These documents are plumbing design plans for the Collier County Public Utilities Raw Water Booster Pump Station Improvements project located in Estero, Florida. The project involves demolition and renovation of an existing pump building's plumbing infrastructure, including removal of existing water and sanitary piping, installation of new domestic cold and hot water lines, and modifications to existing plumbing systems. The design documents, prepared by Tetra Tech and marked as a 100% submittal, include detailed plans for pressure and sanitary piping, plumbing demolition, legends, abbreviations, notes, and technical details covering pipe routing, equipment placement, and compliance with Florida Building Codes (8th Edition, 2023).
The project specifications emphasize contractor responsibilities for field verification of existing conditions, coordination with other trades, restoration of walls and slabs, and compliance with manufacturer recommendations and applicable codes. The electric water heater schedule indicates a 28-gallon Rheem model will be installed, and the design includes provisions for connecting to a potable well and reverse osmosis system. The plans cover multiple building spaces including a pump room, generator room, electrical room, and office area, with specific attention to proper pipe sizing, routing, and installation techniques. The design integrates requirements for pipe supports, sleeves, floor drains, and other technical details to ensure a comprehensive and code-compliant plumbing system upgrade.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIXTURE TAGSK - #
LIMIT OF DEMOLITION
CONNECT TO EXISTING
KEYED NOTE
PIPE SIZE AND SYSTEM TAG3/4"ø HW
PLUMBING LEGEND PLUMBING GENERAL NOTESPLUMBING ABBREVIATIONS
SANITARY SEWER PIPING
COLD WATER PIPING
HOT WATER PIPING
HOT WATER RECIRCULATION PIPING
VENT PIPING
VENT THROUGH ROOF
CLEAN OUT, EXPOSED
CLEAN OUT
DOUBLE YARD CLEANOUT
WATER METER
BACK FLOW PREVENTER
THERMOSTATIC MIXING VALVE
TRAP PRIMER LINE
FLOOR DRAIN
HOSE BIBB W/INTEGRAL VACUUM BREAKER
(INTERIOR SURFACE)
BFP
TPL
HB
GAS COCK/GAS STOP
THERMOMETER
SOLENOID VALVE
BALANCING VALVE
RELIEF VALVE
WATER HAMMER ARRESTER/SHOCK ABSORBER
W
STORM PIPING
STRAINER (BLOW-OFF)
M GAS METER
WALL HYDRANT W/INTEGRAL VACUUM BREAKER
(EXTERIOR SURFACE)
WH
HIDDEN / UNDERGROUND PIPING
ANCHOR, INTERMEDIATE
BUTTERFLY VALVE
PIPE CAP
PIPE CONNECTION, BOTTOM
PIPE CONNECTION, TOP
PIPE ELBOW, TURNED UP
PIPE ELBOW, TURNED DOWN
PIPE TEE
STRAINER VALVE
GATE VALVE
CHECK VALVE
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
PUMP (SCHEMATIC)
UNION
NOTES:
1. THIS LEGEND IS FOR REFERENCE ONLY.
2. ALL SYMBOLS WITHIN THIS LEGEND MAY NOT APPLY TO THIS PROJECT.
AREA OUT OF SCOPE
AREA OF DEMOLITION
Ø DIAMETER
GENERAL NOTES
EQUIPMENT NOTES
APPLICABLE CODES
PRESSURE REGULATOR
CHKD:
DRWN:
PROJ:
DESN:
w w w .t e tr a te c h
.c o m
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p y ri g h t:
T e tr a T e c h
/9
/2
:4
:5
P
M A u to d e s k D o c s /2
-0
-2
C o lli e r
C o
B ri d g e C ra n e A d d /M
-2
C
C B
C A
R
W B
.r v t
200-08486-24001
FFA
RZN
KPK
P-001
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
IM
P R
O V
E M
E N
T S
P L
U M
B
IN
G A
B B
R E
V
IA
T
IO
N S
L
E G
E N
D
N
O T
E S
E N
G
IN
E E
R
IN
G B
U S
IN
E
S S
N O
C
H E
V R
O L E
T W
A Y
S T
E
E S
T E
R O
F
L O
R
ID
A
100% SUBMITTAL
P H
(2
-1
(D) DEMOLITION
(E) EXISTING
(R) RELOCATED
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
APPROX APPROXIMATE
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
CA COMPRESSED AIR
CAP CAPACITY
CO CLEAN OUT
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
D DRAIN
DCW DOMESTIC COLD WATER
DEG DEGREES
DEMO DEMOLITION
DIA DIAMETER
DN DOWN
DS DOWNSPOUT
DWG DRAWING
EA EACH
EEW EMERGENCY EYE/FACE WASH
ENT ENTERING
ESS EMERGENCY SAFETY SHOWER
ET EXPANSION TANK
F FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FH FIRE HYDRANT
FM FLOW METER
FPH FREEZE PROOF HYDRANT
FPM FEET PER MINUTE
GAL GALLONS
GD GARBAGE DISPOSAL
GM GAS METER
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
HB HOSE BIBB
HD HEAD
HO HUB OUTLET
HP HORSEPOWER
HW HOT WATER
HWR HOT WATER RETURN
ID INSIDE DIAMETER/DIMENSION
IE INVERT ELEVATION
IMVB ICE MAKER VALVE BOX
IN INCH
IW INDUSTRIAL WASTE
IWH INSTANTANEOUS WATER HEATER
LAV LAVATORY
M METER
MAX MAXIMUM
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
N/A NOT APPLICABLE
NG NATURAL GAS
NPW NON-POTABLE WATER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
PCV PRESSURE CONTROL VALVE
PD PRESSURE DROP
PG PRESSURE GAUGE
1. THESE GENERAL NOTES APPLY TO ALL SHEETS. REFER TO INDIVIDUAL SHEETS FOR SHEET NOTES.
2. CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE
AND GENERAL ARRANGEMENT ONLY. DO NOT SCALE FOR MATERIAL QUANTITIES. ALL SCALING
SHOULD BE REFERENCED TO ARCHITECTURAL PLANS ONLY.
3. ALL EQUIPMENT AND PIPING SHALL BE INSTALLED IN COMPLIANCE WITH THE CODES LISTED IN THE
TABLE ABOVE.
4. ALL INTERIOR FLOOR DRAINS AND OPEN RECEPTACLES WITH TRAPS SHALL BE PROTECTED BY A
TRAP GUARD.
5. WATER LINES SHALL NOT BE ROUTED ABOVE ANY ELECTRICAL ROOMS, ELECTRICAL PANELS, OR
TELEPHONE ROOMS.
6. CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO MINIMIZE SPATIAL
CONFLICTS.
7. PROVIDE ACCESS PANELS WITH SQUARE HINGED, LOCKING DOORS FOR ALL CONCEALED VALVES, SHOCK ABSORBERS AND TRAP PRIMERS.
8. CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS AND DIMENSIONS BEFORE CONSTRUCTION
BEGINS.
9. PROVIDE ISOLATION VALVES AT ALL PIPE CONNECTIONS TO EQUIPMENT.
10. PROVIDE WALL PIPE PENETRATIONS AS REQUIRED WHERE PIPE ENTERS BUILDING. SLEEVE AND
SEAL OPENING WITH CAULKING AND ESCUTCHEON FOR A WATER-TIGHT INSTALLATION.
1. INSTALL ALL PLUMBING EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
2. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF
ONE MANUFACTURER SHALL BE USED.
3. IDENTIFY ALL NEW PLUMBING EQUIPMENT WITH NAMEPLATES PERMANENTLY ENGRAVED WITH 1/2 INCH HIGH WHITE LETTERS ON A BLACK BACKGROUND. IDENTIFY EQUIPMENT WITH SYMBOLS SHOWN ON THE
PLANS AND AREA SERVED DESCRIPTION.
4. PROVIDE FLEXIBLE PIPING CONNECTIONS TO ALL OPERATING EQUIPMENT, UNO.
5. ALL PLUMBING EQUIPMENT PADS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL
CONTRACTOR.
6. EQUIPMENT AND APPLIANCES SHALL BE ACCESSIBLE FOR SERVICE, INSPECTION, REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION. SUFFICIENT CLEARANCE SHALL BE MAINTAINED TO PERMIT CLEANING, REPLACEMENT OF PARTS, CONTROLS AND LUBRICATION OF MOVING
PARTS.
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
PW POTABLE WATER
R RADIUS
RD ROOF DRAIN
RP RECIRCULATION PUMP
RPBP REDUCED PRESSURE BACKFLOW PREVENTER
RPM REVOLUTIONS PER MINUTE
SAN SANITARY SEWER PIPING
SK SINK
SP SUMP PUMP
SPEC SPECIFICATION
STD STANDARD
STO STORM
SW SERVICE WATER
TBD TO BE DETERMINED
TCV TEMPERING VALVE
TD TRENCH DRAIN
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TW TEPID WATER
TYP TYPICAL
UR URINAL
V VENT
VIF VERIFY IN FIELD
VS VENT STACK
VTR VENT THRU ROOF
WB WASHER BOX
WC WATER CLOSET
WCO WALL CLEAN OUT
WG WATER GAUGE
WPD WATER PRESSURE DROP
NOTE: ALL APPLICABLE BUILDING CODES AND STANDARDS NOT SPECIFIED HEREIN.
APPLICABLE CODES AND STANDARDS
FLORIDA BUILDING CODE, 8TH EDITION
FLORIDA BUILDING CODE, EXISTING BLDG, 8TH EDITION
FLORIDA BUILDING CODE, PLUMBING, 8TH EDITION
FLORIDA BUILDING CODE, HURRICANE TESTING, 8TH EDITION
FLORIDA BUILDING CODE, ENERGY CONSERVATION, 8TH EDITION
FBC 2023
FLORIDA BUILDING CODE, MECHANICAL, 8TH EDITION
FBC-EB 2023
FBC-M 2023
FBC-P 2023
FBC-HT 2023
FBC-EC 2023
FLORIDA FIRE PREVENTION CODE, 8TH EDITION FFPC 2023
NATIONAL ELECTRIC CODE NEC 2020
OCCUPATIONAL SAFETY AND HEALTH ACT OSHA
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
FAISAL.ALTWAL
G:\PE Stamps\Orders\2023\104089 Twal FL-Eng\104089 Twal FL-Eng FINAL Model (1)
EX-SINK
EX-LAV
P-101
P-101
P-101
P-101
N
CHKD:
DRWN:
PROJ:
DESN:
w w w .t e tr a te c h
.c o m
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p y ri g h t:
T e tr a T e c h
0' 8' 16'8'
SCALE: 1/8" = 1'-0"
/9
/2
:4
:5
P
M A u to d e s k D o c s /2
-0
-2
C o lli e r
C o
B ri d g e C ra n e A d d /M
-2
C
C B
C A
R
W B
.r v t
200-08486-24001
FFA
RZN
KPK
P-101
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
IM
P R
O V
E M
E N
T S
E X
IS
T
IN
G
P U
M P
B U
IL
D
IN
G
P L
U M
B
IN
G D
E M
O L
IT
IO
N P
L A
N
E N
G
IN
E E
R
IN
G B
U S
IN
E
S S
N O
C
H E
V R
O L E
T W
A Y
S T
E
E S
T E
R O
F
L O
R
ID
A
100% SUBMITTAL
P H
(2
-1
SCALE: 1/8" = 1'-0"P-101
1 PLUMBING DEMOLITION PLAN
KEYED NOTES:
1. REMOVE AND DISPOSE OF EXISTING 3/4" RAW WATER
PIPING, INCLUDING ALL ASSOCIATED HANGERS AND
SUPPORTS, UP TO THE POINTS INDICATED ON THE
DRAWING. REMAINING PIPING TO BE CAPPED.
GENERAL NOTES:
1. EXISTING SYSTEMS AND INFORMATION SHOWN ON
THESE PLANS WERE DEVELOPED USING EXISTING
BUILDING DRAWINGS. CONTRACTOR SHALL VERIFY AT
SITE ALL EXISTING SYSTEMS. REMOVE ALL PORTIONS OF
PIPING SYSTEMS BEING DEMOLISHED. TERMINATE
EXISTING SYSTEMS IN A MANNER THAT WILL NOT
CONFLICT WITH NEW WORK. CLOSELY COORDINATE NEW
WORK WITH EXISTING SYSTEMS. PROVIDE OFFSETS IN
EXISTING AND NEW SYSTEMS AS REQUIRED TO AVOID
CONFLICTS.
2. COORDINATE DEMOLITION AND DISPOSAL WITH THE
OWNER.
3. CONTRACTOR IS RESPONSIBLE TO REMOVE AND DELIVER
EXISTING EQUIPMENT, MATERIALS, ETC., BEING
DEMOLISHED TO THE OWNER WHERE SO DIRECTED.
SHOULD THE OWNER DECIDE NOT TO KEEP THE
EXISTING EQUIPMENT, MATERIALS ETC., BEING
DEMOLISHED, IT BECOMES THE PROPERTY OF THE
CONTRACTOR AND SHALL BE REMOVED FROM THE SITE
AND BE DISPOSED OF IN A LEGAL MANNER.
4. EXISTING PLUMBING EQUIPMENT, ACCESSORIES,
SUPPORTS, CONTROLS, AND OTHER COMPONENTS
SHALL BE DEMOLISHED AND REMOVED FROM SITE AS
SHOWN.
5. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY
LOCATIONS, DIMENSIONS, AND CONFIGURATION OF ALL
EXISTING EQUIPMENT, HANGERS, SUPPORTS, ANCHORS,
CONTROLS, ETC.
6. CONTRACTOR IS RESPONSIBLE FOR PATCHING ALL
PENETRATIONS CREATED BY REMOVAL OF EQUIPMENT,
PIPING, ETC. TO MATCH EXISTING. REPAIR ADJACENT
CONSTRUCTION AND FINISHES DAMAGED DURING
DEMOLITION AND EXTENSION WORK. PATCH TO MATCH
ORIGINAL CONSTRUCTION. VERIFY ALTERNATIVE OR
SPECIAL REPAIR METHODS WITH ARCHITECT/ENGINEER
BEFORE PROCEEDING WITH DEMOLITION.
SCALE: NTSP-101
2 DEMO PHOTO
SCALE: NTSP-101
3 DEMO PHOTO
SCALE: NTSP-101
4 DEMO PHOTO
SCALE: NTSP-101
5 DEMO PHOTO
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
LEGEND:
NOT IN PROJECT SCOPE
P-201
P-201
"ø
D C
W
BATHROOM
OFFICE
EX SEPTIC FIELD
"ø
D C
W
1"ø DCW
"ø
D C
W
PUMP ROOM
GENERATOR ROOM
ELECTRICAL
ROOM
A B
4"ø EX-SAN
EX-WATER
CLOSET
1"ø DCW
1"ø DCW
EB-EWH-1
1"ø DCW
1"ø HW
1"ø DCW
B
EX-CMU WALLS
EX-CONCRETE
SLAB
EX-CMU WALLS
1"ø HW
1"ø DCW
EX-SERVICE
SINK
EX-WATER
CLOSET
EB-FD-1
"ø
S A
N
2"ø V
2"ø SAN
2"ø SAN
4"ø EX-SAN
3"ø EX-V
2"ø V
B
EX-CMU WALLS
EX-CONCRETE
SLAB
EX-CMU WALLS
EX-SERVICE
SINK
FD-1
N
CHKD:
DRWN:
PROJ:
DESN:
w w w .t e tr a te c h
.c o m
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p y ri g h t:
T e tr a T e c h
0' 8' 16'8'
SCALE: 1/8" = 1'-0"
0' 4' 8'4'
SCALE: 1/4" = 1'-0"
/9
/2
:4
:5
P
M A u to d e s k D o c s /2
-0
-2
C o lli e r
C o
B ri d g e C ra n e A d d /M
-2
C
C B
C A
R
W B
.r v t
200-08486-24001
FFA
RZN
KPK
P-201
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
IM
P R
O V
E M
E N
T S
E X
IS
T
IN
G
P U
M P
B U
IL
D
IN
G
P L
U M
B
IN
G P
R E
S S
U R
E
S A
N
IT
A R
Y P
IP
IN
G P
L A
N
E N
G
IN
E E
R
IN
G B
U S
IN
E
S S
N O
C
H E
V R
O L E
T W
A Y
S T
E
E S
T E
R O
F
L O
R
ID
A
100% SUBMITTAL
P H
(2
-1
# KEYED NOTES:
1. CONNECT 1" DCW PIPING TO THE TURNKEY POTABLE
WELL AND RO SYSTEM. REFER TO CIVIL DRAWINGS FOR
ADDITIONAL DETAILS.
2. POSITION UNIT AT MANUFACTURER'S RECOMMENDED
CLEARANCE.
3. CLEANOUT IS DESIGNED TO BE BUILT INTO SIDEWALL OF
SANITARY PIPE RISER.
4. SLOPE NEW CONCRETE SLAB TO DRAIN.
5. WALL MOUNTED ADA SHOWER SEAT. REFER TO
ARCHITECTURAL DRAWINGS FOR ADDITIONAL DETAILS.
6. PROVIDE SHOWER UNIT ZURN Z7301-SS-MT-DV2P-HW-H9-
S9 OR APPROVED EQUAL.
7. VIF 4" EXISTING SANITARY SEWER LINE TO EXISTING
SEPTIC FIELD.
SCALE: 1/8" = 1'-0"P-201
1 OVERALL PLUMBING PLAN
SCALE: 1/4" = 1'-0"P-201
2 PLUMBING ENLARGED PRESSURE PIPING PLAN
SCALE: 1/4" = 1'-0"P-201
3 PLUMBING ENLARGED SANITARY PIPING PLAN
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
GENERAL NOTES:
1. CONNECTION TO EQUIPMENT AND FIXTURES SHALL BE
VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
2. DIMENSIONS SHALL BE FIELD VERIFIED AND
COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER
DISCIPLINES INVOLVED. FIELD MODIFICATIONS SUCH AS
OFFSETS IN PIPING DUE TO OBSTRUCTIONS OR
INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL
COST.
3. CONTRACTOR IS RESPONSIBLE FOR RESTORATION OF
WALL, SLAB AND PATCHING OF ALL PENETRATIONS
CREATED DURING PLUMBING INFRASTRUCTURE
INSTALLATION. REPAIR ADJACENT CONSTRUCTION AND
FINISHES DURING INSTALLATION. PATCH TO MATCH
ORIGINAL CONSTRUCTION.
CONCEALED PIPING
TERMINATE SLEEVE FLUSH
WITH FINISHED WALL
SURFACES
SEAL OR CAULK
SLEEVES THRU FIRE
WALLS IN A SMOKE-
TIGHT MANNER
FINISHED WALL
SURFACE
FINISHED ESCUTCHEON
PLATE FLUSH AGAINST
WALL AND OF SIZE TO
COMPLETELY COVER
OPENING
STANDARD WEIGHT STEEL
PIPE SLEEVE OF SIZE
TO PASS PIPE AND
INSULATION
PIPING EXPOSED
TO VIEW
NOTE:
PROVIDE UL RATED ASSEMBLIES
FOR ALL WALLS WITH FIRE RATINGS.
PIPE AND INSULATION
TO BE CENTERED IN
SLEEVE - DO NOT
SUPPORT PIPE FROM
SLEEVE
3" MIN CLEARANCE EACH END
(TYP)
3" MIN WALL TO WALL SEPARATION
FOR PIPE < 4"
6" MIN WALL TO WALL
SEPARATION FOR PIPE 5" THRU 8"
LOAD BEARING PIPE CLAMP
(TYP)
STOP LOCK
ASSEMBLY IF REQUIRED BASED
ON MFR RECOMMENDATIONS (TYP)
CHANNEL FRAMING
NOTES:
1. SEE DRAWINGS FOR TYPE, SIZE, AND QUANTITY OF SUPPORTED PIPES.
2. ALL FRAMING AND PIPE SUPPORT MATERIALS SHALL 316 SST (UNISTRUT
OR EQUAL FOR EXTERIOR).
CONCRETE
WALL, THRENCH
OR SLAB
5/8" 316 SST
EXPANSION
ANCHOR,
COUNTERSUNK,
FLATHEAD (TYP)
FLOOR DRAIN W/ TRAP SEAL
FINISHED FLOOR
PRECAST
NON-SHRINK GROUT
"P" TRAP
SEAMLESS 4# LEAD
FLASHING WITH STEEL
REINFORCING BOOT AND 6"
(MINIMUM) SKIRT
CAST IRON CAULK TYPE
COUNTERFLASHING
RING
NOTES:
1. VENT SHALL EXTEND THROUGH FLASHING AND TERMINATE VERTICALLY NOT LESS THAN SIX
INCHES ABOVE THE ROOF NOR LESS THAN ONE FOOT FROM A VERTICAL
SURFACE.
2. VENT SHALL TERMINATE NOT LESS THAN TEN FEET FROM, OR NOT LESS THAN THREE
FEET ABOVE AN OPERABLE WINDOW, DOOR, OPENING, AIR INTAKE, OR
ROOFING
ALLEN HEAD SET SCREW
EPOXY SEALANT
ROOF
VENT PIPE
KEYED NOTES
6 5
28"+/-
28"+/-
2"x2"x1/4" ANGLE FRAME, WELD
ALL JOINTS, GRIND ALL JOINTS
AND SHARP EDGES, PRIME COAT
FOR FIELD PAINTING
3/4" PLYWOOD BASE
(ANCHOR ALL SIDES)
WATER HEATER
EXPANSION TANK
VACUUM RELIEF VALVE
SHUTOFF VALVE
T&P RELIEF VALVE
GROUND JOINT UNION
DRAIN PAN
HOT WATER LINE
COLD WATER LINE
TERMINATE T&P RELIEF @
DRAIN PAN WITH 2" AIR GAP
ROUTE DRAIN PAN TO
JANITORS SINK WITH 2" AIR GAP
MOUNTING PLATFORM
CHKD:
DRWN:
PROJ:
DESN:
w w w .t e tr a te c h
.c o m
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p y ri g h t:
T e tr a T e c h
/9
/2
:4
:5
P
M A u to d e s k D o c s /2
-0
-2
C o lli e r
C o
B ri d g e C ra n e A d d /M
-2
C
C B
C A
R
W B
.r v t
200-08486-24001
FFA
RZN
KPK
P-501
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
IM
P R
O V
E M
E N
T S
E X
IS
T
IN
G
P U
M P
B U
IL
D
IN
G
P L
U M
B
IN
G D
E T
A
IL
S
E N
G
IN
E E
R
IN
G B
U S
IN
E
S S
N O
C
H E
V R
O L E
T W
A Y
S T
E
E S
T E
R O
F
L O
R
ID
A
100% SUBMITTAL
P H
(2
-1
SCALE: NTS
2 PIPE SLEEVES THRU INTERIOR WALLS DETAIL
SCALE: NTS
3 PIPE SUPPORT DETAIL
SCALE: NTS
5 FLOOR DRAIN DETAIL
SCALE: NTS
4 VENT THROUGH FLAT ROOF
SCALE: NTS
1 ELECTRIC WATER HEATER DETAIL
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1"ø DCW
1"ø DCW
1"ø DCW
1"ø DCW
1"ø DCW
"ø
D C
W1 "ø
H W
"ø
D C
W
1"ø DCW
1"ø HW
EB-EWH-1
EX-WATER
CLOSET
1"ø DCW
1"ø DCW
"ø
E X
-V
"ø
V
"ø
V
FD-1
2"ø SAN
2"ø SAN
4"ø EX-SAN
4"ø EX-SAN
4"ø EX-SAN 2"ø SAN
EX-WATER
CLOSET
EB-FD-1
EX-SERVICE
SINK
CHKD:
DRWN:
PROJ:
DESN:
w w w .t e tr a te c h
.c o m
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p y ri g h t:
T e tr a T e c h
/9
/2
:4
:5
P
M A u to d e s k D o c s /2
-0
-2
C o lli e r
C o
B ri d g e C ra n e A d d /M
-2
C
C B
C A
R
W B
.r v t
200-08486-24001
FFA
RZN
KPK
P-601
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
IM
P R
O V
E M
E N
T S
E X
IS
T
IN
G
P U
M P
B U
IL
D
IN
G
P L
U M
B
IN
G S
C H
E D
U L
E S
R
IS
E
R D
IA
G
R A
M S
E N
G
IN
E E
R
IN
G B
U S
IN
E
S S
N O
C
H E
V R
O L E
T W
A Y
S T
E
E S
T E
R O
F
L O
R
ID
A
100% SUBMITTAL
P H
(2
-1
EXISTING PUMP BUILDING ELECTRIC WATER HEATER SCHEDULE
MARK DESCRIPTION
MINIMUM STORAGE
CAPACITY
(GAL.)
MINIMUM
RECOVERY
(GPH @140F)
FUEL
ELECTRICAL
MOCP
ELECTRICAL
MANUFACTURER MODELTOTAL
KW
VOLTS/PHASE
NUMBER OF
ELEMENTS
EB-EWH-1 ELECTRIC WATER HEATER 28 25 ELECTRIC 4.0 240 / 1 25 1 RHEEM XE28S06SB55U1
EXISTING PUMP BUILDING DRAIN & CLEANOUT SCHEDULE
MARK DESCRIPTION
OUTLET
TYPE
SIZE (IN) STRAINER
REMARKS
WASTE VENT MATERIAL TYPE STYLE
EB-FD-1 FLOOR DRAIN CAULK 2 1 1/2 STAINLESS STEEL ROUND ADJUSTABLE STRAINER HEAD PROVIDE TRAP GUARD
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
NOTES:
1. PRODUCT BRANDS SHOWN ON DRAWINGS ARE FOR INFORMATIONAL PURPOSES ONLY AND SHALL NOT BE CONSTRUED AS THE ONLY PRODUCT AVAILABLE. OTHER BRAND SELECTED SHALL MEET THE PERFORMANCE AND MATERIAL SPECIFICATIONS OF PRODUCTS LISTED.
SCALE:P-601
1 PRESSURE PIPING RISER DIAGRAM
SCALE:P-601
2 SANITARY PIPING RISER DIAGRAM
NTS NTS
# KEYED NOTES:
1. CONNECT 1" DCW PIPING TO THE TURNKEY POTABLE
WELL AND RO SYSTEM. REFER TO CIVIL DRAWINGS FOR
ADDITIONAL DETAILS.
2. VIF 4" EXISTING SANITARY SEWER LINE TO EXISTING
SEPTIC FIELD.
3. VIF EXISTING SANITARY PIPING TO EXISTING PLUMBING
FIXTURES. MODIFY IN FIELD AS REQUIRED.
| Sheets |
| P-001 - PLUMBING ABBREVIATIONS, LEGEND, & NOTES |
| P-101 - EXISTING PUMP BUILDING PLUMBING DEMOLITION PLAN |
| P-201 - EXISTING PUMP BUILDING PLUMBING PRESSURE & SANITARY PIPING PLAN |
| P-501 - EXISTING PUMP BUILDING PLUMBING DETAILS |
| P-601 - EXISTING PUMP BUILDING PLUMBING SCHEDULES & RISER DIAGRAMS |
| 2025-04-09T12:56:58-0400 | |
| Faisal Al Twal | |
| I am the author of this document. |
| 2025-04-09T12:57:00-0400 | |
| Faisal Al Twal | |
| I am the author of this document. |
| 2025-04-09T12:57:06-0400 | |
| Faisal Al Twal | |
| I am the author of this document. |
| 2025-04-09T12:57:18-0400 | |
| Faisal Al Twal | |
| I am the author of this document. |
| 2025-04-09T12:57:47-0400 | |
| Faisal Al Twal | |
| I am the author of this document. |
File details come from the government source that posted it. Updated .