Bldg_4704_Asbestos_Survey_Report_Final.pdf
PDF 6 MB Posted
- Attached to
- Central Steam Distribution Replacement Phase 2 Federal contract opportunity
- Solicitation number
- 80MSFC18B0003
About this file
Bldg 4704 Asbestos Survey Report Final
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
General Asbestos Survey for Asbestos-Containing Materials
Prepared for:
Marshall Space Flight Center, AL
Building 4704 Marshall Space Flight Center
GSE - 017
April 30, 2009
Prepared by
Great Southern Engineering, Inc.
3795 Gordon Terry Parkway
Trinity, Alabama 35673
TABLE OF CONTENTS
1. Introduction
2. Summary
2.1. Suspect ACMs
2.2. Recommendations
3. Survey Scope
4. Limitations
5. Survey and Sample Collection Procedure
6. Previous Survey / Plans Review
7. Suspect ACM Materials Not Sampled
8. Survey Sampling Results
9. Appendices
Task Order GSE 017 Page 1 of 25
GENERAL ASBESTOS SURVEY OF
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
1. Introduction
In accordance with GSE Task Order No.GSE-017 dated August 15, 2008, Great Southern Engineering, Inc. (GSE) has performed an asbestos survey of Building 4704 located at George C.
Marshall Space Flight Center, Marshall Space Flight Center, Alabama. The 4,660 square feet building was identified to have been originally constructed in 1952. A total of 30 samples were collected from the building.
The objective of the Asbestos Survey is to determine the location and quantity of asbestos-containing materials at the Property building.
GSE’s Scope of Work included:
Visual inspection and identification of suspect asbestos-containing materials (ACMs) in the Property building and collected a representative number of samples for analysis.
As part of this asbestos survey, GSE personnel collected samples of all suspect friable and suspect damaged non-friable building materials at the Property. The remaining suspect non-friable materials were not be sampled as part of this asbestos survey
Estimated quantities and locations of ACM.
Assessed the condition of the ACM identified.
Assigned a hazard rating to each type of ACM.
This report has been prepared for the use of George C. Marshall Space Flight Center. Our investigation was performed using the degree of care and skill ordinarily exercised under similar circumstances by professional consultants practicing in this or similar localities. No other warranty or guarantee, expressed or implied, is made as to the conclusions included in this report.
Task Order GSE 017 Page 2 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
The GSE, Inc. did not perform destructive sampling procedures at the site; therefore, regardless of the thoroughness of this survey, it is possible that suspected asbestos-containing materials (ACMs) might exist in the building beneath the floors, behind walls, within pipe chases, or in other inaccessible locations. If, during renovation or demolition activities, materials not addressed in this survey are discovered, these materials should be sampled and analyzed for asbestos content prior to disturbance.
Surveyed by:
John A Jackson
University of Alabama Safe State Program Accredited Inspector/Management Planner
Accreditation #AIN0908531941
Written by:
Manju Ramasamudra
University of Alabama Safe State Program Accredited Inspector/Management Planner
Accreditation #APL0308R5089
Task Order GSE 017 Page 3 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
2. Summary
GSE performed an Asbestos Survey and Hazard Assessment at Building 4704 in Marshall Space Flight Center, Alabama on January 20, 2009 and April 2, 2009. Sample collection was completed by licensed personnel – John A Jackson. The following report summarizes the independent conclusions representing GSE’ best professional judgment based on information and data available to us during the course of this survey. Factual information regarding operations, conditions, and tests data provided by the client, owner or their representative has been assumed to be correct and complete. Additionally, the conclusions presented are based on the conditions that existed on the date(s) of the assessment.
The 4,660 square feet building was identified to have been originally constructed in 1952. A total of 30 samples were collected from the building. No homogeneous materials were identified as asbestos-containing materials.
Task Order GSE 017 Page 4 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
2.1. Suspect ACMs
The following information is included for informational purposes:
A. The following suspect asbestos-containing materials were not sampled as part of this scope of work:
Suspect fibrous electrical cable covering (danger of electrocution) were not sampled.
These materials are not subject to regulation under NESHAP for demolition and renovation as long as they are in good condition and are not subject to sanding, grinding, cutting, or abrading.
Since ordinary demolition activities do not include sanding, grinding, cutting, and abrading, these materials may remain in place during building demolition, as long as they remain in good condition and are not friable.
If the material is in poor condition and is friable at the time of demolition or renovation, or if it will be subjected to sanding, grinding, cutting, or abrading, it should first be removed by a licensed asbestos removal contractor and disposed of as asbestos-containing waste.
When removing asphalt-roofing products, the material should be removed using a method that does not subject the material to sanding, cutting, grinding, or abrading (hand tools).
Asbestos-containing roofing may be disposed of as construction debris.
2.2. Recommendations
The following additional actions are recommended:
No further actions are recommended at this time.
Task Order GSE 017 Page 5 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
3. Survey Scope
This survey was conducted for the purpose of identifying asbestos-containing materials (ACM) throughout the building and to conduct a hazard assessment on existing ACM. The survey was non-destructive in nature and limited only to those areas that were readily accessible.
Specific areas to which access was limited by occupant request, unavailability of keys, or by site conditions included the following:
Behind the walls
Beneath the floors
Any suspect ACM not sampled as part of the assessment and if any additional suspect materials were to be identified behind walls and beneath the floors should be sampled prior to repair, renovation, or demolition activities.
Task Order GSE 017 Page 6 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
4. Limitations
GSE did not attempt to disassemble mechanical equipment, open pipe chases or assess materials within wall voids. Regardless of the thoroughness of a survey, the possibility exists that some areas containing asbestos were not identified, inaccessible or different from those at specific locations. The findings and opinions presented are relative to the dates of our site work and should not be relied upon to represent conditions at substantially later dates due to changes in the condition ACM may change over time, renovations and repairs.
This report is for the exclusive use of the client and its agents and use by any unauthorized parties in whole or in part, except as directed by legal jurisdiction, is at the sole risk of the user.
If this assessment includes reliance on work products and/or documents prepared by others, GSE has no responsibility for the accuracy of information contained therein.
Although this assessment has attempted to identify the presence or absence of ACM, potential sources of ACM may have escaped detection due to: (1) the scope of this assessment, (2) the inaccuracy of records, interviews, work products or documents made available to GSE for this report, (3) the presence of undetected or unreported renovations and repairs, (4) inaccessible areas, and/or (5) deliberate concealment of detrimental information.
Estimates presented in this report are based upon observations during the survey and owner-provided information. These reasonable estimates may be affected by unanticipated conditions potentially present in inaccessible or un-surveyed areas. GSE does not warrant or guarantee the quantity estimates. The use of such estimates shall be at the user's own risk and shall constitute a release and agreement to defend and indemnify GSE from and against any liability. If questions arise during the planning for renovation, demolition, or other construction activities, GSE should be notified to permit review of the data and present recommendations.
Interior of the following rooms were inaccessible during our Asbestos Survey on January 20, 2009 and April 2, 2009: None.
Task Order GSE 017 Page 7 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
5. Survey and Sample Collection Procedure
Based on United States Environmental Protection Agency (USEPA) guidance documents, GSE considered all material applications identified during the visual assessment were suspect ACM and sampled as described below.
Bulk samples were collected of any materials, which were suspected of containing asbestos with the exception of fire doors. Fire doors were not sampled because the damage caused by sampling would render these materials friable and may also void the fire rating. Since these materials were not sampled, they should be assumed to be asbestos containing, unless sampled and proven otherwise. Sampling of these assumed ACMs should be performed prior to any renovation or other activity that may cause a material disturbance.
Samples of the remaining suspect ACM were taken in accordance with USEPA recommendations.
The number and location of samples collected was based on the type of material, the manner of application, and the homogeneity of the ACM (similarity of color, texture, and type). Each sample was collected and placed into an individual sample container. The sample location was noted on the field survey form and assigned an individual identification number. This number was affixed to the sample container as the sample was collected. The survey form was also used to note the material type and general condition of the material. During the inspection, each suspect material's accessibility, location, and friability were recorded. This information was used to assess the potential hazard of the ACM and to prioritize response action recommendations.
The USEPA defines asbestos-containing materials (ACM) as those that contain greater than one percent asbestos. Friable materials are defined as those that can be crumbled or reduced to powder by hand pressure.
GSE utilized the “positive-stop” method of sample analysis. In this method, analysis is stopped on a group of samples once the first positive (e.g., greater than 1% asbestos) sample is analyzed.
According to the USEPA, if one sample of a homogenous material is identified to be asbestos containing, the entire material must be considered asbestos containing. By using the positive-stop method, GSE reduces the Client’s laboratory analysis cost by not analyzing the additional samples.
Samples collected were carried and submitted under Chain-of-Custody to Steve Moody Micro Services LLC, Farmers Branch, Texas for analysis of asbestos using USEPA Method 40 CFR, Chapter 1, Part 763, Subpart F, Appendix A, also known as Polarized Light Microscopy (PLM).
Steve Moody Micro Services LLC is certified by the National Voluntary Laboratory Accreditation Program (NVLAP) and licensed by the Department of State Health Services.
Task Order GSE 017 Page 8 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
6. Previous Survey / Plans Review
GSE was not provided with any previously conducted asbestos surveys of the Property. As-built/renovation-site plans and construction drawings were reviewed at the Facilities Department Drawing Room. Review of these documents did not identify building material specifications requiring the use of ACM. However, this does not preclude or prevent the potential use of ACM.
Task Order GSE 017 Page 9 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
7. Suspect ACM Materials Not Sampled
During the course of the property visit, GSE performed a preliminary review of interior, accessible areas of the subject building for the presence of suspect asbestos-containing materials (ACMs). This asbestos survey was conducted for overview purposes only; additional suspect materials may exist in concealed locations (behind walls and above ceilings, beneath the floors, within machinery, etc.). Also, not all suspect materials may have been sampled due to the condition or the location of the suspect materials. Destructive sampling of suspect ACMs was not performed. GSE will not be responsible for damaging materials or causing the materials to become friable. The USEPA defines asbestos-containing material as material containing greater than one percent asbestos. This review was not a pre-demolition/renovation survey or for regulatory submittal purposes.
Suspect and/or presumed ACMs were observed within the subject building during the property visit. These suspect and/or presumed ACMs that were not sampled as part of this asbestos survey are listed in the following table.
Sample Description Physical Condition
Friable Yes/No
Type of
ACM
Sample ID
4704Building Number
Caulking, On Exterior Wall Joints UPS4 NoM
Grout, On Exterior Wall Masonry UPS5 NoM
Wiring, Fibrous Electrical Cable Covering UPS6 NoM
Fire Doors, Fire Door Insulation UPS7 NoM
Mastic, Mirror Mastic UPS8 NoM
Task Order GSE 017 Page 10 of 25
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
8. Survey Sampling Results
The results of the Survey are presented in the tables on the following pages. The tables describe the entire suspect Asbestos-Containing Materials (ACMs) identified in the building and list respective sample numbers and laboratory results. Sample numbers presented in the tables correspond to the sample numbers on attached Laboratory Analysis Forms. Also presented in the tables is the estimated quantity and assessed friability for each suspect ACM. For each suspect material identified as ACM, the assessed hazard potential is presented along with GSE’ recommended response action. Hazard potential for each material application is based on the material condition and accessibility to the public and maintenance personnel.
Glossary of Items for the following Table
Type of Asbestos (1) CH = Chrysotile AM = Amosite CR = Crocidolite AN = Anthophyllite TR = Tremolite AC = Actinolite ND = No Asbestos Detected PC = Point Count Method
Type of ACM (2) M = Miscellaneous S = Surfacing TSI = Thermal Systems Insulation
Friability (3) F = Friable NF = Non Friable
Physical Condition (4) U = Good D = Damaged SD = Significantly Damaged
Potential for Disturbance (5) NPD = No Potential for Disturbance PD = Potential for Disturbance PSD = Potential for Significant Disturbance
Assessment Category (6) 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM 3 = Significantly damaged friable surfacing ACBM 4 = Damaged or significantly damaged friable miscellaneous ACBM 5 = ACBM with potential for damaged 6 = ACBM potential for significant damage 7 = Any remaining friable ACBM or friable suspected
ACBM
X = not applicable
Unit of Measurement SF = Square Feet
LF = Linear Feet
Sample Description
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 1
Pipe Insulation with White Mastic
Yes TSI Yes U XRoom: 100A Grid: F2-4
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
1 PD
Yes TSI Yes U XRoom: 103 Grid: C2-1
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
2 PD
Yes TSI Yes U XRoom: 105 Grid: WL2-1
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
3 PD
Homogeneous Area 2
Expansion Joint Material on Floor
Yes M No U XRoom: 103 Grid: F2-1
ND - Joint Material4 PD
Yes M No U XRoom: 100A Grid: F3-1
ND - Joint Material5 PD
Yes M No U XRoom: 104 Grid: F3-1
ND - Joint Material6 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 3
Cove Base Gray and Associated Mastic
Yes M No U XRoom: 101 Grid: WE1-2
ND - Cove Base ND - Yellow Mastic
7 PD
Yes M No U XRoom: 101 Grid: WE1-3
ND - Cove Base ND - Yellow Mastic
8 PD
Yes M No U XRoom: 101 Grid: WR1-2
ND - Cove Base ND - Yellow Mastic
9 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 4
Pipe Insulation with Gray Mastic
Yes TSI Yes U XRoom: 100 Grid: WE2-4
ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic
10 PD
Yes TSI Yes U XRoom: 100 Grid: WE2-4
ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic
11 PD
Yes TSI Yes U XRoom: 100 Grid: WE2-4
ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic
12 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 5
Gasket Around Window Glass
Yes M No U XRoom: 101 Grid: WF3-2
ND - Gasket13 PD
Yes M No U XRoom: 101 Grid: WF3-2
ND - Gasket14 PD
Yes M No U XRoom: 101 Grid: WF3-2
ND - Gasket15 PD
Homogeneous Area 6
Pipe Insulation with Silver Foil Cover
Yes TSI Yes U XRoom: 100 Grid: F3-3
ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint
16 PD
Yes TSI Yes U XRoom: 100 Grid: F3-3
ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint
17 PD
Yes TSI Yes U XRoom: 100 Grid: F3-3
ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint
18 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 7
Coating Black on Floor Yes M No U XRoom: 100A Grid: F3-2
ND - Coating19 PD
Yes M No U XRoom: 100A Grid: F3-2
ND - Coating20 PD
Yes M No U XRoom: 100A Grid: F3-2
ND - Coating21 PD
Homogeneous Area 8
Wall Covering Wall Panels
Yes M Yes U XRoom: 105 Grid: WE2-2
ND - Wall Panel22 PD
Yes M Yes U XRoom: 105 Grid: WL2-3
ND - Wall Panel23 PD
Yes M Yes U XRoom: 105 Grid: WF2-4
ND - Wall Panel24 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4704Building Number
Homogeneous Area 9
Pipe Insulation with Metal Bands
Yes TSI Yes D XRoom: 105 Grid: WE1-3
ND - Insulation ND - Paper/ Foil Wrap
25 PD
Yes TSI Yes D XRoom: 105 Grid: WR1-2
ND - Insulation ND - Paper/ Foil Wrap
26 PD
Yes TSI Yes D XRoom: 105 Grid: WE1-1
ND - Insulation ND - Paper/ Foil Wrap
27 PD
Homogeneous Area 10
Wallboard System with Texture and Joint Compound
Yes M Yes U XRoom: 100A Grid: WE2-4
ND - Drywall Material ND - Texture/ joint Compound
28 PD
Yes M Yes U XRoom: 100A Grid: WE1-4
ND - Drywall Material ND - Texture/ joint Compound
29 PD
Yes M Yes U XRoom: 100A Grid: WE2-1
ND - Drywall Material ND - Texture/ joint Compound
30 PD
1. CH = Chrysotile; AM = Amosite; CR = Crocidolite; AN = Anthophyllite; TR = Tremolite; AC = Actinolite; ND = No Asbestos Detected; or PC = Point Count Method
2. M = Miscellaneous; S = Surfacing; or TSI = Thermal Systems Insulation
3. F = Friable or NF = Non Friable
4. U = Good; D = Damaged; or SD = Significantly Damaged
5. NPD = No Potential for Disturbance; PD = Potential for Disturbance; or PSD = Potential for Significant Disturbance
6. 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 = Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM potential for significant damage, 7 = Any remaining friable ACBM or friable suspected ACBM, or X = not applicable
SF = Square Feet LF = Linear Feet
9. Appendices
Appendix A— Laboratory Results and Chain of Custody Appendix B— ACM Sample Location Drawings Appendix C— ACM Location Diagrams Appendix D— Photographs Appendix E— Certificates and Licenses
Appendix A
Laboratory Results
PLM Summary Report NVLAP Lab No. 102056
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4704
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.
The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-00859
01/20/2009
01/30/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
01 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
02 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
03 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
04 Expansion Joint Material None Detected - Joint Material
05 Expansion Joint Material None Detected - Joint Material
06 Expansion Joint Material None Detected - Joint Material
07 Cove Base (Gray) and Mastic None Detected - Cove Base
None Detected - Yellow Mastic
08 Cove Base (Gray) and Mastic None Detected - Cove Base
None Detected - Yellow Mastic
09 Cove Base (Gray) and Mastic None Detected - Cove Base
None Detected - Yellow Mastic
10 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation
None Detected - Tar Wrap
None Detected - Paper / Foil Wrap
None Detected - Mastic
11 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation
None Detected - Tar Wrap
None Detected - Paper / Foil Wrap
None Detected - Mastic
12 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation
None Detected - Tar Wrap
None Detected - Paper / Foil Wrap
None Detected - Mastic
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4704
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.
The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-00859
01/20/2009
01/30/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
13 Gasket, Around Window Pane None Detected - Gasket
14 Gasket, Around Window Pane None Detected - Gasket
15 Gasket, Around Window Pane None Detected - Gasket
16 Pipe Insulation (Silver) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - Silver Paint
17 Pipe Insulation (Silver) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - Silver Paint
18 Pipe Insulation (Silver) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - Silver Paint
19 Coating (Black), on Floor None Detected - Coating
20 Coating (Black), on Floor None Detected - Coating
21 Coating (Black), on Floor None Detected - Coating
22 Wall Panels None Detected - Wall Panel
23 Wall Panels None Detected - Wall Panel
24 Wall Panels None Detected - Wall Panel
25 Pipe Insulation with Metal Bands None Detected - Insulation
None Detected - Paper / Foil Wrap
26 Pipe Insulation with Metal Bands None Detected - Insulation
None Detected - Paper / Foil Wrap
27 Pipe Insulation with Metal Bands None Detected - Insulation
None Detected - Paper / Foil Wrap
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4704
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.
The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-00859
01/20/2009
01/30/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
Kirsten TyeAnalyst(s):
Lab Director : Steve Moody Approved Signatory :
Thank you for choosing Steve Moody Micro Services
These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the
National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.
Lab Manager : Bruce Crabb Approved Signatory :
Steve Moody Micro Services, LLC PLM Detail Report NVLAP Lab No. 102056
TDSHS License No. 30-0084
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-00859
01/30/2009
Mineral Wool Fibers01 Insulation (Yellow) 96% 01/2895% KT
Resin Binders01 Insulation (Yellow) 96% 01/285% KT
Cellulose Fibers01 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT
Glass Wool Fibers01 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Metal Foil01 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Pigment / Binders01 White Mastic (Off-White) 2% 01/28100% KT
Mineral Wool Fibers02 Insulation (Yellow) 93% 01/2895% KT
Resin Binders02 Insulation (Yellow) 93% 01/285% KT
Cellulose Fibers02 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT
Glass Wool Fibers02 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Metal Foil02 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Polyethylene Fibers02 White Mastic (Off-White) 5% 01/285% KT
Calcite02 White Mastic (Off-White) 5% 01/2840% KT
Wollastonite02 White Mastic (Off-White) 5% 01/285% KT
Pigment / Binders02 White Mastic (Off-White) 5% 01/2850% KT
Mineral Wool Fibers03 Insulation (Yellow) 93% 01/2895% KT
Resin Binders03 Insulation (Yellow) 93% 01/285% KT
Cellulose Fibers03 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT
Glass Wool Fibers03 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Metal Foil03 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Polyethylene Fibers03 White Mastic (Off-White) 5% 01/285% KT
Calcite03 White Mastic (Off-White) 5% 01/2840% KT
Wollastonite03 White Mastic (Off-White) 5% 01/285% KT
Pigment / Binders03 White Mastic (Off-White) 5% 01/2850% KT
Wood Fibers04 Joint Material (Black) 100% 01/2885% KT
Tar Binders04 Joint Material (Black) 100% 01/2815% KT
Wood Fibers05 Joint Material (Black) 100% 01/2885% KT
Tar Binders05 Joint Material (Black) 100% 01/2815% KT
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-00859
01/30/2009
Wood Fibers06 Joint Material (Black) 1% 01/2885% KT
Tar Binders06 Joint Material (Black) 1% 01/2815% KT
Aggregate06 Concrete (Grey) 99% 01/2865% KT
Cement Binders06 Concrete (Grey) 99% 01/2835% KT
Calcite / Vinyl Binders07 Cove Base (Grey) 95% 01/28100% KT
Glue Binders07 Yellow Mastic (Yellow) 5% 01/28100% KT
Calcite / Vinyl Binders08 Cove Base (Tan) 90% 01/28100% KT
Glue Binders08 Yellow Mastic (Yellow) 10% 01/28100% KT
Calcite / Vinyl Binders09 Cove Base (Tan) 98% 01/28100% KT
Glue Binders09 Yellow Mastic (Yellow) 2% 01/28100% KT
Mineral Wool Fibers10 Insulation (Yellow) 78% 01/2895% KT
Resin Binders10 Insulation (Yellow) 78% 01/285% KT
Tar Binders10 Tar Wrap (Black) 20% 01/28100% KT
Cellulose Fibers10 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT
Glass Wool Fibers10 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Metal Foil10 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Pigment / Binders10 Mastic (Grey) <1% 01/28100% KT
Mineral Wool Fibers11 Insulation (Yellow) 95% 01/2895% KT
Resin Binders11 Insulation (Yellow) 95% 01/285% KT
Tar Binders11 Tar Wrap (Black) 1% 01/28100% KT
Cellulose Fibers11 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT
Glass Wool Fibers11 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Metal Foil11 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Polyethylene Fibers11 Mastic (Grey) 2% 01/285% KT
Calcite11 Mastic (Grey) 2% 01/2840% KT
Wollastonite11 Mastic (Grey) 2% 01/285% KT
Pigment / Binders11 Mastic (Grey) 2% 01/2850% KT
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-00859
01/30/2009
Mineral Wool Fibers12 Insulation (Yellow) 76% 01/2895% KT
Resin Binders12 Insulation (Yellow) 76% 01/285% KT
Tar Binders12 Tar Wrap (Black) 20% 01/28100% KT
Cellulose Fibers12 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT
Glass Wool Fibers12 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Metal Foil12 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT
Pigment / Binders12 Mastic (Grey) 2% 01/28100% KT
Vinyl Binders13 Gasket (Black) 100% 01/28100% KT
Vinyl Binders14 Gasket (Black) 100% 01/28100% KT
Vinyl Binders15 Gasket (Black) 100% 01/28100% KT
Mineral Wool Fibers16 Insulation (Yellow) 97% 01/2895% KT
Resin Binders16 Insulation (Yellow) 97% 01/285% KT
Cellulose Fibers16 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT
Glass Wool Fibers16 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Metal Foil16 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT
Pigment / Binders16 Silver Paint (Silver) 1% 01/28100% KT
Mineral Wool Fibers17 Insulation (Yellow) 89% 01/2895% KT
Resin Binders17 Insulation (Yellow) 89% 01/285% KT
Cellulose Fibers17 Paper / Foil Wrap (White / Silver) 10% 01/2860% KT
Glass Wool Fibers17 Paper / Foil Wrap (White / Silver) 10% 01/2820% KT
Metal Foil17 Paper / Foil Wrap (White / Silver) 10% 01/2820% KT
Pigment / Binders17 Silver Paint (Silver) 1% 01/28100% KT
Mineral Wool Fibers18 Insulation (Yellow) 45% 01/2895% KT
Resin Binders18 Insulation (Yellow) 45% 01/285% KT
Cellulose Fibers18 Paper / Foil Wrap (White / Silver) 50% 01/2860% KT
Glass Wool Fibers18 Paper / Foil Wrap (White / Silver) 50% 01/2820% KT
Metal Foil18 Paper / Foil Wrap (White / Silver) 50% 01/2820% KT
Pigment / Binders18 Silver Paint (Silver) 5% 01/28100% KT
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-00859
01/30/2009
Cellulose Fibers19 Coating (Black, Dirty) 100% 01/283% KT
Calcite19 Coating (Black, Dirty) 100% 01/2840% KT
Binders / Fillers19 Coating (Black, Dirty) 100% 01/2857% KT
Cellulose Fibers20 Coating (Black, Dirty) 100% 01/283% KT
Calcite20 Coating (Black, Dirty) 100% 01/2840% KT
Binders / Fillers20 Coating (Black, Dirty) 100% 01/2857% KT
Cellulose Fibers21 Coating (Black, Dirty) 100% 01/283% KT
Calcite21 Coating (Black, Dirty) 100% 01/2840% KT
Binders / Fillers21 Coating (Black, Dirty) 100% 01/2857% KT
Cellulose Fibers22 Wall Panel (Light Tan) 100% 01/2875% KT
Perlite22 Wall Panel (Light Tan) 100% 01/2820% KT
Tar Binders22 Wall Panel (Light Tan) 100% 01/285% KT
Cellulose Fibers23 Wall Panel (Light Tan) 100% 01/2875% KT
Perlite23 Wall Panel (Light Tan) 100% 01/2820% KT
Tar Binders23 Wall Panel (Light Tan) 100% 01/285% KT
Cellulose Fibers24 Wall Panel (Light Tan) 100% 01/2875% KT
Perlite24 Wall Panel (Light Tan) 100% 01/2820% KT
Tar Binders24 Wall Panel (Light Tan) 100% 01/285% KT
Mineral Wool Fibers25 Insulation (Yellow) 98% 01/2895% KT
Resin Binders25 Insulation (Yellow) 98% 01/285% KT
Cellulose Fibers25 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2860% KT
Glass Wool Fibers25 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2820% KT
Metal Foil25 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2820% KT
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-00859
01/30/2009
Mineral Wool Fibers26 Insulation (Yellow) 98% 01/2895% KT
Resin Binders26 Insulation (Yellow) 98% 01/285% KT
Cellulose Fibers26 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2860% KT
Glass Wool Fibers26 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2820% KT
Metal Foil26 Paper / Foil Wrap (White/Silver, Dirty)
2% 01/2820% KT
Mineral Wool Fibers27 Insulation (Yellow) 95% 01/2895% KT
Resin Binders27 Insulation (Yellow) 95% 01/285% KT
Cellulose Fibers27 Paper / Foil Wrap (White/Silver, Dirty)
5% 01/2860% KT
Glass Wool Fibers27 Paper / Foil Wrap (White/Silver, Dirty)
5% 01/2820% KT
Metal Foil27 Paper / Foil Wrap (White/Silver, Dirty)
5% 01/2820% KT
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4704
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 4/7/2009, three (3) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS. The PLM
Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-03790
04/02/2009
04/07/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
28 Wall System None Detected - Drywall Material
None Detected - Texture / Joint Cmpd
29 Wall System None Detected - Drywall Material
None Detected - Texture / Joint Cmpd
30 Wall System None Detected - Drywall Material
None Detected - Texture / Joint Cmpd
Steve MoodyAnalyst(s):
Lab Director : Steve Moody Approved Signatory :
Thank you for choosing Steve Moody Micro Services
These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the
National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.
Lab Manager : Bruce Crabb Approved Signatory :
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4704
Lab Job No. :
Report Date :
09B-03790
04/07/2009
Cellulose Fibers28 Drywall Material (White) 50% 04/072% SM
Gypsum / Binders28 Drywall Material (White) 50% 04/0798% SM
Cellulose Fibers28 DW Paper Facing (Tan) 10% 04/07100% SM
Calcite / Talc / Binders28 Texture / Joint Cmpd (White) 40% 04/07100% SM
Cellulose Fibers29 Drywall Material (White) 50% 04/072% SM
Gypsum / Binders29 Drywall Material (White) 50% 04/0798% SM
Cellulose Fibers29 DW Paper Facing (Tan) 10% 04/07100% SM
Calcite / Talc / Binders29 Texture / Joint Cmpd (White) 40% 04/07100% SM
Cellulose Fibers30 Drywall Material (White) 50% 04/072% SM
Gypsum / Binders30 Drywall Material (White) 50% 04/0798% SM
Cellulose Fibers30 DW Paper Facing (Tan) 10% 04/07100% SM
Calcite / Talc / Binders30 Texture / Joint Cmpd (White) 40% 04/07100% SM
Appendix B
ACM Sample Location Drawings
First Floor Building 4704
Marshall Space Flight Center Marshall Space Flight Center, AL
Task Order #GSE-017
23322
19, 20, 21
13, 14, 8 7 10, 11, 12
16, 17, 18
28, Appendix C
ACM Location Diagrams
NOT APPLICABLE
Appendix D
Photographs
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
PHOTO 1. View of the building PHOTO 2. Interior view of the building
PHOTO 3. Interior view of the building PHOTO 4. Pipe insulation with white mastic
PHOTO 5. Expansion joint material on floor PHOTO 6. Gray cove base and associated mastic
Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
PHOTO 7. Pipe insulation with gray mastic and paper cover PHOTO 8. Gasket around window glass
PHOTO 9. Pipe insulation with silver foil cover PHOTO 10. Black coating on concrete floor
PHOTO 11. Wall panels PHOTO 12. Pipe insulation with metal bands
Appendix E
License and Certifications
| 1. Introduction |
| 2. Summary |
| 2.1. Suspect ACMs |
| 2.2. Recommendations |
| 3. Survey Scope |
| 4. Limitations |
| 5. Survey and Sample Collection Procedure |
| 6. Previous Survey / Plans Review |
| 7. Suspect ACM Materials Not Sampled |
| 8. Survey Sampling Results |
| 9. Appendices |
| Appendix A Laboratory Results |
| Appendix B ACM Sample Location Drawings |
| Appendix C ACM Location Diagrams |
| Appendix D Photographs |
| Appendix E License and Certifications |
File details come from the government source that posted it.