Attachment_15_-_Exhibit_L_BAAQMD_AZ_AIR_PERMIT.pdf

PDF 369 KB Posted

Attached to
Preventative Maintenance Services for Alcatraz Isl Federal contract opportunity
Solicitation number
140P8623Q0106
Issued by
Department of the Interior National Park Service Pacific West Region

About this file

This document contains an air permit issued by the Bay Area Air Quality Management District to the National Park Service for two diesel generators located at Alcatraz Island. The permit details operating conditions for the generators, including limits on hours of operation, emissions rates for nitrogen oxides, carbon monoxide and particulate matter, fuel sulfur content restrictions, and monitoring and recordkeeping requirements. It also references a related federal contract opportunity posted by the Department of the Interior National Park Service Pacific West Region for preventative maintenance services for equipment at Alcatraz Island.

View the file

Other files for this federal contract opportunity

Other files attached to Preventative Maintenance Services for Alcatraz Isl, newest first.
File Type Posted
Attachment_13_-_Exhibit_E_Alcatraz_Guano_CleanUp_Zones_edit_0003.pdf PDF
Attachment_8_-_Exhibit_B_AZ_PV_System_Training_Manual_0003.pdf PDF
Questions_and_Answers_from_Contractors_0003.pdf PDF
Sol_140P8623Q0106_Amd_0003.pdf PDF
Site_Visit_Sign_In_Sheet_0002.pdf PDF
Questions_and_Answers_from_Site_Visit_on_Alactraz_0002.pdf PDF
Attachment_1_-_Performance_Work_Statement_0002.pdf PDF
Sol_140P8623Q0106_Amd_0002.pdf PDF
Sol_140P8623Q0106_Amd_0001.pdf PDF
Attachment_19_-_52_209-7.pdf PDF
Attachment_2_-_Bid_Schedule.pdf PDF
Attachment_11_-_Exhibit_H2_eONE_2014_drawings.pdf PDF
Attachment_10_-_Exhibit_H1_eone-dh152-grinder-pump-installation-instructions.pdf PDF
Sol_140P8623Q0106.pdf PDF
Attachment_1_-_Performance_Work_Statement.pdf PDF
Attachment_20_-_Limitation_on_Subcontracting_Report_Template.xlsx XLSX spreadsheet
Attachment_12_-_Exhibit_I_-_Directors_Order__83_B4.pdf PDF
Attachment_8_-_Exhibit_F_AZ_PV_System_Training_Manual.pdf PDF
Attachment_7_-_Exhibit_E_Alcatraz_PV_System_Warranty_Management_Plan.pdf PDF
Attachment_6_-_Exhibit_D_-_PV_Inspection_List.pdf PDF
Attachment_4_-_Exhibit_B_Alcatraz_Equipment_Lists.pdf PDF
Attachment_3_-_Exhibit_A_Alcatraz_General_Map.pdf PDF
Attachment_21_-_Quality_Assurance_Surveillance_Plan.pdf PDF
Attachment_18_-_Past_Performance_Questionnaire.pdf PDF
Attachment_17_-_SCA_Wage_Detrmination.pdf PDF
Attachment_16_-_Exhibit_M_General_Requirements_for_Contractors_on_Alcatraz.pdf PDF
Attachment_14_-_Exhibit_K_-_CFR-2020-title40-vol24-part112.pdf PDF
Attachment_13_-_Exhibit_J_Alcatraz_Guano_CleanUp_Zones_edit.pdf PDF
Attachment_9_-_Exhibit_G_Cleaning_of_Historic_Concrete.pdf PDF
Attachment_5_-_Exhibit_C_Alcatraz_Maintenance_Manuals.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

io/28/15 B2596

P E R M IT939 ELLIS STREET

SAN FRANCISCO. CALIFORNIA 94109 TO OPERATE(415) 771-6000

Plant# 12596 Page: 1 Expires: DEC 1, 2017

This document does not permit the holder to violate any District regulation or other law.

National Park Service Fort Mason, Building 201 San Francisco, CA 94123

Location: Alcatraz Island San Francisco, CA 94123

DESCRIPTION [Schedule] PAID

3 Standby Diesel engine, 490 hp, EPA# 9DDXL14.OVLD 515 Stationary Prime Diesel Fueled Generator Set [3,731 days]

Abated by: A3 Catalyzed Diesel Particulate Filter Emissions at: P3 Stack

4 Standby Diesel engine, 490 hp, EPA# ADDXL14.OVLD 515 Stationary Prime Diesel Generator Set [3,731 days]

Abated by: A4 Catalyzed Diesel Particulate Filter Emissions at: P4 Stack

2 Permitted Sources

*** See attached Permit Conditions ***

The operating parameters described above are based on information supplied by permit holder and may differ from the limits set forth in the attached conditions of the Permit to Operate. The limits of operation in the permit conditions are not to be exceeded. Exceeding these limits is considered a violation of District regulations subject to enforcement action.

10/28/is

This document does not permit the holder to violate any District regulation or other law.

PERI’41T CONDITIONS ***

Source# 3 Source# 4 subject to Condition ID# 24786 subject to Condition ID# 24845

32596

BAY AREA AIR QUALITY

MANAGEMENT DISTRICT

SAN FRANCISCO, CALIFORNIA 94109

(415) 771-6000

Plant# 12596 Page: 2 Expires: DEC 1, 2017

10/28/is B2596

P ER M IT939 ELLIS STREET

SAN FRANCISCO, CALIFORNIA941O9 TO OPERATE(415)771-6000

Plant# 12596 Page: 3 Expires: DEC 1, 2017

This document does not permit the holder to violate any District regulation or other law.

*** PERMIT CONDITIONS ***

COND# 24786 applies to S# 3

1. The owner/operator of 5-3 shall not exceed 4368 hours of operation in any consecutive 12-month period.

[Basis: Cumulative Increase; Toxic Risk Screen;

Regulation 2-51

2. The owner/operator of S-3 shall comply with the requirements of Regulation 9-8-304 by January 1, 2012, or the requirements of 9-8-305 by January 1, 2016. If the owner/operator elects to comply with Regulation 9-8-305, the owner/operator shall notify the District in writing no later than January 1, 2012.

[Basis: Regulation 9-8-304, 9-8-305, 9-8-402]

3. Deleted. (S-i has been removed from service.)

[Basis: Cumulative Increase; Offsets]

4. The owner/operator shall abate S-3 by the properly maintained and properly operated A-3 during all times of operation. [Basis:

Cumulative Increase, TBACT]

5. The owner/operator shall not exceed any of the following limits at S-3:

a. NOx: 2.69 g/bhp-hr;

b. CO: 0.16 g/ bhp-hr;

c. PM as determined by a test method in Section 93115.14

(a) (1), Title 17, CCR: 0.01 g/bhp-hr.

[Basis: BACT, TEACT]

6. Deleted. (Initial source test was performed to verify com pliance with Parts Sa, 5b, and 5c on December 18, 2010.

[Basis: BACT, TBACT]

7. The owner/operator shall properly install and operate the following monitoring equipment at 5- 3:

a. A non-resettable totalizing meter that measures the hours of operation for each new

10/28/15 32596

P E R M IT

939 ELLIS STREET

SAN FRANCISCO, CALIFORNIA 94109 TO OPERATE(415) 771-6000

Plant# 12596 Page: 4 Expires: DEC 1, 2017

This document does not permit the holder to violate any District regulation or other law.

PERMIT CONDITIONS ***

stationary prime engine;

b. A backpressure monitor that notifies the owner or operator when the high backpressure limit of the engine is approached.

[Basis: “ATCM for Stationary Compression Ignition Engines” Section 93115.10(e), title 17, CA Code of Regulations]

8. The owner/operator shall not exceed 15 ppm of Sulfur in the fuel used at S-3. [Basis: 40 CFR

60.4207 fb) I

9. In order to demonstrate compliance, the owner/operator shall maintain the following monthly records in a District-approved log for S-3:

a. Hours of operation for each engine;

b. Fuel usage and sulfur content of the fuel for each engine;

c. All source test data to demonstrate compliance.

This log shall be retained on site for at least two years from the date of entry and be made available to district staff upon request. [Basis:

Recordkeeping]

COND# 24845 applies to S# 4

1. The owner/operator of S-4 shall not exceed 4368 hours of operation in any consecutive 12-month period.

[Basis: Cumulative Increase; Toxic Risk Screen;

Regulation 2-5]

2. The owner/operator of 5-4 shall comply with the requirements of Regulation 9-8-304 by January 1, 2012, or the requirements of 9-8-305 by January 1, 2016. If the owner/operator elects to comply with Regulation 9-8-305, the owner/operator shall notify the District in writing no later than January 1, 2012.

10/28/15 B2596

BAY AREA AIR QUALITY

MANAGEMENT DISTRICT

939 ELLIS STREET

SAN FRANCISCO, CALIFORNIA 94709

(415) 771-6000

Plant# 12596 Page: 5 Expires: DEC 1, 2017

This document does not permit the holder to violate any District regulation or other law.

*** PERMIT CONDITIONS ***

[Basis: Regulation 9-8-304, 9-8-305, 9-8-402]

3. The owner/operator shall remove S-2 from service prior to startup operation of 5-4.

[Basis: Cumulative Increase; Offsets]

4. The owner/operator shall abate S-4 by the properly maintained and properly operated A-4 during all times of operation.

[Basis: Cumulative Increase, TBACT]

5. The owner/operator shall not exceed any of the following limits at S-4:

(a) NOx: 2.69 g/bhp-hr;

(b) CO: 0.16 g/ bhp-hr;

[Basis: BACT, TBACT]

6. The owner/operator shall conduct a District-approved source test within 60 days of start-up of S-4 for NOx, and CO in order to demonstrate compliance with emission limits specified in Part 5. The owner/operator shall submit the report of the results within 45 days of the source test.

[Basis: BACT, TBACT]

7. The owner/operator shall properly install and operate the following monitoring equipment at S-4:

(a) A non-resettable totalizing meter that measures the hours of operation for each new stationary prime engine;

(b) A backpressure monitor that notifies the owner or operator when the high backpressure limit of the engine is approached.

[Basis: “ATCM for Stationary Compression Ignition Engines” Section 93115.10(e), title 17, CA Code of Regulations]

8. The owner/operator shall not exceed 15 ppm of Sulfur in the fuel used at S-4.

tBasis: 40 CFR 60.4207(b)]

9. In order to demonstrate compliance, the

10/28/ 15 B2596

This document does not permit the holder to violate any District regulation or other law.

PERIVIIT CONDITIONS ***

owner/operator shall maintain the following monthly records in a District-approved log for S-4:

(a) Hours of operation for each engine;

(b) Fuel usage and sulfur content of the fuel for each engine;

Cc) All source test data to demonstrate compliance.

This log shall be retained on site for at least two years from the date of entry and be made available to district staff upon request.

[Basis: Recordkeepingl

BAY AREA AIR QUALITY

MANAGEMENT DISTRICT

939 ELLIS STREET

SAN FRANCISCO, CALIFORNIA 94109

(415) 771-6000

Plant# 12596 Page: 6

PERMIT

TO OPERATE

Expires: DEC 1, 2017

END OF CONDITIONS

Bay Area Air Quality ** SOURCE EMISSIONS ** PLLNT *12596 Management District Oct 28, 2015

Annual Average lbs/day S# Source Description PART ORG NOx S02 CO

- .49

- .25

.02 .74

** PLANT TOTALS FOR EACH EMITTED TOXIC POLLUTANT **

Pollutant Name Emissions lbs/day

Benzene .02 Diesel Engine Exhaust Particulate Matter .04

3 Stationary Prime Diesel Fueled Generator S 4 Stationary Prime Diesel Generator Set

TO TAL S

.02 .11

.02 .06

.04 .17

4.01 4.08

8.09

File details come from the government source that posted it. Updated .