Attachment_0006_-_Army_GFE.pdf

PDF 459 KB Posted

Attached to
Kuwait Dining Facilities (DFAC) 3. 0
Solicitation number
W52P1J-17-R-0049
Issued by

About this file

Attachment 0006 - Army GFE

View the file

Other files

File Type Posted
W52P1J17R0049-0005.pdf PDF
Attachment_0008_-_L&M_-_31MAY2017.pdf PDF
W52P1J17R0049-0004.pdf PDF
Attachment_0002_-_Air_Force_DFAC_PWS_25May2017.pdf PDF
Attachment_0001_-_ASG-KU_DFAC_PWS_25May2017.pdf PDF
W52P1J17R0049-0003.pdf PDF
Attachment_0026_-_INDUSTRY_Q&A_31May17.xlsx XLSX spreadsheet
Attachment_0012_-_DFAC_3-0_Price_Matrix_31May2017.xlsx XLSX spreadsheet
Attachment_0008_-_L&M_-_31MAY2017.pdf PDF
W52P1J17R0049-0002.pdf PDF
Attachment_0025_-_General_Order_No_1C.pdf PDF
Attachment_0023_-_INDUSTRY_Q&A_FORMAT.xlsx XLSX spreadsheet
W52P1J17R0049-0001.pdf PDF
Attachment_0018_-_ASG-KU_PMO_Installation_Access_SOP_17_Jul_2016.pdf PDF
Attachment_0011_-_PP_Questionnaire.docx DOCX document
Attachment_0013_-_Site_Visit_Q&A_05May2017.pdf PDF
Attachment_0024_-_DFAC_Location_Maps.pdf PDF
Attachment_0021_-_USARCENT_Regulation_385-10_(15_JUN_2010).pdf PDF
Attachment_0008_-_Section_L_and_M.pdf PDF
Attachment_0014_-_AOR_Exception_to_Policy_for_Subsistence_Support.pdf PDF
Attachment_0010_-_Mission_Essential_Services.pdf PDF
Attachment_0016_-_ASG-KU_Eagle_Cash.pdf PDF
Attachment_0012_-_DFAC_3.0_Price_Matrix.xlsx XLSX spreadsheet
Attachment_0017_-_ASG-KU_Food_Service_SOP.pdf PDF
Attachment_0019_-_DFAC_Fact_Sheets.pdf PDF
Attachment_0020_-_USARCENT_Fire_Prevention_Policy.pdf PDF
Attachment_0005_-_CDRLs.pdf PDF
Attachment_0007_-_Air_Force_GFE.pdf PDF
Attachment_0015_-_ASG-KU_Base_Access_Forms.pdf PDF
Attachment_0002_-_Air_Force_DFAC_PWS_05May2017.pdf PDF
Attachment_0001_-_ASG-KU_DFAC_PWS_05May2017.pdf PDF
Attachment_0022_-_USARCENT-ASG-KU_CONOPS_MENU.pdf PDF
Attachment_0004_-_Technical_Drawings.pdf PDF
Attachment_0009_-_PBIF_Plan_05May2017.pdf PDF
W52P1J17R0049.pdf PDF
Attachment_0023_-_DFAC_3.0_RFP_Q&A.xlsx XLSX spreadsheet
Attachment_0003_-_DFAC_3.0_QASP-PRS_05May2017.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Camp Facility/Location Asset ID Asset Tag Asset Description Manufacturer Model Serial # or Other Identifying # Condition Deficiency

Camp Arifjan DFAC/Z-2 N/A N/A Fats, Oils and Grease Storage Tank N/A Unknown N/A Serviceable

Placed within a makeshift (expeditionary style) secondary containment constructed of wood and bladder material. The wood frame is showing signs of fatigue.

Camp Arifjan DFAC/Z-2 N/A N/A Grease Trap N/A Unknown N/A Serviceable

Grease trap system in which water from DFAC operations flows first into a steel UST located on the north side of the DFAC. Once the water flows into the tank, it moves over a series of baffles entrapping the grease and allowing the water to flow into the Camp Arifjan sewer system. Due to the large amount of sodium hypochlorite (bleach) contained in waste water generated at the DFAC, a potential REC exists in the use of a metal underground grease trap system. Sodium hypochlorite is corrosive by nature and corrodes metal. It is reasonable to conclude that over time the integrity of the underground grease trap storage tank could become compromised allowing for continuous contamination of the surrounding soils. Without removing the underground storage tank, it is impossible to know the current condition of the tank or if the integrity of the tank has been compromised.

Camp Arifjan DFAC/Z-2 N/A N/A Ice Reefer Unknown N/A Serviceable Stores bagged ice in a mobile reefer unit powered by diesel motor. The compressor unit of this reefer is leaking POL onto the surrounding soil.

Camp Arifjan DFAC/Z-2 N/A N/A Prime Generator Secondary Containment N/A Unknown N/A Serviceable

Prime Power Generators are placed within makeshift secondary containment units constructed of wood and bladder material. The wood frames are showing signs of fatigue.

Camp Arifjan DFAC/Z-2 N/A N/A Reefer Power Generation Secondary N/A Unknown N/A Serviceable

Generators which supply power to the reefer units and the associated fuel tanks are placed within a makeshift (expeditionary style) secondary containment constructed of wood and bladder material. The wood frame is showing signs of fatigue.

Camp Arifjan DFAC/Z-2 N/A N/A Inside N/A Unknown N/A Serviceable

Ceiling has holes and missing tiles. Floor drains and fans dusty (kitchen area). Shelves are un-organized and handy work for correction (storage area). Exit doors are not marked clearly (all exit areas inside DFAC).

Camp Arifjan DFAC/Z-2 N/A N/A Outside N/A Unknown N/A Serviceable

Dock is lacking attention ( Loading and unloading rear of building). Propane tanks are not secured (Outback). Loading dock has uneven floors and cracks (rear of the building). Treads on stairs for employees break area are not adequate (outside). Door gaskets in main entrance dirty, greasy

Camp Arifjan DFAC/Z-2 N/A N/A Ceiling N/A Unknown N/A Serviceable Over all acceptable. Some area has rust

Camp Arifjan DFAC/Z-2 N/A N/A Doors & Frames N/A Unknown N/A Serviceable

Wood Doors - Acceptable in serving area. One door in the Kitchen area is not closing properly. Steel Doors - Some Doors have settlement and not closing freely. Few of the door closers are not fully efficient. Some locks don’t close freely, needs extra push. One of the emergency doors also doesn't close on its own. Door Frame - Acceptable in Serving area. Emergency door at janitor area does not have dust sealer.

Camp Arifjan DFAC/Z-2 N/A N/A Exterior N/A Unknown N/A Serviceable

Stairs - Staff entrance Grating and supports are Bad. External Walkway - Metal grates at staff entrance is damaged. Metal grate walkway is not aligned with ground. Gravel, Soil etc. – Acceptable.

Camp Arifjan DFAC/Z-2 N/A N/A Floor type 1 N/A Unknown N/A Serviceable

Some floor part has been torn/cracked. Floor connection areas are not filled with suitable filler, to make it seamless.

Camp Arifjan DFAC/Z-2 N/A N/A Floor type 2 N/A Unknown N/A Serviceable

Floor finish in wash area is damaged. Slope for drainage in wash area and drying does not ensure proper drain into the drainage pit. Stability & connection - Acceptable.

Camp Arifjan DFAC/Z-2 N/A N/A General N/A Unknown N/A Serviceable Room Insulation (General Performance) - gap between metal panels does not assist HVAC performance.

Camp Arifjan DFAC/Z-2 N/A N/A Structural N/A Unknown N/A Serviceable

Only visible structural elements are inspected. Frames covered under the ceiling and part of footing under the Building seem to be acceptable with respect to the other visible elements

Camp Arifjan DFAC/Z-2 N/A N/A Wall N/A Unknown N/A Serviceable Overall condition of the wall is acceptable

Camp Arifjan DFAC/Z-2 N/A N/A Windows/Roof N/A Unknown N/A Serviceable Windows are good. Many of the locks are not functional. One window is stuck. Roofs material & connection overall acceptable.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

Class K fire extinguishers are beyond their internal and hydrostatic test dates. The stickers indicating completion of these tests have no certification credentialing listed and are therefore noncompliant with NFPA Maintenance Intervals.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable The West exit walkway going North has an obstruction below 6’8”. This height is required as per NFPA Headroom

Camp Arifjan Zone 2 GFE

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable South East exit marked as “NO EXIT” in one sign and “Emergency Exit” with another sign. Both signs are non-compliant in accordance with NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable The South East exit door protrudes into the means of egress more than 7 inches which exceeds the maximum allowed protrusion as per NFPA.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

The South East and East Mechanical Room exit stairs are not in compliance with NFPA. The South East stair does not meet the minimum width requirements both stairs exceed the maximum riser height allowed.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

All of the hoods are constructed with sheet metal screws and other type fasteners. The use of these fasteners is a violation of NFPA.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

Breaker panels on entrance end of the dining area are obstructed by powdered drink mix display. 36 inches of clear space is required around electrical panels as per NFPA.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Serviceable The manual pull stations for all of the hood suppression systems are mounted too high.

The pull stations should be between in accordance with NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Hood suppression system nozzles are misaligned on the Deep Fat Fryer and Kettle Hood systems.

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

There are no instructions for operating the manual pull stations for any of the hood suppression systems. An instruction placard is not posted and reviewed by employees as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable The loading dock guardrails are damaged and will not close. These guards are required as per NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is evidence of grease leakage at several seams in the Kettle and Deep Fat Fryer Hoods. These seams are required to be sealed and grease tight as NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence the caulking used in all of the hood systems is fire rated as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There are no inspection labels for any of the hood suppression systems as required by

NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable All of the hoods have penetrations that are not welded or sealed as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable All of the hoods are constructed without continuous welds as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Serviceable There are no handrails at the North side emergency exit at the bottom of the stairs in accordance with NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Serviceable The handrail dimensions on the North side walkways are not compliant with NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Serviceable All of the exterior stairs have non-compliant handrails. The elevation of the landings require guards as per NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Grease filters are not rated (no markings present or documentation available at the time of inspection) on all hoods as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable The Deep Fat Fryer Hood is missing a grease collection tray on the grille end of the hood as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Fire extinguisher located in the containment area in accordance with NFPA Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Fire extinguisher is beyond the 6 year internal inspection date. NFPA Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Fire extinguisher tamper seal broken. NFPA Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable Fire extinguisher placed on the ground (not mounted). NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable

The secondary containment for the generator areas are made completely of combustible material and combustible materials are placed inside the containment areas. Containment areas are not in compliance with NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Serviceable The CO compressed gas cylinders are improperly stored (not secured in place) as per

NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of semi-annual maintenance being performed on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of scheduled maintenance on any of the hood systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of scheduled inspection, maintenance, or cleaning on any of the hood systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There are no maintenance reports or recommendations for any the hood suppression systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There are no hood and duct drawings on premises at the time of inspection as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable The year of manufacture and date of installation for the fusible links are not provided for any of the hood systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of maintenance on any of the hood systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of monthly inspections being conducted on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Building N/A Unknown N/A Unserviceable There is no evidence of service technician certification (fusible link replacement) as required by NFPA

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Grill Service Area (Flat grill-01 / Grill-02) N/A Unknown N/A Serviceable Safety Disconnect without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-5 N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-5 N/A Unknown N/A Serviceable Lack of maintenance inside all the Electrical Panels area subject to fire hazard with excess dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-54 N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-54 N/A Unknown N/A Serviceable Lack of maintenance inside all the Electrical Panels area subject to fire hazard with excess dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel LDB-2

N/A Unknown N/A Serviceable Lack of maintenance inside all the Electrical Panels area subject to fire hazard with excess dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel LDB-2

N/A Unknown N/A Serviceable Electrical Panel with improper terminations on Ground Bars.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PB1-A

N/A Unknown N/A Serviceable Electrical Panel with improper terminations on Ground Bars.

Camp Arifjan DFAC/Z-2 N/A N/A Emergency Light Servicing area N/A Unknown N/A Unserviceable Emergency Light found inoperative and the Test Button do not work.

Camp Arifjan DFAC/Z-2 N/A N/A Emergency Light hand wash area N/A Unknown N/A Unserviceable Emergency Light found inoperative and the Test Button do not work.

Camp Arifjan DFAC/Z-2 N/A N/A Emergency Light dining room area N/A Unknown N/A Unserviceable Emergency Light found inoperative and the Test Button do not work.

Camp Arifjan DFAC/Z-2 N/A N/A Emergency Light exit area N/A Unknown N/A Unserviceable Emergency Light found inoperative and the Test Button do not work.

Camp Arifjan DFAC/Z-2 N/A N/A Emergency Light VIP room N/A Unknown N/A Unserviceable Emergency Light found inoperative and the Test Button do not work.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-10

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-8

N/A Unknown N/A Serviceable Lack of maintenance inside all the Electrical Panels area subject to fire hazard with excess dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-11

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-11

N/A Unknown N/A Serviceable Lack of maintenance inside all the Electrical Panels area subject to fire hazard with excess dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-9

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Receptacles (50) N/A Unknown N/A Serviceable All Receptacles (50) equipment bonding jumper shall be connect.

Camp Arifjan DFAC/Z-2 N/A N/A Safety Disconnect Kitchen Area

(13) N/A Unknown N/A Serviceable Safety Disconnect without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Safety Disconnect Kitchen Area

(13) N/A Unknown N/A Serviceable

Lack of maintenance inside all the Safety Disconnect are subject to fire hazard with excess dust debris and greased inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A Control Panel DFAC 600 N/A Unknown N/A Serviceable Control Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A Control Panel DFAC 600 N/A Unknown N/A Serviceable Lack of maintenance inside the Control Panel are subject to fire hazard with excess dust debris and greased inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-1

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-2

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-2

N/A Unknown N/A Serviceable Electrical Panel Cover with improper Bonding terminations.

Camp Arifjan DFAC/Z-2 N/A N/A Electrical Panel PDB-2

N/A Unknown N/A Serviceable Panel without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Office area

N/A Unknown N/A Serviceable The J Box with Unused Opening. Electrical equipment is not installed in a neat and workmanlike manner.

Camp Arifjan DFAC/Z-2 N/A N/A Band Saw Safety Disconnect N/A Unknown N/A Serviceable Equipment Grounding Conductor is not connected to the bonding terminal.

Camp Arifjan DFAC/Z-2 N/A N/A Fire Suppressor Ventilation System - Fire Suppressor Exhaust Fans N/A Unknown N/A Serviceable

Lack of maintenance inside all Exhaust Fans are subject damages and fire hazard with excess Grease and dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #1 N/A Unknown N/A Serviceable

Lack of maintenance inside Exhaust Fans are subject damages and fire hazard with excess Grease and dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #2 N/A Unknown N/A Serviceable

Lack of maintenance inside Exhaust Fans are subject damages and fire hazard with excess Grease and dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #3 N/A Unknown N/A Serviceable

Lack of maintenance inside Exhaust Fans are subject damages and fire hazard with excess Grease and dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #3 N/A Unknown N/A Serviceable Exhaust Fan Belt with Serious Damage.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #5 N/A Unknown N/A Serviceable

Lack of maintenance inside Exhaust Fans are subject damages and fire hazard with excess Grease and dust debris inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Ventilation System - Exhaust Fan #5 N/A Unknown N/A Serviceable Exhaust Fan Belt with Serious Damage.

Camp Arifjan DFAC/Z-2 N/A N/A Water Heater Safety Disconnects N/A Unknown N/A Serviceable Safety Disconnect Switch without Fed from Identification and Voltage Identification.

Camp Arifjan DFAC/Z-2 N/A N/A Water Heater Safety Disconnects N/A Unknown N/A Serviceable Lack of maintenance inside the Control Panel are subject to fire hazard with excess dust debris and greased inside might create arc flash.

Camp Arifjan DFAC/Z-2 N/A N/A Water Heater Pump Receptacle N/A Unknown N/A Serviceable Receptacle with crack cover.

Camp Arifjan DFAC/Z-2 N/A N/A Pump Station (Safety Disconnect and Pressure Switch) N/A Unknown N/A Serviceable

Electrical Equipment with improper terminations.

Camp Arifjan DFAC/Z-2 120700 AJ-DA-COLDCTR01 Cold counter INOKSAN KBH 140 300172680002 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120701 AJ-DA-COLDCTR02 Cold counter INOKSAN KBH 140 300172680006 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120702 AJ-DA-COLDCTR03 Cold counter INOKSAN KBH 140 300172680007 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120703 AJ-DA-COLDCTR04 Cold counter INOKSAN KBH 140 300172680011 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120704 AJ-DA-COLDCTR05 Cold counter INOKSAN KBH 140 300172680013 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120705 AJ-DA-COLDCTR06 Cold counter INOKSAN KBH 140 3001078217 Serviceable Good working condition

Camp Arifjan DFAC/Z-2 120706 AJ-DA-COLDCTR07 Cold counter INOKSAN KBH 140 30024368009 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120707 AJ-DA-COLDCTR08 Cold counter INOKSAN KBH 140 30017273010 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120708 AJ-DA-COLDCTR09 Cold counter INOKSAN KBH 140 3001837001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120709 AJ-DA-COLDCTR010 Cold counter MULTINOX N/A TK-40941 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120710 AJ-DA-COLDCTR011 Cold counter MULTINOX N/A 02-0000 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120711 AJ-DA-COLDCTR012 Cold counter MULTINOX KBH 140 30017264003 Serviceable Water leaking Camp Arifjan DFAC/Z-2 120712 AJ-DA-COLDCTR013 Cold counter MULTINOX KBH 140 30017264004 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120713 AJ-DA-COLDCTR014 Cold counter MULTINOX KBH 140 30017264005 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120714 AJ-DA-HOTCT01 Hot counter MULTINOX KSN195 300172640004 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120715 AJ-DA-HOTCT02 Hot counter MULTINOX KSN195 30018839007 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120716 AJ-DA-HOTCT03 Hot counter MULTINOX KSN195 30018839008 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120717 AJ-DA-HOTCT04 Hot counter MULTINOX KSN195 30018839009 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120718 AJ-DA-HOTCT05 Hot counter MULTINOX KSN195 30017260009 Serviceable Halogen light bulb not functioning Camp Arifjan DFAC/Z-2 120727 AJ-DA-JUICEDISP01 Juice counter COFRIMEL N/A 01-0001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120728 AJ-DA-JUICEDISP02 Juice counter COFRIMEL N/A 02-0001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120759 AJ-KA-FOODWARMER01 Food Warmer LOCAL FAB 09-0001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120760 AJ-KA-FOODWARMER02 Food Warmer LOCAL FAB 09-0002 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120761 AJ-KA-FOODWARMER03 Food Warmer LOCAL FAB 09-0003 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120762 AJ-KA-FOODWARMER04 Food Warmer LOCAL N/A 30013122018 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120763 AJ-KA-FOODWARMER05 Food Warmer INOKSAN FAB 30013122012 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120725 AJ-DA-COFFEEMACH01 Coffee machine AMW FAB A136248 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120726 AJ-DA-COFFEEMACH02 Coffee machine AMW FAB A143514 Serviceable Awaiting material Camp Arifjan DFAC/Z-2 120738 AJ-KA-OVEN01 Oven GARLAND FAB TK-5176 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120739 AJ-KA-OVEN02 Oven FAGOR FAB 02-0004 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120740 AJ-KA-OVEN03 Oven FAGOR FAB 02-0005 Serviceable Awaiting material -motor fan Camp Arifjan DFAC/Z-2 120741 AJ-KA-OVEN04 Oven FAGOR FAB 02-0006 Serviceable Heating element & door handle assy not functioning Camp Arifjan DFAC/Z-2 120742 AJ-KA-OVEN05 Oven FAGOR FAB 02-0007 Serviceable Heating element 4000W X 240V not functioning Camp Arifjan DFAC/Z-2 120743 AJ-KA-OVEN06 Oven FAGOR FAB 02-0008 Serviceable Door handle assy not functioning Camp Arifjan DFAC/Z-2 120744 AJ-KA-TIL TINGPAN01 Tilting pan FAGOR FAB 11211272 1007 000317 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120746 AJ-KA-TIL TINGPAN03 Tilting pan FAGOR FAB 07-0001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120747 AJ-KA-TIL TINGPAN04 Tilting pan FAGOR FAB 07-0002 Serviceable Heating element 2000W X 240V not functioning Camp Arifjan DFAC/Z-2 120748 AJ-KA-TIL TINGPAN05 Tilting pan FAGOR FAB 07-0003 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120749 AJ-KA-TIL TINGPAN06 Tilting pan FAGOR FAB J124036 Serviceable Heating element 2000W X 240V not functioning Camp Arifjan DFAC/Z-2 120750 AJ-KA-BOILER01 Boiler FAGOR FAB 1120523550 1004 000121 Serviceable Awaiting material Camp Arifjan DFAC/Z-2 120751 AJ-KA-DEEPFRYER01 Deep fryer FAGOR FAB 112082000 1003 001031 Serviceable Awaiting material Camp Arifjan DFAC/Z-2 120752 AJ-KA-DEEPFRYER02 Deep fryer FAGOR FAB 112824000 1005 001055 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120753 AJ-KA-DEEPFRYER03 Deep fryer FAGOR FAB 1120824000 1005 001057 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120754 AJ-KA-FG6FT01 Flat grill 6ft FAGOR FAB 08-0001 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120755 AJ-KA-FG6FT02 Flat grill 6ft MARENO FAB 08-0002 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120756 AJ-KA-DOUGHMIXER01 Dough mixer SPAR FAB 101116 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120757 AJ-KA-DOUGHMIXER02 Dough mixer SPAR FAB MO14240 Serviceable Good working condition Camp Arifjan DFAC/Z-2 120758 AJ-KA-DOUGHMIXER03 Dough mixer UNIVEX FAB MO14241 Serviceable Good working condition Camp Arifjan DFAC/Z-2 N/A AJ-DA-FG3FT01 Flat grill 3ft FAGOR FAB 1120110850 Serviceable Good working condition Camp Arifjan DFAC/Z-2 N/A AJ-DA-FG3FT02 Flat grill 3ft FAGOR FAB 04-0000 Serviceable Good working condition Camp Arifjan DFAC/Z-2 N/A AJ-DA-FG3FT03 Flat grill 3ft FAGOR FAB 06-0000 Serviceable Good working condition Camp Arifjan DFAC/Z-2 N/A AJ-DA-FG3FT04 Flat grill 3ft FAGOR FAB 03-0000 Serviceable Good working condition

Camp Arifjan DFAC/Z-2 N/A N/A Safe Waste System near grease trap N/A N/A N/A Serviceable Only one air vent located on the safe waste system (fresh air system)

Camp Arifjan DFAC/Z-2 N/A N/A Dining Area Cornelius/American Metal Ware ED150- BCH/Model:80110E N/A Serviceable Back flow devices not installed on beverage dispensers or Coffee Machine.

Camp Arifjan DFAC/Z-2 N/A N/A Food Serving Area INOKSAN KSF 190 N/A Serviceable 3/8 Flexible drain hose installed on hot food warmer undersized causing periodic stoppage of drainage during cleaning total of 8 units.

Camp Arifjan DFAC/Z-2 N/A N/A Customer Hand Wash Area N/A N/A N/A Serviceable

Some of the Customer Area Hand Wash Sink faucets are loose, rusted and frayed water supply lines, leak on angle stop under counter. Back splash behind counter tops lacking caulk; rust and mildew stains on wall of backsplash.

Camp Arifjan DFAC/Z-2 N/A N/A Bakery Area N/A N/A N/A Serviceable Bakery Area loose Faucet on sink is not secured

Camp Arifjan DFAC/Z-2 N/A AJ-KA-GREASETRAP 01 Underground Grease Interceptor N/A N/A N/A Unserviceable Outdoor Grease trap is Inadequate sized for the facility and no longer serviceable.

Camp Arifjan DFAC/Z-2 N/A N/A Pot Wash Area N/A N/A N/A Serviceable Pot Wash Area 100lb Grease interceptor has a broken weld let (Thread Let) at 2 in drain connection.

Camp Arifjan DFAC/Z-2 N/A N/A Pot Wash Area N/A N/A N/A Serviceable Improper use of pre-rinse faucet recently installed, Pre-rinse faucet has non-compliant hose connection.

Camp Arifjan DFAC/Z-2 N/A N/A Main Kitchen Area N/A N/A N/A Serviceable Main Kitchen Area Single Handle sink Faucet loose

Camp Arifjan DFAC/Z-2 N/A N/A Outside Dining Facility N/A N/A N/A Unserviceable All outside hose faucets do not have a vacuum breaker devices or an anti-siphon hose Bibb installed.

Camp Arifjan DFAC/Z-2 N/A N/A Outside Dining Facility N/A N/A N/A Serviceable Centrifugal Pump # 1 located near water tanks has a leak on pump housing and on 1in Elbow.

Camp Arifjan DFAC/Z-2 N/A N/A Pastry Area N/A N/A N/A Serviceable Bar sink cabinet is not secured to the wall.

Camp Arifjan DFAC/Z-2 N/A N/A DFAC 2 Grounds N/A N/A N/A Serviceable

1. X Bracing on HVAC unit stand is not adjusted properly above the walkway. 2.

Potable water tank #2 has issue at top overflow. 3. Step and or slope is not added to back side stairway. 4. Fence behind chillers is not adequate. 5. Metal walkway in front of chillers, going to DFAC, up ramp and the receiving dock is not adequate. 6. Metal decking in outside grill area is not adequate. 7. Fencing around generators is not adequate. 8. Wooden walkways are not adequate. 9. Handrails are not adequate. 10.

Weapon cleaning station is not adequate. 11. Metal sheeting going up ramp is not adequate. 12. All graveled areas are not adequate.

Camp Arifjan DFAC/Z-2 N/A N/A HVAC Cold room HASAWI H8-LE-20X-EML 10D-325628 Serviceable Abnormal sound from piston ring and crank shaft bearing Camp Arifjan DFAC/Z-2 N/A 51-1403 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Electrical Conductor (3 pol) barking sound (abnormal noisy ) Camp Arifjan DFAC/Z-2 N/A 51-1404 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Freezer drain pipe water leaking and door aluminum reaper loose Camp Arifjan DFAC/Z-2 N/A 51-1250 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Freezer drain pipe water leaking, ice accumulated on the floor Camp Arifjan DFAC/Z-2 N/A 51-1274 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Compressor head leaking.

Camp Arifjan DFAC/Z-2 N/A 51-1441 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Compressor head gas leaking and Condenser coil gas leak Camp Arifjan DFAC/Z-2 N/A 51-1562 HVAC Reefer container HASAWI H8-LE-20X-EML N/A Serviceable Compressor head gas leaking and door beading rubber gasket teared Camp Arifjan DFAC/Z-2 N/A N/A HVAC Cold Room HASAWI H8-LE-20X-EML 10D-325610 Serviceable Condenser Fins bended (evaporator coil).

Camp Arifjan DFAC/Z-2 PKAC-4495 N/A HVAC PKAC unit ROYAL TEMP GPU 340 C703071240410A1140002 Serviceable

“V” belt cracked (belt #BL1950). Blower plump bearing noisy due lack of lubrication (Both side). Air filter clogged. Drain pan dirt and slurry clogged. Fresh air duct filter clogged. Low pressure and high pressure cut-off switch disconnected. Improper insulation on the suction line. Disconnected terminal no insulation

Camp Arifjan DFAC/Z-2 PKAC-4496 N/A HVAC PKAC unit ROYAL TEMP GPU 340 C703071240410A1140003 Serviceable Motor baring noisy. Belt and Pulley misalignment.

Camp Arifjan DFAC/Z-2 SPAC-5048 N/A HVAC split unit TOPCOOL HOM24HR 900046 Serviceable Outdoor Suction line valve gas leaking Camp Arifjan DFAC/Z-2 SPAC-5047 N/A HVAC split unit TOPCOOL HOM24HR 901023 Serviceable Outdoor Suction line valve gas leaking heavily Camp Arifjan DFAC/Z-2 SPAC-5043 N/A HVAC split unit TOPCOOL HOM24HR 901380 Serviceable Sensor E2 heater not working Camp Arifjan DFAC/Z-2 SPAC-5016 N/A HVAC split unit TOPCOOL HOM24HR 901035 Unserviceable Indoor unit noisy and vibrating Camp Arifjan DFAC/Z-2 SPAC-5018 N/A HVAC split unit TOPCOOL HOM24HR 900413 Serviceable Compressor not working Camp Arifjan DFAC/Z-2 SPAC-5019 N/A HVAC split unit TOPCOOL HOM24HR 901268 Unserviceable Indoor unit noisy Camp Arifjan DFAC/Z-2 SPAC-5022 N/A HVAC Split unit TOPCOOL HOM24HR 901401 Serviceable Suction line valve gas and oil leaking Camp Arifjan DFAC/Z-2 SPAC-(no number) N/A HVAC Split unit TOPCOOL HOM24HR B92525500901234 Serviceable Oil presence found in outdoor unit suction valve.

Camp Arifjan DFAC/Z-2 SPAC-5007 N/A HVAC Split unit TOPCOOL HOM24HR 900105 Unserviceable Indoor unit vibration and noisy.

Camp Arifjan DFAC/Z-2 SPAC-5004 N/A HVAC Split unit TOPCOOL HOM24HR 90004 Serviceable Condenser coil fins bended Camp Arifjan DFAC/Z-2 SPAC-5037 N/A HVAC Split unit TOPCOOL HOM24HR 900814 Serviceable Improper cooling. Water leaking from indoor unit due to filter blockage Camp Arifjan DFAC/Z-2 SPAC-5040 N/A HVAC Split unit TOPCOOL HOM24HR 901365 Serviceable Sensor E3 compressor not working .

Camp Arifjan DFAC/Z-2 SPAC-(no number) N/A HVAC Split unit TOPCOOL HOM24HR 900385 Serviceable Outdoor Suction line valve oil and gas leaking.

Camp Arifjan DFAC/Z-2 SPAC-5025 N/A HVAC Split unit TOPCOOL HOM24HR 900422 Serviceable Outdoor unit liquid line and suction line copper pipe pinched off Camp Arifjan DFAC/Z-2 SPAC-5026 N/A HVAC Split unit TOPCOOL HOM24HR 901158 Serviceable Compressor not working.

Camp Arifjan DFAC/Z-2 SPAC-5027 N/A HVAC Split unit TOPCOOL HOM24HR 901257 Serviceable Outdoor Suction line valve oil and gas leaking. Safety electrical service cover missing

Camp Arifjan DFAC/Z-2 SPAC-5033 N/A HVAC Split unit TOPCOOL HOM24HR 901258 Serviceable Indoor Louver blade broken. Filter block (indoor) Camp Arifjan DFAC/Z-2 SPAC-5032 N/A HVAC Split unit TOPCOOL HOM24HR 901267 Unserviceable Indoor unit display not working Camp Arifjan DFAC/Z-2 SPAC-(no number) N/A HVAC Split unit TOPCOOL HOM24HR 900383 Serviceable Outdoor Suction line valve oil and gas leaking Camp Arifjan DFAC/Z-2 SPAC-5011 N/A HVAC Split unit TOPCOOL HOM24HR P92525500101298 Serviceable Water leaking from Indore unit due to filter blockage and blower motor noisy Camp Arifjan DFAC/Z-2 SPAC-5010 N/A HVAC Split unit TOPCOOL HOM24HR 901230 Serviceable Drain lines not arranged properly Camp Arifjan DFAC/Z-2 N/A N/A HVAC Split unit TOPCOOL HOM24HR B92525500900945 Unserviceable Indoor unit vibration and noisy Camp Arifjan DFAC/Z-2 WAC-767 N/A HVAC window unit COOLLINE N/A TK-11021 Serviceable Air filter damaged Camp Arifjan DFAC/Z-2 WAC-973 N/A HVAC window unit COOLLINE N/A N/A Serviceable Blower motor rattling sound Camp Arifjan DFAC/Z-2 Light Fixture N/A Electrical RM Light Fixture N/A N/A N/A Unserviceable See NEC Art. 110.12

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable

The secondary containment for the generator and grease tank areas are made completely of combustible material and combustible materials are placed inside the containment areas. Containment areas are not in compliance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Hood suppression system nozzles are misaligned on the Deep Fat Fryer (above the grills) and Kettle Hood systems.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Serviceable The manual pull stations for all of the hood suppression systems are mounted too high. The pull stations should be in accordance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There are no instructions for operating the manual pull stations for any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There are no inspection labels for any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable

There is evidence contrary to the below NFPA 17A codes for compliant installation of activation devices on Serving line Grill Hood 2. This fusible link is near inadvertent activation due to improper installation.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is evidence of grease leakage at several seams in Hoods 1 & 2, Kettle and Deep Fat Fryer Hoods. These seams are required to be sealed and grease tight as NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence the caulking used in all of the hood systems is fire rated as required by

NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable All of the hoods are constructed with sheet metal screws and other type fasteners. The use of these fasteners is a violation of NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable All of the hoods have penetrations that are not properly sealed in accordance with NFPA Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable All of the hoods have penetrations that are not welded or sealed as required by NFPA.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Grease filters are damaged on the Oven Hood NFPA Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The grease filters in the Oven Hood do not cover the entire area as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The grease filters in the Oven, Kettle, and Bakery Hoods are not easily accessible for cleaning as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no access for Inspection or cleaning the Kettle, Deep Fat Fryer, or Oven duct systems without moving immobile appliances as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable All of the hoods are constructed without continuous welds as required by

NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable

In the generator area, the following issues exist pertaining to fire extinguishers:

1. Fire extinguisher located in the containment area. NFPA

2. Fire extinguisher is beyond the 6 year internal inspection date. NFPA

3. Fire extinguisher label missing. NFPA

4. Fire extinguisher placed on the ground (not mounted) in the generator containment and grease tank areas. NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable

All of the “POWDER” brand fire extinguishers are due, or past due, their 6 year internal inspection.

There are stickers from a local vendor with a 2016 inspection date, but the stickers do not indicate the type of inspection completed and not in compliance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable

Class K fire extinguishers are beyond their internal and hydrostatic test dates. The stickers indicating completion of these tests have no certification credentialing listed and are therefore noncompliant with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Three additional fire extinguishers are required, one on the center hallway in the dining area and two, one on either end, in the kitchen area hallway.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Military office has a coffee pot plugged into a power strip. This overloaded the power strip. The coffee pot should be plugged directly into a wall receptacle in accordance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The stair hand rails at the grease tank are made with 2x4 boards and are not in compliance with

NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The stairs at the grease tank are not in compliance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Staff breakroom means of egress is obstructed by a table. This table is not in accordance with

NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Staff exit and Hallway exit signs are not illuminated in accordance with NFPA Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable Staff exit EXIT sign is made of paper and is not in accordance with NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Serviceable All of the exterior stairs have non-compliant handrails. The elevation of the landings are not in accordance with NFPA. And the guards have a wider separation than allowed by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The Deep Fat Fryers have no evidence of over-temperature shut off as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of testing on the fire suppression systems being conducted on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of monthly inspections being conducted on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of service technician certification (fusible link replacement) as required by

NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of semi-annual maintenance being performed on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable The year of manufacture and date of installation for the fusible links are not provided for any of the hood systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of scheduled maintenance on any of the hood systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of scheduled maintenance on any of the hood systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of scheduled inspection, maintenance, or cleaning on any of the hood systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of maintenance on any of the hood systems as required by NFPA

Camp Arifjan Zone 6 GFE

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There are no maintenance reports or recommendations for any the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There are no hood and duct drawings on premises at the time of inspection as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Building DFAC Zone 6 N/A N/A N/A Unserviceable There is no evidence of 6 month cyclic maintenance being performed on any of the hood suppression systems as required by NFPA

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Fats, Oils and Grease Storage Tank N/A N/A N/A Serviceable Placed within a makeshift (expeditionary style) secondary containment constructed of wood and bladder material. The wood frame is showing signs of fatigue.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Grease Trap N/A N/A N/A Serviceable Metal UST is corroded from excessive use of sodium hypochlorite.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Ice Reefer N/A N/A N/A Serviceable Mobile reefer unit powered by diesel motor has leaked POL onto the surrounding soil.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A Generator Secondary Containment N/A N/A N/A Serviceable Placed within a makeshift (expeditionary style) secondary containment constructed of wood and bladder material. The wood frame is showing signs of fatigue.

Camp Arifjan DFAC T6500 / Z-6 N/A N/A HM Storage Container N/A N/A N/A Serviceable No secondary containment or segregation of incompatible HM stored in the container.

Camp Arifjan DFAC T6500 / Z-6 Unknown AJ-DA-COFFEEMACH Dining Area Coffee Machine BUNN U3A.S.S. U3000142199 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120844 AJ-DA-COFFEEMACH03 Dining Area Coffee Machine CICILWARE CL-100 1-0005 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120845 AJ-DA-COFFEEMACH04 Dining Area Coffee Machine CICILWARE CL-100 1-0006 Serviceable Waiting Material - Machine Repairable Camp Arifjan DFAC T6500 / Z-6 120846 AJ-DA-COFFEEMACH05 Dining Area Coffee Machine CICILWARE CL-100 1-0007 Serviceable Waiting Material - Machine Repairable Camp Arifjan DFAC T6500 / Z-6 120805 AJ-DA-COLDCTR15 Dining Area Cold counter INOKSAN KBH-190 30018847001 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120807 AJ-DA-COLDCTR16 Dining Area Cold counter INOKSAN KBH-190 30018847007 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120808 AJ-DA-COLDCTR17 Dining Area Cold counter INOKSAN KBH-190 30018847009 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120809 AJ-DA-COLDCTR18 Dining Area Cold counter INOKSAN KBH-190 30018847008 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120810 AJ-DA-COLDCTR19 Dining Area Cold counter INOKSAN KBH-190 30018847005 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120811 AJ-DA-COLDCTR20 Dining Area Cold counter INOKSAN KBH-190 30018847004 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120812 AJ-DA-COLDCTR21 Dining Area Cold counter INOKSAN N/A 30018847002 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120813 AJ-DA-COLDCTR22 Dining Area Cold counter INOKSAN KBH-190 30018847006 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120814 AJ-DA-COLDCTR23 Dining Area Cold counter INOKSAN KBH-190 30010782018 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120815 AJ-DA-COLDCTR24 Dining Area Cold counter Local Local TKN55355 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120816 AJ-DA-COLDCTR25 Dining Area Cold counter INOKSAN KBH-140 30018852003 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120817 AJ-DA-COLDCTR26 Dining Area Cold counter INOKSAN KBH-140 30017273003 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120818 AJ-DA-COLDCTR27 Dining Area Cold counter INOKSAN KBH-140 30017273001 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120880 AJ-DA-FG3FT05 Dining Area Flat grill 3ft FAGOR N/A 4100184 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120804 AJ-DA-FG3FT07 Dining Area Flat grill 3ft FAGOR N/A 4090168 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120806 AJ-DA-FG3FT08 Dining Area Flat grill 3ft FAGOR N/A 4090169 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120819 AJ-DA-HOTCTR06 Dining Area Hot counter INOKSAN KBH-195 30024364001 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120820 AJ-DA-HOTCTR07 Dining Area Hot counter INOKSAN KBH-195 30024364002 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120821 AJ-DA-HOTCTR08 Dining Area Hot counter INOKSAN KSN-195 30024364011 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120822 AJ-DA-HOTCTR09 Dining Area Hot counter INOKSAN KBH-195 30024364006 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120823 AJ-DA-HOTCTR010 Dining Area Hot counter INOKSAN N/A 30017260003 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120824 AJ-DA-HOTCTR011 Dining Area Hot counter INOKSAN KBH-195 30017260003 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120825 AJ-DA-HOTCTR012 Dining Area Hot counter INOKSAN KSN-195 30024364007 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120826 AJ-DA-HOTCTR013 Dining Area Hot counter INOKSAN KBH-195 30018843103 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120827 AJ-DA-HOTCTR014 Dining Area Hot counter INOKSAN KSN-195 30018843002 Serviceable Operational Good Condition

Camp Arifjan DFAC T6500 / Z-6 120850 AJ-DA-JUICEDISP05 Dining Area Juice Dispenser COFRIMELL COLDREAM 3M 5010251 Serviceable Operational Good Condition

Camp Arifjan DFAC T6500 / Z-6 120851 AJ-DA-JUICEDISP06 Dining Area Juice Dispenser COFRIMELL COLDREAM 3M 5010244 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120840 AJ-DA-MICROWAVEOVEN01 Dining Area Microwave Oven KENWOOD N/A 14954020079 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120842 AJ-DA-MICROWAVEOVEN03 Dining Area Microwave Oven SHARP KBH-140 1-0002 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120842 AJ-DA-TOASTER01 Dining Area Toaster MILAN TOAST N/A 1-0003 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120874 AJ-KA-BOILER02 Kitchen Area Boiler FAGOR ME9-15-BM 1007000152 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120875 AJ-KA-DEEPFRYER04 Kitchen Area Deep Fryer FAGOR N/A 60300098 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120876 AJ-KA-DEEPFRYER05 Kitchen Area Deep Fryer FAGOR N/A 3020138 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120877 AJ-KA-DEEPFRYER06 Kitchen Area Deep Fryer FAGOR N/A 3020134 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120878 AJ-KA-DEEPFRYER07 Kitchen Area Deep Fryer FAGOR N/A 3070028 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120879 AJ-KA-DEEPFRYER08 Kitchen Area Deep Fryer FAGOR N/A 3070032 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120882 AJ-KA-DOUGHMIXER04 Kitchen Area Dough Mixer TEKNO STAMP N/A 5460701 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120880 AJ-KA-FG3FT03 Dining Area Flat grill 3ft MIRROR N/A 4100184 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120803 AJ-KA-FG3FT06 Dining Area Flat grill 3ft MIRROR N/A 4080169 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120083 AJ-KA-FOODWARMER06 Kitchen Area Food Warmer Local Local 1-0023 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120884 AJ-KA-FOODWARMER07 Kitchen Area Food Warmer Local N/A 1-0024 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120885 AJ-KA-FOODWARMER08 Kitchen Area Food Warmer Local Local 1-0025 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120886 AJ-KA-FOODWARMER09 Kitchen Area Food Warmer INOKSAN ABS-101 30013122015 Serviceable Fan Motor Blower (waiting for material) Camp Arifjan DFAC T6500 / Z-6 120860 AJ-KA-OVEN07 Kitchen Area Oven FAGOR N/A 1-0012 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120861 AJ-KA-OVEN08 Kitchen Area Oven FAGOR N/A 1-0013 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120862 AJ-KA-OVEN09 Kitchen Area Oven FAGOR N/A 1-0014 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120863 AJ-KA-OVEN010 Kitchen Area Oven FAGOR N/A 1-0015 Serviceable Fan Motor Assy (waiting for material) Camp Arifjan DFAC T6500 / Z-6 120864 AJ-KA-OVEN011 Kitchen Area Oven Local N/A 1-0016 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120865 AJ-KA-OVEN012 Kitchen Area Oven FAGOR N/A 1-0017 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120866 AJ-KA-OVEN013 Kitchen Area Oven SANTEC N/A 1-0018 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120867 AJ-KA-TILTINGPAN07 Kitchen Area TilTing Pan FAGOR N/A 3070069 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120868 AJ-KA-TILTINGPAN08 Kitchen Area TilTing Pan FAGOR N/A 3070078 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120869 AJ-KA-TILTINGPAN09 Kitchen Area TilTing Pan FAGOR N/A 61100082 Serviceable Operational Good Condition Camp Arifjan DFAC T6500 / Z-6 120870 AJ-KA-TILTINGPAN010 Kitchen Area TilTing Pan FAGOR N/A 1-0019 Serviceable Operational Good Condition…