About this file

Bldg 4704 Asbestos Survey Report Final

View the file

Other files for this federal contract opportunity

Other files attached to Central Steam Distribution Replacement Phase 2, newest first.
File Type Posted
Abstract_of_Bids,_80MSFC18B0003.pdf PDF
IFB_80MSFC18B0003,_Posted_Copy,_Aug_9,_2018_REVISED_BLOCK_13.pdf PDF
IFB_80MSFC18B0003,_Amendment_4,_REVISED_BLOCKS_11_&_13.pdf PDF
IFB_80MSFC18B0003,_Amendment_4.pdf PDF
IFB_80MSFC18B0003,_Posted_Copy,_Aug_9,_2018.pdf PDF
33_16_15_-_Thermal_Energy_Storage_Tank_Specification,_Amendment_4.pdf PDF
Revised_Plans,_FAC-5071,_80MSFC18B0003.pdf PDF
IFB_80MSFC18B0003,_Amendment_3.pdf PDF
Army_and_NASA_Site_Access_Control_Boundaries_Map.pdf PDF
Bid_Instructions_for_IFB_80MSFC18B0003,_Amendment_3.pdf PDF
Attendees_at_Site_Visit,_June_20,_2018,_IFB_80MSFC18B0003.pdf PDF
IFB_80MSFC18B0003,_Amendment_2.pdf PDF
IFB_80MSFC18B0003,_Posted_Copy,_July_20,_2018.pdf PDF
Bldg_4483_Asbestos_Survey_Report_Final.pdf PDF
IFB_80MSFC18B0003,_Posted_Copy,_June_26,_2018.pdf PDF
80MSFC18B003,_Amendment_1.pdf PDF
Bldg_4711_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4493_Asbestos_Survey_Report_Final.pdf PDF
Specifications_FAC-M5066,_80MSFC18B0003.pdf PDF
Plans,_FAC-5066,_80MSFC18B0003.pdf PDF
Bldg_4776_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4464_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4727_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4312_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4723_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4732_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4491_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4306_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4733_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4747_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4777_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4705_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4738_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4485_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4702_Asbestos_Survey_Report_Final.pdf PDF
Bldg_4715_Asbestos_Survey_Report_Final.pdf PDF
Specifications_FAC-M5071,_80MSFC18B0003.pdf PDF
Plans,_80MSFC18B0003.pdf PDF
IFB_80MSFC18B0003.pdf PDF
Bid_Instructions_for_IFB_80MSFC18B0003.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Asbestos Survey for Asbestos-Containing Materials

Prepared for:

Marshall Space Flight Center, AL

Building 4704 Marshall Space Flight Center

GSE - 017

April 30, 2009

Prepared by

Great Southern Engineering, Inc.

3795 Gordon Terry Parkway

Trinity, Alabama 35673

TABLE OF CONTENTS

1. Introduction

2. Summary

2.1. Suspect ACMs

2.2. Recommendations

3. Survey Scope

4. Limitations

5. Survey and Sample Collection Procedure

6. Previous Survey / Plans Review

7. Suspect ACM Materials Not Sampled

8. Survey Sampling Results

9. Appendices

Task Order GSE 017 Page 1 of 25

GENERAL ASBESTOS SURVEY OF

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

1. Introduction

In accordance with GSE Task Order No.GSE-017 dated August 15, 2008, Great Southern Engineering, Inc. (GSE) has performed an asbestos survey of Building 4704 located at George C.

Marshall Space Flight Center, Marshall Space Flight Center, Alabama. The 4,660 square feet building was identified to have been originally constructed in 1952. A total of 30 samples were collected from the building.

The objective of the Asbestos Survey is to determine the location and quantity of asbestos-containing materials at the Property building.

GSE’s Scope of Work included:

Visual inspection and identification of suspect asbestos-containing materials (ACMs) in the Property building and collected a representative number of samples for analysis.

As part of this asbestos survey, GSE personnel collected samples of all suspect friable and suspect damaged non-friable building materials at the Property. The remaining suspect non-friable materials were not be sampled as part of this asbestos survey

Estimated quantities and locations of ACM.

Assessed the condition of the ACM identified.

Assigned a hazard rating to each type of ACM.

This report has been prepared for the use of George C. Marshall Space Flight Center. Our investigation was performed using the degree of care and skill ordinarily exercised under similar circumstances by professional consultants practicing in this or similar localities. No other warranty or guarantee, expressed or implied, is made as to the conclusions included in this report.

Task Order GSE 017 Page 2 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

The GSE, Inc. did not perform destructive sampling procedures at the site; therefore, regardless of the thoroughness of this survey, it is possible that suspected asbestos-containing materials (ACMs) might exist in the building beneath the floors, behind walls, within pipe chases, or in other inaccessible locations. If, during renovation or demolition activities, materials not addressed in this survey are discovered, these materials should be sampled and analyzed for asbestos content prior to disturbance.

Surveyed by:

John A Jackson

University of Alabama Safe State Program Accredited Inspector/Management Planner

Accreditation #AIN0908531941

Written by:

Manju Ramasamudra

University of Alabama Safe State Program Accredited Inspector/Management Planner

Accreditation #APL0308R5089

Task Order GSE 017 Page 3 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

2. Summary

GSE performed an Asbestos Survey and Hazard Assessment at Building 4704 in Marshall Space Flight Center, Alabama on January 20, 2009 and April 2, 2009. Sample collection was completed by licensed personnel – John A Jackson. The following report summarizes the independent conclusions representing GSE’ best professional judgment based on information and data available to us during the course of this survey. Factual information regarding operations, conditions, and tests data provided by the client, owner or their representative has been assumed to be correct and complete. Additionally, the conclusions presented are based on the conditions that existed on the date(s) of the assessment.

The 4,660 square feet building was identified to have been originally constructed in 1952. A total of 30 samples were collected from the building. No homogeneous materials were identified as asbestos-containing materials.

Task Order GSE 017 Page 4 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

2.1. Suspect ACMs

The following information is included for informational purposes:

A. The following suspect asbestos-containing materials were not sampled as part of this scope of work:

Suspect fibrous electrical cable covering (danger of electrocution) were not sampled.

These materials are not subject to regulation under NESHAP for demolition and renovation as long as they are in good condition and are not subject to sanding, grinding, cutting, or abrading.

Since ordinary demolition activities do not include sanding, grinding, cutting, and abrading, these materials may remain in place during building demolition, as long as they remain in good condition and are not friable.

If the material is in poor condition and is friable at the time of demolition or renovation, or if it will be subjected to sanding, grinding, cutting, or abrading, it should first be removed by a licensed asbestos removal contractor and disposed of as asbestos-containing waste.

When removing asphalt-roofing products, the material should be removed using a method that does not subject the material to sanding, cutting, grinding, or abrading (hand tools).

Asbestos-containing roofing may be disposed of as construction debris.

2.2. Recommendations

The following additional actions are recommended:

No further actions are recommended at this time.

Task Order GSE 017 Page 5 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

3. Survey Scope

This survey was conducted for the purpose of identifying asbestos-containing materials (ACM) throughout the building and to conduct a hazard assessment on existing ACM. The survey was non-destructive in nature and limited only to those areas that were readily accessible.

Specific areas to which access was limited by occupant request, unavailability of keys, or by site conditions included the following:

Behind the walls

Beneath the floors

Any suspect ACM not sampled as part of the assessment and if any additional suspect materials were to be identified behind walls and beneath the floors should be sampled prior to repair, renovation, or demolition activities.

Task Order GSE 017 Page 6 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

4. Limitations

GSE did not attempt to disassemble mechanical equipment, open pipe chases or assess materials within wall voids. Regardless of the thoroughness of a survey, the possibility exists that some areas containing asbestos were not identified, inaccessible or different from those at specific locations. The findings and opinions presented are relative to the dates of our site work and should not be relied upon to represent conditions at substantially later dates due to changes in the condition ACM may change over time, renovations and repairs.

This report is for the exclusive use of the client and its agents and use by any unauthorized parties in whole or in part, except as directed by legal jurisdiction, is at the sole risk of the user.

If this assessment includes reliance on work products and/or documents prepared by others, GSE has no responsibility for the accuracy of information contained therein.

Although this assessment has attempted to identify the presence or absence of ACM, potential sources of ACM may have escaped detection due to: (1) the scope of this assessment, (2) the inaccuracy of records, interviews, work products or documents made available to GSE for this report, (3) the presence of undetected or unreported renovations and repairs, (4) inaccessible areas, and/or (5) deliberate concealment of detrimental information.

Estimates presented in this report are based upon observations during the survey and owner-provided information. These reasonable estimates may be affected by unanticipated conditions potentially present in inaccessible or un-surveyed areas. GSE does not warrant or guarantee the quantity estimates. The use of such estimates shall be at the user's own risk and shall constitute a release and agreement to defend and indemnify GSE from and against any liability. If questions arise during the planning for renovation, demolition, or other construction activities, GSE should be notified to permit review of the data and present recommendations.

Interior of the following rooms were inaccessible during our Asbestos Survey on January 20, 2009 and April 2, 2009: None.

Task Order GSE 017 Page 7 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

5. Survey and Sample Collection Procedure

Based on United States Environmental Protection Agency (USEPA) guidance documents, GSE considered all material applications identified during the visual assessment were suspect ACM and sampled as described below.

Bulk samples were collected of any materials, which were suspected of containing asbestos with the exception of fire doors. Fire doors were not sampled because the damage caused by sampling would render these materials friable and may also void the fire rating. Since these materials were not sampled, they should be assumed to be asbestos containing, unless sampled and proven otherwise. Sampling of these assumed ACMs should be performed prior to any renovation or other activity that may cause a material disturbance.

Samples of the remaining suspect ACM were taken in accordance with USEPA recommendations.

The number and location of samples collected was based on the type of material, the manner of application, and the homogeneity of the ACM (similarity of color, texture, and type). Each sample was collected and placed into an individual sample container. The sample location was noted on the field survey form and assigned an individual identification number. This number was affixed to the sample container as the sample was collected. The survey form was also used to note the material type and general condition of the material. During the inspection, each suspect material's accessibility, location, and friability were recorded. This information was used to assess the potential hazard of the ACM and to prioritize response action recommendations.

The USEPA defines asbestos-containing materials (ACM) as those that contain greater than one percent asbestos. Friable materials are defined as those that can be crumbled or reduced to powder by hand pressure.

GSE utilized the “positive-stop” method of sample analysis. In this method, analysis is stopped on a group of samples once the first positive (e.g., greater than 1% asbestos) sample is analyzed.

According to the USEPA, if one sample of a homogenous material is identified to be asbestos containing, the entire material must be considered asbestos containing. By using the positive-stop method, GSE reduces the Client’s laboratory analysis cost by not analyzing the additional samples.

Samples collected were carried and submitted under Chain-of-Custody to Steve Moody Micro Services LLC, Farmers Branch, Texas for analysis of asbestos using USEPA Method 40 CFR, Chapter 1, Part 763, Subpart F, Appendix A, also known as Polarized Light Microscopy (PLM).

Steve Moody Micro Services LLC is certified by the National Voluntary Laboratory Accreditation Program (NVLAP) and licensed by the Department of State Health Services.

Task Order GSE 017 Page 8 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

6. Previous Survey / Plans Review

GSE was not provided with any previously conducted asbestos surveys of the Property. As-built/renovation-site plans and construction drawings were reviewed at the Facilities Department Drawing Room. Review of these documents did not identify building material specifications requiring the use of ACM. However, this does not preclude or prevent the potential use of ACM.

Task Order GSE 017 Page 9 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

7. Suspect ACM Materials Not Sampled

During the course of the property visit, GSE performed a preliminary review of interior, accessible areas of the subject building for the presence of suspect asbestos-containing materials (ACMs). This asbestos survey was conducted for overview purposes only; additional suspect materials may exist in concealed locations (behind walls and above ceilings, beneath the floors, within machinery, etc.). Also, not all suspect materials may have been sampled due to the condition or the location of the suspect materials. Destructive sampling of suspect ACMs was not performed. GSE will not be responsible for damaging materials or causing the materials to become friable. The USEPA defines asbestos-containing material as material containing greater than one percent asbestos. This review was not a pre-demolition/renovation survey or for regulatory submittal purposes.

Suspect and/or presumed ACMs were observed within the subject building during the property visit. These suspect and/or presumed ACMs that were not sampled as part of this asbestos survey are listed in the following table.

Sample Description Physical Condition

Friable Yes/No

Type of

ACM

Sample ID

4704Building Number

Caulking, On Exterior Wall Joints UPS4 NoM

Grout, On Exterior Wall Masonry UPS5 NoM

Wiring, Fibrous Electrical Cable Covering UPS6 NoM

Fire Doors, Fire Door Insulation UPS7 NoM

Mastic, Mirror Mastic UPS8 NoM

Task Order GSE 017 Page 10 of 25

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

8. Survey Sampling Results

The results of the Survey are presented in the tables on the following pages. The tables describe the entire suspect Asbestos-Containing Materials (ACMs) identified in the building and list respective sample numbers and laboratory results. Sample numbers presented in the tables correspond to the sample numbers on attached Laboratory Analysis Forms. Also presented in the tables is the estimated quantity and assessed friability for each suspect ACM. For each suspect material identified as ACM, the assessed hazard potential is presented along with GSE’ recommended response action. Hazard potential for each material application is based on the material condition and accessibility to the public and maintenance personnel.

Glossary of Items for the following Table

Type of Asbestos (1) CH = Chrysotile AM = Amosite CR = Crocidolite AN = Anthophyllite TR = Tremolite AC = Actinolite ND = No Asbestos Detected PC = Point Count Method

Type of ACM (2) M = Miscellaneous S = Surfacing TSI = Thermal Systems Insulation

Friability (3) F = Friable NF = Non Friable

Physical Condition (4) U = Good D = Damaged SD = Significantly Damaged

Potential for Disturbance (5) NPD = No Potential for Disturbance PD = Potential for Disturbance PSD = Potential for Significant Disturbance

Assessment Category (6) 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM 3 = Significantly damaged friable surfacing ACBM 4 = Damaged or significantly damaged friable miscellaneous ACBM 5 = ACBM with potential for damaged 6 = ACBM potential for significant damage 7 = Any remaining friable ACBM or friable suspected

ACBM

X = not applicable

Unit of Measurement SF = Square Feet

LF = Linear Feet

Sample Description

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 1

Pipe Insulation with White Mastic

Yes TSI Yes U XRoom: 100A Grid: F2-4

ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic

1 PD

Yes TSI Yes U XRoom: 103 Grid: C2-1

ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic

2 PD

Yes TSI Yes U XRoom: 105 Grid: WL2-1

ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic

3 PD

Homogeneous Area 2

Expansion Joint Material on Floor

Yes M No U XRoom: 103 Grid: F2-1

ND - Joint Material4 PD

Yes M No U XRoom: 100A Grid: F3-1

ND - Joint Material5 PD

Yes M No U XRoom: 104 Grid: F3-1

ND - Joint Material6 PD

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 3

Cove Base Gray and Associated Mastic

Yes M No U XRoom: 101 Grid: WE1-2

ND - Cove Base ND - Yellow Mastic

7 PD

Yes M No U XRoom: 101 Grid: WE1-3

ND - Cove Base ND - Yellow Mastic

8 PD

Yes M No U XRoom: 101 Grid: WR1-2

ND - Cove Base ND - Yellow Mastic

9 PD

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 4

Pipe Insulation with Gray Mastic

Yes TSI Yes U XRoom: 100 Grid: WE2-4

ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic

10 PD

Yes TSI Yes U XRoom: 100 Grid: WE2-4

ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic

11 PD

Yes TSI Yes U XRoom: 100 Grid: WE2-4

ND - Insulation ND - Tar Wrap ND - paper/ Foil Wrap ND - Mastic

12 PD

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 5

Gasket Around Window Glass

Yes M No U XRoom: 101 Grid: WF3-2

ND - Gasket13 PD

Yes M No U XRoom: 101 Grid: WF3-2

ND - Gasket14 PD

Yes M No U XRoom: 101 Grid: WF3-2

ND - Gasket15 PD

Homogeneous Area 6

Pipe Insulation with Silver Foil Cover

Yes TSI Yes U XRoom: 100 Grid: F3-3

ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint

16 PD

Yes TSI Yes U XRoom: 100 Grid: F3-3

ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint

17 PD

Yes TSI Yes U XRoom: 100 Grid: F3-3

ND - Insulation ND - Paper/ Foil Wrap ND - Silver Paint

18 PD

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 7

Coating Black on Floor Yes M No U XRoom: 100A Grid: F3-2

ND - Coating19 PD

Yes M No U XRoom: 100A Grid: F3-2

ND - Coating20 PD

Yes M No U XRoom: 100A Grid: F3-2

ND - Coating21 PD

Homogeneous Area 8

Wall Covering Wall Panels

Yes M Yes U XRoom: 105 Grid: WE2-2

ND - Wall Panel22 PD

Yes M Yes U XRoom: 105 Grid: WL2-3

ND - Wall Panel23 PD

Yes M Yes U XRoom: 105 Grid: WF2-4

ND - Wall Panel24 PD

Sample Location

Sample Analyzed

Yes/No

Estimated Quantity of

ACM

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

4704Building Number

Homogeneous Area 9

Pipe Insulation with Metal Bands

Yes TSI Yes D XRoom: 105 Grid: WE1-3

ND - Insulation ND - Paper/ Foil Wrap

25 PD

Yes TSI Yes D XRoom: 105 Grid: WR1-2

ND - Insulation ND - Paper/ Foil Wrap

26 PD

Yes TSI Yes D XRoom: 105 Grid: WE1-1

ND - Insulation ND - Paper/ Foil Wrap

27 PD

Homogeneous Area 10

Wallboard System with Texture and Joint Compound

Yes M Yes U XRoom: 100A Grid: WE2-4

ND - Drywall Material ND - Texture/ joint Compound

28 PD

Yes M Yes U XRoom: 100A Grid: WE1-4

ND - Drywall Material ND - Texture/ joint Compound

29 PD

Yes M Yes U XRoom: 100A Grid: WE2-1

ND - Drywall Material ND - Texture/ joint Compound

30 PD

1. CH = Chrysotile; AM = Amosite; CR = Crocidolite; AN = Anthophyllite; TR = Tremolite; AC = Actinolite; ND = No Asbestos Detected; or PC = Point Count Method

2. M = Miscellaneous; S = Surfacing; or TSI = Thermal Systems Insulation

3. F = Friable or NF = Non Friable

4. U = Good; D = Damaged; or SD = Significantly Damaged

5. NPD = No Potential for Disturbance; PD = Potential for Disturbance; or PSD = Potential for Significant Disturbance

6. 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 = Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM potential for significant damage, 7 = Any remaining friable ACBM or friable suspected ACBM, or X = not applicable

SF = Square Feet LF = Linear Feet

9. Appendices

Appendix A— Laboratory Results and Chain of Custody Appendix B— ACM Sample Location Drawings Appendix C— ACM Location Diagrams Appendix D— Photographs Appendix E— Certificates and Licenses

Appendix A

Laboratory Results

PLM Summary Report NVLAP Lab No. 102056

TDSHS License No. 30-0084

Client :

Project :

Project # :

Identification :

Test Method :

Great Southern Engineering

MSFC, Building 4704

GSE-017

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.

The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:

Steve Moody Micro Services, LLC

Lab Job No. :

Report Date :

09B-00859

01/20/2009

01/30/2009

2051 Valley View Lane

Farmers Branch, TX 75234 (Phone 972-241-8460)

01 Mastic (White) on Pipe Insulation None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - White Mastic

02 Mastic (White) on Pipe Insulation None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - White Mastic

03 Mastic (White) on Pipe Insulation None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - White Mastic

04 Expansion Joint Material None Detected - Joint Material

05 Expansion Joint Material None Detected - Joint Material

06 Expansion Joint Material None Detected - Joint Material

07 Cove Base (Gray) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

08 Cove Base (Gray) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

09 Cove Base (Gray) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

10 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation

None Detected - Tar Wrap

None Detected - Paper / Foil Wrap

None Detected - Mastic

11 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation

None Detected - Tar Wrap

None Detected - Paper / Foil Wrap

None Detected - Mastic

12 Mastic (Gray) on Pipe Insulation with Paper Cover None Detected - Insulation

None Detected - Tar Wrap

None Detected - Paper / Foil Wrap

None Detected - Mastic

TDSHS License No. 30-0084

Client :

Project :

Project # :

Identification :

Test Method :

Great Southern Engineering

MSFC, Building 4704

GSE-017

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.

The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:

Steve Moody Micro Services, LLC

Lab Job No. :

Report Date :

09B-00859

01/20/2009

01/30/2009

2051 Valley View Lane

Farmers Branch, TX 75234 (Phone 972-241-8460)

13 Gasket, Around Window Pane None Detected - Gasket

14 Gasket, Around Window Pane None Detected - Gasket

15 Gasket, Around Window Pane None Detected - Gasket

16 Pipe Insulation (Silver) None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - Silver Paint

17 Pipe Insulation (Silver) None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - Silver Paint

18 Pipe Insulation (Silver) None Detected - Insulation

None Detected - Paper / Foil Wrap

None Detected - Silver Paint

19 Coating (Black), on Floor None Detected - Coating

20 Coating (Black), on Floor None Detected - Coating

21 Coating (Black), on Floor None Detected - Coating

22 Wall Panels None Detected - Wall Panel

23 Wall Panels None Detected - Wall Panel

24 Wall Panels None Detected - Wall Panel

25 Pipe Insulation with Metal Bands None Detected - Insulation

None Detected - Paper / Foil Wrap

26 Pipe Insulation with Metal Bands None Detected - Insulation

None Detected - Paper / Foil Wrap

27 Pipe Insulation with Metal Bands None Detected - Insulation

None Detected - Paper / Foil Wrap

TDSHS License No. 30-0084

Client :

Project :

Project # :

Identification :

Test Method :

Great Southern Engineering

MSFC, Building 4704

GSE-017

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 1/28/2009, twenty seven (27) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.

The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:

Steve Moody Micro Services, LLC

Lab Job No. :

Report Date :

09B-00859

01/20/2009

01/30/2009

2051 Valley View Lane

Farmers Branch, TX 75234 (Phone 972-241-8460)

Kirsten TyeAnalyst(s):

Lab Director : Steve Moody Approved Signatory :

Thank you for choosing Steve Moody Micro Services

These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the

National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.

Lab Manager : Bruce Crabb Approved Signatory :

Steve Moody Micro Services, LLC PLM Detail Report NVLAP Lab No. 102056

TDSHS License No. 30-0084

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-00859

01/30/2009

Mineral Wool Fibers01 Insulation (Yellow) 96% 01/2895% KT

Resin Binders01 Insulation (Yellow) 96% 01/285% KT

Cellulose Fibers01 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT

Glass Wool Fibers01 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Metal Foil01 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Pigment / Binders01 White Mastic (Off-White) 2% 01/28100% KT

Mineral Wool Fibers02 Insulation (Yellow) 93% 01/2895% KT

Resin Binders02 Insulation (Yellow) 93% 01/285% KT

Cellulose Fibers02 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT

Glass Wool Fibers02 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Metal Foil02 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Polyethylene Fibers02 White Mastic (Off-White) 5% 01/285% KT

Calcite02 White Mastic (Off-White) 5% 01/2840% KT

Wollastonite02 White Mastic (Off-White) 5% 01/285% KT

Pigment / Binders02 White Mastic (Off-White) 5% 01/2850% KT

Mineral Wool Fibers03 Insulation (Yellow) 93% 01/2895% KT

Resin Binders03 Insulation (Yellow) 93% 01/285% KT

Cellulose Fibers03 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT

Glass Wool Fibers03 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Metal Foil03 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Polyethylene Fibers03 White Mastic (Off-White) 5% 01/285% KT

Calcite03 White Mastic (Off-White) 5% 01/2840% KT

Wollastonite03 White Mastic (Off-White) 5% 01/285% KT

Pigment / Binders03 White Mastic (Off-White) 5% 01/2850% KT

Wood Fibers04 Joint Material (Black) 100% 01/2885% KT

Tar Binders04 Joint Material (Black) 100% 01/2815% KT

Wood Fibers05 Joint Material (Black) 100% 01/2885% KT

Tar Binders05 Joint Material (Black) 100% 01/2815% KT

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-00859

01/30/2009

Wood Fibers06 Joint Material (Black) 1% 01/2885% KT

Tar Binders06 Joint Material (Black) 1% 01/2815% KT

Aggregate06 Concrete (Grey) 99% 01/2865% KT

Cement Binders06 Concrete (Grey) 99% 01/2835% KT

Calcite / Vinyl Binders07 Cove Base (Grey) 95% 01/28100% KT

Glue Binders07 Yellow Mastic (Yellow) 5% 01/28100% KT

Calcite / Vinyl Binders08 Cove Base (Tan) 90% 01/28100% KT

Glue Binders08 Yellow Mastic (Yellow) 10% 01/28100% KT

Calcite / Vinyl Binders09 Cove Base (Tan) 98% 01/28100% KT

Glue Binders09 Yellow Mastic (Yellow) 2% 01/28100% KT

Mineral Wool Fibers10 Insulation (Yellow) 78% 01/2895% KT

Resin Binders10 Insulation (Yellow) 78% 01/285% KT

Tar Binders10 Tar Wrap (Black) 20% 01/28100% KT

Cellulose Fibers10 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT

Glass Wool Fibers10 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Metal Foil10 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Pigment / Binders10 Mastic (Grey) <1% 01/28100% KT

Mineral Wool Fibers11 Insulation (Yellow) 95% 01/2895% KT

Resin Binders11 Insulation (Yellow) 95% 01/285% KT

Tar Binders11 Tar Wrap (Black) 1% 01/28100% KT

Cellulose Fibers11 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT

Glass Wool Fibers11 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Metal Foil11 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Polyethylene Fibers11 Mastic (Grey) 2% 01/285% KT

Calcite11 Mastic (Grey) 2% 01/2840% KT

Wollastonite11 Mastic (Grey) 2% 01/285% KT

Pigment / Binders11 Mastic (Grey) 2% 01/2850% KT

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-00859

01/30/2009

Mineral Wool Fibers12 Insulation (Yellow) 76% 01/2895% KT

Resin Binders12 Insulation (Yellow) 76% 01/285% KT

Tar Binders12 Tar Wrap (Black) 20% 01/28100% KT

Cellulose Fibers12 Paper / Foil Wrap (Tan / Silver) 2% 01/2860% KT

Glass Wool Fibers12 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Metal Foil12 Paper / Foil Wrap (Tan / Silver) 2% 01/2820% KT

Pigment / Binders12 Mastic (Grey) 2% 01/28100% KT

Vinyl Binders13 Gasket (Black) 100% 01/28100% KT

Vinyl Binders14 Gasket (Black) 100% 01/28100% KT

Vinyl Binders15 Gasket (Black) 100% 01/28100% KT

Mineral Wool Fibers16 Insulation (Yellow) 97% 01/2895% KT

Resin Binders16 Insulation (Yellow) 97% 01/285% KT

Cellulose Fibers16 Paper / Foil Wrap (White / Silver) 2% 01/2860% KT

Glass Wool Fibers16 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Metal Foil16 Paper / Foil Wrap (White / Silver) 2% 01/2820% KT

Pigment / Binders16 Silver Paint (Silver) 1% 01/28100% KT

Mineral Wool Fibers17 Insulation (Yellow) 89% 01/2895% KT

Resin Binders17 Insulation (Yellow) 89% 01/285% KT

Cellulose Fibers17 Paper / Foil Wrap (White / Silver) 10% 01/2860% KT

Glass Wool Fibers17 Paper / Foil Wrap (White / Silver) 10% 01/2820% KT

Metal Foil17 Paper / Foil Wrap (White / Silver) 10% 01/2820% KT

Pigment / Binders17 Silver Paint (Silver) 1% 01/28100% KT

Mineral Wool Fibers18 Insulation (Yellow) 45% 01/2895% KT

Resin Binders18 Insulation (Yellow) 45% 01/285% KT

Cellulose Fibers18 Paper / Foil Wrap (White / Silver) 50% 01/2860% KT

Glass Wool Fibers18 Paper / Foil Wrap (White / Silver) 50% 01/2820% KT

Metal Foil18 Paper / Foil Wrap (White / Silver) 50% 01/2820% KT

Pigment / Binders18 Silver Paint (Silver) 5% 01/28100% KT

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-00859

01/30/2009

Cellulose Fibers19 Coating (Black, Dirty) 100% 01/283% KT

Calcite19 Coating (Black, Dirty) 100% 01/2840% KT

Binders / Fillers19 Coating (Black, Dirty) 100% 01/2857% KT

Cellulose Fibers20 Coating (Black, Dirty) 100% 01/283% KT

Calcite20 Coating (Black, Dirty) 100% 01/2840% KT

Binders / Fillers20 Coating (Black, Dirty) 100% 01/2857% KT

Cellulose Fibers21 Coating (Black, Dirty) 100% 01/283% KT

Calcite21 Coating (Black, Dirty) 100% 01/2840% KT

Binders / Fillers21 Coating (Black, Dirty) 100% 01/2857% KT

Cellulose Fibers22 Wall Panel (Light Tan) 100% 01/2875% KT

Perlite22 Wall Panel (Light Tan) 100% 01/2820% KT

Tar Binders22 Wall Panel (Light Tan) 100% 01/285% KT

Cellulose Fibers23 Wall Panel (Light Tan) 100% 01/2875% KT

Perlite23 Wall Panel (Light Tan) 100% 01/2820% KT

Tar Binders23 Wall Panel (Light Tan) 100% 01/285% KT

Cellulose Fibers24 Wall Panel (Light Tan) 100% 01/2875% KT

Perlite24 Wall Panel (Light Tan) 100% 01/2820% KT

Tar Binders24 Wall Panel (Light Tan) 100% 01/285% KT

Mineral Wool Fibers25 Insulation (Yellow) 98% 01/2895% KT

Resin Binders25 Insulation (Yellow) 98% 01/285% KT

Cellulose Fibers25 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2860% KT

Glass Wool Fibers25 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2820% KT

Metal Foil25 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2820% KT

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-00859

01/30/2009

Mineral Wool Fibers26 Insulation (Yellow) 98% 01/2895% KT

Resin Binders26 Insulation (Yellow) 98% 01/285% KT

Cellulose Fibers26 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2860% KT

Glass Wool Fibers26 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2820% KT

Metal Foil26 Paper / Foil Wrap (White/Silver, Dirty)

2% 01/2820% KT

Mineral Wool Fibers27 Insulation (Yellow) 95% 01/2895% KT

Resin Binders27 Insulation (Yellow) 95% 01/285% KT

Cellulose Fibers27 Paper / Foil Wrap (White/Silver, Dirty)

5% 01/2860% KT

Glass Wool Fibers27 Paper / Foil Wrap (White/Silver, Dirty)

5% 01/2820% KT

Metal Foil27 Paper / Foil Wrap (White/Silver, Dirty)

5% 01/2820% KT

TDSHS License No. 30-0084

Client :

Project :

Project # :

Identification :

Test Method :

Great Southern Engineering

MSFC, Building 4704

GSE-017

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 4/7/2009, three (3) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Steve Moody Micro Services, LLC

Lab Job No. :

Report Date :

09B-03790

04/02/2009

04/07/2009

2051 Valley View Lane

Farmers Branch, TX 75234 (Phone 972-241-8460)

28 Wall System None Detected - Drywall Material

None Detected - Texture / Joint Cmpd

29 Wall System None Detected - Drywall Material

None Detected - Texture / Joint Cmpd

30 Wall System None Detected - Drywall Material

None Detected - Texture / Joint Cmpd

Steve MoodyAnalyst(s):

Lab Director : Steve Moody Approved Signatory :

Thank you for choosing Steve Moody Micro Services

These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the

National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.

Lab Manager : Bruce Crabb Approved Signatory :

Project # : GSE-017

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report 2051 Valley View Lane

Farmers Branch, TX 75234

Client :

Project :

Great Southern Engineering

MSFC, Building 4704

Lab Job No. :

Report Date :

09B-03790

04/07/2009

Cellulose Fibers28 Drywall Material (White) 50% 04/072% SM

Gypsum / Binders28 Drywall Material (White) 50% 04/0798% SM

Cellulose Fibers28 DW Paper Facing (Tan) 10% 04/07100% SM

Calcite / Talc / Binders28 Texture / Joint Cmpd (White) 40% 04/07100% SM

Cellulose Fibers29 Drywall Material (White) 50% 04/072% SM

Gypsum / Binders29 Drywall Material (White) 50% 04/0798% SM

Cellulose Fibers29 DW Paper Facing (Tan) 10% 04/07100% SM

Calcite / Talc / Binders29 Texture / Joint Cmpd (White) 40% 04/07100% SM

Cellulose Fibers30 Drywall Material (White) 50% 04/072% SM

Gypsum / Binders30 Drywall Material (White) 50% 04/0798% SM

Cellulose Fibers30 DW Paper Facing (Tan) 10% 04/07100% SM

Calcite / Talc / Binders30 Texture / Joint Cmpd (White) 40% 04/07100% SM

Appendix B

ACM Sample Location Drawings

First Floor Building 4704

Marshall Space Flight Center Marshall Space Flight Center, AL

Task Order #GSE-017

23322

19, 20, 21

13, 14, 8 7 10, 11, 12

16, 17, 18

28, Appendix C

ACM Location Diagrams

NOT APPLICABLE

Appendix D

Photographs

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

PHOTO 1. View of the building PHOTO 2. Interior view of the building

PHOTO 3. Interior view of the building PHOTO 4. Pipe insulation with white mastic

PHOTO 5. Expansion joint material on floor PHOTO 6. Gray cove base and associated mastic

Building 4704, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama

PHOTO 7. Pipe insulation with gray mastic and paper cover PHOTO 8. Gasket around window glass

PHOTO 9. Pipe insulation with silver foil cover PHOTO 10. Black coating on concrete floor

PHOTO 11. Wall panels PHOTO 12. Pipe insulation with metal bands

Appendix E

License and Certifications

1. Introduction
2. Summary
2.1. Suspect ACMs
2.2. Recommendations
3. Survey Scope
4. Limitations
5. Survey and Sample Collection Procedure
6. Previous Survey / Plans Review
7. Suspect ACM Materials Not Sampled
8. Survey Sampling Results
9. Appendices
Appendix A Laboratory Results
Appendix B ACM Sample Location Drawings
Appendix C ACM Location Diagrams
Appendix D Photographs
Appendix E License and Certifications

File details come from the government source that posted it.