Clarifications_2.pdf

PDF 180 KB Posted

Attached to
HANDRAILS FOR USS MAINE MEMORIAL
Solicitation number
P15PS00451
Issued by

About this file

Clarifications 2

View the file

Other files

File Type Posted
Sol_P15PS00451_Amd_000005.pdf PDF
Sol_P15PS00451_Amd_000004.pdf PDF
ANC_Railing_Contract_Drawings_(REVISED_SET_032715).pdf PDF
Clarifications.pdf PDF
Sol_P15PS00451_Amd_000003.pdf PDF
Sol_P15PS00451_Amd_000002.pdf PDF
Sol_P15PS00451_Amd_000001.pdf PDF
Attachment_6 _G-1.pdf PDF
Attachment_1 _B-1.pdf PDF
Attachment_10 _M-1.pdf PDF
Sol_P15PS00451.pdf PDF
Mast_of_the_Maine_Handrails_Spec.pdf PDF
Attachment_5 _F-1.pdf PDF
Attachment_7 _H-1.pdf PDF
Attachment_2 _C-1.pdf PDF
Attachment_8 _J-1.pdf PDF
ANC_903_120001B_Railing_Contract_Drawings_(SET).pdf PDF
Attachment_4 _E-1.pdf PDF
Attachment_9 _L-1.pdf PDF
Davis_Bacon_Wage_Determination.pdf PDF
Attachment_3 _D-1.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question 1) Is there a specification on the wall mount grab rails starting with Ramp C on sheet A5?

Clarification: The Contractor shall submit the wall mount grab rails during the submittal process for

COR review and approval.

Question 2) Can the steel sleeve be deleted from the scope? The reason for this would be a 2-1/2” diameter id pipe would be required which is 2-7/8” od which in turn would require a 4” hole to allow room for the grout expansion. In the 6” wall there would only be 1” of wall material remaining on each side assuming the wall is straight and wall thickness does not vary.

Clarification: Yes, the sleeve can be deleted as long as the posts are mounted solidly and plumb in the holes with the expansion grout.

Question 3) Would a mill size ¾ x 1-1/2” or a ¾ x 1-3/4 be permissible to use in lieu of the specified ¾ x

1-7/8” which would have to be custom cut from sheet which will get rather expensive?

Clarification: The Contractor shall submit proposed flat bar sizes during the submittal process for COR review and approval.

Question 4) In tandem with question #3, the flat bar at the most needs to be a ¼ x 1-1/4 to keep the cables together and no mount to the concrete is needed. With that said would the architect be open for either what I just listed or just use the same 1-1/2” schedule 40 pipe as the main posts?

Clarification: The Contractor shall submit proposed flat bar sizes during the submittal process for COR review and approval. Schedule 40 piping is not acceptable.