ATTACHMENT_1_NASA_IDF_FINAL_Specifications_Vol_2_COMPILED_-_final.pdf
PDF 4 MB Posted
- Attached to
- Construction of a Instrument Development Facility Federal contract opportunity
- Solicitation number
- NNG17607163R
About this file
ATTACHMENT 1 NASA IDF FINAL Specifications Vol 2 COMPILED
View the file
Other files for this federal contract opportunity
Show all 42
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NASA Goddard Space Flight Center Final Submission Instrument Development Facility December 8, 2016
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 23 00 ALTERNATES
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 35 34 PRODUCT OUTGASSING REQUIREMENTS FOR CLEANROOM CONSTRUCTION
01 35 43 ENVIRONMENTAL PROCEDURES
01 41 00 SPECIAL INSPECTIONS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00 QUALITY CONTROL
01 45 20 CONTRACTOR QUALITY CONTROL
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 50 13 GENERAL CLEAN ZONE CONSTRUCTION PROCEDURES
01 56 39 TEMPORARY TREE AND PLANT PROTECTION
01 58 00 PROJECT IDENTIFICATION
01 65 00 PRODUCT DELIVERY AND GOMAR TAGS
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 00 CONTRACT CLOSEOUT
01 78 23 OPERATION AND MAINTENANCE DATA
01 81 21 INDOOR AIR QUALITY MANAGEMENT (IAQ) DURING CONSTRUCTION
01 81 22 INDOOR AIR QUALITY PROTECTION BEFORE OCCUPANCY
01 86 12 RELIABILITY CENTERED ACCEPTANCE FOR MECHANICAL SYSTEMS
01 91 13 GENERAL COMMISSIONING REQUIREMENTS
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED STUD FRAMING
05 45 23 CHANNEL SUPPORT GRID SYSTEM (CSGS)
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
05 72 00 DECORATIVE METAL SPECIALTIES - BUILDING ID NUMBERS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 LAMINATE CLAD ARCHITECTURAL CASEWORK
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
PROJECT TABLE OF CONTENTS Page 1
07 11 13 BITUMINOUS DAMPPROOFING
07 17 00 BENTONITE WATERPROOFING
07 21 13 BOARD INSULATION
07 21 16 BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 18 SELF-ADHERING AIR BARRIER - VAPOR PERMEABLE
07 42 13 PREFORMED AND COMPOSITE METAL WALL PANELS
07 44 53 GLASS-FIBER-REINFORCED CONCRETE COLUMN COVERS (GFRC)
07 52 00 MODIFIED BITUMINOUS MEMBRANE ROOFING
07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING
07 60 00 FLASHING AND SHEET METAL
07 81 00 SPRAY-APPLIED FIREPROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS
08 14 00 WOOD DOORS
08 33 23 OVERHEAD COILING DOORS
08 41 13 INTERIOR ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 71 00 DOOR HARDWARE
08 71 13 AUTOMATIC SWINGING DOOR OPERATORS
08 81 00 GLAZING
08 84 14 RESIN PANELS (ER-1)
08 91 00 METAL LOUVERS
DIVISION 09 - FINISHES
09 06 90 FINISH LEGEND ALTERNATES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 13 CERAMIC TILING / PORCELAIN TILE (CT-1, CT-4, CT-5, CT-6,
CT-7)
09 51 00 ACOUSTICAL CEILINGS TYPES (ACT-1, ACT-2)
09 61 10 CONCRETE FLOOR TREATMENT (SC)
09 62 38 STATIC-CONTROL FLOORING TYPES - RUBBER (RS-2)
09 65 00 RESILIENT FLOORING TYPES - RUBBER SHEET (RS-1, RS-2),
LINOLEUM SHEET (RF-1, RF-2), AND RUBBER TREAD, RISER AND
LANDINGS (RT-1)
09 66 16 TERRAZZO FLOOR TILE (TT-2, TT-3)
09 67 23.13 RESINOUS FLOORING (RES-1)
09 83 13 WALL TREATMENT PANELS (AWP-1)
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 10 00 VISUAL COMMUNICATIONS SPECIALTIES TYPES - WALL PANEL
SYSTEM WITH BACKPAINTED WRITABLE/MAGNETIC GLASS (WG-01),
BACKPAINTED GLASS BACKSPLASH (WG-02), RAIL AND CABLE
DISPLAY SYSTEM
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 26 13 CORNER GUARDS (CG)
10 28 13 TOILET ACCESSORIES
PROJECT TABLE OF CONTENTS Page 2
10 44 16 FIRE EXTINGUISHERS (FE) AND CABINETS (FEC)
DIVISION 11 - EQUIPMENT
11 13 10 DOCK LEVELERS AND BUMPERS
11 52 00 AUDIO VISUAL EQUIPMENT
11 53 13 LABORATORY FUME HOOD AND EXHAUST DEVICES
11 53 33 LASER SAFETY EQUIPMENT
11 53 43 LABORATORY SERVICE FITTINGS AND FIXTURES
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES TYPES - MOTORIZED SOLAR SHADES
(WS-1, WS-2)
12 35 53 LABORATORY CASEWORK AND OTHER FURNISHINGS
12 36 65 ENGINEERED QUARTZ FABRICATIONS (QUARTZ COUNTERTOPS, SS-1)
12 48 13 ENTRANCE MATS (MAT-1)
12 93 00 SITE FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 60 13 CLEAN ZONE CONSTRUCTION REQUIREMENTS
13 60 16 CLEANROOM PROTOCOL AND CLEANING
13 60 19 CLEANROOM CERTIFICATION
13 61 19 CLEANROOM PASS-THROUGH (CPT)
13 62 13 CLEANROOM GASKETED T-GRID CEILING SYSTEMS (CRCS)
13 62 33 CLEANROOM FAN FILTER UNITS (FFU)
DIVISION 14 - CONVEYING EQUIPMENT
14 24 00 HOLELESS HYDRAULIC ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 00.00 40 FIRE-SUPPRESSION SPRINKLER SYSTEMS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 07 19.00 40 PLUMBING PIPING INSULATION
22 14 29.00 40 SUMP PUMPS
22 15 14.00 40 GENERAL SERVICE COMPRESSED-AIR SYSTEMS, LOW PRESSURE
22 63 13 SPECIALTY GAS SYSTEMS
22 63 21 LIQUID NITROGEN PIPING SYSTEM
22 63 80 HIGH PURITY STAINLESS STEEL PIPING SYSTEMS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 03 00 BASIC MECHANICAL MATERIALS AND METHODS
23 05 15 COMMON PIPING FOR HVAC
23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00 COMMISSIONING OF HVAC SYSTEMS
23 09 23 BACnet DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC
23 09 53 SPACE TEMPERATURE CONTROL SYSTEMS
23 21 13 LOW TEMPERATURE WATER (LTW) HEATING SYSTEM
PROJECT TABLE OF CONTENTS Page 3
23 22 13 STEAM TRAPS
23 22 23 STEAM CONDENSATE PUMPS
23 22 25 STEAM VALVES
23 22 26 STEAM SYSTEM AND TERMINAL UNITS
23 25 00 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS
23 64 26 CHILLED WATER PIPING SYSTEMS
23 84 23 CLEAN STEAM GENERATOR
DIVISION 26 - ELECTRICAL
26 00 00 BASIC ELECTRICAL MATERIALS AND METHODS
26 05 71 LOW VOLTAGE OVERCURRENT PROTECTIVE DEVICES
26 08 00 APPARATUS INSPECTION AND TESTING
26 09 23.00 40 LIGHTING CONTROL DEVICES
26 11 16 SECONDARY UNIT SUBSTATIONS
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 16 PANELBOARDS
26 28 01 COORDINATED POWER SYSTEM PROTECTION
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 33 53.00 20 UNINTERRUPTIBLE POWER SUPPLY (UPS)
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
26 60 13 LOW-VOLTAGE MOTORS
DIVISION 27 - COMMUNICATIONS
27 05 28.36 40 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 73 AIR ASPIRATING SMOKE DETECTION SYSTEMS
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARING AND GRUBBING
31 32 11 SOIL SURFACE EROSION CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 10 00 BITUMINOUS CONCRETE PAVEMENT
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
32 17 23.00 20 PAVEMENT MARKINGS
32 84 24 TEMPORARY IRRIGATION SPRINKLER SYSTEMS
32 92 19 SEEDING
32 93 00 EXTERIOR PLANTS
32 94 00 PLANTING ACCESSORIES
DIVISION 33 - UTILITIES
33 11 00 WATER DISTRIBUTION
33 30 00 SANITARY SEWERS
PROJECT TABLE OF CONTENTS Page 4
33 40 00 STORM DRAINAGE UTILITIES
33 46 16 SUBDRAINAGE SYSTEM
33 60 01 VALVES, PIPING, AND EQUIPMENT IN VALVE MANHOLES
33 61 00 UNDERGROUND CHILLED WATER DISTRIBUTION
33 63 13 UNDERGROUND STEAM DISTRIBUTION SYSTEM
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 5
SECTION 21 13 00.00 40
FIRE-SUPPRESSION SPRINKLER SYSTEMS
08/13
PART 1 GENERAL
1.1 RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
This Section includes performance requirements and other criteria for new wet pipe fire sprinkler and combination standpipe systems and associated alarms.
1.3 RELATED SECTIONS
Related Sections include the following:
a. Division 09 Section 09 90 00 "Paints and Coatings.
b. Division 23 Section 23 03 00 "Basic Mechanical Materials and Methods."
and Section 23 00 00 "Air Supply, Distribution, Ventilation, and Exhaust Systems".
c. Division 26 Section 26 20 00 "Interior Distribution System."
d. Division 28 Section 28 31 76 "Interior Fire Alarm and Mass Notification System."
e. Division 31 Section 31 00 00 "Earthwork." 6. Division 33 Section "Water Distribution."
1.4 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA C104/A21.4 (2013) Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water
AWWA C110/A21.10 (2012) Ductile-Iron and Gray-Iron Fittings for Water
AWWA C111/A21.11 (2012) Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
AWWA C151/A21.51 (2009) Ductile-Iron Pipe, Centrifugally Cast, for Water
SECTION 21 13 00.00 40 Page 1
ASME INTERNATIONAL (ASME)
ASME A112.18.1/CSA B125.1 (2012) Plumbing Supply Fittings
ASME B16.1 (2010) Gray Iron Pipe Flanges and Flanged Fittings Classes 25, 125, and 250
ASME B16.3 (2011) Malleable Iron Threaded Fittings, Classes 150 and 300
ASME B16.39 (2014) Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300
ASME B16.4 (2011) Standard for Gray Iron Threaded Fittings; Classes 125 and 250
ASME B16.9 (2012) Standard for Factory-Made Wrought Steel Buttwelding Fittings
ASME B31.1 (2014; INT 1-47) Power Piping
ASTM INTERNATIONAL (ASTM)
ASTM A126 (2004; R 2014) Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe Fittings
ASTM A135/A135M (2009; R2014) Standard Specification for Electric-Resistance-Welded Steel Pipe
ASTM A183 (2014) Standard Specification for Carbon Steel Track Bolts and Nuts
ASTM A197/A197M (2000; R 2011) Standard Specification for Cupola Malleable Iron
ASTM A234/A234M (2014) Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service
ASTM A307 (2014) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A563 (2007a; R2014) Standard Specification for Carbon and Alloy Steel Nuts
ASTM B370 (2012) Standard Specification for Copper Sheet and Strip for Building Construction
ASTM B749 (2014) Standard Specification for Lead and Lead Alloy Strip, Sheet and Plate Products
SECTION 21 13 00.00 40 Page 2
ASTM C1036 (2011e1) Standard Specification for Flat Glass
ASTM C592 (2013) Standard Specification for Mineral Fiber Blanket Insulation and Blanket-Type Pipe Insulation (Metal-Mesh Covered) (Industrial Type)
ASTM C920 (2014a) Standard Specification for Elastomeric Joint Sealants
ASTM D2000 (2012) Standard Classification System for Rubber Products in Automotive Applications
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
(FCCCHR)
FCCCHR List (continuously updated) List of Approved Backflow Prevention Assemblies
NATIONAL AERONAUTICS AND SPACE ADMINISTRATION (NASA)
RCBEA GUIDE (2004) NASA Reliability Centered Building and Equipment Acceptance Guide
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2015; ERTA 2015) Life Safety Code
NFPA 13 (2013) Standard for the Installation of Sprinkler Systems
NFPA 13E (2015) Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems
NFPA 14 (2013) Standard for the Installation of Standpipes and Hose Systems
NFPA 1963 (2014) Standard for Fire Hose Connections
NFPA 24 (2013) Standard for the Installation of Private Fire Service Mains and Their Appurtenances
NFPA 25 (2014) Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
NFPA 291 (2013) Recommended Practice for Fire Flow Testing and Marking of Hydrants
NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2
SECTION 21 13 00.00 40 Page 3
2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-C-18480 (1992; Rev B; Notice 2 2009) Coating Compound, Bituminous, Solvent, Coal-Tar Base
MIL-STD-101 (2014; Rev C) Color Code for Pipelines and for Compressed Gas Cylinders
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-595 (Rev C; Notice 1) Colors Used in Government Procurement
FS WW-P-421 (Rev D; Notice 1) Pipe, Cast, Gray and Ductile Iron, Pressure (For Water and Other Liquids)
UNDERWRITERS LABORATORIES (UL)
UL Fire Prot Dir (2012) Fire Protection Equipment Directory
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED NC (2009; R2014) Leadership in Energy and Environmental Design(tm) New Construction Rating System
1.5 SYSTEM DESCRIPTION
Furnish piping offsets, fittings, and any other accessories as required to provide a complete installation and to eliminate interference with other construction. Install sprinkler system over and under ducts, piping and platforms when such equipment can negatively affect or disrupt the sprinkler discharge pattern and coverage. Provide wet pipe sprinkler system in all areas of the building unless noted otherwise. Except as modified herein, the system shall be designed and installed in compliance with NFPA 13 . Each floor shall be provide with a separate floor control assembly, regardless of total system size. In-rack sprinklers shall comply with the requirements of NFPA 13 . Pipe sizes which are not indicated on the construction documents shall be determined by hydraulic calculation.
Design any portions of the sprinkler system that are not indicated on the drawings including locating sprinklers, piping and equipment, and size piping and equipment when this information is not indicated on the drawings or is not specified herein. The design of the sprinkler system shall be based on hydraulic calculations, and the other provisions specified herein.
1.5.1 Hydraulic Design
Hydraulically design the system based on hydraulic calculations in compliance with the Area/Density Method of NFPA 13 . Hazard occupancy
SECTION 21 13 00.00 40 Page 4 classification shall be as indicated in the drawings and in compliance with NASA-STD 8719.11A. Occupancies that are typically classified by NFPA 13 as Light Hazard shall be designed as Ordinary Hazard (Group 1) Occupancies at NASA GSFC. Occupancies that are typically classified by NFPA 13 as Ordinary Hazard (Group 1) shall be designed as Ordinary Hazard (Group 2) Occupancies at NASA GSFC. Selection of hazard class is subject to approval by the authority having jurisdiction (AHJ). Water velocity in the piping shall not exceed 20 ft/s.
1.5.1.1 Hose Demand
Hydraulic calculations shall include allowance for exterior hose streams in compliance with NFPA 13 in addition to the sprinkler system demand at the fire hydrant closest to the location of the fire department connection. An allowance for interior hose stations (but not Class I standpipe hose valves) shall also be added to the sprinkler system demand where present or indicated.
1.5.1.2 Basis for Calculations
The design of the system shall be based upon a water supply at the site location. The system demand pressure shall be below the water supply curve by 10 psi or 10 percent of the available pressure, whichever is greater.
Where there is a fire pump existing or to be provided as part of the project, the hydraulic calculations shall be based on the operation of the fire pump(s) at the site. Fire hydrant flow test data will be provided in the construction documents for information only. Unless waived by the Government, the installer shall perform a hydrant fire flow test in compliance with NFPA 291 for developing the water supply for the hydraulic calculations.
1.5.1.3 Water Supply Test
Hydrant flow tests shall be performed by qualified personnel under the guidance and oversight of a registered fire protection engineer (FPE). The flow test shall be performed in compliance with NFPA 291 . Proper equipment and procedures shall be used to prevent soil erosion and damage to landscaping. All discharge water shall be de-chlorinated. All equipment shall be listed for fire flow testing. All gauges shall be calibrated within the previous 12 months, bearing a dated calibration label. All gauges shall be minimum 4 inches in diameter, with an accuracy of at least 1/2 of 1 percent, and be liquid-filled.
Requests for GSFC site specific information (e.g., water main maps) shall be made to the Government. Prior to executing a flow test, submit a Flow Test Plan for review and approval by the Government that includes an equipment list, procedures, and the water main/test hydrants layout.
The test shall be coordinated with the NASA GSFC outside utilities lead in the Operations & Maintenance Division. After the test submit to the Government a completed, legible, Water Supply Test report signed by the supervising FPE and including a hydraulic graph of the results.
1.5.1.4 Hydraulic Calculations
Submit hydraulic calculations, including a drawing showing hydraulic reference points and pipe segments and as outlined in NFPA 13 , except that calculations shall be performed by computer using software intended specifically for fire protection system design using the design data shown
SECTION 21 13 00.00 40 Page 5 on the drawings. Software that uses k-factors for typical branch lines is not permitted. Calculations shall be based on the water supply data measured at the site (or on the contract drawings when permitted by the Government) to substantiate that the design area used in the calculations is the most demanding hydraulically. Water supply curves and system requirements shall be plotted on semi-logarithmic graph paper so as to present a summary of the complete hydraulic calculation. Provide a summary sheet listing sprinklers in the design area and their respective hydraulic reference points, elevations, actual discharge pressures and actual flows.
Elevations of hydraulic reference points (nodes) shall be indicated.
Documentation shall identify each pipe individually and the nodes connected thereto. Indicate the diameter, length, flow, velocity, friction loss, number and type of fittings, total friction loss in the pipe, equivalent pipe length, and Hazen-Williams coefficient for each pipe. For gridded systems, calculations shall show peaking of demand area friction loss to verify that the hydraulically most demanding area is being used.
Also for gridded systems, a flow diagram indicating the quantity and direction of flows shall be included. A drawing showing hydraulic reference points (nodes) and pipe designations used in the calculations shall be included and shall be independent of shop drawings.
1.5.2 Sprinkler Coverage
Sprinklers shall be uniformly spaced except where interrupted by walls and obstructions, and to coordinate with other devices and equipment on and in the ceiling. Sprinklers shall provide coverage throughout 100 percent of the building. This includes all occupied spaces and also non-occupied spaces such as but is not limited to telephone rooms, electrical equipment rooms, boiler rooms, switchgear rooms, transformer rooms, and other electrical and mechanical spaces. Coverage per sprinkler shall be in compliance with NFPA 13 . Exceptions are as follows:
a. Facilities that are designed in compliance with NFPA 13R and NFPA 13D.
b. Sprinklers may be omitted from enclosed non-combustible or limited-combustible shafts, concealed spaces incapable of containing flammable or combustible materials, storage and small rooms which are exempted by NFPA 101 based on occupancy, or specific spaces listed in
NFPA 13 .
1.6 STANDPIPE PERFORMANCE REQUIREMENTS
System design and installation shall be wet Class I standpipe system.
System shall be manual unless a fire pump has been provided, in which case it shall be automatic. All new systems s shall be combined with the building's fire sprinkler system where present. System design and installation shall comply with the required and advisory provisions of NFPA 14 except as modified herein. Standpipe system shall be designed by hydraulic calculations. Each system shall include materials, accessories, and equipment inside and outside the building necessary to provide each system complete and ready for use.
1.6.1 Regulatory Requirement
Devices and equipment shall be UL Fire Prot Dir listed or FM APP GUIDE approved for fire protection service. In the publications referred to herein, the advisory provisions shall be considered to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; reference to the "authority having jurisdiction" shall be
SECTION 21 13 00.00 40 Page 6 interpreted to mean the Chief of Occupational Safety and Health (OS+H) branch of NASA. The OS+H Fire Protection Engineer is an agent of the authority having jurisdiction (AHJ).
1.6.2 Residual Pressure
The minimum residual pressure at the outlet of the most remote 2 1/2 inchhose connection shall be 100 psig while the system is discharging at the required design flow rates.
1.6.3 Friction Losses
Friction losses in piping shall be calculated using the Hazen-Williams formula with 'C' value of 120 for steel piping, 150 for copper tubing, and 140 for cement-lined ductile-iron piping.
1.6.4 Water Supply
Hydraulic calculations shall be based on an assumed static pressure of 175 psi with 1000 gpm available at the fire department connection. This supply will be provided by the Prince George's County fire department's pumper truck. The Contractor shall conduct a hydrant test to confirm that the available public water supply for shop drawing development.
1.7 ADMINISTRATIVE REQUIREMENTS
Conduct a survey of the work area. Submit a record of existing conditions showing the results of the survey of work area conditions and features of existing structures and facilities within and adjacent to the jobsite.
Commencement of work constitutes acceptance of existing conditions.
1.8 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Division 01 Section 01 33 00 "Submittal Procedures":
SD-02 Shop Drawings
Installation Drawings; G
Pipe Hangers and Supports; G
Fire-Department Connections; G
Fire Alarm System; G
Sprinkler Heads; G
Valves; G
SD-03 Product Data
Underground Piping Materials; G
Aboveground Piping Materials; G
SECTION 21 13 00.00 40 Page 7
Valves; G
Fire-Department Connections; G
Riser Alarm Equipment; G
Standpipe Equipment and Fire Hose Valve Cabinets; G
Sprinkler Heads; G
Materials; G
Pipe Hangers and Supports; G
Equipment and Performance Data; G
SD-05 Design Data
Design Analysis and Calculations; G
SD-06 Test Reports
Pressure Tests; G
System Operating Tests; G
1.9 PREDICTIVE TESTING AND INSPECTION TECHNOLOGY REQUIREMENTS
This section contains systems and/or equipment components regulated by NASA's Reliability Centered Building and Equipment Acceptance Program.
This program requires the use of Predictive Testing and Inspection (PT&I) technologies in conformance with RCBEA GUIDE to ensure building equipment and systems installed by the Contractor have been installed properly and contain no identifiable defects that shorten the design life of a system and/or its components. Satisfactory completion of all acceptance requirements is required to obtain Government approval and acceptance of the work.
Perform PT&I tests and provide submittals as specified in Part 1 article titled "SUBMITTALS" SD-06 per NFPA 13 AND NFPA 25 .
1.10 QUALITY ASSURANCE
1.10.1 Installer Qualifications
Engage the services of a qualified installer. Installer shall be a competent person with a minimum of 10 years' experience in the installation of fire extinguishing standpipe systems similar to to the type required by this Contract, and shall have experience completing 5 projects similar in size and scope.
Submit installer qualifications documenting compliance with the requirements of this Section. Include the names and locations of at least 2 successfully completed installations; indicate the type and design of each system and certify that the system has performed satisfactorily for a period of at least 18 months.
SECTION 21 13 00.00 40 Page 8
1.10.2 System Technician Qualifications
Engage the services of a qualified system technician to prepare the shop drawings required by this Section. System technician shall be certified by the National Institute for Certification in Engineering Technologies (NICET), and possess a Level III Certification in the the Automatic Sprinkler System program.
Submit system technician qualifications documenting compliance with the requirements of this Section. Include copies of the system technician's certifications for Government's records.
1.10.3 Shop Drawing Requirement
Submit installation drawings for review and approval. Drawings shall comply with the requirements of NFPA 14 for "Plans and Specifications," and shall be stamped and signed by a registered Fire Protection Engineer.
Drawings shall be drawn to scale, but not less than 1/8 inch equals 1 foot; sheet size shall measure 34 inches by 22 inches. Drawings shall show sufficient detail to ensure the proper installation of each system, but minimally include the following:
a. Room, space or area layout and include pipe supports and hangers.
b. Field wiring diagrams showing locations of devices and points of connection and terminals used for all electrical field connections in the system, with wiring color code scheme.
c. Plan views, elevations, and sections of the systems supply and piping.
d. Show piping schematic of systems supply, devices, valves, pipe, and fittings.
Work shall not commence until shop drawings have been approved.
1.10.4 As-Built Drawing Requirement
Submit as-built drawings of each system upon completion of the Work and prior to final acceptance by the Government. Drawings shall comply with the requirements of Division 01 Section 01 33 00 "Submittal Procedures" and shall be stamped and signed by a registered Fire Protection Engineer.
1.11 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in the manufacturer's original packaging with manufacturer and supplier's labeling clearly visible.
Protect substations and components from damage. Store materials in an enclosed area, free from contact with soil and weather. Where necessary to store materials outside, store them off the ground and employ all means necessary to protect the materials from damage.
Storage area shall be easily accessible for inspection. Damaged items shall be replaced with new when directed by the Government.
SECTION 21 13 00.00 40 Page 9
1.12 SUSTAINABLE DESIGN REQUIREMENTS
1.12.1 Final Sustainability Notebook Submittal
Refer to Section 01 33 29 SUSTAINABILITY REPORTING for federal sustainability product and documentation requirements.
1.12.2 LEED Documentation Notebook
Refer to Section 01 33 29 SUSTAINABILITY REPORTING for LEED NC prerequisites and credits required to be earned for this project (refer to LEED scorecard attached to 01 33 29 SUSTAINABILITY REPORTING for those credits and required points in those credits). Refer to the LEED NC v2009 reference guide and additional online guidance at www.usgbc.org for documentation requirements.
PART 2 PRODUCTS
Provide design analysis and calculations in accordance with NFPA 13 and
NFPA 14 .
Submit connection diagrams indicating the relations and connections of the following items. Indicate on drawings, the general physical layout of all controls, and internal tubing and wiring details.
2.1 SYSTEM DESCRIPTION
Ensure fire-protection system materials and equipment provided under this section conform to the requirements of Underwriters Laboratories (UL) or the Factory Mutual ( FM APP GUIDE).
Products with UL label or seal or listing in UL 6 , and products with FM label or listed in the FM APP GUIDE are acceptable fire-protection system materials and equipment.
Submit equipment and performance data for fire protection sprinkler systems consisting of information on use life, system functional flows, safety features, and mechanical automated details.
2.2 EQUIPMENT
2.2.1 Underground Piping Materials
Provide ells, tees, reducing tees, wyes, couplings, increasers, crosses, transitions, and end caps of the same type and class of material as the pipe or have equal or superior physical and chemical properties.
2.2.1.1 Type Cast Iron Water Pipe
Provide mechanical joint or push-on cast-iron waterpipe, centrifugally cast, UL listed and labeled, conforming to FS WW-P-421 and, as applicable, to AWWA C151/A21.51 , AWWA C110/A21.10 , AWWA C111/A21.11 . Use Class 150 piping. Ensure bell-and-spigot fittings conform to AWWA C110/A21.10 .
For FS WW-P-421 wall-thickness criteria only, depth of cover is 5 feet unless drawings indicate less, in which case, drawing requirements apply.
Field-laying conditions are B (flat-bottom trench, without blocks, tamped backfill).
SECTION 21 13 00.00 40 Page 10
Flanged cast-iron pipe fittings are Class 125 conforming to ASME B16.1 .
Coat pipe and fittings on the outside with a bituminous sealer in accordance with AWWA C104/A21.4 .
Coat pipe and fittings on the inside with a mortar lining in accordance with AWWA C104/A21.4 .
Restraining joints against endwise separation due to internal pressure may be accomplished by a NFPA-recommended metal harness consisting of clamping devices and bolting or by hardened-metal retainers molded into a push-on gasket and engaged by a groove in the spigot end.
Where electrical continuity is indicated, supply the pipe with factory-brazed heavy cross section copper connectors to be joined with copper fasteners upon joint assembly. Connectors, as a minimum, are equal to No. 1/0.
2.2.1.2 Type Ductile Iron Water Pipe
Provide mechanical-joint or push-on type ductile-iron water pipe, centrifugally cast, UL listed and labeled, conforming to applicable provisions of AWWA C111/A21.11 , and AWWA C151/A21.51 . Wall-thickness criteria is 200-pounds per square inch (psi) working pressure plus 100-psi surge allowance, AASHTO H-20 loading with specified trench conditions.
Ensure the gasket elastomer is chloroprene.
Coat pipe on the inside and outside with a bituminous sealer in accordance with AWWA C104/A21.4 .
Coat pipe and fittings on the inside with a mortar lining in accordance with AWWA C104/A21.4 .
Restraining joints against endwise separation due to internal pressure may be accomplished by using a metal harness consisting of clamping devices and bolting or by hardened-metal retainers molded into a pushon gasket and engaged by a groove in the spigot end.
Where electrical continuity is indicated, supply the pipe with factory-brazed heavy cross section copper connectors to be joined with copper fasteners upon joint assembly. Connectors, at a minimum, are equal to No. 1/0.
2.2.2 Aboveground Piping Materials
2.2.2.1 Type BCS - Black Carbon Steel
Pipe 1/8 through 1-1/2 inches: Schedule 40 furnace butt weld black-carbon steel conforming to ASTM A53/A53M, or ASTM A135/A135M , Type F furnace butt welded; Schedule 10 conforming to ASTM A135/A135M , Grade B.
Pipe 2 through 8 inches, where indicated: Schedule 40 seamless or electric-resistance welded black carbon steel, conforming to ASTM A53/A53M or ASTM A135/A135M , Type E (electric-resistance welded), Grade B, or Type S (seamless), Grade B; Schedule 10 conforming to ASTM A135/A135M , Grade B.
Pipe 10 inches and over: Schedule 30 black carbon steel conforming to ASTM A53/A53M, Type E (electric-resistance welded) or Type S (seamless).
SECTION 21 13 00.00 40 Page 11
Unions 2 inches and under): 300-pound per square inch gage (psig) working steam pressure (wsp) female, screwed, black malleable iron, with ground joint and brass-to-iron seat conforming to ASME B16.39 .
Standard pipe couplings: Extra-heavy screwed black steel.
Grooved pipe couplings (all sizes): 175-psig minimum working pressure with a housing fabricated in two or more parts of black malleable-iron castings. Provide coupling gasket molded of synthetic rubber, conforming to requirements of ASTM D2000. Provide coupling bolts that are oval-neck, track-head type with heavy hexagonal nuts, conforming to ASTM A183.
Fittings 4 inches and under: 175-psig working pressure, cast iron, screwed, conforming to ASTM A126, Class A, and ASME B16.4 .
Fittings 6 inches and larger: 175-psig working pressure, cast iron, conforming to ASTM A126, Class A, screwed, conforming to ASME B16.4 , or flanged, conforming to ASME B16.1 .
Fittings 8 inches and under: Provide rolled-groove. Provide rolled only grooves for rolled-groove type; cut grooving is not allowed. Ensure rolled grooves are dimensionally compatible with the couplings.
Grooved fittings (all sizes): ensure 175-psig working pressure fittings used with grooved couplings are fabricated of black malleable-iron castings. If a manufacturer's standard-size malleable-iron fitting pattern is not available, use fabricated fittings. Fabricate fittings from Grade B seamless-steel pipe and long-radius seamless welding fittings, with wall thickness to match pipe, conforming to ASTM A234/A234M and ASME B16.9 .
2.2.2.2 Type GCS - Galvanized Carbon Steel
Pipe 1/2 through 10 inches and where indicated): Schedule 40 seamless or electric resistant welded galvanized steel conforming to ASTM A53/A53M, Type E electric-resistance welded or Type S seamless. Type F (furnace butt welded continuous welded) is acceptable for sizes less than 2 inches.
Fittings (all sizes): 150-psig working pressure banded, galvanized, malleable, screwed, conforming to ASTM A197/A197M and ASME B16.3 .
Fittings 2-1/2 inches and over): 125-psig working pressure cast-iron flanges and flanged fittings conforming to ASTM A126, Class A and to
ASME B16.1 .
Grooved pipe couplings (all sizes): 175-psig minimum working pressure with a housing fabricated in two or more parts of galvanized malleable-iron castings. Provide coupling gasket molded of synthetic rubber, conforming to requirements of ASTM D2000. Ensure coupling bolts are oval-neck, track-head type with heavy hexagonal nuts, conforming to
ASTM A183.
Grooved fittings (all sizes): ensure 175-psig working pressure fittings used with grooved couplings are fabricated of galvanized malleable-iron castings. If a manufacturer's standard-size malleable-iron fitting pattern is not available, use fabricated fittings. Fabricate fittings from Grade B seamless steel pipe and long-radius seamless welding fittings, with wall thickness to match pipe, conforming to ASTM A234/A234M and ASME B16.9 .
SECTION 21 13 00.00 40 Page 12
Unions 2 inches and under: 300-psig working pressure female, screwed, galvanized malleable iron, with brass-to-seat and ground joint.
2.2.3 Pipe Hangers and Supports
Comply with NFPA 13 .
2.2.4 Fire-Department Connections
Ensure hose connections have National Firehose standard-thread form and rocker lugs in accordance with NFPA 1963 . Ensure hose-connection sizes and threads are compatible with the equipment used by the fire department serving the facility.
2.2.4.1 Wall Siamese
Provide cast brass or bronze flush-mounted escutcheon-plate units, with three 2-1/2-inch, fire-department, swivel, female inlets; triple-clapper valves; rocker-lug caps and chains; and cast-in function-identifying lettering. Provide a unit with a chrome-plated or polished surface finish. Ensure chrome plate is in accordance with
ASME A112.18.1/CSA B125.1 .
2.2.4.2 Fire Hydrants
Provide dry-barrel type hydrants, with low-profile and modern appearance.
Design hydrants to remain closed if hydrant barrel is sheared or damaged.
Select hydrants that have two 2-1/2-inch, hose outlets and one 4-1/2-inch hose outlet complete with non-binding caps and cap chains. Ensure hydrant direction of opening is counterclockwise. Ensure surface is filled, primed, and finished with a multiple-coat high-gloss weather-resistant enamel. All surfaces below grade receive a coating of bitumen not less than 20 mils thick. Exercise care not to plug barrel drainage provisions. Ensure hydrant color is standard for the project site.
2.2.5 Riser Alarm Equipment
Ensure riser alarm equipment is UL listed or FM approved for fire-protection use.
2.2.5.1 Wet-Pipe Alarm Check Valve
Provide wet-pipe alarm check valve, complete with standard accessories and trim necessary to give an alarm and includes pressure gages, retard chamber, testing provisions, and all necessary intercomponent piping, fittings, and valves. Ensure pilot valve and clapper have individual elastomer seats.
2.2.5.2 Standard Check Valve
Provide FM-approved or UL-listed standard swing-check valves with elastomer-disc seat. Provide pressure gages on both sides of the clapper. Water-flow alarm is a vane type.
2.2.5.3 Water-Flow Alarm Device
Ensure water-flow alarm devices are UL listed for the particular type of system.
SECTION 21 13 00.00 40 Page 13
a. Vane-Type Flow Alarm
1. Ensure the vane-type flow alarm makes or breaks an alarm circuit upon deflection by a volume of flowing water that equals or exceeds the capacity of a single sprinkler. Ensure alarm has an instant-recycle pneumatic-retard time delay.
2.2.6 Standpipe Equipment and Fire Hose Valve Cabinets
2.2.6.1 Standpipe Valve
Provide a 2-1/2-inch angle hose valve, 175-psi rated, with 2-1/2-inch female to 1-1/2-inch male reducer, 1-1/2-inch cap and chain, and chrome-plated polished brass.
In multistory buildings with fire pumps, include a valve orifice plate to restrict discharge pressure to 65 psig.
2.2.6.2 Fire Valve and Extinguisher Cabinet
Cabinets shall be recess-mounted type; provide where indicated on the construction documents. Cabinets shall be fabricated from cold-rolled, process-leveled, furniture grade steel; minimum 20 gauge steel for the cabinet, and minimum 18 gauge steel for the door and trim. Joints shall be fully welded and ground smooth. Cabinet design shall accommodate reinforced anchorage points for securing cabinets to adjacent construction.
Doors shall be fully glazed, equipped with a continuous hinge, latch, and pull. Hinge door for 180 degree opening. Glazing shall comply with ASTM C1036, Type II (wired), Class 1 (clear), Form 1 (wired, polished both sides), Quality q8 (general purpose), diamond or square wire mesh, 1/4 inch thick.
Cabinet finish shall be factory-applied, both inside and out, with one coat of enamel applied over a primer. Interior finish color shall be white; exterior finish color shall be stainless steel. Provide fire-resistance rated cabinets where located in fire-resistance rated construction.
Fit the door with full size 1/4-inch thick safety or tempered glass and dual friction latches.
Size cabinet to accommodate the valve, and either one 2-1/2-gallon air-pressurized water fire extinguisher or one 15-pound carbon-dioxide extinguisher. Extinguisher will be furnished by the Government.
2.2.7 Sprinkler Heads
2.2.7.1 Head Types
Use standard 1/2-inch orifice sprinkler heads. Heads are automatic on-off type. Install on-off type heads only in wet-pipe systems.
Ensure heads in finished areas below suspended ceilings are flush chrome-plated brass. Provide escutcheon plate of baked enamel finished to match ceiling.
Furnish flush or pendant heads in finished areas below suspended ceiling.
SECTION 21 13 00.00 40 Page 14
Ensure heads and escutcheon plates are chrome-plated brass.
Ensure heads in unfinished areas below suspended ceilings are pendant type. Heads in all other locations are upright type.
Ensure corrosion-resistant heads are lead-coated.
2.2.7.2 Temperature Rating
Fusible links are for ordinary hazard, except where otherwise indicated.
2.2.7.3 Spares
Furnish spares for each type of sprinkler head, complete with appropriate storage cabinet and wrench.
2.2.7.4 Head Protection
Protect heads with paper or plastic bags during painting operations.
Remove protection immediately upon finishing painting operations.
Provide head guards wherever mechanical damage could occur. Guard finish is red enamel.
2.2.8 Valves
2.2.8.1 Post Indicator Valve Assembly (PIV)
Assembly consists of a standard FM-approved or UL-listed inside-screw gate valve with an above-grade post indicator or a completely factory-assembled FM-approved quarter-turn valve and above-grade post indicator-operator.
Direction to open is counterclockwise.
Quarter-turn valve is a wafer-type butterfly valve, rated at175 psi, elastomer-lined and sealed. Ensure the liner acts as a gasket between ASME B16.1 , Class 125 or Class 250 flanges. Ensure post has a fail-safe feature to keep valve intact in case of breaking off above grade. Provide a worm-gear operator with permanently oil-lubricated watertight gear case complete with handle.
Apply a coating of bitumen not less than 20 mils thick on surfaces below grade. Fill, prime and finish above grade surfaces with a multiple coat of high-gloss, weather-resistant, red enamel.
Fit post indicator valves to accommodate electrical supervisory switches.
Provide electrical supervisory switches for interconnection to the building fire alarm system. Ensure switches and connections meet the requirements of Section 28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION.
2.2.8.2 Fire-Hydrant Service Valves
Provide fire-hydrant service valves that are standard FM-approved or UL-listed inside-screw gate valve, with valve box connection flange.
2.2.8.3 Valve Boxes
Install valve boxes with not less than 3/16-inch thick cast-iron construction with locking cover that has a cast-in identification legend.
SECTION 21 13 00.00 40 Page 15
Select adjustable extension type boxes with screw- or slide-type adjustment. Fit the base flange to the valve flange. Ensure the full extended length of box is greater than required by depth of cover by not less than 4 inches. Supply one valve-operating wrench for each size valve nut. Provide guide rings where operating rods are longer than 6 feet.
2.2.8.4 Aboveground Valves
Ensure gate, globe, and check valves (all sizes) are FM approved or UL listed.
Ensure ball valves, 2 inches and under, are FM approved, rated 300 psi, with provisions to wire or lock handle in place where critical alarm function may be isolated.
Ensure butterfly valves, 6-, 8-, and 10-inch are FM approved, rated 175 psi, cast-iron bodied wafer type, with elastomer liners and seals. Ensure liners act as a gasket between standard piping-system flanges. Provide a worm-gear operator, with permanently lubricated gears, and oiltight and watertight case, complete with handle and automatic position indication.
2.2.9 Painting
Furnish equipment of the manufacturer's standard product with the manufacturer's standard finish coat.
Furnish other mechanical equipment with a shop-applied prime paint.
2.2.10 Waterflow Test Connections
Test connections shall be located approximately 6 feet above the floor for each standpipe system or portion thereof equipped with an alarm device;
locate downstream and adjacent to each alarm actuating device.
Discharge from the test connection shall be to the exterior of the building, shall be readily visible, and shall not cause property damage. Discharge to a janitor's utility sink or similar fixtures on the interior of the building shall not be permitted.
Provide discharge orifice equivalent to 1/2 inch sprinkler orifice. The penetration of the exterior wall shall be no greater than 2 feet above finished grade. Discharge onto sidewalks used for stair access or egress shall not be allowed. Provide splash blocks immediately beneath discharges.
2.2.11 Main Drains
Provide drain piping as indicated on the construction documents.
2.2.11.1 Backflow Preventer
Provide detector double check valve assembly backflow preventer with OS&Y gate valve on both ends. Each check valve shall have a drain. Backflow prevention assemblies shall have current "Certificate of Approval" from the Foundation for Cross-Connection Control and Hydraulic Research, FCCCHR List . Listing of the specific make, model, design, and size in the FCCCHR List shall be acceptable as the required documentation.
SECTION 21 13 00.00 40 Page 16
2.3 MATERIALS
2.3.1 Bituminous Coating
Bituminous coating is a solvent cutback, heavy-bodied material to produce not less than a 12-mil dry-film thickness in one coat and is as recommended by the conduit manufacturer for compatibility with factory coating and rubber joints.
For previously coal-tar-coated and for uncoated ferrous surfaces underground, ensure the bituminous coating is a solvent cutback coal-tar type, conforming to MIL-C-18480 .
2.3.2 Bolting
Ensure flange and general-purpose bolting is hex-head and conforms to ASTM A307, Grade B. Ensure heavy hex-nuts conform to ASTM A563.
Square-head bolts and nuts are not acceptable.
2.3.3 Elastomer Caulk
Use two component polysulfide- or polyurethane-base elastomer-caulking material, conforming to ASTM C920.
2.3.4 Escutcheons
Manufacture escutcheons from nonferrous metals. Use chrome-plated escutcheons, except when AISI 300 series corrosion-resistant steel is provided. Ensure metals and finish conform to ASME A112.18.1/CSA B125.1 .
Provide one piece escutcheons where mounted on chrome-plated pipe or tubing and one-piece or split-pattern type elsewhere. Provide escutcheons consisting of internal spring tension devices or setscrews to maintain a fixed position against a surface.
2.3.5 Flashing
2.3.5.1 Lead
Ensure sheet lead conforms to ASTM B749, and weighs not less than 4 pounds per square foot.
2.3.5.2 Copper
Ensure sheet copper conforms to ASTM B370 and weighs not less than 16 ounces per square foot.
2.3.6 Flange Gaskets
Ensure gaskets are suitable for the intended use and contain no asbestos.
2.3.7 Pipe-Thread Compounds
Use tetrafluoroethylene tape or other suitable compounds.
SECTION 21 13 00.00 40 Page 17
PART 3 EXECUTION
3.1 PREPARATION
3.1.1 Painting
If manufacturer's standard-finish equipment surfaces are damaged during construction, bring to as-new condition by touchup or repainting to the satisfaction of the Contracting Officer, or replaced with new undamaged equipment at no additional cost to the Government.
Thoroughly clean and paint hangers, supports, and other iron work in concealed spaces with one coat of primer paint.
Apply two coats of enamel paint to all firex piping, valves, and appurtenances, excluding siamese connections. Use paint color No. 11105 (red) in accordance with MIL-STD-101 and FED-STD-595 .
3.2 INSTALLATION
Ensure installation of system materials and equipment is in accordance with the recommendations and provisions of NFPA 13 , NFPA 13E, NFPA 14 , and NFPA 24 . Perform work in the presence of the Contracting Officer. Notify the Contracting Officer 48 hours in advance of the start of work.
Perform all installation work by licensed fire protection sprinkler contractors, licensed for such work in the state where the work is to be performed.
3.2.1 Underground Piping Installation
Ensure installation of piping materials conforms to the written or published instructions of the manufacturer.
For pipes passing through walls below grade and ground-floor slab, insert the pipe through pipe sleeves one size larger than pipe. Caulk the pipe sleeve watertight with lead and oakum or mechanically expandable chloroprene inserts with bitumen sealed metal components.
In fill areas, ensure the pipe passing under or through building grade beams has a minimum clearance of 4 inches in all directions.
For rubber- or elastomer-jointed piping embedded in concrete walls, install a joint within 6 inches of the face of the wall capable of absorbing movement without leakage.
Use extended-joint or flange-bolt pipe when penetrating earth or concrete grade to a height 6 inches above the grade.
Support underground piping below supported or suspended slabs from the slab with a minimum of two supports per length of pipe. Protect supports with a coating of bitumen.
On excavations near and below building footings, use the backfilling material consisting of 2,000-psi cured-strength concrete, poured or pressure-grouted up to the level of the footing.
After piping has been inspected, and not less than 48 hours prior to being lowered into a trench, coat external surfaces of the piping, valves, valve
SECTION 21 13 00.00 40 Page 18 operators, and valve boxes with a compatible bituminous coating suitable for protection against brackish ground water. Apply coating in accordance with the manufacturer's instructions to a dry-film thickness of not less than 12 mils.
3.2.1.1 Ductile Iron Pipe Construction Tolerances
Ensure maximum deviation from design elevation at any point along piping does not exceed 2-1/2 inches for all sizes of piping.
Maximum deviation from line at the end of an 18-foot length of piping is 2-1/2 inches and cumulatively does not exceed 6 inches. Make corrections from line within preceding tolerances at a rate not to exceed 2-1/2 inches for any one length of piping.
Ensure maximum deflection for curves for 18-foot lengths of cast ferrous pipe is in accordance with NFPA 24 .
When the alignment requires deflections in excess of the above limitations, furnish special bends or a sufficient number of shorter lengths of pipe to provide angular deflections within established limits, as approved.
3.2.1.2 Fire Hydrants
Set hydrant outlet elevations between 24 inches, minimum, to 36 inches, maximum, above grade. Face the 4-1/2-inch outlet toward the road or area of access.
3.2.1.3 Valve Boxes
Set valve and valve boxes plumb. Center valve boxes on the valves. Where feasible, locate valves outside traffic areas. Carefully tamp soil around each valve box to a distance of 4 feet on all sides of the box or to the undisturbed trench face when less than 4 feet.
Install Class 3000A concrete slabs 2 feet square by 4 inches thick to protect valve boxes, unless other protection is…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .