UA2 Single Phase Cable Deadened Terminal Pole 192 UA3 Single Phase Cable Tangent Pole 193 UB2 Two Phase Cable Terminal Pole - Bracket Mounted Arresters 194 UC2 Three Phase Cable Terminal Pole - Bracket Mounted Arresters 195 UC2-1 Three Phase Cable Deadend Terminal Pole 196 UC2-2 Three Phase Cable Tangent Terminal Pole 197 UC5-1 Three Phase Cable Deadend Terminal Pole w/ 600A switches 198 UC6-1 Three Phase Cable Tangent Terminal Pole w/ 600A switches 199
Underground Transformer Assembly Units 200 UG7 Single Phase Pad Mounted Transformer (Loop Feed) 201 UG17-2 Three Phase Pad Mount Transformer (Loop Feed) 202 UX1 Open Delta Connection with Single Phase Transfomers Guide 203
Underground Secondary and Service Assembly Units 204 UJ1-4 Secondary Connector Blocks 205 UJ2-4 Secondary Connector Blocks 205 UJ2-6 Secondary Connector Blocks 205 UK6 Secondary Handhole Underground Cable 206
Underground Construction vi
Underground Construction
Miscellaneous Underground Assembly Units 207 UM1-5NC Pad Assembly 208 UM1-7NC Ground Sleeve Assembly 209 UM3-14 Single Phase Sectionalizing Enclosure 210 UM3-45 Single Phase Pad Mounted Sectionalizer or Recloser 211 UM3E-1 Single Pole Switching 200A enclosure 212 UM3E-3 Fuse Enclosure 200-600A Three Phase 212 UM3E-1G Single Pole Switching 200A enclosure Wiring Guide 213 UM3E-3G Fuse Enclosure 200-600A Three Phase Wiring Guide 214 UM5 Secondary Cable Terminal Pole 215 UM6-1 200A Load Break Elbow 216
UM6-3 600A Non-Load Break Elbow 216 UM6-4 Fault Indicator 216 UM6-5 Feed Through Load Break Insert 216 UM6-7 Bushing Well Plug 217 UM6-10 200A Insulated Protective Cap 217 UM6-11 Insulated Protective Cap 217 UM6-12 Cable Marker Assembly 217 UM6-13 200A Load Break Insert 218
UM6-15 200A Insulated Stand Off 218
UM6-19 200A Insulated Stand Off Feed Through 219 UM6-21 200A Three Point Junction 219 UM6-22 200A Four Point Junction 219 UM6-28 In-Line Primary Cable Splice 220 UM6-34 Surge Arrestor 221 UM8 Meter Installation Underground Source 222 UM8-6 C.T. Meter Installation Single Phase 223 UM8-7 C.T. Meter Installation Three Phase 224 UM33 Multiphase sectionalizing enclosure pad or sleeve mounted 225 UM48-1 Single Rod Grounding Assembly 226 UM48-2 Two Rod Grounding Assembly 227 UM48-5 Grounding Grid For Pad Mounted Equipment 228 vii
UM6-2 Fused Elbow Termination 216
UM6-14 Deadbreak Insert 600A 218
UM6-17 Insulating Plug 600A Connector 218
15 15 Foot Long Pole 30 30 Foot Long Pole 35 35 Foot Long Pole 40 40 Foot Long Pole 45 45 Foot Long Pole 50 50 Foot Long Pole 55 55 Foot Long Pole 60 60 Foot Long Pole 65 65 Foot Long Pole 70 70 Foot Long Pole 75 75 Foot Long Pole 80 80 Foot Long Pole
Overhead Assemblies Section 1 - Pole Units
A pole unit consists of the installation of one pole, one "SEC-COOP" identification tag, and the pole number as indicated on the staking sheet. It does not include the pole-top assembly unit or other parts attached to the pole. The first two digits indicate the length of the pole; the third digit shows the classification per A.S.A.
(Example: 40-4 means a 40ft class 4 pole)
Unit Number Description
November 2009 1 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR POLES AND CROSSARMS
In distributing the poles, large, choice, dense poles shall be used at transformer, deadend, angle, and corner locations.
Poles shall be set so that alternate crossarm gains face in opposite directions, except at terminal and deadends where the gains of the last two (2) poles shall be on the side facing the terminal or deadend. On unusually long spans, the poles shall be set so that the crossarm is located on the side of the pole away from the long span. On lines that curve, crossarms shall be installed on the side of the pole which faces the midpoint of the curve. On sloping terrain, crossarms shall be installed on the uphill side of the pole. Where pole top insulator brackets or pole top pins are used, they shall be located on the opposite side of the pole from the gain.
Poles shall be set in an alignment and plumb, except at corners, terminal, angles, junctions, or other points of strain, where they shall be set and raked against the strain so that the conductors are in line.
Poles shall be raked against the conductor strain not less than 1 inch for each 10 feet of pole length nor more than 2 inches for each 10 feet of pole length after the conductors are installed at the required tension.
Pole backfill shall be thoroughly tamped in full depth. Excess dirt shall be banked around the pole.
November 2009 2 of 228 SEC SPEC
TABLE W
Pole Setting Depths
The minimum depth for setting poles must be as follows:
Length of Pole (Feet)
Setting in Soil (Feet)
Setting in All Solid Rock (Feet)
20 4.0 3.0 25 5.0 3.5 30 5.5 3.5 35 6.0 4.0 40 6.0 4.0 45 6.5 4.5 50 7.0 4.5 55 7.5 5.0 60 8.0 5.0
“Setting in Soil” depths must apply:
A. Where poles are to be set in soil;
B. Where there is a layer of soil or more than two (2) feet in depth over solid rock;
C. Where the hole in solid rock is not substantially vertical or the diameter of the hole at the surface of the rock exceeds approximately twice the diameter of the pole at the same level.
“Setting in All Solid Rock” depths must apply where poles are to be set in solid rock and where the hole is substantially vertical, approximately uniform in diameter and large enough to permit the use of tamping bars the full depth of the hole.
Where there is a layer of soil two (2) feet or less in depth over solid rock, the depth of the hole must be the depth of the soil in addition to the depth specified under “Setting in All Solid Rock” provided, however, that such depth must not exceed the depth specified under “Setting in Soil.”
On sloping ground, the depth of the hole must be measured from the low side of the hole.
November 2009 3 of 228 SEC SPEC
November 2009 4 of 228 SEC SPEC
Overhead Assemblies
6A 6A Copper Weld 8A 8A Copper Weld #2ACSR #2 Aluminum Clad Steel Reinforced 1/0ACSR 1/0 Aluminum Clad Steel Reinforced 4/0ACSR 4/0 Aluminum Clad Steel Reinforced 336ACSR 336MCM Aluminum Clad Steel Reinforced #6DP #6 Duplex #4DP #4 Duplex #2TP #2 Triplex 1/0TP 1/0 Triplex 4/0TP 4/0 Triplex 4/0QP 4/0 Quadraplex 336TP 336MCM Triplex 336QP 336MCM Quadraplex 500TP 500MCM Triplex 500QP 500MCM Quadraplex TG1-8 Tying Guides
Unit Number Description
Section 2 - Conductor Assembly Units A conductor assembly unit consists of 1 foot of conductor or cable for primaries, secondaries or services, and includes tie wires, sleeves for splicing, connectors, and armor rods with clips and armor wire when necessary. Tree trimming necessary for installing the services and secondaries on poles not carrying primary line is included with the conductor assembly unit and shall be performed in accordance with the directions of the Engineer. The service shall be connected to the secondary or transformer and 2 feet of conductor or cable shall be left for connecting the consumer's service entrance.
November 2009 5 of 228 SEC SPEC
CONDUCTOR INSTALLATION SPECIFICATIONS
Conductors must be handled with care. Conductors shall neither be trampled on nor run over by vehicles. Each reel shall be examined and the wire inspected for cuts, kinks, or other injuries. Injured portions shall be cut out and the conductor spliced. The conductors shall be pulled over suitable rollers or stringing blocks properly mounted on the pole or crossarm if necessary to prevent binding while stringing.
Conductors shall be sagged in accordance with the conductor manufacturer's recommendations. All conductors shall be sagged evenly. The air temperature at the time and place of sagging shall be determined by a certified thermometer.
The sag of all conductors after stringing shall be in accordance with the engineer's instructions.
Conductors shall be spliced and dead-ended as shown on the construction drawings. There shall be not more than one splice per conductor in any span and splices shall be located at least 10 feet from the conductor support. No splices shall be located in Grade B crossing spans and preferably not in adjacent spans.
Splices shall be installed in accordance with the manufacturer's specifications and recommendations.
All conductors shall be cleaned thoroughly by wirebrushing before splicing or installing connectors or clamps. A suitable inhibitor shall be used before splicing or applying connectors over aluminum conductor.
Connectors and hot-line clamps suitable for the purpose shall be installed as shown on the drawings and also in accordance with the manufacturer's specifications and recommendations. On all hot-line clamp installations, the clamp and jumper shall be installed so that they are permanently bonded to the load side of the line, allowing the jumper to be de-energized when the clamp is disconnected.
The use of stirrups to connect tap conductors (jumper wires) to primary conductors may be used if the following criteria are met:
• The stirrup and hot line clamp shall be sized to meet or exceed the current carrying capacity of the tap conductor or equipment jumper;
• All stirrup conductors shall be made of copper or bronze;
• All stirrup conductors shall be made of #2 copper equivalent or larger;
November 2009 6 of 228 SEC SPEC
• All-purpose or aluminum hot line clamps shall not be used with stirrups;
• All stirrups, connectors, and clamps shall be installed in accordance with the manufacturer’s specifications;
• Stirrups with two compression connectors are not to be used in areas of vibrating conductors;
• Stirrups are not to be used to connect main lines or heavily loaded tap lines.
Stirrups are not recommended to be used to connect reclosers, autotransformers, or line regulators. Stirrups and hot line clamps should not be used for sectionalizing tap and especially main lines for operational or maintenance purposes. Permanent compression or bolted type connectors should be used because of their better current carrying capabilities and reliability. Line switches, fused cutouts, or solid blade cutouts should be used at line locations where occasional line sectionalizing may be required.
At locations where permanent connections using compression or bolted type connectors are not desired, and where the installation or sectionalizing equipment is also not desired, then the standards specify the installation of hot line clamps (over armor rod on aluminum conductors).
November 2009 7 of 228 SEC SPEC
Last Revised September 17, 2007
CLEARENCES
SEC GROUNDLINE CLEARANCE REQUIREMENTS
Groundline
15.5 ft
Open Wire Secondary
Primary
Triplex
Neutral & Communication
16.5 ft
16.0 ft
18.5 ft
Roads subject to truck traffic
23.5 ft
24.5 ft
24.0 ft
26.5 ft
Railroad Tracks
9.5 ft
16.5 ft
12.0 ft
18.5 ft
Note 1
Note 3
Note 2
Note 4
Areas subject to pedestrian or restricted traffic only
Lakes, ponds resevoirs, and rivers
* Conductors shall meet these clearance requirements with ½ inch of radial ice @ 32 degrees F.
Less then 20 Acres
17.5 ft
18.0 ft
18.5 ft
20.5 ft
200 to 2000 Acres
31.5 ft
32.0 ft
32.5 ft
34.5 ft
20 to 200 Acres
25.5 ft
26.0 ft
26.5 ft
28.5 ft
Over 2000 Acres
37.5 ft
38.0 ft
38.5 ft
40.5 ft
Note 1
Note 2
Note 3
Note 4
November 2009 8 of 228 SEC SPEC
CLEARANCES
SEC BUILDING CLEARANCE REQUIREMENTS
Groundline
Open Wire Secondary
Primary
Triplex
Neutral & Communication
10.5 ft
11.5 ft
11.0 ft
13.5 ft
3.0 ft
10.5 ft
3.5 ft
12.5 ft
18 in.
*see note 1
“Readily Accessible” Roof (Accessible from a window)
*see Note 2
“Non-Readily Accessible” Roof
Notes:
1) Triplex must have 3.0 ft of clearance above the roof at a horizontal distance of 6.0 ft from the point of attachment
2) These clearances also apply to decks
*No buildings or permanent structures are permitted to be constructed in SEC’s right-of-way.
The clearances requirements illustrated on this diagram are those published In the 2007 NESC
* Conductors shall meet these clearance requirements with ½ inch of radial ice @ 32 degrees F.
November 2009 9 of 228 SEC SPEC
CLEARANCES
SEC POLE ATTACHMENT CLEARANCE
REQUIREMENTS
Notes:
1) No clearance requirement between neutral and triplex
2) Clearance from guy to any primary energized components (jumpers) 10.5 in.
3) Clearance between phases of 25kV energized components (jumpers) 18.5 in.
54"
See note 1
30" Min.
12" Min
Drip Loop
20" Min
40" Min
40" Min
12" Min
Upper Communications
Attachment
Lower Communications
Attachment
Neutral
120/240 Service
Drop
Security LightTransformer
40" Min.
Underground Riser
*Clearance between conductors and cables at midspan shall be no less then 75% of the required clearance at the point of attachment
November 2009 10 of 228 SEC SPEC
SOUTHSIDE ELECTRIC
COOPERATIVE
TTying Guide, Single Insulator, One Piece tie - Copper Type Conductors with Armor Rods
Conductor
Copper
Tie Wire Size
*Top
Length
*Side
Length
1/0 - 7 Strand HD Copper #4 90" 96"
2-3 Strand Copper #6 82" 88"
6A #6 65" 71"
8A #6 64" 70"
TG1
November 2009 11 of 228 SEC SPEC
CConductor
Copper
Tie Wire Size
Length
Short Piece
Length
Long Piece
1/0 - 7 Strand HD Copper #4 27" 40"
2-3 Strand Copper #6 23" 35"
6A #6 21" 30"
8A #6 21" 30"
Tying Guide, Single Insulator
Two Piece Tie - Copper Type Conductors with Armor Rods
TG2
November 2009 12 of 228 SEC SPEC
CConductor
Copper
Tie Wire Size First Piece Second Piece
1/0 - 7 Strand HD Copper #6 36" 27"
2-3 Strand Copper #6 34" 25"
6A #6 32" 23"
8A #6 31" 23"
Hot Line Tying Guide - Copper Type
Conductors with Armor Rods
TG3
November 2009 13 of 228 SEC SPEC
HHot Line Tying Guide, Single Insulator, Aluminum Tie Wire, ACSR Conductor with Armor Rods
ACSR
Conductor
Aluminum
Tie Wire Size Length
336 #4 4'-6"
4/0 #4 4'-1"
1/0 #4 3'-9"
#2 #4 3'-6"
TG4
November 2009 14 of 228 SEC SPEC
AACSR
Conductor
Aluminum
Tie Wire Size Length
336 #4 10'-3"
4/0 #4 9'-3"
1/0 #4 8'-3"
#2 #4 7'-5"
Tying Guide, Single Insulator, Aluminum Tie Wire, ACSR Conductor, with Armor Rods
TG5
November 2009 15 of 228 SEC SPEC
AACSR
Conductor
Aluminum
Tie Wire Size Length
336 #4 5'-9"
4/0 #4 5'-3"
1/0 #4 4'-10"
#2 #4 4'-7"
Hot Line Tying guide, Double Insulator
Aluminum Tie Wire, ACSR Conductor, with Armor Rods
TG6
November 2009 16 of 228 SEC SPEC
AACSR
Conductor
Aluminum
Tie Wire Size Length
336 #4 6'-10"
4/0 #4 6'-4"
1/0 #4 6'-0"
#2 #4 5'-9"
Hot Line Tying guide, Single Insulator
Pre-Coiled Aluminum Tie Wire, ACSR Conductor, with Armor Rods
TG7
November 2009 17 of 228 SEC SPEC
AACSR
Conductor
Aluminum
Tie Wire Size Length
336 #4 10'-3"
4/0 #4 9'-3"
1/0 #4 8'-3"
#2 #4 7'-5"
Tying guide, Double Insulator
Aluminum Tie Wire, ACSR Conductor, with Armor Rods
TG8
November 2009 18 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR POLE TOP ASSEMBLIES
Line designs which use high poles to clear obstacles such as railroads, must avoid upstrain on pin-type or post-type insulators on adjacent shorter poles.
The neutral conductor should be installed on the same side (preferably the road side) of all of the tangent and small angle poles throughout the length of the line.
Prior RUS approval is given if it is under the circumstances necessary to lower the neutral attachment on standard construction pole top assemblies an additional distance not exceeding 2 feet for the purpose of economically meeting conductor clearance requirements of the NESC.
Prior RUS approval is given if it is under the circumstances necessary to lower the neutral attachment on standard construction pole top assemblies an additional distance of up to 6 feet for the purpose of performing construction and future line maintenance on these assemblies from bucket trucks designed for such work.
With pin-type or post-type insulators, the conductor must be tied to the top groove of the insulator on tangent poles and on the side of the insulator away from the strain at angles. Pin-type and post-type insulators must be tight on the pins and bracket, respectively, and the top groove must be in line with the conductor after tying.
Factory-formed ties must be installed in accordance with the manufacturer’s specifications and recommendations.
A 3 inch by 3 inch (minimum), square, curved washer, item “d”, shall be used abutting the pole when installing primary or neutral conductor deadend assemblies directly to the pole to mitigate the crushing of wood fibers and to facilitate the allowable longitudinal loading as given in the design parameters on the construction drawings.
A locknut must be installed with each nut and eyenut, on all machine, upset and double arming bolts, and all other threaded hardware such as insulator pins and studs.
The calculated “maximum line angle” values in the tables are based on the “designated maximum” transverse loading on insulator pins as specified by RUS, and the application of the appropriate overload factors from the 1997 edition of the NESC.
November 2009 19 of 228 SEC SPEC
“Allowable longitudinal (or transverse) loading” values in the design parameters were derived from known or designated maximum strengths of materials to which the appropriate NESC safety factors have already been applied.
November 2009 20 of 228 SEC SPEC
VA1.01 Single Support - Miscellaneous VA1.011 Single Support - Miscellaneous VA1.1 Single Support (Tangent) VA1.1 - AC Tangent Aerial Cable VA1.11 Single Support (Tangent) on Crossarm VA2.021 Double Support - Miscellaneous VA2.1 Double Support (Shallow Angle) VA2.1 - AC Angle Aerial Cable VA2.21 Double Support - Miscellaneous VA3.1 Suspension Angle VA4.1 Dead End Angle (90°-150°) VA4.2 Dead End Angle (20°-90°) VA5.1 Single Dead End VA5.1 - AC Dead End Aerial Cable VA5.3 Single Dead End - Miscellaneous VA5.4 Single Dead End - Miscellaneous VA5.21 Single Dead End on Crossarms VA5.31 Single Dead End on Crossarms VA6.1 Double Dead End (Straight) VA6.2 Double Dead End (Feed Through) VA6.21 Double Dead End on Crossarms VA1.12G Single Phase Junction Guide VA5.5G Single Phase Tap Guide
A pole top assembly unit consists of the installation the hardware, crossarms, and their appurtenances, insulators, ect. required to support the primary and neutral conductors. It does not include the pole.
Unit Number Description
Primary Pole Top Assembly Units
Section A - Single Phase Primary Pole Top Assembly Units
November 2009 21 of 228 SEC SPEC
VVA1.01
VA1.011
November 2009 22 of 228 SEC SPEC
November 2009 23 of 228 SEC SPEC
IITEM QTY MATERIAL Design Parameter
1 1 Messenger Bracket, Hendrix type BM-14 Line Angles 0-6
2 1 Hendrix Stirrup TS-1, supplied with 1/2" hardware
3 1 1/0 AWG 25kV Tree Proof Aerial Cable
4 1 252 AWA Alumoweld - Aluminum Messenger
5 Hendrix H20V Spacer with Ring Ties (Ring Ties not shown)
6 1 Hendrix BAS-14F Anti-sway Bracket supplied with Plastic Pin
7 1 Connector, size and type as required
8 Ground Wire, #6 Soft Draw (min)
9 Ground Wire Stable
10 2 Machine Bolts, 5/8", length as req.
11 2 Square Washer, 2 1/4" X 2 1/4" X 3/16"
12 1 Fetter Drive Lag Screw, 1/2" X 4"
VA1.1-AC
1-PHASE
24.9 / 14.4kV
JAN 2008
TANGENT AERIAL CABLE
SEC
November 2009 24 of 228 SEC SPEC mmust be installed on both sides of X-arm
November 2009 25 of 228 SEC SPEC
IITEM QTY MATERIAL
a 2 Insulator, pin type (24.9/14.4 kV) f 2 Pin, crossarm steel, 5/8" x 14"
VA2.021
SOUTHSIDE ELECTRIC
November 2009 26 of 228 SEC SPEC
SHALLOW ANGLE AND
DOUBLE SUPPORT TANGENT SOUTHSIDE ELECTRIC
November 2009 27 of 228 SEC SPEC
VVA2.1-AC
1-PHASE
24.9 / 14.4kV
JAN 2008
ANGLE AERIAL CABLE
SEC
ITEM QTY MATERIAL
1 1 Messenger Bracket, Hendrix type BM-14
2 2 Insulator, Pin Type, Hendrix HP1-15VTP
3 2 Insulator Pin, Hendrix SSP-2
4 1 1/0 AWG 25kV Tree Proof Aerial Cable
5 1 252 AWA Alumoweld - Aluminum Messenger
6 1 Guy Hook
7 1 Eye Bolt, 3/4", length as req.
8 2 Machine Bolts, 5/8", length as req.
9 2 Curved Washer, 3" X 3" X 3/16"
10 1 Angle Clamp, Hendrix CMA-1
11 Ground Wire, #6 Soft Draw (min)
12 Ground Wire Stable
13 1 Connector, size and type as req.
14 1 Insulator Plate, Hendrix 21P
Design Parameter
Line Angles 7-60
November 2009 28 of 228 SEC SPEC mmust be installed on both sides of X-arm
SHALLOW ANGLE AND
DOUBLE SUPPORT TANGENT
ON CROSSARMS
SOUTHSIDE ELECTRIC
November 2009 29 of 228 SEC SPEC
NNOTE: When 2 guys are required, install 1 guy attachment with guy strain insulator 6" below the Primary eyebolt and the second guy attachment
6" below the Neutral eyebolt.
ACSR conductors require armor rods.
m 2 Clamp, angle, suspension (di stribution) m m
November 2009 30 of 228 SEC SPEC
DDOUBLE DEADENDED ANGLE
NOTES:
Separate 6" (top position only) when angle = 90 degrees
Install insulated extension link in lower primary attachment
November 2009 31 of 228 SEC SPEC
DDOUBLE DEADENDED ANGLE
NOTES:
Separate 6" (top position only) when angle = 90 degrees
Install insulated extension link in lower primary attachment
November 2009 32 of 228 SEC SPEC
NNOTE: When 2 guys are required, install 1 guy attachment with guy strain insulator 6" below the Primary eyebolt and the second guy attachment
6" below the Neutral eyebolt.
SOUTHSIDE ELECTRIC
November 2009 33 of 228 SEC SPEC
VVA5.1-AC
1-PHASE
24.9 / 14.4kV
JAN 2008
DEAD-END AERIAL CABLE
SEC
ITEM QTY MATERIAL
1 1 1/0 AWG 25kV Tree Proof Aerial Cable
2 1 Preshaped Conductor Grip, Coated
3 1 252 AWA Alumoweld - Aluminum Messenger
4 1 Preshaped Messenger Grip
5 1 Insulator, 25kV Suspension
6 1 Eye Bolt, 3/4", length as req.
7 1 Curved Washer, 3" X 3" X 3/16"
8 1 Thimble Clevis, Hendrix Catolog No. HDTC
9 1 Thimble Clevis, Hendrix Catolog No. TC
10 1 Connector, size and type as req.
11 1 Guy Hook
12 Ground Wire, #6 Soft Draw (min)
13 Ground Wire Stable
November 2009 34 of 228 SEC SPEC
VVA5.3
DEAD END OFF EXISTING DEADEND SOUTHSIDE ELECTRIC
November 2009 35 of 228 SEC SPEC
VA5.4
SINGLE TAP
(SEE TAP GUIDE VA5.5G )
SOUTHSIDE ELECTRIC
November 2009 36 of 228 SEC SPEC
November 2009 37 of 228 SEC SPEC
November 2009 38 of 228 SEC SPEC
November 2009 39 of 228 SEC SPEC aa 2 Insulator, pin type (24.9/14.4 kV) f 2 Pin, crossarm steel, 5/8" x 14"
DOUBLE DEADEND ON CROSSARMS
VA6.21
must be installed on both sides of crossarm
November 2009 40 of 228 SEC SPEC
November 2009 41 of 228 SEC SPEC
MikeB Line
November 2009 42 of 228 SEC SPEC
VB1.11L Single Support on Crossarm (Tangent) VB1.14L Single Support, Neutral on Crossarm VB2.21L Double Support on Crossarms (Shallow Angle) VB2.22L Double Support Neutral on Crossarms (Shallow Angle) VB3.1 Suspension Angle VB4.1 Deadend Angle (90°-150°) VB5.1 Single Deadend -Vertical VB5.21 Single Deadend on Crossarms VB5.31 Single Deadend on Crossarms VB6.21 Double Deadend on Crossarms
Primary Pole Top Assembly Units A pole top assembly unit consists of the installation the hardware, crossarms, and their appurtenances, insulators, ect. required to support the primary and neutral conductors. It does not include the pole.
Section B - Two Phase Primary Pole Top Assembly Units
November 2009 43 of 228 SEC SPEC
November 2009 44 of 228 SEC SPEC must be installed on both
November 2009 45 of 228 SEC SPEC
SHALLOW ANGLE AND
DOUBLE SUPPORT TANGENT
ON CROSSARMS
November 2009 46 of 228 SEC SPEC must be installed on both
November 2009 47 of 228 SEC SPEC m 3 Clamp, angle, suspension (di stribution)
Position of guy, Guy strain insulator required
Position of guy
NOTE:
Armor rods must be installed on ACSR conductors
November 2009 48 of 228 SEC SPEC
Position of guys, Guy strain insulators required
Position of guys
November 2009 49 of 228 SEC SPEC
Position of guy, Guy strain insulator required
Position of guy
November 2009 50 of 228 SEC SPEC
November 2009 51 of 228 SEC SPEC aa 4 Insulator, pin type (24.9/14.4 kV) f 4 Pin, crossarm steel, 5/8" x 14"
SOUTHSIDE ELECTRIC
November 2009 52 of 228 SEC SPEC
VC1.11 Single Support on Crossarm (Tangent) VC1.11L Single Support on Crossarm (Tangent) (Large Conductors) VC1.41 Single Support, Neutral on Crossarm VC1.41L Single Support, Neutral on Crossarm (Large Conductors) VC2.21L Double Support on Crossarms (Shallow Angle) VC2.21L Double Support on Crossarms (Shallow Angle) (Large Cond.)
VC2.51 Double Support Neutral on Crossarms VC2.51L Double Support Neutral on Crossarms (Large Conductors) VC2.52 Double Support on 10ft Crossarms VC2.52L Double Support on 10ft Crossarms (Large Conductors) VC3.1 Suspension Angle - Angle Shoe Neutral VC3.2L Suspension Angle (Large Conductors) VC4.2L Deadend Angle (Large Conductors) VC5.2L Single Deadend -Vertical - (Large Cond.)
VC5.21 Single Deadend on 2 Crossarms VC5.31 Single Deadend on 3 Crossarms VC5.51-XF Single Deadend on 10ft Fiberglass X-arm VC5.71-XF Single Deadend on 1 Fiberglass X-arm VC5.91-XF Single Deadend on 12ft Fiberglass X-arm VC6.21 Double Deadend on 2 Crossarms VC6.31 Double Deadend on 3 Crossarms VC6.31-XF Double Deadend on 1 Fiberglass X-arm VC6.51 Double Deadend on 10ft Crossarms VC6.51-XF Double Deadend on 10ft Fiberglass X-arm VC6.91-XF Double Deadend on 12ft Fiberglass X-arm VC1.81G Three Phase Junction Guide VC5.11G Single Phase Tap Guide VC5.82G Three Phase Horizontal Tap "Buckarm" Guide
Description
A pole top assembly unit consists of the installation the hardware, crossarms, and their appurtenances, insulators, ect. required to support the primary and neutral conductors. It does not include the pole.
Primary Pole Top Assembly Units
Section C - Three Phase Primary Pole Top Assembly Units
Unit Number
November 2009 53 of 228 SEC SPEC
November 2009 54 of 228 SEC SPEC
November 2009 55 of 228 SEC SPEC mmust be installed on both
SOUTHSIDE ELECTRIC
November 2009 56 of 228 SEC SPEC
SOUTHSIDE ELECTRIC
November 2009 57 of 228 SEC SPEC
November 2009 58 of 228 SEC SPEC
November 2009 59 of 228 SEC SPEC
SOUTHSIDE ELECTRIC
November 2009 60 of 228 SEC SPEC
SOUTHSIDE ELECTRIC
November 2009 61 of 228 SEC SPEC
November 2009 62 of 228 SEC SPEC
November 2009 63 of 228 SEC SPEC mm 4 Clamp, angle, suspension (distribution) m
SOUTHSIDE ELECTRIC
COOPERATIVE
Position of guy, Guy strain insulator required
Position of guy, Guy strain insulator required
Position of guy
Armor rods must be installed on ASCR conductors
November 2009 64 of 228 SEC SPEC m 4 Clamp, angle, suspension (di stribution)
SOUTHSIDE ELECTRIC
COOPERATIVE
Position of guy, Guy strain insulator required
Position of guy, Guy strain insulator required
Position of guy
Armor rods must be installed on ASCR conductors
November 2009 65 of 228 SEC SPEC
November 2009 66 of 228 SEC SPEC
VERTICAL DEADEND
VC5.2L
November 2009 67 of 228 SEC SPEC
When used as a buckarm install
12" extension link in center phase
Position of guys, Guy strain insulators required
Position of guy
November 2009 68 of 228 SEC SPEC
NOTES:
2 guy attachments integrated into fiberglass crossarm.
Guy strain insulators (E5 .1X) required on crossarm guy attachments.
Fiberglass crossarm (gx) includes 3 1/2" x 3 1/2" x 1/4" washers, eyebolts, and
Fiberglass Xarm, 3 1/2" x 7 1/2" x 10'
Suitable for Grade B and
336ACSR construction.
VC5.51-XF
SINGLE DEADEND
ON 10' FIBERGLASS CROSSARM
eyenuts for phase attachments..
November 2009 69 of 228 SEC SPEC
NOTES:
2 guy attachments integrated into fiberglass crossarm.
Fiberglass Xarm, 3 1/2" x 7 1/2" x 8'
Suitable for Grade B and
336ACSR construction.
VC5.71-XF
SINGLE DEADEND
ON FIBERGLASS CROSSARM
When used as a buckarm, install 12" extension link in center phase.
eyenuts for outside phase attachments.
Position of Neutral to be noted on the Staking Sheet
November 2009 70 of 228 SEC SPEC
NOTES:
2 guy attachments integrated into fiberglass crossarm.
Fiberglass Xarm, 3 1/2" x 7 1/2" x 12'
Suitable for Grade B and
336ACSR construction.
VC5.91-XF
SINGLE DEADEND
ON 12' FIBERGLASS CROSSARM
When used as a buckarm, install 12" extension link in center phase.
eyenuts for outside phase attachments.
5'-6"5'-6"
Position of Neutral to be specified on the Staking Sheets
November 2009 71 of 228 SEC SPEC
November 2009 72 of 228 SEC SPEC
VVC6.31-XF
DOUBLE DEADEND ON
FIBERGLASS CROSSARM
Suitable for Grade B
= 6000
Fiberglass Xarm, 3 1/2" x 7 1/2" x 8'
November 2009 73 of 228 SEC SPEC
November 2009 74 of 228 SEC SPEC
Fiberglass Xarm, 3 1/2" x 7 1/2" x 10'
NOTES:
1. Suitable for Grade B
VC6.51-XF
November 2009 75 of 228 SEC SPEC
VVC6.71-XF
DOUBLE DEADEND ON
10' FIBERGLASS CROSSARM
Suitable for Grade B
= 6000
Fiberglass Xarm, 3 1/2" x 7 1/2" x 10'
4'-6"
Position of Neutral
November 2009 75.5 of 228 SEC SPEC
4'-6"
5' -0
VVC6.91-XF
DOUBLE DEADEND ON
12' FIBERGLASS CROSSARM
Suitable for Grade B
= 6000
Fiberglass Xarm, 3 1/2" x 7 1/2" x 12'
5'-6"5'-6"
Position of Neutral to be noted on the Staking Sheet
November 2009 76 of 228 SEC SPEC
November 2009 77 of 228 SEC SPEC
VC1.11L
VS1.01
NOTES: All single phase taps off of multiphase to be fused.
VC1.11L
VA5.4
VS1.01
SOUTHSIDE ELECTRIC
November 2009 78 of 228 SEC SPEC
VVC5.71-XF
"BUCKARM" GUIDE
VC5.71-XF
SOUTHSIDE ELECTRIC
November 2009 79 of 228 SEC SPEC
VD1.83L Single Support on Crossarms (Tangent) (Large Conductors) VD2.91L Double Support on Crossarms (Shallow Angle) (Large Cond.)
VD6.91 Double Deadend on Crossarms VD3.1G Double Ckt Suspension Angle Guide VD4.2LG Double Ckt Deadend Guide VD5.91G Double Ckt Three Phase Tap Guide
Primary Pole Top Assembly Units A pole top assembly unit consists of the installation the hardware, crossarms, and their appurtenances, insulators, ect. required to support the primary and neutral conductors. It does not include the pole.
Section D - Double-Circuit Primary Pole Top Assembly Units
November 2009 80 of 228 SEC SPEC
November 2009 81 of 228 SEC SPEC
November 2009 82 of 228 SEC SPEC
November 2009 83 of 228 SEC SPEC
SOUTHSIDE ELECTRIC
November 2009 84 of 228 SEC SPEC
VVD4.2LG
November 2009 85 of 228 SEC SPEC
VVC5.71-XF
VD1.83L
VC5.71-XF
VD1.83L
VD1.83L
VC5.71-XF
SOUTHSIDE ELECTRIC
November 2009 86 of 228 SEC SPEC
E1.01 Single Overhead Guy (Through Bolt Type) E2.01 Single Overhead Guy - Heavy Duty (Through Bolt Type) E2.01X Single Overhead Guy w/ Guy Strain Insulator (Through Bolt Type) E2.1 Single Down Guy - Heavy Duty (Through Bolt Type) E2.1X Single Down Guy w/ Guy Strain Insulator (Through Bolt Type) E3.10X Guy Marker E5.1X Guy Strain Insulator E2.3G Three Down Guy Guide E2.4G Four Down Guy Guide
Description
A guy assembly unit consists of the hardware, wire, guy marker. An Overhead guy does not include the associated pole or down guy. Should the line design reflect the use of a guy strain insulator, the appropriate unit will be shown on the staking sheet.
Section E - Guying Assembly Units
Unit Number
November 2009 87 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR GUYS
Guys shall be placed before the conductors are strung and shall be attached to the pole as shown in the construction drawings.
The grade of construction of the guys shall be the same as the structure or the highest grade required for any other conductors supported by the pole or structure.
Deadend structure guys shall be installed in line with the pull of conductors as nearly as practical. Bisector guys at an angle structure shall be installed as nearly as practical to the true bisector of the line angle.
A 1:1 slope for guy leads is recommended, especially on deadend structures. Minimum guy leads are not recommended.
The applicable NESC safety factors have not been but must be applied to determine the “allowable guy wire tension” as denoted in the design parameters of the guying assembly units.
November 2009 88 of 228 SEC SPEC
PPreform
3/8 HSS
November 2009 89 of 228 SEC SPEC
PPreform
3/8 HSS
1'-6" min.
SINGLE OVERHEAD GUY WITH
GUY STRAIN INSULATOR
E2.01X pole eye plate
Insulator, guy strainw w
#2ACSR jumper
November 2009 90 of 228 SEC SPEC
3/8 HSS
Preform
SOUTHSIDE ELECTRIC
November 2009 91 of 228 SEC SPEC
(Preform, deadend type)
Preform
3/8 HSS
w Insulator, guy strainpole eye plate
SOUTHSIDE ELECTRIC
COOPERATIVE
SINGLE DOWN GUY WITH
GUY STRAIN INSULATOR
E2.1X
November 2009 92 of 228 SEC SPEC
EE3.10X
GUY MARKER
November 2009 93 of 228 SEC SPEC zz figure eight z
E5.1X
SOUTHSIDE ELECTRIC
November 2009 94 of 228 SEC SPEC
(Preform, deadend type)
Guy strain insulators required
Guy strain insulators ar e required when the thr ough bolt of a guy attachment has vertical separation from the through bolt of a primary attachment of less then 15", and the primary attach ment does not contain an insulated link. This is done in an attempt to achieve RUS's recommended BIL of 300kV.
(see RUS's "Items of Engineering Interest" 2005 p.5)
SOUTHSIDE ELECTRIC
COOPERATIVE
*When 3 anchors are used spacing can be reduced to 5ft.
November 2009 95 of 228 SEC SPEC
(Preform, deadend type)
Guy strain insulators required
Guy strain insulators ar e required when the thr ough bolt of a guy attachment has vertical separation from the through bolt of a primary attachment of less then 15", and the primary attach ment does not contain an insulated link. This is done in an attempt to achieve RUS's recommended BIL of 300kV.
(see RUS's "Items of Engineering Interest" 2005 p.5)
SOUTHSIDE ELECTRIC
COOPERATIVE
*When 3 anchors are used spacing can be reduced to 5ft.
E2.4GE2.4G
November 2009 96 of 228 SEC SPEC
F1.8 Expanding Anchor 5/8" x 7'0" Rod F1.12 Expanding Anchor 3/4" x 8'0" Rod F2.12 Screw Anchor (Power Installed) F2.X Multihelix Power Installed Screw Anchor F5.3 Rock Anchor F6.8 Swamp Anchor (Power Installed)
Unit Number Description
An anchor assembly unit consists of the installation of an anchor with rod complete, and ready for attaching the guy wire.
Section F - Anchor Assembly Units
November 2009 97 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR ANCHORING
All anchors and rods shall be in line with the strain and shall be installed so that approximately 6 inches of the rod remains out of the ground. In cultivated fields or other locations, as deemed necessary, the projection of the anchor rod above earth may be increased to a maximum of 12 inches to prevent burial of the rod eye. The backfill of all anchor holes must be thoroughly tamped the full depth.
After a cone anchor has been set in place, the hole shall be backfilled with coarse crushed rock for 2 feet above the anchor and tamped during the filling. The remainder of the hole shall be backfilled and tamped with dirt.
The maximum load with overload factors transferred to the anchor should not exceed the designated maximum holding power given in the design parameters on the anchor assembly drawing. The rating is coordinated with the maximum holding power of average, class 5, soil conditions.
When the anchor is used in poorer soils, the holding power of the anchor should be derated. A suggested guide is to derate by 25 percent in class 6 soil and by 50 percent in class 7 soil. For class 8 soil it is usually necessary to use swamp anchors or power driven screw anchors which can penetrate the poor soil into firmer soil.
November 2009 98 of 228 SEC SPEC
November 2009 99 of 228 SEC SPEC
November 2009 100 of 228 SEC SPEC
11 Anchor, Double or Triple Helix, 8"-10"-12" 1
2 Anchor Extensions, 1 1/2" x 7' (as req'd)
3 Anchor Head, Triple Eye
4 Anchor Bonding Clamp
Multihelix Power Installed Screw Anchor
F2.X
Notes:
1. Maximum Holding force to be determined by the Engineer.
2. Minimum Average Torque = 2,000 ft-lbs. The average torque must be developed continuously for at least the last three feet of installation of the screw anchor and with the use of at least one 7' anchor extension. The average developed torque for each anchor must be recorded and made available to the Engineer.
2. Minimum projection = 6" maximum projection = 12" but may be increased to avoid over torquing of the shaft, any final projections over 18" shall be approved by the Engineer.
November 2009 101 of 228 SEC SPEC
November 2009 102 of 228 SEC SPEC
November 2009 103 of 228 SEC SPEC
VG1.4 Single Phase Transformer, Multi-Phase Pole, Cutout Protection VG1.5 Single Phase Transformer, Single Phase Pole, Cutout Protection VG1.6 Single Phase Transformer, Single Phase Pole, Cutout Protection VG1.7 Single Phase Transformer Tangent VG1G Single Phase Transformer Guide VG1.8 Single Phase Transformer Deadend VG2.1 Two-Phase Transformer Bank - Open Delta VG2.1G Two-Phase Transformer Bank - Open Delta Guide VG3.1 Three-Phase Transformer Bank - Delta VG3.1G Three-Phase Transformer Bank - Delta Guide VG3.2 Three-Phase Transformer Bank - Corner Grounded Delta VG3.2G Three-Phase Transformer Bank - Corner Grounded Delta Guide VG3.3 Three-Phase Transformer Bank - Wye VG3.3G Three-Phase Transformer Bank - Wye Guide
A transformer assembly unit consists of the installation of the transformer, its protective equipment and its hardware and leads with their connectors and supporting insulators and pins. This does not include the installation of the pole top, secondary, service, or grounding assemblies. A transformer assembly shall include “its protective equipment” as identified. Such protective equipment will include a flipper-fuse kit or cutout, and lightning arrestor.
Section G - Transformer Assembly Units
November 2009 104 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR TAPS, JUMPERS, AND ARRESTERS
Jumpers and other leads connected to line conductors shall have sufficient slack to allow free movement of the conductors. Where slack is not shown on the construction drawings, it will be provided by at least two (2) bends in a vertical plane, or one
(1) in a horizontal plane, or the equivalent. In areas where aeolian vibration occurs, special measures to minimize the effects of jumper breaks shall be used as may be specified.
All leads on equipment, such as transformers, reclosers, etc., shall be a minimum of #6 copper conductivity. Where aluminum jumpers are used, a connection to an unplated bronze terminal shall be made by splicing a short stub of copper to the aluminum jumpers using a compression connector suitable for the bimetallic connection.
Where applicable, the external gap electrodes of surge arresters, combination arrester cutout units, and transformers mounted arresters shall be adjusted to the manufacturer’s recommended spacing. Care shall be taken so that the adjusted gap is not disturbed when the equipment is installed.
It may be necessary, and is permissible, to lower the neutral attachment on standard construction pole top assemblies an additional distance not exceeding 2 feet to provide adequate clearance between cutout and single-phase, conventional distribution transformers.
November 2009 105 of 228 SEC SPEC
November 2009 106 of 228 SEC SPEC
MikeB Polygonal Line
MikeB Text Box (Continuous Conductor. From source to load;
cut-out, arrestor and then transformer bushing)
MikeB Polygonal Line
MikeB Line
MikeB Polygon
MikeB Polygonal Line
MikeB Line
MikeB Polygon
MikeB Polygonal Line
MikeB Line
MikeB Polygonal Line
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box
(3) pieces of wildlife protection
MikeB Text Box (Continuous Conductor. From source to load;
cut-out, arrestor and then transformer bushing)
November 2009 107 of 228 SEC SPEC
MikeB Polygonal Line
MikeB Line
MikeB Polygon
MikeB Polygonal Line
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box
(3) pieces of wildlife protection
MikeB Polygonal Line
MikeB Text Box Continuous conductor. From source to load; cut-out, arrestor and then transformer bushing.
November 2009 108 of 228 SEC SPEC
November 2009 109 of 228 SEC SPEC
VVG1G
November 2009 110 of 228 SEC SPEC
November 2009 111 of 228 SEC SPEC
MikeB Line
MikeB Polygon
MikeB Polygonal Line
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box
(3) pieces of wildlife protection
MikeB Text Box Continuous conductor. From source to load; cut-out, arrestor and then transformer bushing.
MikeB Polygon
MikeB Polygon
MikeB Line
MikeB Line
MikeB Polygonal Line
MikeB Polygonal Line
VVG2.1G
November 2009 112 of 228 SEC SPEC
November 2009 113 of 228 SEC SPEC
MikeB Line
MikeB Polygon
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box
(3) pieces of wildlife protection
MikeB Line
MikeB Line
MikeB Line
MikeB Polygon
MikeB Polygon
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygon
MikeB Polygon
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Text Box Continuous conductor. From source to load; cut-out, arrestor and then transformer bushing.
A B C
November 2009 114 of 228 SEC SPEC
November 2009 115 of 228 SEC SPEC
MikeB Line
MikeB Polygon
MikeB Text Box
(3) pieces of wildlife protection
MikeB Line
MikeB Line
MikeB Line
MikeB Line
MikeB Polygon
MikeB Polygon
MikeB Polygon
MikeB Polygon
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box Continuous conductor. From source to load; cut-out, arrestor and then transformer bushing.
November 2009 116 of 228 SEC SPEC
November 2009 117 of 228 SEC SPEC
MikeB Line
MikeB Polygon
MikeB Text Box
(3) pieces of wildlife protection
MikeB Line
MikeB Line
MikeB Line
MikeB Line
MikeB Polygon
MikeB Polygon
MikeB Polygon
MikeB Polygon
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Polygonal Line
MikeB Line
MikeB Line
MikeB Line
MikeB Text Box Continuous conductor. From source to load; cut-out, arrestor and then transformer bushing.
November 2009 118 of 228 SEC SPEC
H1.1, H1.1X Grounding Assembly - Ground Rod Type H3.1 Grounding Assembly - Ground Rod Type (For Airbreak Switch) H4.1 Grounding Assembly - Platform Type (For Airbreak Switch)
Unit Number Description
A grounding assembly unit consists of the installation of a ground wire on the pole, installation of any required hardware, driving a ground rod or ground rods in undisturbed earth, and making all the appropriate connections.
Section H - Grounding Assembly Units
November 2009 119 of 228 SEC SPEC
CONSTRUCTION SPECIFICATIONS FOR GROUNDING
Ground rods shall be driven full length in undisturbed earth in accordance with the construction drawings. They shall be installed a minimum of 2 feet from the face of the pole. The top of the ground rods shall be at least 12 inches below the surface of the earth. The ground wire shall be attached to the rod with an appropriate ground rod clamp and shall be secured to the pole with staples. The staples on the ground wire shall be spaced 2 feet part, except for a distance of 8 feet above the ground and 8 feet down from the top of the pole, as applicable, where they shall be 6 inches apart.
The connection between the ground rod and the system neutral should be made by one continuous piece of conductor, (the pole ground wire), and installed in the…