NASA Goddard Space Flight Center Final Submission Instrument Development Facility December 8, 2016
SECTION 23 00 00
AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
11/15
PART 1 GENERAL
1.1 RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
This Section includes performance requirements and other criteria for duct systems, air systems equipment, air handling units, terminal units, ceiling cassette units, energy recovery devices, and HVAC-related supplemental components.
1.3 RELATED SECTIONS
Related Sections include the following:
1. Division 01 Section 01 91 13 "General Commissioning Requirements."
2. Division 05 Section 05 50 13 "Miscellaneous Metal Fabrications."
3. Division 07 Section 07 84 00 "Firestopping."
4. Division 08 Section 08 91 00 "Metal Wall Louvers."
5. Division 09 Section 09 90 00 "Paints and Coatings."
6. Division 22 Section 22 00 00 "Plumbing, General Purpose."
7. Division 23 Section 23 05 93 "Testing, Adjusting and Balancing for
HVAC."
8. Division 23 Section 23 07 00 "Thermal Insulation for Mechanical Systems."
9. Division 23 Section 23 09 23 "BACnet Direct Digital Control Systems for HVAC."
10. Division 23 Section 23 09 53 "Space Temperature Control Systems."
11. Division 23 Section 23 64 26 "Chilled Water Piping Systems."
12. Division 26 Section 26 20 00 "Interior Distribution System."
1.4 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
SECTION 23 00 00 Page 1
NASA Goddar d Space Fl i ght Cent er Fi nal Submi ssi on I nst r ument Devel opment Faci l i t y December 8, 2016
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ANSI Z9. 5 ( 2012) Labor at or y Vent i l at i on
AI R- CONDI TI ONI NG, HEATI NG AND REFRI GERATI ON I NSTI TUTE ( AHRI )
AHRI 350 ( 2008) Sound Rat i ng of Non- Duct ed I ndoor Ai r - Condi t i oni ng Equi pment
AHRI 410 ( 2001; Addendum 1 2002; Addendum 2 2005;
Addendum 3 2011) For ced- Ci r cul at i on Ai r - Cool i ng and Ai r - Heat i ng Coi l s
AHRI 440 ( 2008) Room Fan- Coi l s and Uni t Vent i l at or s
AHRI 640 ( 2005) Per f or mance Rat i ng of Commer ci al and I ndust r i al Humi di f i er s
AHRI 880 I - P ( 2011) Per f or mance Rat i ng of Ai r Ter mi nal s
AHRI 885 ( 2008; Addendum 2011) Pr ocedur e f or Est i mat i ng Occupi ed Space Sound Level s i n t he Appl i cat i on of Ai r Ter mi nal s and Ai r Outlets
AHRI Gui del i ne D ( 1996) Appl i cat i on and I nst al l at i on of Cent r al St at i on Ai r - Handl i ng Uni t s
AMERI CAN I RON AND STEEL I NSTI TUTE ( AI SI )
AI SI C1045 ( 2007) St andar d Pr act i ce f or Cal cul at i ng Ther mal Tr ansmi ssi on Pr oper t i es Under St eady- St at e Condi t i ons
AI R MOVEMENT AND CONTROL ASSOCI ATI ON I NTERNATI ONAL ( AMCA)
AMCA 201 ( 2002; R 2011) Fans and Syst ems
AMCA 204 ( 2005) Test Met hods f or Ai r Cur t ai n Uni t s
AMCA 210 ( 2007) Labor at or y Met hods of Test i ng Fans f or Aer odynami c Per f or mance Rat i ng
AMCA 220 ( 2005) Test Met hods f or Ai r Cur t ai n Uni t s
AMCA 260 ( 2013) Labor at or y Met hods of Test i ng I nduced Fl ow Fans f or Rat i ng
AMCA 300 ( 2014) Rever ber ant Room Met hod f or Sound Test i ng of Fans
AMCA 301 ( 2014) Met hods f or Cal cul at i ng Fan Sound Rat i ngs f r om Labor at or y Test Dat a
AMCA 500- D ( 2012) Labor at or y Met hods of Test i ng Damper s f or Rat i ng
SECTI ON 23 00 00 Page 2
AMERI CAN BEARI NG MANUFACTURERS ASSOCI ATI ON ( ABMA)
ABMA 11 ( 2014) Load Rat i ngs and Fat i gue Li f e f or Rol l er Bear i ngs
ABMA 9 ( 1990; ERTA 2012; S 2013) Load Rat i ngs and Fat i gue Li f e f or Bal l Bear i ngs
AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG
ENGI NEERS ( ASHRAE)
ASHRAE 52. 2 ( 2012; Er r at a 2013; I NT 1 2014; ADD A, B, AND D SUPP 2015; I NT 3 2015) Met hod of Test i ng Gener al Vent i l at i on Ai r - Cl eani ng Devi ces f or Removal Ef f i c i ency by Par t i c l e Size
ASHRAE 62. 1 ( 2010; Er r at a 2011; I NT 3 2012; I NT 4 2012; I NT 5 2013) Vent i l at i on f or Accept abl e I ndoor Ai r Qual i t y
ASHRAE 70 ( 2006; R 2011) Met hod of Test i ng f or Rat i ng t he Per f or mance of Ai r Out l et s and Inlets
ASHRAE 90. 1 - I P ( 2013; I NT 1 2013; Er r at a 1- 3 2013; Er r at a 4- 6 2014; Er r at a 7- 8 2015; I NT 2- 3 2015) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs
ASME I NTERNATI ONAL ( ASME)
ASME A13. 1 ( 2007; R 2013) Scheme f or t he I dent i f i cat i on of Pi pi ng Syst ems
ASTM I NTERNATI ONAL ( ASTM)
ASTM A123/ A123M ( 2013) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s
ASTM A167 ( 2011) St andar d Speci f i cat i on f or St ai nl ess and Heat - Resi st i ng Chr omi um- Ni ckel St eel Pl at e, Sheet , and Strip
ASTM A53/ A53M ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess
ASTM A924/ A924M ( 2014) St andar d Speci f i cat i on f or Gener al Requi r ement s f or St eel Sheet , Met al l i c- Coat ed by t he Hot - Di p Pr ocess
ASTM B117 ( 2011) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us
ASTM B152/ B152M ( 2013) St andar d Speci f i cat i on f or Copper Sheet , St r i p, Pl at e, and Rol l ed Bar
SECTI ON 23 00 00 Page 3
ASTM B209 ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e
ASTM B766 ( 1986; R 2015) St andar d Speci f i cat i on f or El ect r odeposi t ed Coat i ngs of Cadmi um
ASTM C1071 ( 2012) St andar d Speci f i cat i on f or Fi br ous Gl ass Duct Li ni ng I nsul at i on ( Ther mal and Sound Absor bi ng Mat er i al )
ASTM C1363 ( 2011) St andar d Test Met hod f or Ther mal Per f or mance of Bui l di ng Mat er i al s and Envel ope Assembl i es by Means of a Hot Box Apparatus
ASTM C553 ( 2013) St andar d Speci f i cat i on f or Mi ner al Fi ber Bl anket Ther mal I nsul at i on f or Commer ci al and I ndust r i al Appl i cat i ons
ASTM C754 ( 2015) I nst al l at i on of St eel Fr ami ng Member s t o Recei ve Scr ew- At t ached Gypsum Panel Pr oduct s
ASTM C916 ( 2014) St andar d Speci f i cat i on f or Adhesi ves f or Duct Ther mal I nsul at i on
ASTM D1654 ( 2008) Eval uat i on of Pai nt ed or Coat ed Speci mens Subj ect ed t o Cor r osi ve Environments
ASTM D3359 ( 2009; E 2010; R 2010) Measur i ng Adhesi on by Tape Test
ASTM E84 ( 2015b) St andar d Test Met hod f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA MG 1 ( 2014) Mot or s and Gener at or s
NEMA MG 10 ( 2013) Ener gy Management Gui de f or Sel ect i on and Use of Fi xed Fr equency Medi um AC Squi r r el - Cage Pol yphase I nduct i on Mot or s
NEMA MG 11 ( 1977; R 2012) Ener gy Management Gui de f or Sel ect i on and Use of Si ngl e Phase Mot or s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 701 ( 2015) St andar d Met hods of Fi r e Test s f or Fl ame Pr opagat i on of Text i l es and Fi l ms
NFPA 80 ( 2013) St andar d f or Fi r e Door s and Ot her Openi ng Pr ot ect i ves
NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of
SECTI ON 23 00 00 Page 4
Ai r Condi t i oni ng and Vent i l at i ng Syst ems
NFPA 105 ( 2016) St andar d f or I nst al l at i on of Smoke Door Assembl i es and Ot her Openi ng Protectives
SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON
(SMACNA)
SMACNA 1819 ( 2002) Fi r e, Smoke and Radi at i on Damper I nst al l at i on Gui de f or HVAC Syst ems, 5t h Edition
SMACNA 1884 ( 2003) Fi br ous Gl ass Duct Const r uct i on St andar ds, 7t h Edi t i on
SMACNA 1966 ( 2005) HVAC Duct Const r uct i on St andar ds Met al and Fl exi bl e, 3r d Edi t i on
SMACNA 1972 CD ( 2012) HVAC Ai r Duct Leakage Test Manual - 2nd Edi t i on
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
40 CFR 82 Pr ot ect i on of St r at ospher i c Ozone
29 CFR 1910. 333 El ect r i cal - Saf et y Rel at ed Wor k Pr act i ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel
UL 94 ( 2013; Repr i nt Jan 2015) St andar d f or Test s f or Fl ammabi l i t y of Pl ast i c Mat er i al s f or Par t s i n Devi ces and Appliances
UL 181 ( 2013) Fact or y- Made Ai r Duct s and Ai r Connectors
UL 555 ( 2006; Repr i nt May 2014) St andar d f or Fi r e Dampers
UL 555S ( 2014) Smoke Damper s
UL 586 ( 2009; Repr i nt Sep 2014) St andar d f or Hi gh- Ef f i c i ency Par t i cul at e, Ai r Fi l t er Units
UL 723 ( 2008; Repr i nt Aug 2013) Test f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials
UL 900 ( 2015) St andar d f or Ai r Fi l t er Uni t s
UL 998 ( 2011) St andar d f or Saf et y Humi di f i er s
UL 1995 ( 2011) Heat i ng and Cool i ng Equi pment
SECTI ON 23 00 00 Page 5
UL Bl d Mat Di r ( 2012) Bui l di ng Mat er i al s Di r ect or y
U. S. GREEN BUI LDI NG COUNCI L ( USGBC)
LEED NC ( 2009; R2014) Leader shi p i n Ener gy and Envi r onment al Desi gn( t m) New Const r uct i on Rat i ng Syst em
1. 5 SYSTEM DESCRI PTI ON
Fur ni sh duct wor k, pi pi ng of f set s, f i t t i ngs, and accessor i es as r equi r ed t o pr ovi de a compl et e i nst al l at i on. Coor di nat e t he wor k of t he di f f er ent t r ades t o avoi d i nt er f er ence bet ween pi pi ng, equi pment , st r uct ur al , and el ect r i cal wor k. Pr ovi de compl et e, i n pl ace, al l necessar y of f set s i n pi pi ng and duct wor k, and al l f i t t i ngs, and ot her component s, r equi r ed t o i nst al l t he wor k as i ndi cat ed and speci f i ed.
1. 5. 1 Mechani cal Equi pment I dent i f i cat i on
The number of char t s and di agr ams shal l be equal t o or gr eat er t han t he number of mechani cal equi pment r ooms. Wher e mor e t han one char t or di agr am per space i s r equi r ed, mount t hese i n edge pi vot ed, swi ngi ng l eaf , ext r uded al umi num f r ame hol der s whi ch open t o 170 degr ees.
1. 5. 1. 1 Charts
Pr ovi de char t l i s t i ng of equi pment by desi gnat i on number s and capaci t i es such as f l ow r at es, pr essur e and t emper at ur e di f f er ences, heat i ng and cool i ng capaci t i es, hor sepower , pi pe s i zes, and vol t age and cur r ent characteristics.
1. 5. 1. 2 Val ve Tags and Syst em Di agr ams
Pr ovi de t ags and syst em di agr ams f or new or modi f i ed Power Pl an mechani cal syst ems. When i ndi cat ed on t he const r uct i on document s, pr ovi de t ags and syst em di agr ams f or ot her speci al mechani cal syst ems. I dent i f i cat i on t ags made of br ass or al umi num i ndi cat i ng f unct i on of a val ve, cont r ol , or s i mi l ar component shal l be i nst al l ed on such syst em devi ces. Tags shal l be 2 i nches i n di amet er and mar ki ng shal l be st amped. Syst em or ser vi ce abbr evi at i on and number i ng shal l be as i ndi cat ed on t he const r uct i on documents.
Tags shal l be wi r ed t o val ve or equi pment i t ems wi t h AWG No. 12 ( 0. 0808- i nch di amet er ) cor r osi on- r esi st ant st eel wi r e.
Di agr ams shal l show schemat i c ar r angement of syst em pi pi ng or duct wor k, l ocat i on and t ag i dent i f i cat i on of val ves, damper s, cont r ol s or s i mi l ar component s, and GOMAR number s f or such equi pment as pumps, wat er heat er s, ai r - handl i ng syst em equi pment , and heat exchanger s.
Di agr ams shal l be neat mechani cal dr awi ngs pr ovi ded wi t h ext r uded al umi num f r ames and 1/ 8- i nch t hi ck c l ear acr yl i c pl ast i c pr ot ect i on. Locat i on shal l be as di r ect ed by t he Gover nment . Copi es of t he di agr ams shal l al so be i ncl uded i n t he Oper at i ons and Mai nt enance Manual s f or t he syst em.
1. 5. 1. 3 GOMAR Cei l i ng Mar ker s
Wher e new equi pment i s conceal ed above cei l i ngs, pr ovi de GOMAR cei l i ng
SECTI ON 23 00 00 Page 6 mar ker s i n compl i ance wi t h t he par agr aph ent i t l ed " GOMAR Tags. "
1. 5. 1. 4 GOMAR Tags
I n addi t i on t o st andar d manuf act ur er ' s i dent i f i cat i on pl at es, pr ovi de GOMAR t ags f or each new pi ece of mechani cal equi pment . GOMAR t ags shal l show t he equi pment number as i ndi cat ed on t he const r uct i on document s.
Pr ovi de 0. 125- i nch t hi ck mel ami ne l ami nat ed pl ast i c namepl at es f or al l GOMAR equi pment , bl ack mat t e f i ni sh wi t h whi t e cent er cor e wi t h engr aved GOMAR number . Si ze shal l be 1 i nch hi gh and mi ni mum 4 i nches l ong.
Let t er i ng hei ght shal l be a mi ni mum 0. 5 i nch. Namepl at es shal l be f ast ened by st ai nl ess st eel sel f - t appi ng scr ews or cont act - t ype per manent adhesi ve compat i bl e wi t h l abel and subst r at e. Key namepl at es t o a char t and schedul e f or each syst em. Fr ame char t s and schedul es under c l ear acr yl i c pl ast i c pr ot ect i on. Fur ni sh 2 copi es of each char t and schedul e.
1. 5. 2 Ser vi ce Label i ng
I dent i f y s i mi l ar ser vi ces wi t h di f f er ent t emper at ur es or pr essur es. Wher e pr essur es coul d exceed 125 pounds per squar e i nch, i ncl ude t he maxi mum syst em pr essur e i n t he l abel . Label and ar r ow pi pi ng i n accor dance wi t h t he f ol l owi ng:
a. Each poi nt of ent r y and exi t of pi pe and duct wor k passi ng t hr ough wal l s.
b. Each change i n di r ect i on ( i . e. , el bows, t ees) .
c. I n congest ed or hi dden ar eas and at al l access panel s at each poi nt r equi r ed t o c l ar i f y ser vi ce or i ndi cat ed hazar d.
d. I n l ong st r ai ght r uns, l ocat e l abel s at di st ances wi t hi n eyesi ght of each ot her not t o exceed 75 f eet . Al l l abel s shal l be v i s i bl e and l egi bl e f r om t he pr i mar y ser vi ce and oper at i ng ar ea.
For Bar e or I nsul at ed Pi pes and Duct wor k
For Out si de Di amet er s of : Let t er i ng Hei ght :
1/ 2 t hr u 1- 3/ 8 i nch 1/ 2 i nch
1- 1/ 2 t hr u 2- 3/ 8 i nch 3/ 4 i nch
2- 1/ 2 i nch t hr u 6 i nches 1- 1/ 4 i nch over 6 i nches t hr u 10 i nches 2- 1/ 2 i nch over 10 i nches 3- 1/ 2 i nch
Label s shal l be made of sel f - st i ck i ng, pl ast i c f i l m desi gned f or per manent i nst al l at i on. Label s shal l be col or - coded i n compl i ance wi t h ASME A13. 1.
1. 5. 3 Col or Codi ng and Pai nt i ng
Except wi t hi n t he power pl ant s ( Bui l di ngs 24 and 31) , pai nt i ng of pi pi ng and duct wor k shal l not be col or coded. Unl ess ot her wi se i ndi cat ed, exposed
SECTI ON 23 00 00 Page 7 pi pi ng and duct wor k shal l be pai nt ed t o mat ch sur r oundi ng sur f aces i n f i ni shed ar eas.
Pi pi ng i n power pl ant s ( Bui l di ngs 24 and 31) shal l be pai nt ed wi t h col or codes compl i ant wi t h ASME A13. 1.
1. 5. 4 Hazar dous Exhaust St ack and Fan Label i ng
For pur poses of l abel i ng, al l exhaust f ans and st acks, ot her t han t oi l et exhaust s and bui l di ng or ai r handl er r el i ef ai r vent s, shal l be consi der ed " hazar dous. " Pr ovi de a 3- i nch wi de yel l ow band ar ound t he out l et of each hazar dous exhaust out l et . I n addi t i on t o t he equi pment i dent i f i cat i on pl at es speci f i ed her ei n, pr ovi de a caut i on s i gn af f i xed t o each hazar dous exhaust f an or st ack i n a pr omi nent l ocat i on. Caut i on s i gns shal l be a mi ni mum 14 i nches wi de by 10 i nches hi gh, 0. 020 i nch t hi ck al umi num. Top por t i on of t he s i gn shal l be a bl ack band wi t h " WARNI NG" l et t er ed i n yel l ow. Bel ow t hi s shal l be a yel l ow backgr ound wi t h t he f ol l owi ng l et t er i ng i n bl ack ( i ncl ude bl anks as shown f or f i el d mar ki ng by t he Government):
HAZARDOUS EXHAUST
Hazar d Cl asses: ______________________________
Or i gi n: Bui l di ng____________Room____________
User:________________________________________
Si gns shal l be s i mi l ar t o model number W- CVAR, as manuf act ur ed by Al l st at e Si gn and Pl aque, Deer Par k, NY.
1. 6 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . The f ol l owi ng shal l be submi t t ed i n accor dance wi t h Di v i s i on 01 Sect i on 01 33 00 " Submi t t al Procedures":
SD- 01 Pr econst r uct i on Submi t t al s
Test Pr ocedur es; G
SD- 02 Shop Dr awi ngs
Det ai l Dr awi ngs; G, AE
Val ve Tags And Syst em Di agr ams; G, AE
SD- 03 Pr oduct Dat a
Met al Duct wor k; G, AE
Met al l i c Fl exi bl e Duct ; G, AE
I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s; G, AE
SECTI ON 23 00 00 Page 8
Duct Access Door s; G, AE
Fi r e Damper s; G, AE
Manual Bal anci ng Damper s; G, AE
Combi nat i on Fi r e- Smoke Damper s; G, AE
Aut omat i c Smoke Damper s; G, AE
Doubl e Wal l Panel s f or Fi el d- Fabr i cat ed Pl enums; G, AE
Sound At t enuat i on Equi pment ; G, AE
Acoust i cal Duct Li ner ; G, AE
Di f f user s; G, AE
Regi st er s And Gr i l l es; G, AE
Cent r i f ugal Type Power Roof Vent i l at or s; G, AE
Hi gh Pl ume Di l ut i on Bl ower s, G, AE
Panel Type Power Wal l Vent i l at or s; G, AE
Ai r Cur t ai n Fans; G, AE
Coi l s; G, AE
Humi di f i er s; G, AE
Ai r Fi l t er s; G, AE
Cust om Ai r Handl i ng Uni t s; G, AE
Out si de Ai r Uni t ; G, AE
Ret ur n Ai r Uni t ; G, AE
Exhaust Ai r Uni t ; G, AE
Run- Ar ound Ener gy Recover y/ Heat i ng Syst em; G, AE
Room Fan- Coi l Uni t s; G, AE
Var i abl e Ai r Vol ume Ter mi nal Uni t s; G, AE
SD- 05 Desi gn Dat a
Met al Duct wor k; G, AE
SD- 06 Test Repor t s
Duct wor k Leak Test ; G, AE
Damper Accept ance Test ; G, AE
Syst em Per f or mance Test i ng; G, AE
SECTI ON 23 00 00 Page 9
SD- 07 Cer t i f i cat es
Bol t s; G
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i on and Mai nt enance Manual s; G
SD- 11 Cl oseout Submi t t al s
Fi nal Sust ai nabi l i t y Not ebook Submi t t al ; G
LEED Document at i on Not ebook; G
1. 7 QUALI TY ASSURANCE
Except as ot her wi se speci f i ed, appr oval of mat er i al s and equi pment i s based on manuf act ur er ' s publ i shed dat a.
a. Wher e mat er i al s and equi pment ar e speci f i ed t o conf or m t o t he st andar ds of t he Under wr i t er s Labor at or i es, t he l abel of or l i s t i ng wi t h r eexami nat i on i n UL Bl d Mat Di r , and UL 6 i s accept abl e as suf f i c i ent evi dence t hat t he i t ems conf or m t o Under wr i t er s Labor at or i es r equi r ement s. I n l i eu of such l abel or l i s t i ng, submi t a wr i t t en cer t i f i cat e f r om any nat i onal l y r ecogni zed t est i ng agency, adequat el y equi pped and compet ent t o per f or m such ser vi ces, s t at i ng t hat t he i t ems have been t est ed and t hat t he uni t s conf or m t o t he speci f i ed r equi r ement s. Out l i ne met hods of t est i ng used by t he speci f i ed agencies.
b. Wher e mat er i al s or equi pment ar e speci f i ed t o be const r uct ed or t est ed, or bot h, i n compl i ance wi t h t he st andar ds of t he ASTM I nt er nat i onal ( ASTM) , t he ASME I nt er nat i onal ( ASME) , or ot her st andar ds, a manuf act ur er ' s cer t i f i cat e of compl i ance of each i t em i s accept abl e as pr oof of compl i ance.
c. Conf or mance t o such agency r equi r ement s does not r el i eve t he i t em f r om compl i ance wi t h ot her r equi r ement s of t hese speci f i cat i ons.
1. 7. 1 Pr event i on of Cor r osi on
Pr ot ect met al l i c mat er i al s agai nst cor r osi on. Manuf act ur er shal l pr ovi de r ust - i nhi bi t i ng t r eat ment and st andar d f i ni sh f or t he equi pment encl osur es. Do not use al umi num i n cont act wi t h ear t h, and wher e connect ed t o di ssi mi l ar met al . Pr ot ect al umi num by appr oved f i t t i ngs, bar r i er mat er i al , or t r eat ment . Fer r ous par t s such as anchor s, bol t s, br aces, boxes, bodi es, c l amps, f i t t i ngs, guar ds, nut s, pi ns, r ods, shi ms, t hi mbl es, washer s, and mi scel l aneous par t s not of cor r osi on- r esi st ant st eel or nonf er r ous mat er i al s shal l be hot - di p gal vani zed i n compl i ance wi t h ASTM A123/ A123M f or ext er i or l ocat i ons and cadmi um- pl at ed i n compl i ance with ASTM B766 f or i nt er i or l ocat i ons. Pr ovi de wr i t t en cer t i f i cat i on f r om t he bol t manuf act ur er t hat t he bol t s f ur ni shed compl y wi t h t he r equi r ement s of t hi s speci f i cat i on. I ncl ude i l l ust r at i ons of pr oduct mar ki ngs, and t he number of each t ype of bol t t o be f ur ni shed i n t he cer t i f i cat i on.
1. 7. 2 Asbest os Pr ohi bi t i on
Do not use asbest os and asbest os- cont ai ni ng pr oduct s.
SECTI ON 23 00 00 Page 10
1. 7. 3 Si l i cone Pr ohi bi t i on
Do not use s i l i cone and si l i cone- cont ai ni ng pr oduct s.
1. 7. 4 Use of Ozone Depl et i ng Subst ances, Ot her t han Ref r i ger ant s
The use of Cl ass I or Cl ass I I ODS' s l i s t ed as nonessent i al i n 40 CFR 82 Par t 82. 66 Subpar t C i s pr ohi bi t ed. These pr ohi bi t ed mat er i al s and uses include:
a. Any pl ast i c par t y spr ay st r eamer or noi se hor n whi ch i s pr opel l ed by a chlorofluorocarbon
b. Any c l eani ng f l ui d f or el ect r oni c and phot ogr aphi c equi pment whi ch cont ai ns a chl or of l uor ocar bon; i ncl udi ng l i qui d packagi ng, sol vent wi pes, sol vent spr ays, and gas spr ays.
c. Any pl ast i c f l exi bl e or packagi ng f oam pr oduct whi ch i s manuf act ur ed wi t h or cont ai ns a chl or of l uor ocar bon, i ncl udi ng, open cel l f oam, open cel l r i gi d pol yur et hane pour ed f oam, c l osed cel l ext r uded pol yst yr ene sheet f oam, c l osed cel l pol yet hyl ene f oam and cl osed cel l pol ypr opyl ene f oam except f or f l exi bl e or packagi ng f oam used i n coaxi al cabl i ng.
d. Any aer osol pr oduct or ot her pr essur i zed di spenser whi ch cont ai ns a chl or of l uor ocar bon, except f or t hose l i s t ed i n 40 CFR 82 Par t 82. 66 Subpar t C.
Request a wai ver i f a f aci l i t y r equi r ement di ct at es t hat a pr ohi bi t ed mat er i al i s necessar y t o achi eve pr oj ect goal s. Submi t t he wai ver r equest i n wr i t i ng t o t he Gover nment . The wai ver wi l l be eval uat ed and dispositioned.
1. 7. 5 Det ai l Dr awi ngs
Submi t det ai l dr awi ngs showi ng equi pment l ayout , i ncl udi ng assembl y and i nst al l at i on det ai l s and el ect r i cal connect i on di agr ams; duct wor k l ayout showi ng t he l ocat i on of al l suppor t s and hanger s, t ypi cal hanger det ai l s , gauge r ei nf or cement , r ei nf or cement spaci ng r i gi di t y c l assi f i cat i on, and st at i c pr essur e and seal c l assi f i cat i ons. I ncl ude any i nf or mat i on r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and f unct i ons pr oper l y as a uni t on t he dr awi ngs and show equi pment r el at i onshi p t o ot her par t s of t he wor k, i ncl udi ng c l ear ances r equi r ed f or oper at i on and mai nt enance.
Submi t dr awi ngs showi ng bol t - set t i ng i nf or mat i on, and f oundat i on bol t s pr i or t o concr et e f oundat i on const r uct i on f or al l equi pment i ndi cat ed or r equi r ed t o have concr et e f oundat i ons. Submi t f unct i on desi gnat i on of t he equi pment and any ot her r equi r ement s speci f i ed t hr oughout t hi s Sect i on wi t h t he shop dr awi ngs.
1. 7. 6 Test Pr ocedur es
Submi t pr oposed t est pr ocedur es f or t he duct wor k l eak t est , damper accept ance t est , and syst em per f or mance t est i ng f or each syst em at l east 2 weeks pr i or t o t he st ar t of r el at ed t est i ng.
1. 7. 7 Sust ai nabl e Desi gn Cer t i f i cat i on
Pr oduct shal l be t hi r d par t y cer t i f i ed i n accor dance wi t h ULE Gr eenguar d Gol d, SCS Sci ent i f i c Cer t i f i cat i on Syst ems I ndoor Advant age Gol d or equal .
SECTI ON 23 00 00 Page 11
Cer t i f i cat i on shal l be per f or med annual l y and shal l be cur r ent .
1. 8 DELI VERY, STORAGE, AND HANDLI NG
Del i ver mat er i al s t o t he pr oj ect s i t e i n t he manuf act ur er ' s or i gi nal packagi ng, cont ai ner s, or bundl es wi t h manuf act ur er and suppl i er ' s l abel i ng c l ear l y v i s i bl e.
Pr ot ect st or ed equi pment at t he j obsi t e f r om t he weat her , humi di t y and t emper at ur e var i at i ons, di r t and dust , or ot her cont ami nant s.
Addi t i onal l y, cap or pl ug al l pi pes unt i l i nst al l ed.
St or age ar ea shal l be easi l y accessi bl e f or i nspect i on. Damaged i t ems shal l be r epl aced wi t h new when di r ect ed by t he Gover nment .
1. 9 SUSTAI NABLE DESI GN REQUI REMENTS
1. 9. 1 Fi nal Sust ai nabi l i t y Not ebook Submi t t al
Ref er t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG f or f eder al sust ai nabi l i t y pr oduct and document at i on r equi r ement s.
1. 9. 2 LEED Document at i on Not ebook
Ref er t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG f or LEED NC pr er equi s i t es and cr edi t s r equi r ed t o be ear ned f or t hi s pr oj ect ( r ef er t o LEED scor ecar d at t ached t o 01 33 29 SUSTAI NABI LI TY REPORTI NG f or t hose cr edi t s and r equi r ed poi nt s i n t hose cr edi t s) . Ref er t o t he LEED NC v2009 r ef er ence gui de and addi t i onal onl i ne gui dance at www. usgbc. or g f or document at i on r equi r ement s.
PART 2 PRODUCTS
2. 1 STANDARD PRODUCTS
Pr ovi de component s and equi pment t hat ar e t he " st andar d pr oduct s" of a manuf act ur er r egul ar l y engaged i n t he manuf act ur i ng of pr oduct s t hat ar e of a s i mi l ar mat er i al , desi gn and wor kmanshi p. " St andar d pr oduct s" shal l be def i ned as bei ng i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s, i ncl udi ng appl i cat i ons of component s and equi pment under s i mi l ar c i r cumst ances and of s i mi l ar s i ze, sat i sf act or i l y compl et ed by a pr oduct t hat i s sol d on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es. Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d ar e accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on, f or not l ess t han 6000 hour s excl usi ve of t he manuf act ur er ' s f act or y t est s, can be shown. Pr ovi de equi pment i t ems t hat ar e suppor t ed by a ser vi ce or gani zat i on. Wher e appl i cabl e, pr ovi de equi pment t hat i s l i s t ed on t he ENERGY STAR Qual i f i ed Pr oduct s Li st or t hat meet s or exceeds t he FEMP- desi gnat ed Ef f i c i ency Requi r ement .
2. 2 EQUI PMENT GUARDS AND ACCESS
Ful l y encl ose or guar d bel t s, pul l eys, chai ns, gear s, coupl i ngs, pr oj ect i ng set scr ews, keys, and ot her r ot at i ng par t s exposed t o per sonnel cont act accor di ng t o OSHA r equi r ement s. Pr oper l y guar d or cover wi t h i nsul at i on of a t ype speci f i ed, hi gh t emper at ur e equi pment and pi pi ng exposed t o cont act by per sonnel or wher e i t cr eat es a pot ent i al f i r e hazar d. The r equi r ement s f or cat wal ks, oper at i ng pl at f or ms, l adder s, and guar dr ai l s ar e speci f i ed i n Di v i s i on 05 Sect i on 05 50 13 " Mi scel l aneous Met al Fabr i cat i ons. "
SECTI ON 23 00 00 Page 12
2. 3 ELECTRI CAL WORK
a. Pr ovi de mot or s, cont r ol l er s, i nt egr al di sconnect s, cont act or s, and cont r ol s wi t h t hei r r espect i ve pi eces of equi pment , except cont r ol l er s i ndi cat ed as par t of mot or cont r ol cent er s. Pr ovi de el ect r i cal equi pment , i ncl udi ng mot or s and wi r i ng, as speci f i ed i n Di v i s i on 26 Sect i on 26 20 00 " I nt er i or Di st r i but i on Syst em. " Pr ovi de manual or aut omat i c cont r ol and pr ot ect i ve or s i gnal devi ces r equi r ed f or t he oper at i on speci f i ed and cont r ol wi r i ng r equi r ed f or cont r ol s and devi ces speci f i ed, but not shown. For packaged equi pment , i ncl ude manuf act ur er pr ovi ded cont r ol l er s wi t h t he r equi r ed moni t or s and t i med restart.
b. For s i ngl e- phase mot or s, pr ovi de hi gh- ef f i c i ency t ype, f r act i onal - hor sepower al t er nat i ng- cur r ent mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em, t hat compl y wi t h t he r equi r ement s of NEMA MG 11.
I nt egr al s i ze mot or s shal l be t he pr emi um ef f i c i ency t ype compl i ant with NEMA MG 1.
c. For pol yphase mot or s, pr ovi de squi r r el - cage medi um i nduct i on mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em , and t hat meet t he ef f i c i ency r at i ngs f or pr emi um ef f i c i ency mot or s i n compl i ance wi t h NEMA MG 1. Sel ect pr emi um ef f i c i ency pol yphase mot or s i n compl i ance with NEMA MG 10.
d. Pr ovi de mot or s compl i ant wi t h NEMA MG 1 and of suf f i c i ent s i ze t o dr i ve t he l oad at t he speci f i ed capaci t y wi t hout exceedi ng t he namepl at e r at i ng of t he mot or . Pr ovi de mot or s r at ed f or cont i nuous dut y wi t h t he encl osur e speci f i ed. Pr ovi de mot or dut y t hat al l ows f or maxi mum f r equency st ar t - st op oper at i on and mi ni mum encount er ed i nt er val bet ween st ar t and st op. Pr ovi de mot or t or que capabl e of accel er at i ng t he connect ed l oad wi t hi n 20 seconds wi t h 80 per cent of t he r at ed vol t age mai nt ai ned at mot or t er mi nal s dur i ng one st ar t i ng per i od. Pr ovi de mot or st ar t er s compl et e wi t h t her mal over l oad pr ot ect i on and ot her necessar y appur t enances. Fi t mot or bear i ngs wi t h gr ease suppl y f i t t i ngs and gr ease r el i ef t o out s i de of t he encl osur e or use seal ed bearings.
e. Pr ovi de var i abl e f r equency dr i ves f or mot or s as speci f i ed i n Di v i s i on 26 Sect i on 26 29 23 " Var i abl e Fr equency Dr i ve Syst ems Under 600 Vol t s. "
2. 4 ANCHOR BOLTS
Pr ovi de anchor bol t s f or equi pment pl aced on concr et e equi pment pads or on concr et e s l abs. Bol t s t o be of t he s i ze and number r ecommended by t he equi pment manuf act ur er and l ocat ed by means of sui t abl e t empl at es.
I nst al l at i on of anchor bol t s shal l not degr ade t he sur r oundi ng concr et e.
2. 5 FI ELD- APPLI ED PAI NTI NG
Fi el d- appl i ed pai nt i ng shal l compl y wi t h equi pment manuf act ur er ' s st andar ds, unl ess speci f i ed ot her wi se. Per mi ssi on t o t ouch- up f act or y- appl i ed pai nt f i ni shes shal l be gr ant ed by t he Gover nment pr i or t o execut i on. Ot her wi se, equi pment shal l be r et ur ned t o t he f act or y f or re-finishing.
SECTI ON 23 00 00 Page 13
2. 6 I NDOOR AI R QUALI TY
Pr ovi de equi pment and component s t hat compl y wi t h t he r equi r ement s of ASHRAE 62. 1 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed her ei n.
2. 7 DUCT SYSTEMS
2. 7. 1 Met al Duct wor k
Pr ovi de met al duct wor k const r uct i on, i ncl udi ng al l f i t t i ngs and component s, t hat compl i es wi t h SMACNA 1966, HVAC Duct Const r uct i on St andar ds, as suppl ement ed and modi f i ed by t he f ol l owi ng:
a. Duct wor k shal l be const r uct ed meet i ng t he r equi r ement s f or t he duct syst em st at i c pr essur e speci f i ed i n Di v i s i on 23 Sect i on 23 05 93 " Test i ng, Adj ust i ng and Bal anci ng f or HVAC. "
b. Pr ovi de r adi us t ype el bows wi t h a cent er l i ne r adi us of 1. 5 t i mes t he wi dt h or di amet er of t he duct wher e space per mi t s. Ot her wi se, el bows havi ng a mi ni mum r adi us equal t o t he wi dt h or di amet er of t he duct or squar e el bows wi t h f act or y f abr i cat ed t ur ni ng vanes ar e al l owed.
c. Pr ovi de duct wor k t hat meet s t he r equi r ement s of Seal Cl ass A. Pr ovi de duct wor k i n VAV syst ems upst r eam of t he VAV boxes t hat meet s t he r equi r ement s of Seal Cl ass A.
d. Pr ovi de seal ant s t hat conf or m t o f i r e hazar d c l assi f i cat i on speci f i ed i n Di v i s i on 23 Sect i on 23 07 00 " Ther mal I nsul at i on f or Mechani cal Syst ems" and ar e sui t abl e f or t he r ange of ai r di s t r i but i on and ambi ent t emper at ur es t o whi ch i t i s exposed. Do not use pr essur e sensi t i ve t ape as a seal ant .
e. Make spi r al l ock seam duct , and f l at oval wi t h duct seal ant and l ock wi t h not l ess t han 3 equal l y spaced dr i ve scr ews or ot her appr oved met hods i ndi cat ed i n SMACNA 1966. Appl y t he seal ant t o t he exposed mal e par t of t he f i t t i ng col l ar so t hat t he seal er i s on t he i nsi de of t he j oi nt and f ul l y pr ot ect ed by t he met al of t he duct f i t t i ng. Appl y one br ush coat of t he seal ant over t he out s i de of t he j oi nt t o at l east 2 i nch band wi dt h cover i ng al l scr ew heads and j oi nt gap. Dent s i n t he mal e por t i on of t he s l i p f i t t i ng col l ar ar e not accept abl e. Fabr i cat e out door ai r i nt ake duct s and pl enums wi t h wat er t i ght sol der ed or br azed j oi nt s and seams.
f . See f ol l owi ng t abl e f or duct mat er i al :
DUCT SYSTEM
MATERIAL
G90 GALV. STEEL 316L STAI NLESS STEEL
SUPPLY X
RETURN X
OUTSI DE AI R X
SECTI ON 23 00 00 Page 14
NASA Goddard Space Flight Center Final Submission Instrument Development Facility December 8, 2016
DUCT SYSTEM
MATERIAL
G90 GALV. STEEL 316L STAINLESS STEEL
RELIEF AIR X
EXHAUST AIR X
EXCEPT AS SHOWN
AT RIGHT
X
FOR FUME HOODS AND
SNORKELS BRANCH DUCTS TO
MAIN EXHAUST DUCTS
2.7.1.1 Metallic Flexible Duct
a. Provide duct that complies with UL 181 and NFPA 90A, with factory applied insulation, vapor barrier, and end connections.
Provide duct assembly that does not exceed 25 for flame spread and 50 for smoke developed. Provide ducts designed for working pressures of 2 inches water gauge positive and 1.5 inches water gauge negative.
Provide flexible round duct length that does not exceed 5 feet. Secure connections by applying adhesive for 2 inches over rigid duct, apply flexible duct 2 inches over rigid duct, apply metal clamp, and provide minimum of three No. 8 sheet metal screws through clamp and rigid duct.
b. Inner duct core: Provide interlocking spiral or helically corrugated flexible core constructed of zinc coated steel, aluminum, or stainless steel; or constructed of inner liner of continuous galvanized spring steel wire helix fused to continuous, fire retardant, flexible vapor barrier film, inner duct core.
c. Insulation: Provide inner duct core that is insulated with mineral fiber blanket type flexible insulation, minimum thickness of 1 inch with minimum installed R Value of 4.2. Provide insulation covered on exterior with manufacturer's standard fire retardant vapor barrier jacket for flexible round duct.
2.7.1.1 Insulated Nonmetallic Flexible Duct Runouts
Use flexible duct runouts only where indicated. Runout length is indicated on the drawings, and is not to exceed 5 feet. Provide runouts that are preinsulated, factory fabricated, and that comply with NFPA 90A and UL 181 .
Provide either field or factory-applied vapor barrier. Provide not less than 20 ounce glass fabric duct connectors coated on both sides with neoprene. Where coil induction or high velocity units are supplied with vertical air inlets, use a streamlined, vaned and mitered elbow transition piece for connection to the flexible duct or hose. Provide a die stamped elbow and not a flexible connector as the last elbow to these units other than the vertical air inlet type. Insulated flexible connectors are allowed as runouts. Provide insulated material and vapor barrier that conform to the requirements of Division 23 Section 23 07 00 "Thermal Insulation for Mechanical Systems." Do not expose the insulation material surface to the air stream. Pressure class rating of flexible duct shall match pressure rating of duct system in which it is used.
SECTION 23 00 00 Page 15
2. 7. 1. 2 Gener al Ser vi ce Duct Connect or s
Pr ovi de a f l exi bl e duct connect or appr oxi mat el y 6 i nches i n wi dt h wher e sheet met al connect i ons ar e made t o f ans or wher e duct s of di ssi mi l ar met al s ar e connect ed. For r ound/ oval duct s, secur e t he f l exi bl e mat er i al by st ai nl ess st eel or z i nc- coat ed, i r on c l i nch- t ype dr aw bands. For r ect angul ar duct s, i nst al l t he f l exi bl e mat er i al l ocked t o met al col l ar s usi ng nor mal duct const r uct i on met hods. Pr ovi de a composi t e connect or syst em t hat compl i es wi t h NFPA 701 and i s c l assi f i ed as " f l ame- r et ar dant f abr i cs" i n UL Bl d Mat Di r .
2. 7. 1. 3 Al umi num Duct s
Compl y wi t h ASTM B209, Al l oy 3003- H14 f or al umi num sheet and Al l oy 6061- T6 or equi val ent st r engt h f or al umi num connect or s and bar st ock.
2. 7. 1. 4 Copper Sheet s
Compl y wi t h ASTM B152/ B152M, l i ght col d r ol l ed t emper .
2. 7. 1. 5 Cor r osi on Resi st i ng ( St ai nl ess) St eel Sheet s
Compl y wi t h ASTM A167.
2. 7. 2 Duct Access Door s
Pr ovi de hi nged access door s conf or mi ng t o SMACNA 1966 i n duct wor k and pl enums wher e i ndi cat ed and at al l ai r f l ow measur i ng pr i mar i es, aut omat i c damper s, f i r e damper s, coi l s , t her most at s, and ot her appar at us r equi r i ng ser vi ce and i nspect i on i n t he duct syst em. Pr ovi de access door s upst r eam and downst r eam of ai r f l ow measur i ng pr i mar i es and heat i ng and cool i ng coi l s. Duct access door s f or r ound, ai r - f oi l , and mul t i - bl ade st y l es of f i r e damper s shal l pr ovi de di r ect access t o t he j ackshaf t and f usi bl e l i nk wi t hout r eachi ng t hr ough t he bl ades. Pr ovi de door s t hat ar e a mi ni mum 15 by 18 i nches, unl ess ot her wi se shown. Wher e duct s i ze does not accommodat e t hi s s i ze door , make t he door s as l ar ge as pr act i cabl e. Equi p door s 24 by 24 i nches or l ar ger wi t h f ast ener s oper abl e f r om i nsi de and out s i de t he duct . Use i nsul at ed t ype door s i n i nsul at ed duct s.
2. 7. 3 Fi r e Damper s
Use 1. 5 hour r at ed st at i c f i r e damper s unl ess ot her wi se i ndi cat ed. Fi r e damper s and t hei r i nst al l at i on shal l compl y wi t h t he r equi r ement s of NFPA 80, NFPA 90A, UL 555, and t he manuf act ur er ' s i nst al l at i on i nst r uct i ons.
Pr ovi de f i r e damper s appr oved f or t he speci f i c appl i cat i on, and i nst al l accor di ng t o t hei r l i s t i ng. Associ at ed ai r handl er or exhaust uni t s shal l shut down upon act i vat i on of t ot al ar ea smoke det ect i on or duct smoke det ect i on syst ems. Equi p f i r e damper s wi t h a st eel s l eeve or adequat el y s i zed f r ame i nst al l ed i n such a manner t hat di sr upt i on of t he at t ached duct wor k, i f any, does not i mpai r t he oper at i on of t he damper . Pr ovi de br eak- away connect i ons t o t he at t achi ng duct wor k. I n met al st ud f r amed par t i t i ons, ensur e t hat t he wal l openi ngs have been pr oper l y f r amed i n compl i ance wi t h ASTM C754. Pr ovi de expansi on space cl ear ance ar ound al l f i r e damper s. Pr ovi de per i met er mount i ng/ r et ai ni ng angl es on bot h s i des of t he wal l or f l oor openi ng. I nst al l at i on of mount i ng/ r et ai ni ng angl es on one si de wi l l be accept ed wher e per mi t t ed by t he f i r e damper manuf act ur er .
Fast en t he per i met er mount i ng/ r et ai ni ng angl es t o t he damper s l eeve, and f or one- si ded angl e i nst al l at i ons al so f ast en t o t he wal l or f l oor as r equi r ed by t he manuf act ur er ' s i nst al l at i on i nst r uct i ons. St at i c f i r e
SECTI ON 23 00 00 Page 16 damper s shal l be cur t ai n t ype wi t h damper bl ades st or ed compl et el y out of t he ai r st r eam. Pr ovi de r ound f i r e damper s i n r ound duct . I nst al l damper s t hat do not r educe t he duct or t he ai r t r ansf er openi ng cr oss- sect i onal ar ea. I nst al l damper s so t hat t he cent er l i ne of t he damper dept h or t hi ckness i s l ocat ed i n t he cent er l i ne of t he wal l , par t i t i on or f l oor s l ab dept h or t hi ckness. Wher e necessar y t o pr ovi de unobst r uct ed access t o t he f i r e damper , out - of - wal l ( out - of - par t i t i on) f i r e damper s ar e per mi t t ed t o be i nst al l ed i n compl i ance wi t h t he manuf act ur er ' s i nst al l at i on i nst r uct i ons. Unl ess ot her wi se i ndi cat ed, compl y wi t h t he i nst al l at i on det ai l s gi ven i n SMACNA 1819 and i n manuf act ur er ' s i nst r uct i ons f or f i r e dampers.
2. 7. 4 Manual Bal anci ng Damper s
Fur ni sh manual bal anci ng damper s wi t h accessi bl e oper at i ng mechani sms. Use chr omi um pl at ed oper at or s ( wi t h al l exposed edges r ounded) i n f i ni shed por t i ons of t he bui l di ng. Pr ovi de manual vol ume cont r ol damper s t hat ar e oper at ed by l ocki ng- t ype quadr ant oper at or s. I nst al l damper s t hat ar e 2 gages heavi er t han t he duct i n whi ch i nst al l ed. Unl ess ot her wi se i ndi cat ed, pr ovi de opposed bl ade t ype mul t i - l eaf damper s wi t h maxi mum bl ade wi dt h of 12 i nches. Pr ovi de access door s or panel s f or al l conceal ed damper oper at or s and l ocki ng set scr ews. Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s not l ess t han t he t hi ckness of t he i nsul at i on when t he l ocki ng- t ype quadr ant oper at or s f or damper s ar e i nst al l ed on duct s t o be t her mal l y i nsul at ed, t o pr ovi de c l ear ance bet ween t he duct sur f ace and t he oper at or . St and- of f mount i ng i t ems shal l be i nt egr al wi t h t he oper at or or st andar d accessor y of t he damper manuf act ur er .
2. 7. 4. 1 Squar e or Rect angul ar Damper s
2. 7. 4. 1. 1 Duct Hei ght 12 i nches and Less
2. 7. 4. 1. 1. 1 Frames
Width Height Gal vani zed St eel Thickness
Length
Maxi mum 19 i nches Maxi mum 12 i nches Mi ni mum 20 gauge Mi ni mum 3 i nches
Mor e t han 19 i nches Maxi mum 12 i nches Mi ni mum 16 gauge Mi ni mum 3 i nches
2. 7. 4. 1. 1. 2 Si ngl e Leaf Bl ades
Width Height Gal vani zed St eel Thickness
Length
Maxi mum 19 i nches Maxi mum 12 i nches Mi ni mum 20 gauge Mi ni mum 3 i nches
Mor e t han 19 i nches Maxi mum 12 i nches Mi ni mum 16 gauge Mi ni mum 3 i nches
2. 7. 4. 1. 1. 3 Bl ade Axl es
To suppor t t he bl ades of r ound damper s, pr ovi de gal vani zed st eel shaf t s suppor t i ng t he bl ade t he ent i r e duct di amet er f r ame- t o- f r ame. Axl e shaf t s shal l ext end t hr ough st andof f br acket and hand quadr ant .
SECTI ON 23 00 00 Page 17
Width Height Material Squar e Shaf t
Maxi mum 19 i nches Maxi mum 12 i nches Gal vani zed St eel Mi ni mum 3/ 8 i nch
Mor e t han 19 i nches Maxi mum 12 i nches Gal vani zed St eel Mi ni mum 1/ 2 i nch
2. 7. 4. 1. 1. 4 Axl e Bear i ngs
Suppor t t he shaf t on each end at t he f r ames wi t h shaf t bear i ngs. Shaf t bear i ngs conf i gur at i on shal l be a pr essed f i t t o pr ovi de a t i ght j oi nt bet ween bl ade shaf t and damper f r ame.
Width Height Material
Maxi mum 19 i nches Maxi mum 12 i nches sol i d nyl on, or equi val ent sol i d pl ast i c, or oi l - i mpr egnat ed br onze
Mor e t han 19 i nches Maxi mum 12 i nches oi l - i mpr egnat ed br onze
2. 7. 4. 1. 1. 5 Cont r ol Shaf t / Hand Quadr ant
Pr ovi de damper s wi t h accessi bl e l ocki ng- t ype cont r ol shaf t / hand quadr ant operators.
Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s f or t he l ocki ng- t ype quadr ant oper at or s on damper s i nst al l ed on duct s t o be t her mal l y i nsul at ed. St and- of f di st ance shal l be a mi ni mum of 2 i nches of f t he met al duct sur f ace. St and- of f mount i ng i t ems shal l be i nt egr al wi t h t he oper at or or st andar d accessor y of t he damper manuf act ur er .
2. 7. 4. 1. 1. 6 Finish
Mi l l gal vani zed.
2. 7. 4. 1. 2 Duct Hei ght Gr eat er t han 12 i nches.
2. 7. 4. 1. 2. 1 Dampers
Pr ovi de damper s wi t h mul t i - l eaf opposed- t ype bl ades.
2. 7. 4. 1. 2. 2 Frames
Maxi mum 48 i nches i n hei ght ; maxi mum 48 i nches i n wi dt h; mi ni mum of 16 gauge gal vani zed st eel , mi ni mum of 5 i nches l ong.
2. 7. 4. 1. 2. 3 Blades
Mi ni mum of 16 gauge gal vani zed st eel ; 6 i nch nomi nal wi dt h.
SECTI ON 23 00 00 Page 18
2. 7. 4. 1. 2. 4 Bl ade Axl es
To suppor t t he bl ades of r ound damper s, pr ovi de gal vani zed squar e st eel shaf t s suppor t i ng t he bl ade t he ent i r e duct di amet er f r ame- t o- f r ame. Axl e shaf t s shal l ext end t hr ough st andof f br acket and hand quadr ant .
2. 7. 4. 1. 2. 5 Axl e Bear i ngs
Suppor t t he shaf t on each end at t he f r ames wi t h shaf t bear i ngs const r uct ed of oi l - i mpr egnat ed br onze, or sol i d nyl on, or a sol i d pl ast i c equi val ent t o nyl on. Shaf t bear i ngs conf i gur at i on shal l be a pr essed f i t t o pr ovi de a t i ght j oi nt bet ween bl ade shaf t and damper f r ame.
2. 7. 4. 1. 2. 6 Bl ade Act uat or
Mi ni mum 1/ 2 i nch di amet er gal vani zed st eel .
2. 7. 4. 1. 2. 7 Bl ade Act uat or Li nkage
Mi l l Gal vani zed st eel bar and cr ank pl at e wi t h st ai nl ess st eel pi vot s.
2. 7. 4. 1. 2. 8 Cont r ol Shaf t / Hand Quadr ant
Pr ovi de damper s wi t h accessi bl e l ocki ng- t ype cont r ol shaf t / hand quadr ant operators.
Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s f or t he l ocki ng- t ype quadr ant oper at or s on damper s i nst al l ed on duct s t o be t her mal l y i nsul at ed. St and- of f di st ance shal l be a mi ni mum of 2 i nches of f t he met al duct sur f ace. St and- of f mount i ng i t ems shal l be i nt egr al wi t h t he oper at or or st andar d accessor y of t he damper manuf act ur er .
2. 7. 4. 1. 2. 9 Finish
Mi l l gal vani zed.
2. 7. 4. 2 Round Damper s
2. 7. 4. 2. 1 Frames
Size Gal vani zed St eel Thi ckness Length
4 t o 20 i nches Mi ni mum 20 gauge Mi ni mum 6 i nches
22 t o 30 i nches Mi ni mum 20 gauge Mi ni mum 10 i nches
32 t o 40 i nches Mi ni mum 16 gauge Mi ni mum 10 i nches
SECTI ON 23 00 00 Page 19
2. 7. 4. 2. 2 Blades
Size Gal vani zed St eel Thi ckness
4 t o 20 i nches Mi ni mum 20 gauge
22 t o 30 i nches Mi ni mum 16 gauge
32 t o 40 i nches Mi ni mum 10 gauge
2. 7. 4. 2. 3 Bl ade Axl es
To suppor t t he bl ades of r ound damper s, pr ovi de gal vani zed st eel shaf t s suppor t i ng t he bl ade t he ent i r e duct di amet er f r ame- t o- f r ame. Axl e shaf t s shal l ext end t hr ough st andof f br acket and hand quadr ant .
Size Shaf t Si ze and Shape
4 t o 20 i nches Mi ni mum 3/ 8 i nch squar e
22 t o 30 i nches Mi ni mum 1/ 2 i nch squar e
32 t o 40 i nches Mi ni mum 3/ 4 i nch squar e
2. 7. 4. 2. 4 Axl e Bear i ngs
Suppor t t he shaf t on each end at t he f r ames wi t h shaf t bear i ngs const r uct ed of oi l - i mpr egnat ed br onze, or sol i d nyl on, or a sol i d pl ast i c equi val ent t o nyl on. Shaf t bear i ngs conf i gur at i on shal l be a pr essed f i t t o pr ovi de a t i ght j oi nt bet ween bl ade shaf t and damper f r ame.
Size Material
4 t o 20 i nches sol i d nyl on, or equi val ent sol i d pl ast i c, or oi l - i mpr egnat ed br onze
22 t o 30 i nches sol i d nyl on, or equi val ent sol i d pl ast i c, or oi l - i mpr egnat ed br onze
32 t o 40 i nches oi l - i mpr egnat ed br onze, or st ai nl ess st eel s l eeve bear i ng
2. 7. 4. 2. 5 Cont r ol Shaf t / Hand Quadr ant
Pr ovi de damper s wi t h accessi bl e l ocki ng- t ype cont r ol shaf t / hand quadr ant operators.
Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s f or t he l ocki ng- t ype quadr ant oper at or s on damper s i nst al l ed on duct s t o be t her mal l y i nsul at ed. St and- of f di st ance shal l be a mi ni mum of 2 i nches of f t he met al duct sur f ace. St and- of f mount i ng i t ems shal l be i nt egr al wi t h
SECTI ON 23 00 00 Page 20 t he oper at or or st andar d accessor y of t he damper manuf act ur er .
2. 7. 5 Aut omat i c Bal anci ng Damper s
Pr ovi de damper s as speci f i ed i n t he par agr aph ent i t l ed " Suppl ement al Component s/ Ser vi ces, " subpar agr aph " Cont r ol s. "
2. 7. 6 Combi nat i on Fi r e- Smoke Damper s and Aut omat i c Smoke Damper s
Combi nat i on f i r e smoke damper s and f i r e smoke damper i nst al l at i on shal l compl y wi t h NFPA 80 and UL 555 as a 90- mi nut e r at ed f i r e damper , and UL 555S and NFPA 105 as a smoke l eakage r at ed damper . Pr ovi de mul t i - bl ade t ype, 165 degr ee F f usi bl e l i nk f i r e damper ; f i r e- smoke damper assembl y shal l i ncl ude an el ect r i c damper oper at or . Smoke l eakage r at ed damper i nst al l at i on shal l compl y wi t h NFPA 105 and UL 555S. Smoke damper assembl y shal l i ncl ude an el ect r i c damper oper at or . Pr ovi de a UL 555S l eakage r at i ng t hat i s no hi gher t han Cl ass I I at an el evat ed t emper at ur e Cat egor y B ( 250 degr ees F f or 30 mi nut es) . Ensur e t hat pr essur e dr op i n t he damper open posi t i on does not exceed 0. 1 i nch wat er gauge wi t h aver age duct vel oci t i es of 2500 f pm. The el ect r i c act uat or shal l be ext er nal l y mount ed. The smoke- f i r e damper shal l be pr ovi ded wi t h an open- cl ose i ndi cat or wi r ed t o r emot e i ndi cat or l i ght s, and moni t or ed by t he bui l di ng f i r e al ar m syst em.
2. 7. 7 Ai r Suppl y and Exhaust Ai r Damper s
Wher e out door ai r suppl y and exhaust ai r damper s ar e r equi r ed t hey shal l have a maxi mum l eakage r at e when t est ed i n accor dance wi t h AMCA 500- D as r equi r ed by ASHRAE 90. 1 - I P, i ncl udi ng maxi mum Damper Leakage as f ol l ows:
a. The maxi mum damper l eakage at 1 i nch wat er gauge i s 10 cf m per squar e f oot and f or non- mot or i zed damper s i s 20 cf m per squar e f oot of damper area.
Damper s smal l er t han 24 i nches i n ei t her di r ect i on may have l eakage of 40 cf m per squar e f oot .
2. 7. 8 Doubl e Wal l Panel s f or Fi el d- Fabr i cat ed Pl enums
2. 7. 8. 1 Plenums
Fabr i cat e and er ect pl enums f or out s i de ai r and r el i ef ai r…