Tagos-13 Class FMEA 09-11-2020_122451610.pdf
PDF 613 KB Posted
- Attached to
- FY27 NOAA Ship Gordon Gunter Drydock REFERENCES Federal contract opportunity
- Solicitation number
- 1305M226Q0144REF
About this file
This is a Failure Mode Effect Analysis (FMEA) Design Verification Test Procedure document for a Monitor and Alarm System Profinet Upgrade on three NOAA vessels: TAGOS-13 Class, NOAA GUNTER, and NOAA SETTE, dated November 9, 2020, and reviewed by ABS Houston.
The document provides comprehensive failure analysis for the upgraded Monitor and Alarm System, examining primary component failures and their effects on the vessel operators' ability to monitor machinery and safety systems. The analysis assumes the system operates properly before failure, the vessel is underway with propulsion control on the bridge, only single non-concurrent failures are considered, and the engine room operates in unattended mode. For each failure scenario, the document details the failure description, operational effect, crew detection methods, alternative operational procedures, required corrections, and test procedures for verification. The system employs redundancy across critical components, including dual power supplies, dual Profinet buses (A and B), and multiple Profinet Scanner Modules (PSM 1-8) that manage Input/Output (I/O) modules. Failures analyzed span system power (main, emergency, 24 VDC supplies, and UPS), Programmable Logic Controller components (power supply, CPU, Ethernet module, and dual Profinet buses), Personal Computer systems, communication cables, and sixty-one individual I/O modules monitoring various vessel systems including main diesel cylinders, propulsion motors, steering gears, generators, fire systems, bilge systems, and auxiliary equipment. The document demonstrates system resilience through operational redundancy, allowing continued vessel monitoring through alternative power sources and communication pathways when individual components fail, with alarms alerting crew to failures requiring corrective action.
View the file
Other files for this federal contract opportunity
Show all 50
FY27 NOAA Ship Gordon Gunter Drydock REFERENCES has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Failure Mode Effect Analysis Design Verification Test Procedure
Monitor and Alarm System Profinet Upgrade for
NOAA TAGOS-13 CLASS
NOAA GUNTER
NOAA SETTE
November 09, 2020
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
NOAA TAGOS-13 CLASS
Failure Mode Effect Analysis Design Verification Test Procedure
Monitor and Alarm System
Table of Contents
1 Overview and Conventions…………………………………….…………….……..
2 System Power………………………………………………………….……………
2.1 Main Power Failure……………………………………………….…...……
2.2 Emergency Power Failure……………………………………...…….…..…
2.3 24 VDC Power Supply “A” Fail……………………………….……...……
2.4 24 VDC Power Supply “B” Fail……………………………….…………...
2.5 UPS Failure…………………………………..…………….………….……
3 Programmable Logic Controller (PLC)…………………………….…………..…..
3.1 PLC Power Supply Failure……………………………………...………….
3.2 PLC CPU Failure……………………………………….…………………..
3.3 PLC Ethernet Module “A” Failure……………….……………….………..
3.4 Profinet Module “A” Module Failure………………………………………
3.5 Profinet Module “B” Module Failure………………………………………
4 Personal Computer (PC) Failures…….…………………………………………….
4.1 PC Failure….………………………………………………………….…
4.2 PC Monitor Failure…..……………………………………………………..
5 I/O Communication Failures………………………………………………………..
5.1 I/O Communication Cable “A” Failure ……………………………………
5.3 I/O Communication Cable “B” Failure ……………………………………
6 PC Communications Failures.…………………………………………...…………
6.1 Ethernet Cable Failure “A” Open………………………………..…………
7 I/O Module Failures………………………………………………………………...
7.1 Profinet Scanner Module 1 Failure………………………………………..
7.2 I/O Module D1-M1 Failure…………………………………………………
7.3 I/O Module D1-M2 Failure…………………………………………………
7.4 I/O Module D1-M3 Failure…..……………………………………………..
7.5 I/O Module D1-M4 Failure…..……………………………………………..
7.6 I/O Module D1-M5 Failure…………………..……………………………..
7.7 I/O Module D1-M6 Failure………..……………………………………….
7.8 I/O Module D1-M7 Failure…………………………………………………
7.9 I/O Module D1-M8 Failure………………………………………………...
7.10 Profinet Scanner Module 2 Failure…...……………………………………
7.11 I/O Module D2-M1 Failure……………………..…………………………..
7.12 I/O Module D2-M2 Failure………………...……..………………………...
7.13 I/O Module D2-M3 Failure………………………..………………………..
7.14 I/O Module D2-M4 Failure…………………………………………………
7.15 I/O Module D2-M5 Failure………………………..………………………..
7.16 Profinet Scanner Module 3 Failure…………………………………………
7.17 I/O Module D3-M1 Failure…………………………………………………
7.18 I/O Module D3-M2 Failure…………………………………………………
7.19 I/O Module D3-M3 Failure…………………………………………………
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.20 I/O Module D3-M4 Failure………………………………..…………...…...
7.21 I/O Module D3-M5 Failure……………………………………………....…
7.22 Profinet Scanner Module 4 Failure……………………………………...….
7.23 I/O Module D4-M1A Failure……………………………………………
7.24 I/O Module D4-M1B Failure……………………………………………… .
7.25 I/O Module D4-M2A Failure…………………………………………
7.26 I/O Module D4-M2B Failure……….……………………..………………..
7.27 I/O Module D4-M3A Failure…….…………………………..……………..
7.28 I/O Module D4-M3B Failure…….…………………………..………… .….
7.29 I/O Module D4-M4 Failure…………………………………………………
7.30 I/O Module D4-M5 Failure…………………………………………………
7.31 Profinet Scanner Module 5 Failure……………………………..…………..
7.32 I/O Module D5-M1A Failure……………………………………..………..
7.33 I/O Module D5-M1B Failure……………………………………………….
7.34 I/O Module D5-M2A Failure……………………………………………… .
7.35 I/O Module D5-M2B Failure………………………………………..……...
7.36 I/O Module D5-M3A Failure…………………………………..…………..
7.37 I/O Module D5-M3B Failure………………………………..……………...
7.38 I/O Module D5-M4A Failure……………………………………………….
7.39 I/O Module D5-M4B Failure……………………………………………….
7.40 I/O Module D5-M5A Failure……………………………………………….
7.41 I/O Module D5-M5B Failure……………………………………………….
7.42 I/O Module D5-M6A Failure……………………………………………….
7.43 I/O Module D5-M6B Failure……………………………………………….
7.44 Profinet Scanner Module 6 Failure…,,,……………………………….……
7.45 I/O Module D6-M1 Failure………………………………………..………..
7.46 I/O Module D6-M2 Failure………………………………………..………..
7.47 I/O Module D6-M3 Failure…………………………………………………
7.48 Profinet Scanner Module 7 Failure……………………………...…………
7.49 I/O Module D7-M1A Failure……………………………………………….
7.50 I/O Module D7-M1B Failure……………………………………………….
7.51 I/O Module D7-M2 Failure……………………………………………..…..
7.52 I/O Module D7-M3 Failure…………………………………………………
7.53 Profinet Scanner Module 8 Failure………………………………………...
7.54 I/O Module D8-M1A Failure……………………………………………….
7.55 I/O Module D8-M1B Failure……………………………………………….
7.56 I/O Module D8-M2A Failure……………………………………………… .
7.57 I/O Module D8-M2B Failure……………………………………...………..
7.58 I/O Module D8-M3A Failure……………………………………………….
7.59 I/O Module D8-M3B Failure …………………………………………
7.60 I/O Module D8-M4A Failure……………………………………………….
7.61 I/O Module D8-M5 Failure…………………………………………………
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
1 Overview and Conventions This Failure Analysis is intended to examine the integrity of the Monitor and Alarm system to be upgraded aboard the ships. The analysis will focus on failures of the primary system components and the effects on the operators’ ability to monitor the vessels’ machinery and safety systems. The basic assumption used in this FMEA is that the system is operating properly at the time of the failure, the vessel is underway, the propulsion control location is on the bridge and only single non-concurrent failures will be considered. We will also assume the engine room is being operated in the unattended mode. The following structure will be used in each component’s failure analysis.
Failure Describes the failed components in the system.
Effect Describes the effect of the failed component on the system.
Detection Describes how the ships crew is made aware of the failure.
Alternatives Describes alternate means of safely operating the plant until corrective action is taken on the failed component.
Correction Describes what corrective actions are necessary to bring the system back to normal operation.
Test Procedure Describes a test procedure to verify actions in the Failure Analysis.
The MCSC is the “Main Control Station Console” located in the Engine Control Room.
2 System Power This section will examine failures of the Monitor and Alarm System power, including ship supply power, power supplies and UPS.
2.1 Main Power Failure
Failure The Main Power to the system fails.
Effect The ABT will switch to the Emergency Power supply and system operation will be unaffected. The UPS will prevent momentary interruption of power.
Detection 1. "Main Power Fail" alarm is annunciated on the MCSC.
2. "Engineer Trouble" alarm is annunciated on the EAP’s.
3. The "Main Power Available" IL on the MCSC is extinguished.
Alternatives System operates normally on the Emergency power source.
Correction Restore normal power.
Test Procedure 1. Secure the Main Power to MCSC.
2. Verify "Main Power Fail" alarm on MCSC CRT.
3. Verify the "Engineer Trouble" alarm on the EAP’s.
4. Verify the “Main Power Available” IL is extinguished.
5. Verify the system operates properly though the power loss.
Verify
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
2.2 Emergency Power Failure
Failure Emergency Power to the system fails while in operation.
Effect Operation will continue with operation from UPS Power.
Detection 1. “UPS Active" alarm is annunciated on the MCSC.
2. "Engineer Trouble" alarm is annunciated on the EAP’s.
3. The "Emergency Power Available" IL on the MCSC is extinguished.
Alternatives System operates normally on the UPS power source.
Correction Restore Emergency power.
Test Procedure 1. Secure the Emergency Power to MCSC.
2. Verify " UPS Active" alarm on MCSC CRT.
3. Verify the "Engineer Trouble" alarm on the EAP’s.
4. Verify the “Emergency Power Available” IL is extinguished.
5. Verify the system operates properly though the power loss.
Verified
2.3 24 VDC Power Supply “A” Fail
Failure 24 VDC Power Supply "A" fails.
Effect The 24 VDC power load is handled by the redundant "B" power supply. There is no effect on system operation.
Detection 1. "24 VDC "A" Power Supply Fail" alarm is annunciated on the
MCSC.
2. "Engineer Trouble" alarm is annunciated on the EAP’s.
Alternatives System operates normally on the "B" power supply.
Correction Correct problem with 24 VDC "A" power supply.
Test Procedure 1. Remove power to 24 VDC "A" power supply by removing Fuse
PSA.
2. Verify "24 VDC "A" Power Supply Fail" alarm on MCSC CRT.
3. Verify the “Engineer Trouble” alarm on the EAP’s.
4. Verify the system operates properly through the power supply failure.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
2.4 24 VDC Power Supply “B” Fail
Failure 24 VDC Power Supply "B" fails.
Effect The 24 VDC power load is handled by the redundant "A" power supply. There is no effect on system operation.
Detection 1. "24 VDC "B" Power Supply Fail" alarm is annunciated on the
MCSC.
2. "Engineer Trouble" alarm is annunciated on the EAP’s.
Alternatives System operates normally on the "B" power supply.
Correction Correct problem with 24 VDC "B" power supply.
Test Procedure 1. Remove power to 24 VDC "B" power supply by removing Fuse
PSB.
2. "24 VDC "B" Power Supply Fail" alarm on MCSC CRT.
3. Verify the “Engineer Trouble” alarm on the EAP’s.
4. Verify the system operates properly through the power supply failure.
Verified
2.5 UPS Failure
Failure The UPS supplying power to the Monitor and Alarm system fails.
Effect 115 VAC is momentarily interrupted to the Monitor and Alarm system. The monitor and alarm system will restart after the power interruption.
Detection 1. "Engineer's Assistance Needed" alarm will sound on the EAP’s.
2. "UPS Fail" alarm is annunciated on the MCSC after system restarts.
Alternatives System operates normally after restart.
Correction Correct problem with UPS.
Test Procedure 1. Simulate UPS failure by turning UPS ON/OFF switch of OFF.
2. Verify the Engineer's Assistance Needed" alarm sounds on the
EAP’s.
3. Verify the “UPS Fail” alarm is annunciated on the MCSC after system restarts.
4. Verify the system operates properly after system restart.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
3 Programmable Logic Controller (PLC) This section will examine failures in the PLC.
3.1 PLC Power Supply Failure
Failure The PLC power supply module fails.
Effect PLC functions are disabled. This causes I/O processing to terminate.
Detection 1. "Engineer’s Assistance Needed" alarm will sound on the EAP's.
2. "PLC Failure" alarm is displayed on the MCSC CRT.
Alternatives System machinery will need to be monitored locally until failure is corrected.
Correction Replace PLC Power Supply Module.
Test Procedure 1. Simulate PLC Power Supply failure by removing power to CPU.
2. Verify the "Engineer's Assistance Needed" alarm sounds on the
EAP's.
3. Verify the “PLC Failure” alarm is displayed on the MCSC CRT.
4. Verify the system operates properly after PLC power restored.
Verified
3.2 PLC CPU Failure
Failure The PLC CPU module fails.
Effect PLC functions are disabled. This causes I/O processing to terminate.
Detection 1. "Engineer’s Assistance Needed" alarm will sound on the EAP's.
2. "PLC Failure" alarm is displayed on the MCSC CRT.
Alternatives System machinery will need to be monitored locally until failure is corrected.
Correction Replace PLC CPU Module.
Test Procedure 1. Simulate PLC CPU failure by removing power to CPU.
2. Verify the "Engineer's Assistance Needed" alarm sounds on the
EAP's.
3. Verify the “PLC Failure” alarm is annunciated on the MCSC.
4. Verify the system operates properly after the PLC CPU mode is restored on “On Line”.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
3.3 PLC Ethernet Module Failure
Failure The PLC Ethernet communication fails.
Effect PLC to PC communication functions are disabled. This prevents I/O updates to the PC.
Detection 1. "Engineer’s Assistance Needed" alarm will sound on the EAP's.
2. "PLC Failure" alarm is displayed on the MCSC CRT.
Alternatives System machinery will need to be monitored locally until failure is corrected.
Correction Replace PLC Ethernet Module.
Test Procedure 1. Simulate PLC Ethernet Module failure by disconnecting the
Ethernet cable from the PLC Ethernet Module.
2. Verify the "Engineer's Assistance Needed" alarm sounds on the
EAP's.
3. Verify the “PLC Failure” alarm is displayed on the MCSC CRT.
4. Verify the system operates properly after the Ethernet cable is reconnected.
Verified
3.4 Profinet Bus A Fails
Failure Profinet Bus "A" module or cable fails.
Effect PLC to I/O Module communications on Bus "A" are disabled. I/O communications will continue on Bus "B" with no loss of functionality.
Detection 1. “Profinet Bus A Fail” alarm is annunciated on the MCSC.
2. Engineer Trouble" alarm will sound on the system.
Alternatives There is no loss of functionality on the system.
Correction Replace PBM "A" Module or Cable.
Test Procedure 1. Simulate Profinet Bus A fail by disconnecting cable A from
PLC Profinet module.
2. Verify the "Profinet Bus A Fail" alarm is annunciated on the
MCSC.
3. Verify there is no loss or interruption of Monitor and Alarm functionality.
4. Verify the system operates properly after the cable is reconnected.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
3.5 Profinet Bus B Fails
Failure Profinet Bus "B" module or cable fails.
Effect PLC to I/O Module communications on Bus "B" are disabled. I/O communications will continue on Bus "A" with no loss of functionality.
Detection 1. " Profinet Bus B Fail" alarm is annunciated on the MCSC.
2. "Engineer Trouble" alarm will sound on the system.
Alternatives There is no loss of functionality on the system.
Correction Replace PBM "B" Module or Cable.
Test Procedure 1. Simulate Profinet Bus B fail by disconnecting cable B from
PLC Profinet module.
2. Verify the "Profinet Bus B Fail" alarm is annunciated on the
MCSC.
3. Verify there is no loss or interruption of Monitor and Alarm functionality.
4. Verify the system operates properly after the cable is reconnected.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
4 Personal Computer (PC) Failures
This section will examine in the PC, including the circuit boards, drives and monitor.
4.1 PC Failure
Failure The PC fails.
Effect The Monitor and Alarm functions will be disabled until problem corrected.
Detection 1. "Engineer's Assistance Needed" alarm will sound on the EAP's.
2. The PC will have a "No Data" displayed on the monitor.
Alternatives System machinery will need to be monitored locally until failure is corrected.
Correction 1. Changeover to backup PC.
Test Procedure 1. Simulate a PC failure by removing the power connection while the system is in operation.
2. Verify the "Engineer's Assistance Needed" alarm sounds on the
EAP's.
3. Verify there is no PC operation.
4. Verify the system operation returns to normal after power up.
Verified
4.2 PC Monitor Failure
Failure The PC Monitor fails.
Effect The Monitor and Alarm system will function properly except there will be no display on the CRT.
Detection There will be no display on the monitor.
Alternatives 1. The system will operate normally except for display functions.
Correction Replace monitor.
Test Procedure 1. Simulate monitor failure by removing power to the monitor.
2. Initiate an alarm.
3. Verify the alarm is sounds on the MCSC.
4. Verify the “Engineer Trouble” alarm annunciates on the
EAP’s.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
5 I/O Communication Failures
This section will consider failures of the I/O Communications bus.
5.1 I/O Communication Cable “A” Failure
Failure The I/O Communication cable fails due to an open in one of the conductors in the "A" Bus cable.
Effect I/O Module to PLC communication on Bus "A" is disabled. I/O communications will continue on Bus "B" with no loss of functionality.
Detection 1. "Profinet Bus "A" Fail: alarm is annunciated on the MCSC.
2. "Engineer Trouble" alarm will sound on the EAP's.
Alternatives There is no loss of functionality on the system.
Correction Repair problem with cable.
Test Procedure 1. Simulate I/O Communications failure by lifting one of the wires for Bus "A" located on the PSM "A" Module in the PLC.
2. Verify the "Profinet Bus "A" Fail" alarm is annunciated on the
MCSC.
3. Verify “Engineer Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality.
5. Verify the alarm clears on the MCSC after replacing the lifted wire.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
5.3 I/O Communication Cable “B” Failure
Failure The I/O Communication cable fails due to an open in one of the conductors in the "B" Bus cable.
Effect I/O Module to PLC communication on Bus "B" is disabled. I/O communications will continue on Bus "A" with no loss of functionality.
Detection 1. "Profinet Bus "B" Fail: alarm is annunciated on the MCSC.
2. "Engineer Trouble" alarm will sound on the EAP's.
Alternatives There is no loss of functionality on the system.
Correction Repair problem with cable.
Test Procedure 1. Simulate I/O Communications failure by lifting one of the wires for Bus “B” located on the PSM “B” Module in the PLC.
2. Verify the "Profinet Bus “B” Fail" alarm is annunciated on the
MCSC.
3. Verify the “Engineer Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality.
5. Verify the alarm clears on the MCSC after replacing the lifted wire.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
6 PC Communication Failures This section will consider failures of the PC to PLC Communications bus.
6.1 Ethernet Cable Failure Open
Failure The Ethernet cable fails due to an open in one of the conductors of the cable.
Effect PLC TO PC communication is disabled. Monitor and Alarm functions will be disabled.
Detection 1. “PC/PLC Communication Failure” alarm is displayed on the
MCSC CRT.
2. “Engineers Assistance Needed” alarm will sound on the EAP’s.
Alternatives System machinery will need to be monitored locally until problem is corrected.
Correction Repair problem with cable.
Test Procedure 1. Simulate I/O Communications failure by disconnecting the
Ethernet cable from the PLC Ethernet Adapter.
2. “Verify the “PC/PLC” Communication Failure” alarm is displayed on the MCSC CRT.
3. Verify the “Engineers Assistance Needed” alarm sounds on the
EAP’s.
4. Verify the alarm clears and system returns to normal after replacing the Ethernet cable.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7 I/O Module Failures This section will examine failure of the I/O modules and their effect on the system. Each
I/O Module will have a table listing the I/O Points affected. The “I/O Type” field of the table has the following legend:
● DI - Digital Input – Contact closure input, normally 24 VDC and is an alarm indication or a status.
● DO – Digital Output – This I/O Type is normally associated with an indicating light or a relay.
● AI – Analog Input – This is a 4-20mA or voltage input. A continuous display will be available from this type of input.
● AO – Analog Output – This is a 4-20mA or voltage output. This I/O Type normally drives a meter display.
● RTD – Resistance Temperature Detector input. This is temperature dependant element sensor. A continuous display will be available from this type of input.
● TC – Thermocouple sensor input. A continuous display will be available from this type of input.
7.1 Profinet Scanner Module “PSM” Failure
Failure PSM 1 fails. This is the communications interface for I/O Modules D1-
M1, D1-M2, D1-M3, D1-M4, D1-M5, D1-M6, D1-M7, D1-M8.
Effect There will no communications to the above I/O Modules. (See the failure cases for the individual modules for I/O data points affected).
Detection 1. “PSM 1 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace PSM 1 Module
Test Procedure 1. Simulate PSM 1 failure by removing power to the PSM.
2. “Verify the “PSM 1 Fail” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after restoring power to PSM
1.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.2 I/O Module D1-M1 Failure
Failure I/O Module D1-M1 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M1.
Detection 1. “D1-M1 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M1 Module
Test Procedure
1. Simulate D1-M1 failure by removing this module from the rack.
2. Verify the “D1-M1” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M1 to the rack.
Verified
Channel No. I/O Type Description
050 TC MAIN DSL # 1 CYL # 1 TEMP
051 TC MAIN DSL # 1 CYL # 2 TEMP
052 TC MAIN DSL # 1 CYL # 3 TEMP
053 TC MAIN DSL # 1 CYL # 4 TEMP
054 TC MAIN DSL # 1 CYL # 5 TEMP
055 TC MAIN DSL # 1 CYL # 6 TEMP
056 TC MAIN DSL # 1 CYL # 7 TEMP
Table D1-M1
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.3 I/O Module D1-M2 Failure
Failure I/O Module D1-M2 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M2.
Detection 1. “D1-M2 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M2 Module
Test Procedure
1. Simulate D1-M2 failure by removing this module from the rack.
2. Verify the “D1-M2” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M2 to the rack.
Verified
Channel No. I/O Type Description
057 TC MAIN DSL # 1 CYL # 8 TEMP
058 TC MAIN DSL # 1 CYL # 9 TEMP
059 TC MAIN DSL # 1 CYL # 10 TEMP
060 TC MAIN DSL # 1 CYL # 11 TEMP
061 TC MAIN DSL # 1 CYL # 12 TEMP
062 TC MAIN DSL # 2 CYL # 1 TEMP
063 TC MAIN DSL # 2 CYL # 2 TEMP
Table D1-M2
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.4 I/O Module D1-M3 Failure
Failure I/O Module D1-M3 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M3.
Detection 1. “D1-M3 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M3 Module
Test Procedure
1. Simulate D1-M3 failure by removing this module from the rack.
2. Verify the “D1-M3” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M3 to the rack.
Verified
Channel No. I/O Type Description
066 TC MAIN DSL # 2 CYL # 3 TEMP
067 TC MAIN DSL # 2 CYL # 4 TEMP
068 TC MAIN DSL # 2 CYL # 5 TEMP
069 TC MAIN DSL # 2 CYL # 6 TEMP
070 TC MAIN DSL # 2 CYL # 7 TEMP
071 TC MAIN DSL # 2 CYL # 8 TEMP
072 TC MAIN DSL # 2 CYL # 9 TEMP
Table D1-M3
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.5 I/O Module D1-M4 Failure
Failure I/O Module D1-M4 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M4.
Detection 1. “D1-M4 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M4 Module
Test Procedure
1. Simulate D1-M4 failure by removing this module from the rack.
2. Verify the “D1-M4” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M4 to the rack.
Verified
Channel No. I/O Type Description
073 TC MAIN DSL # 2 CYL # 10 TEMP
074 TC MAIN DSL # 2 CYL # 11 TEMP
075 TC MAIN DSL # 2 CYL # 12 TEMP
076 TC MAIN DSL # 3 CYL # 1 TEMP
077 TC MAIN DSL # 3 CYL # 2 TEMP
078 TC MAIN DSL # 3 CYL # 3 TEMP
079 TC MAIN DSL # 3 CYL # 4 TEMP
Table D1-M4
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.6 I/O Module D1-M5 Failure
Failure I/O Module D1-M5 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M5.
Detection 1. “D1-M5 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M5 Module
Test Procedure
1. Simulate D1-M5 failure by removing this module from the rack.
2. Verify the “D1-M5” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M5 to the rack.
Verified
Channel No. I/O Type Description
082 TC MAIN DSL # 3 CYL # 5 TEMP
083 TC MAIN DSL # 3 CYL # 6 TEMP
084 TC MAIN DSL # 3 CYL # 7 TEMP
085 TC MAIN DSL # 3 CYL # 8 TEMP
086 TC MAIN DSL # 3 CYL # 9 TEMP
087 TC MAIN DSL # 3 CYL # 10 TEMP
088 TC MAIN DSL # 3 CYL # 11 TEMP
Table D1-M5
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.7 I/O Module D1-M6 Failure
Failure I/O Module D1-M6 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M6.
Detection 1. “D1-M6 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M6 Module
Test Procedure
5. Simulate D1-M6 failure by removing this module from the rack.
6. Verify the “D1-M6” alarm is annunciated on the MCSC.
7. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
8. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M6 to the rack.
Verified
Channel No. I/O Type Description
089 TC MAIN DSL # 3 CYL # 12 TEMP
090 TC MAIN DSL # 4 CYL # 1 TEMP
091 TC MAIN DSL # 4 CYL # 2 TEMP
092 TC MAIN DSL # 4 CYL # 3 TEMP
093 TC MAIN DSL # 4 CYL # 4 TEMP
094 TC MAIN DSL # 4 CYL # 5 TEMP
095 TC MAIN DSL # 4 CYL # 6 TEMP
Table D1-M6
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.8 I/O Module D1-M7 Failure
Failure I/O Module D1-M7 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M7.
Detection 1. “D1-M7 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M7 Module
Test Procedure
9. Simulate D1-M7 failure by removing this module from the rack.
10. Verify the “D1-M7” alarm is annunciated on the MCSC.
11. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
12. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M7 to the rack.
Verified
Channel No. I/O Type Description
098 TC MAIN DSL # 4 CYL # 7 TEMP
099 TC MAIN DSL # 4 CYL # 8 TEMP
100 TC MAIN DSL # 4 CYL # 9 TEMP
101 TC MAIN DSL # 4 CYL # 10 TEMP
102 TC MAIN DSL # 4 CYL # 11 TEMP
103 TC MAIN DSL # 4 CYL # 12 TEMP
104 TC MAIN DEISEL 1 EXHAUST TEMP
Table D1-M7
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.9 I/O Module D1-M8 Failure
Failure I/O Module D1-M8 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D1-M8.
Detection 1. “D1-M8 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D1-M8 Module
Test Procedure
13. Simulate D1-M8 failure by removing this module from the rack.
14. Verify the “D1-M8” alarm is annunciated on the MCSC.
15. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
16. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D1-M8 to the rack.
Verified
Channel No. I/O Type Description
105 TC MAIN DEISEL 2 EXHAUST TEMP
106 TC MAIN DEISEL 3 EXHAUST TEMP
107 TC MAIN DEISEL 4 EXHAUST TEMP
Table D1-M8
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.10 Profinet Scanner Module PSM 2 Failure
Failure PSM 2 fails. This is the communications interface for I/O Modules D2-
M1, D2-M2, D2-M3, D2-M4, D2-M5.
Effect There will no communications to the above I/O Modules. (See the failure cases for the individual modules for I/O data points affected).
Detection 1. “PSM 2 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace PSM 2 Module
Test Procedure 1. Simulate PSM 2 failure by removing power to the PSM.
2. Verify the “PSM 2 Fail” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after restoring power to PSM
2.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.11 I/O D2-M1 Failure
Failure I/O Module D2-M1 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D2-M1.
Detection 1. “D2-M1 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D2-M1 Module
Test Procedure
1. Simulate D2-M1 failure by removing this module from the rack.
2. Verify the “D2-M1” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D2-M1 to the rack.
Verified
Channel No. I/O Type Description
113 RTD P PRPLN MTR COMM FLD TEMP
114 RTD S PRPLN MTR COMM FLD TEMP
115 RTD P PRPLN MTR SHNTFLD TEMP
116 RTD S PRPLN MTR SHNTFLD TEMP
Table D2-M1
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.12 I/O Module D2-M2 Failure
Failure I/O Module D2-M2 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D2-M2.
Detection 1. “D2-M2 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D2-M2 Module
Test Procedure
1. Simulate D2-M2 failure by removing this module from the rack.
2. Verify the “D2-M2” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D2-M2 to the rack.
Verified
Channel No. I/O Type Description
117 RTD P PRPLN MTR AFT THR BRG TEMP
118 RTD S PRPLN MTR AFT THR BRG TEMP
119 RTD P PRPLN MTR FWD THR BRG TEMP
120 RTD S PRPLN MTR FWD THR BRG TEMP
Table D2-M2
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.13 I/O Module D2-M3 Failure
Failure I/O Module D2-M3 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D2-M3.
Detection 1. “D2-M3 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D2-M3 Module
Test Procedure
1. Simulate D2-M3 failure by removing this module from the rack.
2. Verify the “D2-M3” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D2-M3 to the rack.
Verified
Channel No. I/O Type Description
121 RTD P PRPLN MTR FWD JNL BRG TEMP
122 RTD S PRPLN MTR FWD JNL BRG TEMP
123 RTD P PRPLN MTR AFT JNL BRG TEMP
124 RTD S PRPLN MTR AFT JNL BRG TEMP
Table D2-M3
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.14 I/O Module D2-M4 Failure
Failure I/O Module D2-M4 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D2-M4.
Detection 1. “D2-M4 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D2-M4 Module
Test Procedure
1. Simulate D2-M4 failure by removing this module from the rack.
2. Verify the “D2-M4” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D2-M4 to the rack.
Verified
Channel No. I/O Type Description
125 RTD P PRPLN MTR COOLING AIR TEMP
126 RTD S PRPLN MTR COOLING AIR TEMP
127 RTD NO. 1 DSL LUBO TEMP
128 RTD NO. 2 DSL LUBO TEMP
Table D2-M4
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.15 I/O Module D2-M5 Failure
Failure I/O Module D2-M5 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D2-M5.
Detection 1. “D2-M5 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D2-M5 Module
Test Procedure
5. Simulate D2-M5 failure by removing this module from the rack.
6. Verify the “D2-M5” alarm is annunciated on the MCSC.
7. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
8. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D2-M5 to the rack.
Verified
Channel No. I/O Type Description
129 RTD NO. 3 DSL LUBO TEMP
130 RTD NO. 4 DSL LUBO TEMP
131 RTD NO. 1 DSL J.W. HIGH TEMP
132 RTD NO. 2 DSL J.W. HIGH TEMP
Table D2-M5
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.16 Profinet Scanner Module PSM 3 Failure
Failure PSM 3 fails. This is the communications interface for I/O Modules D3-
M1, D3-M2, D3-M3, D3-M4, D3-M5.
Effect There will no communications to the above I/O Modules. (See the failure cases for the individual modules for I/O data points affected).
Detection 1. “PSM 3 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace PSM 3 Module
Test Procedure 6. Simulate PSM 3 failure by removing power to the PSM.
7. Verify the “PSM 3 Fail” alarm is annunciated on the MCSC.
8. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
9. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
10. Verify the alarm clears on the MCSC after restoring power to PSM
3.
Verified
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.17 I/O Module D3-M1 Failure
Failure I/O Module D3-M1 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D3-M1.
Detection 1. “D3-M1 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D3-M1 Module
Test Procedure
1. Simulate D3-M1 failure by removing this module from the rack.
2. Verify the “D3-M1” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D3-M1 to the rack.
Verified
Channel No. I/O Type Description
133 RTD NO. 3 DSL J.W. HIGH TEMP
134 RTD NO. 4 DSL J.W. HIGH TEMP
135 RTD GEN NO. 1 WINDING TEMP # 1
136 RTD GEN NO. 1 WINDING TEMP # 2
Table D3-M1
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.18 I/O D3-M2 Failure
Failure I/O Module D3-M2 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D3-M2.
Detection 1. “D3-M2 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D3-M2 Module
Test Procedure
1. Simulate D3-M2 failure by removing this module from the rack.
2. Verify the “D3-M2” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D3-M2 to the rack.
Verified
Channel No. I/O Type Description
137 RTD GEN NO. 1 WINDING TEMP # 3
138 RTD GEN NO. 2 WINDING TEMP # 1
139 RTD GEN NO. 2 WINDING TEMP # 2
140 RTD GEN NO. 2 WINDING TEMP # 3
Table D3-M2
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.19 I/O D3-M3 Failure
Failure I/O Module D3-M3 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D3-M3.
Detection 1. “D3-M3 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D3-M3 Module
Test Procedure
1. Simulate D3-M3 failure by removing this module from the rack.
2. Verify the “D3-M3” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D3-M3 to the rack.
Verified
Channel No. I/O Type Description
141 RTD GEN NO. 3 WINDING TEMP # 1
142 RTD GEN NO. 3 WINDING TEMP # 2
143 RTD GEN NO. 3 WINDING TEMP # 3
144 RTD GEN NO. 4 WINDING TEMP # 1
Table D3-M3
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.20 I/O Module D3-M4 Failure
Failure I/O Module D3-M4 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D3-M4.
Detection 1. “D3-M4 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D3-M4 Module
Test Procedure
1. Simulate D3-M4 failure by removing this module from the rack.
2. Verify the “D3-M4” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D3-M4 to the rack.
Verified
Channel No. I/O Type Description
145 RTD GEN NO. 4 WINDING TEMP # 2
146 RTD GEN NO. 4 WINDING TEMP # 3
147 RTD PORT STERN TUBE BEARING TEMP
148 RTD STBD STERN TUBE BEARING TEMP
Table D3-M4
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.21 I/O Module D3-M5 Failure
Failure I/O Module D3-M5 fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D3-M5.
Detection 1. “D3-M5 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D3-M5 Module
Test Procedure
1. Simulate D3-M5 failure by removing this module from the rack.
2. Verify the “D3-M5” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D3-M5 to the rack.
Verified
Channel No. I/O Type Description
149 RTD NO. 1 DSL J.W. LOW TEMP
150 RTD NO. 2 DSL J.W. LOW TEMP
151 RTD NO. 3 DSL J.W. LOW TEMP
152 RTD NO. 4 DSL J.W. LOW TEMP
Table D3-M5
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.22 Profinet Scanner Module PSM 4 Failure
Failure PSM 4 fails. This is the communications interface for I/O Modules D4-
M1, D4-M2, D4-M3, D4-M4, D4-M5.
Effect There will be no communications to the above I/O Modules. (See the failure cases for the individual modules for I/O data points affected).
Detection 1. “PSM 4 Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace PSM 4 Module
Test Procedure 1. Simulate PSM 4 failure by removing power to the PSM.
2. Verify the “PSM 4 Fail” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after restoring power to PSM
4.
Verified e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.23 I/O Module D4-M1A Failure
Failure I/O Module D4-M1A fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M1A.
Detection 1. “D4-M1A Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M1A Module
Test Procedure
1. Simulate D4-M1A failure by removing this module from the rack.
2. Verify the “D4-M1A” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D4-
M1A to the rack.
Verified
Table D4-M1A
Channel No. I/O Type Description
701 DO PORT PRPLN SYSTEM POWER LIMITING
702 DO PORT BARRING GEAR BOT STOWED
DO PORT PRPLN MOTOR LUBE HEAD TANK
LEVEL LOW
704 DO ABNORMAL ASSIGNMENT PORT SCR
705 DO NO. 1 STEERING GEAR MOTOR RUNNG
706 DO NO. 1 STEERING GEAR CKT BKR OPEN
707 DO NO. 1 STEERING GEAR PHASE FAILURE
708 DO PORT PRPLN MOTOR L.O. LEVEL LOW
DO STARBOARD PRPLN SYSTEM POWER
LIMITING
710 DO STARBOARD BARRING GEAR NOT STOWED
DO STARBOARD PRPLN MOTOR LUBE HEAD
TANK LEVEL LOW
712 DO ABNORMAL ASSIGNMENT STARBOARD SCR
713 DO NO. 2 STEERING GEAR MOTOR RUNNING
714 DO NO. 2 STEERING GEAR CKT BKR OPEN
715 DO NO. 2 STEERING GEAR PHASE FAILURE
716 DO STARBOARD PRPLN MOTOR L.O. LEVEL LOW
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.24 I/O D4-M1B Failure
Failure I/O Module D4-M1B fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M1B.
Detection 1. “D4-M1B Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M1B Module
Test Procedure
1. Simulate D4-M1B failure by removing this module from the rack.
2. Verify the “D4-M1B” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D4-
M1B to the rack.
Verified
Channel No. I/O Type Description
717 DO FIRE PUMP NO. 1 RUNNING
718 DO FIRE PUMP NO. 1 SUCTION VALVE OPEN
719 DO FIRE PUMP NO. 1 SUCTION VALVE CLOSED
720 DO FIRE PUMP NO. 1 DISCHARGE VALVE OPEN
721 DO FIRE PUMP NO. 1 DISCHARGE VALVE CLOSED
722 DO ENGINEER TROUBLE HORN/ETEA 700E
725 DO FIRE PUMP NO. 2 RUNNING
726 DO FIRE PUMP NO. 2 SUCTION VALVE OPEN
727 DO FIRE PUMP NO. 2 SUCTION VALVE CLOSED
728 DO FIRE PUMP NO. 2 DISCHARGE VALVE OPEN
729 DO FIRE PUMP NO. 2 DISCHARGE VALVE CLOSED
Table D4-M1B
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.25 I/O D4-M2A Failure
Failure I/O Module D4-M2A fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M2A.
Detection 1. “D4-M2A Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M2A Module
Test Procedure
1. Simulate D4-M2A failure by removing this module from the rack.
2. Verify the “D4-M2A” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D4-
M2A to the rack.
Verified
Channel No. I/O Type Description
733 DO WATERTIGHT DOOR NO. 1 OPEN
734 DO WATERTIGHT DOOR NO. 2 OPEN
735 DO WATERTIGHT DOOR NO. 3 OPEN
736 DO WATERTIGHT DOOR NO. 4 OPEN
737 DO WATERTIGHT DOOR NO. 1 CLOSED
738 DO WATERTIGHT DOOR NO. 2 CLOSED
739 DO WATERTIGHT DOOR NO. 3 CLOSED
740 DO WATERTIGHT DOOR NO. 4 CLOSED
741 DO PORT PRPLN MOTOR L.O. PUMP RUNNING
742 DO
STARBOARD PRPLN MOTOR L.O. PUMP
RUNNING
743 DO MCSC IN CONTROL
744 DO PILOT HOUSE IN CONTROL
745 DO WINCH HOUSE IN CONTROL
746 DO
PILOT HOUSE IN CONTROL
(BOW THRUSTER)
747 DO
WINCH HOUSE IN CONTROL
(BOW THRUSTER)
Table D4-M2A
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.26 I/O Module D4-M2B Failure
Failure I/O Module D4-M2B fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M2B.
Detection 1. “D4-M2B Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M2B Module
Test Procedure
1. Simulate D4-M2B failure by removing this module from the rack.
2. Verify the “D4-M2B” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D4-
M2B to the rack.
Verified
Channel No. I/O Type Description
749 DO AC COMP. NO. 1 RUNNING
750 DO AC COMP. NO. 2 RUNNING
751 DO AC COMP. NO. 3 RUNNING
752 DO THRUSTER MOTOR COOLING PUMP RUNNING
753 DO EMERGENCY GENERATOR RUNNING
754 DO NO. 1 BILGE LEVEL HIGH
755 DO
ENGINEER NEEDS ASSISTANCE (MTD. IN
ENG. ROOM)
756 DO PRINTER RELAY
757 DO ENGINEERING TROUBLE SUMMARY
758 DO FIRE SUMMARY
759 DO BILGE LEVEL SUMMARY
760 DO ENGINEER TROUBLE HORN
761 DO STEERING GEAR MALFUNCTION
762 DO PROPULSION MOTOR MALFUNCTION
763 DO DIESEL GENERATOR MALFUNCTION
764 DO LOW LEVEL FOR FUEL SERVICE TANK
Table D4-M2B
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.27 I/O Module D4-M3A Failure
Failure I/O Module D4-M3A fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M3A.
Detection 1. “D4-M3A Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M3A Module
Test Procedure
1. Simulate D4-M3A failure by removing this module from the rack.
2. Verify the “D4-M3A” alarm is annunciated on the MCSC.
3. Verify the “Engineers Trouble” alarm sounds on the EAP’s.
4. Verify there is no loss or interruption of Monitor and Alarm functionality, except for the affected I/O Module.
5. Verify the alarm clears on the MCSC after returning Module D4-
M3A to the rack.
Verified
Channel No. I/O Type Description
765 DO ENGEERING TROUBLE SUMAMRY
766 DO FIRE SUMMARY
767 DO BILGE LEVEL SUMMARY
768 DO ENGINEER TROUBLE HORN
769 DO STEERING GEAR MALFUNCTION
770 DO PROPULSION MOTOR MALFUNCTION
771 DO DIESEL GENERATOR MALFUNCTION
772 DO LOW LEVEL FOR FUEL SERVICE TANK
773 DO ENGINEERING TROUBLE SUMMARY
774 DO FIRE SUMMARY
775 DO BILGE LEVEL SUMMARY
776 DO ENGEER TROUBLE HORN
777 DO STEERING GEAR MALFUNCTION
778 DO PROPULSION MOTOR MALFUNCTION
779 DO DIESEL GENERATOR MALFUNCTION
780 DO LOW LEVEL FOR FUEL SERVICE TANK
Table D4-M3A
S e e A
B S H o u s to n L e tt e r R e f T D a te d
-J
A N
-2
7.28 I/O Module D4-M3B Failure
Failure I/O Module D4-M3B fails.
Effect I/O data points monitored by this module will be disabled. A list of these points is shown in Table D4-M3B.
Detection 1. “D4-M3B Fail” alarm is annunciated on the MCSC.
2. “Engineers Trouble” alarm will sound on the EAP’s.
Alternatives The affected points will need to be monitored locally until problem is corrected.
Correction Replace D4-M3B Module
Test Procedure
1. Simulate D4-M3B failure by removing this module from the rack.
2. Verify the “D4-M3B” alarm is annunciated on the MCSC.
3. Verify the “Engineers…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .