ATTACHMENT 5 - PRICE LIST AND SCOPE OF WORK
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Base Year
| BASE YEAR - PRICE LIST AND SCOPE OF WORK | ||||
| DESCRIPTION | POP CALENDAR DAYS | LEASED FACILITY PRICE | PENTAGON PRICE | |
| Item No. | I. Main Entry Zone Packages: | |||
| I.1.30 | Item I.1.30 (Main Entry-Expedited): Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 30 days | |||
| I.1.60 | Item I.1.60 (Main Entry-Standard) Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 60 days | |||
| I.2.30 | ISSC Item I.2.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.2.60 | ISSC Item I.2.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.3.30 | ISSC Item I.3.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.3.60 | ISSC Item I.3.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.4.30 | ISSC Item I.4.30 (Main Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| I.4.60 | ISSC Item I.4.60 (Main Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| I.5.30 | ISSC Item I.5.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.5.60 | ISSC Item I.5.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.6.30 | ISSC Item I.6.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.6.60 | ISSC Item I.6.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.7.30 | ISSC Item I.7.30 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.7.60 | ISSC Item I.7.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.8.30 | ISSC Item I.8.30 (Main Entry): HID FIPS 201 Reader-ACS IDS-NO lock or panel | |||
| I.8.60 | ISSC Item I.8.60 (Main Entry): HID FIPS 201 Reader-No Panel-ACSIDS- No Lock | |||
| II. Secondary Zone Packages: | ||||
| II.1.30 | ISSC Item II.1.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.1.60 | ISSC Item II.1.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.2.30 | ISSC Item II.2.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.2.60 | ISSC Item II.2.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.3.30 | ISSC Item II.3.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.3.60 | ISSC Item II.3.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| II.4.30 | ISSC Item II.4.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.4.60 | ISSC Item II.4.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.5.30 | ISSC Item II.5.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.5.60 | ISSC Item II.5.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.6.30 | ISSC Item II.6.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.6.60 | ISSC Item II.6.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_No Lock | |||
| III. Access Control Only Packages: | ||||
| III.1.30 | ISSC Item III.1.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.1.60 | ISSC Item III.1.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.2.30 | ISSC Item III.2.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.2.60 | ISSC Item III.2.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.3.30 | ISSC Item III.3.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ No Lock | |||
| III.3.60 | ISSC Item III.3.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_No Lock | |||
| III.4.30 | ISSC Item III.4.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ES | |||
| III.4.60 | ISSC Item III.4.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_ES | |||
| III.5.30 | ISSC Item III.5.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.5.60 | ISSC Item III.5.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.6.30 | ISSC Item III.6.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ No Lock | |||
| III.6.60 | ISSC Item III.6.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_No Lock | |||
| IV. Egress Door: | ||||
| IV.1.30 | ISSC Item IV.1.30 (Egress Door)- Expedited | |||
| IV.1.60 | ISSC Item IV.1.60 (Egress Door) - Standard | |||
| DRS-OPR-65-05 | ||||
| V. Additional Devices: | ||||
| These devices below are strictly for adding to packages, I‐III above. | ||||
| V.1.30 | ISSC Item V.1.30 (Additional PIR) - Expedited | |||
| V.1.60 | ISSC Item V.1.60 (Additional PIR) - Standard | |||
| V.2.30 | ISSC Item V.2.30 (Additional Duress) - Expedited | |||
| V.2.60 | ISSC Item V.2.60 (Additional Duress) - Standard | |||
| V.3.30 | ISSC Item V.3.30 (Additional IDRS) - Expedited | |||
| V.3.60 | ISSC Item V.3.60 (Additional IDRS) - Standard | |||
| V.4.30 | ISSC Item V.4.30 (Additional IDRS Button) - Expedited | |||
| V.4.60 | ISSC Item V.4.60 (Additional IDRS Button) - Standard | |||
| V.5.30 | ISSC Item V.5.30 (Additional IDRS Piezo) - Expedited | |||
| V.5.60 | ISSC Item V.5.60 (Additional IDRS Piezo) - Standard | |||
| V.6.30 | ISSC Item V.6.30 (Additional Mortise lock) - Expedited | |||
| V.6.60 | ISSC Item V.6.60 (Additional Mortise lock) - Standard | |||
| V.7.30 | ISSC Item V.7.30 (Additional BMS) - Expedited | |||
| V.7.60 | ISSC Item V.7.60 (Additional BMS) - Standard | |||
| V.8.30 | ISSC Item V.8.30 (Additional Glass Break) - Expedited | |||
| V.8.60 | ISSC Item V.8.60 (Additional Glass Break) - Standard | |||
| V.9.30 | ISSC Item V.9.30 (Additional Aiphone Door Video Unit) - Expedited | |||
| V.9.60 | ISSC Item V.9.60 (Additional Aiphone Door Video Unit) - Standard | |||
| V.10.30 | ISSC Item V.10.30 (Additional Aiphone Sub - Desk Unit) - Expedited | |||
| V.10.60 | ISSC Item V.10.60 (Additional Aiphone Sub - Desk Unit) - Standard | |||
| V.11.30 | ISSC Item V.11.30 (Additional M2100 DCU & IO Boards) | |||
| V.12.30 | ISSC Item V.12.30 (Additional M2150 DC & IO Boards) | |||
| VI. AMAG M2100 /M2150 Alarm Control Panel Accessories: | ||||
| VI.1.30 | ISSC Item VI.1.30 (Additional M2100 DCU & IO Boards to Existing Panel) | |||
| VI.2.30 | ISSC Item VI.2.30 (Additional M2150 DC & IO Boards) - Expedited | |||
| DRS-OPR-65-05 | ||||
| VII. New Installation of Devices to existing panels: | ||||
| VII.1.30 | ISSC Item VII.1.30 (New Individual PIR) - Expedited | |||
| VII.1.60 | ISSC Item VII.1.60 (New Individual PIR) - Standard | |||
| VII.2.30 | ISSC Item VII.2.30 (New Individual BMS) - Expedited | |||
| VII.2.60 | ISSC Item VII.2.60 (New Individual BMS) – Standard | |||
| VII.3.30 | ISSC Item VII.3.30 (New Individual Glass Break) - Expedited | |||
| VII.3.60 | ISSC Item VII.3.60 (New Individual Glass Break) - Standard | |||
| VII.4.30 | ISSC Item VII.4.30 (New Electric Strike) - Expedited | |||
| VII.4.60 | ISSC Item VII.4.60 (New Electric Strike) - Standard | |||
| VII.5.35 | ISSC Item VII.5.35 (New Duress Button) | |||
| VII.6.35 | ISSC Item VII.6.35 (New IDRS) | |||
| VII.7.35 | ISSC Item VII.7.35 (New IDRS Button) | |||
| VII.8.35 | ISSC Item VII.8.35 (New IDRS Piezo) | |||
| VII.9.30 | ISSC Item VII.9.30 (Aiphone Door Video System w/ Desk Master Unit) - Expedited | |||
| VII.9.60 | ISSC Item VII.9.60 (Aiphone Door Video System w/ Desk Master Unit) - Standard | |||
| VII.10.30 | ISSC Item VII.10.30 (New Aiphone Door Video Unit to Existing System) - Expedited | |||
| VII.10.60 | ISSC Item VII.10.60 (New Aiphone Door Video Unit to Existing System) - Standard | |||
| VII.11.30 | ISSC Item VII.11.30 (Additional Aiphone Sub Desk Unit to Existing System)-Expedited | |||
| VII.11.60 | ISSC Item VII.11.60 (Additional Aiphone Sub Desk Unit to Existing System) - Standard | |||
| VII.12.30 | ISSC Item VII.12.30 New Door Box Device Rough In) | |||
| VIII. Miscellaneous Items | ||||
| VIII.1.30 | ISSC Item VIII.1.30 (Decommissioning One Zone or Subzone) Removal of all Equipment from zone | |||
| VIII.2.30 | ISSC Item VIII.2.30 (Relocate One IDRS Button) | |||
| IX. Permits | ||||
| IX.1.30 | ISSC Item IX.1.30 (Building Permit) 1st Floor with the first door locking device | |||
| DRS-OPR-65-05 | ||||
| IX.2.30 | ISSC Item IX.2.30 (Building and Low Voltage Permit) 1st Floor, First Door Locking Device, 1st group of 4-devices, & wiring. | |||
| IX.3.30 | ISSC Item IX.3.30 (Low Voltage Permit) 1st group of 4-devices & wiring. | |||
| IX.4.30 | ISSC Item IX.4.30 (Low Voltage Permit-Each Additional 4-Devices over base permit) 4-devices & wiring. | |||
| IX.5.30 | ISSC Item IX.5.30 (Building Permit-Each Additional Locking Door) $69.75 | |||
| TOTAL | ||||
| Multiply the total by 10 for evaluation purposes. | x10 | x10 | ||
| Subtotal | ||||
| Add $2 Million for non-priced items | $ 2,000,000.00 | $ 2,000,000.00 | ||
| Grand Total | ||||
| Note 1: The Price List will be reviewed annually before the option is exercised and revised as necessary by mutual agreement. | ||||
| Note 2: Additional Devices and New Installation of Devices shall be compatible with the existing AMAG systems. | ||||
| GOVERNMENT PROVIDED ITEMS | ||||
| 2. The Government will provide necessary power and connectivity that will be installed within three feet of the devices that is represented in the system requirements matrix. | ||||
| 3. If a magnetic lock is requested the Government will provide an independent fire alarm dry contact relay within three feet of the AMAG alarm control panel. | ||||
| 4. All door hardware, doors, and frames will be provided by the Government. | ||||
| 5. The Government will provide necessary AMAG servers and software as the current limitation is 64 panels/nodes per communications client server. |
Option Year 1
| OPTION YEAR 1 - PRICE LIST AND SCOPE OF WORK | ||||
| DESCRIPTION | POP CALENDAR DAYS | LEASED FACILITY PRICE | PENTAGON PRICE | |
| Item No. | I. Main Entry Zone Packages: | |||
| I.1.30 | Item I.1.30 (Main Entry-Expedited): Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 30 days | |||
| I.1.60 | Item I.1.60 (Main Entry-Standard) Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 60 days | |||
| I.2.30 | ISSC Item I.2.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.2.60 | ISSC Item I.2.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.3.30 | ISSC Item I.3.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.3.60 | ISSC Item I.3.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.4.30 | ISSC Item I.4.30 (Main Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| I.4.60 | ISSC Item I.4.60 (Main Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| I.5.30 | ISSC Item I.5.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.5.60 | ISSC Item I.5.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.6.30 | ISSC Item I.6.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.6.60 | ISSC Item I.6.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.7.30 | ISSC Item I.7.30 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.7.60 | ISSC Item I.7.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.8.30 | ISSC Item I.8.30 (Main Entry): HID FIPS 201 Reader-ACS IDS-NO lock or panel | |||
| I.8.60 | ISSC Item I.8.60 (Main Entry): HID FIPS 201 Reader-No Panel-ACSIDS- No Lock | |||
| II. Secondary Zone Packages: | ||||
| II.1.30 | ISSC Item II.1.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.1.60 | ISSC Item II.1.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.2.30 | ISSC Item II.2.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.2.60 | ISSC Item II.2.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.3.30 | ISSC Item II.3.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.3.60 | ISSC Item II.3.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| II.4.30 | ISSC Item II.4.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.4.60 | ISSC Item II.4.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.5.30 | ISSC Item II.5.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.5.60 | ISSC Item II.5.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.6.30 | ISSC Item II.6.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.6.60 | ISSC Item II.6.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_No Lock | |||
| III. Access Control Only Packages: | ||||
| III.1.30 | ISSC Item III.1.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.1.60 | ISSC Item III.1.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.2.30 | ISSC Item III.2.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.2.60 | ISSC Item III.2.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.3.30 | ISSC Item III.3.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ No Lock | |||
| III.3.60 | ISSC Item III.3.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_No Lock | |||
| III.4.30 | ISSC Item III.4.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ES | |||
| III.4.60 | ISSC Item III.4.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_ES | |||
| III.5.30 | ISSC Item III.5.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.5.60 | ISSC Item III.5.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.6.30 | ISSC Item III.6.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ No Lock | |||
| III.6.60 | ISSC Item III.6.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_No Lock | |||
| IV. Egress Door: | ||||
| IV.1.30 | ISSC Item IV.1.30 (Egress Door)- Expedited | |||
| IV.1.60 | ISSC Item IV.1.60 (Egress Door) - Standard | |||
| DRS-OPR-65-05 | ||||
| V. Additional Devices: | ||||
| These devices below are strictly for adding to packages, I‐III above. | ||||
| V.1.30 | ISSC Item V.1.30 (Additional PIR) - Expedited | |||
| V.1.60 | ISSC Item V.1.60 (Additional PIR) - Standard | |||
| V.2.30 | ISSC Item V.2.30 (Additional Duress) - Expedited | |||
| V.2.60 | ISSC Item V.2.60 (Additional Duress) - Standard | |||
| V.3.30 | ISSC Item V.3.30 (Additional IDRS) - Expedited | |||
| V.3.60 | ISSC Item V.3.60 (Additional IDRS) - Standard | |||
| V.4.30 | ISSC Item V.4.30 (Additional IDRS Button) - Expedited | |||
| V.4.60 | ISSC Item V.4.60 (Additional IDRS Button) - Standard | |||
| V.5.30 | ISSC Item V.5.30 (Additional IDRS Piezo) - Expedited | |||
| V.5.60 | ISSC Item V.5.60 (Additional IDRS Piezo) - Standard | |||
| V.6.30 | ISSC Item V.6.30 (Additional Mortise lock) - Expedited | |||
| V.6.60 | ISSC Item V.6.60 (Additional Mortise lock) - Standard | |||
| V.7.30 | ISSC Item V.7.30 (Additional BMS) - Expedited | |||
| V.7.60 | ISSC Item V.7.60 (Additional BMS) - Standard | |||
| V.8.30 | ISSC Item V.8.30 (Additional Glass Break) - Expedited | |||
| V.8.60 | ISSC Item V.8.60 (Additional Glass Break) - Standard | |||
| V.9.30 | ISSC Item V.9.30 (Additional Aiphone Door Video Unit) - Expedited | |||
| V.9.60 | ISSC Item V.9.60 (Additional Aiphone Door Video Unit) - Standard | |||
| V.10.30 | ISSC Item V.10.30 (Additional Aiphone Sub - Desk Unit) - Expedited | |||
| V.10.60 | ISSC Item V.10.60 (Additional Aiphone Sub - Desk Unit) - Standard | |||
| V.11.30 | ISSC Item V.11.30 (Additional M2100 DCU & IO Boards) | |||
| V.12.30 | ISSC Item V.12.30 (Additional M2150 DC & IO Boards) | |||
| VI. AMAG M2100 /M2150 Alarm Control Panel Accessories: | ||||
| VI.1.30 | ISSC Item VI.1.30 (Additional M2100 DCU & IO Boards to Existing Panel) | |||
| VI.2.30 | ISSC Item VI.2.30 (Additional M2150 DC & IO Boards) - Expedited | |||
| DRS-OPR-65-05 | ||||
| VII. New Installation of Devices to existing panels: | ||||
| VII.1.30 | ISSC Item VII.1.30 (New Individual PIR) - Expedited | |||
| VII.1.60 | ISSC Item VII.1.60 (New Individual PIR) - Standard | |||
| VII.2.30 | ISSC Item VII.2.30 (New Individual BMS) - Expedited | |||
| VII.2.60 | ISSC Item VII.2.60 (New Individual BMS) – Standard | |||
| VII.3.30 | ISSC Item VII.3.30 (New Individual Glass Break) - Expedited | |||
| VII.3.60 | ISSC Item VII.3.60 (New Individual Glass Break) - Standard | |||
| VII.4.30 | ISSC Item VII.4.30 (New Electric Strike) - Expedited | |||
| VII.4.60 | ISSC Item VII.4.60 (New Electric Strike) - Standard | |||
| VII.5.35 | ISSC Item VII.5.35 (New Duress Button) | |||
| VII.6.35 | ISSC Item VII.6.35 (New IDRS) | |||
| VII.7.35 | ISSC Item VII.7.35 (New IDRS Button) | |||
| VII.8.35 | ISSC Item VII.8.35 (New IDRS Piezo) | |||
| VII.9.30 | ISSC Item VII.9.30 (Aiphone Door Video System w/ Desk Master Unit) - Expedited | |||
| VII.9.60 | ISSC Item VII.9.60 (Aiphone Door Video System w/ Desk Master Unit) - Standard | |||
| VII.10.30 | ISSC Item VII.10.30 (New Aiphone Door Video Unit to Existing System) - Expedited | |||
| VII.10.60 | ISSC Item VII.10.60 (New Aiphone Door Video Unit to Existing System) - Standard | |||
| VII.11.30 | ISSC Item VII.11.30 (Additional Aiphone Sub Desk Unit to Existing System)-Expedited | |||
| VII.11.60 | ISSC Item VII.11.60 (Additional Aiphone Sub Desk Unit to Existing System) - Standard | |||
| VII.12.30 | ISSC Item VII.12.30 New Door Box Device Rough In) | |||
| VIII. Miscellaneous Items | ||||
| VIII.1.30 | ISSC Item VIII.1.30 (Decommissioning One Zone or Subzone) Removal of all Equipment from zone | |||
| VIII.2.30 | ISSC Item VIII.2.30 (Relocate One IDRS Button) | |||
| IX. Permits | ||||
| IX.1.30 | ISSC Item IX.1.30 (Building Permit) 1st Floor with the first door locking device | |||
| DRS-OPR-65-05 | ||||
| IX.2.30 | ISSC Item IX.2.30 (Building and Low Voltage Permit) 1st Floor, First Door Locking Device, 1st group of 4-devices, & wiring. | |||
| IX.3.30 | ISSC Item IX.3.30 (Low Voltage Permit) 1st group of 4-devices & wiring. | |||
| IX.4.30 | ISSC Item IX.4.30 (Low Voltage Permit-Each Additional 4-Devices over base permit) 4-devices & wiring. | |||
| IX.5.30 | ISSC Item IX.5.30 (Building Permit-Each Additional Locking Door) $69.75 | |||
| TOTAL | ||||
| Multiply the total by 10 for evaluation purposes. | x10 | x10 | ||
| Subtotal | ||||
| Add $2 Million for non-priced items | $ 2,000,000.00 | $ 2,000,000.00 | ||
| Grand Total | ||||
| Note 1: The Price List will be reviewed annually before the option is exercised and revised as necessary by mutual agreement. | ||||
| Note 2: Additional Devices and New Installation of Devices shall be compatible with the existing AMAG systems. | ||||
| GOVERNMENT PROVIDED ITEMS | ||||
| 2. The Government will provide necessary power and connectivity that will be installed within three feet of the devices that is represented in the system requirements matrix. | ||||
| 3. If a magnetic lock is requested the Government will provide an independent fire alarm dry contact relay within three feet of the AMAG alarm control panel. | ||||
| 4. All door hardware, doors, and frames will be provided by the Government. | ||||
| 5. The Government will provide necessary AMAG servers and software as the current limitation is 64 panels/nodes per communications client server. |
Option Year 2
| OPTION YEAR 2 - PRICE LIST AND SCOPE OF WORK | ||||
| DESCRIPTION | POP CALENDAR DAYS | LEASED FACILITY PRICE | PENTAGON PRICE | |
| Item No. | I. Main Entry Zone Packages: | |||
| I.1.30 | Item I.1.30 (Main Entry-Expedited): Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 30 days | |||
| I.1.60 | Item I.1.60 (Main Entry-Standard) Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 60 days | |||
| I.2.30 | ISSC Item I.2.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.2.60 | ISSC Item I.2.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.3.30 | ISSC Item I.3.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.3.60 | ISSC Item I.3.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.4.30 | ISSC Item I.4.30 (Main Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| I.4.60 | ISSC Item I.4.60 (Main Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| I.5.30 | ISSC Item I.5.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.5.60 | ISSC Item I.5.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.6.30 | ISSC Item I.6.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.6.60 | ISSC Item I.6.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.7.30 | ISSC Item I.7.30 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.7.60 | ISSC Item I.7.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.8.30 | ISSC Item I.8.30 (Main Entry): HID FIPS 201 Reader-ACS IDS-NO lock or panel | |||
| I.8.60 | ISSC Item I.8.60 (Main Entry): HID FIPS 201 Reader-No Panel-ACSIDS- No Lock | |||
| II. Secondary Zone Packages: | ||||
| II.1.30 | ISSC Item II.1.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.1.60 | ISSC Item II.1.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.2.30 | ISSC Item II.2.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.2.60 | ISSC Item II.2.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.3.30 | ISSC Item II.3.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.3.60 | ISSC Item II.3.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| II.4.30 | ISSC Item II.4.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.4.60 | ISSC Item II.4.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.5.30 | ISSC Item II.5.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.5.60 | ISSC Item II.5.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.6.30 | ISSC Item II.6.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.6.60 | ISSC Item II.6.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_No Lock | |||
| III. Access Control Only Packages: | ||||
| III.1.30 | ISSC Item III.1.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.1.60 | ISSC Item III.1.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.2.30 | ISSC Item III.2.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.2.60 | ISSC Item III.2.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.3.30 | ISSC Item III.3.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ No Lock | |||
| III.3.60 | ISSC Item III.3.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_No Lock | |||
| III.4.30 | ISSC Item III.4.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ES | |||
| III.4.60 | ISSC Item III.4.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_ES | |||
| III.5.30 | ISSC Item III.5.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.5.60 | ISSC Item III.5.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.6.30 | ISSC Item III.6.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ No Lock | |||
| III.6.60 | ISSC Item III.6.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_No Lock | |||
| IV. Egress Door: | ||||
| IV.1.30 | ISSC Item IV.1.30 (Egress Door)- Expedited | |||
| IV.1.60 | ISSC Item IV.1.60 (Egress Door) - Standard | |||
| DRS-OPR-65-05 | ||||
| V. Additional Devices: | ||||
| These devices below are strictly for adding to packages, I‐III above. | ||||
| V.1.30 | ISSC Item V.1.30 (Additional PIR) - Expedited | |||
| V.1.60 | ISSC Item V.1.60 (Additional PIR) - Standard | |||
| V.2.30 | ISSC Item V.2.30 (Additional Duress) - Expedited | |||
| V.2.60 | ISSC Item V.2.60 (Additional Duress) - Standard | |||
| V.3.30 | ISSC Item V.3.30 (Additional IDRS) - Expedited | |||
| V.3.60 | ISSC Item V.3.60 (Additional IDRS) - Standard | |||
| V.4.30 | ISSC Item V.4.30 (Additional IDRS Button) - Expedited | |||
| V.4.60 | ISSC Item V.4.60 (Additional IDRS Button) - Standard | |||
| V.5.30 | ISSC Item V.5.30 (Additional IDRS Piezo) - Expedited | |||
| V.5.60 | ISSC Item V.5.60 (Additional IDRS Piezo) - Standard | |||
| V.6.30 | ISSC Item V.6.30 (Additional Mortise lock) - Expedited | |||
| V.6.60 | ISSC Item V.6.60 (Additional Mortise lock) - Standard | |||
| V.7.30 | ISSC Item V.7.30 (Additional BMS) - Expedited | |||
| V.7.60 | ISSC Item V.7.60 (Additional BMS) - Standard | |||
| V.8.30 | ISSC Item V.8.30 (Additional Glass Break) - Expedited | |||
| V.8.60 | ISSC Item V.8.60 (Additional Glass Break) - Standard | |||
| V.9.30 | ISSC Item V.9.30 (Additional Aiphone Door Video Unit) - Expedited | |||
| V.9.60 | ISSC Item V.9.60 (Additional Aiphone Door Video Unit) - Standard | |||
| V.10.30 | ISSC Item V.10.30 (Additional Aiphone Sub - Desk Unit) - Expedited | |||
| V.10.60 | ISSC Item V.10.60 (Additional Aiphone Sub - Desk Unit) - Standard | |||
| V.11.30 | ISSC Item V.11.30 (Additional M2100 DCU & IO Boards) | |||
| V.12.30 | ISSC Item V.12.30 (Additional M2150 DC & IO Boards) | |||
| VI. AMAG M2100 /M2150 Alarm Control Panel Accessories: | ||||
| VI.1.30 | ISSC Item VI.1.30 (Additional M2100 DCU & IO Boards to Existing Panel) | |||
| VI.2.30 | ISSC Item VI.2.30 (Additional M2150 DC & IO Boards) - Expedited | |||
| DRS-OPR-65-05 | ||||
| VII. New Installation of Devices to existing panels: | ||||
| VII.1.30 | ISSC Item VII.1.30 (New Individual PIR) - Expedited | |||
| VII.1.60 | ISSC Item VII.1.60 (New Individual PIR) - Standard | |||
| VII.2.30 | ISSC Item VII.2.30 (New Individual BMS) - Expedited | |||
| VII.2.60 | ISSC Item VII.2.60 (New Individual BMS) – Standard | |||
| VII.3.30 | ISSC Item VII.3.30 (New Individual Glass Break) - Expedited | |||
| VII.3.60 | ISSC Item VII.3.60 (New Individual Glass Break) - Standard | |||
| VII.4.30 | ISSC Item VII.4.30 (New Electric Strike) - Expedited | |||
| VII.4.60 | ISSC Item VII.4.60 (New Electric Strike) - Standard | |||
| VII.5.35 | ISSC Item VII.5.35 (New Duress Button) | |||
| VII.6.35 | ISSC Item VII.6.35 (New IDRS) | |||
| VII.7.35 | ISSC Item VII.7.35 (New IDRS Button) | |||
| VII.8.35 | ISSC Item VII.8.35 (New IDRS Piezo) | |||
| VII.9.30 | ISSC Item VII.9.30 (Aiphone Door Video System w/ Desk Master Unit) - Expedited | |||
| VII.9.60 | ISSC Item VII.9.60 (Aiphone Door Video System w/ Desk Master Unit) - Standard | |||
| VII.10.30 | ISSC Item VII.10.30 (New Aiphone Door Video Unit to Existing System) - Expedited | |||
| VII.10.60 | ISSC Item VII.10.60 (New Aiphone Door Video Unit to Existing System) - Standard | |||
| VII.11.30 | ISSC Item VII.11.30 (Additional Aiphone Sub Desk Unit to Existing System)-Expedited | |||
| VII.11.60 | ISSC Item VII.11.60 (Additional Aiphone Sub Desk Unit to Existing System) - Standard | |||
| VII.12.30 | ISSC Item VII.12.30 New Door Box Device Rough In) | |||
| VIII. Miscellaneous Items | ||||
| VIII.1.30 | ISSC Item VIII.1.30 (Decommissioning One Zone or Subzone) Removal of all Equipment from zone | |||
| VIII.2.30 | ISSC Item VIII.2.30 (Relocate One IDRS Button) | |||
| IX. Permits | ||||
| IX.1.30 | ISSC Item IX.1.30 (Building Permit) 1st Floor with the first door locking device | |||
| DRS-OPR-65-05 | ||||
| IX.2.30 | ISSC Item IX.2.30 (Building and Low Voltage Permit) 1st Floor, First Door Locking Device, 1st group of 4-devices, & wiring. | |||
| IX.3.30 | ISSC Item IX.3.30 (Low Voltage Permit) 1st group of 4-devices & wiring. | |||
| IX.4.30 | ISSC Item IX.4.30 (Low Voltage Permit-Each Additional 4-Devices over base permit) 4-devices & wiring. | |||
| IX.5.30 | ISSC Item IX.5.30 (Building Permit-Each Additional Locking Door) $69.75 | |||
| TOTAL | ||||
| Multiply the total by 10 for evaluation purposes. | x10 | x10 | ||
| Subtotal | ||||
| Add $2 Million for non-priced items | $ 2,000,000.00 | $ 2,000,000.00 | ||
| Grand Total | ||||
| Note 1: The Price List will be reviewed annually before the option is exercised and revised as necessary by mutual agreement. | ||||
| Note 2: Additional Devices and New Installation of Devices shall be compatible with the existing AMAG systems. | ||||
| GOVERNMENT PROVIDED ITEMS | ||||
| 2. The Government will provide necessary power and connectivity that will be installed within three feet of the devices that is represented in the system requirements matrix. | ||||
| 3. If a magnetic lock is requested the Government will provide an independent fire alarm dry contact relay within three feet of the AMAG alarm control panel. | ||||
| 4. All door hardware, doors, and frames will be provided by the Government. | ||||
| 5. The Government will provide necessary AMAG servers and software as the current limitation is 64 panels/nodes per communications client server. |
Option Year 3
| OPTION YEAR 3 - PRICE LIST AND SCOPE OF WORK | ||||
| DESCRIPTION | POP CALENDAR DAYS | LEASED FACILITY PRICE | PENTAGON PRICE | |
| Item No. | I. Main Entry Zone Packages: | |||
| I.1.30 | Item I.1.30 (Main Entry-Expedited): Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 30 days | |||
| I.1.60 | Item I.1.60 (Main Entry-Standard) Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 60 days | |||
| I.2.30 | ISSC Item I.2.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.2.60 | ISSC Item I.2.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.3.30 | ISSC Item I.3.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.3.60 | ISSC Item I.3.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.4.30 | ISSC Item I.4.30 (Main Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| I.4.60 | ISSC Item I.4.60 (Main Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| I.5.30 | ISSC Item I.5.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.5.60 | ISSC Item I.5.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.6.30 | ISSC Item I.6.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.6.60 | ISSC Item I.6.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.7.30 | ISSC Item I.7.30 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.7.60 | ISSC Item I.7.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.8.30 | ISSC Item I.8.30 (Main Entry): HID FIPS 201 Reader-ACS IDS-NO lock or panel | |||
| I.8.60 | ISSC Item I.8.60 (Main Entry): HID FIPS 201 Reader-No Panel-ACSIDS- No Lock | |||
| II. Secondary Zone Packages: | ||||
| II.1.30 | ISSC Item II.1.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.1.60 | ISSC Item II.1.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.2.30 | ISSC Item II.2.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.2.60 | ISSC Item II.2.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.3.30 | ISSC Item II.3.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.3.60 | ISSC Item II.3.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| II.4.30 | ISSC Item II.4.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.4.60 | ISSC Item II.4.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.5.30 | ISSC Item II.5.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.5.60 | ISSC Item II.5.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.6.30 | ISSC Item II.6.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.6.60 | ISSC Item II.6.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_No Lock | |||
| III. Access Control Only Packages: | ||||
| III.1.30 | ISSC Item III.1.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.1.60 | ISSC Item III.1.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.2.30 | ISSC Item III.2.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.2.60 | ISSC Item III.2.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.3.30 | ISSC Item III.3.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ No Lock | |||
| III.3.60 | ISSC Item III.3.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_No Lock | |||
| III.4.30 | ISSC Item III.4.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ES | |||
| III.4.60 | ISSC Item III.4.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_ES | |||
| III.5.30 | ISSC Item III.5.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.5.60 | ISSC Item III.5.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.6.30 | ISSC Item III.6.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ No Lock | |||
| III.6.60 | ISSC Item III.6.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_No Lock | |||
| IV. Egress Door: | ||||
| IV.1.30 | ISSC Item IV.1.30 (Egress Door)- Expedited | |||
| IV.1.60 | ISSC Item IV.1.60 (Egress Door) - Standard | |||
| DRS-OPR-65-05 | ||||
| V. Additional Devices: | ||||
| These devices below are strictly for adding to packages, I‐III above. | ||||
| V.1.30 | ISSC Item V.1.30 (Additional PIR) - Expedited | |||
| V.1.60 | ISSC Item V.1.60 (Additional PIR) - Standard | |||
| V.2.30 | ISSC Item V.2.30 (Additional Duress) - Expedited | |||
| V.2.60 | ISSC Item V.2.60 (Additional Duress) - Standard | |||
| V.3.30 | ISSC Item V.3.30 (Additional IDRS) - Expedited | |||
| V.3.60 | ISSC Item V.3.60 (Additional IDRS) - Standard | |||
| V.4.30 | ISSC Item V.4.30 (Additional IDRS Button) - Expedited | |||
| V.4.60 | ISSC Item V.4.60 (Additional IDRS Button) - Standard | |||
| V.5.30 | ISSC Item V.5.30 (Additional IDRS Piezo) - Expedited | |||
| V.5.60 | ISSC Item V.5.60 (Additional IDRS Piezo) - Standard | |||
| V.6.30 | ISSC Item V.6.30 (Additional Mortise lock) - Expedited | |||
| V.6.60 | ISSC Item V.6.60 (Additional Mortise lock) - Standard | |||
| V.7.30 | ISSC Item V.7.30 (Additional BMS) - Expedited | |||
| V.7.60 | ISSC Item V.7.60 (Additional BMS) - Standard | |||
| V.8.30 | ISSC Item V.8.30 (Additional Glass Break) - Expedited | |||
| V.8.60 | ISSC Item V.8.60 (Additional Glass Break) - Standard | |||
| V.9.30 | ISSC Item V.9.30 (Additional Aiphone Door Video Unit) - Expedited | |||
| V.9.60 | ISSC Item V.9.60 (Additional Aiphone Door Video Unit) - Standard | |||
| V.10.30 | ISSC Item V.10.30 (Additional Aiphone Sub - Desk Unit) - Expedited | |||
| V.10.60 | ISSC Item V.10.60 (Additional Aiphone Sub - Desk Unit) - Standard | |||
| V.11.30 | ISSC Item V.11.30 (Additional M2100 DCU & IO Boards) | |||
| V.12.30 | ISSC Item V.12.30 (Additional M2150 DC & IO Boards) | |||
| VI. AMAG M2100 /M2150 Alarm Control Panel Accessories: | ||||
| VI.1.30 | ISSC Item VI.1.30 (Additional M2100 DCU & IO Boards to Existing Panel) | |||
| VI.2.30 | ISSC Item VI.2.30 (Additional M2150 DC & IO Boards) - Expedited | |||
| DRS-OPR-65-05 | ||||
| VII. New Installation of Devices to existing panels: | ||||
| VII.1.30 | ISSC Item VII.1.30 (New Individual PIR) - Expedited | |||
| VII.1.60 | ISSC Item VII.1.60 (New Individual PIR) - Standard | |||
| VII.2.30 | ISSC Item VII.2.30 (New Individual BMS) - Expedited | |||
| VII.2.60 | ISSC Item VII.2.60 (New Individual BMS) – Standard | |||
| VII.3.30 | ISSC Item VII.3.30 (New Individual Glass Break) - Expedited | |||
| VII.3.60 | ISSC Item VII.3.60 (New Individual Glass Break) - Standard | |||
| VII.4.30 | ISSC Item VII.4.30 (New Electric Strike) - Expedited | |||
| VII.4.60 | ISSC Item VII.4.60 (New Electric Strike) - Standard | |||
| VII.5.35 | ISSC Item VII.5.35 (New Duress Button) | |||
| VII.6.35 | ISSC Item VII.6.35 (New IDRS) | |||
| VII.7.35 | ISSC Item VII.7.35 (New IDRS Button) | |||
| VII.8.35 | ISSC Item VII.8.35 (New IDRS Piezo) | |||
| VII.9.30 | ISSC Item VII.9.30 (Aiphone Door Video System w/ Desk Master Unit) - Expedited | |||
| VII.9.60 | ISSC Item VII.9.60 (Aiphone Door Video System w/ Desk Master Unit) - Standard | |||
| VII.10.30 | ISSC Item VII.10.30 (New Aiphone Door Video Unit to Existing System) - Expedited | |||
| VII.10.60 | ISSC Item VII.10.60 (New Aiphone Door Video Unit to Existing System) - Standard | |||
| VII.11.30 | ISSC Item VII.11.30 (Additional Aiphone Sub Desk Unit to Existing System)-Expedited | |||
| VII.11.60 | ISSC Item VII.11.60 (Additional Aiphone Sub Desk Unit to Existing System) - Standard | |||
| VII.12.30 | ISSC Item VII.12.30 New Door Box Device Rough In) | |||
| VIII. Miscellaneous Items | ||||
| VIII.1.30 | ISSC Item VIII.1.30 (Decommissioning One Zone or Subzone) Removal of all Equipment from zone | |||
| VIII.2.30 | ISSC Item VIII.2.30 (Relocate One IDRS Button) | |||
| IX. Permits | ||||
| IX.1.30 | ISSC Item IX.1.30 (Building Permit) 1st Floor with the first door locking device | |||
| DRS-OPR-65-05 | ||||
| IX.2.30 | ISSC Item IX.2.30 (Building and Low Voltage Permit) 1st Floor, First Door Locking Device, 1st group of 4-devices, & wiring. | |||
| IX.3.30 | ISSC Item IX.3.30 (Low Voltage Permit) 1st group of 4-devices & wiring. | |||
| IX.4.30 | ISSC Item IX.4.30 (Low Voltage Permit-Each Additional 4-Devices over base permit) 4-devices & wiring. | |||
| IX.5.30 | ISSC Item IX.5.30 (Building Permit-Each Additional Locking Door) $69.75 | |||
| TOTAL | ||||
| Multiply the total by 10 for evaluation purposes. | x10 | x10 | ||
| Subtotal | ||||
| Add $2 Million for non-priced items | $ 2,000,000.00 | $ 2,000,000.00 | ||
| Grand Total | ||||
| Note 1: The Price List will be reviewed annually before the option is exercised and revised as necessary by mutual agreement. | ||||
| Note 2: Additional Devices and New Installation of Devices shall be compatible with the existing AMAG systems. | ||||
| GOVERNMENT PROVIDED ITEMS | ||||
| 2. The Government will provide necessary power and connectivity that will be installed within three feet of the devices that is represented in the system requirements matrix. | ||||
| 3. If a magnetic lock is requested the Government will provide an independent fire alarm dry contact relay within three feet of the AMAG alarm control panel. | ||||
| 4. All door hardware, doors, and frames will be provided by the Government. | ||||
| 5. The Government will provide necessary AMAG servers and software as the current limitation is 64 panels/nodes per communications client server. |
Option Year 4
| OPTION YEAR 4 - PRICE LIST AND SCOPE OF WORK | ||||
| DESCRIPTION | POP CALENDAR DAYS | LEASED FACILITY PRICE | PENTAGON PRICE | |
| Item No. | I. Main Entry Zone Packages: | |||
| I.1.30 | Item I.1.30 (Main Entry-Expedited): Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 30 days | |||
| I.1.60 | Item I.1.60 (Main Entry-Standard) Install one AMAG alarm control panel: (1) DCU board (2) I/O Board, (1) 4-amp power supply, (1) AMAG exterior reader, (1) AMAG interior reader, (1) alarm status indicator, (1) electric strike, (1) request to exit sensor, (1) Infrared motion sensor, and (1) balanced magnetic switch. Complete in 60 days | |||
| I.2.30 | ISSC Item I.2.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.2.60 | ISSC Item I.2.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.3.30 | ISSC Item I.3.30 (Main Entry-Expedited) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.3.60 | ISSC Item I.3.60 (Main Entry-Standard) AMAG FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.4.30 | ISSC Item I.4.30 (Main Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| I.4.60 | ISSC Item I.4.60 (Main Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| I.5.30 | ISSC Item I.5.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.5.60 | ISSC Item I.5.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Electric Strike | |||
| I.6.30 | ISSC Item I.6.30 (Main Entry-Expedited) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.6.60 | ISSC Item I.6.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_Mortise | |||
| I.7.30 | ISSC Item I.7.30 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.7.60 | ISSC Item I.7.60 (Main Entry-Standard) HID FIPS 201_Panel_ACS_IDS_No Lock | |||
| I.8.30 | ISSC Item I.8.30 (Main Entry): HID FIPS 201 Reader-ACS IDS-NO lock or panel | |||
| I.8.60 | ISSC Item I.8.60 (Main Entry): HID FIPS 201 Reader-No Panel-ACSIDS- No Lock | |||
| II. Secondary Zone Packages: | ||||
| II.1.30 | ISSC Item II.1.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.1.60 | ISSC Item II.1.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.2.30 | ISSC Item II.2.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.2.60 | ISSC Item II.2.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.3.30 | ISSC Item II.3.30 (Secondary Entry-Expedited) AMAG FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.3.60 | ISSC Item II.3.60 (Secondary Entry-Standard) AMAG FIPS 201_No Panel_ACS_IDS_No Lock | |||
| II.4.30 | ISSC Item II.4.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.4.60 | ISSC Item II.4.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Electric Strike | |||
| II.5.30 | ISSC Item II.5.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.5.60 | ISSC Item II.5.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_Mortise | |||
| II.6.30 | ISSC Item II.6.30 (Secondary Entry-Expedited) HID FIPS 201_No Panel_ACS_IDS_ No Lock | |||
| II.6.60 | ISSC Item II.6.60 (Secondary Entry-Standard) HID FIPS 201_No Panel_ACS_IDS_No Lock | |||
| III. Access Control Only Packages: | ||||
| III.1.30 | ISSC Item III.1.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.1.60 | ISSC Item III.1.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_ES | |||
| III.2.30 | ISSC Item III.2.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.2.60 | ISSC Item III.2.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_Mortise | |||
| III.3.30 | ISSC Item III.3.30 (Access Control Only Entry-Expedited) AMAG FIPS 201_No Panel_ACS_ No Lock | |||
| III.3.60 | ISSC Item III.3.60 (Access Control Only Entry-Standard) AMAG FIPS 201_No Panel_ACS_No Lock | |||
| III.4.30 | ISSC Item III.4.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ES | |||
| III.4.60 | ISSC Item III.4.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_ES | |||
| III.5.30 | ISSC Item III.5.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.5.60 | ISSC Item III.5.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_Mortise | |||
| III.6.30 | ISSC Item III.6.30 (Access Control Only Entry-Expedited) HID FIPS 201_No Panel_ACS_ No Lock | |||
| III.6.60 | ISSC Item III.6.60 (Access Control Only Entry-Standard) HID FIPS 201_No Panel_ACS_No Lock | |||
| IV. Egress Door: | ||||
| IV.1.30 | ISSC Item IV.1.30 (Egress Door)- Expedited | |||
| IV.1.60 | ISSC Item IV.1.60 (Egress Door) - Standard | |||
| DRS-OPR-65-05 | ||||
| V. Additional Devices: | ||||
| These devices below are strictly for adding to packages, I‐III above. | ||||
| V.1.30 | ISSC Item V.1.30 (Additional PIR) - Expedited | |||
| V.1.60 | ISSC Item V.1.60 (Additional PIR) - Standard | |||
| V.2.30 | ISSC Item V.2.30 (Additional Duress) - Expedited | |||
| V.2.60 | ISSC Item V.2.60 (Additional Duress) - Standard | |||
| V.3.30 | ISSC Item V.3.30 (Additional IDRS) - Expedited | |||
| V.3.60 | ISSC Item V.3.60 (Additional IDRS) - Standard | |||
| V.4.30 | ISSC Item V.4.30 (Additional IDRS Button) - Expedited | |||
| V.4.60 | ISSC Item V.4.60 (Additional IDRS Button) - Standard | |||
| V.5.30 | ISSC Item V.5.30 (Additional IDRS Piezo) - Expedited | |||
| V.5.60 | ISSC Item V.5.60 (Additional IDRS Piezo) - Standard | |||
| V.6.30 | ISSC Item V.6.30 (Additional Mortise lock) - Expedited | |||
| V.6.60 | ISSC Item V.6.60 (Additional Mortise lock) - Standard | |||
| V.7.30 | ISSC Item V.7.30 (Additional BMS) - Expedited | |||
| V.7.60 | ISSC Item V.7.60 (Additional BMS) - Standard | |||
| V.8.30 | ISSC Item V.8.30 (Additional Glass Break) - Expedited | |||
| V.8.60 | ISSC Item V.8.60 (Additional Glass Break) - Standard | |||
| V.9.30 | ISSC Item V.9.30 (Additional Aiphone Door Video Unit) - Expedited | |||
| V.9.60 | ISSC Item V.9.60 (Additional Aiphone Door Video Unit) - Standard | |||
| V.10.30 | ISSC Item V.10.30 (Additional Aiphone Sub - Desk Unit) - Expedited | |||
| V.10.60 | ISSC Item V.10.60 (Additional Aiphone Sub - Desk Unit) - Standard | |||
| V.11.30 | ISSC Item V.11.30 (Additional M2100 DCU & IO Boards) | |||
| V.12.30 | ISSC Item V.12.30 (Additional M2150 DC & IO Boards) | |||
| VI. AMAG M2100 /M2150 Alarm Control Panel Accessories: | ||||
| VI.1.30 | ISSC Item VI.1.30 (Additional M2100 DCU & IO Boards to Existing Panel) | |||
| VI.2.30 | ISSC Item VI.2.30 (Additional M2150 DC & IO Boards) - Expedited | |||
| DRS-OPR-65-05 | ||||
| VII. New Installation of Devices to existing panels: | ||||
| VII.1.30 | ISSC Item VII.1.30 (New Individual PIR) - Expedited | |||
| VII.1.60 | ISSC Item VII.1.60 (New Individual PIR) - Standard | |||
| VII.2.30 | ISSC Item VII.2.30 (New Individual BMS) - Expedited | |||
| VII.2.60 | ISSC Item VII.2.60 (New Individual BMS) – Standard | |||
| VII.3.30 | ISSC Item VII.3.30 (New Individual Glass Break) - Expedited | |||
| VII.3.60 | ISSC Item VII.3.60 (New Individual Glass Break) - Standard | |||
| VII.4.30 | ISSC Item VII.4.30 (New Electric Strike) - Expedited | |||
| VII.4.60 | ISSC Item VII.4.60 (New Electric Strike) - Standard | |||
| VII.5.35 | ISSC Item VII.5.35 (New Duress Button) | |||
| VII.6.35 | ISSC Item VII.6.35 (New IDRS) | |||
| VII.7.35 | ISSC Item VII.7.35 (New IDRS Button) | |||
| VII.8.35 | ISSC Item VII.8.35 (New IDRS Piezo) | |||
| VII.9.30 | ISSC Item VII.9.30 (Aiphone Door Video System w/ Desk Master Unit) - Expedited | |||
| VII.9.60 | ISSC Item VII.9.60 (Aiphone Door Video System w/ Desk Master Unit) - Standard | |||
| VII.10.30 | ISSC Item VII.10.30 (New Aiphone Door Video Unit to Existing System) - Expedited | |||
| VII.10.60 | ISSC Item VII.10.60 (New Aiphone Door Video Unit to Existing System) - Standard | |||
| VII.11.30 | ISSC Item VII.11.30 (Additional Aiphone Sub Desk Unit to Existing System)-Expedited | |||
| VII.11.60 | ISSC Item VII.11.60 (Additional Aiphone Sub Desk Unit to Existing System) - Standard | |||
| VII.12.30 | ISSC Item VII.12.30 New Door Box Device Rough In) | |||
| VIII. Miscellaneous Items | ||||
| VIII.1.30 | ISSC Item VIII.1.30 (Decommissioning One Zone or Subzone) Removal of all Equipment from zone | |||
| VIII.2.30 | ISSC Item VIII.2.30 (Relocate One IDRS Button) | |||
| IX. Permits | ||||
| IX.1.30 | ISSC Item IX.1.30 (Building Permit) 1st Floor with the first door locking device | |||
| DRS-OPR-65-05 | ||||
| IX.2.30 | ISSC Item IX.2.30 (Building and Low Voltage Permit) 1st Floor, First Door Locking Device, 1st group of 4-devices, & wiring. | |||
| IX.3.30 | ISSC Item IX.3.30 (Low Voltage Permit) 1st group of 4-devices & wiring. | |||
| IX.4.30 | ISSC Item IX.4.30 (Low Voltage Permit-Each Additional 4-Devices over base permit) 4-devices & wiring. | |||
| IX.5.30 | ISSC Item IX.5.30 (Building Permit-Each Additional Locking Door) $69.75 | |||
| TOTAL | ||||
| Multiply the total by 10 for evaluation purposes. | x10 | x10 | ||
| Subtotal | ||||
| Add $2 Million for non-priced items | $ 2,000,000.00 | $ 2,000,000.00 | ||
| Grand Total | ||||
| Note 1: The Price List will be reviewed annually before the option is exercised and revised as necessary by mutual agreement. | ||||
| Note 2: Additional Devices and New Installation of Devices shall be compatible with the existing AMAG systems. | ||||
| GOVERNMENT PROVIDED ITEMS | ||||
| 2. The Government will provide necessary power and connectivity that will be installed within three feet of the devices that is represented in the system requirements matrix. | ||||
| 3. If a magnetic lock is requested the Government will provide an independent fire alarm dry contact relay within three feet of the AMAG alarm control panel. | ||||
| 4. All door hardware, doors, and frames will be provided by the Government. | ||||
| 5. The Government will provide necessary AMAG servers and software as the current limitation is 64 panels/nodes per communications client server. |