This document provides details on a federal solicitation opportunity and related technical file. The solicitation number is 140P2022R0100 for a project titled "GRCA 190083 - Improve Potable Water Supply to Inne." The opportunity type is a solicitation from the Department of the Interior National Park Service National Office to replace the Transcanyon Waterline and improve potable water systems at Grand Canyon National Park. The technical file is a set of revised drawings dated July 5, 2022 but does not include the content of the drawings. The solicitation seeks to address needed upgrades to the park's water infrastructure through replacement and improvement projects.
View the file
Other files
Show 40 more
Latest 50 of 93 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 REV 1 ADEQ COMMENTS 05/22/22
R
R = DUCT WIDTH
SLOPE 4" IN 12"
FULL RADIUS ELBOWSQUARE THROAT ELBOW
RECTANGULAR BRANCH TAKE-OFF RECTANGULAR TEE
NOTE: SEE "BRANCH TAKEOFF & DAMPER" DETAIL, ALSO
SQUARE THROAT ELBOW
MAY BE USED TO CONSERVE
SPACE
NOTE:
INSTALL MANUAL VOLUME DAMPERS
IN ALL LOW PRESSURE SUPPLY, RETURN AND EXHAUST DUCT
BRANCHES.
SQUARE THROAT
ELBOW MAY BE
USED TO
CONSERVE
SPACE
2"
ABOVE GROUND WALL PENETRATION ONLY
PVC SCH40 PIPE
SLEEVE SIZE TO FIT
REFRIGERANT PIPE
EXTERIOR NON-RATED WALL
LIQUID REFRIGERANT PIPE W/
FLEXIBLE ELASTOMERIC
INSULATION
0.25" TYPICAL CLEARANCE
BETWEEN PIPE AND SLEEVE
PVC PIPE SLEEVE SIZE NOT TO EXCEED 6" SCH 40
WEATHERPROOF
SEALANT BETWEEN PIPE
SLEEVE AND WALL
FLEXIBLE WEATHERPROOF
FOAM FILL AROUND PIPE
REFRIGERANT SUCTION PIPE W/
FLEXIBLE ELASTOMERIC
INSULATION
SEE ARCHITECTURAL DRAWINGS
FOR WALL CONSTRUCTION
DETAILS, DIMENSIONS, AND OTHER
REQUIREMENTS.
MOTOR OPERATED OR BACKDRAFT
DAMPER IN DUCTED APPLICATION
SHALL BE FULL SIZE OF DUCT
UNLESS OTHERWISE INDICATED.
REFER TO PLANS FOR DUCT SIZE
AND ROUTING.
NOTES:
WALL
LOUVER SEE
SCHEDULE
FOR SIZE
MOTOR OPERATED
OR BACKDRAFT
DAMPER WHERE
INDICATED
CLIP ANGLE
FASTEN TO
LOUVER
PROVIDE SHEET
METAL DUCT
SEALANT,
BACKER ROD
AND SHIMS
INSECT SCREEN
1.
2.
3.
NOTE:
1. INSTALL CONCENTRIC VENT IN STRICT ACCORDANCE WITH
MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
MAINTAIN MINIMUM CLEARANCES AWAY FROM OTHER
STRUCTURES.
SEALANT STAINLESS STEEL DRAWBAND
1/4" MIN. CLEARANCE TO RAIN
COLLAR
WATERTIGHT SHEET METAL RAIN COLLAR
OVERLAPPING FLASHING COLLAR BY 3"
TO 4"
SHEET METAL FLASHING COLLAR
MINIMUM OF 8" ABOVE ROOFING
1/4" MINIMUM CLEARANCE BETWEEN
FLASHING COLLAR AND SUPPORT
MINIMUM 36" UNLESS MANUFACTURER
REQUIRED HEIGHT IS HIGHER.
FLUE BOOT
FASTENERS AS REQUIRED
COMPATIBLE SEALANT UNDER
BOOT PERIMETER
COMPATIBLE SEALANT UNDER
TOP OF BOOT
STAINLESS STEEL CLAMPING
RING
FAN SECTION
SPRING ISOLATOR (TYP.)
STRUCTURE
P-TRAP
CHILLED WATER COOLING COIL
PROVIDE A MOISTURE SWITCH IN
AUXILIARY DRAIN PAN TO
DE-ENERGIZE FAN AND COIL
UNIT UPON DETECTION OF
CONDENSATE
PRIMARY
CONDENSATE DRAIN
SECONDARY GALVANIZED
STEEL DRAIN PAN
SUSPENDED FROM UNIT
REFRIGERANT PIPING
RETURN OR
FLEXIBLE DUCT
CONNECTION (TYP.)
ACCESS DOOR
ACCESS DOOR
FILTER SECTION
OUTSIDE
(TYP.)
SUPPLY AIR DUCT
AIR DUCT
NOTES:
1. NOT ALL AIR HANDLING UNITS HAVE ALL COMPONENTS AS SHOWN.
REFER TO SCHEDULES FOR EXACT REQUIREMENTS.
FLEXIBLE CONNECTION
WATER TIGHT.
FASTENERS. CAULK
OPENING WITH METAL
TO STEEL FRAMED
SECURE WALL COLLAR
AUTOMATIC DAMPER
(REFER TO
STRUCTURAL DWG.)
STEEL FRAMED OPENING
EXTERIOR WALL
FAN WALL COLLAR
SIDE GUARD
MOTOR
WALL MTD FAN. SEE
SCHEDULES ON
PLANS
(REFER TO
ARCHITECTURAL DWG.)
AIR FLOW
WATER TIGHT.
FASTENERS. CAULK
OPENING WITH METAL
TO STEEL FRAMED
SECURE WALL COLLAR
AUTOMATIC DAMPER
(REFER TO
STRUCTURAL DWG.)
STEEL FRAMED OPENING
EXTERIOR WALL
FAN WALL COLLAR
SIDE GUARD
MOTOR
AIR FLOW
LOUVER SEE
SCHEDULE FOR SIZE
(REFER TO
ARCHITECTURAL DWG.)
WALL MTD FAN. SEE
SCHEDULES ON
PLANS
SPECIFIED FORFLANGED
1-1/2" MIN. TO 3"
MATERIAL TAUT.
6" NOMINAL WITH
MAX. INSTALLED.
DUCTWORK.
RIVET ON
4" CENTERS
DRAW BAND
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
ON FAN SIDE
CONNECTION
4" CENTERS
FLANGED
FLANGE
5/16"
1/2"
BOLT ON
ON FAN SIDE
CONNECTION
1"x1/8"
WASHER
1 1/2" MIN. TO 3" MAX.
INSTALLED 6" NOMINAL
WITH MATERIAL
1/2"
ON 12" CENTERS
1-1/2"
DUCTWORK.
SPECIFIED FOR
SHEET METAL AS
SHEET METAL SCREWS
DUCT
SHEET METAL AS
1-1/2"
SLIP
AS SPECIFIED
FLEXIBLE MATERIAL
1"X1/8" BAND IRON
BOLT ON 4" CENTERS
OF BOLT
POSITION
ALTERNATE
1" FLANGE
DUCT
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N
P S
G ra n d C a n y o n
S o u th
R im W
T P
/1
M
P
S R
W T
P .r v t
/1
/2
:0
:5
A M
M503
GRAND CANYON NATIONAL PARK
190083
MECHANICAL STANDARD
DETAILS 3
A. ORTON
D. SAUCEDO
04/22/2022
S. GAETA
14456600-
NO SCALE00-M503
TYPICAL LOW PRESSURE DUCT
CONNECTION2
NO SCALE00-M503
TYPICAL REFRIGERANT PIPE SLEEVE
THROUGH NON-RATED EXTERIOR WALL3
NO SCALE00-M503
4 DUCTED LOUVER IN WALL DETAIL
NO SCALE00-M503
5 CONCENTRIC FLUE DETAIL
NO SCALE00-M503
6 SUSPENDED AIR HANDLING UNIT DETAIL
NO SCALE00-M503
7 WALL MOUNTED PROP FAN DETAIL
NO SCALE00-M503
8 WALL MOUNTED PROP FAN W/ LOUVER DETAIL
NO SCALE00-M503
1 FLEXIBLE DUCT CONNECTION DETAIL
06/13/2022
REV 1 DSC QA COMMENTS 06/13/22
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N
P S
G ra n d C a n y o n
S o u th
R im W
T P
/1
M
P
S R
W T
P .r v t
/2
/2
:5
:5
P M
M602
GRAND CANYON NATIONAL PARK
190083
MECHANICAL SCHEDULES 2A. ORTON
D. SAUCEDO
04/22/2022
S. GAETA
14456600-
9. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.
8. PROVIDE WALL MOUNTING BRACKET FOR INDOOR UNIT.
7. PROVIDE WITH INTEGRAL CONDENSATE PUMP. CONDENSATE PUMP SHALL NOT REQUIRE A SEPARATE ELECTRICAL CONNECTION.
6. PROVIDE WIRED WALL MOUNTED DIGITAL CONTROLLER AND TEMPERATURE SENSOR.
5. SINGLE POINT POWER. INDOOR UNIT SERVED BY OUTDOOR UNIT.
4. NOMINAL CAPACITY BASED ON AHRI CONDITIONS.
3. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.
2. MINIMUM SENSIBLE COOLING CAPACITY REQUIRED AT PROJECT ELEVATION (2,570 FT) AND SCHEDULED AMBIENT TEMPERATURE.
1. MINIMUM SENSIBLE COOLING CAPACITY REQUIRED AT PROJECT ELEVATION (7,000 FT) AND SCHEDULED AMBIENT TEMPERATURE.
NOTES:
04-SS-1 / 04-SSCU-1 SCADA IT WALL MOUNT 17.5 9.3 18,100 31,400 22,400 750 50 115 35 150 19.8 20 208/1 MFR MFR SS-A DAIKIN FTX30 RX30 2,5-8
01-SS-2 / 01-SSCU-2 VESTIBULE WALL MOUNT 17.5 9.3 20,000 31,400 22,400 750 50 100 10 150 19.8 20 208/1 MFR MFR SS-B DAIKIN FTX30 RX30 1,5-8
01-SS-1 / 01-SSCU-1 SCADA IT WALL MOUNT 17.5 9.3 20,000 31,400 22,400 750 50 100 10 150 19.8 20 208/1 MFR MFR SS-A DAIKIN FTX30 RX30 1,5-8
(CFM) WT. (LBS)
SUMMER WINTER
WT. (LBS) PHASE BY
TAG SERVICE CONFIGURATION
SEER HSPF COOLING HEATING @ 17F
AIR FLOW UNIT
AMBIENT (DEG F)
UNIT
MCA (A) MOCP (A)
VOLTS/ DISCONNECT CONTROLLER/
STARTER BY
MFR
INDOOR
MODEL
OUTDOOR
MODEL
NOTES
MIN. EFFICIENCY
MIN. SENSIBLE
CLG. CAPACITY
(BTU/hr)
NOMINAL CAPACITY (BTU/hr) (NOTE 4) INDOOR UNIT OUTDOOR UNIT ELECTRICAL (NOTE 3)
CONTROL
TYPE
(NOTE 9)
BASIS OF DESIGN
DUCTLESS MINI-SPLIT HEAT PUMP SCHEDULE
14. PROVIDE WITH BELT TENSIONER AND BELT GUARD.
13. ALL ALUMINUM CONSTRUCTION. PROVIDE WITH FLEXIBLE CONNECTORS, ISOLATION RAILS, AND RUBBER-IN-SHEAR ISOLATORS.
12. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.
11. PROVIDE WITH AUTOMATIC BACKDRAFT DAMPER.
10. PROVIDE WITH MFR'S FLOW SWITCH, SECONDARY LINT TRAP, AND WALL TERMINATION LOUVER/BACKDRAFT DAMPER. UL705 CERTIFIED.
9. SCHEDULED ESP EXCLUDES HOUSING, SHUTTER, AND SCREEN DAMPER LOSSES.
8. HOUSED PROP FAN WITH DISCHARGE SHUTTER, ALUMINUM BIRD SCREEN, WIRE MOTOR GUARD. DISCHARGE SHUTTER FINISH TO BE ARCHITECTURAL BRONZE.
7. PROVIDE WITH VIBRATION ISOLATORS FOR UNIT MOUNTING AS RECOMMENDED BY THE FAN MANUFACTURER.
6. PROVIDE WITH MOTOR SIDE WIRE GUARD.
5. PROVIDE WITH EC MOTOR AND LOCAL FAN SPEED CONTROLLER.
4. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME PLATE RATING.
3. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.
2. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 2,570 FT.
1. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 7,000 FT.
NOTES:
04-DF-1 DRYER BOOSTER FAN INLINE 130 0.40 - - DIRECT - - 0.10 0.25 115/1 EC MFR/ECM DF-A DEDPV-705 FANTECH 25 2,7,10
04-EF-2 CHEMICAL STORAGE RM EXHAUST VENT SET 550 0.50 2,688 1,725 BELT TEFC PHENOLIC 0.36 0.50 115/1 MFR MFR/ECM EF-B CPA LOREN COOK 200 2,13,14
04-EF-1 GENERAL EXHAUST INLINE 150 0.50 1,457 1,725 DIRECT ODP-EC EPOXY PC 0.04 0.25 115/1 MFR MFR/ECM EF-A SQN-D LOREN COOK 100 2,5,7
01-EF-11 PROCESS AREA VENTILATION INLINE 450 0.50 1,454 1,725 DIRECT ODP-EC EPOXY PC 0.12 0.25 115/1 MFR MFR/ECM EF-F SQN-D LOREN COOK 100 1,5,7
01-EF-10 PROCESS AREA VENTILATION INLINE 450 0.50 1,454 1,725 DIRECT ODP-EC EPOXY PC 0.12 0.25 115/1 MFR MFR/ECM EF-F SQN-D LOREN COOK 100 1,5,7
01-EF-9 BRINE TANK VAULT VENTILATION PROP 300 0.35 1,305 1,725 DIRECT ODP-EC EPOXY PC 0.08 0.25 115/1 MFR MFR/ECM EF-E XWD-VF LOREN COOK 100 1,5,6
01-EF-8 BASIN VENTILATION INLINE 4,800 0.90 1,519 1,725 DIRECT TEFC-EC EPOXY PC 1.70 2.00 208/3 MFR MFR/ECM EF-D SQN-D LOREN COOK 225 1,5,7
01-EF-7 GENERAL EXHAUST INLINE 225 0.50 1,495 1,725 DIRECT ODP-EC EPOXY PC 0.05 0.33 115/1 MFR MFR/ECM EF-A SQN-D LOREN COOK 100 1,5,7,11
01-EF-6 CAUSTIC SODA ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14
01-EF-5 SODIUM HYPOCHLORITE ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14
01-EF-4 COAGULANT ROOM EXHAUST INLINE 1,100 0.50 2,379 3,450 BELT TEFC PHENOLIC 0.37 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 75 1,14
01-EF-3 CHEMICAL DRUM ROOM EXHAUST INLINE 1,700 0.50 1,530 1,725 BELT TEFC PHENOLIC 0.41 0.50 115/1 MFR EC/NOTE 3 EF-B SQN-B LOREN COOK 100 1,14
01-EF-2 PROCESS AREA VENTILATION PROP 30,000 0.15 706 1,725 BELT TEFC EPOXY PC 5.38 7.50 460/3 MFR EC/NOTE 3 EF-C EPB LOREN COOK 700 1,8,9,14
01-EF-1 PROCESS AREA VENTILATION PROP 30,000 0.15 706 1,725 BELT TEFC EPOXY PC 5.38 7.50 460/3 MFR EC/NOTE 3 EF-C EPB LOREN COOK 700 1,8,9,14
FAN MOTOR BHP (NOTE 4) MHP (NOTE 4) VOLTAGE/PHASE DISCONNECT BY CONTROLLER/STARTER BY/TYPE MODEL MANUFACTURER
SYMBOL SERVICE TYPE
AIRFLOW
(CFM)
ESP
(IN. WC.)
RPM
DRIVE
MOTOR
TYPE
COATING
ELECTRICAL CONTROL
TYPE
(NOTE 12)
BASIS OF DESIGN
WEIGHT
(LBS)
NOTES
FAN SCHEDULE
9. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.
8. PROVIDE BV-4 BALANCED FANS AND SHAFT GROUNDING RING.
7. PROVIDE WITH PIEZOELECTRIC FLOW METER FOR EACH FAN AND TOTALIZER WITH DIGITAL READOUT OF FAN ARRAY FLOW.
6. PROVIDE MANUFACTURER RECOMMENDED FLOOR SPRING ISOLATORS WITH 2" DEFLECTION TO SUPPORT ENTIRE ARRAY.
5. PROVIDE EACH FAN WITH AN INLET BACKDRAFT DAMPER AND INLET SCREEN.
4. EACH FAN IN THE ARRAY SHALL BE A MODULAR UNIT CAPABLE OF BEING REPLACED INDIVIDUALLY.
3. FAN SHALL NOT EXCEED 90% OF THE RATED MOTOR HORSEPOWER.
2. REFER TO ELECTRICAL FOR ADDITIONAL INFORMATION.
1. SCHEDULED PERFORMANCE REFLECTS AN ELEVATION OF 7,000 FT.
NOTES:
01-FA-1 PROCESS AREA VENTILATION PLENUM DIRECT 60,000 0.85 3H X 5W TEFC-PE 1.64 2 21.10 30 460/3 EC EC/VFD SF-A MPA LOREN COOK 5,600 4-8
BHP MHP BHP (NOTE 3) MHP (NOTE 3) VOLTAGE/PHASE DISCONNECT BY CONTROLLER BY/TYPE MODEL MANUFACTURER
SYMBOL SERVICE TYPE DRIVE
TOTAL
AIRFLOW
(CFM)
ESP
(IN. WC.)
ARRAY
CONFIG.
MOTOR
TYPE
EACH FAN TOTAL ARRAY ELECTRICAL (NOTE 2) CONTROL
TYPE
(NOTE 9)
BASIS OF DESIGN
WEIGHT
(LBS)
NOTES
FAN ARRAY SCHEDULE
1REV 1 DSC QA COMMENTS 6/20/22
06/20/2022
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N
P S
G ra n d C a n y o n
S o u th
R im W
T P
/1
M
P
S R
W T
P .r v t
/2
/2
:5
:5
P M
M603
GRAND CANYON NATIONAL PARK
190083
MECHANICAL SCHEDULES 3A. ORTON
D. SAUCEDO
04/22/2022
S. GAETA
14456600-
5. PROVIDE WITH INTEGRAL OPPOSED BLADE DAMPER WHERE DAMPER IS NOT SHOWN IN DUCTWORK.
4. PROVIDE FULL 22x22 CORE AREA. WHERE SHOWN DUCTED, PROVIDE TRANSITION TO INDICATED DUCT SIZE.
3. ALL SUPPLY DIFFUSERS SHALL HAVE 4-WAY THROW UNLESS OTHERWISE INDICATED ON PLANS.
2. AIR DEVICE SHALL HAVE A FULL SIZED CORE AREA AS SPECIFIED. PROVIDE TRANSITION TO SPECIFIED INLET SIZE AS REQUIRED.
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
NOTES:
EG-2 ALUMINUM 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 350FL 2,5
EG-1 ALUMINUM EGG CRATE LAY-IN 8X8 12X12 WHITE TITUS 50F 2
XG-1 316 STAINLESS HEAVY DUTY 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 MILL TITUS 33RL-SS 2
RG-2 ALUMINUM 35° DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 350FL 2,5
RG-1 ALUMINUM EGG CRATE LAY-IN 22x22 24x24 WHITE TITUS 50F 2,4
SG-1 ALUMINUM 3/4" SPC DBL DEFL. GRILLE VARIES SEE PLANS INLET + 2 WHITE TITUS 300FL 2,5
DL-1 ALUMINUM SPLIT DRUM LOUVER DUCT MOUNT 20X12 INLET + 1 MILL TITUS DL-SV 5
CD-2 ALUMINUM SQUARE PLAQUE VARIES SEE PLANS 12x12 WHITE TITUS OMNI-AA 3
CD-1 ALUMINUM SQUARE PLAQUE VARIES SEE PLANS 24x24 WHITE TITUS OMNI-AA 3
SYMBOL MATERIAL TYPE MARGIN (NOTE 1) INLET SIZE (IN) FACE SIZE (IN) FINISH MANUFACTURER MODEL NOTES
GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE
12. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
11. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAMEPLATE RATING.
10. PROVIDE WITH STAINLESS STEEL INSULATED CONDENSATE DRAIN PAN.
9. PROVIDE WITH LINE SET REGULATOR SUITABLE FOR 2 PSI SERVICE.
8. PROVIDE WITH INTEGRAL CONTROLS AND REMOTE MONITORING PANEL.
7. PROVIDE WITH MOTORIZED INLET DAMPER.
6. PROVIDE WITH ANGLED FILTER SECTION AND SIDE ACCESS FILTERS WITH HINGED ACCESS DOORS.
5. PROVIDE WITH INLET AND MANIFOLD GAS PRESSURE GAUGES.
4. DOUBLE WALL INSULATED CONSTRUCTION WITH TOP OR END DISCHARGE AS INDICATED ON PLANS.
3. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.
2. MINIMUM CAPACITY REQUIRED AT PROJECT ELEVATION OF 7,000 FT.
1. EXTERNAL STATIC PRESSURE INCLUDES SYSTEM LOSSES AND CLEAN/DIRTY FILTER LOSSES ONLY.
NOTES:
NOTES 4-9 4-10 4-9 4-9 4-10 4-9
BASIS OF DESIGN MODEL DG DGX DG DG DGX DG
BASIS OF DESIGN MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK GREENHECK GREENHECK
CONTROL TYPE (NOTE 3) MAU-A MAU-D MAU-A MAU-B MAU-D MAU-C
WEIGHT (LBS) 725 950 725 800 1,000 800
UNIT INFORMATION
CONTROLLER/STARTER BY/TYPE MFR/VFD MFR/VFD MFR/VFD MFR/VFD MFR/VFD MFR/VFD
DISCONNECT BY MFR MFR MFR MFR MFR MFR
MOCP 15 15 15 15 15 15
MCA 2.9 2.8 2.9 9.8 4 9.8
VOLTAGE/PHASE 460/3 460/3 460/3 460/3 460/3 460/3
ELECTRICAL (NOTE 11)
DIRTY FILTER ALLOWANCE A.P.D. (IN. WC) 0.25 0.25 0.25 0.25 0.25 0.25
MAX FACE VEL (FPM) 500 500 500 500 500 500
TYPE 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8 2" MERV 8
FILTERS
OUTPUT CAPACITY (MBH) (NOTE 2) 46,190 46,190 46,190 115,475 74,888 115,475
INPUT CAPACITY (MBH) 50,207 50,207 50,207 125,516 81,400 125,516
LEAVING AIR TEMPERATURE (DEG F) 65 65 65 65 65 65
ENTERING AIR TEMPERATURE (DEG F) 10 10 10 10 10 10
INLET PRESSURE (IN W.C.) 3-14 3-14 3-14 3-14 3-14 3-14
FUEL TYPE PROPANE PROPANE PROPANE PROPANE PROPANE PROPANE
DIRECT-FIRED GAS FURNACE
SENSIBLE CAPACITY (MBH) (NOTE 2) - 29,400 - - 47,040 -
TOTAL CAPACITY (MBH) (NOTE 2) - 29,400 - - 47,040 -
LEAVING AIR DB/WB (DEG F) - 60 / 45.4 - - 60 / 45.4 -
ENTERING AIR DB/WB (DEG F) - 95 / 58.2 - - 95 / 58.2 -
DIRECT EXPANSION COOLING COIL
MOTOR HP (NOTE 10) 1 1 1 5 1-1/2 5
BRAKE HP (NOTE 10) 0.61 0.62 0.61 1.43 0.86 1.43
BLOWER RPM 2,015 2,031 2,015 2,650 2,217 2,650
EXT. STATIC PRESSURE (IN. WC) (NOTE 1) 1.25 1.25 1.25 1.25 1.25 1.25
DRIVE / TYPE DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM DIRECT / PLENUM
SUPPLY AIRFLOW (CFM) 1,000 1,000 1,000 2,500 1,600 2,500
SUPPLY FAN
TYPE INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED INDOOR FLOOR MOUNTED
SERVICE COAGULANT ROOM SODIUM HYPOCHLORITE RM CAUSTIC SODA ROOM PROCESS AREA CHEMICAL DRUM ROOM PROCESS AREA
SYMBOL 01-MAU-1 01-MAU-2 01-MAU-3 01-MAU-4 01-MAU-5 01-MAU-6
MAKE-UP AIR UNIT SCHEDULE
5. PROVIDE WITH ADJUSTABLE COUNTERBALANCED BACKDRAFT DAMPER EQUIVALENT TO RUSKIN CBD4 FULL SIZE OF LOUVER.
4. PROVIDE WITH PVDF (KYNAR 500, HYLAR 5000 OR DURANAR) COATING.
3. PROVIDE WITH ALUMINUM INSECT SCREEN.
2. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION.
1. COLOR TO BE ARCHITECTURAL BRONZE. FINAL APPROVAL OF COLOR BY ARCHITECT.
NOTES:
04-L-07 04-AHU-3 RELIEF AIR STD 6,250 44X76 457 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4,5
04-L-06 04-AHU-3 OUTSIDE AIR INTAKE STD 6,890 44X76 504 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4
04-L-05 04-AHU-2 OUTSIDE AIR INTAKE STD 5,200 44X76 380 13.7 0.05 RUSKIN ELF6375DX 1,2,3,4
04-L-04 04-EF-2 EXHAUST AIR FLG 550 16X16 480 1.15 0.05 RUSKIN ELF6375DX 1,2,3,4,5
04-L-03 04-AHU-2 RELIEF AIR STD 5,200 80X24 778 6.69 0.08 RUSKIN ELF6375DX 1,2,3,4,5
04-L-02 04-EF-1 EXHAUST AIR FLG 150 16X16 206 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5
04-L-01 04-AHU-1 OUTSIDE AIR INTAKE FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4
01-L-18 01-EF-11 EXHAUST AIR FLG 450 16X16 616 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-17 01-EF-10 EXHAUST AIR FLG 450 16X16 616 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-16 01-EF-9 EXHAUST AIR FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-15 01-EF-9 OUTSIDE AIR INTAKE FLG 300 16X16 411 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4
01-L-14 01-EF-8 EXHAUST AIR FLG 4,800 64X48 392 12.2 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-13 01-AHU-4 OUTSIDE AIR INTAKE STD 205 16X16 280 0.73 0.05 RUSKIN ELF6375DX 1,2,3,4
01-L-12 01-EF-3 EXHAUST AIR FLG 1,700 32X24 661 2.57 0.06 RUSKIN ELF6375DX 1,2,3,4,5
01-L-11 PROCESS AREA RELIEF AIR FLG 3,200 54X48 312 10.3 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-10 PROCESS AREA RELIEF AIR FLG 2,500 36X30 630 3.97 0.06 RUSKIN ELF6375DX 1,2,3,4,5
01-L-09 01-EF-6 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-08 01-EF-5 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-07 01-EF-4 EXHAUST AIR STD 1,100 24X24 558 1.97 0.05 RUSKIN ELF6375DX 1,2,3,4,5
01-L-06 MAKE-UP AIR UNIT INTAKE FLG 8,000 64X48 653 12.2 0.07 RUSKIN ELF6375DX 1,2,3,4
01-L-05 01-MAU-5 OUTSIDE AIR INTAKE FLG 1,600 48X48 176 9.08 0.05 RUSKIN ELF6375DX 1,2,3,4
01-L-04C 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4
01-L-04B 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4
01-L-04A 01-FA-1 OUTSIDE AIR INTAKE STD 20,000 72X72 936 21.36 0.14 RUSKIN ELF6375DX 1,2,3,4
01-L-03 01-AHU-3 OUTSIDE AIR INTAKE STD 3,650 72X24 510 6.28 0.06 RUSKIN ELF6375DX 1,2,3,4
01-L-02 01-AHU-1 OUTSIDE AIR INTAKE STD 2,160 48X24 528 4.13 0.05 RUSKIN ELF6375DX 1,2,3,4
01-L-01
01-AHU-1 RELIEF AND
01-EF-07 EXHAUST
STD 2,385 48X24 577 4.13 0.05 RUSKIN ELF6375DX 1,2,3,4
(CFM) (IN) (FPM) AREA (SQ.FT.) LOSS (IN.W.G.)
MANUFACTURER MODEL
SYMBOL SERVICE
FRAME
TYPE
AIRFLOW SIZE WxH VELOCITY MIN. FREE MAX. PRESSURE
BASIS OF DESIGN
NOTES
LOUVER SCHEDULE
9. TWO STAGE SEPARATED COMBUSTION FURNACE.
8. PROVIDE WITH HIGH ALTITUDE KIT IF REQUIRED BY MANUFACTURER.
7. REFER TO 00-M700 SERIES FOR DESCRIPTION OF CONTROL TYPE.
6. PROVIDE WITH LINE PRESSURE REGULATOR SUITABLE FOR 2 PSI SERVICE AND COMPATIBLE WITH UNIT TURNDOWN REQUIREMENTS.
5. PROVIDE WITH FURNACE CONTROLLER AND MODULATING GAS VALVE WITH TURNDOWN TO 35%.
4. PROVIDE MANUFACTURER'S CONCENTRIC VENT TERMINATION KIT. REFER TO PLANS FOR CONFIGURATION.
3. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT AND FLEXIBLE GAS CONNECTOR.
2. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
1. SCHEDULED NOMINAL PERFORMANCE ACCOUNTS FOR THE PROJECT ELEVATION OF 7,000 FT.
NOTES:
01-GDH-1 01-AHU-1 0.5 2,180 57.4 100.6 100,000 80,000 115/1 MFR MFR AHU-C 175 MODINE DFS 3,4,5,6,8,9
AIR FLOW
(CFM)
E.A.T.
(DEG. F.)
L.A.T.
(DEG. F.)
INPUT
CAPACITY
(BTU/hr)
OUTPUT
CAPACITY
(BTU/hr)
VOLT/
PHASE
DISCONNECT
BY
CONTROLLER/
STARTER BY
MFR MODEL
SYMBOL SERVICE
MAX PRESSURE
DROP
(IN. W.C.)
PROPANE GAS FURNACE (NOTE 1) ELECTRICAL (NOTE 2)
CONTROL
TYPE
(NOTE 7)
WEIGHT
(LBS)
BASIS OF DESIGN
NOTES
GAS-FIRED DUCT HEATER SCHEDULE
1REV 1 DSC QA COMMENTS 6/20/22
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT
DAMPER.
FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN
SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",
THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.
SEQUENCE OF OPERATION:
WHEN IN OCCUPIED MODE, THE EXHAUST FAN SHALL OPERATE
CONTINUOUSLY AT A CONSTANT SPEED.
WHEN IN UNOCCUPIED MODE, THE EXHAUST FAN SHALL BE DE-ENERGIZED.
SCADA SYSTEM CONNECTIONS:
• FROM SCADA - OCCUPIED/UNOCCUPIED MODE
• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER
CT TO SCADA
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF AN INLINE OR UTILITY VENT SET EXHAUST FAN
SERVING A CHEMICAL STORAGE ROOM WITH GRAVITY BACKDRAFT DAMPER
AND ONE OR MORE HORN/STROBE ALARM DEVICES TO INDICATE INADEQUATE
FLOW.
SEQUENCE OF OPERATION:
THE EXHAUST FAN SHALL OPERATE CONTINUOUSLY AT A CONSTANT SPEED
24/7.
IF THE EMERGENCY ALARM PUSH-BUTTON IS ACTIVATED, THE EXHAUST FAN
AND ASSOCIATED MAKE-UP AHU SHALL BE SHUT DOWN.
IF THE FLOW SWITCH IS NOT ACTIVATED FOR AT LEAST 0.5 SECONDS (ADJ.),
INDICATING INADEQUATE FLOW, OR IF THE EMERGENCY ALARM IS ACTIVATED
MANUALLY, AN ALARM SHALL BE GENERATED AT THE SCADA SYSTEM
OPERATOR WORKSTATION, AND THE ASSOCIATED HORN/STROBE DEVICES
SHALL BE ACTIVATED. ALARM MUST BE RESET MANUALLY.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - VENTILATION ALARM ACTIVATED
TO SCADA
F
HORN/STROBE DEVICE(S)
REF: PLANS FOR QUANTITY
AND LOCATIONS.
SEE 28 42 00
EAC
PANEL
120V
EMERGENCY ALARM
PUSH-BUTTON.
REF: PLANS FOR
LOCATION.
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF TWO PROPELLER TYPE EXHAUST FANS OPERATING
IN A LEAD/LAG FASHION WITH GRAVITY BACKDRAFT DAMPERS. BACKDRAFT
DAMPERS SHALL BE EQUIPPED WITH SHUTTER SWITCH AND DRY CONTACT
FOR FAN STATUS.
THE SYSTEM SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND",
BOTH FANS SHALL OPERATE. WHEN IN "OFF" BOTH FANS SHALL BE OFF.
WHEN IN "AUTO", THE FANS SHALL OPERATE AS DESCRIBED IN THIS
SEQUENCE.
SEQUENCE OF OPERATION:
A STANDALONE LEAD/LAG CONTROLLER SHALL PROVIDE THE CONTROL
LOGIC TO STAGE AS DESCRIBED BELOW AND ALTERNATE LEAD/LAG
DESIGNATION BETWEEN FANS TO BALANCE OPERATING TIME.
THE LEAD EXHAUST FAN SHALL BE ENABLED AND SHALL OPERATE AT
CONSTANT SPEED WHENEVER THE SPACE TEMPERATURE EXCEEDS THE
PRIMARY SETPOINT OF 85 DEG F (ADJ.).
THE LAG EXHAUST FAN SHALL BE ENABLED AND SHALL OPERATE AT
CONSTANT SPEED IF THE SPACE TEMPERATURE CONTINUES TO RISE
ABOVE THE SECONDARY SETPOINT OF 95 DEG F (ADJ.).
THE LAG FAN SHALL BE DISABLED IF THE SPACE TEMPERATURE FALLS
BELOW 90 DEG F (ADJ.) FOR MORE THAN 30 MINUTES.
THE LEAD FAN SHALL BE DISABLED IF THE SPACE TEMPERATURE FALLS
BELOW 80 DEG F (ADJ.) FOR MORE THAN 30 MINUTES.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - FAN STATUS VIA SHUTTER FLOW SWITCH
EF
M
EXHAUST
AIR
F
T
SPACE TEMP. SENSOR
REF: FLOOR PLANS
LEAD/LAG
CONTROLLER
TO SCADA
F TO SCADA
DF
M
DRYER
EXHAUST
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF AN INLINE DRYER BOOSTER FAN AND ASSOCIATED
CONTROLS/FLOW SWITCH.
SEQUENCE OF OPERATION:
THE DRYER BOOSTER FAN SHALL BE ENABLED WHENEVER THE INTEGRAL
FLOW SWITCH DETECTS THAT THE CONNECTED DRYER IS OPERATING.
SCADA SYSTEM CONNECTIONS:
• NONE
F
SF
M
OUTSIDE
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF A DIRECT DRIVE PLENUM SUPPLY FAN ARRAY WITH MOTOR
OPERATED DAMPER AND MERV-8 FILTER BANK UPSTREAM.
FAN ARRAY SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN
ARRAY SHALL OPERATE AT A USER SELECTED SPEED VIA THE VFD. WHEN IN "OFF"
THE FAN ARRAY SHALL BE OFF. WHEN IN "AUTO", THE FAN ARRAY SHALL OPERATE
AS DESCRIBED IN THIS SEQUENCE.
SEQUENCE OF OPERATION:
THE FAN ARRAY CONTROLLER SHALL BE CAPABLE OF RECEIVING A FLOW
SETPOINT FROM THE SCADA SYSTEM AND CONTROLLING THE ARRAY'S VARIABLE
FREQUENCY DRIVE. EACH FAN IN THE ARRAY SHALL BE EQUIPPED WITH A PIEZO-
RING TYPE FLOW METER AND TRANSDUCER. THE TOTAL CFM FLOW THROUGH THE
ARRAY SHALL BE DISPLAYED ON THE FAN ARRAY CONTROLLER.
WHEN THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS ENERGIZED, THE
MOTORIZED DAMPER SHALL BE OPENED AND THE SUPPLY FAN ARRAY SHALL BE
ENERGIZED ONLY WHEN THE DAMPER END SWITCH CONFIRMS ITS OPEN
POSITION.
WHEN ONLY THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS ENERGIZED, THE
FAN ARRAY SHALL MODULATE ITS SPEED TO PROVIDE 30,000 CFM OF SUPPLY AIR
TO THE SPACE.
WHEN BOTH THE LEAD AND LAG FAN OF THE EF-C CONTROL SEQUENCE IS ACTIVE,
THE FAN ARRAY SHALL MODULATE ITS SPEED TO PROVIDE 60,000 CFM OF SUPPLY
AIR TO THE SPACE.
WHEN THE LEAD FAN OF THE EF-C CONTROL SEQUENCE IS DEACTIVATED, THE
SUPPLY FAN ARRAY SHALL BE DE-ENERGIZED AND THE MOTORIZED DAMPER
SHALL BE CLOSED.
WHEN THE PRESSURE DROP ACROSS THE FILTER BANK EXCEEDS THE CLEAN
FILTER PRESSURE DROP + 0.25 IN W.C. (ADJ.), THE DIRTY FILTER ALARM SHALL BE
ACTIVATED.
IF THE DUCT MOUNTED SMOKE DETECTOR DETECTS SMOKE, THE FAN ARRAY
SHALL BE SHUT DOWN.
IF A FAULT OCCURS AT THE VFD, AN ALARM SHALL BE SENT TO THE SCADA
SYSTEM.
SCADA SYSTEM CONNECTIONS:
• FROM SCADA - FAN ARRAY ENABLE/DISABLE
• FROM SCADA - FLOW SETPOINT
• FROM SCADA - MOTOR OPERATED DAMPER OPEN/CLOSE
• TO SCADA - FAN STATUS VIA VFD
• TO SCADA - MOTOR OPERATED DAMPER POSITION
• TO SCADA - VFD FAULT ALARM
• TO SCADA - DIRTY FILTER ALARM
MERV-8 FILTER BANK
ΔPM
SF
M
SF
M
SUPPLY AIR
5X3 SF ARRAY
TO SCADA
V F D
TO/FROM SCADA
TO SCADA
FROM SCADA
FAN
CONTROLLER
S
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF A DUCTLESS MINI-SPLIT HEAT PUMP SYSTEM AND
ASSOCIATED WALL MOUNTED THERMOSTAT/CONTROLLER.
SEQUENCE OF OPERATION:
THE SPLIT SYSTEM IS CONTROLLED BY A FACTORY ASSEMBLED
MICROPROCESSOR BASED CONTROL SYSTEM.
THE CONTROLLER SHALL ENABLE/DISABLE/MODULATE THE SYSTEM TO
MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT OF 75 DEG F (ADJ.)
AND HEATING SPACE TEMPERATURE SETPOINT OF 70 DEG F (ADJ.).
THE CONTROLLER SHALL BE CAPABLE OF AUTOMATIC CHANGEOVER AND 7-
DAY PROGRAMMABLE SCHEDULE. THE SYSTEM SHALL AUTOMATICALLY
RESTART FOLLOWING POWER FAILURE.
A SEPARATE TEMPERATURE SENSOR WILL ALARM TO SCADA IF THE ROOM
TEMPERATURE EXCEEDS THE COOLING SETPOINT + 10 DEG F.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - ROOM TEMPERATURE (4-20 MA)
TTEMP SENSOR
T
SPLIT SYSTEM
CONTROLLER
INDOOR UNIT
OUTDOOR UNIT
TO SCADA
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF A DUCTLESS MINI-SPLIT HEAT PUMP SYSTEM AND
ASSOCIATED WALL MOUNTED THERMOSTAT/CONTROLLER.
SEQUENCE OF OPERATION:
THE SPLIT SYSTEM IS CONTROLLED BY A FACTORY ASSEMBLED
MICROPROCESSOR BASED CONTROL SYSTEM.
THE CONTROLLER SHALL ENABLE/DISABLE/MODULATE THE SYSTEM TO
MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT OF 85 DEG F (ADJ.)
AND HEATING SPACE TEMPERATURE SETPOINT OF 60 DEG F (ADJ.).
THE CONTROLLER SHALL BE CAPABLE OF AUTOMATIC CHANGEOVER AND 7-
DAY PROGRAMMABLE SCHEDULE. THE SYSTEM SHALL AUTOMATICALLY
RESTART FOLLOWING POWER FAILURE.
SCADA SYSTEM CONNECTIONS:
• NONE
T
SPLIT SYSTEM
CONTROLLER
INDOOR UNIT
OUTDOOR UNIT
SYSTEM DESCRIPTION:
EMERGENCY FIXTURE FLOW SWITCH ALARM.
SEQUENCE OF OPERATION:
WHEN THE ASSOCIATED EMERGENCY SHOWER, EYEWASH, OR
SHOWER/EYEWASH COMBINATION UNIT IS ACTIVATED, A LOCAL AUDIBLE
AND VISUAL ALARM SHALL BE ACTIVATED AND THE ALARM SHALL BE SENT
TO THE SCADA SYSTEM. THE SYSTEM SHALL BE EQUIPPED WITH A BUTTON
TO SILENCE THE LOCAL ALARM.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - EMERGENCY FIXTURE USAGE ALARM
LOCAL AUDIBLE/
VISUAL ALARM F
WATER SUPPLY
TO
EMERGENCY
FIXTURE
TO SCADA
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT
DAMPER AND A HUMIDISTAT.
FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN
SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",
THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.
SEQUENCE OF OPERATION:
IF THE SPACE RELATIVE HUMIDITY RISES ABOVE 70% (ADJ.), THE EXHAUST
FAN SHALL BE ENERGIZED AND SHALL OPERATE IN A CONSTANT VOLUME
FASHION.
WHEN THE SPACE RELATIVE HUMIDITY FALLS BELOW 60% (AHJ.), THE
EXHAUST FAN SHALL BE DE-ENERGIZED.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER
REMOTE
HUMIDISTAT
H
CT TO SCADA
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF A PROPELLER TYPE EXHAUST FAN WITH GRAVITY
BACKDRAFT DAMPER, A MOTORIZED INTAKE DAMPER, AND A THERMOSTAT.
FAN SHALL BE EQUIPPED WITH A H-O-A SWITCH. WHEN IN "HAND", THE FAN
SHALL OPERATE. WHEN IN "OFF" THE FAN SHALL BE OFF. WHEN IN "AUTO",
THE FAN SHALL OPERATE AS DESCRIBED IN THIS SEQUENCE.
SEQUENCE OF OPERATION:
IF THE SPACE RELATIVE HUMIDITY RISES ABOVE 70% (ADJ.), THE EXHAUST
FAN SHALL BE ENERGIZED AND SHALL OPERATE IN A CONSTANT VOLUME
FASHION.
WHEN THE SPACE RELATIVE HUMIDITY FALLS BELOW 60% (AHJ.), THE
EXHAUST FAN SHALL BE DE-ENERGIZED.
WHENEVER THE EXHAUST FAN IS ENERGIZED, THE ASSOCIATED INTAKE
DAMPER SHALL BE OPENED. WHEN THE EXHAUST FAN IS DE-ENERGIZED,
THE INTAKE DAMPER SHALL BE CLOSED.
SCADA SYSTEM CONNECTIONS:
• TO SCADA - FAN STATUS VIA CURRENT TRANSMITTER
CT
REMOTE T'STAT
REF: FLOOR PLANS
T M
INTAKE
AIR
INTERLOCKED
INTAKE DAMPER
TO SCADA
GLOBAL REFERENCE POINTS:
PROVIDE GLOBAL OUTSIDE AIR TEMPERATURE, DEWPOINT, AIR PRESSURE,
AND RELATIVE HUMIDITY TRANSMITTERS.
OUTSIDE AIR PRESSURE SHALL BE INSTALLED ON ALL FOUR SIDES OF THE
BUILDING AND PIPED WITH EQUAL LENGTHS OF 1/4" TUBING TO A PIPE
MANIFOLD. PIPING BY TCC. LOCATIONS TO BE DETERMINED PER
MANUFACTURER'S RECOMMENDATIONS AND CONTRACTING OFFICER'S
APPROVAL. TCC SHALL PRIME AND PAINT THE DEVICE ENCLOSURE.
GLOBAL SENSORS SHALL CONTINUOUSLY UPDATE SCADA SYSTEM FOR USE
IN CONTROLLING MECHANICAL EQUIPMENT AS REQUIRED IN SEQUENCES OF
OPERATION.
SCADA SYSTEM CONNECTIONS:
• TO SCADA: GLOBAL OUTSIDE AIR TEMPERATURE
• TO SCADA: GLOBAL OUTSIDE AIR DEWPOINT
• TO SCADA: GLOBAL OUTSIDE AIR PRESSURE
• TO SCADA: GLOBAL OUTSIDE AIR RELATIVE HUMIDITY
TH P
TO SCADA
D
MOUNT TO NORTH
FACE OF BUILDING
SUNSHIELD
EF
M
EXHAUST
AIR
SYSTEM DESCRIPTION:
SYSTEM CONSISTS OF AN INLINE EXHAUST FAN WITH GRAVITY BACKDRAFT
DAMPER.
SEQUENCE OF OPERATION:
FAN SHALL OPERATE CONTINUOUSLY 24/7.
SCADA SYSTEM CONNECTIONS:
• NONE
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N
P S
G ra n d C a n y o n
S o u th
R im W
T P
/1
M
P
S R
W T
P .r v t
/2
/2
:5
:5
P M
M702
GRAND CANYON NATIONAL PARK
190083
MECHANICAL CONTROLS 2A. ORTON
D. SAUCEDO
04/22/2022
A. ORTON
14456600-
00-M702
1 EF-A: EXHAUST FAN CONTROL SEQUENCE
00-M702
2 EF-B: EXHAUST FAN CONTROL SEQUENCE
00-M702
3 EF-C: EXHAUST FAN CONTROL SEQUENCE
00-M702
DF-A: DRYER FAN CONTROL SEQUENCE6
00-M702
8 SF-A: SUPPLY FAN CONTROL SEQUENCE
00-M702
10 SS-A: SPLIT SYSTEM CONTROL SEQUENCE
00-M702
11 SS-B: SPLIT SYSTEM CONTROL SEQUENCE
00-M702
7 EMERGENCY FIXTURE CONTROL SEQUENCE
00-M702
4 EF-D: EXHAUST FAN CONTROL SEQUENCE
00-M702
5 EF-E: EXHAUST FAN CONTROL SEQUENCE
00-M702
9 GLOBAL SENSOR ARRAY
00-M702
12 EF-F: EXHAUST FAN CONTROL SEQUENCE
REV 1 DSC QA COMMENTS 6/20/22
GRADE
1,000 GAL
PROPANE TANK
1,000 GAL
PROPANE TANK
EQUIPMENT PAD BY
GC, SEE
STRUCTURAL
PRESSURE
GAUGE TYP.
UNION TYP.
TWO ABOVE GROUND, STEEL, 1000 GALLON PROPANE
TANKS PROVIDED BY UTILITY PROVIDER.
TANKS SHALL COMPLY W/ ASME CODE FOR PRESSURE
VESSELS, SECTION VIII, DIV.1 AND NFPA 58. RATED AT 250
PSIG TO 125°F. AND RATED FOR FULL VACUUM TO 14.7 PSI.
TANK COATING PER UTILITY PROVIDER REQUIREMENTS.
TANK PRESSURE
REGULATOR AND
SERVICE VALVE
(TYP.)
1" LP
CONFIRM FINAL SIZE
WITH UTILITY PROVIDER
NOTES:
1. EQUIPMENT AND INSTALLATION SHALL BE IN
ACCORDANCE WITH NFPA 58, ALL APPLICABLE LOCAL
CODES AND MFR'S RECOMMENDATIONS.
2. FINAL EQUIPMENT REQUIREMENTS SHALL BE
DETERMINED BY THE PROPANE UTILITY PROVIDER.
3. PIPE ROUTING IS DIAGRAMMATIC. UTILITY PROVIDER IS
RESPONSIBLE FOR FINAL PIPING ARRANGEMENT, PIPE
SIZES, SUPPORTS, ROUTING, VALVES, GAUGES, AND ALL
OTHER NECESSARY ELEMENTS.
4. PROVIDE EXCESS FLOW VALVES AT TANKS WHERE
REQUIRED.
BY UTILITY
BY PC
REFER TO GAS SERVICE
ENTRANCE DETAIL
SHEET 00-P502
UNDERGROUND HDPE PIPING.
REFER TO CIVIL PLANS FOR
EXACT ROUTING AND POINT OF
TERMINATION.
PROVIDE TANK SUPPORT LEGS TO EXTEND
BOTTOM OF TANKS TO 24" MIN ABOVE
SURROUNDING GRADE.
TRANSITION FITTING
HDPE TO STEEL
FLEXIBLE LP GAS
CONNECTOR (TYP.)
PROTECTIVE HOOD (TYP.)
PRESSURE RELIEF
VALVE (TYP.)
COATED STEEL PIPING
PRESSURE
RELIEF VALVE
NOTES:
1. FINISH AND GRIND ALL ROUGH EDGES, TYPICAL.
2. GALVANIZE ALL PIECES AFTER FABRICATION.
3. BOTTOM OF STEEL PLATE AT WALL TO BE MOUNTED AT +
48" ABOVE FINISHED FLOOR.
4. WHERE LOCATED NEAR HB-1. PROVIDE WITH 50 FT
RUBBER HOSE WITH STANDARD 3/4" THREADED
CONNECTIONS.
3" 3"5" 5"
2" 2"
10"
1'-4"
1/4" STEEL PLATE
FACE OF WALL
OR COLUMN
3/4" DIAMETER
BAR (TYP. OF 3)
3/4" DIA SS EXP ANCHORS
(3 PER RACK)
ELEVATION SECTION
TYPE F ALUMINUM QUICK
CONNECT FITTING
GLOBE VALVE
MODULAR FRAMING SYSTEM
SECURED TO WALL. SEE
SPECIFICATIONS. (TYP.)
RUBBER CUSHION (TYP.)
FACE OF WALL OR COLUMN
2-1/2" SUPPLY PIPING
DIELECTRIC UNION
NOTES:
1. INSTALL VALVE SUCH THAT CENTER OF VALVE OUTLET IS
AT +36" ABOVE FINISHED FLOOR.
2. PROVIDE REMOVEABLE QUICK CONNECT DUST CAP WITH
CHAIN.
3. FACE OUTLET OF VB-1 TOWARD ADJACENT HOSE RACK.
VB-1
WDV-1
DUST CAP
F R L
1/2" COMP
DRIP LEG WITH
NORMALLY CLOSED
DRAIN VALVE AND
THREADED HOSE
CONNECTION
FRL-1
NOTES:
P
12"
MIN
PIPE ANCHOR
BLEED-AIR
SHUTOFF VALVE
MOUNT AT
APPROX. 5 FT
AFF
HR-1
1. REFER TO SHEET 00-P600 SERIES FOR PLUMBING MATERIAL LIST, HR-1, AND FRL-1
REQUIREMENTS.
2. WHERE DROPS ARE SHOWN WITHOUT A HOSE REEL, TERMINATE COMPRESSED
AIR PIPING WITH A 3/8" QUICK DISCONNECT (TOTAL OF TWO), OR AS INDICATED.
3. MOUNT FRL-1 AT AN APPROXIMATE ELEVATION OF 48" AFF. COORDINATE FINAL
MOUNTING LOCATION AND ELEVATION OF FRL-1 AND HR-1 WITH INSTALLATION
CONDITIONS. IN GENERAL, INSTALL HR-1 HIGH WITH HOSE EXTENDED TO WITHIN
REACH WITH RUBBER STOPPER.
TEE OFF TOP
OF PIPE
3/4" COMP
P
PRESS.
GAUGE
(TYP.)
1/4" COMP DROP W/
3/8" QUICK DISC.
(TYP.)
1/2" COMP
LOWER LEVEL
7047.00
UPPER LEVEL
7057.00
JJJJJ
PROCESS
CONTAINMENT LEVEL
7044.00
4" CMV
2" DR
EMV-1
1-1/4"TW
1" HW
EEW-1
ES-1
FS-2
6" CMV
3" CW
FRP GRATING
3/4" CW
WHA-2
SST SUPPORT ROD
FASTEN TO WALL
WITH SST EXP
ANCHORS
NOTES:
1. DRAWING IS DIAGRAMMATIC. CONTRACTOR TO CONNECT AND INSTALL ALL COMPONENTS PER
EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. PROVIDE ALL NECESSARY UNIONS AND SHUT OFF VALVES FOR SERVICING AND REMOVAL OF EACH
PIECE OF EQUIPMENT.
REFER TO
FLOOR PLANS FOR
PIPE SIZES AND
CONTINUATION PACKAGED AIR
COMPRESSOR
AND DRYER
PRESSURE
GAUGE (TYP.)
FLEXIBLE
CONNECTOR
CONCRETE EQUIPMENT PAD FLOOR SINKVIBRATION
ISOLATORS (TYP.)
DRIP LEG
W/DRAIN
VALVE
AUTOMATIC AND
MANUAL DRAINS
VENTILATED
ACOUSTIC
ENCLOSURE
PRESSURE
GAUGES AND
CONTROLS
ISO VIEW
10" MIN.
45°
3"
PROTECTED
PIPE OR
CONDUIT
YELLOW AND BLACK
REFLECTIVE CAUTION TAPE
APPLIED TO TOP
PROTECTED PIPE OR
CONDUIT
3/16" THICK SST
FLOOR PLATE
1/2" SS EXPANSION
ANCHORS 8" O.C.
NOTES:
1. MAINTAIN MINIMUM REQUIRED SLOPE FOR
ALL PROTECTED DRAIN PIPES. SUPPORT AS
NECESSARY.
1"
ASCALE 1/4" = 1'-0"
SCALE OF FEET
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N
P S
G ra n d C a n y o n
S o u th
R im W
T P
/1
M
P
S R
W T
P .r v t
/1
/2
:0
:0
A M
P503 190083
PLUMBING STANDARD
DETAILS 3
A. ORTON
D. SAUCEDO
04/22/2022
S. GAETA
14456600-
NO SCALE00-P503
1 PROPANE TANKS DETAIL
NO SCALE00-P503
2 HOSE RACK DETAIL
NO SCALE00-P503
3 WDV-1 DETAIL
NO SCALE00-P503
COMPRESSED AIR DROP DETAIL4
SCALE A01-P102
A SECTION AT EMV-1, EEW-1 AND ES-1
NO SCALE00-P503
5 AIR COMPRESSOR PIPING DETAIL
NO SCALE00-P503
6 PROTECTIVE PIPE COVER DETAIL
06/13/2022
REV 1 DSC QA COMMENTS 06/13/22
LOWER LEVEL
7047.00
CCC C
STANDING SEAM METAL
ROOFING (MTL-1)
RIDGE CAP
LIGHT FIXTURE; SEE
ELECTRICAL
SPLITFACE CMU VENEER
113B113C113D113E113F112A102B102C 113A
4'-0" 5'-4" 26'-0"
8" X 6" RECTANGULAR PRE-FINISHED
STEEL GUTTER
3 3/4" X 4 3/4" PRE-FINISHED STEEL
DOWNPOUT W/ SPLASHBLOCK
SNOW FENCE
8" X 6" RECTANGULAR PRE-FINISHED
STEEL GUTTER
8" X 6" RECTANGULAR PRE-FINISHED
STEEL GUTTER
GUTTER SHALL RUN BEHIND CORTEN
SCREEN INTO FRENCH DRAIN BELOW
BACK SLOPE SOUTH
PORTION OF GUTTER
INTO CONDUCTOR HEAD
PERFORATED CORTEN
SCREEN
BOLLARD; SEE CIVIL
CORTEN CORRUGATED
WALL PANEL (MTL-3)
CHEMICAL FILL STATIONS;
SEE PROCESS
C.J. C.J. C.J.C.J.
C.J.
8'-8" 20'-0" 16'-8" 4'-0"25'-4"26'-8"
C.J.C.J.C.J.C.J.C.J.CMU
C.J.
29'-8 1/4"25'-4"16'-0"
01-L-12
01-L-11
01-L-10
01-EF-2 01-EF-1
30'-8"
4" X 6" PRE-FINISHED STEEL
DOWNSPOUT (MTL-1)
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
PREFINISHED METAL FASCIA
(MTL-1)
SNOW FENCE
STANDING SEAM METAL
ROOFING (MTL-1)
VENT; SEE MECHANICAL
SNOW FENCE
STACKED STONE VENEER
(STN-1)
LOWER LEVEL
7047.00
A A A A
3"
1'-0"
3"
1'-0"
3"
1'-0" 3"
1'-0"
PERFORATED CORTEN SCREEN
(MTL-2)
CORTEN CORRUGATED
WALL PANEL (MTL-3)
STACKED STONE VENEER
(STN-1)
LIGHT FIXTURE; SEE
ELECTRICAL
SPLITFACE CMU VENEER
TURN DOWN STACKED FASCIA
BOARDS ALONG EDGE OF WALL.
PROVIDE RAKE END TRANSITION
OF STANDING SEAM ROOFING
VENEER CONTROL JOINT
C.J.
C.J.C.J.
1'-4"
01-L-13
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
4" X 6" PRE-FINISHED STEEL
DOWNSPOUT (MTL-1)
PREFINISHED METAL FASCIA
(MTL-1)
STANDING SEAM METAL
ROOFING (MTL-1)
SNOW FENCE
PREFINISHED METAL WALL
PANELS (MTL-1)
STOREFRONT SYSTEM
E
ALUMINUM LOUVER
1'-4"
LOWER LEVEL
7047.00
6'-6"
1'-4"
41°
1'-2" 5'-11"
LOWER LEVEL
7047.00
A
01-A301
11'-6" 11'-6"
1'-7"
2'-8"
1/4" TH. CORTEN
PANEL
STEEL FRAMING
BEHIND; SEE
STRUCTURAL
BSCALE 1/4" = 1'-0"
SCALE OF FEET
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N P
S
G ra n d C a n y o n S o u th
R im
W T
P
/1
A
S
R W
T P
.r v t
/2
/2
:3
:3
A M
A201
GRAND CANYON NATIONAL PARK
190083
EXTERIOR ELEVATIONS 1S. HEANEY
R. McKINLEY
04/22/2022
S. KENNY
14456601-
SCALE A01-A201
2 EXTERIOR ELEVATION - EAST
SCALE A01-A201
1 EXTERIOR ELEVATION - SOUTH
SCALE B01-A201
3 CORTEN SCREEN WALL ENLARGED ELEVATION
SCALE B01-A201
4 CORTEN SCREEN WALL ENLARGED ELEVATION
3/32" = 1'-0" 8 0 8 2416
SCALE OF FEET
SCALE A
REV 1 DSC QA COMMENTS 6/20/22
/2
0/
LOWER LEVEL
7047.00
STANDING SEAM METAL
ROOFING (MTL-1)
DDD
113G 114A 107B A A
MECHANICAL EQUIPMENT;
SEE MECHANICAL MECHANICAL EQUIPMENT;
SEE MECHANICAL
SPLITFACE CMU VENEER
STANDING SEAM METAL
ROOFING (MTL-1)
115A 29'-4" 29'-4" 35'-3"29'-4"6 3/4"
W/ CONDUCTOR HEAD
ALIGNED WITH DOWNSPOUT
ABOVE
BOLLARD; SEE CIVIL
LOUVER
LIGHT FIXTURE; SEE
ELECTRICAL
4'-0"
20'-0"
4'-0"
17'-4"2'-8"
8"
6'-8" 10'-8" 2'-8"
C.J. C.J.C.J. C.J. C.J.C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
4'-8" 16'-0" 8'-8" 29'-4" 29'-4" 29'-4" 24'-8"
C.J.
/2
01-L-04A
01-L-05
01-L-04B
01-L-04C
01-L-03
01-L-1401-L-06
01-L-01L-02
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
SNOW FENCE
4" X 6" PRE-FINISHED STEEL
DOWNSPOUT (MTL-1)
4" X 6" PRE-FINISHED STEEL
DOWNSPOUT (MTL-1)
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
CORTEN CORRUGATED
WALL PANEL (MTL-3)
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
STANDING SEAM METAL
ROOFING (MTL-1)
EQUIPMENT PAD; SEE
STUCTURAL
BOLLARD; SEE CIVIL
LOWER LEVEL
7047.00
SPLITFACE CMU VENEER
LIGHT FIXTURE; SEE
ELECTRICAL
3"
1'-0"
119D 119C 118C 118B 117D 117C
CORTEN CORRUGATED
WALL PANEL (MTL-3)
OVERHEAD COILING DOOR
3"
1'-0"
BOLLARD; SEE CIVIL
STANDING SEAM METAL
ROOFING (MTL-1)
116B
CENTER LOUVERS ON
O.H. DOOR, TYP.
C.J.
C.J. C.J.
C.J. C.J.
C.J. C.J.
4'-0"
2'-0"
01-L-07 01-L-08 01-L-09
SNOW FENCE
PREFINISHED METAL FASCIA
(MTL-1)
8" X 6" PRE-FINISHED STEEL
GUTTER (MTL-1)
4" X 6" PRE-FINISHED STEEL
DOWNSPOUT (MTL-1)
1'-4"
ALUMINUM LOUVER
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N P
S
G ra n d C a n y o n S o u th
R im
W T
P
/1
A
S
R W
T P
.r v t
/2
/2
:3
:5
A M
A202
GRAND CANYON NATIONAL PARK
190083
EXTERIOR ELEVATIONS 2S. HEANEY
R. McKINLEY
04/22/2022
S. KENNY
14456601-
3/32" = 1'-0" 8 0 8 2416
SCALE OF FEET
SCALE A
01-A202
2 EXTERIOR ELEVATION - WEST
01-A202
1 EXTERIOR ELEVATION - NORTH
REV 1 DSC QA COMMENTS 6/20/22
/2
0/
IC
IC
IC
IC
IC
IC
IC
IC
IC
IC
IC
IC
MATCHLINE - SEE SHEET 01-01-E113 FOR CONTINUATION
2.7
MECHANICAL
MEZZANINE
1 2.3 2.8
5 6
G.4
1.2 4.8
K
J
H
01-EF-2
01-EF-1
LIT
LSH
LSL
LIT
LSH
LSL
LIT
LSH
LSL
LIT
LSH
LSL
01-IRH-601-IRH-5
2.7
01-MAU-3 01-MAU-4
01-MAU-2
01-MAU-1
01-MAU-6
01-EF-11
ASCALE 3/16" = 1'-0"
4 0 4 128
SCALE OF FEET
A
B
D
C
KEY PLAN
MATCHLINE
MATCHLINE
MATCHLINE
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N P
S
G ra n d C a n y o n S o u th
R im
W T
P
/1
E
S
R W
T P
.r v t
/2
/2
:3
:3
A M
E112
GRAND CANYON NATIONAL PARK
190083
BASIN LEVEL
POWER PLAN AREA A
T. MOORE
P. DAVILA
04/22/2022
N. LYNCH
14456601-
01-E112
1 BASIN LEVEL POWER PLAN AREA A
AREA CLASSIFICATION TYPE:
CONTRACTOR SHALL PROVIDE AND INSTALL ALL APPLICABLE ELECTRICAL
COMPONENTS, DEVICES, EQUIPMENT, ETC. PER THE AREA
CLASSIFICATION TYPE LISTED FOR EACH ROOM TYPE INDICATED ON THIS
SHEET. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
ROOM TYPE: AREA CLASSIFICATION:
201 - MECH MEZZANINE INDOOR - WET/ CORROSIVE
REV 1 DSC QA COMMENTS 6/20/22 1
T D
-3 T
D -3
T D
-3
TD-3 TD-3
T D
-3 T
D -3
T D
-3
IC
IC
IC
MATCHLINE - SEE SHEET 01-01-E113 FOR CONTINUATION
2.7
1 2.8
D.4
D.2
C.8
C
D
E
01-FA-1
01-IRH-04
01-IRH-03
LI
LSH
LSL
I
01-IRH-10
01-IRH-11
01-IRH-12
01-MOD-6
2.7
01-MAU-5
01-EF-10
ASCALE 3/16" = 1'-0"
4 0 4 128
SCALE OF FEET
A
B
D
C
KEY PLAN
MATCHLINE
MATCHLINE
MATCHLINE
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
B
IM
/1
N P
S
G ra n d C a n y o n S o u th
R im
W T
P
/1
E
S
R W
T P
.r v t
/2
/2
:3
:1
A M
E114
GRAND CANYON NATIONAL PARK
190083
BASIN LEVEL
POWER PLAN AREA C
T. MOORE
P. DAVILA
04/22/2022
N. LYNCH
14456601-
01-E114
1 BASIN LEVEL POWER PLAN AREA C
AREA CLASSIFICATION TYPE:
CONTRACTOR SHALL PROVIDE AND INSTALL ALL APPLICABLE ELECTRICAL
COMPONENTS, DEVICES, EQUIPMENT, ETC. PER THE AREA
CLASSIFICATION TYPE LISTED FOR EACH ROOM TYPE INDICATED ON THIS
SHEET. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
ROOM TYPE: AREA CLASSIFICATION:
201 - PRETREAT BASIN PLATFORM INDOOR - WET/ CORROSIVE
DESIGN KVA: 13.85 DESIGN AMPACITY: 17 AMPS
PHASE B 2664 540 428 0 348 3980 4174 15
PHASE C 2664 0 0 0 0 2664 2664 10
TOTAL 7992 1080 673 0 936 10681 11083
PANEL DEMAND KVA: 11.08 PANEL DEMAND AMPACITY: 13 AMPS
RESERVE KVA: 2.77 RESERVE AMPACITY: 3 AMPS
PANEL 'SR-PP-1'
LOCATION: BRINE TANK VALVE VAULT VOLTAGE: 277/480 V KAIC: 42 BUSSING SHALL BE FULLY RATED
MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT
ENCLOSURE: NEMA 4X STYLE: PER SPECS BUSSING: 225 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL
BRKR MTG: BOLT-ON MCB: 225 A ACCESSORIES: GROUND BUS, 42 SPACE
(3) #15 - #15 3/4"
15/3 FV-7237
37 333 X 38
SPARE 15/30 39 333 X 40
0 41 333 X 42
EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP
PHASE A 2664 540 245 0 588 4037 4245 15
0 27 333 X 28
0 29 333 X 30
(3) #14 - #14 3/4"
15/3 FV-7236
31 333 X 32
SPARE 15/30 33 333 X 34
0 35 333 X 36
WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING
PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT
(3) #12 - #12 3/4"
15/3 FV-7231
1 333 X 1,581 2
MINI-POWER ZONE 'SR-MPZ-3' 30/2
SEE 'SR-SWBD-1' ONE-LINE
0 3 333 X 1,510 4 7
0 5 333 X 6 SPARE 20/1
0 17 333 X 18
(3) #12 - #12 3/4"
15/3 FV-7234
19 333 X 20
SPARE 15/30 21 333 X 22
0 23 333 X 24
(3) #13 - #13 3/4"
15/3 FV-7235
25 333 X 26
SPARE 15/3
(3) #12 - #12 3/4"
15/3 FV-7232
7 333 X 333 8
FV-7238 15/3
(3) #12 - #12 3/4"0 9 333 X 333 10 0
0 11 333 X 333 12 0
(3) #12 - #12 3/4"
15/3 FV-7233
13 333 X 14
SPARE 15/30 15 333 X 16
DESIGN KVA: 59.77 DESIGN AMPACITY: 166 AMPS
PANEL 'SR-LP-1'
LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120 V KAIC: 42 BUSSING SHALL BE FULLY RATED
MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT
ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL
BRKR MTG: BOLT-ON MCB: 250 A ACCESSORIES: GROUND BUS, 84 SPACE
WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING
PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT
#12 #12 #12 3/4" 0 20/1 LIGHTING CONTACTOR 'LCP-SR-LP1' 1 500 X 2 SPARE 20/1
20/1 SPARE 83 X 84 SPARE 20/1
NOTE:
1) PROVIDE AS A SINGLE SECTION
PANELBOARD WITH A MAXIMUM 20"
WIDTH.
EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP
PHASE A 6150 0 4075 2987 2044 15256 16786 140
PHASE B 3950 0 4637 4425 2632 15644 17461 146
PHASE C 5206 0 3868 2254 1020 12348 13570 113
TOTAL 15306 0 12580 9666 5696 43248 47817
PANEL DEMAND KVA: 47.82 PANEL DEMAND AMPACITY: 133 AMPS
RESERVE KVA: 11.95 RESERVE AMPACITY: 33 AMPS
20/1 SPARE 67 X 68 SPARE 20/1
20/1 SPARE 69 X 70 SPARE 20/1
20/1 SPARE 71 X 72 SPARE 20/1
20/1 SPARE 73 X 74 SPARE 20/1
20/1 SPARE 75 X 76 SPARE 20/1
20/1 SPARE 77 X 78 SPARE 20/1
20/1 SPARE 79 X 80 SPARE 20/1
20/1 SPARE 81 X 82 SPARE 20/1
#12 #12 #12 3/4" 0 20/1 PMP-2721 51 1,200 X 52 NF MAIN CONTROL PANEL 20/1
#12 #12 #12 3/4" 0 20/1 PMP-6221 53 1,200 X 54 01-EF-10 20/1
20/1 WATER PLANT RIO 55 X 56 01-EF-11 20/1
20/1 WATER PLANT RIO 57 X 58 SPARE 20/1
20/1 SPARE 59 X 60 SPARE 20/1
20/1 SPARE 61 X 62 SPARE 20/1
20/1 SPARE 63 X 64 SPARE 20/1
20/1 SPARE 65 X 66 SPARE 20/1
#12 #12 #12 3/4" 0 20/1 LCP-8101 3 250 X 319 4 EXTERIOR EGRESS LUMINAIRES 20/1 2 #10 #10 #10 3/4"
#12 #12 #12 3/4" 0 20/1 LCP-8201 5 250 X 511 6 EXTERIOR BLDG LUMINAIRES 20/1 2 #10 #10 #10 3/4"
#12 #12 #12 3/4" 0 20/1 LCP-8301 7 250 X 1,351 8 RM 113,116,119,120,121 LUMINAIRES 20/1 2 #6 #6 #10 1"
#6 #6 #10 1" 2 20/1 RM 201 LUMINAIRES 9 940 X 1,297 10 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"
#6 #6 #10 1" 2 20/1 RM 201 LUMINAIRES 11 998 X 1,474 12 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"
#8 #8 #10 1" 2 20/1 RM 102,103, 112 LUMINAIRES 13 1,548 X 1,176 14 RM 113 LUMINAIRES 20/1 2 #6 #6 #10 1"
#10 #10 #10 3/4" 2 20/1 RM 100,101,110,111 LUMINAIRES 15 883 X 1,198 16 RM 113 LUMINAIRES 20/1 2 #8 #8 #10 1"
#10 #10 #10 3/4" 2 20/1 RM 105,106,107,108,109 LUMINAIRES 17 885 X 600 18 01-EWC-1 20/1 0 SEE EQUIP. CONNECTION SCHEDULE
4 35 1,654 X 480 36 01-IRH-1, 2, 3, 4, 5, 6 20/1 4 SEE EQUIP. CONNECTION SCHEDULE
SEE EQUIP. CONNECTION SCHEDULE
35/2 01-EUH-2
37 2,507 X 480 38 01-IRH-7, 8, 9, 10, 11, 12 20/1 4 SEE EQUIP. CONNECTION SCHEDULE
4 39 2,507 X 264 40 01-GFUH-1 20/1 4 SEE EQUIP. CONNECTION SCHEDULE
SEE EQUIP. CONNECTION SCHEDULE 4 20/1 01-GWH-1 41 120 X 432 42 01-CF-1 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
#12 #12 #12 3/4" 0 20/1 UF SKID 1 MASTER CONTROL PANEL 43 500 X 1,456 44
ENTRANCE GATE MOTOR 'GMO-1' (1 HP) 20/2
(2) #6 - #10 2"
#12 #12 #12 3/4" 0 20/1 UF SKID 2 RIO CONTROL PANEL 45 500 X 1,456 46 6
#12 #12 #12 3/4" 0 20/1 UF SKID 3 RIO CONTROL PANEL 47 500 X 48 SR WATER PLANT PLC 20/1
#12 #12 #12 3/4" 0 20/1 PMP-2121 49 1,200 X 50 SR WATER PLANT PLC 20/1
#12 #12 #12 3/4" 0 20/1 RM 106 REFRIGERATOR 19 840 X 1,000 20 RM 106 ABOVE COUNTER MICROWAVE 20/1 0 #12 #12 #12 3/4"
#12 #12 #12 3/4" 0 20/1 RM 106 ABOVE COUNTER MICROWAVE 21 1,000 X 1,000 22 RM 106 ABOVE COUNTER MICROWAVE 20/1 0 #12 #12 #12 3/4"
#12 #12 #12 3/4" 0 20/1 RM 106 UNDERCOUNTER MICROWAVE 23 1,000 X 1,656 24 RM 106 3/4 HP GARBAGE DISPOSAL 20/1 0 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-MOD-1, 2, 3, 4, 5, 6, 7, 8 25 540 X 1,200 26 RM 106 UNDERCOUNTER DISH WASHER 20/1 0 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE
25/2 01-SS-1 & 01-SSCU-1
27 2,059 X 588 28 01-EF-3 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
3 29 2,059 X 588 30 01-EF-4 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-GDH-1 31 120 X 588 32 01-EF-5 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
SEE EQUIP. CONNECTION SCHEDULE
20/2 01-EUH-1
33 1,654 X 588 34 01-EF-6 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
1,920
1,920
#12 #12 #12 3/4" 0
#12 #12 #12 3/4" 0
1,920
1,920
0 #12 #12 #12 3/4"
0 #12 #12 #12 3/4"
500 0 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE
SEE EQUIP. CONNECTION SCHEDULE
DESIGN KVA: 46.47 DESIGN AMPACITY: 129 AMPS
20/1 SPARE 83 X 84 SPARE 20/1
NOTE:
1) PROVIDE AS A SINGLE SECTION
PANELBOARD WITH A MAXIMUM 20"
WIDTH.
EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP
PHASE A 3732 5580 0 3408 1278 13998 13093 109
PHASE B 2512 7200 0 4057 682 14451 13042 109
PHASE C 2110 5040 0 4057 750 11957 11039 92
TOTAL 8354 17820 0 11522 2710 40406 37174
PANEL DEMAND KVA: 37.17 PANEL DEMAND AMPACITY: 103 AMPS
RESERVE KVA: 9.29 RESERVE AMPACITY: 26 AMPS
PANEL 'SR-LP-2'
LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120 V KAIC: 42 BUSSING SHALL BE FULLY RATED
MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT
ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL
BRKR MTG: BOLT-ON MCB: 250 A ACCESSORIES: GROUND BUS, 84 SPACE
WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING
PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT
#10 #10 #10 3/4" 1 20/1 EXTERIOR GFCI RECEPTACLES 1 900 X 720 2 EXTERIOR GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"
20/1 SPARE 67 X 68 SPARE 20/1
20/1 SPARE 69 X 70 SPARE 20/1
20/1 SPARE 71 X 72 SPARE 20/1
20/1 SPARE 73 X 74 SPARE 20/1
20/1 SPARE 75 X 76 SPARE 20/1
20/1 SPARE 77 X 78 SPARE 20/1
20/1 SPARE 79 X 80 SPARE 20/1
20/1 SPARE 81 X 82 SPARE 20/1
4 51 1,654 X 900 52 RM 111 RACEWAY RECEPTACLES 20/1 1 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE
20/2 01-EUH-4
53 1,654 X 500 54 VENTILATION HORNS AND STROBES 20/1 0 #12 #12 #12 3/4"
4 55 1,654 X 360 56 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"
20/1 SPARE 57 X 58 SPARE 20/1
20/1 SPARE 59 X 60 SPARE 20/1
20/1 SPARE 61 X 62 SPARE 20/1
20/1 SPARE 63 X 64 SPARE 20/1
20/1 SPARE 65 X 66 SPARE 20/1
#12 #12 #12 3/4" 1 20/1 RM 106 RECEPTACLES 19 540 X 540 20 RM 106 RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 1 20/1 RM 111 RECEPTACLES 21 720 X 360 22 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"
#12 #12 #12 3/4" 0 20/1 RM 111 PRINTER 23 1,000 X 360 24 RM 110 'SR-WTP-NW-RACK' 20/1 0 #12 #12 #12 3/4"
W/ PULLSTRING 3/4" 0 20/1 FUTURE DOOR ACCESS CONTROLS 25 1,000 X 26 SPARE 20/1
#12 #12 #12 3/4" 1 20/1 RM 111 RACEWAY RECEPTACLES 27 900 X 900 28 RM 111 RACEWAY RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 0 20/1 RM 112 CHEM FEED PUMP 29 250 X 250 30 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"
#12 #12 #12 3/4" 0 20/1 FACU 31 500 X 250 32 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE 0 20/1 01-EMV-1s 33 280 X 250 34 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"
#10 #10 #10 3/4" 1 20/1 RM 116 GFCI RECEPTACLES 3 720 X 1,080 4 RM 113,119,120,121 GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"
#10 #10 #10 3/4" 1 20/1 RM 113 GFCI RECEPTACLES 5 1,080 X 900 6 RM 113, 119, 120, 121 GFCI RECEPTACLES 20/1 1 #10 #10 #10 3/4"
#10 #10 #10 3/4" 1 20/1 RM 113 GFCI RECEPTACLES 7 1,080 X 720 8 RM 114, 115 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 1 20/1 RM 103,112 GFCI RECEPTACLES 9 720 X 720 10 RM 101 RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 1 20/1 RM 102 GFCI RECEPTACLES 11 720 X 720 12 RM 102 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 1 20/1 RM 106,111 RECEPTACLES 13 1,080 X 1,872 14
SCADA/IT RACK 'SR-WTP-NW-RACK' 30/2
(2) #10 - #10 3/4"
#12 #12 #12 3/4" 1 20/1 RM 110 RECEPTACLES 15 540 X 1,872 16 0
#12 #12 #12 3/4" 1 20/1 RM 111 RACEWAY RECEPTACLES 17 900 X 720 18 RM 107,108,109 GFCI RECEPTACLES 20/1 1 #12 #12 #12 3/4"
#12 #12 #12 3/4" 5 20/1 RM 112 CHEM FEED PUMP 35 250 X 250 36 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"
#12 #12 #12 3/4" 5 20/1 RM 112 CHEM FEED PUMP 37 250 X 250 38 RM 112 CHEM FEED PUMP 20/1 5 #12 #12 #12 3/4"
SEE EQUIP. CONNECTION SCHEDULE
25/2 01-SS-2 & 01-SSCU-2
39 2,059 X 432 40 01-EF-7 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
3 41 2,059 X 42 SPARE 20/1
SEE EQUIP. CONNECTION SCHEDULE
25/3 01-EF-8
43 1,589 X 528 44 01-CP-1 20/1 5 SEE EQUIP. CONNECTION SCHEDULE
3 45 1,589 X 2,403 46
01-EWH-1 20/2
SEE EQUIP. CONNECTION SCHEDULE
3 47 1,589 X 2,403 48 4
SEE EQUIP. CONNECTION SCHEDULE
20/2 01-EUH-3
49 1,654 X 100 50 01-ESEW-2 HEAT TRACE 20/1 4 SEE EQUIP. CONNECTION SCHEDULE
DESIGN KVA: 118.32 DESIGN AMPACITY: 142 AMPS
3 83 2,938 X 84
NOTE:
1) PROVIDE AS A SINGLE SECTION
PANELBOARD WITH A MAXIMUM 20"
WIDTH.
EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP
PHASE A 7997 0 0 23554 0 31551 31551 114
PHASE B 7997 0 0 23554 0 31551 31551 114
PHASE C 7997 0 0 23554 0 31551 31551 114
TOTAL 23991 0 0 70662 0 94653 94653
PANEL DEMAND KVA: 94.65 PANEL DEMAND AMPACITY: 114 AMPS
RESERVE KVA: 23.66 RESERVE AMPACITY: 28 AMPS
PANEL 'SR-PP-2'
LOCATION: ELECTRICAL ROOM VOLTAGE: 480 V KAIC: 42 BUSSING SHALL BE FULLY RATED
MOUNTING: SURFACE PHASE: 3 P / 3W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT
ENCLOSURE: NEMA 1 STYLE: PER SPECS BUSSING: 225 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR, 7=PANEL
BRKR MTG: BOLT-ON MCB: 225 A ACCESSORIES: GROUND BUS, 84 SPACE
WIRING BREAKERS: 75 DEGREE TERMINALS MLO: A WIRING
PHASE NEUT. GND CONDUIT CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE PHASE NEUT. GND CONDUIT
(3) #12 - #12 3/4"