AV-000- GENERAL NOTES AND LEGENDS.pdf
PDF 81 KB Posted
- Attached to
- Audio Visual System Bethany Library
- Solicitation number
- 19-053-08
- Issued by
- Oklahoma County, Beggs City, Oklahoma
About this file
This document is a technical legend and general notes sheet for an Audio/Visual (AV) systems infrastructure project for the Bethany Library in Oklahoma, prepared by WJHW consulting firm for the City of Bethany. The document provides comprehensive technical specifications for AV equipment installation, including detailed symbols, mounting instructions, box type schedules, conduit and pathway distribution guidelines, and specific installation notes. The project involves providing infrastructure, projection screens, and equipment racks (ER-1 and ER-2), with all AV equipment designated as Owner Furnished and Owner Installed (OFOI).
The technical specifications outline precise requirements for conduit installation, pathway systems, cable support, grounding standards, and penetration sealing. Key technical stipulations include maintaining proper conduit bend radii, limiting uninterrupted conduit runs to 100 contiguous feet, using pull boxes at specified intervals, and ensuring all architectural barrier penetrations are completely sealed. The document emphasizes compliance with ANSI/TIA/EIA standards for telecommunications infrastructure, with specific attention to cable pathway support, bonding, grounding, and installation methodologies. The project appears to be a comprehensive AV system infrastructure implementation for the Bethany Library, focusing on technical precision and standardized installation practices.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AUDIO/VIDEO SYSTEMS - SYMBOL LEGEND
SYMBOL DEVICE
ROUGH-IN BOX TYPE (H" x W" x D")
MOUNTING HEIGHT NOTES
WALL OR CEILINGS MASONRY SURFACE
NOTES:
(SOME DEVICES AND SYMBOLS SHOWN ON THIS LEGEND MAY NOT BE APPLICABLE TO PROJECT)
FLUSH IN CEILING.1
AV PLATEAV2 TYPE 4 TYPE 5 MOUNT AT BUILDING OUTLET HEIGHT.
FLAT PANEL MONITOR PROVIDE CHIEF PAC-526 FREFERENCE ARCHITECTURAL
DRAWINGS FOR ELEVATION.FPM
CEILING SPEAKER ---
FLUSH IN CEILING.2 ---------CEILING MOUNTED
SUB-WOOFER
PROJECTION SCREEN
PS --- ---
TOUCH PANELTP MOUNT AT BUILDING SWITCH HEIGHT.
BUTTON PANELBP TYPE 1 TYPE 2 MOUNT AT BUILDING SWITCH HEIGHT.
TYPE 4 TYPE 5
FB FLOOR BOX ---------
REFERENCE ELECTRICAL DRAWINGS FOR FLOOR BOX SPECIFICATION.
REFERENCE ARCHITECTURAL DRAWINGS FOR LOCATION.IN FLOOR
REFERENCE AV-411 FOR ELEVATIONS------
AV PLATEAV1 TYPE 1 TYPE 2 --- MOUNT AT BUILDING OUTLET HEIGHT. ---
ASSISTED LISTENING
SYSTEM
ALS TYPE 1 TYPE 2
WIRELESS ANTENNAWA TYPE 1 TYPE 2
--- MOUNT AT 6" B.F.C.
MOUNT AT 6" B.F.C. ---
BOX TYPE SCHEDULE
1. 1-GANG RACO 231 STEEL BOX, 2-1/8" DEEP WITH 1-GANG TRIM RING. COVER EDGE
TO BE FLUSH WITH FINISHED WALL.
2. 1-GANG MASONRY: RACO 690 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN
6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
3. 1-GANG DIE CAST: RACO 5324 DIE CAST ALUMINUM 2-5/8" DEEP.
4. 2-GANG 4" SQUARE: RACO 231 STEEL BOX, 2-1/8" DEEP WITH 2-GANG TRIM RING.
COVER EDGE TO BE FLUSH WITH FINISHED WALL.
5. 2-GANG MASONRY: RACO 691 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN
6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
6. 2-GANG DIE CAST: RACO 5345 DIE CAST ALUMINUM 2-5/8" DEEP.
7. 3-GANG: RACO 686 STEEL SWITCH BOX, 2-1/2" DEEP. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
8. 3-GANG MASONRY: RACO 692 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN
6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
9. 3-GANG DIE CAST: RACO 5390 DIE CAST ALUMINUM 2-5/8" DEEP.
10. 4-GANG: RACO 687 STEEL SWITCH BOX, 2-1/2" DEEP. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
11. 4-GANG MASONRY: RACO 693 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN
6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
12. 5-GANG MASONRY: RACO 694 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN
6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH
WITH FINISHED WALL.
13. ACE BACKSTAGE #122XXYY WITH #ISO102BBX BACK BOX. FINISH PER ARCHITECT.
COVER TO BE FLUSH WITH FINISHED FLOOR.
14. STAINLESS STEEL WEATHER PROOF ENCLOSURE: AFC-UNIFAB AV-MP10/10/08-CPT-
SS-S-LOCK. FOR INFORMATION: HTTP://WWW.AFCWEB.COM/UNIFAB/INDEX.HTML
15. STAINLESS STEEL WEATHER PROOF ENCLOSURE: HOFFMAN TYPE 4X,
A-606CHNFSS.
SPECIFIC SCHEDULE NOTES
PROVIDE HOFFMAN PAINTED STEEL TYPE 1 SCREW COVER PULL BOX SIZE AS
REQUIRED. PROVIDE 3/4" VOID FREE PLYWOOD COATED WITH A FIRE
RETARDING WHITE PAINT ON BACK WALL OF JUNCTION BOX FROM SIDEWALL
TO SIDEWALL. INCREASE SIZE OF BOX AS REQUIRED TO ACCOMMODATE
CONDUITS TERMINATIONS AT BOX.
PROVIDE HOFFMAN PAINTED STEEL TYPE 412 HINGED COVER, LOCKING, PULL
BOX SIZE AS REQUIRED. PROVIDE 3/4" VOID FREE PLYWOOD COATED WITH A
FIRE RETARDING WHITE PAINT ON BACK WALL OF JUNCTION BOX FROM
SIDEWALL TO SIDEWALL. INCREASE SIZE OF BOX AS REQUIRED TO
ACCOMMODATE CONDUITS TERMINATING AT BOX.
PROVIDE 3/4"C. INTERCONNECTING LOUDSPEAKERS WITHIN THE SAME
SERVICE AREA OR ZONE OR IN ACCESSIBLE CEILINGS PROVIDE CLIPS, RINGS,
AND CABLE PER LOCAL CODE REQUIREMENTS.
IF LOUDSPEAKER IS LOCATED IN AN INACCESSIBLE CEILING, PROVIDE A 3/4"
CONDUIT STUB AT NEAREST ACCESSIBLE CEILING.
PROVIDE A 3/4" CONDUIT STUB TO NEAREST ACCESSIBLE CEILING.
PROVIDE NON-METALLIC CONDUIT BETWEEN JUNCTION BOX AND
EQUIPMENT RACK. ISOLATE CONDUIT FROM RACK. PROVIDE A SEPARATE
CONDUIT FOR EACH SIGNAL TYPE AND SIZE CONDUIT TO PROVIDE A
MAXIMUM OF 40% FILL.
PROVIDE BLOCKING AS REQUIRED TO SUPPORT THE WEIGHT OF SPEAKER
AND BRACKET OR WALL MOUNTED EQUIPMENT RACK. FIELD VERIFY
EXISTING CONDITIONS FOR REQUIREMENT.
PROVIDE COVER WITH CONDUIT NIPPLE WITH BUSHING FOR CABLE EXIT.
PROVIDE KELLUM TYPE GRIP FOR STRAIN RELIEF OF CABLE SPANNING TO
CLUSTER.
1.
2.
3.
4.
5.
6.
7.
8.
ABBREVIATION LEGEND
A.F.F. - ABOVE FINISHED FLOOR
B.F.C. - BELOW FINISHED CEILING
C. - CONDUIT
ER - EQUIPMENT RACK ER-###
M.C. - MAIN CROSSCONNECT
O.F.E. - OWNER FURNISHED EQUIPMENT
RE - REFERENCE, REFER
T.C. - TELECOMMUNICATIONS CLOSET
U.O.N. - UNLESS OTHERWISE NOTED
PATHWAY DISTRIBUTION
RACEWAY CONCEALED OR EXPOSED
RACEWAY HIDDEN OR BELOW FLOOR SLAB
J-HOOKS ON 4' CENTERS
HOME RUN
CONDUIT STUB TO ABOVE ACCESSIBLE CEILING OR CABLE TRAY
CABLE TRAY, SHOWN FOR REFERENCE ONLY. REFER
TO
ELECTRICAL DRAWINGS FOR DETAILS.
DESTINATION
(2) 1" C
CONDUIT
CONDUIT SIZE
NUMBER OF CONDUITS
CONDUITS AND PATHWAY NOTES
GENERAL:
THE DRAWINGS INDICATE ONE ROUTING METHOD OF THE CABLING PATHWAYS. CHANGES
MAY BE MADE TO THE PATHWAY SYSTEM TO ACCOMMODATE SITE CONDITIONS OR
SIMPLIFY INSTALLATION AS LONG AS ADEQUATE SIZING IS MAINTAINED, HORIZONTAL
DISTANCE LIMITATIONS ARE NOT EXCEEDED, AND THE ARCHITECT APPROVES THE
COORDINATION DRAWINGS SUBMITTED FOR REVIEW.
CONDUIT TO OUTLETS SHALL PROVIDE A CONTINUOUS PATHWAY TO THE NEAREST CABLE
TRAY OR ACCESSIBLE CEILING.
REGARDLESS OF PATHWAY TYPE, ALL CABLING SHALL BE SUPPORTED AT A 5'-0" MAXIMUM
INTERVAL.
UNLESS NOTED OTHERWISE, CABLE PATHWAY WITHIN ROOMS WILL RUN PARALLEL TO
WALLS FOR ADDITIONAL 50 LINEAR FEET.
MAINTAIN PROPER BONDING AND GROUNDING OF HORIZONTAL PATHWAYS IN
ACCORDANCE WITH APPLICABLE ELECTRICAL CODES AND STANDARDS, AND
ANSI/TIA/EIA-607
SOLID LINE ( ) DEPICTS CONDUIT IN WALLS OR ABOVE CEILINGS.
DASHED LINE ( ) DEPICTS METALLIC CONDUIT IN SLAB OR COATED RIGID CONDUIT
UNDERGROUND.
CONDUIT:
SIZE ALL CONDUIT IN ACCORDANCE WITH ANSI EIA/TIA-569A CONDUIT CAPACITY
STANDARDS.
UNLESS NOTED OTHERWISE ALL CONDUITS ARE 3/4" C.
CONDUIT RUNS SHALL NOT CONTAIN 90° CONDUIT BODIES.
UNINTERRUPTED, STRAIGHT AND LEVEL CONDUIT RUNS SHALL NOT EXCEED 100
CONTIGUOUS FEET. FOR RUNS IN EXCESS OF 100 FEET, INSERT PULL BOXES AT 100 FOOT
INTERVALS, MAXIMUM.
MAINTAIN PROPER CONDUIT BEND RADIUS IN ACCORDANCE WITH ANSI/EIA/TIA-569-A. FOR
CONDUIT WITH AN INTERNAL DIAMETER OF 2" OR LESS, MAINTAIN A BEND RADIUS OF AT
LEAST 6-TIMES THE INTERNAL CONDUIT DIAMETER. FOR CONDUIT WITH AN INTERNAL
DIAMETER GREATER THAN 2", MAINTAIN A BEND RADIUS OF AT LEAST 10-TIMES THE
INTERNAL CONDUIT DIAMETER.
IF A CONDUIT REQUIRES MORE THAN TWO 90° BENDS, THEN PROVIDE A PULL BOX
BETWEEN SECTIONS WITH 2 BENDS OR LESS. IF A CONDUIT RUN REQUIRES A REVERSE
BEND (BETWEEN 100° AND 180°, THEN INSERT A PULL BOX AT EACH BEND HAVING AN
ANGLE FROM 100° AND 180°. IF A CONDUIT RUN REQUIRES MORE THAN TWO 90° BENDS
BETWEEN PULL BOXES, THEN FOR EACH ADDITIONAL BEND EITHER DERATE THE CONDUIT
CAPACITY BY 15% OR USE THE NEXT LARGER SIZE CONDUIT.
DO NOT CONSIDER A PULL BOX AS A BEND. ALL CONDUITS MUST RUN STRAIGHT
THROUGH A PULL BOX WITH THE BEND EITHER BEFORE OR AFTER THE PULL BOX.
REAM ALL CONDUIT ENDS. FIT STUBBED CONDUITS WITH AN INSULATED BUSHING TO
ELIMINATE SHARP EDGES THAT MAY DAMAGE CABLE DURING INSTALLATION OR SERVICE.
EQUIP ALL CONDUIT WITH "MULE TAPE" OR PULL CORD WITH A MINIMUM TEST RATING OF
1250 LBS.
BACKBONE CABLE CONDUIT FOR FIBER OPTICAL CABLES SHALL BE PROVIDED WITH
INNER-DUCT SIZED ACCORDING TO CONDUIT TRADE SIZE.
ALL PENETRATIONS OF ARCHITECTURAL BARRIERS SHALL BE COMPLETELY SEALED AT
THE CONCLUSION OF INSTALLATION. PENETRATIONS OF FIRE-RATED BARRIERS SHALL BE
FIRE-STOPPED WITH UL AND ASTM APPROVED MATERIALS THAT WILL PRESERVE THE
HOUR-RATING OF THE BARRIER. CABLE TRAY PENETRATIONS SHALL EMPLOY
MECHANICAL SEALING SYSTEMS THAT READILY PERMIT ADDITIONS OF MEDIA IN FUTURE
ADDS, MOVES AND CHANGES. CONDUIT PENETRATIONS SHALL USE LATEX ENDOTHERMIC
SEALANT AROUND THE OUTSIDE PERIMETER AND INTUMESCENT FIRE-STOP PILLOWS
WITHIN. MEMBRANE PENETRATIONS FOR OUTLET BOXES, CONTROL BOXES AND OTHER
EQUIPMENT THAT BREACHES ONE SIDE OF A BARRIER SHALL BE PROTECTED BY
PRODUCTS AND METHODS AS PUBLISHED IN UL CATEGORY CLIV.
ALL CONDUITS ENTERING OR EXITING EQUIPMENT RACKS TO BE ISOLATED WITH A NON-
METALIC SPACER OR FITTING.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
NOTE
ALL AV EQUIPMENT IS OWNER FURNISHED AND
OWNER INSTALLED (OFOI). CONTRACTOR IS TO
PROVIDE INFRASTRUCTURE, PROJECTION
SCREENS, AND EQUIPMENT RACK ER-1 AND ER-2.
KEY PLAN
APPROVED BY
CHECKED BY
A
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
23456
B
C
D
E
F 2500 McGee Drive Suite 100 Norman, OK 73072
Smith Roberts Baldischwiler
601 S.Lewis Ave.
Tulsa, OK 74104
Howell & Vancuren
1350 South Boulder Ave Suite 600 Tulsa, Oklahoma 74119
Dewberry Engineers Inc.
13431 Broadway Ext.
Suite 101 Oklahoma City, OK 73114
Alvine Engineering
3424 Midcourt Rd.
Suite 124 Carrollton, Tx 75006
WJHW
12" = 1'-0"
/3
/2
:2
:5
P
M
AV-000
GENERAL NOTES
AND LEGENDS
WJHW
CC
BK
06/01/2017
Dewberry Architects Inc.
50085544
B E
T H
A N
Y L
IB
R
A R
Y
C it y o f B e th a n y O k la h o m a
F
IN
A L C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
N
W th
S tr e e t
B e th a n y O
K
1350 South Boulder Ave Suite 600 Tulsa, OK 74119
No. Description Date
File details come from the government source that posted it. Updated .