Exhibit M8 - Miscellaneous Best Practices Shave Energy.pdf
PDF 156 KB Posted
- Attached to
- Full Maintenance and Operations, Laredo, TX Federal contract opportunity
- Solicitation number
- 47PH0220R0014
View the file
Other files for this federal contract opportunity
Show all 50
Full Maintenance and Operations, Laredo, TX has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT
JM15
Miscellaneous Best Practices Shave Energy
The Shave Energy Program is designed to assist field offices to systematically identify and implement simple no cost energy efficiency measures. The primary objective of the program is to identify no cost inefficiencies in operations, make appropriate adjustments, and reduce total energy consumption at participating facilities, on average, by 10% per year. Program participants will use various audit procedures, tools, templates, strategies, educational tools and reference materials to implement a variety of best practices. These include optimizing HVAC & lighting schedules, controls, and equipment, implementing energy- and comfort-optimized thermal set points and lighting levels, demand shedding, and tenant engagement.
Field office personnel will be essential to the success of the program and will be pivotal to reducing cost significantly through no cost means. They will be supported by regional super users and Central Office contract with technical support.
The Miami Service Centers participated in the unintentional Shave Energy pilot program last year and the results are very promising. The Service Center, under the leadership of Don Rollins, implemented numerous no cost items into its portfolio and the benefits were profound as they maintained reductions over a one year period.
Over the past year (2011), the Service Center reduced energy consumption by 4,916 BTU/GSF and a 15% reduction in total KWH usage (equivalent to almost 6 million KWH). This reduction is very significant and equivalent to “not using” 161,294 gallons of gas. The cost benefit associated with these reductions is also significant as it reduced total energy cost by $541,419 in FY11 KWH dollars.
The Wilkie Ferguson facility has also seen phenomenal success on its own as it reduced its usage by 15,369 BTU/GSF over the last year. The property manager reduced total consumption by 3.5 million KWH or 29% over the last year. This reduction is equivalent to “not using” 95,093 gallons of gas or removing 1,521 cars from the road. The cost savings associated with these reductions is $314,861 in FY11 KWH dollars.
The Pilot Shave Energy Program was expanded to include an additional service center in the fall. After initial walk through and audits of two of its’ facilities, possible annual consumption reductions between 2.8 million and 3.8 million KWH were identified. Again, these reductions would result from “no cost” methods. The potential cost savings is approximately $250K to $340K. The pilot participants are currently vetting the various audit procedures, tools, templates, and strategies with much success.
The Shave Energy Program presents a unique methodology to bridge the gap between the identification of energy- saving opportunities and implementation of energy retrofits by outlining specific actionable items based on simple operational best practices. Integration of Shave Energy with advanced metering programs will significantly expedite the detection of opportunities for energy reduction through the analysis of building energy consumption.
The success of Shave Energy is dependent on managerial commitment to existing GSA operational standards. In order to maximize the impact of the Shave Energy Program, GSA management must be proactively engaged at the national, regional, field office, and building levels.
The first step is to identify core team members. These core team members will assist in fully developing the program and providing guidance to the national program team. The second step is to make people and buildings available for training and implementation of best practices. This program’s training is expected to be 10 hours for regional and field office super users and participating property managers. The audit process is expected to take approximately 24 to 30 hours per facility depending on size. And a strong commitment to implement cost saving measures uncovered during the audits.
In conclusion, it is still feasible to reduce consumption and cost with little or no investment. In these current uncertain fiscal times your commitment and support is fundamental.
Schedule Alignment One of the easiest ways to reduce energy usage in a building is to ensure that operations such as heating, cooling, and lighting satisfy occupant requirements only during occupied times. The GSA definition of occupancy in the workplace is defined as the times during which at least 75% of all people typically working in the office are present.
The Contractor should align all operational schedules to reflect GSA’s occupancy definition.
Providing heating and cooling services beyond the occupied operational schedule without prior approval of GSA is prohibited unless those services will be required to maintain the facility in accordance to ASHRAE thermal comfort and efficiency standards. All operating schedules must be adjusted seasonally and be approved by GSA every 90 days.
Unoccupied Heating and Cooling Operations During unoccupied times, heating and cooling operations should be shut off, or in climates that require the circulation of mildly conditioned air, their set points set back by (at minimum) 8-10°F (e.g. if the cooling set point is 74°F then an appropriate unoccupied set point would be 84°F). As required by the Federal Management Regulations, heating temperature set points must be no higher than 55°F during non-working hours. When the building is unoccupied, only emergency lighting should remain on inside the building. During times when occupants are filtering in or out of the building at the beginning and end of the day, the air conditioning system can be in the process of ramping up or down because a lower internal load (i.e. body heat and appliance use) exists under these conditions. For more information, see SEP Reference Manual Sections.
Morning Start-Up and Afternoon Drift Depending on the system type and building size and air conditioning load, some systems may take a number of hours to stabilize at the desired heating or cooling set points. The O&M Contractor should be aware of these start-up times and should operate the equipment schedules based on the observed response and the space occupancy. However, the system start-up response time will also vary by season. For example, GSA would expect a system that takes 2 hours to meet occupied cooling set points in August to take significantly less time to meet these set points in March. The Contractor should adjust the heating and cooling system start-up times seasonally to align the observed stabilized response of the system with the periods of 75% occupancy or greater, keeping in mind that full air conditioning need not be applied during times of lower occupancy.
Many building automation systems have algorithms for optimal start procedures based on the outside air temperature and the load required to reach set points in morning start-up. Where such systems exist, these algorithms should be utilized to minimize start-up energy consumption.
GSA recommends that Contractors shut down or set back equipment in a similar manner. In many buildings, while exact temperature set points may not be upheld, favorable temperatures will be maintained long after equipment have been shut off or set back to unoccupied levels. As occupants leave at the end of the day, cooling loads decrease. For example, if occupants leave the building between 3:30 p.m. and 5:00 p.m., the unoccupied temperature set back can actually be applied at 4:00 or 4:15 and the temperature allowed to slowly drift upwards as people leave the building. In order to determine the appropriate time for shutting down or setting back equipment operations, the Contractor should evaluate the current system capabilities and adjust the systems schedule daily if needed to optimize energy usage while maintaining acceptable levels of comfort.
Heating, Ventilation, and Air Conditioning (HVAC) This Section summarizes the best practices for operating heating, ventilation, and air conditioning systems. As the Contractor surveys the building spaces and the associated systems, each of the following practices should be verified and the need for adjustment noted.
Timing of HVAC Adjustments Changes to centralized building temperature set points for more efficient operation should be gradual but substantial enough to reduce system inefficiencies. If centralized building temperature set points are required the Contractor should adjust no more than by 2°F per week.
Set Point Control ASHRAE Standard 55 for Thermal Comfort identifies acceptable comfort ranges based on humidity and mean outdoor air temperature using a metric of Predicted Percentage Dissatisfied (PPD) to optimize thermal comfort. For most summer climates for which air conditioning is utilized in the United States, acceptable cooling set points range between 74°F and 78°F. Acceptable heating set points range between 68°F and 72°F for most US climates. The Contractor shall operate all GSA conditioned space in accordance to ASHRAE Standard 55 for appropriate space types and all building thermostat dead bands shall be limited to no more than ± 2°F. For example, an appropriate set point and dead band would be 74°F ± 2°F for a cooling environment if the ASHRAE standard acceptable cooling set points range between 74°F and 78°F. An inappropriate set point and dead band would be 72°F ± 2°F or 74°F ± 3°F for a cooling environment if the ASHRAE standard acceptable cooling set points range between 74°F and 78°F.
Supply Air Temperature Resets When outside air temperatures are lower, the building can meet space cooling temperature set points using higher supply air temperature set points. This lowers the energy costs associated with running the cooling system and, in buildings with zonal reheat, this can also prevent the waste of energy through simultaneous heating and cooling. For applicable systems, the Contractor should implement a supply air temperature reset. Where such automation is not possible, Contractors should manually implement this strategy on a seasonal basis. In most climates, discharge air temperature can be reset by about 10°F while maintaining favorable indoor temperatures and reducing energy consumption. Typical discharge air temperature resets range between 50°F and 60°F for cooling.
Chilled Water and Hot Water Resets The prescribed recommendations for the reset of chilled water and heating hot water set points apply only to hydronic systems, in which the heating and cooling sources to the air handler are chilled water and hot water served by chiller(s) and boiler(s) respectively.
Many HVAC system configurations can be programmed to automatically reset the CHW temperature set point in response to building load, similar to supply air temperature reset control, if the system is programmable the Contractor shall automate all configurations. The Contractor should adopt a chilled water reset strategy and implement a temperature control range of 5-10°F. In general the lower limit of the control range should be no less than 42°F and that the upper limit should be no more than 2°F less than the minimum supply air temperature.
Where such automation is not possible, Contractors should implement this strategy on a seasonal basis.
Most buildings can be programmed to automatically modulate hot water temperatures in response to building load. The Contractor should implement a hot water reset strategy which decreases the range to which the hot water temperature can be reset; if the system is programmable the Contractor shall automate all configurations. As a rule of thumb, the hot water temperature set point should be no lower than 140°F and no greater than 180°F. For example, if the building is controlling heating hot water temperatures to 170°F, an appropriate reset control strategy would control heating hot water between 140°F and 170°F.
Static Pressure Resets Variable air volume systems typically modulate supply fan speed to maintain a constant duct static pressure. This static pressure set point is designed to overcome all system pressure loss at peak fan airflows. Under partial load conditions, the required airflow is less than the design airflow and a lower duct static pressure is required to meet the load. In order to meet ventilation requirements, the degree to which duct static pressure can be reduced depends on the number of zones, the zone size and maximum occupancy, and the system’s air balance. Poorly balanced systems require greater static pressure to ventilate the worst-served zones. The Contractor shall rebalance any poorly balanced zones.
Most air handling units use constant duct static pressure set points around 2” WC. Depending on the building, static pressure may even be reset to below 0.5” WC while maintaining sufficient airflow for heating, cooling, and ventilation. The Contractor should determine the minimum required static pressure to meet ventilation requirements. If adjustment is possible the Contractor shall lower the static pressure until airflow to the worst stops providing adequate ventilation, as required by ASHRAE 62.1 (see next Section). Wherever systems can support it, the Contractor shall implement a duct static pressure reset control strategy that ranges from the design static pressure to the minimum static pressure required for ventilation.
Outside Air Intake When buildings are occupied, they are required by law to intake a certain amount of outside air to maintain appropriate indoor air quality. The Contractor must verify that all HVAC systems provide ventilation as required by ASHRAE Standard 62.1 – 2010 every three years through system testing. These reports must be submitted to GSA for approval. The use of TAB reports to verify performance is strictly prohibited. The value to note in verifying the intake of outside air is the combined outdoor air rate, shown in Table 6-1 of ASHRAE 62.1. This may be calculated based on the maximum number of occupants and floor area, as shown in the equation below, or using the default values based on default occupant densities.
Required Ventilation (CFM) = RP ∗ (Max.# Occupants) + Ra ∗ (Floor Area)
Table 1 Selection of ASHRAE Standard
62.1 Table 6-1
One Section of the ASHRAE 62.1 Table 6-1 is shown above. The Contractor can access the full document and a comprehensive list on the GSA Shave Energy Google Site. A conservative estimate for the required outside air flow is 20 CFM per occupant. The intake of outside air above minimum requirements can reduce or increase the total cooling energy use, depending on the outside air temperature. If possible, the Contractor shall implement airside economizer control to optimize the intake of outside air for cooling operations. If the minimum outside air intake is greater than required by ASHRAE 62.1, however, then additional energy is required to condition that air to space requirements. As best practice, minimum ventilation rates should be within 100-110% of that required by ASHRAE 62.1.
Exhaust Fan Control GSA prohibits running exhaust fans constantly. The Contractor shall adopt an exhaust fan strategy and where possible use sensors to control all exhaust fan systems.
Placement of Supply and Return Air Diffusers In order for building spaces to be effectively cooled and heated, the air supplied to each zone must be allowed to distribute and mix with the warmer (for cooling) or cooler (for heating) air in these spaces. If supply and return diffusers are placed too close to each other, then air flow will be short-circuited and conditioned air will be returned without effectively conditioning the space. The Contractor shall verify that all supply and return air diffusers are placed no less than 5 feet apart. The O&M Contractors shall re-distribute the supply and return air connections when necessary and feasible.
Demand Response Strategies If GSA has a Demand Response Strategy in place the Contractor shall operate the facility in accordance to that strategy. In addition, any strategies that can be adopted on a normal routine should be adopted as standard daily practice. Any strategy that can temporarily decrease energy consumption (e.g. lighting reduction, where applicable) should be applied during high-rate demand response events and were feasible daily. The Contractor shall maximize demand reduction strategies during high-rate periods.
Lighting and Lighting Controls The Contractor shall remove or replace lighting fixtures and bulbs with more efficient equivalent alternatives when available when those alternatives can be procured at the same market cost. It is important to note that these investments in time pay off on their end as well because in the future they’ll need to replace fewer bulbs less often.
If such an alternative more efficient product is available at the request of the government the Contractor is required to use them if the payback is less than three-fourths of the Contract period or less than eighteen months whichever is less. In addition, if an appropriate lighting efficiency strategy is identified at the facility the Contractor, shall support the effort if there is no undue burden placed upon the Contractor (e.g. a de-lamping 2 hours per week over a specified amount of time).
Acceptable Levels of Luminance Section 6.3 in the P100 specifies interior lighting requirements, which must be realized at work surfaces or a height of 30 inches by the combination of ambient lighting fixtures, task lighting, and ambient daylight. These standards should be interpreted as guidelines for appropriate lighting levels - as in actual application, these levels will vary throughout the space. The below guidelines recommended minimum and maximum values for luminance for most GSA space types. These are to be realized at working surfaces by a combination of installed lighting fixtures, task lighting, and daylight.
Table 2 Acceptable Levels of Luminance Area/Activity Guideline Average Illuminance (foot candles) Recommended Minimum Illuminance (foot candles)
Recommended Maximum Illuminance (foot candles) Parking lot N/A .1 5 Elevator N/A 5 10 Inactive storage 5 5 10 Active storage 10 5 15 Stairs 10 10 15 Restroom
10 10 20 Corridor 10 10 30 Dining area 10 10 30 Lounge 10 10 30 Atrium 10 10 30 Lobby 10 10 30 Elec./Mech/Tech. room 30 20 40 Enclosed office 30 20 50 Open office 30 30 50 Conference 30 30 50 Classroom 30 30 50 The U.S.
Courts Design Guide derives required levels of illumination from IESNA standards, as shown below. These have also been coupled with recommended minimum and maximum values for space luminance.
Table 3 U.S. Court Facilities – Acceptable Levels of Luminance Area/Activity Guideline Average Illuminance (foot candles) Recommended Minimum Illuminance (foot candles)
Recommended Maximum Illuminance (foot candles) Public seating 10 10 20 Supplies and storage 20 10 30 Attorney witness table 30 30 50 Witness box 30 30
50 News media room 30 30 50 Attorney work room 30 30 50 Attorney witness room 30 30 50 Jury assembly suite 30 30 50 Trial jury suite 30 30 50 Grand jury suite 30 30 50 Central court libraries 30-50 30 50 Judges chamber suites 30-50 30 50 Judge’s bench 50 40 60 Bailiff 50 40 60 Interpreter 50 40 60 Court reporter 50 40 60 Jury box 50 40 60 The recommended levels of luminance should be provided for each space and over lit spaces should be reduced in electrical lighting by one of the following lighting reduction measures.
Removal and Relocation of Fixtures Where excessive lighting exists, the simplest measure to reduce lighting energy consumption is to remove some of the fixtures that serve that area.
Where over lit spaces can output favorable lighting levels using fewer of the existing installed fixtures, determine the minimum number of fixtures required to meet the desired level of luminance. Remove the unnecessary lighting fixtures and rearrange them to effectively distribute luminance throughout the space. A multiple period plan should be developed and submitted to GSA if removal or relocation of fixtures is warranted.
Removal of Lamps (De-lamping) Where the distribution of lighting fixtures is appropriate, yet lighting levels are higher than needed, one option for reducing lighting energy is to remove lamps from the existing fixtures. For example, if a room with excessive lighting has six fixtures with three lamps per fixture, an acceptable solution could be to remove the center lamp from each fixture in order to maintain fixture symmetry yet reduce the lighting energy by 33%.
Replacement of Lamps/Fixtures Many buildings were installed with fixtures and lamps that are grossly inefficient compared to modern lighting technology. Furthermore, newer induction, CFL and LED technologies last longer and require replacement less often than older, inefficient lamps. As these lamps burn out, they should be replaced with more efficient lamps, and where necessary, fixtures should be replaced. To maintain aesthetic consistency, a plan to replace the lamps or fixtures for an entire zone over time should be submitted to GSA for approval. For more information regarding appropriate efficient lighting technologies, see GSA Standards Related to Shave Energy and the P100 Facilities Standards for the Public Buildings Service.
Re-ballasting fixtures Re-ballasting fixtures can be an effective method for reducing the energy consumption of lighting fixtures or increasing their total lifetime. Ballasts regulate the amount of electrical current available to a lighting fixture. When older, more inefficient, ballasts are in place and expire the Contractor shall replace them with more efficient technology. When lighting fixtures are replaced and/or existing ballasts are incompatible with the installed lighting, the Contractor must ensure that the ballast is installed to the light bulb specifications. Improper ballasting severely reduces lamp life and incurs additional maintenance and repair costs. For spaces in which dimming capabilities are desired, such as for photocell control, install dimmable ballasts to regulate the electrical current to the light bulbs.
Occupancy Control Occupancy controls have become significantly more economical in recent years, and are proven to significantly reduce energy by allowing lighting to turn on only when spaces are occupied. They can be applied to any building interior space or parking structure.
Depending on the layout and use for each space, the Contractor should choose (a combination
of) specific sensor types found below when current lighting controls fail or require replacement:
• Wall-Mounted Sensors
• Ceiling-Mounted Sensors
• Bi-Level Sensors
• Passive Infrared (PIR)
• Ultrasonic
• Dual Technology
Daylight Control Many office spaces maintain high levels of luminance during the day through windows and skylights and require no electrical lighting during most occupied hours.
In some places, lighting fixtures can simply be removed where they are not unnecessary. In places where electrical lighting is only required during some hours, however, one of two strategies should be employed by the Contractor if appropriate systems are in place to allow the lights to come on only when needed:
Photocell Sensors: Measures luminance and interacts with the fixtures or BAS to control area lighting by switching lights on and off or by electronic dimming. The sensor sensitivity is adjustable.
Timer Switches: Timers interact with the fixtures directly or through the BAS to control area lighting based on the time of day.
Lighting Demand Response Lighting reductions may also be utilized as a measure for demand response. For buildings that incur demand charges and where systems are in place, implement a continuous dimming or stepped lighting reduction demand response strategy during the peak demand period. From standard lighting levels, dim lighting by 20%, 40%, and 60% for zones with no daylight, low daylight, and high daylight respectively without occupant impact – assuming that the dimming takes place over the matter of minutes – GSA recommends at 1% per minute. With prior GSA approval lighting can be reduced up to 60% across the board during the worst demand response.
Stepped lighting reductions require stepped dimming lighting control or a wiring configuration that supports turning only some lights off. During peak demand periods, reduce the stepped lighting output or the number of lights served.
Federal High Performance Guiding Principles
Performance Measurement - Building Automation System (GP4.3a)
A BAS supports ongoing accountability and optimization of the building energy performance, and helps building engineers to efficiently operate GSA assets.
The BAS must monitor and control the major building systems, including at minimum, heating, cooling, ventilation exterior and interior lighting, if a preexisting BAS is in place. Operating in manual or non-automated modes is strictly prohibited. Altering any building system that is, was, or previously has been automated or controlled by the BAS or similar control system is prohibited and is grounds for Contract termination or penalty. Lighting may be controlled by the BAS or by time clocks, occupancy sensors, or photocells. Critical spaces include all spaces within the building except for storage closets and mechanical closets. All regularly occupied spaces, stairwells, lobbies, and corridors are considered to be critical spaces and therefore must have automatic controls in place if applicable.
All critical sensors should be calibrated annually to ensure accurate readings and control points. When used effectively, a BAS allows building engineers and management to make informed decisions regarding changes in building operations and energy saving investments.
The Contractor shall record the Base Building Systems Control and BAS Operating Capabilities in the GSA Sustainable Operations and Maintenance Tool. The Contractor shall develop a maintenance plan for all zone level sensors and actuators using GSA’s “Zone Level Sensor Maintenance Plan Template and Sample.” The maintenance plan must demonstrate that zone level sensors and actuators will be calibrated according to the manufacturer recommended intervals to ensure sensor and actuator accuracy and precision and proper operation of the overall systems. The plan must also demonstrate that any malfunctioning zone level sensors and actuators will be repaired or replaced. At a minimum, the maintenance plan must include the following zone level sensors and actuators:
• Terminal unit damper
• Terminal unit flow sensor
• Space temperature sensors
• Space humidity sensors (if applicable at the facility)
• Zone CO2 sensors (if applicable at the facility)
• Calibrate all system level sensors and actuators annually
The Contractor shall maintain zone level sensors and actuators according to the Zone Level Sensors Maintenance Plan. Ensure the standard operating procedure for responding to comfort calls includes calibration/verification of zone level sensors and actuators as applicable to the facility. The Contractor shall check temperature set points and resets annually, record changes to set points, programming, and schedules, set up trends so that unusual equipment operation can be identified and corrected, annually provide GSA a Calibration and Testing Report. The Contractor shall operate the facility in accordance to the Federal High Performance Guiding Principles 3.1 Performance Measurement - Building Automation System as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide. The Contractor shall provide GSA documentation to support compliance to the Federal High Performance Guiding Principles 3.1 Performance Measurement - Building Automation System as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide. The Contractor shall provide GSA a schematic of the floor layout showing automated lighting controls.
If no BAS system is in place or limited control the Contractor shall operate the GSA asset in accordance to the GSA GP3.3b - (EQc2.2) - Controllability of Systems – Lighting requirements. The contractor will confirm that the facility provides automated lighting controls (occupancy/vacancy sensors with manual-off capacity) for appropriate spaces including restrooms, conference and meeting rooms, employee lunch and break rooms, training classrooms and offices. Provide GSA a schematic of the floor layout showing automated lighting controls
Benchmarking, Energy and GHG Performance (GP 2.1a, 2.3, 2.4, 2.5) GSA utilizes EPA’s Energy Star Portfolio Manager (ESPM) as a tool to allow buildings to directly compare their observed energy consumption to a database of national energy data, and to establish a building energy performance rating accordingly. The facility’s ESPM will be shared with the Contractor in a read only view.
GSA’s Energy Star Rating goal is an Energy Star Rating of at least 75 or be 19th percentile points above the national average energy usage intensity. GSA centrally maintains all energy use for its buildings centrally and that data is uploaded to Energy Star on or about the 20th of each month.
The Contractor shall annually review the space information and building profile in the facility’s ESPM account for accuracy and report to GSA an inaccuracy. The Contractor shall not update, alter, or change any utility data or entries. Support GSA in efforts of documenting compliance for an Energy Star Label. Operate the facility in accordance to the Energy Star PE Guide standards. Calibrate meters in accordance to the GSA Sustainable Operations and Maintenance Tool and Reference Guide. Operate the facility in accordance to the Federal High Performance Guiding Principles 2.1a, 2.3, 2.4, & 2.5 Energy and GHG Performance as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide.
Provide GSA documentation to support compliance to the Federal High Performance Guiding Principles 2.1a, 2.3, 2.4, & 2.5 Energy and GHG Performance as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide.
BP 1 - ASHRAE
62.1-2007
To ensure that the facility is adequately ventilated with outside air (OA) the GSA has adopted the ASHRAE 62.1- 2007 standards. Facilities with naturally ventilated systems (i.e. no mechanical ventilation) are not required to document compliance to the ASHRAE 62.1-2007 standard. An alternative standard can be used at GSA’s discretion.
The Contractor shall annually document that all mechanical ventilation systems are meeting ventilation requirements of ASHRAE 62.1-2007. Any air handlers (AHU) that are physically not able to meet these standards must provide at least 10 CFM/person of outside air. The
Contractor shall annually document proper function of all dedicated exhaust systems and operate the facility in accordance to the Federal High Performance Guiding Principles 4.1 Outside Air Ventilation & Indoor Air Quality Best Management Practices as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide. The Contract shall operate all heating and cooling systems and equipment in accordance the Shave Energy program standards, best practices, training, and reference guides. The Contractor shall provide GSA documentation to support the Federal High Performance Guiding Principles 4.1 Outside Air Ventilation & Indoor Air Quality Best Management Practices as outlined in the GSA Sustainable Operations and Maintenance Tool and Reference Guide.
Besides the aforementioned lighting and HVAC efficiency measures, there are a great number of other no cost efficiency measures that can easily be implemented into building operation.
The following list demonstrates a number of additional strategies the Contractor should adopt if appropriate and feasible at the GSA facility:
• Timer control for, or removal of, water fountain cooling systems
• Keypad access to freight elevators
• Smart programming for elevator operation (automated, timer, BAS, sleep mode)
• Extended elevator door close operation
• LED lighting for elevators, stairs, exterior, flood lighting
• Weather stripping of doors and windows
• Plug standby load controllers (timer, occupancy)
• Dynamic modification of BAS equipment schedules
• Additional strategies can be found in the National Energy Efficiency Best Practices Study.
File details come from the government source that posted it. Updated .