FV01-000-01_(HVAC_Loads) AS-BUILT_2006-09-14)ab.pdf
PDF 721 KB Posted
- Attached to
- DRYDOCK REPAIRS FOR NOAA SHOP PISCES
- Solicitation number
- EA-133M-16-RP-0112
View the file
Other files
Show 40 more
Latest 50 of 77 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX
SHT TITLE SHT TITLE
NO. NO.
1 TITLE SHEET
2 INDEX
3 REVISION STATUS
4 REVISIONS
5 REFERENCES
6 GENERAL NOTES
7 GENERAL NOTES (Cont) 8 GENERAL NOTES (Cont) 9 GENERAL NOTES (Cont)
10 LIST OF SPACES (ALPHABETICAL ORDER)
11 LIST OF SPACES (ALPHABETICAL ORDER)
12 LIST OF SPACES (ALPHABETICAL ORDER)
13 A/C SYSTEM SUMMARY
1 VENT VENTILATION SYSTEM SUMMARY
2 VENT VENTILATION SYSTEM SUMMARY
3 VENT VENTILATION SYSTEM SUMMARY
1 A/C SUMMARY - CLG & HTG SUMMARY - A/C SYS #AC1
1A A/C SUMMARY - CLG & HTG SUM(CONT) - A/C SYS #AC1
1B A/C SUMMARY - PSYCHROMETRICS - A/C SYS #AC1
1C A/C PSYCHROMETRIC CHART - A/C SYS #AC1
2 A/C SUMMARY - CLG & HTG SUMMARY - A/C SYS #AC2
2A A/C SUMMARY - CLG & HTG SUM(CONT) - A/C SYS #AC2
2B A/C SUMMARY - PSYCHROMETRICS - A/C SYS #AC2
2C A/C PSYCHROMETRIC CHART - A/C SYS #AC2
3 A/C SUMMARY - CLG & HTG SUMMARY - A/C SYS #AC3 001L* INDIVIDUAL ROOM LOAD SHEETS
3A A/C SUMMARY - CLG & HTG SUM(CONT) - A/C SYS #AC3 TO
3B A/C SUMMARY - PSYCHROMETRICS - A/C SYS #AC3 119L* *SHEETS NUMBERED AS "XXXL(A)", "XXXE", AND "XXXEQU" ARE INCLUDED
3C A/C PSYCHROMETRIC CHART - A/C SYS #AC3 AS REQUIRED FOR THE INDIVIDUAL ROOM LOADS AS REFERENCED ON
4 A/C SUMMARY - CLG & HTG SUMMARY - A/C SYS #AC4 THE ROOM MASTER SHEETS NUMBERED "XXXL". SEE GENERAL NOTE #4.
4A A/C SUMMARY - CLG & HTG SUM(CONT) - A/C SYS #AC4 JOB:
4B A/C SUMMARY - PSYCHROMETRICS - A/C SYS #AC4 A NOAA FRV40 CLASS 63m VESSEL REV 0
4C A/C PSYCHROMETRIC CHART - A/C SYS #AC4 FSCM: DRAWING NO.:
M282-512-FV01
SCALE: N/A SWBS: SHT NO.: 2 OF INDEX
REVISION STATUS
SHT REVISION SHT REVISION SHT REVISION SHT REVISION SHT REVISION SHT REVISION SHT REVISION SHT REVISION SHT REVISION
NO. NO. NO. NO. NO. NO. NO. NO. NO.
1 1 4 A/C 0 001L 0 029L 0 057L 0 085L 0 113L 0 2 0 4A A/C 0 002L 0 030L 0 058L 0 086L 0 114L 0 3 1 4B A/C 0 003L 0 031L 0 059L 0 087L 0 115L 0 4 1 4C A/C 0 004L 0 032L 0 060L 0 088L 0 116L 0 5 0 005L 0 033L 0 061L 0 089L 0 117L 0 6 0 006L 0 034L 0 062L 0 090L 0 118L 0 7 0 007L 0 035L 0 063L 0 091L 0 119L 0 8 0 008L 0 036L 0 064L 0 092L 0 9 0 009L 0 037L 0 065L 0 093L 0
10 0 010L 0 038L 0 066L 0 094L 0 11 0 011L 0 039L 0 067L 0 095L 0 12 0 012L 0 040L 0 068L 0 096L 0 13 0 013L 0 041L 0 069L 0 097L 0
1 VENT 0 014L 0 042L 0 070L 0 098L 0
2 VENT 0 015L 0 043L 0 071L 0 099L 0
3 VENT 0 016L 0 044L 0 072L 0 100L 0
1 A/C 0 017L 0 045L 0 073L 0 101L 0
1A A/C 0 018L 0 046L 0 074L 0 102L 0 1B A/C 0 019L 0 047L 0 075L 0 103L 0 1C A/C 0 020L 0 048L 0 076L 0 104L 0 2 A/C 0 021L 0 049L 0 077L 0 105L 0
2A A/C 0 022L 0 050L 0 078L 0 106L 0 2B A/C 0 023L 0 051L 0 079L 0 107L 0 2C A/C 0 024L 0 052L 0 080L 0 108L 0 3 A/C 0 025L 0 053L 0 081L 0 109L 0
3A A/C 0 026L 0 054L 0 082L 0 110L 0 3B A/C 0 027L 0 055L 0 083L 0 111L 0 3C A/C 0 028L 0 056L 0 084L 0 112L 0
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 1
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 3 OF INDEX
REVISIONS
REV SHT # ITEM DESCRIPTION
1 1, 3 &4 2 THIS REVISION IS HEREBY ISSUED TO SUIT "AS-BUILT" CONDITIONS.
BY: VES, INC.
DATE: 09/14/2006
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 1
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 4 OF INDEX
REFERENCES
REV NO TITLE DRAWING
NO.
1 SNAME TECH & RES BULLETIN NO. 4-7", "THERMAL INSULATION REPORT" N/A
2 SNAME TECH & RES BULLETIN NO. 4-16, "CALC. FOR MERCHANT SHIP HV&AC DESIGN N/A
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 5 OF INDEX
GENERAL NOTES
1) THE INSULATION VALUES USED IN THESE CALCULATIONS ARE TAKEN FROM REFERENCE NO.1.
2) THE CALCULATION METHODS USED ARE IN ACCORDANCE WITH REFERENCE NO. 2
3) LIST OF SYMBOLS AND ABBREVIATIONS:
KEY...... INDICATION OF DIRECTION OR SOURCE OF HEAT LOAD WITH THE FOLLOWING
MEANING:
1........HEAT TRANSFER FROM DECK OVER
2........HEAT TRANSFER FROM DECK BELOW
3........HEAT TRANSFER FROM OUTBOARD BULKHEAD OR SHELL
4........HEAT TRANSFER FROM FORWARD BULKHEAD
5........HEAT TRANSFER FROM AFTER BULKHEAD
6........HEAT TRANSFER FROM INBOARD BULKHEAD
7........HEAT LOAD FORM LIGHTING
8........HEAT LOAD FROM EQUIPMENT
9........HEAT LOAD FROM PERSONNEL
T................. ROOM TEMPERATURE (DEGREES FAHRENHEIT)
To................ ADJACENT TEMPERATURE (DEGREES FAHRENHEIT) Td................ TEMPERATURE DIFFERENCE (DEGREES FAHRENHEIT)
U................. HEAT TRANSFER COEFFICIENT (BTU/HR/°F/SQ FT)
BTU............... BRITISH TERMAL UNIT
Hw................ HEATING ROOM LOAD (BTU/HR)
HR................ HOUR
°F................ DEGREES FAHRENHEIT
Hs................ SENSIBLE HEAT LOAD (BTU/HR) Hl................ LATENT HEAT LOAD (BTU/HR) Ht................ TOTAL HEAT LOAD (BTU/HR)
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 6 OF INDEX
3) U-KEY............. INDICATION OF BOUNDARY CONSTRUCTION IN ACCORDANCE WITH
(CONT) SNAME T&R BULLETIN NO. 4-7, "THERMAL INSULATION REPORT"
AS FOLLOWS:
N N N S S - D
WHERE: N N N ......... INSULATION KEY GIVEN IN SNAME 4-7.
S S .......... BOUNDRY CONDITION: "W" Τ INSIDE AIR TO WEATHER
"IN" Τ INSIDE AIR TO INSIDE AIR
"SEA" Τ INSIDE AIR TO SEAWATER
"S" Τ SOLAR
D ............. DIRECTION OF HEAT FLOW: "D" Τ HEAT FLOW DOWN
"U" Τ HEAT FLOW UP
"H" Τ HEAT FLOW HORIZONTAL
EXAMPLE: 55IN-H Τ INSULATION TYPE 55, INSIDE AIR TO INSIDE AIR, HORIZONTAL
HEAT FLOW
SQ FT............. SQUARE FEET
R/C............... RATE OF CHANGE IN MINUTES
CFM............... CUBIC FEET PER MINUTE
KW................ KILOWATTS
O.A............... OUTSIDE AIR
4) ROOM LOAD SHEETS ARE PRESENTED WITH THE FOLLOWING NUMBERING LOGIC:
SHEETS NUMBERED AS " xyz L ".........................................MASTER ROOM LOAD SHEET FOR EACH COMPARTMENT.
SHEETS NUMBERED AS " xyz L(A) ".........................................CONTINUATION OF MASTER ROOM LOAD SHEET NO. "xyzL" IF REQUIRED.
SHEETS NUMBERED AS " xyz E ".......................................EQUIPMENT LIST FOR MASTER ROOM LOAD SHEET NO. xyzL. THE TOTAL EQUIPMENT HEAT LOAD
IS SHOWN ON THE MASTER ROOM LOAD SHEET IN LINE HAVING KEY "8". IF THE TOTAL EQUIPMENT IN A PARTICULAR COMPARTMENT IS SMALL, THE EQUIPMENT IS LISTED ON THE MASTER ROOM LOAD SHEET ONLY, ON LINES HAVING KEY "8", AND A SHEET NUMBERED AS "xyzE" IS NOT PROVIDED.
SHEETS NUMBERED AS " xyz EQU ".......................................IN A/C SPACES, IF IT IS DETERMINED ON THE MASTER ROOM LOAD SHEET THAT THE AIR FLOW
IS DETERMINED BY THE MINIMUM RATE OF CHANGE AND NOT THE TEMPERATURE RISE, THE
FINAL EQUILIBRIUM ROOM TEMPERATURE IS DETERMINED USING THE LARGER AIR FLOW.
IF TEMPERATURE RISE DETERMINES AIR FLOW, A SHEET NUMBERED AS "xyzEQU" IS NOT GIVEN.
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 7 OF INDEX
5) EACH LAB CONTAINING HOODS SHALL BE EXHAUSTED WITH A DEDICATED EXHAUST SYSTEM WHICH SHALL BE A CONSTANTLY RUNNING SYSTEM. THIS EXHAUST SYSTEM SHALL SERVICE THE HOODS LOCATED IN THE SPACE AND SERVE AS THE SPACE EXHAUST SYSTEM REQUIRED BY U.S.C.G. FOR CHEMISTRY LABS. BY HAVING THE SPACE EXHAUST SYSTEM CONFIGURED TO ALSO SERVICE THE HOODS, THE SPACE INBALANCE, NORMALLY ENCOUNTERED WHEN THE EXHAUST HOOD IS ACTUATED, IS NEGATED.
THIS NOTE PERTAINS TO THE FOLLOWING SPACES: THE CHEMISTRY LAB; THE DRY LAB, THE FISH/WET LAB AND THE PSVTN ALCOVE.
THE OPERATION LOGIC FOR THE PORTABLE HOODS
IS SHOWN ON THE SKETCH SHOWN ON THE RIGHT ------>
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 8 OF INDEX
THE OPERATION LOGIC FOR THE LABCONCO FUME HOODS
IS SHOWN ON THE SKETCH SHOWN ON THE RIGHT ------>
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 9 OF INDEX
LIST OF SPACES (ALPHABETICAL ORDER)
SHT SPACE DECK FRAMES SHT SPACE DECK FRAMES
NO. NO.
060 ACOUSTIC/COMPUTER LAB MAIN 38-57 P 098 EOS 2ND 63-72 CL
106 AMR TANKTOP 39-49 P 043 ET SHOP 01 47-53 P
117 AMR TANKTOP 39-49 CL 070 EXERCISE RM T/S 2ND 19-22 S
102 BOW THRUSTER MACNY ROOM INNERBOTTOM 13-19 CL 071 EXERCISE ROOM 2ND 19-24 CL
001 BRIDGE 03 35-55 CL 040 FAN ROOM 01 37-47 CL
119 CENTERBOARD TRUNK VAR 39-45 CL 049 FAN ROOM MAIN 16-19 S
032 CG LOCKER 01 27-29 S 113 FREEZE STOREROOM MN 7-11 CL
080 CG LOCKER 2ND 21-23 P 052 GALLEY MAIN 23-31 S
109 CG LOCKER 02 45-47 CL 105 GENERAL STORES TANKTOP 32-39 S
059 CHEMISTRY LAB MAIN 31-44 S 065 HAZMATL/PAINT STORAGE MAIN 78-82 P
003 CHIEF ENGR. 02 29-37 P 018 HOSPITAL 02 50-56 S
004 CHIEF ENGR. T/S 02 35-37 P 019 HOSPITAL T/S 02 50-53 S
007 CHIEF SCIENTIST SR 02 29-37 S 057 HYDROGRAPHIC LAB MAIN 36-42 S
112 CHILL STOREROOM MN 11-16 P 068 LAUNDRY 2ND 7-19 S
041 CO2 ROOM 01 44-47 S 035 LINEN LOCKER 01 29-30 S
036 CONFERENCE ROOM 01 29-37 S 045 LINEN LOCKER 2ND 39-42 S
012 C.O. SR 02 39-45 S 108 LINEN LOCKER 02 44-45 P
021 DC LOCKER 02 53-56 P 110 LINEN LOCKER MAIN 47-49 S
023 DC LOCKER 01 10-14 CL 104 LOCKED STORES TANKTOP 29-32 S
024 DECK LOCKER 01 12-17 S 029 LOUNGE 01 19-29 S
066 DECK LOCKER MAIN 78-82 P 050 MESSROOM MAIN 19-38 CL
020 DECK TOILET 02 50-53 CL 107 MMR (LOWER) TANKTOP 49-72 CL
062 DECK TOILET MAIN 63-65 P 096 MMR (UPPER LEVEL) 2ND 49-63 CL
111 DECK TOILET MAIN 43-45 P 100 OCEANOGRAPHIC WINCH RM (LOWER)TANKTOP 68-82 CL
025 DIVE LOCKER 01 10-17 S 099 OCEANOGRAPHIC WINCH RM (UPPER)2ND 68-82 CL
103 DOMESTIC EQUIPMENT SPACE TANKTOP 29-39 CL 039 OFFICE SUITE 01 37-47 P
053 DRY LAB MAIN 47-58 CL 009 PASSAGE 02 37-56
048 DRY STORES MAIN 7-16 S 028 PASSAGE 01 19-49 CL
044 EMERGENCY GEN RM 01 56-63 CL
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 10 OF INDEX
NO. NO.
055 PASSAGE MAIN 36-47 CL 092 SR 2ND 44-49 P
074 PASSAGE 2ND 24-29 CL 094 SR 2ND 44-49 S
079 PASSAGE 2ND 29-39-CL 006 SR T/S 02 35-37 S
089 PASSAGE 2ND 39-49 CL 011 SR T/S 02 43-46 P
054 PSVTN ALCOVE MAIN 31-36 S 014 SR T/S 02 44-46 P
002 RADIO/CHART AREA 03 47-55 P 017 SR T/S 02 45-47 S
064 READY ROOM MAIN 70-78 P 027 SR T/S 01 21-23 P
022 REEFER MACH'Y ROOM 01 10-16 P 031 SR T/S 01 24-26 P
115 SCIENTIFIC FREEZER MN 58-63 S 034 SR T/S 01 30-32 P
046 SCIENTIFIC STORES MAIN -2-7 CL 038 SR T/S 01 33-35 P
069 SCIENTIFIC STORES 2ND 7-19 CL 042 SSS CONTROL BOOTH 01 41-44 S
114 SCIENTIST'S READY ROOM MAIN 56-64 CL 067 STEWARD STORES 2ND 7-11 S
051 SCULLERY MAIN 19-23 S 047 STORES PASSAGE MAIN 7-19 CL
005 SR 02 29-37 CL 097 TRANSDUCER RM (LOWER) INNERBOTTOM 23-29 CL
010 SR 02 37-44 P 116 TRANSDUCER RM (UPPER) TANKTOP 19-29 CL
015 SR 02 46-53 P 063 TRASH ROOM MAIN 65-70 P
016 SR 02 45-50 S 101 TRAWL WINCH ROOM 2ND 82-101 CL
026 SR 01 19-24 P 008 T/S 02 35-37 S
030 SR 01 24-28 P 013 T/S 02 42-44 S
033 SR 01 28-32 P 073 T/S 2ND 26-29 P
037 SR 01 33-37 P 076 T/S 2ND 26-29 S
072 SR 2ND 23-29 P 078 T/S 2ND 29-32 P
075 SR 2ND 24-29 S 082 T/S 2ND 31-34 S
077 SR 2ND 29-34 P 084 T/S 2ND 29-32 S
081 SR 2ND 31-39 S 086 T/S 2ND 36-39 P
083 SR 2ND 31-39 S 088 T/S 2ND 39-41 P
085 SR 2ND 34-39 P 091 T/S 2ND 39-41 S
087 SR 2ND 39-44 P 093 T/S 2ND 44-49 P
090 SR 2ND 39-44 S
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 11 OF INDEX
NO. NO.
095 T/S 2ND 46-49 S
118 WEATHER PASSAGE 01 14-19 CL
061 WET/FISH LAB MAIN 58-82 S
056 (SHEET NOT USED) 0
058 (SHEET NOT USED) 0
JOB:
A NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 12 OF INDEX
A/C SYSTEM SUMMARY
CFM SENSIBLE LOAD TOTAL LOAD CHILLED WATER FLOW
SPACE SERVED SYSTEM NO. TOTAL OUTSIDE RETURN BTU/HR TONS BTU/HR TONS (3.6 gpm/TON)
AIR Tin (°F) Tout (°F) gpm
OUTSIDE AIR SUPPLY AC1 2,865 2865 0 76,736 6.4 167,442 14.0 45.0 51.7 50.2
EOS AC2 5,080 200 4,880 287,372 23.9 303,236 25.3 45.0 51.7 91.0
VARIOUS ROOM FCU'S N/A N/A N/A SEE DWG 943,939 78.7 45.0 51.2 304.0
#M282-512-FV03-001-00
FOR COMPLETE LISTING
OF ALL FCU LOADS
HAZMATL/PAINT STORAGE AC3 200 145 55 5,180 0.4 11,076 0.9 45.0 51.7 3.3
OUTSIDE AIR SUPPLY AC4 5,750 5750 0 154,008 12.8 336,052 28.0 45.0 51.7 100.8
TOTAL = 1,761,745 146.8 549.3
JOB:
TWO (2) A/C CHILLED WATER PLANTS ARE REQUIRED. A NOAA FRV40 CLASS 63m VESSEL REV 0 EACH PLANT HAS A CAPACITY EQUAL TO 51.1% OF THE CONNECTED LOAD FSCM: DRAWING NO.:
EACH PLANT HAS A CAPACITY = 75 TONS. M282-512-FV01
SCALE: N/A SWBS: SHT NO.: 13 OF INDEX
VENTILATION SYSTEM SUMMARY
SYSTEM SHT. NO. SPACE DECK FRAME CFM SYSTEM SHT. NO. SPACE DECK FRAME CFM
E 01 027L SR T/S 01 21-23 P 55
E 01 031L SR T/S 01 24-26 P 55 E 06 114L SCIENTIST'S READY ROOM MAIN 56-64 CL 75
E 01 032L CG LOCKER 01 27-29 S 35 E 06 060L ACOUSTIC/COMPUTER LAB MAIN 38-57 P 245
E 01 034L SR T/S 01 30-32 P 55 E 06 062L DECK TOILET MAIN 63-65 P 65
E 01 035L LINEN LOCKER 01 29-30 S 35 E 06 110L LINEN LOCKER MAIN 47-49 S 35
E 01 038L SR T/S 01 33-35 P 55 E 06 111L DECK TOILET MAIN 43-45 P 65
E 01 040L FAN ROOM 01 37-47 CL 130 E 06 064L READY ROOM MAIN 70-78 P 95
E 01 041L CO2 ROOM 01 44-47 S 85 E 06 066L DECK LOCKER MAIN 78-82 P 35
E 01 004L CHIEF ENGR. T/S 02 35-37 P 50 E 06 050L MESSROOM MAIN 19-38 CL 385
E 01 006L SR T/S 02 35-37 S 50 TOTAL = 1,000
E 01 008L T/S 02 35-37 S 50
E 01 011L SR T/S 02 43-46 P 50
E 01 013L T/S 02 42-44 S 50 E 07 059L CHEMISTRY LAB MAIN 31-44 S 1,785
E 01 014L SR T/S 02 44-46 P 50 CONSISTING OF THE FOLLOWING: TOTAL = 1,785
E 01 017L SR T/S 02 45-47 S 50 1) 1050 CFM CONNECTION FOR (3) GFE PORTABLE HOODS
E 01 019L HOSPITAL T/S 02 50-53 S 65 2) 735 CONNECTION FOR FUME HOOD
E 01 020L DECK TOILET 02 50-53 CL 45
E 01 021L DC LOCKER 02 53-56 P 35 E 08 061L WET/FISH LAB MAIN 58-82 S 1,520
E 01 108L LINEN LOCKER 02 44-45 P 35 CONSISTING OF THE FOLLOWING: TOTAL = 1,520
E 01 109L CG LOCKER 02 45-47 CL 35 1) 735 CFM CONNECTION FOR FUME HOOD
E 01 029L LOUNGE 01 19-29 S 170 2) 785 CFM SPACE EXH TERMINAL
E 01 036L CONFERENCE ROOM 01 29-37 S 120
E 01 039L OFFICE SUITE 01 37-47 P 115 E 09 065L HAZMATL/PAINT STORAGE MAIN 78-82 P 145
E 01 043L ET SHOP 01 47-53 P 40 TOTAL = 145
TOTAL = 1,515
E 10 067L STEWARD STORES 2ND 7-11 S 645
E 02 022L REEFER MACH'Y ROOM 01 10-16 P 1,400 E 10 068L LAUNDRY 2ND 7-19 S 660
TOTAL = 1,400 E 10 069L SCIENTIFIC STORES 2ND 7-19 CL 1,325
E 10 049L FAN ROOM MAIN 16-19 S 260
E 03 023L DC LOCKER 01 10-14 CL 285 E 10 047L STORES PASSAGE MAIN 7-19 CL 105
E 03 024L DECK LOCKER 01 12-17 S 185 TOTAL = 2,995
E 03 025L DIVE LOCKER 01 10-17 S 785
TOTAL = 1,255
E 04 051L SCULLERY MAIN 19-23 S 775
E 04 052L GALLEY MAIN 23-31 S 2,800
TOTAL = 3,575
E 05 053L DRY LAB MAIN 47-58 CL 1,050 A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
CONSISTING OF THE FOLLOWING: TOTAL = 1,050
1) 1050 CFM CONNECTION FOR GFE PORTABLE HOODS FSCM:
2) 0 CFM SPACE EXH TERMINAL DRAWING NO.:
M282-512-FV01
SCALE: SWBS: SHT NO.:
N/A 1 VENT
CFM
E 11 045L LINEN LOCKER 2ND 39-42 S 35 S 01 044L EMERGENCY GEN RM 01 56-63 CL 2,110
E 11 070L EXERCISE RM T/S 2ND 19-22 S 90 TOTAL = 2,110
E 11 073L T/S 2ND 26-29 P 65
E 11 076L T/S 2ND 26-29 S 65 S 02 096L MMR (UPPER LEVEL) 2ND 49-63 CL 11,490
E 11 078L T/S 2ND 29-32 P 65 S 02 107L MMR (LOWER) TANKTOP 49-72 CL 27,480
E 11 080L CG LOCKER 2ND 21-23 P 50 TOTAL = 38,970
E 11 082L T/S 2ND 31-34 S 65
E 11 084L T/S 2ND 29-32 S 65 S 03 096L MMR (UPPER LEVEL) 2ND 49-63 CL 11,490
E 11 086L T/S 2ND 36-39 P 65 S 03 107L MMR (LOWER) TANKTOP 49-72 CL 27,480
E 11 088L T/S 2ND 39-41 P 65 TOTAL = 38,970
E 11 091L T/S 2ND 39-41 S 65
E 11 093L T/S 2ND 44-49 P 65 S 04 117L AMR TANKTOP 39-49 CL 1,320
E 11 095L T/S 2ND 46-49 S 65 TOTAL = 1,320
TOTAL = 825
E 12 102L BOW THRUSTER MACNY ROOM INNERBOTTOM13-19 CL 4,180 S 05 099L OCEANOGRAPHIC WINCH RM (UPPER)2ND 68-82 CL 6,815
TOTAL = 4,180 S 05 100L OCEANOGRAPHIC WINCH RM (LOWER)TANKTOP 68-82 CL 275
TOTAL = 7,090
E 13 103L DOMESTIC EQUIPMENT SPACE TANKTOP 29-39 CL 4,940 S 06 101L TRAWL WINCH ROOM 2ND 82-101 CL 2,770
E 13 104L LOCKED STORES TANKTOP 29-32 S 95 TOTAL = 2,770
E 13 105L GENERAL STORES TANKTOP 32-39 S 250
TOTAL = 5,285 S 07 102L BOW THRUSTER MACNY ROOMINNERBOTTOM13-19 CL 4,180
TOTAL = 4,180
E 14 054L PSVTN ALCOVE MAIN 31-36 S 735
CONSISTING OF THE FOLLOWING: TOTAL = 735
1) 735 CFM CONNECTION FOR FUME HOOD
E 15 SYSTEM NOT USED ON M282
E 16 SYSTEM NOT USED ON M282
E 17 063L TRASH ROOM MAIN 65-70 P 1,165
TOTAL = 1,165
E 18 117L AMR TANKTOP 39-49 CL 1,320
TOTAL = 1,320 A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM:
DRAWING NO.:
M282-512-FV01
N/A 2 VENT
OUTSIDE AIR SYSTEM
S 08 097L TRANSDUCER RM (LOWER) INNERBOTTOM23-29 CL 395 AC 01 001L BRIDGE 03 35-55 CL 260 S 08 116L TRANSDUCER RM (UPPER) TANKTOP 19-29 CL 540 AC 01 009L PASSAGE 02 37-56 530
TOTAL = 935 AC 01 028L PASSAGE 01 19-49 CL 735
AC 01 040L FAN ROOM 01 37-47 CL 130
S 09 046L SCIENTIFIC STORES MAIN -2-7 CL 1,420 AC 01 050L MESSROOM MAIN 19-38 CL 385
TOTAL = 1,420 AC 01 074L PASSAGE 2ND 24-29 CL 270
AC 01 079L PASSAGE 2ND 29-39-CL 260
AC 01 089L PASSAGE 2ND 39-49 CL 295
TA 01 022L REEFER MACH'Y ROOM 01 10-16 P 1,400 TOTAL = 2,865
TOTAL = 1,400
AC 02 098L EOS 2ND 63-72 CL 5,080
TA 02 067L STEWARD STORES 2ND 7-11 S 645 TOTAL = 5,080
TA 02 068L LAUNDRY 2ND 7-19 S 660
TA 02 069L SCIENTIFIC STORES 2ND 7-19 CL 1,325 AC 03 065L HAZMATL/PAINT STORAGE MAIN 78-82 P 200
TA 02 049L FAN ROOM MAIN 16-19 S 260 TOTAL = 200
TA 02 047L OA for STORES PASSAGE MAIN 7-19 CL 65 OUTSIDE AIR SYSTEM TA 02 048L OA for DRY STORES MAIN 7-16 S 40 AC 04 053L DRY LAB MAIN 47-58 CL 1,050
TOTAL = 2,995 AC 04 054L PSVTN ALCOVE MAIN 31-36 S 735
AC 04 059L CHEMISTRY LAB MAIN 31-44 S 1,785
AC 04 061L WET/FISH LAB MAIN 58-82 S 1,520
AC 04 064L READY ROOM MAIN 70-78 P 95
TA 03 051L SCULLERY MAIN 19-23 S 775 AC 04 057L HYDROGRAPHIC LAB MAIN 36-42 S 80
TA 03 052L GALLEY MAIN 23-31 S 2,800 AC 04 055L PASSAGE MAIN 36-47 CL 485
TOTAL = 3,575 TOTAL = 5,750
TA 04 103L DOMESTIC EQUIPMENT SPACE TANKTOP 29-39 CL 4,940
TA 04 104L LOCKED STORES TANKTOP 29-32 S 95
TA 04 105L GENERAL STORES TANKTOP 32-39 S 250
TOTAL = 5,285
TA 05 063L TRASH ROOM MAIN 65-70 P 2,050 / 1,468**
(Nat Sup Sys) TOTAL = 2,050 / 1,468**
** CFM SHOWN ABOVE IS AS FOLLOWS:
2,050 CFM W/ FAN FULL SPEED + COMB AIR
1,468 CFM W/ FAN 1/2 SPEED + COMB AIR
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM:
DRAWING NO.:
M282-512-FV01
N/A 3 VENT
A/C SYSTEM AC1 COOLING AND HEATING SUMMARY
SHT SPACE DECK FRAMES CALC RM LOAD (BTU/HR) A/C MINIMUM O.A. CALCULATIONS RM TEMP FINAL NO. Hs Hl Ht SUPPLY R/C (50CFM/PER MAX) NUMBER OF PEOPLE MIN O.A. @ MAX COOL R/C
CFM VOL (FT3) MIN R/C CFM # PLPE CFM/PER CFM (MAX R/C OR PLPE) w/o REHEAT (MIN)
N/A VARIOUS VARIOUS VARIOUS N/A N/A N/A 2,865 N/A 30 0 N/A 15 0 77 N/A
BASED
ON
R/C
BASED
ON
PERSONNEL
TOTAL = 2,865 MINIMUM O.A. BASED ON R/C OR # OF PEOPLE = 0
MINIMUM O.A. BASED ON AREA EXH. REQ'TS = 2,865
FINAL OUTSIDE AIR REQUIRED (MAX OF ABOVE) = 2,865
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 1 A/C
A/C SYSTEM AC1 COOLING AND HEATING SUMMARY (CONT)
SHEET REHEATER SUMMER LIGHT LOAD ANALYSIS HEATER WINTER ANALYSIS HEATER NOTE #2 FINAL ROOM LOAD FINAL NO. LIGHT LOAD SUPPLY NOTE #1 REHTR CAP ROOM RM LOAD TEMP TEMP HEATER CAP FINAL SIZE REQUIRED DELTA BELOW BTU/HR CLG RM
BTU/HR TEMP (°F) BELOW (KW) TEMP °F BTU/HR °F IN °F OUT (KW) °F IN °F OUT (KW) TEMP BTU/HR Hs Hl Ht TEMP °F N/A N/A N/R N/R N/R 9.0 70.0 55.35 9.0 70.0 55.35 61.0 N/A N/A N/A N/A 77.0
FINAL TOTALS = 0 0 0
NOTES: 1.REQUIRED ROOM SUPPLY TEMPERATURE (°F) TO MAINTAIN MINIMUM OF 72°F
WITH ROOM AT LIGHT LOAD. A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
2.REHEAT REQUIRED AT MAXIMUM COOLING TO MAINTAIN THE SPACE FSCM: DRAWING NO.:
AT A MINIMUM TEMP OF 72°F WHEN CFM IS A FUNCTION OF THE MINIMUM M282-512-FV01
RATE OF CHANGE AS OPPOSED TO THE ROOM SENSIBLE LOAD. SCALE: SWBS: SHT NO.:
3.SUMMER REHEATING IS NOT REQUIRED SINCE UNIT SERVES ONE ROOM ONLY N/A 1A A/C
A/C SYSTEM AC1 SUMMARY -- PSYCHROMETRICS
COOLING CFM CFM CFM
Hs Hl Ht TOTAL O.A. RETURN
TOTAL OF ROOMS = 0 0 0 2,865 2,865 0
MAXIMUM LENGTH OF SUPPLY DUCT = 80 FT ---> SUPPLY DUCT TEMP RISE = 2.00 °F (BASED ON EQ #19 OF SNAME T&R 4-16 W/2.00°F MIN) MAXIMUM LENGTH OF RETURN DUCT = 0 FT ---> RET DUCT AIR TEMP RISE = 0.00 °F (BASED ON EQ #20 OF SNAME T&R 4-16) PASSAGE RISE (WHEN ALSO USED FOR R.A.) = 0.00 °F ---> TOTAL R.A. RISE = 0.00 °F (NO RETURN AIR - ALL OUTSIDE AIR SYSTEM) FAN PRESSURE = 6.00 "W.G.--> FAN HEAT RISE = 4.80 °F (BASED ON EQ #18 OF SNAME T&R 4-16 W/MOTOR IN AIR STREAM)
AVERAGE ROOM TEMP = 77.00 °F
SUPPLY AIR TEMP TO ROOM = 77.00 °F
PSY DRY BULB RELATIVE WET BULB HUMIDITY
KEY POINT DESCRIPTION DEW POINT TEMP HUMIDITY ENTHALPY TEMP RATIO
# °F °F % (BTU/lbm) °F COIL SENSIBLE LOAD = 76,736 BTU/HR = 6.4 TONS 1 CONDITIONS LEAVING COIL: 69.00 70.20 95.00% 33.37 69.14 0.01513 COIL TOTAL LOAD = 167,442 BTU/HR = 14.0 TONS
2 CONDITIONS LEAVING FAN: 69.00 75.00 80.65% 34.53 70.50 0.01513
3 CONDITIONS ENTERING ROOM: 69.00 77.00 75.41% 35.01 71.06 0.01513
4 AVERAGE ROOM CONDITIONS: 69.00 77.00 75.41% 35.01 71.06 0.01508 HEATER ANALYSIS 5 RETURN AIR CONDITIONS: 69.00 77.00 75.41% 35.01 71.06 0.01508 OUTSIDE TEMPERATURE: 0.00 °F 6 OUTSIDE AIR CONDITIONS: 79.00 95.00 59.54% 46.36 82.40 0.02135 ENTERING TEMP (w/Fan Heat Rise): 8.97 °F 7 CONDITIONS ENTERING COIL: 79.00 95.00 59.54% 46.36 82.40 0.02135 LEAVING TEMPERATURE: 70.00 °F
HEATER CAPACITY: 188,854 BTU/HR
SUMMARY OF LOADS Hs Ht 55.35 KW
BTU/HR TONS BTU/HR TONS
ROOM LOAD: 0 0.00 0 0.00 NOTE: ONLY ONE HEATER REQUIRED; SYSTEM SERVES ONLY ONE SPACE.
FAN LOAD: 14,852 1.24 14,852 1.24
SUPPLY DUCT LOAD: 6,188 0.52 6,188 0.52
RETURN AIR LOAD: 0 0.00 0 0.00
OUTSIDE AIR LOAD: 55,696 4.64 146,401 12.20
TOTAL: 76,736 6 167,442 14
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 1B A/C
PSYCHROMETRIC CHART - A/C SYSTEM #AC1
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
SCALE: SWBS: SHT NO.:
N/A 1C A/C
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
4&5321
DRY BULB TEMPERATURE (°F)
H U
M
ID
IT
Y
R A
T
IO
(l bs
M O
IS
T
U R
E /lb
D R
Y A
IR
SA
TU
RA
TIO
N
CU
RV
E
R .H
R .H
R .H
20% R.H.
A/C SYSTEM AC2 COOLING AND HEATING SUMMARY
NO. Hs Hl Ht SUPPLY R/C (50CFM/PER MAX) NUMBER OF PEOPLE MIN O.A. @ MAX COOL R/C
CFM VOL (FT3) MIN R/C CFM # PLPE CFM/PER CFM (MAX R/C OR PLPE) w/o REHEAT (MIN)
098L EOS 2ND 63-72 CL 137,100 2,060 139,160 5,080 6,910 20 200 4 12 48 80 1.4
BASED
ON
R/C
BASED
ON
PERSONNEL
TOTAL = 5,080 MINIMUM O.A. BASED ON R/C OR # OF PEOPLE = 200
MINIMUM O.A. BASED ON AREA EXH. REQ'TS = N/A
FINAL OUTSIDE AIR REQUIRED (MAX OF ABOVE) = 200
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 2 A/C
A/C SYSTEM AC2 COOLING AND HEATING SUMMARY (CONT)
SHEET REHEATER SUMMER LIGHT LOAD ANALYSIS HEATER WINTER ANALYSIS HEATER NOTE #2 FINAL ROOM LOAD FINAL NO. LIGHT LOAD SUPPLY NOTE #1 REHTR CAP ROOM RM LOAD TEMP TEMP HEATER CAP FINAL SIZE REQUIRED DELTA BELOW BTU/HR CLG RM
BTU/HR TEMP (°F) BELOW (KW) TEMP °F BTU/HR °F IN °F OUT (KW) °F IN °F OUT (KW) TEMP BTU/HR Hs Hl Ht TEMP °F 098L 4,688 N/R N/R N/R 70 9,278 67.2 71.7 7.15 67.2 71.7 7.15 4.4 N/A 137,100 2,060 139,160 80.0
FINAL TOTALS = 137,100 2,060 139,160
NOTES: 1.REQUIRED ROOM SUPPLY TEMPERATURE (°F) TO MAINTAIN MINIMUM OF 72°F
WITH ROOM AT LIGHT LOAD. A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
2.REHEAT REQUIRED AT MAXIMUM COOLING TO MAINTAIN THE SPACE FSCM: DRAWING NO.:
AT A MINIMUM TEMP OF 72°F WHEN CFM IS A FUNCTION OF THE MINIMUM M282-512-FV01
3.SUMMER REHEATING IS NOT REQUIRED SINCE UNIT SERVES ONE ROOM ONLY N/A 2A A/C
A/C SYSTEM AC2 SUMMARY -- PSYCHROMETRICS
Hs Hl Ht TOTAL O.A. RETURN
TOTAL OF ROOMS = 137,100 2,060 139,160 5,080 200 4,880
MAXIMUM LENGTH OF SUPPLY DUCT = 0 FT ---> SUPPLY DUCT TEMP RISE = 2.00 °F (BASED ON EQ #19 OF SNAME T&R 4-16 W/2.00°F MIN) MAXIMUM LENGTH OF RETURN DUCT = 0 FT ---> RET DUCT AIR TEMP RISE = 0.00 °F (BASED ON EQ #20 OF SNAME T&R 4-16) PASSAGE RISE (WHEN ALSO USED FOR R.A.) = 0.00 °F ---> TOTAL R.A. RISE = 0.00 °F (BASED ON SAMPLE CASE #39 OF SNAME T&R 4-16) FAN PRESSURE = 3.00 "W.G.--> FAN HEAT RISE = 2.40 °F (BASED ON EQ #18 OF SNAME T&R 4-16 W/MOTOR IN AIR STREAM)
AVERAGE ROOM TEMP = 80.0 °F
SUPPLY AIR TEMP TO ROOM = 55.00 °F
SCR LOAD INTO RETURN AIR = 122,832 BTU/HR
RETURN AIR RISE PER SCR LOAD = 23.31 °F
PSY DRY BULB RELATIVE WET BULB HUMIDITY
KEY POINT DESCRIPTION DEW POINT TEMP HUMIDITY ENTHALPY TEMP RATIO
# °F °F % (BTU/lbm) °F COIL SENSIBLE LOAD = 287,372 BTU/HR = 23.9 TONS 1 CONDITIONS LEAVING COIL: 49.00 50.60 95.00% 20.21 49.83 0.00745 COIL TOTAL LOAD = 303,236 BTU/HR = 25.3 TONS
2 CONDITIONS LEAVING FAN: 49.00 53.00 86.88% 20.79 50.86 0.00745
3 CONDITIONS ENTERING ROOM: 49.00 55.00 80.68% 21.27 51.70 0.00745
4 AVERAGE ROOM CONDITIONS: 49.00 80.00 16.34% 27.36 68.63 0.00746 HEATER ANALYSIS 5 RETURN AIR CONDITIONS: 49.00 103.31 34.09% 32.95 61.29 0.00746 OUTSIDE TEMPERATURE: 0.00 °F 6 OUTSIDE AIR CONDITIONS: 79.00 95.00 59.54% 46.36 82.40 0.02135 ENTERING TEMPERATURE: 67.24 °F 7 CONDITIONS ENTERING COIL: 51.00 102.98 17.71% 33.48 69.27 0.00821 LEAVING TEMPERATURE: 71.69 °F
HEATER CAPACITY: 24,398 BTU/HR
SUMMARY OF LOADS Hs Ht 7.15 KW
BTU/HR TONS BTU/HR TONS
ROOM LOAD: 137,100 11.42 139,160 11.60 NOTE: ONLY ONE HEATER REQUIRED; SYSTEM SERVES ONLY ONE SPACE.
FAN LOAD: 13,167 1.10 13,167 1.10
SUPPLY DUCT LOAD: 10,973 0.91 10,973 0.91
RETURN AIR LOAD: 122,832 10.24 122,832 10.24
OUTSIDE AIR LOAD: 3,240 0.27 17,104 1.43
TOTAL: 287,312 24 303,236 25
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 2B A/C
PSYCHROMETRIC CHART - A/C SYSTEM #AC2
FSCM: DRAWING NO.:
M282-512-FV01
SCALE: SWBS: SHT NO.:
N/A 2C A/C
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
1 2 3 4&5
DRY BULB TEMPERATURE (°F)
H U
M
ID
IT
Y
R A
T
IO
(l bs
M O
IS
T
U R
E /lb
D R
Y A
IR
SA
TU
RA
TIO
N
CU
RV
E
R .H
R .H
R .H
A/C SYSTEM AC3 COOLING AND HEATING SUMMARY
NO. Hs Hl Ht SUPPLY R/C (50CFM/PER MAX) NUMBER OF PEOPLE MIN O.A. @ MAX COOL R/C
CFM VOL (FT3) MIN R/C CFM # PLPE CFM/PER CFM (MAX R/C OR PLPE) w/o REHEAT (MIN)
065L HAZMATL/PAINT STORAGE MAIN 78-82 P 2,038 0 2,038 200 576 30 0 0 15 0 79 2.9
BASED
ON
R/C
BASED
ON
PERSONNEL
TOTAL = 200 MINIMUM O.A. BASED ON R/C OR # OF PEOPLE = 0
MINIMUM O.A. BASED ON AREA EXH. REQ'TS = 145
FINAL OUTSIDE AIR REQUIRED (MAX OF ABOVE) = 145
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01-001-00
N/A 3 A/C
A/C SYSTEM AC3 COOLING AND HEATING SUMMARY (CONT)
SHEET REHEATER SUMMER LIGHT LOAD ANALYSIS HEATER WINTER ANALYSIS HEATER NOTE #2 FINAL ROOM LOAD FINAL NO. LIGHT LOAD SUPPLY NOTE #1 REHTR CAP ROOM RM LOAD TEMP TEMP HEATER CAP FINAL SIZE REQUIRED DELTA BELOW BTU/HR CLG RM
BTU/HR TEMP (°F) BELOW (KW) TEMP °F BTU/HR °F IN °F OUT (KW) °F IN °F OUT (KW) TEMP BTU/HR Hs Hl Ht TEMP °F 065L 803 N/R N/R N/R 55 1,398 19.3 61.9 2.70 19.3 61.9 2.70 42.6 N/A 2,038 0 2,038 78.8
FINAL TOTALS = 2,038 0 2,038
NOTES: 1.REQUIRED ROOM SUPPLY TEMPERATURE (°F) TO MAINTAIN MINIMUM OF 72°F
WITH ROOM AT LIGHT LOAD. A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
2.REHEAT REQUIRED AT MAXIMUM COOLING TO MAINTAIN THE SPACE FSCM: DRAWING NO.:
AT A MINIMUM TEMP OF 72°F WHEN CFM IS A FUNCTION OF THE MINIMUM M282-512-FV01-001-00
3.SUMMER REHEATING IS NOT REQUIRED SINCE UNIT SERVES ONE ROOM ONLY N/A 3A A/C
A/C SYSTEM AC3 SUMMARY -- PSYCHROMETRICS
Hs Hl Ht TOTAL O.A. RETURN
TOTAL OF ROOMS = 2,038 0 2,038 200 145 55
MAXIMUM LENGTH OF SUPPLY DUCT = 2 FT ---> SUPPLY DUCT TEMP RISE = 2.00 °F (BASED ON EQ #19 OF SNAME T&R 4-16 W/2.00°F MIN) MAXIMUM LENGTH OF RETURN DUCT = 0 FT ---> RET DUCT AIR TEMP RISE = 0.00 °F (BASED ON EQ #20 OF SNAME T&R 4-16) PASSAGE RISE (WHEN ALSO USED FOR R.A.) = 0.00 °F ---> TOTAL R.A. RISE = 0.00 °F (BASED ON SAMPLE CASE #39 OF SNAME T&R 4-16) FAN PRESSURE = 1.00 "W.G.--> FAN HEAT RISE = 0.80 °F (BASED ON EQ #18 OF SNAME T&R 4-16 W/MOTOR IN AIR STREAM)
AVERAGE ROOM TEMP = 78.8 °F
SUPPLY AIR TEMP TO ROOM = 69.37 °F
PSY DRY BULB RELATIVE WET BULB HUMIDITY
KEY POINT DESCRIPTION DEW POINT TEMP HUMIDITY ENTHALPY TEMP RATIO
# °F °F % (BTU/lbm) °F COIL SENSIBLE LOAD = 5,180 BTU/HR = 0.4 TONS 1 CONDITIONS LEAVING COIL: 65.00 66.57 95.00% 30.50 65.56 0.013 COIL TOTAL LOAD = 11,076 BTU/HR = 0.9 TONS
2 CONDITIONS LEAVING FAN: 65.00 67.37 92.38% 30.69 65.81 0.013
3 CONDITIONS ENTERING ROOM: 65.00 69.37 86.18% 31.17 66.43 0.013
4 AVERAGE ROOM CONDITIONS: 65.00 78.80 62.59% 33.44 69.22 0.013 HEATER ANALYSIS
5 RETURN AIR CONDITIONS: 65.00 78.80 62.59% 33.44 69.22 0.013 OUTSIDE TEMPERATURE: 0.00 °F 6 OUTSIDE AIR CONDITIONS: 79.00 95.00 59.54% 46.36 82.40 0.021 ENTERING TEMPERATURE: 19.25 °F 7 CONDITIONS ENTERING COIL: 75.00 90.55 61.46% 42.81 79.17 0.019 LEAVING TEMPERATURE: 61.87 °F
HEATER CAPACITY: 9,206 BTU/HR
SUMMARY OF LOADS Hs Ht 2.70 KW
BTU/HR TONS BTU/HR TONS
ROOM LOAD: 2,038 0.17 2,038 0.17 NOTE: ONLY ONE HEATER REQUIRED; SYSTEM SERVES ONLY ONE SPACE.
FAN LOAD: 173 0.01 173 0.01
SUPPLY DUCT LOAD: 432 0.04 432 0.04
RETURN AIR LOAD: 0 0.00 0 0.00
OUTSIDE AIR LOAD: 2,537 0.21 8,433 0.70
TOTAL: 5,180 0 11,076 1
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01-001-00
N/A 3B A/C
PSYCHROMETRIC CHART - A/C SYSTEM #AC3
FSCM: DRAWING NO.:
M282-512-FV01-001-00
SCALE: SWBS: SHT NO.:
N/A 3C A/C
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
1&2 3 4&5
DRY BULB TEMPERATURE (°F)
H U
M
ID
IT
Y
R A
T
IO
(l bs
M O
IS
T
U R
E /lb
D R
Y A
IR
SA
TU
RA
TIO
N
CU
RV
E
R .H
R .H
R .H
A/C SYSTEM AC4 COOLING AND HEATING SUMMARY
NO. Hs Hl Ht SUPPLY R/C (50CFM/PER MAX) NUMBER OF PEOPLE MIN O.A. @ MAX COOL R/C
CFM VOL (FT3) MIN R/C CFM # PLPE CFM/PER CFM (MAX R/C OR PLPE) w/o REHEAT (MIN)
N/A VARIOUS VARIOUS VARIOUS N/A N/A N/A 5,750 N/A 30 0 N/A 15 0 77 N/A
BASED
ON
R/C
BASED
ON
PERSONNEL
TOTAL = 5,750 MINIMUM O.A. BASED ON R/C OR # OF PEOPLE = 0
MINIMUM O.A. BASED ON AREA EXH. REQ'TS = 5,750
FINAL OUTSIDE AIR REQUIRED (MAX OF ABOVE) = 5,750
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 4 A/C
A/C SYSTEM AC4 COOLING AND HEATING SUMMARY (CONT)
SHEET REHEATER SUMMER LIGHT LOAD ANALYSIS HEATER WINTER ANALYSIS HEATER NOTE #2 FINAL ROOM LOAD FINAL NO. LIGHT LOAD SUPPLY NOTE #1 REHTR CAP ROOM RM LOAD TEMP TEMP HEATER CAP FINAL SIZE REQUIRED DELTA BELOW BTU/HR CLG RM
BTU/HR TEMP (°F) BELOW (KW) TEMP °F BTU/HR °F IN °F OUT (KW) °F IN °F OUT (KW) TEMP BTU/HR Hs Hl Ht TEMP °F N/A N/A N/R N/R N/R 4.5 70.0 119.27 4.5 70.0 119.27 65.5 N/A N/A N/A N/A 77.0
FINAL TOTALS = 0 0 0
NOTES: 1.REQUIRED ROOM SUPPLY TEMPERATURE (°F) TO MAINTAIN MINIMUM OF 72°F
WITH ROOM AT LIGHT LOAD. A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
2.REHEAT REQUIRED AT MAXIMUM COOLING TO MAINTAIN THE SPACE FSCM: DRAWING NO.:
AT A MINIMUM TEMP OF 72°F WHEN CFM IS A FUNCTION OF THE MINIMUM M282-512-FV01
3.SUMMER REHEATING IS NOT REQUIRED SINCE UNIT SERVES ONE ROOM ONLY N/A 4A A/C
A/C SYSTEM AC4 SUMMARY -- PSYCHROMETRICS
Hs Hl Ht TOTAL O.A. RETURN
TOTAL OF ROOMS = 0 0 0 5,750 5,750 0
MAXIMUM LENGTH OF SUPPLY DUCT = 80 FT ---> SUPPLY DUCT TEMP RISE = 2.00 °F (BASED ON EQ #19 OF SNAME T&R 4-16 W/2.00°F MIN) MAXIMUM LENGTH OF RETURN DUCT = 0 FT ---> RET DUCT AIR TEMP RISE = 0.00 °F (BASED ON EQ #20 OF SNAME T&R 4-16) PASSAGE RISE (WHEN ALSO USED FOR R.A.) = 0.00 °F ---> TOTAL R.A. RISE = 0.00 °F (NO RETURN AIR - ALL OUTSIDE AIR SYSTEM) FAN PRESSURE = 6.00 "W.G.--> FAN HEAT RISE = 4.80 °F (BASED ON EQ #18 OF SNAME T&R 4-16 W/MOTOR IN AIR STREAM)
AVERAGE ROOM TEMP = 77.00 °F
SUPPLY AIR TEMP TO ROOM = 77.00 °F
PSY DRY BULB RELATIVE WET BULB HUMIDITY
KEY POINT DESCRIPTION DEW POINT TEMP HUMIDITY ENTHALPY TEMP RATIO
# °F °F % (BTU/lbm) °F COIL SENSIBLE LOAD = 154,008 BTU/HR = 12.8 TONS 1 CONDITIONS LEAVING COIL: 69.00 70.20 95.00% 33.37 69.14 0.01513 COIL TOTAL LOAD = 336,052 BTU/HR = 28.0 TONS
2 CONDITIONS LEAVING FAN: 69.00 75.00 80.65% 34.53 70.50 0.01513
3 CONDITIONS ENTERING ROOM: 69.00 77.00 75.41% 35.01 71.06 0.01513
4 AVERAGE ROOM CONDITIONS: 69.00 77.00 75.41% 35.01 71.06 0.01508 HEATER ANALYSIS 5 RETURN AIR CONDITIONS: 69.00 77.00 75.41% 35.01 71.06 0.01508 OUTSIDE TEMPERATURE: 0.00 °F 6 OUTSIDE AIR CONDITIONS: 79.00 95.00 59.54% 46.36 82.40 0.02135 ENTERING TEMP (w/Fan Heat Rise): 4.47 °F 7 CONDITIONS ENTERING COIL: 79.00 95.00 59.54% 46.36 82.40 0.02135 LEAVING TEMPERATURE: 70.00 °F
HEATER CAPACITY: 406,960 BTU/HR
SUMMARY OF LOADS Hs Ht 119.27 KW
BTU/HR TONS BTU/HR TONS
ROOM LOAD: 0 0.00 0 0.00 NOTE: ONLY ONE HEATER REQUIRED; SYSTEM SERVES ONLY ONE SPACE.
FAN LOAD: 29,808 2.48 29,808 2.48
SUPPLY DUCT LOAD: 12,420 1.04 12,420 1.03 4.467
RETURN AIR LOAD: 0 0.00 0 0.00
OUTSIDE AIR LOAD: 111,780 9.32 293,824 24.49
TOTAL: 154,008 13 336,052 28
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
M282-512-FV01
N/A 4B A/C
PSYCHROMETRIC CHART - A/C SYSTEM #AC4
FSCM: DRAWING NO.:
M282-512-FV01
SCALE: SWBS: SHT NO.:
N/A 4C A/C
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
20 40 60 80 100 120 140
0.01
0.02
0.03
0.04
0.05
4&5321
DRY BULB TEMPERATURE (°F)
H U
M
ID
IT
Y
R A
T
IO
(l bs
M O
IS
T
U R
E /lb
D R
Y A
IR
SA
TU
RA
TI
O N
CU
RV
E
R .H
R .H
R .H
20% R.H.
ADJUST SUPPLY TEMP TO MATCH R/C CFM (YES/NO): NO
MAX SOLAR COND: MULTI 1410.132 HEATING & COOLING LOAD CALCULATIONS
SPACE: BRIDGE SQ FT (MEAN)= 1413 VOLUME= 9891 DECK: 03 # PEOPLE SHT NO.: 001L
SPACE NO: (NONE) HEIGHT (MEAN)= 7 R of C= 8 FRAMES: 35-55 CL 4 REV 0
VENT. TEMP. RISE = 25.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 130 92S-D 40.7*35.4-16.3*12.75+2*((20+7)/2)*6.661413 50 0.117 8,265 WEATHER 70 0 92W-U 70 0.101 9,988
2 80 90 0IN-U 5*5 25 10 1.113 278 CHIEF ENGR. T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 5*5 25 10 1.113 278 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 6*3.5 21 10 1.113 234 DECK TOILET 70 70 0IN-D 0 0.695 0
2 80 85 0IN-U 5*5 25 5 1.113 139 HOSPITAL T/S 70 75 0IN-U -5 0.993 NO CREDIT
2 80 75 0IN-D 12*19.5-6*3.5-5*5-(2*19.5) 149 -5 0.801 (597) HOSPITAL 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 3*2 6 10 1.113 67 LINEN LOCKER 70 60 0IN-D 10 0.695 42
3 80 115 98S-H 8.2*(17+9.5+7+9.5+4)-(2*9.19+6*4.81+5*6.56)305 35 0.089 951 WEATHER 70 0 98W-H 70 0.073 1,560
3 80 115 1S-H 2*9.19+6*4.81+5*6.56 80.0 1 120 9605 WEATHER 70 0 1W-H 70 1.13 6331
3 80 95 98W-H 8.2*(17+9.5+7+9.5+4)-(2*9.19+6*4.81+5*6.56)305 15 0.08 366 WEATHER 70 0 98W-H 70 0.073 1,560
3 80 95 1W-H 2*9.19+6*4.81+5*6.56 80.0 15 0.82 984 WEATHER 70 0 1W-H 70 1.13 6331
4 80 115 98S-H 8.2*36-(4*4.81+7*6.56) 230 35 0.089 717 WEATHER 70 0 98W-H 70 0.073 1,176
4 80 115 1S-H 4*4.81+7*6.56 65.2 1 120 7819 WEATHER 70 0 1W-H 70 1.13 5154
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 17,857 SHT #001A LOAD = 31812 9705 SHT #001A LOAD = 71,970
TOTAL (Hs, Hl) = 62,310 9705 TOTAL HEAT = 72,015 TOTAL HEAT LOSS = 104,113
VENT CFM= 62,310 BTU/HR = 2,308
(BY TEMP RISE) 1.08 X (80 - 55.0)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 9,891 CU FT = 1,236
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 2,310 A/C SYS: 501 SCALE: N/A SWBS: SHT NO.: 001L
HEATING & COOLING LOAD CALCULATIONS (CONT)
SPACE: BRIDGE (CONT) DECK: 03 SHT NO.: 001L(A)
SPACE NO: (NONE) FRAMES: 35-55 CL REV 0
COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
7 LIGHTS BTU/HR/SQFT = 6.7 1413 -- -- 9536
8 EQUIPMENT FROM SHT #001E: 17,060 -- -- 17,060
9 PERSONNEL Hs = 285 4 1,140
9 PERSONNEL Hl = 515 4 2,060
2 80 95 98W-U 2*7*7+7*13 189 15 0.083 235 WEATHER 70 0 98W-D 70 0.07 926
2 80 90 0IN-U 5*3 15 10 1.113 167 CG LOCKER 70 60 0IN-D 10 0.695 104
2 80 80 0IN-D 12.5*16+3*3-5*5 184 0 0.801 0 CHIEF ENGR. 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 16*11-5*5 151 0 0.801 0 SR 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 12.5*16-5*5 175 0 0.801 0 CHIEF SCIENTIST SR 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 12.5*12.5-3*3 147 0 0.801 0 SR 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 11.5*16-5*5 159 0 0.801 0 C.O. SR 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 10*19.5-5*3-5*5 155 0 0.801 0 SR 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 32.2*4+15*7+3.5*16-(2*3.5)-3.5*12 241 0 0.801 0 PASSAGE 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 1*10.5+2.5*2 16 0 0.801 0 SR 70 70 0IN-D 0 0.695 0
5 80 95 98W-H 8.2*23-(2*4.81+8*6.56) 127 15 0.08 152 WEATHER 70 0 98W-H 70 0.073 646
5 80 95 1W-H 2*4.81+8*6.56 62.1 15 0.82 764 WEATHER 70 0 1W-H 70 1.13 4912
2 80 95 52IN-U 3.5*12 42 15 0.139 88 CENTERBOARD TRUNK 70 0 52IN-D 70 0.122 359
INFIL SEN LOAD (@60 MIN R/C) = 165 X 1.08 X (95-80) = 2,671 INFIL SEN HEATING LOAD (@10 MIN R/C) = 989 X 1.08 X (70-0) =
INFIL LATENT LOAD (@60 MIN R/C) = INFIL TOTAL LOAD (165 X 4.5 X (46.4-32.5) - INFIL SEN LOAD = 7,645 65,023
TOTAL (THIS SHT)(Hs, Hl) = 31,812 9,705 TOTAL HEAT = 41517 TOTAL HEAT LOSS (THIS SHT)= 71,970
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 001L(A)
HEATING & COOLING LOAD CALCULATIONS
SPACE: BRIDGE (EQUIPMENT LIST) DECK: 03 SHT NO.: 001E
SPACE NO: N/A FRAMES: 35-55 CL REV 0
EQUIPMENT LIST
EQUIPMENT HEAT DISSIPATION* USE RM LOAD | EQUIPMENT HEAT DISSIPATION USE RM LOAD
QTY DESCRIPTION BTU/HR FACTOR BTU/HR | QTY DESCRIPTION KW or BTU/HR FACTOR BTU/HR
1 Misc Equipment (5 kw) which includes: 5*3412 1 17,060 |
DEICING SYSTEM XFMR & CONN BOX, P405-2(A) |
DEICING SYSTEM XFMR & CONN BOX, P405-2(C) |
DEICING SYSTEM XFMR & CONN BOX, P405-2(B) |
4.3 KVA UPS |
LIGHTING PNL, L123A |
LIGHTING PNL L122F |
LIGHTING PNL, L122A |
LIGHTING PNL, L122H |
LIGHTING PNL L122E |
EMERGENCY LTG PNL, EL126 |
DEICING SYSTEM XFMR & CONN BOX, P406-1(A) |
PILOTHOUSE EMERGENCY PWR PNL EP128 |
PILOTHOUSE CONSOLES |
ALL OTHER MISC EQUIPMENT |
TOTAL HEAT TO RM = 17,060 BTU/HR
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 001E
MAX SOLAR COND: MULTI HEATING & COOLING LOAD CALCULATIONS
SPACE: RADIO/CHART AREA SQ FT (MEAN)= 221 VOLUME= 1812 DECK: 03 # PEOPLE SHT NO.: 002L
SPACE NO: (NONE) HEIGHT (MEAN)= 8.2 R of C= 8 FRAMES: 47-55 P 2 REV 0
VENT. TEMP. RISE = 25.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 130 92S-D 17*13 221 50 0.117 1,293 WEATHER 70 0 92W-U 70 0.101 1,562
2 80 110 52IN-U 4*10 40 30 0.139 167 DC LOCKER 70 0 52IN-D 70 0.122 342
2 80 80 0IN-D 3*12 36 0 0.801 0 PASSAGE 70 70 0IN-D 0 0.695 0
3 80 115 92S-H 8.2*17 139 35 0.116 566 WEATHER 70 0 92W-H 70 0.099 966
2 80 80 0IN-D 13*10+5*3 145.0 0 0.801 0 SR 70 70 0IN-D 0 0.695 0
5 80 115 92S-H 8.2*13 107 35 0.116 433 WEATHER 70 0 92W-H 70 0.099 739
7 LIGHTS BTU/HR/SQFT = 6.7 221 -- -- 1491
8 EQUIPMENT FROM SHT #002E: 1,706 -- -- 1,706
9 PERSONNEL Hs = 285 2 570
9 PERSONNEL Hl = 515 2 1,030
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 1,514
TOTAL (Hs, Hl) = 6,226 1030 TOTAL HEAT = 7,256 TOTAL HEAT LOSS = 3,609
VENT CFM= 6,226 BTU/HR = 231
(BY TEMP RISE) 1.08 X (80 - 55.0)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 1,812 CU FT = 227
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 230 A/C SYS: 502 SCALE: N/A SWBS: SHT NO.: 002L
SPACE: RADIO/CHART AREA (EQUIPMENT LIST) DECK: 03 SHT NO.: 002E
SPACE NO: N/A FRAMES: 47-55 P REV 0
EQUIPMENT LIST
EQUIPMENT HEAT DISSIPATION* USE RM LOAD | EQUIPMENT HEAT DISSIPATION USE RM LOAD
QTY DESCRIPTION BTU/HR FACTOR BTU/HR | QTY DESCRIPTION KW or BTU/HR FACTOR BTU/HR
1 Misc Equipment (0.5 kw) 0.5*3412 1 1,706 |
TOTAL HEAT TO RM = 1,706 BTU/HR
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 002E
SPACE: CHIEF ENGR. SQ FT (MEAN)= 184 VOLUME= 1288 DECK: 02 # PEOPLE SHT NO.: 003L
SPACE NO: (NONE) HEIGHT (MEAN)= 7 R of C= 8 FRAMES: 29-37 P 1 REV 0
VENT. TEMP. RISE = 25.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 80 0IN-D 6*12.5-5*5+3*3 59 0 0.801 0 BRIDGE 70 70 0IN-D 0 0.695 0
1 80 130 92S-D 10*12.5 125 50 0.117 731 WEATHER 70 0 92W-U 70 0.101 884
2 80 90 0IN-U 1.5*5 8 10 1.113 83 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 1.5*5 8 10 1.113 83 SR T/S 70 70 0IN-D 0 0.695 0
3 80 115 92S-H 8.2*11-(2.5*3) 83 35 0.116 336 WEATHER 70 0 92W-H 70 0.099 573
3 80 115 1S-H 2.5*3 7.5 1 120 900 WEATHER 70 0 1W-H 70 1.13 593
4 80 115 52IN-H 5*12.5 63 35 0.137 300 S.W. TANK 70 0 52IN-H 70 0.124 543
3/5 80 80 5IN-H 8.2*(3+3+4.5) 86 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
6 80 80 5IN-H 8.2*16 131 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
6 80 80 5IN-H 8.2*3 25 0 0.376 0 PASSAGE 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 184 -- -- 1242
9 PERSONNEL Hs = 240 1 240
9 PERSONNEL Hl = 360 1 360
3/5 80 90 5IN-H 8.2*(5+5) 82 10 0.376 308 CHIEF ENGR. T/S 70 70 5IN-H 0 0.354 0
4 80 115 92S-H 3.2*12.5 40 35 0.116 162 WEATHER 70 0 92W-H 70 0.099 277
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 1,572
TOTAL (Hs, Hl) = 4,386 360 TOTAL HEAT = 4,746 TOTAL HEAT LOSS = 2,870
VENT CFM= 4,386 BTU/HR = 162
(BY TEMP RISE) 1.08 X (80 - 55.0)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 1,288 CU FT = 161
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 160 A/C SYS: 503 SCALE: N/A SWBS: SHT NO.: 003L
MAX SOLAR COND: SIDE HEATING & COOLING LOAD CALCULATIONS
SPACE: CHIEF ENGR. T/S SQ FT (MEAN)= 25 VOLUME= 205 DECK: 02 # PEOPLE SHT NO.: 004L
SPACE NO: (NONE) HEIGHT (MEAN)= 8.2 R of C= 4 FRAMES: 35-37 P N/A REV 0
VENT. TEMP. RISE = 10.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 90 80 0IN-U 5*5 25 -10 1.113 (278) BRIDGE 70 70 0IN-D 0 0.695 0
2 90 80 0IN-D 5*5 25 -10 0.801 (200) SR 70 70 0IN-D 0 0.695 0
3 90 125 92S-H 8.2*5 41 35 0.116 166 WEATHER 70 0 92W-H 70 0.099 284
4/6 90 80 5IN-H 8.2*(5+5) 82 -10 0.376 (308) CHIEF ENGR. 70 70 5IN-H 0 0.354 0
5 90 80 5IN-H 8.2*5 41 -10 0.376 (154) SR 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 25 -- -- 169
USE: 50 CFM M/E
50 CFM N/S VIA DOOR
TOTAL (Hs, Hl) = (606) 0 TOTAL HEAT = (606) TOTAL HEAT LOSS = 284
USE A CONVECTOR WITH A CAPACITY = 0.08 KW
VENT CFM= (606) BTU/HR = (56)
(BY TEMP RISE) 1.08 X (10)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 205 CU FT = 51
(BY R/C) 4 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 50 SCALE: N/A SWBS: SHT NO.: 004L
ADJUST SUPPLY TEMP TO MATCH R/C CFM (YES/NO): YES
MAX SOLAR COND: TOP HEATING & COOLING LOAD CALCULATIONS
SPACE: SR SQ FT (MEAN)= 151 VOLUME= 1057 DECK: 02 # PEOPLE SHT NO.: 005L
SPACE NO: (NONE) HEIGHT (MEAN)= 7 R of C= 8 FRAMES: 29-37 CL 2 REV 0
VENT. TEMP. RISE = 24.04 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 80 0IN-D 6.5*11-5*5 47 0 0.801 0 BRIDGE 70 70 0IN-D 0 0.695 0
1 80 145 92S-D 10*11 110 65 0.117 837 WEATHER 70 0 92W-U 70 0.101 778
2 80 90 0IN-U 4*5 20 10 1.113 223 SR T/S 70 70 0IN-D 0 0.695 0
2 80 90 0IN-U 4*5 20 10 1.113 223 SR T/S 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 16*3.5-1*5 51 0 0.801 0 PASSAGE 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 11*4 44 0 0.801 0 CONFERENCE ROOM 70 70 0IN-D 0 0.695 0
3 80 80 5IN-H 8.2*16 131 0 0.376 0 CHIEF ENGR. 70 70 5IN-H 0 0.354 0
3 80 80 5IN-H 8.2*11 90 0 0.376 0 CHIEF SCIENTIST SR 70 70 5IN-H 0 0.354 0
3/5 80 90 5IN-H 8.2*(5+5) 82 10 0.376 308 SR T/S 70 70 5IN-H 0 0.354 0
5 80 80 5IN-H 8.2*6 49 0 0.376 0 PASSAGE 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 151 -- -- 1019
9 PERSONNEL Hs = 240 2 480
9 PERSONNEL Hl = 360 2 720
4 80 115 52SEA-H 5*11 55 35 0.147 283 SEA WATER 70 26 52SEA-H 44 0.138 334
4 80 95 92W-H 3.2*11 35 15 0.111 59 WEATHER 70 0 92W-H 70 0.099 244
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 1,206
TOTAL (Hs, Hl) = 3,431 720 TOTAL HEAT = 4,151 TOTAL HEAT LOSS = 1,356
VENT CFM= 3,431 BTU/HR = 132
(BY TEMP RISE) 1.08 X (80 - 56.0)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 1,057 CU FT = 132
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 130 A/C SYS: 505 SCALE: N/A SWBS: SHT NO.: 005L
MAX SOLAR COND: N/A HEATING & COOLING LOAD CALCULATIONS
SPACE: SR T/S SQ FT (MEAN)= 25 VOLUME= 205 DECK: 02 # PEOPLE SHT NO.: 006L
SPACE NO: (NONE) HEIGHT (MEAN)= 8.2 R of C= 4 FRAMES: 35-37 S N/A REV 0
VENT. TEMP. RISE = 10.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 90 80 0IN-U 5*5 25 -10 1.113 (278) BRIDGE 70 70 0IN-D 0 0.695 0
2 90 80 0IN-D 4*5 20 -10 0.801 (160) CONFERENCE ROOM 70 70 0IN-D 0 0.695 0
2 90 80 0IN-D 1*5 5 -10 0.801 (40) PASSAGE 70 70 0IN-D 0 0.695 0
3 90 90 0IN-H 8.2*5 41 0 0.93 0 T/S 70 70 0IN-H 0 0.833 0
4/6 90 80 5IN-H 8.2*(5+5) 82 -10 0.376 (308) SR 70 70 5IN-H 0 0.354 0
5 90 80 5IN-H 8.2*5 41 -10 0.376 (154) PASSAGE 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 25 -- -- 169
USE: 50 CFM M/E
50 CFM N/S VIA DOOR
TOTAL (Hs, Hl) = (772) 0 TOTAL HEAT = (772) TOTAL HEAT LOSS = 0
TEMP DROP < 2°F => HTR NOT REQ'D
VENT CFM= (772) BTU/HR = (72)
(BY TEMP RISE) 1.08 X (10)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 205 CU FT = 51
(BY R/C) 4 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 50 SCALE: N/A SWBS: SHT NO.: 006L
SPACE: CHIEF SCIENTIST SR SQ FT (MEAN)= 175 VOLUME= 1225 DECK: 02 # PEOPLE SHT NO.: 007L
SPACE NO: (NONE) HEIGHT (MEAN)= 7 R of C= 8 FRAMES: 29-37 S 1 REV 0
VENT. TEMP. RISE = 25.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 80 0IN-D 12.5*6.5-5*5 56 0 0.801 0 BRIDGE 70 70 0IN-D 0 0.695 0
1 80 130 92S-D 12.5*10 125 50 0.117 731 WEATHER 70 0 92W-U 70 0.101 884
2 80 80 0IN-D 12.5*16-5*5-(5*5) 150 0 0.801 0 CONFERENCE ROOM 70 70 0IN-D 0 0.695 0
3 80 115 92S-H 8.2*16-(2.5*3) 124 35 0.116 502 WEATHER 70 0 92W-H 70 0.099 857
3 80 115 1S-H 2.5*3 7.5 1 120 900 WEATHER 70 0 1W-H 70 1.13 593
5 80 80 5IN-H 8.2*7.5 62 0 0.376 0 PASSAGE 70 70 5IN-H 0 0.354 0
5/6 80 90 5IN-H 8.2*(5+5) 82 10 0.376 308 T/S 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 175 -- -- 1181
9 PERSONNEL Hs = 240 1 240
9 PERSONNEL Hl = 360 1 360
4 80 115 92S-H 3.2*12.5 40 35 0.116 162 WEATHER 70 0 92W-H 70 0.099 277
4 80 115 52IN-H 5*12.5 63 35 0.137 300 S.W. TANK 70 26 52IN-H 44 0.124 341
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 1,572
TOTAL (Hs, Hl) = 4,325 360 TOTAL HEAT = 4,685 TOTAL HEAT LOSS = 2,952
VENT CFM= 4,325 BTU/HR = 160
(BY TEMP RISE) 1.08 X (80 - 55.0)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 1,225 CU FT = 153
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 160 A/C SYS: 507 SCALE: N/A SWBS: SHT NO.: 007L
SPACE: T/S SQ FT (MEAN)= 25 VOLUME= 205 DECK: 02 # PEOPLE SHT NO.: 008L
SPACE NO: (NONE) HEIGHT (MEAN)= 8.2 R of C= 4 FRAMES: 35-37 S N/A REV 0
VENT. TEMP. RISE = 10.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 90 80 0IN-U 5*5 25 -10 1.113 (278) BRIDGE 70 70 0IN-D 0 0.695 0
2 90 80 0IN-D 5*5 25 -10 0.801 (200) CONFERENCE ROOM 70 70 0IN-D 0 0.695 0
3/4 90 80 5IN-H 8.2*(5+5) 82 -10 0.376 (308) CHIEF SCIENTIST SR 70 70 5IN-H 0 0.354 0
5 90 80 5IN-H 8.2*5 41 -10 0.376 (154) PASSAGE 70 70 5IN-H 0 0.354 0
6 90 90 0IN-H 8.2*5 41 0 0.93 0 SR T/S 70 70 0IN-H 0 0.833 0
7 LIGHTS BTU/HR/SQFT = 6.7 25 -- -- 169
USE: 50 CFM M/E
50 CFM N/S VIA DOOR
TOTAL (Hs, Hl) = (772) 0 TOTAL HEAT = (772) TOTAL HEAT LOSS = 0
TEMP DROP < 2°F => HTR NOT REQ'D
VENT CFM= (772) BTU/HR = (72)
(BY TEMP RISE) 1.08 X (10)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 205 CU FT = 51
(BY R/C) 4 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 50 SCALE: N/A SWBS: SHT NO.: 008L
SPACE: PASSAGE SQ FT (MEAN)= 205 VOLUME= 1681 DECK: 02 # PEOPLE SHT NO.: 009L
SPACE NO: (NONE) HEIGHT (MEAN)= 8.2 R of C= 8 FRAMES: 37-56 0 REV 0
VENT. TEMP. RISE = 17.36 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 80 0IN-D 322*4+15*7+3.5*16 1449 0 0.801 0 BRIDGE 70 70 0IN-D 0 0.695 0
2 80 115 52IN-U 4*12 48 35 0.139 234 FAN ROOM 70 40 52IN-D 30 0.122 176
2 80 80 0IN-D 13.5*4 54 0 0.801 0 PASSAGE 70 70 0IN-D 0 0.695 0
2 80 115 52IN-U 4*13.5 54 35 0.139 263 FAN ROOM 70 40 52IN-D 30 0.122 198
2 80 95 92W-U 3.5*3 11 15 0.109 17 WEATHER 70 0 92W-D 70 0.097 71
3 80 95 92W-H 8.2*3.5-(2*2) 25 15 0.111 41 WEATHER 70 0 92W-H 70 0.099 171
3 80 95 1W-H 2*2 4.0 15 0.82 49 WEATHER 70 0 1W-H 70 1.13 316
6 80 80 5IN-H 8.2*6.5 53 0 0.376 0 C.O. SR 70 70 5IN-H 0 0.354 0
6 80 90 5IN-H 8.2*5 41 10 0.376 154 T/S 70 70 5IN-H 0 0.354 0
3/4 80 90 5IN-H 8.2*(3+2) 41 10 0.376 154 CG LOCKER 70 60 5IN-H 10 0.354 145
6 80 80 5IN-H 8.2*5 41 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
5/6 80 90 5IN-H 8.2*(6+2) 66 10 0.376 247 DECK TOILET 70 70 5IN-H 0 0.354 0
6 80 75 5IN-H 8.2*6 49 -5 0.376 (92) HOSPITAL 70 70 5IN-H 0 0.354 0
3 80 80 5IN-H 8.2*3 25 0 0.376 0 CHIEF ENGR. 70 70 5IN-H 0 0.354 0
3 80 80 5IN-H 8.2*9.5 78 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
3 80 90 5IN-H 8.2*3 25 10 0.376 92 LINEN LOCKER 70 60 5IN-H 10 0.354 87
3 80 80 5IN-H 8.2*8 66 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
3 80 80 0IN-H 8.2*13.5 111 0 0.93 0 PASSAGE 70 70 0IN-H 0 0.833 0
4 80 80 5IN-H 8.2*6 49 0 0.376 0 SR 70 70 5IN-H 0 0.354 0
SUMMER LIGHT LOAD (0% EQUIP & LIGHTS + 50% OTHER) = 1,278 SHT #009A LOAD = 2781 0 SHT #009A LOAD = 1,591
TOTAL (Hs, Hl) = 3,940 0 TOTAL HEAT = 3,940 TOTAL HEAT LOSS = 2,755
VENT CFM= 3,940 BTU/HR = 210
(BY TEMP RISE) 1.08 X (80 - 62.6)
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
VENT CFM= 1,681 CU FT = 210
(BY R/C) 8 MINUTES FSCM: DRAWING NO.:
FINAL VENTILATION CFM = 210 A/C SYS: 509 SCALE: N/A SWBS: SHT NO.: 009L
SPACE: PASSAGE (CONT) DECK: 02 SHT NO.: 009L(A)
SPACE NO: (NONE) FRAMES: 37-56 REV 0
COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
4 80 90 5IN-H 8.2*5 41 10 0.376 154 SR T/S 70 70 5IN-H 0 0.354 0
4 80 90 5IN-H 8.2*5 41 10 0.376 154 T/S 70 70 5IN-H 0 0.354 0
4 80 80 5IN-H 8.2*7.5 62 0 0.376 0 CHIEF SCIENTIST SR 70 70 5IN-H 0 0.354 0
3/5 80 80 5IN-H 8.2*(16+6.5) 185 0 0.376 0 C.O. SR 70 70 5IN-H 0 0.354 0
5 80 125 92S-H 8.2*3.5-(2*2) 25 45 0.116 129 WEATHER 70 0 92W-H 70 0.099 171
5 80 125 1S-H 2*2 4.0 1 160 640 WEATHER 70 0 1W-H 70 1.13 316
7 LIGHTS BTU/HR/SQFT = 6.7 205 -- -- 1383
3 80 90 10IN-H 8.2*2 16 10 0.361 59 SR T/S 70 70 10IN-H 0 0.328 0
3/5 80 95 52IN-H 8.2*(12+3.5) 127 15 0.137 261 CENTERBOARD TRUNK 70 0 52IN-H 70 0.124 1,103
TOTAL (THIS SHT)(Hs, Hl) = 2,781 0 TOTAL HEAT = 2781 TOTAL HEAT LOSS (THIS SHT)= 1,591
A JOB: NOAA FRV40 CLASS 63m VESSEL REV 0
FSCM: DRAWING NO.:
SCALE: N/A SWBS: SHT NO.: 009L(A)
SPACE: SR SQ FT (MEAN)= 147.25 VOLUME= 1031 DECK: 02 # PEOPLE SHT NO.: 010L
SPACE NO: (NONE) HEIGHT (MEAN)= 7 R of C= 8 FRAMES: 37-44 P 2 REV 0
VENT. TEMP. RISE = 25.00 COOLING LOAD HEATING LOAD
KEY T To U-KEY DIMENSION AREA Td U Hs Hl ADJ. COMPARTMENT T To U-KEY Td U Hw
1 80 80 0IN-D 12.5*12.5-3*3 147 0 0.801 0 BRIDGE 70 70 0IN-D 0 0.695 0
2 80 80 0IN-D 12.5*12.5-3*3 147 0 0.801 0 OFFICE SUITE 70 70 0IN-D 0 0.695 0
3 80 125 92S-H 8.2*12.5-(2.5*3) 95 45 0.116 496 WEATHER 70 0 92W-H 70 0.099 658
3 80 125 1S-H 2.5*3 7.5 1 160 1200 WEATHER 70 0 1W-H 70 1.13 593
4/6 80 80 5IN-H 8.2*(4.5+3+3) 86 0 0.376 0 CHIEF ENGR. 70 70 5IN-H 0 0.354 0
5 80 90 5IN-H 8.2*2 16 10 0.376 62 LINEN LOCKER 70 60 5IN-H 10 0.354 58
5 80 90 5IN-H 8.2*5 41 10 0.376 154 SR T/S 70 70 5IN-H 0 0.354 0
5 80 90 5IN-H 8.2*5 41 10 0.376 154 SR T/S 70 70 5IN-H 0 0.354 0
6 80 80 5IN-H 8.2*9.5 78 0 0.376 0 PASSAGE 70 70 5IN-H 0 0.354 0
7 LIGHTS BTU/HR/SQFT = 6.7 147 -- -- 994
9 PERSONNEL Hs = 240 2 480
9 PERSONNEL Hl = 360 2 720
SUMMER LIGHT LOAD (0%…