VOC_SBO_FFE Checklist.pdf
PDF 219 KB Posted
- Attached to
- MO FY27 Thomas Jefferson Drydock REFERENCES and ATTACHMENTS Federal contract opportunity
- Solicitation number
- 1305M226Q0100REF
About this file
This document is a VOC/SBO (Vessel Operations Center/Small Business Operations) checklist for Fire Fighting Equipment (FFE) servicing on NOAA vessels. The checklist establishes mandatory procedures and verification requirements for the maintenance and testing of fire suppression systems to ensure operational readiness and personnel safety.
The checklist is divided into three system categories: Pre-engineered systems (NFPA 2001), CO2 systems (NFPA 12), and Halon systems (NFPA 12A). Pre-service items include verification that personnel are NFPA-certified for the specific system type, propulsion and generator engines are operable for shutdown testing, and engine room blowers are functional. For all systems, the checklist requires witnessed verification of multiple safety measures including successful shutdown of propulsion/generator engines, activation of audible/visual alarms, closure of ventilation systems, and proper functioning of manual discharge devices. Additional requirements encompass inspection and hydrostatic testing of flexible hoses (within 12 years), weight verification or HALON level marking of bottles, hydrotest date verification not exceeding 12 years (with Halon bottles exempted), servicing of manual release cables, installation of seals on release pins, and affixing of servicing tags/decals. For CO2 and Halon systems specifically, a witnessed 30-second delay before system discharge into machinery space must be recorded, with the delay bottle not activating prior to 30 seconds or longer than 36 seconds. The document emphasizes that NOAA personnel shall not occupy any space protected by a fire suppression system during testing, maintenance, or repairs. All servicing activities must be documented in a servicing report filed with vessel documents, and both the NOAA representative and technician must sign and date the completed checklist.
View the file
Other files for this federal contract opportunity
Show all 50
MO FY27 Thomas Jefferson Drydock REFERENCES and ATTACHMENTS has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOC/SBO checklist for FFE servicing
Pre-service items:
Pre-engineered systems NFPA 2001
Personnel NFPA certified for type of system to be serviced
Propulsion and generator engines are operable for shutdown test
Engine room blowers are operational (if installed)
Instructions for manual deployment are located at discharge control(s)
Witnessed gauge reading of bottle within green zone
Witnessed successful shutdown of all propulsion and generator engines within the protected space and audible/ visual alarm sounded.
Witnessed successful shutdown of all powered ventilation blowers (if installed)
Confirmed electrically powered machinery space ventilation closures fully closed after discharge test shutdown initiated (if installed)
Confirmed technician serviced manual remote release cable
Confirmed technician installed seal on release pin for manual discharge handle
Confirmed technician reattached remote release cable onto bottle discharge mechanism
Confirmed technician affixed servicing tag/decal to bottle
Confirmed manual closure devices for machinery space(s) operate or properly stowed for immediate use
Confirmed discharge control display is illuminated green and override switch is in the "normal" position
Verbally discussed with technician any deficiencies and or tests that could not be conducted.
Confirmed system was placed back into an operational status. Servicing pin removed/release cable reattached.
Received servicing report and filed with vessel documents
Instructions for deployment are located at remote discharge controls AND local discharge controls at storage bottle(s)
Bottle weighed and weight recorded or HALON level marked on bottle.
Bottle hydrotest date verified not to have exceeded 12 years (Halon bottles are exempted from hydro testing)
Confirmed interconnecting flexible hoses were visually inspected and were hydrostatically tested within 12 years.
Witnessed successful shutdown of all powered ventilation blowers (if installed)
Witnessed 30 second delay before system discharge into machinery space. Time to be recorded on servicing report.
Delay bottle must not activate prior to 30 sec or longer than 36 sec.
Confirmed powered discharge warning alarms activated (if installed).
Confirmed electrically powered machinery space ventilation closures fully closed after discharge test shutdown initiated (if installed)
Confirmed manual closure devices for machinery space(s) operate or properly stowed for immediate use
Confirmed technician serviced manual remote release cable
Confirmed technician reattached remote release cable onto bottle discharge mechanism
Confirmed technician affixed servicing tag/decal to bottle
Verbally discussed with technician any deficiencies and or tests that could not be conducted.
Confirmed system was placed back into an operational status.
Received servicing report and filed with vessel documents
CO2 NFPA 12 and Halon NFPA 12A systems
At no time shall NOAA personnel occupy a space protected by a fire suppression system during testing, maintenance, or repairs.
NOAA Rep: _________________________ Date: ________
Technician: _________________________ Date: ________