Att1i_Revised_Drawings_1_7-5-22.pdf

PDF 11 MB Posted

Attached to
GRCA 190083 - Improve Potable Water Supply to Inne
Solicitation number
140P2022R0100
Issued by

About this file

This document provides details on a federal solicitation opportunity and related technical file. The solicitation number is 140P2022R0100 for a project titled "GRCA 190083 - Improve Potable Water Supply to Inne." The opportunity type is a solicitation from the Department of the Interior National Park Service National Office to replace the Transcanyon Waterline and improve potable water systems at Grand Canyon National Park. The technical file is a set of revised drawings dated July 5, 2022 but does not include the content of the drawings. The solicitation seeks to address needed upgrades to the park's water infrastructure through replacement and improvement projects.

View the file

Other files

File Type Posted
Amendment_8_40_91_10_Primary_Meters_and_Transmitters_(IG_Phase_3)_08.pdf PDF
Amendment_8_Questions_and_Answers_9-8-22_08.docx DOCX document
Amendment_8_SF_30_9-8-22_08.pdf PDF
Sol_140P2022R0100_Amd_08.pdf PDF
Amendment_7_Questions_and_Answers_9-2-22_07.docx DOCX document
Sol_140P2022R0100_Amd_07.pdf PDF
Amendment_7_SF_30_9-2-22_07.pdf PDF
Amendment_6_Wage_Determination_AZ20220007_Heavy_06.pdf PDF
Sol_140P2022R0100_Amd_06.pdf PDF
Amendment_6_Questions_and_Answers_8-26-22_06.docx DOCX document
Amendment_6_06_82_00_-_FIBERGLASS_REIN_PLASTIC_FABS_Rev_2022-08-25_06.pdf PDF
Amendment_6_Wage_Determination_AZ20220016_Heavy_06.pdf PDF
Amendment_6_43_23_04_Horizontal_Multistage_Pumps_GRCA_261633_Pump_3_06.pdf PDF
Amendment_6_Wage_Determination_AZ20220030_Building_06.pdf PDF
Amendment_6_SF_30_8-26-22_06.pdf PDF
Amendment_5_Questions_and_Answers_8-19-22_05.docx DOCX document
Sol_140P2022R0100_Amd_05.pdf PDF
Amendment_5_SF_30_8-19-22_05.pdf PDF
Amendment_4_SF_30_8-12-22_04.pdf PDF
Sol_140P2022R0100_Amd_04.pdf PDF
Amendment_4_Att12b_CSF_Drawings_Rev_8-12-22_04.pdf PDF
Amendment_4_Questions_and_Answers_8-12-22_04.docx DOCX document
Amendment_3_03-E504_REV1_2022-08-02_03.pdf PDF
Amendment_3_03-C405_REV1_2022-08-02_03.pdf PDF
Amendment_3_03-E503_REV1_2022-08-02_03.pdf PDF
Sol_140P2022R0100_Amd_03.pdf PDF
Amendment_3_SF_30_8-5-22_03.pdf PDF
Amendment_3_Questions_and_Answers_8-5-22_03.docx DOCX document
Amendment_3_03-C137_REV1_2022-08-02_03.pdf PDF
Amendment_3_03-C131_REV1_2022-08-22_03.pdf PDF
Amendment_2_Questions_and_Answers_7-29-22_02.docx DOCX document
Sol_140P2022R0100_Amd_02.pdf PDF
Amendment_2_SF_30_7-29-22_02.pdf PDF
Sol_140P2022R0100_Amd_01.pdf PDF
Amendment_1_01-E601_REV_1_7-22-22_01.pdf PDF
Amendment_1_01-E104_REV_1_7-22-22_01.pdf PDF
Amendment_1_Questions_and_Answers_7-22-22_01.docx DOCX document
Amendment_1_SF_30_7-22-22_01.pdf PDF
Amendment_1_01-E100_REV1_7-22-22_01.pdf PDF
Amendment_1_01-E631_REV_1_7-22-22_01.pdf PDF
Att4b_GRCA 190083 Basis of Design Report_Appendices only.pdf PDF
Att1f_GRCA 190083 Vol 04_Drawings_Pg 497to698_4-22-22.pdf PDF
Att7d_TransCanyon Waterline Drone Footage - End Plateau.mp4 MP4 file
Att6f_Innercanyon_Single-Phase_Transformer_Short_Circuit.pdf PDF
Att7e_Phantom_Rnch_Headworks_Excav_Photos.pdf PDF
Att6i_GRCA_190083_Geotech_Field_Work_Photo_Album_4-17-18.pdf PDF
Att7b_TransCanyon_Waterline_Drone_Footage.mp4 MP4 file
Att2a_GRCA_190083_Final_CD_Specifications_Vol_1_Division_1.pdf PDF
Att6c_Suez_Proposal_for_GRCA_190083_MF-UF_Equip_9-2-20.pdf PDF
Att5b_Addendum_to_the_Geotechnical_Investigation_Report_12-23-20.pdf PDF
Show 40 more

Latest 50 of 93 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 REV 1 ADEQ COMMENTS 05/22/22

R

R = DUCT WIDTH

SLOPE 4" IN 12"

FULL RADIUS ELBOWSQUARE THROAT ELBOW

RECTANGULAR BRANCH TAKE-OFF RECTANGULAR TEE

NOTE: SEE "BRANCH TAKEOFF & DAMPER" DETAIL, ALSO

SQUARE THROAT ELBOW

MAY BE USED TO CONSERVE

SPACE

NOTE:

INSTALL MANUAL VOLUME DAMPERS

IN ALL LOW PRESSURE SUPPLY, RETURN AND EXHAUST DUCT

BRANCHES.

SQUARE THROAT

ELBOW MAY BE

USED TO

CONSERVE

SPACE

2"

ABOVE GROUND WALL PENETRATION ONLY

PVC SCH40 PIPE

SLEEVE SIZE TO FIT

REFRIGERANT PIPE

EXTERIOR NON-RATED WALL

LIQUID REFRIGERANT PIPE W/

FLEXIBLE ELASTOMERIC

INSULATION

0.25" TYPICAL CLEARANCE

BETWEEN PIPE AND SLEEVE

PVC PIPE SLEEVE SIZE NOT TO EXCEED 6" SCH 40

WEATHERPROOF

SEALANT BETWEEN PIPE

SLEEVE AND WALL

FLEXIBLE WEATHERPROOF

FOAM FILL AROUND PIPE

REFRIGERANT SUCTION PIPE W/

FLEXIBLE ELASTOMERIC

INSULATION

SEE ARCHITECTURAL DRAWINGS

FOR WALL CONSTRUCTION

DETAILS, DIMENSIONS, AND OTHER

REQUIREMENTS.

MOTOR OPERATED OR BACKDRAFT

DAMPER IN DUCTED APPLICATION

SHALL BE FULL SIZE OF DUCT

UNLESS OTHERWISE INDICATED.

REFER TO PLANS FOR DUCT SIZE

AND ROUTING.

NOTES:

WALL

LOUVER SEE

SCHEDULE

FOR SIZE

MOTOR OPERATED

OR BACKDRAFT

DAMPER WHERE

INDICATED

CLIP ANGLE

FASTEN TO

LOUVER

PROVIDE SHEET

METAL DUCT

SEALANT,

BACKER ROD

AND SHIMS

INSECT SCREEN

1.

2.

3.

NOTE:

1. INSTALL CONCENTRIC VENT IN STRICT ACCORDANCE WITH

MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.

MAINTAIN MINIMUM CLEARANCES AWAY FROM OTHER

STRUCTURES.

SEALANT STAINLESS STEEL DRAWBAND

1/4" MIN. CLEARANCE TO RAIN

COLLAR

WATERTIGHT SHEET METAL RAIN COLLAR

OVERLAPPING FLASHING COLLAR BY 3"

TO 4"

SHEET METAL FLASHING COLLAR

MINIMUM OF 8" ABOVE ROOFING

1/4" MINIMUM CLEARANCE BETWEEN

FLASHING COLLAR AND SUPPORT

MINIMUM 36" UNLESS MANUFACTURER

REQUIRED HEIGHT IS HIGHER.

FLUE BOOT

FASTENERS AS REQUIRED

COMPATIBLE SEALANT UNDER

BOOT PERIMETER

COMPATIBLE SEALANT UNDER

TOP OF BOOT

STAINLESS STEEL CLAMPING

RING

FAN SECTION

SPRING ISOLATOR (TYP.)

STRUCTURE

P-TRAP

CHILLED WATER COOLING COIL

PROVIDE A MOISTURE SWITCH IN

AUXILIARY DRAIN PAN TO

DE-ENERGIZE FAN AND COIL

UNIT UPON DETECTION OF

CONDENSATE

PRIMARY

CONDENSATE DRAIN

SECONDARY GALVANIZED

STEEL DRAIN PAN

SUSPENDED FROM UNIT

REFRIGERANT PIPING

RETURN OR

FLEXIBLE DUCT

CONNECTION (TYP.)

ACCESS DOOR

ACCESS DOOR

FILTER SECTION

OUTSIDE

(TYP.)

SUPPLY AIR DUCT

AIR DUCT

NOTES:

1. NOT ALL AIR HANDLING UNITS HAVE ALL COMPONENTS AS SHOWN.

REFER TO SCHEDULES FOR EXACT REQUIREMENTS.

FLEXIBLE CONNECTION

WATER TIGHT.

FASTENERS. CAULK

OPENING WITH METAL

TO STEEL FRAMED

SECURE WALL COLLAR

AUTOMATIC DAMPER

(REFER TO

STRUCTURAL DWG.)

STEEL FRAMED OPENING

EXTERIOR WALL

FAN WALL COLLAR

SIDE GUARD

MOTOR

WALL MTD FAN. SEE

SCHEDULES ON

PLANS

(REFER TO

ARCHITECTURAL DWG.)

AIR FLOW

WATER TIGHT.

FASTENERS. CAULK

OPENING WITH METAL

TO STEEL FRAMED

SECURE WALL COLLAR

AUTOMATIC DAMPER

(REFER TO

STRUCTURAL DWG.)

STEEL FRAMED OPENING

EXTERIOR WALL

FAN WALL COLLAR

SIDE GUARD

MOTOR

AIR FLOW

LOUVER SEE

SCHEDULE FOR SIZE

(REFER TO

ARCHITECTURAL DWG.)

WALL MTD FAN. SEE

SCHEDULES ON

PLANS

SPECIFIED FORFLANGED

1-1/2" MIN. TO 3"

MATERIAL TAUT.

6" NOMINAL WITH

MAX. INSTALLED.

DUCTWORK.

RIVET ON

4" CENTERS

DRAW BAND

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

ON FAN SIDE

CONNECTION

4" CENTERS

FLANGED

FLANGE

5/16"

1/2"

BOLT ON

ON FAN SIDE

CONNECTION

1"x1/8"

WASHER

1 1/2" MIN. TO 3" MAX.

INSTALLED 6" NOMINAL

WITH MATERIAL

1/2"

ON 12" CENTERS

1-1/2"

DUCTWORK.

SPECIFIED FOR

SHEET METAL AS

SHEET METAL SCREWS

DUCT

SHEET METAL AS

POCKET

1-1/2"

SLIP

AS SPECIFIED

FLEXIBLE MATERIAL

1"X1/8" BAND IRON

BOLT ON 4" CENTERS

OF BOLT

POSITION

ALTERNATE

1" FLANGE

DUCT

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N

P S

G ra n d C a n y o n

S o u th

R im W

T P

/1

M

P

S R

W T

P .r v t

/1

/2

:0

:5

A M

M503

GRAND CANYON NATIONAL PARK

190083

MECHANICAL STANDARD

DETAILS 3

A. ORTON

D. SAUCEDO

04/22/2022

S. GAETA

14456600-

NO SCALE00-M503

TYPICAL LOW PRESSURE DUCT

CONNECTION2

NO SCALE00-M503

TYPICAL REFRIGERANT PIPE SLEEVE

THROUGH NON-RATED EXTERIOR WALL3

NO SCALE00-M503

4 DUCTED LOUVER IN WALL DETAIL

NO SCALE00-M503

5 CONCENTRIC FLUE DETAIL

NO SCALE00-M503

6 SUSPENDED AIR HANDLING UNIT DETAIL

NO SCALE00-M503

7 WALL MOUNTED PROP FAN DETAIL

NO SCALE00-M503

8 WALL MOUNTED PROP FAN W/ LOUVER DETAIL

NO SCALE00-M503

1 FLEXIBLE DUCT CONNECTION DETAIL

06/13/2022

REV 1 DSC QA COMMENTS 06/13/22

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N

P S

G ra n d C a n y o n

S o u th

R im W

T P

/1

M

P

S R

W T

P .r v t

/2

/2

:5

:5

P M

M602

GRAND CANYON NATIONAL PARK

190083

MECHANICAL SCHEDULES 2A. ORTON

D. SAUCEDO

04/22/2022

S. GAETA

14456600-

9. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.

8. PROVIDE WALL MOUNTING BRACKET FOR INDOOR UNIT.

7. PROVIDE WITH INTEGRAL CONDENSATE PUMP. CONDENSATE PUMP SHALL NOT REQUIRE A SEPARATE ELECTRICAL CONNECTION.

6. PROVIDE WIRED WALL MOUNTED DIGITAL CONTROLLER AND TEMPERATURE SENSOR.

5. SINGLE POINT POWER. INDOOR UNIT SERVED BY OUTDOOR UNIT.

4. NOMINAL CAPACITY BASED ON AHRI CONDITIONS.

3. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.

2. MINIMUM SENSIBLE COOLING CAPACITY REQUIRED AT PROJECT ELEVATION (2,570 FT) AND SCHEDULED AMBIENT TEMPERATURE.

1. MINIMUM SENSIBLE COOLING CAPACITY REQUIRED AT PROJECT ELEVATION (7,000 FT) AND SCHEDULED AMBIENT TEMPERATURE.

NOTES:

04-SS-1 / 04-SSCU-1 SCADA IT WALL MOUNT 17.5 9.3 18,100 31,400 22,400 750 50 115 35 150 19.8 20 208/1 MFR MFR SS-A DAIKIN FTX30 RX30 2,5-8

01-SS-2 / 01-SSCU-2 VESTIBULE WALL MOUNT 17.5 9.3 20,000 31,400 22,400 750 50 100 10 150 19.8 20 208/1 MFR MFR SS-B DAIKIN FTX30 RX30 1,5-8

01-SS-1 / 01-SSCU-1 SCADA IT WALL MOUNT 17.5 9.3 20,000 31,400 22,400 750 50 100 10 150 19.8 20 208/1 MFR MFR SS-A DAIKIN FTX30 RX30 1,5-8

(CFM) WT. (LBS)

SUMMER WINTER

WT. (LBS) PHASE BY

TAG SERVICE CONFIGURATION

SEER HSPF COOLING HEATING @ 17F

AIR FLOW UNIT

AMBIENT (DEG F)

UNIT

MCA (A) MOCP (A)

VOLTS/ DISCONNECT CONTROLLER/

STARTER BY

MFR

INDOOR

MODEL

OUTDOOR

MODEL

NOTES

MIN. EFFICIENCY

MIN. SENSIBLE

CLG. CAPACITY

(BTU/hr)

NOMINAL CAPACITY (BTU/hr) (NOTE 4) INDOOR UNIT OUTDOOR UNIT ELECTRICAL (NOTE 3)

CONTROL

TYPE

(NOTE 9)

BASIS OF DESIGN

DUCTLESS MINI-SPLIT HEAT PUMP SCHEDULE

14. PROVIDE WITH BELT TENSIONER AND BELT GUARD.

13. ALL ALUMINUM CONSTRUCTION. PROVIDE WITH FLEXIBLE CONNECTORS, ISOLATION RAILS, AND RUBBER-IN-SHEAR ISOLATORS.

12. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.

11. PROVIDE WITH AUTOMATIC BACKDRAFT DAMPER.

10. PROVIDE WITH MFR'S FLOW SWITCH, SECONDARY LINT TRAP, AND WALL TERMINATION LOUVER/BACKDRAFT DAMPER. UL705 CERTIFIED.

9. SCHEDULED ESP EXCLUDES HOUSING, SHUTTER, AND SCREEN DAMPER LOSSES.

8. HOUSED PROP FAN WITH DISCHARGE SHUTTER, ALUMINUM BIRD SCREEN, WIRE MOTOR GUARD. DISCHARGE SHUTTER FINISH TO BE ARCHITECTURAL BRONZE.

7. PROVIDE WITH VIBRATION ISOLATORS FOR UNIT MOUNTING AS RECOMMENDED BY THE FAN MANUFACTURER.

6. PROVIDE WITH MOTOR SIDE WIRE GUARD.

5. PROVIDE WITH EC MOTOR AND LOCAL FAN SPEED CONTROLLER.

4. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME PLATE RATING.

3. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.

2. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 2,570 FT.

1. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 7,000 FT.

NOTES:

04-DF-1 DRYER BOOSTER FAN INLINE 130 0.40 - - DIRECT - - 0.10 0.25 115/1 EC MFR/ECM DF-A DEDPV-705 FANTECH 25 2,7,10

04-EF-2 CHEMICAL STORAGE RM EXHAUST VENT SET 550 0.50 2,688 1,725 BELT TEFC PHENOLIC 0.36 0.50 115/1 MFR MFR/ECM EF-B CPA LOREN COOK 200 2,13,14

04-EF-1 GENERAL EXHAUST INLINE 150 0.50 1,457 1,725 DIRECT ODP-EC EPOXY PC 0.04 0.25 115/1 MFR MFR/ECM EF-A SQN-D LOREN COOK 100 2,5,7

01-EF-11 PROCESS AREA VENTILATION INLINE 450 0.50 1,454 1,725 DIRECT ODP-EC EPOXY PC 0.12 0.25 115/1 MFR MFR/ECM EF-F SQN-D LOREN COOK 100 1,5,7

01-EF-10 PROCESS AREA VENTILATION INLINE 450 0.50 1,454 1,725 DIRECT ODP-EC EPOXY PC 0.12 0.25 115/1 MFR MFR/ECM EF-F SQN-D LOREN COOK 100 1,5,7

01-EF-9 BRINE TANK VAULT VENTILATION PROP 300 0.35 1,305 1,725 DIRECT ODP-EC EPOXY PC 0.08 0.25 115/1 MFR MFR/ECM EF-E XWD-VF LOREN COOK 100 1,5,6

01-EF-8 BASIN VENTILATION INLINE 4,800 0.90 1,519 1,725 DIRECT TEFC-EC EPOXY PC 1.70 2.00 208/3 MFR MFR/ECM EF-D SQN-D LOREN COOK 225 1,5,7

01-EF-7 GENERAL EXHAUST INLINE 225 0.50 1,495 1,725 DIRECT ODP-EC EPOXY PC 0.05 0.33 115/1 MFR MFR/ECM EF-A SQN-D LOREN COOK 100 1,5,7,11

01-EF-6 CAUSTIC SODA ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14

01-EF-5 SODIUM HYPOCHLORITE ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14

01-EF-4 COAGULANT ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14

01-EF-3 CHEMICAL DRUM ROOM EXHAUST INLINE 1,700 0.50 1,530 1,725 BELT TEFC PHENOLIC 0.41 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 100 1,14

01-EF-2 PROCESS AREA VENTILATION PROP 30,000 0.15 706 1,725 BELT TEFC EPOXY PC 5.38 7.50 460/3 MFR EC/NOTE 3 EF-C EPB LOREN COOK 700 1,8,9,14

01-EF-1 PROCESS AREA VENTILATION PROP 30,000 0.15 706 1,725 BELT TEFC EPOXY PC 5.38 7.50 460/3 MFR EC/NOTE 3 EF-C EPB LOREN COOK 700 1,8,9,14

FAN MOTOR BHP (NOTE 4) MHP (NOTE 4) VOLTAGE/PHASE DISCONNECT BY CONTROLLER/STARTER BY/TYPE MODEL MANUFACTURER

SYMBOL SERVICE TYPE

AIRFLOW

(CFM)

ESP

(IN. WC.)

RPM

DRIVE

MOTOR

TYPE

COATING

ELECTRICAL CONTROL

TYPE

(NOTE 12)

BASIS OF DESIGN

WEIGHT

(LBS)

NOTES

FAN SCHEDULE

9. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.

8. PROVIDE BV-4 BALANCED FANS AND SHAFT GROUNDING RING.

7. PROVIDE WITH PIEZOELECTRIC FLOW METER FOR EACH FAN AND TOTALIZER WITH DIGITAL READOUT OF FAN ARRAY FLOW.

6. PROVIDE MANUFACTURER RECOMMENDED FLOOR SPRING ISOLATORS WITH 2" DEFLECTION TO SUPPORT ENTIRE ARRAY.

5. PROVIDE EACH FAN WITH AN INLET BACKDRAFT DAMPER AND INLET SCREEN.

4. EACH FAN IN THE ARRAY SHALL BE A MODULAR UNIT CAPABLE OF BEING REPLACED INDIVIDUALLY.

3. FAN SHALL NOT EXCEED 90% OF THE RATED MOTOR HORSEPOWER.

2. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.

1. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 7,000 FT.

NOTES:

01-FA-1 PROCESS AREA VENTILATION PLENUM DIRECT 60,000 0.85 3H X 5W TEFC-PE 1.64 2 21.10 30 460/3 EC EC/VFD SF-A MPA LOREN COOK 5,600 4-8

BHP MHP BHP (NOTE 3) MHP (NOTE 3) VOLTAGE/PHASE DISCONNECT BY CONTROLLER BY/TYPE MODEL MANUFACTURER

SYMBOL SERVICE TYPE DRIVE

TOTAL

AIRFLOW

(CFM)

ESP

(IN. WC.)

ARRAY

CONFIG.

MOTOR

TYPE

EACH FAN TOTAL ARRAY ELECTRICAL (NOTE 2) CONTROL

TYPE

(NOTE 9)

BASIS OF DESIGN

WEIGHT

(LBS)

NOTES

FAN ARRAY SCHEDULE

1REV 1 DSC QA COMMENTS 6/20/22

06/20/2022

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N

P S

G ra n d C a n y o n

S o u th

R im W

T P

/1

M

P

S R

W T

P .r v t

/2

/2

:5

:5

P M

M603

GRAND CANYON NATIONAL PARK

190083

MECHANICAL SCHEDULES 3A. ORTON

D. SAUCEDO

04/22/2022

S. GAETA

14456600-

5. PROVIDE WITH INTEGRAL OPPOSED BLADE DAMPER WHERE DAMPER IS NOT SHOWN IN DUCTWORK.

4. PROVIDE FULL 22x22 CORE AREA. WHERE SHOWN DUCTED, PROVIDE TRANSITION TO INDICATED DUCT SIZE.

3. ALL SUPPLY DIFFUSERS SHALL HAVE 4-WAY THROW UNLESS OTHERWISE INDICATED ON PLANS.

2. AIR DEVICE SHALL HAVE A FULL SIZED CORE AREA AS SPECIFIED. PROVIDE TRANSITION TO SPECIFIED INLET SIZE AS REQUIRED.

1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

NOTES:

EG-2 ALUMINUM 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 350FL 2,5

EG-1 ALUMINUM EGG CRATE LAY-IN 8X8 12X12 WHITE TITUS 50F 2

XG-1 316 STAINLESS HEAVY DUTY 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 MILL TITUS 33RL-SS 2

RG-2 ALUMINUM 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 350FL 2,5

RG-1 ALUMINUM EGG CRATE LAY-IN 22x22 24x24 WHITE TITUS 50F 2,4

SG-1 ALUMINUM 3/4" SPC DBL DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 300FL 2,5

DL-1 ALUMINUM SPLIT DRUM LOUVER DUCT MOUNT 20X12 INLET + 1 MILL TITUS DL-SV 5

CD-2 ALUMINUM SQUARE PLAQUE VARIES SEE PLANS 12x12 WHITE TITUS OMNI-AA 3

CD-1 ALUMINUM SQUARE PLAQUE VARIES SEE PLANS 24x24 WHITE TITUS OMNI-AA 3

SYMBOL MATERIAL TYPE MARGIN (NOTE 1) INLET SIZE (IN) FACE SIZE (IN) FINISH MANUFACTURER MODEL NOTES

GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE

12. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.

11. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAMEPLATE RATING.

10. PROVIDE WITH STAINLESS STEEL INSULATED CONDENSATE DRAIN PAN.

9. PROVIDE WITH LINE SET REGULATOR SUITABLE FOR 2 PSI SERVICE.

8. PROVIDE WITH INTEGRAL CONTROLS AND REMOTE MONITORING PANEL.

7. PROVIDE WITH MOTORIZED INLET DAMPER.

6. PROVIDE WITH ANGLED FILTER SECTION AND SIDE ACCESS FILTERS WITH HINGED ACCESS DOORS.

5. PROVIDE WITH INLET AND MANIFOLD GAS PRESSURE GAUGES.

4. DOUBLE WALL INSULATED CONSTRUCTION WITH TOP OR END DISCHARGE AS INDICATED ON PLANS.

3. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.

2. MINIMUM CAPACITY REQUIRED AT PROJECT ELEVATION OF 7,000 FT.

1. EXTERNAL STATIC PRESSURE INCLUDES SYSTEM LOSSES AND CLEAN/DIRTY FILTER LOSSES ONLY.

NOTES:

NOTES 4-9 4-10 4-9 4-9 4-10 4-9

BASIS OF DESIGN MODEL DG DGX DG DG DGX DG

BASIS OF DESIGN MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK GREENHECK GREENHECK

CONTROL TYPE (NOTE 3) MAU-A MAU-D MAU-A MAU-B MAU-D MAU-C

WEIGHT (LBS) 725 950 725 800 1,000 800

UNIT INFORMATION

CONTROLLER/STARTER BY/TYPE MFR/VFD MFR/VFD MFR/VFD MFR/VFD MFR/VFD MFR/VFD

DISCONNECT BY MFR MFR MFR MFR MFR MFR

MOCP 15 15 15 15 15 15

MCA 2.9 2.8 2.9 9.8 4 9.8

VOLTAGE/PHASE 460/3 460/3 460/3 460/3 460/3 460/3

ELECTRICAL (NOTE 11)

DIRTY FILTER ALLOWANCE A.P.D. (IN. WC) 0.25 0.25 0.25 0.25 0.25 0.25

MAX FACE VEL (FPM) 500 500 500 500 500 500

TYPE 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8

FILTERS

OUTPUT CAPACITY (MBH) (NOTE 2) 46,190 46,190 46,190 115,475 74,888 115,475

INPUT CAPACITY (MBH) 50,207 50,207 50,207 125,516 81,400 125,516

LEAVING AIR TEMPERATURE (DEG F) 65 65 65 65 65 65

ENTERING AIR TEMPERATURE (DEG F) 10 10 10 10 10 10

INLET PRESSURE (IN W.C.) 3-14 3-14 3-14 3-14 3-14 3-14

FUEL TYPE PROPANE PROPANE PROPANE PROPANE PROPANE PROPANE

DIRECT-FIRED GAS FURNACE

SENSIBLE CAPACITY (MBH) (NOTE 2) - 29,400 - - 47,040 -

TOTAL CAPACITY (MBH) (NOTE 2) - 29,400 - - 47,040 -

LEAVING AIR DB/WB (DEG F) - 60 / 45.4 - - 60 / 45.4 -

ENTERING AIR DB/WB (DEG F) - 95 / 58.2 - - 95 / 58.2 -

DIRECT EXPANSION COOLING COIL

MOTOR HP (NOTE 10) 1 1 1 5 1-1/2 5

BRAKE HP (NOTE 10) 0.61 0.62 0.61 1.43 0.86 1.43

BLOWER RPM 2,015 2,031 2,015 2,650 2,217 2,650

EXT. STATIC PRESSURE (IN. WC) (NOTE 1) 1.25 1.25 1.25 1.25 1.25 1.25

DRIVE / TYPE DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM

SUPPLY AIRFLOW (CFM) 1,000 1,000 1,000 2,500 1,600 2,500

SUPPLY FAN

TYPE INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED

SERVICE COAGULANT ROOM SODIUM HYPOCHLORITE RM CAUSTIC SODA ROOM PROCESS AREA CHEMICAL DRUM ROOM PROCESS AREA

SYMBOL 01-MAU-1 01-MAU-2 01-MAU-3 01-MAU-4 01-MAU-5 01-MAU-6

MAKE-UP AIR UNIT SCHEDULE

5. PROVIDE WITH ADJUSTABLE COUNTERBALANCED BACKDRAFT DAMPER EQUIVALENT TO RUSKIN CBD4 FULL SIZE OF LOUVER.

4. PROVIDE WITH PVDF (KYNAR 500, HYLAR 5000 OR DURANAR) COATING.

3. PROVIDE WITH ALUMINUM INSECT SCREEN.

2. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION.

1. COLOR TO BE ARCHITECTURAL BRONZE. FINAL APPROVAL OF COLOR BY ARCHITECT.

NOTES:

04-L-07 04-AHU-3 RELIEF AIR STD 6,250 44X76 457 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4,5

04-L-06 04-AHU-3 OUTSIDE AIR INTAKE STD 6,890 44X76 504 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4

04-L-05 04-AHU-2 OUTSIDE AIR INTAKE STD 5,200 44X76 380 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4

04-L-04 04-EF-2 EXHAUST AIR FLG 550 16X16 480 1.15 0.05 RUSKIN ELF6375DX 1,2,3,4,5

04-L-03 04-AHU-2 RELIEF AIR STD 5,200 80X24 778 6.69 0.08 RUSKIN ELF6375DX 1,2,3,4,5

04-L-02 04-EF-1 EXHAUST AIR FLG 150 16X16 206 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5

04-L-01 04-AHU-1 OUTSIDE AIR INTAKE FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4

01-L-18 01-EF-11 EXHAUST AIR FLG 450 16X16 616 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-17 01-EF-10 EXHAUST AIR FLG 450 16X16 616 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-16 01-EF-9 EXHAUST AIR FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-15 01-EF-9 OUTSIDE AIR INTAKE FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4

01-L-14 01-EF-8 EXHAUST AIR FLG 4,800 64X48 392 12.2 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-13 01-AHU-4 OUTSIDE AIR INTAKE STD 205 16X16 280 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4

01-L-12 01-EF-3 EXHAUST AIR FLG 1,700 32X24 661 2.57 0.06 RUSKIN ELF6375DX 1,2,3,4,5

01-L-11 PROCESS AREA RELIEF AIR FLG 3,200 54X48 312 10.3 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-10 PROCESS AREA RELIEF AIR FLG 2,500 36X30 630 3.97 0.06 RUSKIN ELF6375DX 1,2,3,4,5

01-L-09 01-EF-6 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-08 01-EF-5 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-07 01-EF-4 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5

01-L-06 MAKE-UP AIR UNIT INTAKE FLG 8,000 64X48 653 12.2 0.07 RUSKIN ELF6375DX 1,2,3,4

01-L-05 01-MAU-5 OUTSIDE AIR INTAKE FLG 1,600 48X48 176 9.08 0.05 RUSKIN ELF6375DX 1,2,3,4

01-L-04C 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4

01-L-04B 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4

01-L-04A 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4

01-L-03 01-AHU-3 OUTSIDE AIR INTAKE STD 3,650 72X24 510 6.28 0.06 RUSKIN ELF6375DX 1,2,3,4

01-L-02 01-AHU-1 OUTSIDE AIR INTAKE STD 2,160 48X24 528 4.13 0.05 RUSKIN ELF6375DX 1,2,3,4

01-L-01

01-AHU-1 RELIEF AND

01-EF-07 EXHAUST

STD 2,385 48X24 577 4.13 0.05 RUSKIN ELF6375DX 1,2,3,4

(CFM) (IN) (FPM) AREA (SQ.FT.) LOSS (IN.W.G.)

MANUFACTURER MODEL

SYMBOL SERVICE

FRAME

TYPE

AIRFLOW SIZE WxH VELOCITY MIN. FREE MAX. PRESSURE

BASIS OF DESIGN

NOTES

LOUVER SCHEDULE

9. TWO STAGE SEPARATED COMBUSTION FURNACE.

8. PROVIDE WITH HIGH ALTITUDE KIT IF REQUIRED BY MANUFACTURER.

7. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.

6. PROVIDE WITH LINE PRESSURE REGULATOR SUITABLE FOR 2 PSI SERVICE AND COMPATIBLE WITH UNIT TURNDOWN REQUIREMENTS.

5. PROVIDE WITH FURNACE CONTROLLER AND MODULATING GAS VALVE WITH TURNDOWN TO 35%.

4. PROVIDE MANUFACTURER'S CONCENTRIC VENT TERMINATION KIT. REFER TO PLANS FOR CONFIGURATION.

3. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT AND FLEXIBLE GAS CONNECTOR.

2. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.

1. SCHEDULED NOMINAL PERFORMANCE ACCOUNTS FOR THE PROJECT ELEVATION OF 7,000 FT.

NOTES:

01-GDH-1 01-AHU-1 0.5 2,180 57.4 100.6 100,000 80,000 115/1 MFR MFR AHU-C 175 MODINE DFS 3,4,5,6,8,9

AIR FLOW

(CFM)

E.A.T.

(DEG. F.)

L.A.T.

(DEG. F.)

INPUT

CAPACITY

(BTU/hr)

OUTPUT

CAPACITY

(BTU/hr)

VOLT/

PHASE

DISCONNECT

BY

CONTROLLER/

STARTER BY

MFR MODEL

SYMBOL SERVICE

MAX PRESSURE

DROP

(IN. W.C.)

PROPANE GAS FURNACE (NOTE 1) ELECTRICAL (NOTE 2)

CONTROL

TYPE

(NOTE 7)

WEIGHT

(LBS)

BASIS OF DESIGN

NOTES

GAS-FIRED DUCT HEATER SCHEDULE

1REV 1 DSC QA COMMENTS 6/20/22

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT

DAMPER.

FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN

SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",

THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.

SEQUENCE OF OPERATION:

WHEN IN OCCUPIED MODE, THE EXHAUST FAN SHALL OPERATE

CONTINUOUSLY AT A CONSTANT SPEED.

WHEN IN UNOCCUPIED MODE, THE EXHAUST FAN SHALL BE DE-ENERGIZED.

SCADA SYSTEM CONNECTIONS:

• FROM SCADA - OCCUPIED/UNOCCUPIED MODE

• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER

CT TO SCADA

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF AN INLINE OR UTILITY VENT SET EXHAUST FAN

SERVING A CHEMICAL STORAGE ROOM WITH GRAVITY BACKDRAFT DAMPER

AND ONE OR MORE HORN/STROBE ALARM DEVICES TO INDICATE INADEQUATE

FLOW.

SEQUENCE OF OPERATION:

THE EXHAUST FAN SHALL OPERATE CONTINUOUSLY AT A CONSTANT SPEED

24/7.

IF THE EMERGENCY ALARM PUSH-BUTTON IS ACTIVATED, THE EXHAUST FAN

AND ASSOCIATED MAKE-UP AHU SHALL BE SHUT DOWN.

IF THE FLOW SWITCH IS NOT ACTIVATED FOR AT LEAST 0.5 SECONDS (ADJ.),

INDICATING INADEQUATE FLOW, OR IF THE EMERGENCY ALARM IS ACTIVATED

MANUALLY, AN ALARM SHALL BE GENERATED AT THE SCADA SYSTEM

OPERATOR WORKSTATION, AND THE ASSOCIATED HORN/STROBE DEVICES

SHALL BE ACTIVATED. ALARM MUST BE RESET MANUALLY.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - VENTILATION ALARM ACTIVATED

TO SCADA

F

HORN/STROBE DEVICE(S)

REF: PLANS FOR QUANTITY

AND LOCATIONS.

SEE 28 42 00

EAC

PANEL

120V

EMERGENCY ALARM

PUSH-BUTTON.

REF: PLANS FOR

LOCATION.

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF TWO PROPELLER TYPE EXHAUST FANS OPERATING

IN A LEAD/LAG FASHION WITH GRAVITY BACKDRAFT DAMPERS. BACKDRAFT

DAMPERS SHALL BE EQUIPPED WITH SHUTTER SWITCH AND DRY CONTACT

FOR FAN STATUS.

THE SYSTEM SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND",

BOTH FANS SHALL OPERATE. WHEN IN "OFF" BOTH FANS SHALL BE OFF.

WHEN IN "AUTO", THE FANS SHALL OPERATE AS DESCRIBED IN THIS

SEQUENCE.

SEQUENCE OF OPERATION:

A STANDALONE LEAD/LAG CONTROLLER SHALL PROVIDE THE CONTROL

LOGIC TO STAGE AS DESCRIBED BELOW AND ALTERNATE LEAD/LAG

DESIGNATION BETWEEN FANS TO BALANCE OPERATING TIME.

THE LEAD EXHAUST FAN SHALL BE ENABLED AND SHALL OPERATE AT

CONSTANT SPEED WHENEVER THE SPACE TEMPERATURE EXCEEDS THE

PRIMARY SETPOINT OF 85 DEG F (ADJ.).

THE LAG EXHAUST FAN SHALL BE ENABLED AND SHALL OPERATE AT

CONSTANT SPEED IF THE SPACE TEMPERATURE CONTINUES TO RISE

ABOVE THE SECONDARY SETPOINT OF 95 DEG F (ADJ.).

THE LAG FAN SHALL BE DISABLED IF THE SPACE TEMPERATURE FALLS

BELOW 90 DEG F (ADJ.) FOR MORE THAN 30 MINUTES.

THE LEAD FAN SHALL BE DISABLED IF THE SPACE TEMPERATURE FALLS

BELOW 80 DEG F (ADJ.) FOR MORE THAN 30 MINUTES.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - FAN STATUS VIA SHUTTER FLOW SWITCH

EF

M

EXHAUST

AIR

F

T

SPACE TEMP. SENSOR

REF: FLOOR PLANS

LEAD/LAG

CONTROLLER

TO SCADA

F TO SCADA

DF

M

DRYER

EXHAUST

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF AN INLINE DRYER BOOSTER FAN AND ASSOCIATED

CONTROLS/FLOW SWITCH.

SEQUENCE OF OPERATION:

THE DRYER BOOSTER FAN SHALL BE ENABLED WHENEVER THE INTEGRAL

FLOW SWITCH DETECTS THAT THE CONNECTED DRYER IS OPERATING.

SCADA SYSTEM CONNECTIONS:

• NONE

F

SF

M

OUTSIDE

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF A DIRECT DRIVE PLENUM SUPPLY FAN ARRAY WITH MOTOR

OPERATED DAMPER AND MERV-8 FILTER BANK UPSTREAM.

FAN ARRAY SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN

ARRAY SHALL OPERATE AT A USER SELECTED SPEED VIA THE VFD. WHEN IN "OFF"

THE FAN ARRAY SHALL BE OFF. WHEN IN "AUTO", THE FAN ARRAY SHALL OPERATE

AS DESCRIBED IN THIS SEQUENCE.

SEQUENCE OF OPERATION:

THE FAN ARRAY CONTROLLER SHALL BE CAPABLE OF RECEIVING A FLOW

SETPOINT FROM THE SCADA SYSTEM AND CONTROLLING THE ARRAY'S VARIABLE

FREQUENCY DRIVE. EACH FAN IN THE ARRAY SHALL BE EQUIPPED WITH A PIEZO-

RING TYPE FLOW METER AND TRANSDUCER. THE TOTAL CFM FLOW THROUGH THE

ARRAY SHALL BE DISPLAYED ON THE FAN ARRAY CONTROLLER.

WHEN THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS ENERGIZED, THE

MOTORIZED DAMPER SHALL BE OPENED AND THE SUPPLY FAN ARRAY SHALL BE

ENERGIZED ONLY WHEN THE DAMPER END SWITCH CONFIRMS ITS OPEN

POSITION.

WHEN ONLY THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS ENERGIZED, THE

FAN ARRAY SHALL MODULATE ITS SPEED TO PROVIDE 30,000 CFM OF SUPPLY AIR

TO THE SPACE.

WHEN BOTH THE LEAD AND LAG FAN OF THE EF-C CONTROL SEQUENCE IS ACTIVE,

THE FAN ARRAY SHALL MODULATE ITS SPEED TO PROVIDE 60,000 CFM OF SUPPLY

AIR TO THE SPACE.

WHEN THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS DEACTIVATED, THE

SUPPLY FAN ARRAY SHALL BE DE-ENERGIZED AND THE MOTORIZED DAMPER

SHALL BE CLOSED.

WHEN THE PRESSURE DROP ACROSS THE FILTER BANK EXCEEDS THE CLEAN

FILTER PRESSURE DROP + 0.25 IN W.C. (ADJ.), THE DIRTY FILTER ALARM SHALL BE

ACTIVATED.

IF THE DUCT MOUNTED SMOKE DETECTOR DETECTS SMOKE, THE FAN ARRAY

SHALL BE SHUT DOWN.

IF A FAULT OCCURS AT THE VFD, AN ALARM SHALL BE SENT TO THE SCADA

SYSTEM.

SCADA SYSTEM CONNECTIONS:

• FROM SCADA - FAN ARRAY ENABLE/DISABLE

• FROM SCADA - FLOW SETPOINT

• FROM SCADA - MOTOR OPERATED DAMPER OPEN/CLOSE

• TO SCADA - FAN STATUS VIA VFD

• TO SCADA - MOTOR OPERATED DAMPER POSITION

• TO SCADA - VFD FAULT ALARM

• TO SCADA - DIRTY FILTER ALARM

MERV-8 FILTER BANK

ΔPM

SF

M

SF

M

SUPPLY AIR

5X3 SF ARRAY

TO SCADA

V F D

TO/FROM SCADA

TO SCADA

FROM SCADA

FAN

CONTROLLER

S

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF A DUCTLESS MINI-SPLIT HEAT PUMP SYSTEM AND

ASSOCIATED WALL MOUNTED THERMOSTAT/CONTROLLER.

SEQUENCE OF OPERATION:

THE SPLIT SYSTEM IS CONTROLLED BY A FACTORY ASSEMBLED

MICROPROCESSOR BASED CONTROL SYSTEM.

THE CONTROLLER SHALL ENABLE/DISABLE/MODULATE THE SYSTEM TO

MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT OF 75 DEG F (ADJ.)

AND HEATING SPACE TEMPERATURE SETPOINT OF 70 DEG F (ADJ.).

THE CONTROLLER SHALL BE CAPABLE OF AUTOMATIC CHANGEOVER AND 7-

DAY PROGRAMMABLE SCHEDULE. THE SYSTEM SHALL AUTOMATICALLY

RESTART FOLLOWING POWER FAILURE.

A SEPARATE TEMPERATURE SENSOR WILL ALARM TO SCADA IF THE ROOM

TEMPERATURE EXCEEDS THE COOLING SETPOINT + 10 DEG F.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - ROOM TEMPERATURE (4-20 MA)

TTEMP SENSOR

T

SPLIT SYSTEM

CONTROLLER

INDOOR UNIT

OUTDOOR UNIT

TO SCADA

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF A DUCTLESS MINI-SPLIT HEAT PUMP SYSTEM AND

ASSOCIATED WALL MOUNTED THERMOSTAT/CONTROLLER.

SEQUENCE OF OPERATION:

THE SPLIT SYSTEM IS CONTROLLED BY A FACTORY ASSEMBLED

MICROPROCESSOR BASED CONTROL SYSTEM.

THE CONTROLLER SHALL ENABLE/DISABLE/MODULATE THE SYSTEM TO

MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT OF 85 DEG F (ADJ.)

AND HEATING SPACE TEMPERATURE SETPOINT OF 60 DEG F (ADJ.).

THE CONTROLLER SHALL BE CAPABLE OF AUTOMATIC CHANGEOVER AND 7-

DAY PROGRAMMABLE SCHEDULE. THE SYSTEM SHALL AUTOMATICALLY

RESTART FOLLOWING POWER FAILURE.

SCADA SYSTEM CONNECTIONS:

• NONE

T

SPLIT SYSTEM

CONTROLLER

INDOOR UNIT

OUTDOOR UNIT

SYSTEM DESCRIPTION:

EMERGENCY FIXTURE FLOW SWITCH ALARM.

SEQUENCE OF OPERATION:

WHEN THE ASSOCIATED EMERGENCY SHOWER, EYEWASH, OR

SHOWER/EYEWASH COMBINATION UNIT IS ACTIVATED, A LOCAL AUDIBLE

AND VISUAL ALARM SHALL BE ACTIVATED AND THE ALARM SHALL BE SENT

TO THE SCADA SYSTEM. THE SYSTEM SHALL BE EQUIPPED WITH A BUTTON

TO SILENCE THE LOCAL ALARM.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - EMERGENCY FIXTURE USAGE ALARM

LOCAL AUDIBLE/

VISUAL ALARM F

WATER SUPPLY

TO

EMERGENCY

FIXTURE

TO SCADA

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT

DAMPER AND A HUMIDISTAT.

FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN

SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",

THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.

SEQUENCE OF OPERATION:

IF THE SPACE RELATIVE HUMIDITY RISES ABOVE 70% (ADJ.), THE EXHAUST

FAN SHALL BE ENERGIZED AND SHALL OPERATE IN A CONSTANT VOLUME

FASHION.

WHEN THE SPACE RELATIVE HUMIDITY FALLS BELOW 60% (AHJ.), THE

EXHAUST FAN SHALL BE DE-ENERGIZED.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER

REMOTE

HUMIDISTAT

H

CT TO SCADA

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF A PROPELLER TYPE EXHAUST FAN WITH GRAVITY

BACKDRAFT DAMPER, A MOTORIZED INTAKE DAMPER, AND A THERMOSTAT.

FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN

SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",

THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.

SEQUENCE OF OPERATION:

IF THE SPACE RELATIVE HUMIDITY RISES ABOVE 70% (ADJ.), THE EXHAUST

FAN SHALL BE ENERGIZED AND SHALL OPERATE IN A CONSTANT VOLUME

FASHION.

WHEN THE SPACE RELATIVE HUMIDITY FALLS BELOW 60% (AHJ.), THE

EXHAUST FAN SHALL BE DE-ENERGIZED.

WHENEVER THE EXHAUST FAN IS ENERGIZED, THE ASSOCIATED INTAKE

DAMPER SHALL BE OPENED. WHEN THE EXHAUST FAN IS DE-ENERGIZED,

THE INTAKE DAMPER SHALL BE CLOSED.

SCADA SYSTEM CONNECTIONS:

• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER

CT

REMOTE T'STAT

REF: FLOOR PLANS

T M

INTAKE

AIR

INTERLOCKED

INTAKE DAMPER

TO SCADA

GLOBAL REFERENCE POINTS:

PROVIDE GLOBAL OUTSIDE AIR TEMPERATURE, DEWPOINT, AIR PRESSURE,

AND RELATIVE HUMIDITY TRANSMITTERS.

OUTSIDE AIR PRESSURE SHALL BE INSTALLED ON ALL FOUR SIDES OF THE

BUILDING AND PIPED WITH EQUAL LENGTHS OF 1/4" TUBING TO A PIPE

MANIFOLD. PIPING BY TCC. LOCATIONS TO BE DETERMINED PER

MANUFACTURER'S RECOMMENDATIONS AND CONTRACTING OFFICER'S

APPROVAL. TCC SHALL PRIME AND PAINT THE DEVICE ENCLOSURE.

GLOBAL SENSORS SHALL CONTINUOUSLY UPDATE SCADA SYSTEM FOR USE

IN CONTROLLING MECHANICAL EQUIPMENT AS REQUIRED IN SEQUENCES OF

OPERATION.

SCADA SYSTEM CONNECTIONS:

• TO SCADA: GLOBAL OUTSIDE AIR TEMPERATURE

• TO SCADA: GLOBAL OUTSIDE AIR DEWPOINT

• TO SCADA: GLOBAL OUTSIDE AIR PRESSURE

• TO SCADA: GLOBAL OUTSIDE AIR RELATIVE HUMIDITY

TH P

TO SCADA

D

MOUNT TO NORTH

FACE OF BUILDING

SUNSHIELD

EF

M

EXHAUST

AIR

SYSTEM DESCRIPTION:

SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT

DAMPER.

SEQUENCE OF OPERATION:

FAN SHALL OPERATE CONTINUOUSLY 24/7.

SCADA SYSTEM CONNECTIONS:

• NONE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N

P S

G ra n d C a n y o n

S o u th

R im W

T P

/1

M

P

S R

W T

P .r v t

/2

/2

:5

:5

P M

M702

GRAND CANYON NATIONAL PARK

190083

MECHANICAL CONTROLS 2A. ORTON

D. SAUCEDO

04/22/2022

A. ORTON

14456600-

00-M702

1 EF-A: EXHAUST FAN CONTROL SEQUENCE

00-M702

2 EF-B: EXHAUST FAN CONTROL SEQUENCE

00-M702

3 EF-C: EXHAUST FAN CONTROL SEQUENCE

00-M702

DF-A: DRYER FAN CONTROL SEQUENCE6

00-M702

8 SF-A: SUPPLY FAN CONTROL SEQUENCE

00-M702

10 SS-A: SPLIT SYSTEM CONTROL SEQUENCE

00-M702

11 SS-B: SPLIT SYSTEM CONTROL SEQUENCE

00-M702

7 EMERGENCY FIXTURE CONTROL SEQUENCE

00-M702

4 EF-D: EXHAUST FAN CONTROL SEQUENCE

00-M702

5 EF-E: EXHAUST FAN CONTROL SEQUENCE

00-M702

9 GLOBAL SENSOR ARRAY

00-M702

12 EF-F: EXHAUST FAN CONTROL SEQUENCE

REV 1 DSC QA COMMENTS 6/20/22

GRADE

1,000 GAL

PROPANE TANK

1,000 GAL

PROPANE TANK

EQUIPMENT PAD BY

GC, SEE

STRUCTURAL

PRESSURE

GAUGE TYP.

UNION TYP.

TWO ABOVE GROUND, STEEL, 1000 GALLON PROPANE

TANKS PROVIDED BY UTILITY PROVIDER.

TANKS SHALL COMPLY W/ ASME CODE FOR PRESSURE

VESSELS, SECTION VIII, DIV.1 AND NFPA 58. RATED AT 250

PSIG TO 125°F. AND RATED FOR FULL VACUUM TO 14.7 PSI.

TANK COATING PER UTILITY PROVIDER REQUIREMENTS.

TANK PRESSURE

REGULATOR AND

SERVICE VALVE

(TYP.)

1" LP

CONFIRM FINAL SIZE

WITH UTILITY PROVIDER

NOTES:

1. EQUIPMENT AND INSTALLATION SHALL BE IN

ACCORDANCE WITH NFPA 58, ALL APPLICABLE LOCAL

CODES AND MFR'S RECOMMENDATIONS.

2. FINAL EQUIPMENT REQUIREMENTS SHALL BE

DETERMINED BY THE PROPANE UTILITY PROVIDER.

3. PIPE ROUTING IS DIAGRAMMATIC. UTILITY PROVIDER IS

RESPONSIBLE FOR FINAL PIPING ARRANGEMENT, PIPE

SIZES, SUPPORTS, ROUTING, VALVES, GAUGES, AND ALL

OTHER NECESSARY ELEMENTS.

4. PROVIDE EXCESS FLOW VALVES AT TANKS WHERE

REQUIRED.

BY UTILITY

BY PC

REFER TO GAS SERVICE

ENTRANCE DETAIL

SHEET 00-P502

UNDERGROUND HDPE PIPING.

REFER TO CIVIL PLANS FOR

EXACT ROUTING AND POINT OF

TERMINATION.

PROVIDE TANK SUPPORT LEGS TO EXTEND

BOTTOM OF TANKS TO 24" MIN ABOVE

SURROUNDING GRADE.

TRANSITION FITTING

HDPE TO STEEL

FLEXIBLE LP GAS

CONNECTOR (TYP.)

PROTECTIVE HOOD (TYP.)

PRESSURE RELIEF

VALVE (TYP.)

COATED STEEL PIPING

PRESSURE

RELIEF VALVE

NOTES:

1. FINISH AND GRIND ALL ROUGH EDGES, TYPICAL.

2. GALVANIZE ALL PIECES AFTER FABRICATION.

3. BOTTOM OF STEEL PLATE AT WALL TO BE MOUNTED AT +

48" ABOVE FINISHED FLOOR.

4. WHERE LOCATED NEAR HB-1. PROVIDE WITH 50 FT

RUBBER HOSE WITH STANDARD 3/4" THREADED

CONNECTIONS.

3" 3"5" 5"

2" 2"

10"

1'-4"

1/4" STEEL PLATE

FACE OF WALL

OR COLUMN

3/4" DIAMETER

BAR (TYP. OF 3)

3/4" DIA SS EXP ANCHORS

(3 PER RACK)

ELEVATION SECTION

TYPE F ALUMINUM QUICK

CONNECT FITTING

GLOBE VALVE

MODULAR FRAMING SYSTEM

SECURED TO WALL. SEE

SPECIFICATIONS. (TYP.)

RUBBER CUSHION (TYP.)

FACE OF WALL OR COLUMN

2-1/2" SUPPLY PIPING

DIELECTRIC UNION

NOTES:

1. INSTALL VALVE SUCH THAT CENTER OF VALVE OUTLET IS

AT +36" ABOVE FINISHED FLOOR.

2. PROVIDE REMOVEABLE QUICK CONNECT DUST CAP WITH

CHAIN.

3. FACE OUTLET OF VB-1 TOWARD ADJACENT HOSE RACK.

VB-1

WDV-1

DUST CAP

F R L

1/2" COMP

DRIP LEG WITH

NORMALLY CLOSED

DRAIN VALVE AND

THREADED HOSE

CONNECTION

FRL-1

NOTES:

P

12"

MIN

PIPE ANCHOR

BLEED-AIR

SHUTOFF VALVE

MOUNT AT

APPROX. 5 FT

AFF

HR-1

1. REFER TO SHEET 00-P600 SERIES FOR PLUMBING MATERIAL LIST, HR-1, AND FRL-1

REQUIREMENTS.

2. WHERE DROPS ARE SHOWN WITHOUT A HOSE REEL, TERMINATE COMPRESSED

AIR PIPING WITH A 3/8" QUICK DISCONNECT (TOTAL OF TWO), OR AS INDICATED.

3. MOUNT FRL-1 AT AN APPROXIMATE ELEVATION OF 48" AFF. COORDINATE FINAL

MOUNTING LOCATION AND ELEVATION OF FRL-1 AND HR-1 WITH INSTALLATION

CONDITIONS. IN GENERAL, INSTALL HR-1 HIGH WITH HOSE EXTENDED TO WITHIN

REACH WITH RUBBER STOPPER.

TEE OFF TOP

OF PIPE

3/4" COMP

P

PRESS.

GAUGE

(TYP.)

1/4" COMP DROP W/

3/8" QUICK DISC.

(TYP.)

1/2" COMP

LOWER LEVEL

7047.00

UPPER LEVEL

7057.00

JJJJJ

PROCESS

CONTAINMENT LEVEL

7044.00

4" CMV

2" DR

EMV-1

1-1/4"TW

1" HW

EEW-1

ES-1

FS-2

6" CMV

3" CW

FRP GRATING

3/4" CW

WHA-2

SST SUPPORT ROD

FASTEN TO WALL

WITH SST EXP

ANCHORS

NOTES:

1. DRAWING IS DIAGRAMMATIC. CONTRACTOR TO CONNECT AND INSTALL ALL COMPONENTS PER

EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS.

2. PROVIDE ALL NECESSARY UNIONS AND SHUT OFF VALVES FOR SERVICING AND REMOVAL OF EACH

PIECE OF EQUIPMENT.

REFER TO

FLOOR PLANS FOR

PIPE SIZES AND

CONTINUATION PACKAGED AIR

COMPRESSOR

AND DRYER

PRESSURE

GAUGE (TYP.)

FLEXIBLE

CONNECTOR

CONCRETE EQUIPMENT PAD FLOOR SINKVIBRATION

ISOLATORS (TYP.)

DRIP LEG

W/DRAIN

VALVE

AUTOMATIC AND

MANUAL DRAINS

VENTILATED

ACOUSTIC

ENCLOSURE

PRESSURE

GAUGES AND

CONTROLS

ISO VIEW

10" MIN.

45°

3"

PROTECTED

PIPE OR

CONDUIT

YELLOW AND BLACK

REFLECTIVE CAUTION TAPE

APPLIED TO TOP

PROTECTED PIPE OR

CONDUIT

3/16" THICK SST

FLOOR PLATE

1/2" SS EXPANSION

ANCHORS 8" O.C.

NOTES:

1. MAINTAIN MINIMUM REQUIRED SLOPE FOR

ALL PROTECTED DRAIN PIPES. SUPPORT AS

NECESSARY.

1"

ASCALE 1/4" = 1'-0"

SCALE OF FEET

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N

P S

G ra n d C a n y o n

S o u th

R im W

T P

/1

M

P

S R

W T

P .r v t

/1

/2

:0

:0

A M

P503 190083

PLUMBING STANDARD

DETAILS 3

A. ORTON

D. SAUCEDO

04/22/2022

S. GAETA

14456600-

NO SCALE00-P503

1 PROPANE TANKS DETAIL

NO SCALE00-P503

2 HOSE RACK DETAIL

NO SCALE00-P503

3 WDV-1 DETAIL

NO SCALE00-P503

COMPRESSED AIR DROP DETAIL4

SCALE A01-P102

A SECTION AT EMV-1, EEW-1 AND ES-1

NO SCALE00-P503

5 AIR COMPRESSOR PIPING DETAIL

NO SCALE00-P503

6 PROTECTIVE PIPE COVER DETAIL

06/13/2022

REV 1 DSC QA COMMENTS 06/13/22

LOWER LEVEL

7047.00

CCC C

STANDING SEAM METAL

ROOFING (MTL-1)

RIDGE CAP

LIGHT FIXTURE; SEE

ELECTRICAL

SPLITFACE CMU VENEER

113B113C113D113E113F112A102B102C 113A

4'-0" 5'-4" 26'-0"

8" X 6" RECTANGULAR PRE-FINISHED

STEEL GUTTER

3 3/4" X 4 3/4" PRE-FINISHED STEEL

DOWNPOUT W/ SPLASHBLOCK

SNOW FENCE

8" X 6" RECTANGULAR PRE-FINISHED

STEEL GUTTER

8" X 6" RECTANGULAR PRE-FINISHED

STEEL GUTTER

GUTTER SHALL RUN BEHIND CORTEN

SCREEN INTO FRENCH DRAIN BELOW

BACK SLOPE SOUTH

PORTION OF GUTTER

INTO CONDUCTOR HEAD

PERFORATED CORTEN

SCREEN

BOLLARD; SEE CIVIL

CORTEN CORRUGATED

WALL PANEL (MTL-3)

CHEMICAL FILL STATIONS;

SEE PROCESS

C.J. C.J. C.J.C.J.

C.J.

8'-8" 20'-0" 16'-8" 4'-0"25'-4"26'-8"

C.J.C.J.C.J.C.J.C.J.CMU

C.J.

29'-8 1/4"25'-4"16'-0"

01-L-12

01-L-11

01-L-10

01-EF-2 01-EF-1

30'-8"

4" X 6" PRE-FINISHED STEEL

DOWNSPOUT (MTL-1)

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

PREFINISHED METAL FASCIA

(MTL-1)

SNOW FENCE

STANDING SEAM METAL

ROOFING (MTL-1)

VENT; SEE MECHANICAL

SNOW FENCE

STACKED STONE VENEER

(STN-1)

LOWER LEVEL

7047.00

A A A A

3"

1'-0"

3"

1'-0"

3"

1'-0" 3"

1'-0"

PERFORATED CORTEN SCREEN

(MTL-2)

CORTEN CORRUGATED

WALL PANEL (MTL-3)

STACKED STONE VENEER

(STN-1)

LIGHT FIXTURE; SEE

ELECTRICAL

SPLITFACE CMU VENEER

TURN DOWN STACKED FASCIA

BOARDS ALONG EDGE OF WALL.

PROVIDE RAKE END TRANSITION

OF STANDING SEAM ROOFING

VENEER CONTROL JOINT

C.J.

C.J.C.J.

1'-4"

01-L-13

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

4" X 6" PRE-FINISHED STEEL

DOWNSPOUT (MTL-1)

PREFINISHED METAL FASCIA

(MTL-1)

STANDING SEAM METAL

ROOFING (MTL-1)

SNOW FENCE

PREFINISHED METAL WALL

PANELS (MTL-1)

STOREFRONT SYSTEM

E

ALUMINUM LOUVER

1'-4"

LOWER LEVEL

7047.00

6'-6"

1'-4"

41°

1'-2" 5'-11"

LOWER LEVEL

7047.00

A

01-A301

11'-6" 11'-6"

1'-7"

2'-8"

1/4" TH. CORTEN

PANEL

STEEL FRAMING

BEHIND; SEE

STRUCTURAL

BSCALE 1/4" = 1'-0"

SCALE OF FEET

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N P

S

G ra n d C a n y o n S o u th

R im

W T

P

/1

A

S

R W

T P

.r v t

/2

/2

:3

:3

A M

A201

GRAND CANYON NATIONAL PARK

190083

EXTERIOR ELEVATIONS 1S. HEANEY

R. McKINLEY

04/22/2022

S. KENNY

14456601-

SCALE A01-A201

2 EXTERIOR ELEVATION - EAST

SCALE A01-A201

1 EXTERIOR ELEVATION - SOUTH

SCALE B01-A201

3 CORTEN SCREEN WALL ENLARGED ELEVATION

SCALE B01-A201

4 CORTEN SCREEN WALL ENLARGED ELEVATION

3/32" = 1'-0" 8 0 8 2416

SCALE OF FEET

SCALE A

REV 1 DSC QA COMMENTS 6/20/22

/2

0/

LOWER LEVEL

7047.00

STANDING SEAM METAL

ROOFING (MTL-1)

DDD

113G 114A 107B A A

MECHANICAL EQUIPMENT;

SEE MECHANICAL MECHANICAL EQUIPMENT;

SEE MECHANICAL

SPLITFACE CMU VENEER

STANDING SEAM METAL

ROOFING (MTL-1)

115A 29'-4" 29'-4" 35'-3"29'-4"6 3/4"

W/ CONDUCTOR HEAD

ALIGNED WITH DOWNSPOUT

ABOVE

BOLLARD; SEE CIVIL

LOUVER

LIGHT FIXTURE; SEE

ELECTRICAL

4'-0"

20'-0"

4'-0"

17'-4"2'-8"

8"

6'-8" 10'-8" 2'-8"

C.J. C.J.C.J. C.J. C.J.C.J.

C.J.

C.J.

C.J.

C.J.

C.J.

C.J.

C.J.

C.J.

C.J.

4'-8" 16'-0" 8'-8" 29'-4" 29'-4" 29'-4" 24'-8"

C.J.

/2

01-L-04A

01-L-05

01-L-04B

01-L-04C

01-L-03

01-L-1401-L-06

01-L-01L-02

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

SNOW FENCE

4" X 6" PRE-FINISHED STEEL

DOWNSPOUT (MTL-1)

4" X 6" PRE-FINISHED STEEL

DOWNSPOUT (MTL-1)

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

CORTEN CORRUGATED

WALL PANEL (MTL-3)

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

STANDING SEAM METAL

ROOFING (MTL-1)

EQUIPMENT PAD; SEE

STUCTURAL

BOLLARD; SEE CIVIL

LOWER LEVEL

7047.00

SPLITFACE CMU VENEER

LIGHT FIXTURE; SEE

ELECTRICAL

3"

1'-0"

119D 119C 118C 118B 117D 117C

CORTEN CORRUGATED

WALL PANEL (MTL-3)

OVERHEAD COILING DOOR

3"

1'-0"

BOLLARD; SEE CIVIL

STANDING SEAM METAL

ROOFING (MTL-1)

116B

CENTER LOUVERS ON

O.H. DOOR, TYP.

C.J.

C.J. C.J.

C.J. C.J.

C.J. C.J.

4'-0"

2'-0"

01-L-07 01-L-08 01-L-09

SNOW FENCE

PREFINISHED METAL FASCIA

(MTL-1)

8" X 6" PRE-FINISHED STEEL

GUTTER (MTL-1)

4" X 6" PRE-FINISHED STEEL

DOWNSPOUT (MTL-1)

1'-4"

ALUMINUM LOUVER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N P

S

G ra n d C a n y o n S o u th

R im

W T

P

/1

A

S

R W

T P

.r v t

/2

/2

:3

:5

A M

A202

GRAND CANYON NATIONAL PARK

190083

EXTERIOR ELEVATIONS 2S. HEANEY

R. McKINLEY

04/22/2022

S. KENNY

14456601-

3/32" = 1'-0" 8 0 8 2416

SCALE OF FEET

SCALE A

01-A202

2 EXTERIOR ELEVATION - WEST

01-A202

1 EXTERIOR ELEVATION - NORTH

REV 1 DSC QA COMMENTS 6/20/22

/2

0/

IC

IC

IC

IC

IC

IC

IC

IC

IC

IC

IC

IC

MATCHLINE - SEE SHEET 01-01-E113 FOR CONTINUATION

2.7

MECHANICAL

MEZZANINE

1 2.3 2.8

5 6

G.4

1.2 4.8

K

J

H

01-EF-2

01-EF-1

LIT

LSH

LSL

LIT

LSH

LSL

LIT

LSH

LSL

LIT

LSH

LSL

01-IRH-601-IRH-5

2.7

01-MAU-3 01-MAU-4

01-MAU-2

01-MAU-1

01-MAU-6

01-EF-11

ASCALE 3/16" = 1'-0"

4 0 4 128

SCALE OF FEET

A

B

D

C

KEY PLAN

MATCHLINE

MATCHLINE

MATCHLINE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N P

S

G ra n d C a n y o n S o u th

R im

W T

P

/1

E

S

R W

T P

.r v t

/2

/2

:3

:3

A M

E112

GRAND CANYON NATIONAL PARK

190083

BASIN LEVEL

POWER PLAN AREA A

T. MOORE

P. DAVILA

04/22/2022

N. LYNCH

14456601-

01-E112

1 BASIN LEVEL POWER PLAN AREA A

AREA CLASSIFICATION TYPE:

CONTRACTOR SHALL PROVIDE AND INSTALL ALL APPLICABLE ELECTRICAL

COMPONENTS, DEVICES, EQUIPMENT, ETC. PER THE AREA

CLASSIFICATION TYPE LISTED FOR EACH ROOM TYPE INDICATED ON THIS

SHEET. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

ROOM TYPE: AREA CLASSIFICATION:

201 - MECH MEZZANINE INDOOR - WET/ CORROSIVE

REV 1 DSC QA COMMENTS 6/20/22 1

T D

-3 T

D -3

T D

-3

TD-3 TD-3

T D

-3 T

D -3

T D

-3

IC

IC

IC

MATCHLINE - SEE SHEET 01-01-E113 FOR CONTINUATION

2.7

1 2.8

D.4

D.2

C.8

C

D

E

01-FA-1

01-IRH-04

01-IRH-03

LI

LSH

LSL

I

01-IRH-10

01-IRH-11

01-IRH-12

01-MOD-6

2.7

01-MAU-5

01-EF-10

ASCALE 3/16" = 1'-0"

4 0 4 128

SCALE OF FEET

A

B

D

C

KEY PLAN

MATCHLINE

MATCHLINE

MATCHLINE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

B

IM

/1

N P

S

G ra n d C a n y o n S o u th

R im

W T

P

/1

E

S

R W

T P

.r v t

/2

/2

:3

:1

A M

E114

GRAND CANYON NATIONAL PARK

190083

BASIN LEVEL

POWER PLAN AREA C

T. MOORE

P. DAVILA

04/22/2022

N. LYNCH

14456601-

01-E114

1 BASIN LEVEL POWER PLAN AREA C

AREA CLASSIFICATION TYPE:

CONTRACTOR SHALL PROVIDE AND INSTALL ALL APPLICABLE ELECTRICAL

COMPONENTS, DEVICES, EQUIPMENT, ETC. PER THE AREA

CLASSIFICATION TYPE LISTED FOR EACH ROOM TYPE INDICATED ON THIS

SHEET. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

ROOM TYPE: AREA CLASSIFICATION:

201 - PRETREAT BASIN PLATFORM INDOOR - WET/ CORROSIVE

DESIGN KVA: 13.85 DESIGN AMPACITY: 17 AMPS

PHASE B 2664 540 428 0 348 3980 4174 15

PHASE C 2664 0 0 0 0 2664 2664 10

TOTAL 7992 1080 673 0 936 10681 11083

PANEL DEMAND KVA: 11.08 PANEL DEMAND AMPACITY: 13 AMPS

RESERVE KVA: 2.77 RESERVE AMPACITY: 3 AMPS

PANEL 'SR-PP-1'

LOCATION: BRINE TANK VALVE VAULT VOLTAGE: 277/480 V KAIC: 42 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 4X STYLE: PER SPECS BUSSING: 225 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL

BRKR MTG: BOLT-ON MCB: 225 A ACCESSORIES: GROUND BUS, 42 SPACE

(3) #15 - #15 3/4"

15/3 FV-7237

37 333 X 38

SPARE 15/30 39 333 X 40

0 41 333 X 42

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 2664 540 245 0 588 4037 4245 15

0 27 333 X 28

0 29 333 X 30

(3) #14 - #14 3/4"

15/3 FV-7236

31 333 X 32

SPARE 15/30 33 333 X 34

0 35 333 X 36

WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING

PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT

(3) #12 - #12 3/4"

15/3 FV-7231

1 333 X 1,581 2

MINI-POWER ZONE 'SR-MPZ-3' 30/2

SEE 'SR-SWBD-1' ONE-LINE

0 3 333 X 1,510 4 7

0 5 333 X 6 SPARE 20/1

0 17 333 X 18

(3) #12 - #12 3/4"

15/3 FV-7234

19 333 X 20

SPARE 15/30 21 333 X 22

0 23 333 X 24

(3) #13 - #13 3/4"

15/3 FV-7235

25 333 X 26

SPARE 15/3

(3) #12 - #12 3/4"

15/3 FV-7232

7 333 X 333 8

FV-7238 15/3

(3) #12 - #12 3/4"0 9 333 X 333 10 0

0 11 333 X 333 12 0

(3) #12 - #12 3/4"

15/3 FV-7233

13 333 X 14

SPARE 15/30 15 333 X 16

DESIGN KVA: 59.77 DESIGN AMPACITY: 166 AMPS

PANEL 'SR-LP-1'

LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120 V KAIC: 42 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL

BRKR MTG: BOLT-ON MCB: 250 A ACCESSORIES: GROUND BUS, 84 SPACE

WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING

PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT

#12 #12 #12 3/4" 0 20/1 LIGHTING CONTACTOR 'LCP-SR-LP1' 1 500 X 2 SPARE 20/1

20/1 SPARE 83 X 84 SPARE 20/1

NOTE:

1) PROVIDE AS A SINGLE SECTION

PANELBOARD WITH A MAXIMUM 20"

WIDTH.

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 6150 0 4075 2987 2044 15256 16786 140

PHASE B 3950 0 4637 4425 2632 15644 17461 146

PHASE C 5206 0 3868 2254 1020 12348 13570 113

TOTAL 15306 0 12580 9666 5696 43248 47817

PANEL DEMAND KVA: 47.82 PANEL DEMAND AMPACITY: 133 AMPS

RESERVE KVA: 11.95 RESERVE AMPACITY: 33 AMPS

20/1 SPARE 67 X 68 SPARE 20/1

20/1 SPARE 69 X 70 SPARE 20/1

20/1 SPARE 71 X 72 SPARE 20/1

20/1 SPARE 73 X 74 SPARE 20/1

20/1 SPARE 75 X 76 SPARE 20/1

20/1 SPARE 77 X 78 SPARE 20/1

20/1 SPARE 79 X 80 SPARE 20/1

20/1 SPARE 81 X 82 SPARE 20/1

#12 #12 #12 3/4" 0 20/1 PMP-2721 51 1,200 X 52 NF MAIN CONTROL PANEL 20/1

#12 #12 #12 3/4" 0 20/1 PMP-6221 53 1,200 X 54 01-EF-10 20/1

20/1 WATER PLANT RIO 55 X 56 01-EF-11 20/1

20/1 WATER PLANT RIO 57 X 58 SPARE 20/1

20/1 SPARE 59 X 60 SPARE 20/1

20/1 SPARE 61 X 62 SPARE 20/1

20/1 SPARE 63 X 64 SPARE 20/1

20/1 SPARE 65 X 66 SPARE 20/1

#12 #12 #12 3/4" 0 20/1 LCP-8101 3 250 X 319 4 EXTERIOR EGRESS LUMINAIRES 20/1 2 #10 #10 #10 3/4"

#12 #12 #12 3/4" 0 20/1 LCP-8201 5 250 X 511 6 EXTERIOR BLDG LUMINAIRES 20/1 2 #10 #10 #10 3/4"

#12 #12 #12 3/4" 0 20/1 LCP-8301 7 250 X 1,351 8 RM 113,116,119,120,121 LUMINAIRES 20/1 2 #6 #6 #10 1"

#6 #6 #10 1" 2 20/1 RM 201 LUMINAIRES 9 940 X 1,297 10 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"

#6 #6 #10 1" 2 20/1 RM 201 LUMINAIRES 11 998 X 1,474 12 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"

#8 #8 #10 1" 2 20/1 RM 102,103, 112 LUMINAIRES 13 1,548 X 1,176 14 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"

#10 #10 #10 3/4" 2 20/1 RM 100,101,110,111 LUMINAIRES 15 883 X 1,198 16 RM 113 LUMINAIRES 20/1 2 #8 #8 #10 1"

#10 #10 #10 3/4" 2 20/1 RM 105,106,107,108,109 LUMINAIRES 17 885 X 600 18 01-EWC-1 20/1 0 SEE EQUIP. CONNECTION SCHEDULE

4 35 1,654 X 480 36 01-IRH-1, 2, 3, 4, 5, 6 20/1 4 SEE EQUIP. CONNECTION SCHEDULE

SEE EQUIP. CONNECTION SCHEDULE

35/2 01-EUH-2

37 2,507 X 480 38 01-IRH-7, 8, 9, 10, 11, 12 20/1 4 SEE EQUIP. CONNECTION SCHEDULE

4 39 2,507 X 264 40 01-GFUH-1 20/1 4 SEE EQUIP. CONNECTION SCHEDULE

SEE EQUIP. CONNECTION SCHEDULE 4 20/1 01-GWH-1 41 120 X 432 42 01-CF-1 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

#12 #12 #12 3/4" 0 20/1 UF SKID 1 MASTER CONTROL PANEL 43 500 X 1,456 44

ENTRANCE GATE MOTOR 'GMO-1' (1 HP) 20/2

(2) #6 - #10 2"

#12 #12 #12 3/4" 0 20/1 UF SKID 2 RIO CONTROL PANEL 45 500 X 1,456 46 6

#12 #12 #12 3/4" 0 20/1 UF SKID 3 RIO CONTROL PANEL 47 500 X 48 SR WATER PLANT PLC 20/1

#12 #12 #12 3/4" 0 20/1 PMP-2121 49 1,200 X 50 SR WATER PLANT PLC 20/1

#12 #12 #12 3/4" 0 20/1 RM 106 REFRIGERATOR 19 840 X 1,000 20 RM 106 ABOVE COUNTER MICROWAVE 20/1 0 #12 #12 #12 3/4"

#12 #12 #12 3/4" 0 20/1 RM 106 ABOVE COUNTER MICROWAVE 21 1,000 X 1,000 22 RM 106 ABOVE COUNTER MICROWAVE 20/1 0 #12 #12 #12 3/4"

#12 #12 #12 3/4" 0 20/1 RM 106 UNDERCOUNTER MICROWAVE 23 1,000 X 1,656 24 RM 106 3/4 HP GARBAGE DISPOSAL 20/1 0 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-MOD-1, 2, 3, 4, 5, 6, 7, 8 25 540 X 1,200 26 RM 106 UNDERCOUNTER DISH WASHER 20/1 0 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE

25/2 01-SS-1 & 01-SSCU-1

27 2,059 X 588 28 01-EF-3 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

3 29 2,059 X 588 30 01-EF-4 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-GDH-1 31 120 X 588 32 01-EF-5 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

SEE EQUIP. CONNECTION SCHEDULE

20/2 01-EUH-1

33 1,654 X 588 34 01-EF-6 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

1,920

1,920

#12 #12 #12 3/4" 0

#12 #12 #12 3/4" 0

1,920

1,920

0 #12 #12 #12 3/4"

0 #12 #12 #12 3/4"

500 0 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE

SEE EQUIP. CONNECTION SCHEDULE

DESIGN KVA: 46.47 DESIGN AMPACITY: 129 AMPS

20/1 SPARE 83 X 84 SPARE 20/1

NOTE:

1) PROVIDE AS A SINGLE SECTION

PANELBOARD WITH A MAXIMUM 20"

WIDTH.

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 3732 5580 0 3408 1278 13998 13093 109

PHASE B 2512 7200 0 4057 682 14451 13042 109

PHASE C 2110 5040 0 4057 750 11957 11039 92

TOTAL 8354 17820 0 11522 2710 40406 37174

PANEL DEMAND KVA: 37.17 PANEL DEMAND AMPACITY: 103 AMPS

RESERVE KVA: 9.29 RESERVE AMPACITY: 26 AMPS

PANEL 'SR-LP-2'

LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120 V KAIC: 42 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL

BRKR MTG: BOLT-ON MCB: 250 A ACCESSORIES: GROUND BUS, 84 SPACE

WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING

PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT

#10 #10 #10 3/4" 1 20/1 EXTERIOR GFCI RECEPTACLES 1 900 X 720 2 EXTERIOR GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"

20/1 SPARE 67 X 68 SPARE 20/1

20/1 SPARE 69 X 70 SPARE 20/1

20/1 SPARE 71 X 72 SPARE 20/1

20/1 SPARE 73 X 74 SPARE 20/1

20/1 SPARE 75 X 76 SPARE 20/1

20/1 SPARE 77 X 78 SPARE 20/1

20/1 SPARE 79 X 80 SPARE 20/1

20/1 SPARE 81 X 82 SPARE 20/1

4 51 1,654 X 900 52 RM 111 RACEWAY RECEPTACLES 20/1 1 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE

20/2 01-EUH-4

53 1,654 X 500 54 VENTILATION HORNS AND STROBES 20/1 0 #12 #12 #12 3/4"

4 55 1,654 X 360 56 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"

20/1 SPARE 57 X 58 SPARE 20/1

20/1 SPARE 59 X 60 SPARE 20/1

20/1 SPARE 61 X 62 SPARE 20/1

20/1 SPARE 63 X 64 SPARE 20/1

20/1 SPARE 65 X 66 SPARE 20/1

#12 #12 #12 3/4" 1 20/1 RM 106 RECEPTACLES 19 540 X 540 20 RM 106 RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 1 20/1 RM 111 RECEPTACLES 21 720 X 360 22 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"

#12 #12 #12 3/4" 0 20/1 RM 111 PRINTER 23 1,000 X 360 24 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"

W/ PULLSTRING 3/4" 0 20/1 FUTURE DOOR ACCESS CONTROLS 25 1,000 X 26 SPARE 20/1

#12 #12 #12 3/4" 1 20/1 RM 111 RACEWAY RECEPTACLES 27 900 X 900 28 RM 111 RACEWAY RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 0 20/1 RM 112 CHEM FEED PUMP 29 250 X 250 30 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"

#12 #12 #12 3/4" 0 20/1 FACU 31 500 X 250 32 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-EMV-1s 33 280 X 250 34 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"

#10 #10 #10 3/4" 1 20/1 RM 116 GFCI RECEPTACLES 3 720 X 1,080 4 RM 113,119,120,121 GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"

#10 #10 #10 3/4" 1 20/1 RM 113 GFCI RECEPTACLES 5 1,080 X 900 6 RM 113, 119, 120, 121 GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"

#10 #10 #10 3/4" 1 20/1 RM 113 GFCI RECEPTACLES 7 1,080 X 720 8 RM 114, 115 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 1 20/1 RM 103,112 GFCI RECEPTACLES 9 720 X 720 10 RM 101 RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 1 20/1 RM 102 GFCI RECEPTACLES 11 720 X 720 12 RM 102 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 1 20/1 RM 106,111 RECEPTACLES 13 1,080 X 1,872 14

SCADA/IT RACK 'SR-WTP-NW-RACK' 30/2

(2) #10 - #10 3/4"

#12 #12 #12 3/4" 1 20/1 RM 110 RECEPTACLES 15 540 X 1,872 16 0

#12 #12 #12 3/4" 1 20/1 RM 111 RACEWAY RECEPTACLES 17 900 X 720 18 RM 107,108,109 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"

#12 #12 #12 3/4" 5 20/1 RM 112 CHEM FEED PUMP 35 250 X 250 36 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"

#12 #12 #12 3/4" 5 20/1 RM 112 CHEM FEED PUMP 37 250 X 250 38 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"

SEE EQUIP. CONNECTION SCHEDULE

25/2 01-SS-2 & 01-SSCU-2

39 2,059 X 432 40 01-EF-7 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

3 41 2,059 X 42 SPARE 20/1

SEE EQUIP. CONNECTION SCHEDULE

25/3 01-EF-8

43 1,589 X 528 44 01-CP-1 20/1 5 SEE EQUIP. CONNECTION SCHEDULE

3 45 1,589 X 2,403 46

01-EWH-1 20/2

SEE EQUIP. CONNECTION SCHEDULE

3 47 1,589 X 2,403 48 4

SEE EQUIP. CONNECTION SCHEDULE

20/2 01-EUH-3

49 1,654 X 100 50 01-ESEW-2 HEAT TRACE 20/1 4 SEE EQUIP. CONNECTION SCHEDULE

DESIGN KVA: 118.32 DESIGN AMPACITY: 142 AMPS

3 83 2,938 X 84

NOTE:

1) PROVIDE AS A SINGLE SECTION

PANELBOARD WITH A MAXIMUM 20"

WIDTH.

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 7997 0 0 23554 0 31551 31551 114

PHASE B 7997 0 0 23554 0 31551 31551 114

PHASE C 7997 0 0 23554 0 31551 31551 114

TOTAL 23991 0 0 70662 0 94653 94653

PANEL DEMAND KVA: 94.65 PANEL DEMAND AMPACITY: 114 AMPS

RESERVE KVA: 23.66 RESERVE AMPACITY: 28 AMPS

PANEL 'SR-PP-2'

LOCATION: ELECTRICAL ROOM VOLTAGE: 480 V KAIC: 42 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 3W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 225 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL

BRKR MTG: BOLT-ON MCB: 225 A ACCESSORIES: GROUND BUS, 84 SPACE

WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING

PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT

(3) #12 - #12 3/4"

This is the start of the file's text. The full file is on GovTribe.