SFMTA-2027-01-FTA_-_Attachment_1-C_-_Specifications.pdf

PDF 3 MB Posted

Attached to
EXT MTA | SFMTA-2027-01-FTA Precast ADA Acc Stops
Solicitation number
SFGOV-0000012037
Issued by
California

About this file

This is a technical specifications document for the San Francisco Municipal Transit Agency (SFMTA) procurement of precast ADA accessible stops, specifically detailing requirements for cast-in-place detectable surface tiles and anti-graffiti coating. The project involves furnishing and installing polymer composite concrete ADA-compliant tactile warning tiles at curb ramps, transit platforms, boarding islands, and sidewalk crossings across multiple Muni line locations. The specifications require yellow tiles conforming to Federal Standard 595B Color No. 33538 with two dome pattern configurations: inline dome configuration for curb ramps and crossings with 1.67-inch center-to-center spacing, and staggered dome configuration for transit platforms and boarding islands with 2.35-inch center-to-center spacing. Individual tile panels must be a minimum of 2 feet wide by 3 feet long, with a minimum 3-foot depth of detectable warning tiles required at each curb ramp unless otherwise noted. The document specifies that tiles must be fabricated by StrongGo Industries LLC using their TekWay system, which is made of nano-engineered polymer concrete. Installation must be performed by manufacturer-certified installers using wet-set installation methods in fresh concrete with a slump range of 4 to 7 inches, and all submittals must be reviewed and approved by the Engineer before installation begins. Cast-in-place tiles are guaranteed in writing for five years from the project's final acceptance, covering defective work, breakage, deformation, loosening, and fastener failures.

The specifications establish rigorous quality control requirements with tiles required to meet minimum performance standards including 11,000 psi compressive strength, 1,700 psi tensile strength, 2,700 psi flexural ultimate strength, 0.80 minimum slip resistance (wet and dry), water absorption not exceeding 2 percent, abrasion resistance of 0.0035 per 2,000 cycles, and freeze-thaw resistance of 0.00 percent as verified through certified independent testing laboratories using ASTM test methods. Contractors must submit product data, manufacturer literature, two minimum 6-inch by 8-inch tile samples, shop drawings, and material test reports no more than six months old prior to installation. The document also specifies anti-graffiti coating requirements using Rainguard Pro VandlGuard IsoFree Aliphatic Urethane 2K as a non-sacrificial, weather-resistant clear coat with no gloss finish, applied over exposed walls, concrete, stucco, brick, window frames, doors, barriers, railings, and platform surfaces. Contractors must supply five gallons each of spare anti-graffiti coating and VandlClean graffiti cleaner to a designated Muni yard, with coating application restricted to temperatures between 50 and 90 degrees Fahrenheit and surfaces completely free of moisture, requiring at least two coats applied with uniform film thickness and approval of a thickness gauge test conducted by the Engineer.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NO.

of

PLAN OF TILE

Notes:

1. The allowable width of tile is 24.00" ± 0.06".

2. The allowable length of tile is 36.00" ± 0.06".

3. The allowable distance between domes is 2.35"

± 0.05" measured from the center of the dome.

4. All dimensions are in inches.

DRAWING TITLE

24" X 36" TekWay ADA Dome- Tile Staggered - Bull-Nose Edge Wide Spacing 2G - Plan & Elevation

ELEVATION OF TILE2

Scale: NTS

Scale: NTS

3296 E. Hemisphere Loop Tucson, AZ. 85706 Tel: (520) 547-3510 Fax: (520) 547-3515

24.00"

.0

0"

9 Equal Spaces

E qu al

S pa ce s

2.35"

24.00"

See Detail-A on Sheet 2

0.75"

2.35" 0.50" Bull-Nose Edge

R 0.50"

TekWay ADA Dome-Tile Anchor System, See Section 1, Sheet 2

This drawing contains information that is property of StrongGo INDUSTRIES. This document may not in whole or in part be duplicated or disclosed or used for manufacture of the part disclosed herein without written permission of StrongGo INDUSTRIES.

Te kW ay

TekWay

0.167"

Tactile Warning Systems

Attachment 1-C-1

SHEET NO.

of

TYPICAL - WET-SET INSTALLATION (Fresh Concrete)

Notes:

1. The allowable width of tile is 24.00" ± 0.06".

2. The allowable length of tile is 36.00" ± 0.06".

3. The allowable distance between domes is 2.35"

± 0.05" measured from the center of the dome.

4. All dimensions are in inches.

DRAWING TITLE

24" X 36" TekWay ADA Dome- Tile Staggered - Bull-Nose Edge Wide Spacing 2G - Plan & Elevation

Scale: NTS

3296 E. Hemisphere Loop Tucson, AZ. 85706 Tel: (520) 547-3510 Fax: (520) 547-3515

DETAIL - A2

Scale: NTS

0.45"

0.90"

R 0.50"

0.75"

0.20"

24.00"

4" (min.)

4" (min.)

R 0.50" TekWay ADA Dome-Tile

1/8” Radius at all sides of tile

Thicken slab under tile location

TekWay ADA Dome-Tile Anchor System Mortar, refer to TekWay ADA Dome-Tile Wet-Set Installation Instructions

This drawing contains information that is property of StrongGo INDUSTRIES. This document may not in whole or in part be duplicated or disclosed or used for manufacture of the part disclosed herein without written permission of StrongGo INDUSTRIES.

Attachment 1-C-1

Industry Leading TekWay ADA Domes TekWay High Performance ADA Domes are considered since 2004 ‘The Perfect Fit for any Project’™. Our ADA Dome tiles possess the perfect combination of outstanding physical properties, aesthetics and ease of installation.

TekWay Dome-Tiles are the only concrete-based ADA Domes available in authentic federal colors with homogenous color throughout, such as Federal Standard 595 - #33538 (Yellow).

StrongGo Industries offer a full complement of TekWay High Performance ADA Domes and Architectural Series tile which are fully compliant and right for any job large or small.

These durable, aesthetically pleasing domes are available in most all Federal colors, sizes, dome spacing.

CHALLENGE INNOVATIONS OUTCOME COMPLIANCE SAFETY

Heavy Foot and Wheel Traffic Nano-engineered polymer concrete Durability & Performance √ √ Higher Vibration and Stresses TekWay Anchor System Securely Anchored Tiles √ √ Design requires Cutting of Tile Structural Fiber-Reinforcement throughout the Tile Guaranteed Integrity of Tile √ √

Nano-Tech Materials TekWay ADA Dome-Tiles are made of nano-engineered polymer concrete to achieve excellent physical, chemical and mechanical properties while being able to form perfect-to-specification domes, retain color and maintain high slip-resistance.

VFI

Void-Free Installation

VFI

Void-Free Installation

NTM

NanoTech Materials

HP

High-Performance

HPD

High-Performance Domes

Void-Free Installation The proven TekWay Anchor System and Installation Instructions ensure the permanent attachment of the Dome-Tile and the substrate by creating a monolithic structure that will withstand flooding, ice, snow, traffic-vibrations and drive-overs.

High Performance Domes

The Synthesis of Nano-Technology and Void-Free Installation = TekWay High Performance Domes.

Attachment 1-C-2

Please call 1-866-439-3216 or email at csd@stronggo.com StrongGo® Industries, 3296 E. Hemisphere Loop, Tucson, Arizona, 85706

Made in U.S.A. by StrongGo Industries®

State DOT Approved

Available Sizes in either narrow (1.67”) or wide (2.35”) spacing

Authentic Federal Colors *

Black Red

Yellow Blue

White

TekWay ADA Domes, are designed with the ability to custom cut and fit tiles in the field to meet specific architectural design requirements. All TekWay products are engineered with Nano-Technology along with a continuous fiber reinforced membrane. This allows high flexural strengths and gives installers the ability to easily core and/or saw cut tiles using a diamond blade without concerns of chipping and cracking.

12” x 12” 24” x 36”

24” x 24” 30” x 36” (2.35 spacing only)

24” x 30” 24” x 48”

* All FED-STD-595 Colors are available with homogenous color throughout.

Specify requested number upon ordering.

Visit our website at: www.stronggo.com or scan QR Code

CERTIFIED ASTM - TEST DATA

PHYSICAL PROPERTYTEST METHOD RESULTS
Compression Strength ASTM C 39-04>12,500psi
Abrasion ResistanceASTM C 418-12 <0.03 cm³/cm²
Freeze / ThawASTM C 1262=0.00 %
Water AbsorptionASTM C 97<0.15 %
Slip ResistanceASTM C 1028Fa ≥ 0.85
Slip ResistanceASTM E 303-93>70 (wet)
Flexural StrengthASTM C 947>3,000 psi
Tensile StrengthASTM C 496>3,000 psi

Attachment 1-C-2

TECHNICAL SPECIFICATIONS TO 213 M&J Muni Forward

DIVISION 9: FINISHES

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-1 PROJECT TITLE

12/2/2025

PART 1 - GENERAL

1.01 DESCRIPTION

A. This Section includes specifications for furnishing and installing cast-in- place detectable surface tiles embedded in all curb ramps, transit platforms and boarding islands, and sidewalk crossings at the locations and to the dimensions shown on the Contract Drawings and as directed by the Engineer.

1.02 RELATED WORK

A. Section 03 30 00 Cast-In-Place Concrete.

1.03 REFERENCES

A. Americans with Disabilities Act (ADA) Title 49 CFR Transportation, Part 37.9 “Standards for Accessible Transportation Facilities”, Appendix A, Section 4.29.2 “Detectable Warnings on Walking Surfaces” B. California Code of Regulations (CCR) Title 24 Part 1, Articles 2, 3 and 4; and Section 205 Part 2 definition of “Detectable Warning”, Section 1127B.5 for “Curb Ramps”, and Section 1133B.8.5 for “Detectable Warnings at Hazardous Vehicle Areas.”

C. American Society for Testing and Materials (ASTM) International Test Methods:

1. B117 Standard Practice for Operating Salt Spray (Fog)

Apparatus

2. C39 Standard Test Method for Compressive Strength of

Cylindrical Concrete Specimens

3. C140 Standard Test Method for Water Absorption

4. C947 Standard Test Method for Flexural Properties of Thin

Glass Fiber Reinforced Concrete for using Sample Beam with Third Party Loading

5. C1028 Standard Test Method for Determining the Static Coefficient of Friction of Ceramic Tile and other like surfaces be the Horizontal Dynamometer Pull-Meter Method

6. D543 Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents

Attachment 1-C-3

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-2 PROJECT TITLE

12/2/2025

7. D570 Standard Test Method for Water Absorption of Plastics

8. D638 Standard Test Method for Tensile Properties of Plastics

9. D695 Standard Test Method for Compressive Properties of Rigid Plastics

10. D790 Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulting Materials

11. D1037 Standard Test Methods for Evaluating Properties of Wood Base Fiber and Particle Panel Materials

12. D2486 Standard Test Methods for Scrub Resistance of Wall Paints

13. D2565 Standard Practice for Xenon Arc Exposure of Plastics Intended for Outdoor Applications

14. D5420 Standard Test Method for Impact Resistance of Flat, Rigid Plastic Specimen by Means of a Striker Impacted by a Falling Weight

15. E84 Review of ASTM Test for Surface Burning Characteristics of Building Materials

D. City and County of San Francisco, Public Works Accessible Street Crossing Standards.

E. Standard Specifications of the City and County of San Francisco, Public Works, Department of Bureau of Engineering (SPDPWSF).

1.04 SUBMITTALS

A. Product Data: Submit manufacturer’s literature describing products, installation procedures, and maintenance instructions.

B. Samples for Verification Purposes: Submit two tile samples minimum 6 Inches by 8 inches of the kind proposed for use. Samples shall be properly labeled and shall contain the following information: Name of Project; Submitted by; Date of Submittal; Manufacture’s Name; Catalog No., and Date of Fabrication.

C. Shop drawings: Submit shop drawings showing plans of tile placement including joints, all materials to be used, and an outline of installation procedures.

D. Material Test Reports: Submit current test reports from a qualified independent testing laboratory indicating that materials proposed for use are

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-3 PROJECT TITLE

12/2/2025 in compliance with requirements and meet the properties indicated. Tests listed in Section 1.05 shall be performed by a certified and qualified independent testing laboratory on a cast-in-place tactile system. All test reports submitted shall be certified by the testing laboratory and shall be no more than 6 months old from the time of the submittal.

1.05 QUALITY CONTROL

A. Provide cast-in-place detectable surface tiles and accessories as produced by a single manufacturer.

B. Installer’s Qualifications: Engage an experienced Installer, certified in writing by tile manufacturer, who has successfully completed tile installations similar in material, design, and extent to that indicated for Project.

C. Tiles shall meet or exceed the following test criteria using the most current test methods:

Polymer Composite Concrete Based Tiles

Property Test Method

Limit

Compressive Strength

ASTM

C39

11,000 psi minimum

Tensile Strength ASTM C96

1,700 psi minimum

Flexural Ultimate Strength

ASTM

C947

2,700 psi minimum

Slip Resistance ASTM C1028

0.80 minimum

Water Absorption ASTM C140

Not to exceed 2%

Abrasion Resistance

ASTM

C418

0.0035 / 2,000 cycles

Freeze thaw ASTM C1262

= 0.00%

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-4 PROJECT TITLE

12/2/2025

D. Tile Size: Individual panel size will be a minimum of 2 feet wide by 3 feet long. Minimum 3 feet of detectable warning tile depth is required at each curb ramp unless noted otherwise on Contract Drawings.

E. Filler: Non-shrink grout per the grout manufacturer’s requirements.

F. Cleaning materials used on site will have code acceptable low VOC solvent content and low flammability.

1.06 DELIVERY, STORAGE AND HANDLING

A. Tiles shall be suitably packaged or crated to prevent damage in shipping or handling. Finished surfaces shall be protected by sturdy wrappings.

1.07 GUARANTEE

A. Cast-in-place concrete tiles shall be guaranteed in writing for a period of 5 years from date of Project’s Final Acceptance. The guarantee includes but is not limited to defective work; breakage; deformation;

loosening of tiles; and failure of fasteners and anchors.

PART 2 - PRODUCTS

2.01 MATERIALS

A. Cast-in-place detectable surface tiles shall be made of polymer composite concrete and ADA and CCR compliant.

B. Color: Yellow conforming to Federal Standard 595B Table IV, Color No. 33538. Color shall be homogeneous throughout the tile.

C. Dome Patterns:

1. For Curb Ramps and Crossings - Inline Dome Configuration (Square grid pattern) of raised truncated domes of 0.2-inch nominal height, base diameter of 0.9 inch, and top diameter of 0.45 inch. Domes shall have a center-to-center spacing of 1.67 inches, and a base-to-base spacing of

0.77 inch measured between the most adjacent domes on square grid.

2. For Transit Platforms and Boarding Islands - Staggered Dome- Configuration (Diamond pattern) of raised truncated domes of 0.2-inch nominal height, base diameter of 0.9 inch, and top diameter of 0.45 inch.

Domes shall have a center-to-center spacing measured horizontal and vertical is 2.35” and the diagonal dome dimension is 1.67”.

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-5 PROJECT TITLE

12/2/2025

D. The field area shall consist of a non-slip surface with a minimum static coefficient of friction of 0.80, wet and dry.

E. Tile Size: Individual panel size shall be a minimum of 2 feet wide by 3 feet long.

F. Filler: In accordance with manufacturer’s requirements.

G. Cleaning materials used on site shall have code acceptable low VOC solvent content and low flammability.

H. The specifications of the concrete, sealants, and related materials shall be in accordance with the Contract Documents and the guidelines set by their respective manufacturers.

2.02 CONTRAST SEPARATION STRIP – (THIS ITEM IS PROJECT SPECIFIC.

IT IS REQUIRED ONLY AT LOCATIONS WHERE VISUAL CONTRAST

DOES NOT EXCEEDS 70% BETWEEN THE ADA TACTILES AND THE

WALKING SURFACE NEXT TO THE TACTILES. REFER TO CALIFORNIA

ACCESS COMPLIANCE ADVISORY CODE. EXAMPLE – THE STRIP IS

REQUIRED IF THE WALKING SURFACE IS LIGHTER COLOR THAN

TACTILE DOME TILES. THE STRIP IS NOT REQUIRED IF THE

WALKING SURFACE IS DARKER COLOR THAN TACTILE DOMES

TILES.)

A. Cast-in-place pre-warning strip shall be made of polymer composite concrete and ADA and CCR compliant.

B. Color: Black or Ebony with same properties as ADA Tactile.

C. Size: 2 inch width x 6 inch length nominal size.

2.03 MANUFACTURERS

A. Available Manufacturers subject to compliance with these Specifications include, but are not limited to, the following:

Location/Use Manufacturer Type and Model

Material

Curb Ramps and Crossings

StrongGo Industries

LLC

TekWay Yellow Cast-in-place Inline Domes Configuration

Polymer Composite Concrete

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-6 PROJECT TITLE

12/2/2025

High Level Transit Platforms

StrongGo Industries

LLC

TekWay Yellow Cast-in-place Straight Edge Staggered Pattern Domes Configuration

Polymer Composite Concrete

Low Level Boarding Islands

StrongGo Industries

LLC

TekWay Yellow Cast-in-place Bull Nose Staggered Pattern Domes Configuration

Polymer Composite Concrete

Contrast Separation Strip

StrongGo Industries

LLC

TekWay Cast-in-place Black Contrast Separation Strip

Polymer Composite Concrete

2.04 EQUIPMENT

A. Contractor shall provide all tools, equipment, and services required for satisfactory installation according to manufacturer’s instruction as incidental work. Equipment, which may be required, include typical mason’s tools, a 4-foot long level with electronic slope readout, 25-lb.

weights, vibrator, small sledge hammer with 2-inch by 6-inch by 20-inch wood tamping plate, and a device for cutting the tiles.

PART 3 - EXECUTION

3.01 PREPARATION

A. During all concrete pouring and tile installation procedures, ensure adequate safety guidelines are in place and that they are in accordance with the applicable industry and government standards.

B. The physical characteristics of the concrete shall be consistent with the

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-7 PROJECT TITLE

12/2/2025

Contract Specifications while maintaining a slump range of 4 to 7 inches to permit solid placement of the Polymer Composite Concrete Tile System.

C. The concrete shall be poured and finished, true and smooth to the required dimensions and slope prior to tile placement.

3.02 INSTALLATION

A. Contractor will not be allowed to install curb ramps, tactiles, and Contrast Separation Strip (PROJECT SPECIFIC OPTION, DESIGNER MUST DELETE IF NOT APPLICABLE TO PROJECT) until all submittals have been reviewed and approved by the Engineer.

B. Tile and Contrast Separation Strip (CONTRACT SPECIFIC

OPTION, DESIGNER MUST DELTE IF NOT APPLICABLE TO

PROJECT) shall be installed according to manufacturer’s instructions.

C. For sidewalk curb ramp and crossing the tile shall be oriented such that the rows of detectable surface domes are parallel with the direction of the ramp.

D. The largest size tile manufactured shall be used to minimize multiple tiles on the ramp. When multiple tiles are used, the domes shall be aligned between the tiles and throughout the entire detectable surface installation. Tile shall be placed to the back of curb in accordance with the Contract Drawings. Cutting the tiles may be required.

E. The Polymer Composite Concrete Tile System shall be tamped or vibrated into the fresh concrete to ensure that there are no voids or air pockets and the field level of tile is flush to the adjacent concrete surface or as the Contract Drawings indicate to permit proper water drainage and eliminate tripping hazards between adjacent finishes. When the tile edge or dome is cut and the tile edge/dome is not flush with the surface of the curb ramp, the edge/dome shall be beveled at 1:2 maximum slope.

F. While the concrete is workable, a 1/8-inch radius-edging tool shall be used to create a finished edge of concrete, then a steel trowel shall be used to finish the concrete around the tile’s perimeter, flush to the field level of the tile.

G. An overly wet mix will cause the Cast-In-Place System to float, therefore under these conditions suitable weights such as two concrete blocks or sandbags (25 lb) shall be placed on each tile.

3.03 CLEANING AND PROTECTING

A. Protect tiles against damage during construction period to comply with

32 17 33: CAST-IN-PLACE DETECTABLE SURFACE TILES

MXXXX 32 17 33-8 PROJECT TITLE

12/2/2025 tactile tile manufacturer’s specifications.

B. During and after the tile installation and the concrete curing stage, it is imperative that there is no walking, leaning, or external forces placed on the tile to rock the tile, causing a void between the underside of tile and concrete.

C. Protect tiles against damage from rolling loads following installation by covering with plywood or hardwood.

D. Clean tiles not more than 4 days prior to date scheduled for inspection intended to establish date of Substantial Completion in each area of project.

Clean tiles by method specified by tactile tile manufacturer.

END OF SECTION 32 17 33

No. Date Description Revised Checked Approved 0 3/5/18 Section 09310, Rev. 0 JN HN MR 1 4/24/23 Revised to 6-Digits CSI JN SN PW

TECHNICAL SPECIFICATIONS

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-1 MXXX.X

8/18/2026

PROJECT TITLE

PART 1 - GENERAL

1.01 DESCRIPTION

The work shall consist of preparing and applying anti-graffiti coating over all exposed surfaces including ( DESIGNER NEEDS TO INCLUDE WORK ITEMS THAT ARE SPECIFIC TO THE PROJECT: all exposed walls including concrete, stucco and brick walls, window frames, exterior doors, barriers, railings, handrails, all non-waking surfaces on boarding ramps, boarding islands, platform concrete surfaces, and other exposed surfaces related to project work and where noted or indicated on the Contract Drawings, as specified hereinafter and as needed for a complete and proper installation.

1.02 RELATED SECTIONS

Section 03 30 00: Cast-in-Place Concrete Section 09 91 00: Painting

1.03 SUBMITTALS

A. Submit the manufacturer's product data and technical information for coatings including coating type, label analysis and application instructions.

The information shall include the manufacturer's name, trade name and current descriptive data for each coating, the schedule list of coatings and number of coats for each surface to be coated. Work that is not in compliance with these requirements shall be removed, refinished and re-coated.

B. Submit manufacturer's and Contractor's recommended coverage rates for types of surfaces to be treated, and evidence that coating conforms to all requirements specified herein.

C. Submit the manufacturer's product data and technical information for graffiti removal which is compatible with anti-graffiti coating.

1.04 DELIVERY AND STORAGE

A. Deliver coating materials in sealed original labeled containers, bearing manufacturer's name, type of paint, brand name, lot number, brand code, coverage, surface preparation, drying time, cleanup requirements, color designation, and instructions for mixing and/or reducing.

1. Name and title of material

2. Federal specification number, if applicable

3. Manufacturer's name

Attachment 1-C-4

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-2 MXXX.X

8/18/2026

PROJECT TITLE

4. Manufacturer's stock number and date of manufacture

5. Contents by volume, for the major vehicle constituents

6. Application instructions

7. Material Safety and Data Sheets

B. Store materials in a clean, dry location, protected from weather and abuse.

1.05 GUARANTEE

During guarantee period any coating failures or evidence of effloresce of the substrate is hereby defined as defective materials and workmanship and shall be repaired promptly by the Contractor without additional cost to the City. Coating failures are defined as water and graffiti penetration, wrinkling, cracking, flaking, loss of adhesion, holidays, excessive dusting, yellowing and clouding of the surface coating.

1.06 QUALITY CONTROL

A. All coatings shall be applied by an applicator approved by the product manufacturer.

B. Contractor shall make tests on interior and/or exterior surfaces and elsewhere where noted or indicated on the Contract Drawings, as directed by the Engineer to establish the actual application rates required to meet all requirements specified herein. Established application rates must not be less than those recommended in the manufacturer's product and technical data for the kind of material surfaces. The surfaces shall be coated as many times as necessary to obtain approval by the Engineer.

PART 2 - PRODUCTS

2.01 MATERIALS

A. General: Graffiti resistant coating shall be a clear, non-sacrificial anti-graffiti resistant, compatible with the surfaces, no gloss, weather and rain resistant, abrasive resistant, peel resistant, ultra-violet resistant, non-yellowing, allow moisture vapor transmission, cause little or no change in appearance of treated surface after removal of graffiti and be non-toxic.

B. Surfaces:

1. Primer Coat for Non-Painted or Porous surfaces including concrete, brick, stucco and masonry surface: Use Rainguard Pro VandlGuard IsoFree™ Aliphatic Urethane 2K. Install per manufacture Technical Data Sheet (TDS) and Specifications.

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-3 MXXX.X

8/18/2026

PROJECT TITLE

The product consists of two components:

Part A (Base Resin): The main water-based acrylic/polyol resin component.

Part B (Catalyst / Crosslinker): The specialized, isocyanate-free hardener component.

The product comes with both containers pre-measured to a 3:1 ratio (e.g., 96

fl. oz. of Part A and 32 fl. oz. of Part B). Mixing Part B into Part A triggers the chemical cross-linking reaction that cures the coating into a tough, non-sacrificial protective layer.

2. Anti-slip coating: Anti-slip additives are separate, secondary materials (such as fine aggregate, micronized polypropylene powder, or aluminum oxide) that are added after Part A and Part B have already been thoroughly mixed together.

3. Correct Sequence:

1) Combine Part A + Part B of VandlGuard IsoFree 2K.

2) Mix thoroughly for 2–3 minutes to start the chemical catalyst reaction.

3) Introduce the separate anti-slip aggregate (or water for dilution, if needed) into the mixed resin while maintaining continuous agitation so the aggregate doesn't settle.

4. Color: Clear

5. Finish: Non-Gloss

C. Graffiti Remover:

VandlClean Super graffiti cleaner by Rainguard International Products.

2.02 SPARE MATERIALS

A. The Contractor shall furnish and deliver the following spare parts to a Muni yard in San Francisco.

Quantity Item

5 gallons Non-Sacrificial Anti-Graffiti Coating Zero Gloss 5 gallons VandlClean Graffiti Cleaner

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-4 MXXX.X

PART 3 - EXECUTION

3.01 GENERAL

Anti-graffiti coating shall not be applied until all the surfaces have been completed.

This requirement shall not relieve the Contractor of his/her responsibilities stated under Section 3.20 “Delegation of Control of the Site; Protection of Work, Persons and Property Against Damage” in the General Provisions.

A. Surface Preparation:

1. Surface shall be free of dirt, dust, contaminants such as curing compounds, hardeners, bond breakers, and form release. Allow painted surfaces to cure properly. Do not water blast painted surfaces. Assure surfaces are clean and dry in accordance with the manufacturer's instructions.

2. Mask and protect adjoining surfaces where overspray is undesirable.

Protect plant life, glass and other areas that may be damaged by the coating.

B. Weather Limitations:

1. All coating shall be done under favorable weather conditions. No painting shall be done when any of the following conditions exist:

- Temperature of air below 50F.

- Temperature of air above 90F.

- Temperature of surface to be coated is below 40F or above

135F

- Wind or rain present or imminent, and excessive dry weather.

2. Coating shall be applied only under such combinations of humidity and temperatures of the ambient atmosphere and surfaces to be coated as will cause evaporation rather than condensation, and only to surfaces which are completely free of moisture as determined by sight or touch. For practical purposes, satisfaction of requirement for dew point is when a thin and clearly defined water film, applied to the cleaned surface with a damp cloth, evaporates within 15 minutes.

C. Procedure:

1. Thinning of anti-graffiti coating shall conform to the manufacturer's printed instructions. Thinning will be allowed only when required.

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-5 MXXX.X

2. Coatings shall be applied and cured in accordance with the manufacturer's printed instructions with care to uniform film thickness, and at the rates determined by the manufacturer, Contractor and as approved by the Engineer.

3. One application of coating shall be applied the same day that the cleaning of the surfaces is performed. A second application shall be applied as soon as the drying time of the first permits.

4. Allow each coat to dry thoroughly and in accordance with the manufacturer's recommendations before recoating.

5. The Engineer will make random tests of coating thickness with a thickness gauge. Coatings of insufficient thickness shall be brought to specified minimum thickness by the Contractor.

6. Finished surfaces shall be free of cloudiness, spotting, holidays, laps, brush marks, runs, sags, curtains, ropiness, improper cutting-in, overspray or other surface deviations or imperfections.

7. Finished surfaces shall be uniform in sheen and texture.

8. Discolorations caused by the Contractor's operations which result in an unsightly appearance on surfaces not designated to be coated shall be repaired at the Contractor's expense.

D. Protection:

1. Contractor shall provide enclosures for protection of coating until cured.

E. Remove masking.

F. Touch-up to the satisfaction of the Engineer where required to achieve uniform, smooth finish.

Coated surfaces marred or damaged as a result of the Contractor's operations shall be repaired at the Contractor's expense, with materials and to a condition equal to that of the coating specified.

G. Upon completion of all operations, the coated surfaces shall be thoroughly cleaned of dust, dirt, grease or other unsightly materials.

END OF SECTION 09 96 23

Contract Number

09 96 23: ANTI-GRAFFITI COATING

09 96 23-6 MXXX.X

No. Date Description Revised Checked Approved

0 1/25/18 Section 09860, Rev. 0 JN CR MR 1 4/24/23 Revised to 6-Digits CSI JN

24x36 WS Staggered Bull-Nose 2G pg 1
Sheets and Views
8.5 x 11
24x36 WS Staggered Bull-Nose 2G pg 2
Sheets and Views
8.5 x 11
Attachment 3a - 32 17 33 - Cast-In-Place Detectable Surface Tiles - 04-24-23.pdf
part 1 - GENERAL
1.01 DESCRIPTION
1.02 related work
A. Section 03 30 00 Cast-In-Place Concrete.
1.03 REFERENCES
A. Americans with Disabilities Act (ADA) Title 49 CFR Transportation, Part 37.9 “Standards for Accessible Transportation Facilities”, Appendix A, Section 4.29.2 “Detectable Warnings on Walking Surfaces”
B. California Code of Regulations (CCR) Title 24 Part 1, Articles 2, 3 and 4; and Section 205 Part 2 definition of “Detectable Warning”, Section 1127B.5 for “Curb Ramps”, and Section 1133B.8.5 for “Detectable Warnings at Hazardous Vehicle Areas.”
C. American Society for Testing and Materials (ASTM) International Test Methods:
1. B117 Standard Practice for Operating Salt Spray (Fog) Apparatus
3. C140 Standard Test Method for Water Absorption
4. C947 Standard Test Method for Flexural Properties of Thin Glass Fiber Reinforced Concrete for using Sample Beam with Third Party Loading
5. C1028 Standard Test Method for Determining the Static Coefficient of Friction of Ceramic Tile and other like surfaces be the Horizontal Dynamometer Pull-Meter Method
6. D543 Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents
7. D570 Standard Test Method for Water Absorption of Plastics
8. D638 Standard Test Method for Tensile Properties of Plastics
9. D695 Standard Test Method for Compressive Properties of Rigid Plastics
10. D790 Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulting Materials
11. D1037 Standard Test Methods for Evaluating Properties of Wood Base Fiber and Particle Panel Materials
12. D2486 Standard Test Methods for Scrub Resistance of Wall Paints
13. D2565 Standard Practice for Xenon Arc Exposure of Plastics Intended for Outdoor Applications
14. D5420 Standard Test Method for Impact Resistance of Flat, Rigid Plastic Specimen by Means of a Striker Impacted by a Falling Weight
15. E84 Review of ASTM Test for Surface Burning Characteristics of Building Materials
D. City and County of San Francisco, Public Works Accessible Street Crossing Standards.
E. Standard Specifications of the City and County of San Francisco, Public Works, Department of Bureau of Engineering (SPDPWSF).
1.04 SUBMITTALS
A. Product Data: Submit manufacturer’s literature describing products, installation procedures, and maintenance instructions.
B. Samples for Verification Purposes: Submit two tile samples minimum 6 Inches by 8 inches of the kind proposed for use. Samples shall be properly labeled and shall contain the following information: Name of Project; Submitted by; Date of Submittal;...
C. Shop drawings: Submit shop drawings showing plans of tile placement including joints, all materials to be used, and an outline of installation procedures.
D. Material Test Reports: Submit current test reports from a qualified independent testing laboratory indicating that materials proposed for use are in compliance with requirements and meet the properties indicated. Tests listed in Section 1.05 shall...
1.05 QUALITY CONTROL
A. Provide cast-in-place detectable surface tiles and accessories as produced by a single manufacturer.
B. Installer’s Qualifications: Engage an experienced Installer, certified in writing by tile manufacturer, who has successfully completed tile installations similar in material, design, and extent to that indicated for Project.
C. Tiles shall meet or exceed the following test criteria using the most current test methods:
Polymer Composite Concrete Based Tiles
D. Tile Size: Individual panel size will be a minimum of 2 feet wide by 3 feet long. Minimum 3 feet of detectable warning tile depth is required at each curb ramp unless noted otherwise on Contract Drawings.
E. Filler: Non-shrink grout per the grout manufacturer’s requirements.
F. Cleaning materials used on site will have code acceptable low VOC solvent content and low flammability.
1.06 DELIVERY, STORAGE AND HANDLING
A. Tiles shall be suitably packaged or crated to prevent damage in shipping or handling. Finished surfaces shall be protected by sturdy wrappings.
1.07 GUARANTEE
A. Cast-in-place concrete tiles shall be guaranteed in writing for a period of 5 years from date of Project’s Final Acceptance. The guarantee includes but is not limited to defective work; breakage; deformation; loosening of tiles; and failure of fast...
Limit
Test Method
Property
11,000 psi minimum
ASTM C39
Compressive Strength
1,700 psi minimum
ASTM C96
Tensile Strength
2,700 psi minimum
ASTM C947
Flexural Ultimate Strength
0.80 minimum
ASTM C1028
Slip Resistance
Not to exceed 2%
ASTM C140
Water Absorption
0.0035 / 2,000 cycles
ASTM C418
Abrasion Resistance
= 0.00%
ASTM C1262
Freeze thaw
PART 2 - PRODUCTS
2.01 MATERIALS
A. Cast-in-place detectable surface tiles shall be made of polymer composite concrete and ADA and CCR compliant.
B. Color: Yellow conforming to Federal Standard 595B Table IV, Color No. 33538. Color shall be homogeneous throughout the tile.
C. Dome Patterns:
1. For Curb Ramps and Crossings - Inline Dome Configuration (Square grid pattern) of raised truncated domes of 0.2-inch nominal height, base diameter of 0.9 inch, and top diameter of 0.45 inch. Domes shall have a center-to-center spacing of 1.67 inche...
2. For Transit Platforms and Boarding Islands - Staggered Dome-Configuration (Diamond pattern) of raised truncated domes of 0.2-inch nominal height, base diameter of 0.9 inch, and top diameter of 0.45 inch. Domes shall have a center-to-center spacing ...
D. The field area shall consist of a non-slip surface with a minimum static coefficient of friction of 0.80, wet and dry.
E. Tile Size: Individual panel size shall be a minimum of 2 feet wide by 3 feet long.
F. Filler: In accordance with manufacturer’s requirements.
G. Cleaning materials used on site shall have code acceptable low VOC solvent content and low flammability.
H. The specifications of the concrete, sealants, and related materials shall be in accordance with the Contract Documents and the guidelines set by their respective manufacturers.
2.02 contrast separation STRIP – (this item is project specific. it is required only at locations where visual contrast does not exceeds 70% between the ada tactiles and the walking surface next to the tactiles. refer to california access compliance a...
A. Cast-in-place pre-warning strip shall be made of polymer composite concrete and ADA and CCR compliant.
B. Color: Black or Ebony with same properties as ADA Tactile.
C. Size: 2 inch width x 6 inch length nominal size.
2.03 MANUFACTURERS
A. Available Manufacturers subject to compliance with these Specifications include, but are not limited to, the following:
2.04 EQUIPMENT
A. Contractor shall provide all tools, equipment, and services required for satisfactory installation according to manufacturer’s instruction as incidental work. Equipment, which may be required, include typical mason’s tools, a 4-foot long level with...
Material
Type and Model
Manufacturer
Location/Use
Polymer Composite Concrete
TekWay Yellow Cast-in-place Inline Domes Configuration
StrongGo Industries LLC
Curb Ramps and Crossings
Polymer Composite Concrete
TekWay Yellow Cast-in-place Straight Edge Staggered Pattern Domes Configuration
StrongGo Industries LLC
High Level Transit Platforms
Polymer Composite Concrete
TekWay Yellow Cast-in-place Bull Nose Staggered Pattern Domes Configuration
StrongGo
Low Level Boarding Islands
Industries LLC
Polymer Composite Concrete
TekWay Cast-in-place
StrongGo
Contrast Separation Strip
Industries LLC
Black Contrast Separation Strip
part 3 - EXECUTION
3.01 PREPARATION
A. During all concrete pouring and tile installation procedures, ensure adequate safety guidelines are in place and that they are in accordance with the applicable industry and government standards.
B. The physical characteristics of the concrete shall be consistent with the Contract Specifications while maintaining a slump range of 4 to 7 inches to permit solid placement of the Polymer Composite Concrete Tile System.
C. The concrete shall be poured and finished, true and smooth to the required dimensions and slope prior to tile placement.
3.02 INSTALLATION
A. Contractor will not be allowed to install curb ramps, tactiles, and Contrast
Separation Strip (PROJECT SPECIFIC OPTION, DESIGNER MUST DELETE IF NOT APPLICABLE TO PROJECT) until all submittals have been reviewed and approved by the Engineer.
B. Tile and Contrast Separation Strip (CONTRACT SPECIFIC OPTION, DESIGNER MUST DELTE IF NOT APPLICABLE TO PROJECT) shall be installed according to manufacturer’s instructions.
C. For sidewalk curb ramp and crossing the tile shall be oriented such that the rows of detectable surface domes are parallel with the direction of the ramp.
D. The largest size tile manufactured shall be used to minimize multiple tiles on the ramp. When multiple tiles are used, the domes shall be aligned between the tiles and throughout the entire detectable surface installation. Tile shall be placed to t...
E. The Polymer Composite Concrete Tile System shall be tamped or vibrated into the fresh concrete to ensure that there are no voids or air pockets and the field level of tile is flush to the adjacent concrete surface or as the Contract Drawings indica...
F. While the concrete is workable, a 1/8-inch radius-edging tool shall be used to create a finished edge of concrete, then a steel trowel shall be used to finish the concrete around the tile’s perimeter, flush to the field level of the tile.
G. An overly wet mix will cause the Cast-In-Place System to float, therefore under these conditions suitable weights such as two concrete blocks or sandbags (25 lb) shall be placed on each tile.
3.03 CLEANING AND PROTECTING
A. Protect tiles against damage during construction period to comply with tactile tile manufacturer’s specifications.
B. During and after the tile installation and the concrete curing stage, it is imperative that there is no walking, leaning, or external forces placed on the tile to rock the tile, causing a void between the underside of tile and concrete.
C. Protect tiles against damage from rolling loads following installation by covering with plywood or hardwood.
D. Clean tiles not more than 4 days prior to date scheduled for inspection intended to establish date of Substantial Completion in each area of project. Clean tiles by method specified by tactile tile manufacturer.