AV-000- GENERAL NOTES AND LEGENDS.pdf

PDF 81 KB Posted

Attached to
Audio Visual System Bethany Library
Solicitation number
19-053-08
Issued by
Oklahoma County, Beggs City, Oklahoma

About this file

This document is a technical legend and general notes sheet for an Audio/Visual (AV) systems infrastructure project for the Bethany Library in Oklahoma, prepared by WJHW consulting firm for the City of Bethany. The document provides comprehensive technical specifications for AV equipment installation, including detailed symbols, mounting instructions, box type schedules, conduit and pathway distribution guidelines, and specific installation notes. The project involves providing infrastructure, projection screens, and equipment racks (ER-1 and ER-2), with all AV equipment designated as Owner Furnished and Owner Installed (OFOI).

The technical specifications outline precise requirements for conduit installation, pathway systems, cable support, grounding standards, and penetration sealing. Key technical stipulations include maintaining proper conduit bend radii, limiting uninterrupted conduit runs to 100 contiguous feet, using pull boxes at specified intervals, and ensuring all architectural barrier penetrations are completely sealed. The document emphasizes compliance with ANSI/TIA/EIA standards for telecommunications infrastructure, with specific attention to cable pathway support, bonding, grounding, and installation methodologies. The project appears to be a comprehensive AV system infrastructure implementation for the Bethany Library, focusing on technical precision and standardized installation practices.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AUDIO/VIDEO SYSTEMS - SYMBOL LEGEND

SYMBOL DEVICE

ROUGH-IN BOX TYPE (H" x W" x D")

MOUNTING HEIGHT NOTES

WALL OR CEILINGS MASONRY SURFACE

NOTES:

(SOME DEVICES AND SYMBOLS SHOWN ON THIS LEGEND MAY NOT BE APPLICABLE TO PROJECT)

FLUSH IN CEILING.1

AV PLATEAV2 TYPE 4 TYPE 5 MOUNT AT BUILDING OUTLET HEIGHT.

FLAT PANEL MONITOR PROVIDE CHIEF PAC-526 FREFERENCE ARCHITECTURAL

DRAWINGS FOR ELEVATION.FPM

CEILING SPEAKER ---

FLUSH IN CEILING.2 ---------CEILING MOUNTED

SUB-WOOFER

PROJECTION SCREEN

PS --- ---

TOUCH PANELTP MOUNT AT BUILDING SWITCH HEIGHT.

BUTTON PANELBP TYPE 1 TYPE 2 MOUNT AT BUILDING SWITCH HEIGHT.

TYPE 4 TYPE 5

FB FLOOR BOX ---------

REFERENCE ELECTRICAL DRAWINGS FOR FLOOR BOX SPECIFICATION.

REFERENCE ARCHITECTURAL DRAWINGS FOR LOCATION.IN FLOOR

REFERENCE AV-411 FOR ELEVATIONS------

AV PLATEAV1 TYPE 1 TYPE 2 --- MOUNT AT BUILDING OUTLET HEIGHT. ---

ASSISTED LISTENING

SYSTEM

ALS TYPE 1 TYPE 2

WIRELESS ANTENNAWA TYPE 1 TYPE 2

--- MOUNT AT 6" B.F.C.

MOUNT AT 6" B.F.C. ---

BOX TYPE SCHEDULE

1. 1-GANG RACO 231 STEEL BOX, 2-1/8" DEEP WITH 1-GANG TRIM RING. COVER EDGE

TO BE FLUSH WITH FINISHED WALL.

2. 1-GANG MASONRY: RACO 690 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN

6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

3. 1-GANG DIE CAST: RACO 5324 DIE CAST ALUMINUM 2-5/8" DEEP.

4. 2-GANG 4" SQUARE: RACO 231 STEEL BOX, 2-1/8" DEEP WITH 2-GANG TRIM RING.

COVER EDGE TO BE FLUSH WITH FINISHED WALL.

5. 2-GANG MASONRY: RACO 691 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN

6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

6. 2-GANG DIE CAST: RACO 5345 DIE CAST ALUMINUM 2-5/8" DEEP.

7. 3-GANG: RACO 686 STEEL SWITCH BOX, 2-1/2" DEEP. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

8. 3-GANG MASONRY: RACO 692 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN

6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

9. 3-GANG DIE CAST: RACO 5390 DIE CAST ALUMINUM 2-5/8" DEEP.

10. 4-GANG: RACO 687 STEEL SWITCH BOX, 2-1/2" DEEP. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

11. 4-GANG MASONRY: RACO 693 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN

6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

12. 5-GANG MASONRY: RACO 694 STEEL MASONRY BOX, NO LESS THAN 2-1/2" DEEP IN

6" CMU, BRICK OR CONCRETE AND 3-1/2" DEEP IN 8" CMU. COVER EDGE TO BE FLUSH

WITH FINISHED WALL.

13. ACE BACKSTAGE #122XXYY WITH #ISO102BBX BACK BOX. FINISH PER ARCHITECT.

COVER TO BE FLUSH WITH FINISHED FLOOR.

14. STAINLESS STEEL WEATHER PROOF ENCLOSURE: AFC-UNIFAB AV-MP10/10/08-CPT-

SS-S-LOCK. FOR INFORMATION: HTTP://WWW.AFCWEB.COM/UNIFAB/INDEX.HTML

15. STAINLESS STEEL WEATHER PROOF ENCLOSURE: HOFFMAN TYPE 4X,

A-606CHNFSS.

SPECIFIC SCHEDULE NOTES

PROVIDE HOFFMAN PAINTED STEEL TYPE 1 SCREW COVER PULL BOX SIZE AS

REQUIRED. PROVIDE 3/4" VOID FREE PLYWOOD COATED WITH A FIRE

RETARDING WHITE PAINT ON BACK WALL OF JUNCTION BOX FROM SIDEWALL

TO SIDEWALL. INCREASE SIZE OF BOX AS REQUIRED TO ACCOMMODATE

CONDUITS TERMINATIONS AT BOX.

PROVIDE HOFFMAN PAINTED STEEL TYPE 412 HINGED COVER, LOCKING, PULL

BOX SIZE AS REQUIRED. PROVIDE 3/4" VOID FREE PLYWOOD COATED WITH A

FIRE RETARDING WHITE PAINT ON BACK WALL OF JUNCTION BOX FROM

SIDEWALL TO SIDEWALL. INCREASE SIZE OF BOX AS REQUIRED TO

ACCOMMODATE CONDUITS TERMINATING AT BOX.

PROVIDE 3/4"C. INTERCONNECTING LOUDSPEAKERS WITHIN THE SAME

SERVICE AREA OR ZONE OR IN ACCESSIBLE CEILINGS PROVIDE CLIPS, RINGS,

AND CABLE PER LOCAL CODE REQUIREMENTS.

IF LOUDSPEAKER IS LOCATED IN AN INACCESSIBLE CEILING, PROVIDE A 3/4"

CONDUIT STUB AT NEAREST ACCESSIBLE CEILING.

PROVIDE A 3/4" CONDUIT STUB TO NEAREST ACCESSIBLE CEILING.

PROVIDE NON-METALLIC CONDUIT BETWEEN JUNCTION BOX AND

EQUIPMENT RACK. ISOLATE CONDUIT FROM RACK. PROVIDE A SEPARATE

CONDUIT FOR EACH SIGNAL TYPE AND SIZE CONDUIT TO PROVIDE A

MAXIMUM OF 40% FILL.

PROVIDE BLOCKING AS REQUIRED TO SUPPORT THE WEIGHT OF SPEAKER

AND BRACKET OR WALL MOUNTED EQUIPMENT RACK. FIELD VERIFY

EXISTING CONDITIONS FOR REQUIREMENT.

PROVIDE COVER WITH CONDUIT NIPPLE WITH BUSHING FOR CABLE EXIT.

PROVIDE KELLUM TYPE GRIP FOR STRAIN RELIEF OF CABLE SPANNING TO

CLUSTER.

1.

2.

3.

4.

5.

6.

7.

8.

ABBREVIATION LEGEND

A.F.F. - ABOVE FINISHED FLOOR

B.F.C. - BELOW FINISHED CEILING

C. - CONDUIT

ER - EQUIPMENT RACK ER-###

M.C. - MAIN CROSSCONNECT

O.F.E. - OWNER FURNISHED EQUIPMENT

RE - REFERENCE, REFER

T.C. - TELECOMMUNICATIONS CLOSET

U.O.N. - UNLESS OTHERWISE NOTED

PATHWAY DISTRIBUTION

RACEWAY CONCEALED OR EXPOSED

RACEWAY HIDDEN OR BELOW FLOOR SLAB

J-HOOKS ON 4' CENTERS

HOME RUN

CONDUIT STUB TO ABOVE ACCESSIBLE CEILING OR CABLE TRAY

CABLE TRAY, SHOWN FOR REFERENCE ONLY. REFER

TO

ELECTRICAL DRAWINGS FOR DETAILS.

DESTINATION

(2) 1" C

CONDUIT

CONDUIT SIZE

NUMBER OF CONDUITS

CONDUITS AND PATHWAY NOTES

GENERAL:

THE DRAWINGS INDICATE ONE ROUTING METHOD OF THE CABLING PATHWAYS. CHANGES

MAY BE MADE TO THE PATHWAY SYSTEM TO ACCOMMODATE SITE CONDITIONS OR

SIMPLIFY INSTALLATION AS LONG AS ADEQUATE SIZING IS MAINTAINED, HORIZONTAL

DISTANCE LIMITATIONS ARE NOT EXCEEDED, AND THE ARCHITECT APPROVES THE

COORDINATION DRAWINGS SUBMITTED FOR REVIEW.

CONDUIT TO OUTLETS SHALL PROVIDE A CONTINUOUS PATHWAY TO THE NEAREST CABLE

TRAY OR ACCESSIBLE CEILING.

REGARDLESS OF PATHWAY TYPE, ALL CABLING SHALL BE SUPPORTED AT A 5'-0" MAXIMUM

INTERVAL.

UNLESS NOTED OTHERWISE, CABLE PATHWAY WITHIN ROOMS WILL RUN PARALLEL TO

WALLS FOR ADDITIONAL 50 LINEAR FEET.

MAINTAIN PROPER BONDING AND GROUNDING OF HORIZONTAL PATHWAYS IN

ACCORDANCE WITH APPLICABLE ELECTRICAL CODES AND STANDARDS, AND

ANSI/TIA/EIA-607

SOLID LINE ( ) DEPICTS CONDUIT IN WALLS OR ABOVE CEILINGS.

DASHED LINE ( ) DEPICTS METALLIC CONDUIT IN SLAB OR COATED RIGID CONDUIT

UNDERGROUND.

CONDUIT:

SIZE ALL CONDUIT IN ACCORDANCE WITH ANSI EIA/TIA-569A CONDUIT CAPACITY

STANDARDS.

UNLESS NOTED OTHERWISE ALL CONDUITS ARE 3/4" C.

CONDUIT RUNS SHALL NOT CONTAIN 90° CONDUIT BODIES.

UNINTERRUPTED, STRAIGHT AND LEVEL CONDUIT RUNS SHALL NOT EXCEED 100

CONTIGUOUS FEET. FOR RUNS IN EXCESS OF 100 FEET, INSERT PULL BOXES AT 100 FOOT

INTERVALS, MAXIMUM.

MAINTAIN PROPER CONDUIT BEND RADIUS IN ACCORDANCE WITH ANSI/EIA/TIA-569-A. FOR

CONDUIT WITH AN INTERNAL DIAMETER OF 2" OR LESS, MAINTAIN A BEND RADIUS OF AT

LEAST 6-TIMES THE INTERNAL CONDUIT DIAMETER. FOR CONDUIT WITH AN INTERNAL

DIAMETER GREATER THAN 2", MAINTAIN A BEND RADIUS OF AT LEAST 10-TIMES THE

INTERNAL CONDUIT DIAMETER.

IF A CONDUIT REQUIRES MORE THAN TWO 90° BENDS, THEN PROVIDE A PULL BOX

BETWEEN SECTIONS WITH 2 BENDS OR LESS. IF A CONDUIT RUN REQUIRES A REVERSE

BEND (BETWEEN 100° AND 180°, THEN INSERT A PULL BOX AT EACH BEND HAVING AN

ANGLE FROM 100° AND 180°. IF A CONDUIT RUN REQUIRES MORE THAN TWO 90° BENDS

BETWEEN PULL BOXES, THEN FOR EACH ADDITIONAL BEND EITHER DERATE THE CONDUIT

CAPACITY BY 15% OR USE THE NEXT LARGER SIZE CONDUIT.

DO NOT CONSIDER A PULL BOX AS A BEND. ALL CONDUITS MUST RUN STRAIGHT

THROUGH A PULL BOX WITH THE BEND EITHER BEFORE OR AFTER THE PULL BOX.

REAM ALL CONDUIT ENDS. FIT STUBBED CONDUITS WITH AN INSULATED BUSHING TO

ELIMINATE SHARP EDGES THAT MAY DAMAGE CABLE DURING INSTALLATION OR SERVICE.

EQUIP ALL CONDUIT WITH "MULE TAPE" OR PULL CORD WITH A MINIMUM TEST RATING OF

1250 LBS.

BACKBONE CABLE CONDUIT FOR FIBER OPTICAL CABLES SHALL BE PROVIDED WITH

INNER-DUCT SIZED ACCORDING TO CONDUIT TRADE SIZE.

ALL PENETRATIONS OF ARCHITECTURAL BARRIERS SHALL BE COMPLETELY SEALED AT

THE CONCLUSION OF INSTALLATION. PENETRATIONS OF FIRE-RATED BARRIERS SHALL BE

FIRE-STOPPED WITH UL AND ASTM APPROVED MATERIALS THAT WILL PRESERVE THE

HOUR-RATING OF THE BARRIER. CABLE TRAY PENETRATIONS SHALL EMPLOY

MECHANICAL SEALING SYSTEMS THAT READILY PERMIT ADDITIONS OF MEDIA IN FUTURE

ADDS, MOVES AND CHANGES. CONDUIT PENETRATIONS SHALL USE LATEX ENDOTHERMIC

SEALANT AROUND THE OUTSIDE PERIMETER AND INTUMESCENT FIRE-STOP PILLOWS

WITHIN. MEMBRANE PENETRATIONS FOR OUTLET BOXES, CONTROL BOXES AND OTHER

EQUIPMENT THAT BREACHES ONE SIDE OF A BARRIER SHALL BE PROTECTED BY

PRODUCTS AND METHODS AS PUBLISHED IN UL CATEGORY CLIV.

ALL CONDUITS ENTERING OR EXITING EQUIPMENT RACKS TO BE ISOLATED WITH A NON-

METALIC SPACER OR FITTING.

1.

2.

3.

4.

5.

6.

7.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

NOTE

ALL AV EQUIPMENT IS OWNER FURNISHED AND

OWNER INSTALLED (OFOI). CONTRACTOR IS TO

PROVIDE INFRASTRUCTURE, PROJECTION

SCREENS, AND EQUIPMENT RACK ER-1 AND ER-2.

KEY PLAN

APPROVED BY

CHECKED BY

A

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SCALE

SEAL

REVISIONS

23456

B

C

D

E

F 2500 McGee Drive Suite 100 Norman, OK 73072

Smith Roberts Baldischwiler

601 S.Lewis Ave.

Tulsa, OK 74104

Howell & Vancuren

1350 South Boulder Ave Suite 600 Tulsa, Oklahoma 74119

Dewberry Engineers Inc.

13431 Broadway Ext.

Suite 101 Oklahoma City, OK 73114

Alvine Engineering

3424 Midcourt Rd.

Suite 124 Carrollton, Tx 75006

WJHW

12" = 1'-0"

/3

/2

:2

:5

P

M

AV-000

GENERAL NOTES

AND LEGENDS

WJHW

CC

BK

06/01/2017

Dewberry Architects Inc.

50085544

B E

T H

A N

Y L

IB

R

A R

Y

C it y o f B e th a n y O k la h o m a

F

IN

A L C

O N

S T

R U

C T

IO

N

D O

C U

M E

N T

S

N

W th

S tr e e t

B e th a n y O

K

1350 South Boulder Ave Suite 600 Tulsa, OK 74119

No. Description Date

File details come from the government source that posted it. Updated .