2_-_Structural_Plans_-_100%_-_4-9-25_.pdf
PDF 1 MB Posted
- Attached to
- Raw Water Booster Pump Station Improvements
- Solicitation number
- 25-8400
- Issued by
- Collier County, Florida
About this file
These are structural engineering design documents for a Raw Water Booster Pump Station Parking Canopy project prepared by TRC Worldwide Engineering for Collier County Public Utilities. The project involves constructing a pre-engineered metal building (PEMB) parking canopy structure with specific design parameters including wind load requirements per ASCE 7-10, Florida Building Code 5th Edition, and a wind speed of 147 MPH (3-second gust). The structural drawings provide comprehensive details for foundation, framing, roof, elevations, and specific construction requirements, including footing specifications, concrete design criteria, reinforcing steel guidelines, and metal building system design parameters.
The project includes specific technical specifications such as a 4,000 PSI concrete design, ASTM A615 Grade 60 reinforcing steel, and detailed requirements for concrete testing, post-installed anchors, and metal building system design. The structural system is designed to be self-supporting and stable, with specific attention to wind load resistance, lateral deflection limits, and compliance with building codes. The documents outline precise requirements for shop drawings, contractor submittals, and engineering review processes, ensuring a rigorous approach to structural design and construction quality control for this public utility infrastructure project.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1061 DESIGN LOADS:
A. THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN
DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, 5TH EDITION.
B. WIND DESIGN LOADS: ASCE 7-10
H = <22.5> FT Vult = 147 MPH (3 SECOND GUST) Vasd = 114 MPH (3 SECOND GUST)
I = <1.0> EXPOSURE C
Kz = <0.95> Kzt = 1.0 Kd = <0.85> GCpi = 0.0
RISK CATEGORY: I
BUILDING IS CONSIDERED TO BE OPEN
STRUCTURAL NOTES
STRUCTURAL NOTES:
A. ELECTRONIC VERSIONS OF STRUCTURAL DRAWINGS ARE THE SOLE, COPYRIGHTED
PROPERTY OF TRC WORLDWIDE ENGINEERING. ELECTRONIC VERSIONS OF
DRAWINGS ARE NOT TO BE USED OR TRANSFERRED WITHOUT THE EXPRESS,
WRITTEN PERMISSION OF TRC WORLDWIDE ENGINEERING.
1010 GENERAL:
A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR DEPRESSIONS, DIMENSIONS, AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
B. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING
WITH THE AFFECTED PART OF THE WORK.
C. WHERE DRAWINGS AND SPECIFICATIONS ARE IN CONFLICT, THE MORE STRINGENT
RESTRICTIONS AND REQUIREMENTS SHALL GOVERN.
D. PLAN NOTES, DETAILS AND SECTIONS SHALL TAKE PRECEDENCE OVER GENERAL
STRUCTURAL NOTES. TYPICAL DETAILS AND SECTIONS NOT CUT ON PLANS SHALL
APPLY UNLESS NOTED OTHERWISE.
E. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO DETERMINE
ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND
IT’S COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY
SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIE DOWNS. CONTRACTOR IS
RESPONSIBLE FOR ENSURING THAT CONSTRUCTION COMPLIES WITH OSHA
REGULATION INCLUDING DESIGN OF CONNECTIONS OF MEMBERS THAT WILL NOT BE
FULLY COMPLETED AT THE TIME OF INSTALLATION.
F. TOWER CRANES ARE A CONTRACTOR RESPONSIBILITY AND SHALL BE DESIGNED FOR
APPLICABLE CRITERIA INCLUDING BUT NOT LIMITED TO INSURANCE REQUIREMENTS
AND APPLICABLE BUILDING CODES AT THE PROJECT LOCATION. THE CONTRACTOR
SHALL SUBMIT A CRANE LAYOUT, SHOP DRAWINGS, CALCULATIONS AND REACTIONS
FOR BOTH FOUNDATIONS AND CRANE TIE-IN LOCATIONS, SIGNED AND SEALED BY A
FLORIDA LICENSED PROFESSIONAL ENGINEER. THE ENGINEER OF RECORD SHALL BE
RETAINED BY THE CONTRACTOR TO EVALUATE CRANE TIE-IN FORCES ON THE
BUILDING STRUCTURE AND TO PROVIDE CRANE FOUNDATION DESIGN.
1011 CONTRACTOR PROPOSED CHANGES AND SUBSTITUTIONS:
A. PROPOSED CHANGES OR SUBSTITUTIONS TO STRUCTURAL DETAILS OR PLANS
SHALL BE SUBMITTED TO THE ENGINEER OF RECORD (EOR) FOR REVIEW AND
APPROVAL. SUBMITTALS SHALL CONTAIN FULL DOCUMENTATION OF CHANGES OR
SUBSTITUTIONS WITH SUPPORTING, SEALED CALCULATIONS (WHERE APPLICABLE).
THE REVIEW OF CHANGES AND SUBSTITUTIONS, RE-ANALYSIS AND/OR RE-DRAFTING
TO INCORPORATE CHANGES OR SUBSTITUTIONS INTO CONTRACT DOCUMENTS ARE
ADDITIONAL SERVICES FOR EOR. EOR IS NOT RESPONSIBLE FOR DETERMINING THE
COST EFFECTIVENESS OF PROPOSED CHANGES.
1012 CONTRACTOR REQUIRED REMEDIAL WORK:
A. DESIGN OF REMEDIAL WORK RELATED TO CONSTRUCTION ERRORS, INSTALLATIONS
NOT IN CONFORMANCE WITH CONTRACT DOCUMENTS, OR IN ANY WAY BROUGHT
ABOUT BY ACTIVITIES OF THE CONTRACTOR, IS NOT WITHIN THE SCOPE OF
CONSTRUCTION ADMINISTRATION SERVICES PROVIDED BY TRC WORLDWIDE
ENGINEERING. THE CONTRACTOR SHALL CARRY IN THEIR BASE BID THE COSTS FOR
ENGINEERING WORK ASSOCIATED TRC PROVIDING ADDITIONAL SERVICES IN
REACTION TO NON-CONFORMING WORK.
1120 SHOP DRAWING REVIEW CONTINUED:
C. SHOP DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE CONTRACTOR’S FIELD
ENGINEER PRIOR TO SUBMITTAL TO THE ARCHITECT/ENGINEER. DRAWINGS
SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
D. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN
INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO
QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
E. SHOP DRAWING SUBMITTALS SHALL BE SUBMITTED IN ELECTRONIC PDF FILE FORMAT
ONLY.
F. SHOP DRAWINGS SHALL NOT CONTAIN DETAILS COPIED OR REPRODUCED FROM THE
CONTRACT DOCUMENTS. REPRODUCTION OF THE CONTRACT DOCUMENTS WILL
RESULT IN A REJECTION OF THE SHOP DRAWINGS
G. ELECTRONIC VERSIONS OF STRUCTURAL CONTRACT DOCUMENTS ARE THE SOLE,
COPYRIGHTED PROPERTY OF TRC WORLDWIDE ENGINEERING. ELECTRONIC VERSIONS
OF DRAWINGS ARE NOT TO BE USED OR TRANSFERRED WITHOUT THE EXPRESS,
WRITTEN PERMISSION OF TRC WORLDWIDE ENGINEERING. USERS WILL SIGN A
RELEASE AND REIMBURSE TRC WORLDWIDE ENGINEERING. FOR EXPENSES INCURRED
IN PREPARING AND TRANSMITTING ELECTRONIC DRAWINGS AT THE RATE TO BE
DETERMINED UPON REQUEST.
H. THE CONTRACT DOCUMENTS SHALL GOVERN OVER THE SHOP DRAWINGS UNLESS
OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER.
I. CHANGES AND ADDITIONS MADE ON RE-SUBMITTALS SHALL BE CLEARLY FLAGGED AND
NOTED. THE PURPOSE OF THE RE-SUBMITTALS SHALL BE CLEARLY NOTED ON THE
LETTER OF TRANSMITTAL. ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS
CAUSING THE RE-SUBMITTAL.
J. ELECTRONIC SUBMITTALS OF SHOP DRAWINGS WILL ONLY BE ACCEPTED AND
REVIEWED PENDING ABOVE CONDITIONS ARE MET. TRC WORLDWIDE ENGINEERING.
WILL ELECTRONICALLY RETURN SUBMITTAL IN PDF FORMAT AND WILL NOT BE
RESPONSIBLE FOR PRINTING MULTIPLE COPIES FOR DISTRIBUTION.
1121 SHOP DRAWINGS FOR SPECIALTY ENGINEERED PRODUCTS:
A. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE FABRICATION
AND ERECTION DRAWINGS PREPARED BY A DELEGATED ENGINEER. DELEGATED
ENGINEER SHALL POSSESS CURRENT PROFESSIONAL LICENSURE IN THE JURISDICTION
OF THE PROJECT. THE SPECIALTY/DELEGATE ENGINEER SHALL POSSESS AND
MAINTAIN A MINIMUM OF $1,000,000 LIMIT OF PROFESSIONAL LIABILITY INSURANCE.
a. METAL BUILDING
A. SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND APPLICABLE
CODES, LIST THE DESIGN CRITERIA, AND SHOW ALL DETAILS AND PLANS NECESSARY
FOR PROPER FABRICATION AND INSTALLATION. CALCULATIONS AND SHOP DRAWINGS
SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED. GENERIC PRODUCTS WILL NOT BE
ACCEPTED.
B. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT
SUPERVISION AND CONTROL OF THE DELEGATED ENGINEER. SHOP DRAWINGS AND
CALCULATIONS REQUIRE THE IMPRESSED SEAL (OR ELECTRONICALLY SIGNED AND
SEALED PER FLORIDA RULES), DATE AND SIGNATURE OF THE DELEGATED ENGINEER.
C. REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OF SUBMITTALS IS LIMITED TO
VERIFYING THE FOLLOWING:
a. THAT THE SPECIFIED STRUCTURAL SUBMITTALS HAVE BEEN FURNISHED.
b. THAT THE STRUCTURAL SUBMITTALS HAVE BEEN SIGNED AND SEALED BY THE
DELEGATED ENGINEER.
c. THAT THE DELEGATED ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AND HAS
USED THE SPECIFIED STRUCTURAL CRITERIA. (NO DETAILED CHECK OF
CALCULATIONS WILL BE MADE).
d. THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTALS IS
CONSISTENT WITH THE CONTRACT DOCUMENTS. (NO DETAILED CHECK OF
DIMENSIONS OR QUANTITIES WILL BE MADE).
D. SUBMITTALS NOT MEETING THE ABOVE CRITERIA WILL NOT BE REVIEWED.
1122 RFI REVIEW:
A. ALL OF CONTRACTOR'S REQUEST(S) FOR INFORMATION (RFI's) SHALL STATE
CONTRACTOR’S SUGGESTION(S) FOR RESOLUTION AND COST IMPLICATIONS FOR
SUGGESTION(S). ENGINEER OF RECORD IS NOT RESPONSIBLE FOR DETERMINING
COST OR COST EFFECTIVENESS OF RFI RESPONSES.
1060 DESIGN AND CONSTRUCTION STANDARDS:
A. THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE
WITH THE FOLLOWING CODES AND REFERENCED STANDARDS:
(FBC 2023) FLORIDA BUILDING CODE 8th EDITION BY THE INTERNATIONAL CODE
COUNCIL, INC
(ACI 318-19) 2019 EDITION OF AMERICAN CONCRETE INSTITUTE BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE
(AISC 15 ED) FIFTEENTH EDITION OF THE STEEL CONSTRUCTION MANUAL BY THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(ASCE 7-22) MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS
AND OTHER STRUCTURES BY THE AMERICAN SOCIETY OF CIVIL
ENGINEERS
B. CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH THE ABOVE
REFERENCED CODES AND STANDARDS AND THE FOLLOWING:
(ACI 117-10) SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION
MATERIALS
(ACI 301-16) SPECIFICATIONS FOR TOLERANCES FOR STRUCTURAL CONCRETE
CONSTRUCTION MATERIALS
(ACI 304R-00) RECOMMENDED PRACTICES FOR MEASURING, MIXING, TRANSPORTING,
AND PLACING CONCRETE.
(ACI 305R-10) HOT WEATHER CONCRETING
(ACI 309R-05) GUIDE FOR CONSOLIDATION OF CONCRETE
(ACI 315-18) DETAILS AND DETAILING OF CONCRETE REINFORCING
(MNL-15 (16)) FIELD REFERENCE MANUAL: SPECIFICATIONS FOR STRUCTURAL
CONCRETE (ACI 301-16) WITH SELECTED ACI AND ASTM REFERENCES
(AWS D1.1-20) STRUCTURAL WELDING CODE - STEEL
(AWS D1.4-17) STRUCTURAL WELDING CODE - REINFORCING STEEL
2010 FOUNDATIONS: (NO GEOTECH REPORT)
A. FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000
PSF ON COMPACTED FILL. BEFORE CONSTRUCTION COMMENCES, SOIL BEARING
CAPACITY SHALL BE VERIFIED BY A SUBSURFACE INVESTIGATION, AS WELL AS FIELD
AND LABORATORY TESTS PERFORMED BY A CERTIFIED TESTING LABORATORY, WHO’S
REPORT SHALL INCLUDE ANALYSIS AND RECOMMENDATIONS FOR SITE PREPARATION
IN ORDER TO BEAR THE FOUNDATION LOADS. ABOVE REPORT SHALL BE PREPARED
AND SEALED BY A GEOTECHNICAL ENGINEER, LICENSED WITHIN THE JURISDICTION OF
THE PROJECT AND SHALL BE SUBMITTED TO ENGINEER FOR REVIEW.
2011 FOUNDATIONS:
A. RESERVED FOR GEOTECHNICAL REPORT INFORMATION BY CONTRACTOR.
B. NO APPROVAL OR VERIFICATION OF RECOMMENDATIONS MADE WITHIN THE ABOVE
NOTED GEOTECHNICAL REPORT IS IMPLIED THROUGH REFERENCE OR USE BY TRC.
C. A GEOTECHNICAL ENGINEER, LICENSED WITHIN THE JURISDICTION OF THE PROJECT,
SHALL VERIFY IN THE FIELD THAT ALL SITE PREPARATION FILL OPERATIONS, BEARING
CONDITIONS, FOUNDATION TESTING AND INSTALLATION COMPLY WITH THE SOILS
REPORT.
D. FOUNDATION DESIGN FOR SHALLOW FOUNDATIONS SYSTEMS ARE BASED UPON AN
ALLOWABLE NET SOIL BEARING PRESSURE *,*** PSF AS PROVIDED BY ABOVE
GEOTECHNICAL REPORT.
E. FOUNDATION WALLS ARE DESIGNED FOR THE FOLLOWING DESIGN LOADS:
a. SOIL WEIGHT:........................................................ 120 PCF
b. AT-REST PRESSURE: (BRACED AT TOP)........... 60 PCF
c. ACTIVE PRESSURE:............................................... 40 PCF
d. PASSIVE PRESSURE:............................................ 240 PCF
e. FRICTION COEFFICIENT:.......................................0.35
F. SUBGRADE PREPARATION AND VAPOR RETARDER INSTALLATION FOR SLAB-ON-
GRADE SHALL BE PERFORMED IN ACCORDANCE WITH PROJECT GEOTECHNICAL
REPORT.
G. CONCRETE FOR FOOTINGS SHALL BE PLACED IMMEDIATELY AFTER FINAL
INSPECTION AND ACCEPTANCE BY THE GEOTECHNICAL ENGINEER. IN NO CASE
SHALL FOOTING EXCAVATIONS BE ALLOWED TO STAND OPEN OVERNIGHT OR
DURING RAIN.
H. GRADE SHALL BE SUCH THAT THICKNESS OF FOUNDATION, SLAB ON GRADE, ETC. IS
NOT REDUCED BY MORE THAN 5% OF THAT SHOWN ON DRAWINGS.
3101 FORMWORK AND SHORING (CONCRETE SLABS AND BEAMS):
A. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT LEAST
TWO-THIRDS OF THE 28 DAY DESIGN STRENGTH (& ALL TENDONS STRESSED FOR PT
SLABS). A MINIMUM OF 3 STORIES OF SHORING AND (/OR) RESHORING SHALL BE
USED WHICH SHALL CONSIST OF ONE COMPLETE SET OF VERTICAL SHORES AND
TWO SETS OF VERTICAL SHORES THAT COMPRISE AT LEAST 50% OF A COMPLETE
SET.
B. DRAWINGS FOR SHORING AND RESHORING SHALL BE PREPARED BY AN ENGINEER
LICENSED WITHIN THE JURISDICTION OF THE PROJECT.
C. DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK, SHORES AND RESHORES
SHALL MEET REQUIREMENTS SET FORTH IN ACI STANDARDS 347 AND 301.
D. SUBMIT SIGNED & SEALED SHORING DRAWINGS INCLUDING POUR SEQUENCE AND
CALCULATIONS, WHERE NECESSARY, TO DEMONSTRATE THAT THE POUR SEQUENCE
AND SHORING/RE-SHORING METHODS DO NOT OVERSTRESS THE STRUCTURE. THIS
ANALYSIS SHALL INCLUDE STRESSES CAUSED BY SHRINKAGE OF STRUCTURAL SLAB.
PROVIDE LOCATION AND DETAILS OF POUR STRIPS IF REQUIRED TO REDUCE
SHRINKAGE AND RESTRAINT CRACKS.
E. SHORING INSPECTIONS SHALL BE PERFORMED BY THE SHORING ENGINEER.
F. UNLESS ARCHITECT SPECIFIES OTHERWISE, CONSTRUCT FORMWORK SO CONCRETE
SURFACES CONFORM TO THE TOLERANCE LIMITS OF ACI 117 [STANDARD
SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION MATERIALS].
THE CLASS OF SERVICE FOR OFFSET BETWEEN ADJACENT PIECES OF FORMWORK
FACING MATERIAL SHALL BE CLASS B FOR SURFACES PERMANENTLY EXPOSED TO
PUBLIC VIEW AND CLASS D FOR SURFACES THAT WILL BE PERMANENTLY
CONCEALED.
3104 CONSTRUCTION JOINTS AND CONTROL JOINTS:
A. CONSTRUCTION JOINTS AND CONTROL JOINTS SHALL BE LOCATED AS SHOWN IN
PLAN OR SECTION.
B. UNLESS NOTED OTHERWISE, CONTROL JOINTS IN SLABS ON GRADE SHALL BE
PROVIDED SO THAT THE MAXIMUM DISTANCE BETWEEN JOINTS SHALL BE NO MORE
THAN 3 TIMES THE SLAB THICKNESS IN FEET (OR AS SHOWN ON PLANS). SAWCUT
CONTROL JOINTS SHALL BE MADE AS SOON AS SLAB WILL SAFELY SUPPORT MEN
AND EQUIPMENT AND THE SLAB WILL NOT BE DAMAGED BY EQUIPMENT. ASPECT
RATIO (LONGSIDE TO SHORTSIDE OF CONCRETE AREA) SHALL NOT EXCEED 1.5.
C. DEVIATION FROM OR ADDITION TO CONSTRUCTION OR CONTROL JOINT LOCATIONS
SHOWN SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL AND
ARE ACCEPTABLE ONLY AS A CHANGE ORDER THAT WILL INCLUDE ENGINEERING
CHARGES BY THE ENGINEER OF RECORD FOR REDESIGN OF THE STRUCTURE AS
REQUIRED. SHORING REQUIREMENTS TO IMPLEMENT REVISED CONSTRUCTION
JOINTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
3301 CAST-IN-PLACE CONCRETE:
A. ALL CAST-IN-PLACE CONCRETE SHALL BE PER AN APPROVED MIX DESIGN
PROPORTIONED TO ACHIEVE A STRENGTH AT 28 DAYS AS LISTED BELOW WITH A
PLASTIC AND WORKABLE MIX:
B. CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI 301(16) STANDARDS
AND SPECIFICATIONS.
C. PRIOR TO CONCRETE PLACEMENT, MIX DESIGN SHALL BE SUBMITTED AND
ACCEPTED BY ENGINEER FOR USE. MIX DESIGN SHALL INCLUDE THE FOLLOWING:
a. MIX DESIGN WHICH SHALL INCLUDE TESTED, STATISTICAL BACK-UP DATA AS PER
ACI 301, ARTICLE 4.2.3.
b. ONLY TYPE II CEMENT SHALL BE USED FOR SLAB-ON GRADE CONCRETE.
c. CONCRETE MIX DESIGNS SHALL INCLUDE A WRITTEN DESCRIPTION INDICATING
WHERE EACH PARTICULAR MIX IS TO BE PLACED WITHIN THE STRUCTURE.
FAILURE TO COMPLY MAY RESULT IN REJECTION OF THE MIX. IF ACCEPTED, PEA
ROCK PUMP MIX USE IS LIMITED TO VERTICAL ELEMENT POURS AND BEAM
POURS LESS THAN 60 LINEAL FEET PER POUR
d. MIX DESIGN SHALL MEET THE REQUIREMENTS OF ASTM C33 FOR COARSE
AGGREGATE.
e. CALCIUM CHLORIDES SHALL NOT BE UTILIZED
f. OTHER ADMIXTURES MAY BE USED ONLY WITH THE APPROVAL OF THE
ENGINEER.
g. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING STRUCTURAL DRAWINGS
AND SPECIFYING THE USE OF WATER REDUCERS WHERE REINFORCING
CONGESTION WARRANTS.
D. CONCRETE SHALL COMPLY WITH THE REQUIREMENTS OF ASTM STANDARD C94 FOR
MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME
STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM THE
TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS FINAL POSITION
SHALL NOT EXCEED ONE AND ONE HALF (1 1/2) HOURS. IF FOR ANY REASON THERE
IS A LONGER DELAY THAN THAT STATED ABOVE, THE CONCRETE SHALL BE
DISCARDED. IT SHALL BE THE RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE
OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NONCOMPLIANCE WITH
THE ABOVE.
E. SLABS SHALL BE CURED USING A DISSIPATING CURING COMPOUND MEETING ASTM
STANDARD C309 TYPE 1-D AND SHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL
BE PLACED AS SOON AS THE FINISHING IS COMPLETED OR AS SOON AS THE WATER
HAS LEFT THE UNFINISHED CONCRETE. SCUFFED OR BROKEN AREAS IN THE CURING
MEMBRANE SHALL BE RECOATED DAILY.
F. WATER/CEMENTITIOUS MATERIAL RATIO FOR CONCRETE BELOW OR AT GRADE AND
FOR CONCRETE SUBJECTED TO DEICERS AND/OR SPECIFIED TO BE WATERTIGHT
SHALL NOT EXCEED 0.45 BY WEIGHT. MAXIMUM PERMISSIBLE W/C RATIO: 0.50 FOR
ALL OTHER CONCRETE AND CONCRETE BELOW GRADE SUBJECTED TO
FREEZE/THAW.
G. ALL CONCRETE EXPOSED TO THE WEATHER SHALL BE AIR-ENTRAINED. FOR
SURFACE FINISHES AND OTHER REQUIREMENTS, REFER TO THE CONCRETE
SPECIFICATIONS.
H. WHERE SPECIFIED COLUMN CONCRETE STRENGTH IS 1.4 TIMES THE SPECIFIED SLAB
CONCRETE STRENGTH, SEE COLUMN SCHEDULE FOR PUDDLING REQUIREMENTS. IF
REQUIRED, THE STRENGTH OF THE PUDDLED CONCRETE SHALL BE AT LEAST EQUAL
TO THE STRENGTH OF THE COLUMN CONCRETE. PUDDLING SHALL EXTEND 2'-0"
MINIMUM FROM FACE OF COLUMN IN ALL DIRECTIONS.
I. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS, CHAMFERS, REGLETS,
SLOTS, SLEEVES, ANCHORS, AND INSERTS. UNLESS SHOWN ON STRUCTURAL
DRAWINGS NO OPENINGS LARGER THAN 12"x12" SHALL BE PLACED IN SLABS OR
WALLS. FOR OPENINGS NOT SHOWN ON STRUCTURAL DRAWINGS, APPROVALS
MUST BE OBTAINED FROM THE ENGINEER PRIOR TO FABRICATION OF STEEL AND
PLACEMENT OF CONCRETE. LOCATION DRAWINGS FOR ALL SLEEVES AND
BLOCKOUTS IN THE CONCRETE SHALL BE SUBMITTED FOR APPROVAL BY THE
STRUCTURAL ENGINEER PRIOR TO PLACEMENT.
J. CONCRETE WALLS SHALL BE CAST MONOLITHIC WITH ADJOINING COLUMNS UNLESS
SPECIFICALLY NOTED OTHERWISE. CONCRETE FOR SUCH WALLS SHALL BE THE
SAME TYPE AND STRENGTH AS SPECIFIED COLUMNS.
K. CONTRACTOR SHALL CONFORM TO ACI 306R FOR COLD WEATHER CONCRETING
AND ACI 305R FOR HOT WEATHER CONCRETING WHEN ANY COMBINATION OF HIGH
TEMPERATURE, LOW RELATIVE HUMIDITY AND WIND VELOCITY TEND TO IMPAIR THE
QUALITY OF THE CONCRETE. CONCRETE IS TO BE REJECTED IF ITS TEMPERATURE
AT TIME OF PLACEMENT IS 90°F OR ABOVE. PROTECT SURFACES OF EXPOSED
CONCRETE FROM PRECIPITATION DAMAGE UNTIL ADEQUATE STRENGTH IS GAINED
TO PREVENT DAMAGE.
L. CONCRETE SHALL BE VIBRATED BY MECHANICAL VIBRATORS.
M. A PRE-CONCRETE CONFERENCE SHALL BE HELD BY THE CONTRACTOR WITH
SUBCONTRACTORS, TESTING LAB PERSONNEL, ARCHITECT AND ENGINEERS. THESE
CONFERENCES SHALL BE HELD WELL IN ADVANCE OF CONSTRUCTION TO ENSURE
PROPER INTERPRETATION OF DESIGN INTENT. STEEL ERECTOR SHALL FIELD VERIFY
CORRECTNESS OF FOUNDATION, ANCHOR RODS, OR OTHER EXISTING WORK
AFFECTING THE STEEL BEFORE STARTING ERECTION.
CONCRETE DESIGN CRITERIA
MINIMUM 28-DAY
COMPRESSIVE STRENGTH
4000 PSI
* HIGHER SLUMPS ARE PERMITTED WHEN HIGH RANGE WATER REDUCER
(HRWR) ADMIXTURES (SUPER PLASTICIZER) ARE USED PENDING ENGINEER
OF RECORD APPROVAL OF MIX DESIGN.
MAXIMUM
SLUMP
USED FOR:
4 (±1)* ALL CONCRETE
3201 REINFORCING STEEL:
A. CONTRACTOR SHALL CARRY AN ALLOWANCE IN THEIR BID FOR SUPPLYING AND
ERECTING (5) TONS OF REINFORCING STEEL IN ADDITION TO THAT SHOWN ON PLANS
AND WITHIN SECTIONS, DETAIL AND SCHEDULES TO BE USED AT THE DISCRETION OF
THE STRUCTURAL ENGINEER.
B. REINFORCING STEEL SHALL BE ASTM A615 GRADE 60 DEFORMED BARS (WELDABLE
REINFORCING "DBA" SHALL CONFORM TO ASTM A-706 GRADE 60), FREE FROM OIL,
SCALE AND RUST AND PLACED IN ACCORDANCE WITH THE TYPICAL BENDING
DIAGRAM AND PLACING DETAILS OF ACI STANDARDS AND SPECIFICATIONS. SECURE
APPROVAL OF SHOP DRAWINGS PRIOR TO COMMENCING FABRICATION.
REINFORCING BAR DETAILING SHALL COMPLY WITH ACI 315 "MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" AND CRSI MANUAL
OF STANDARD PRACTICE.
C. CLEAR COVER TO REINFORCING SHALL BE AS INDICATED BELOW. WHERE A SPECIFIC
CONDITION IS NOT NOTED, REFER TO ACI REQUIREMENTS FOR COVER:
TOP BOTTOM SIDES/EDGES
FRAMED SLABS ON GRADE.......1" 3" NA
FOUNDATION WALL/PILASTER..NA NA 2" EXTERIOR
1 1/2" INTERIOR
SPREAD FOOTING......................2" 3" 3"
COLUMNS & WALLS................... NA NA 2" AGAINST SOIL
1 1/2" TYPICAL
EXTERIOR NON-PT
- #5 AND SMALLER...............1" 1 1/2" 2"
- #6 AND LARGER.................2" 2" 2"
BEAMS
(INTERIOR)..................................1 1/2" 1 1/2" 1 1/2"
(EXTERIOR EXPOSURE)........... 2" 1 1/2" 1 1/2"
NOTE: MAXIMUM DEVIATION IN BAR PLACEMENT SHALL BE AS DICTATED BY ACI.
D. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS, CHAMFERS, REGLETS,
SLOTS, SLEEVES, ANCHORS, AND INSERTS. UNLESS SHOWN ON STRUCTURAL
DRAWINGS NO OPENINGS LARGER THAN 12"x12" SHALL BE PLACED IN SLABS OR
WALLS. FOR OPENINGS NOT SHOWN ON STRUCTURAL DRAWINGS, APPROVALS MUST
BE OBTAINED FROM THE ENGINEER PRIOR TO FABRICATION OF STEEL AND
PLACEMENT OF CONCRETE. SEE NOTES ON EMBEDDED ITEMS FOR ADDITIONAL
LIMITATIONS.
E. PROVIDE CONTINUOUS REINFORCING WHERE POSSIBLE, SPLICE ONLY AS SHOWN ON
DRAWINGS OR AS APPROVED BY STRUCTURAL ENGINEER. PROVIDE CORNER BARS
AT ALL WALL, GRADE BEAM AND STRIP FOOTING CORNERS. BARS SHALL BE THE
SAME SIZE AND SPACING AS THE HORIZONTAL REINFORCING. INTERSECTING WALLS,
GRADE BEAMS AND STRIP FOOTINGS SHALL BE DOWELED TOGETHER IN THE SAME
MANNER. PROVIDE 2 NO. 4 TOP DIAGONAL BARS 4'-0" LONG AT ALL REENTRANT
CORNERS IN ALL SLABS ON GRADE AND ELEVATED SLABS.
F. SHOP DRAWINGS SHALL ADEQUATELY DEPICT THE REINFORCING BAR SIZES AND
PLACEMENT. SHOP DRAWINGS SHALL INCLUDE ADEQUATE SECTIONS, ELEVATIONS
AND DETAILS. WRITTEN DESCRIPTIONS ARE NOT ACCEPTABLE. ALL CONCRETE
WALLS SHALL BE DETAILED IN ELEVATION.
G. SPLICING OF REINFORCING SHALL BE AS SHOWN OR AS INDICATED IN SCHEDULE.
MECHANICAL SPLICING DEVICES SHALL DEVELOP 125% OF THE SPECIFIED YIELD
STRENGTH (FY) OF THE BAR. STAGGER MECHANICAL SPLICES WHERE POSSIBLE. ALL
STEEL NOTED AS CONTINUOUS SHALL BE A CLASS "B" SPLICE PER SCHEDULE.
H. DO NOT WELD OR TACK WELD REINFORCING STEEL UNLESS APPROVED OR
DIRECTED BY THE STRUCTURAL ENGINEER.
I. TIE ALL REINFORCING AND EMBEDS SECURELY IN PLACE PRIOR TO PLACING
CONCRETE. PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF
REINFORCEMENT AND EMBEDS WITHIN SPECIFIED TOLERANCES DURING ALL
CONSTRUCTION ACTIVITIES.
J. THE SHOP DRAWINGS FOR REINFORCING STEEL SHALL INCLUDE SCALE ELEVATIONS
OF ALL CONCRETE WALLS.
K. OPENINGS THROUGH CONCRETE WALLS, SLABS OR OTHER STRUCTURAL ELEMENTS
NOT DETAILED ON THE STRUCTURAL DRAWINGS MUST BE LOCATED AND SHOWN ON
THE APPLICABLE REINFORCING STEEL SHOP DRAWINGS. THE FINAL LOCATION OF
ALL OPENINGS MUST BE REVIEWED BY THE A/E BEFORE THE CONCRETE IS POURED.
1120 SHOP DRAWING REVIEW:
A. SHOP DRAWING SUBMITTALS ARE REQUIRED FOR ALL COMPONENTS SHOWN ON
THESE STRUCTURAL CONTRACT DOCUMENTS INCLUDING, BUT NOT LIMITED TO:
a. CONCRETE MIXES
b. CONCRETE REINFORCING
c. ALL FASTENERS, ANCHORS, BOLTS, EPOXY ADHESIVES
d. WELDER QUALIFICATIONS/CERTIFICATIONS FOR STEEL AND ALUMINUM
B. SHOP DRAWINGS SHALL PROVIDE ACCURATE, DETAILED DIMENSIONAL INFORMATION
AS WELL AS COMPLETE SHOP AND FIELD ERECTION DETAILS NOT SHOWN ON
CONTRACT DOCUMENTS NECESSARY FOR FABRICATION AND INSTALLATION OF
COMPONENT.
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p yr ig h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:3
A M
A u to d e sk D o cs
/T
R C
F lo ri d a R e vi t
/2
F T
M
-R
W B
P C a n o p yR
.r vt
S-101
S T
R U
C T
U R
A L
N O
T E
S
D E
S
IG
N C
R
IT
E R
IA
RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
SHEET INDEX
SHT # DESCRIPTION
S-101 STRUCTURAL NOTES & DESIGN CRITERIA
S-102 STRUCTURAL NOTES & ABBREVIATIONS
S-103 FOUNDATION AND ROOF PLANS
S-104 PEMB FRAME ELEVATION
S-105 FOUNDATION SECTIONS AND DETAILS
S-106 ROOF SECTIONS AND DETAILS
S-107 ELEVATIONS
No. 60487
STATE OFP
R
O F
ESS I ONA L ENG
I N
E E
R
L EI CENS
P
AU
L
S. MOE RSCHE
L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
STRUCTURAL NOTES
3304 CONCRETE TESTING:
A. AN INDEPENDENT TESTING LABORATORY SHALL PERFORM THE FOLLOWING TESTS ON
CAST-IN-PLACE CONCRETE:
a. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT
CONCRETE."
b. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF
CYLINDRICAL CONCRETE SPECIMENS." A SEPARATE TEST SHALL BE CONDUCTED
FOR EACH CLASS, FOR EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED
PER DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS FOLLOWS:
28 DAY SPEC:
1. EARLY CYLINDERS (AS NEEDED): 1, 2, AND 3 DAY BREAKS ARE A GOOD RANGE
TO HAVE FOR STRESSING OR OTHER EARLY NEEDS. EACH TEST REQUIRES (3)
CYLINDERS.
2. (3) 7 DAY CYLINDERS
3. (3) 28 DAY CONFORMANCE CYLINDERS
4. (3) 56 DAY HOLD CYLINDERS (TO BE TESTED IF THE 28 DAY CYLINDERS DO NOT
MEET SPEC AND CAN BE TESTED AT ANY TIME AT THE REQUEST/DISCRETION
OF THE ENGINEER/CONTRACTOR).
56 DAY SPEC:
1. EARLY CYLINDERS (AS NEEDED): 1, 2 AND 3 DAY BREAKS ARE A GOOD RANGE
TO HAVE FOR STRESSING OR OTHER EARLY NEEDS. EACH TEST REQUIRES (3)
CYLINDERS.
2. (3) 7 DAY CYLINDERS
3. (2) 28 DAY CYLINDERS
4. (3) 56 DAY CONFORMANCE CYLINDERS
3307 PENETRATIONS:
A. NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN
THOSE SPECIFICALLY DESIGNATED ON THE STRUCTURAL DRAWINGS WITHOUT
PREVIOUS APPROVAL OF THE ENGINEER. CONTRACTOR SHALL SUBMIT A
PENETRATION PLAN FOR APPROVAL INDICATING ANY PENETRATIONS NOT SHOWN ON
THE STRUCTURAL DRAWINGS PRIOR TO CONCRETE PLACEMENT.
3601 POST-INSTALLED ANCHORS:
A. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE
DRAWINGS.
B. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD PRIOR TO
USING POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN ANCHORS.
C. CARE SHALL BE GIVEN TO AVOID DAMAGING EXISTING REBAR WHEN DRILLING HOLES.
HOLES SHALL BE DRILLED AND CLEANED PER MANUFACTURER’S INSTRUCTIONS.
D. UNLESS SPECIFIED OTHERWISE, ANCHORS SHALL BE EMBEDDED IN THE
APPROPRIATE SUBSTRATE WITH A MINIMUM EMBEDMENT OF 8 TIMES THE NOMINAL
ANCHOR DIAMETER OR THE EMBEDMENT REQUIRED FOR SUPPORT OF THE INTENDED
LOAD. ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER’S INSTALLATION
INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE DISTANCE AND/OR SPACING
INDICATED IN THE MANUFACTURER’S LITERATURE.
E. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED BELOW SHALL
BE SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL WITH
CALCULATIONS PREPARED, SIGNED AND SEALED BY AN ENGINEER REGISTERED IN
THE JURISDICTION OF THE PROJECT SHOWING THAT THE SUBSTITUTED PRODUCT
WILL ACHIEVE AN EQUIVALENT CAPACITY USING THE APPROPRIATE DESIGN
PROCEDURE.
F. ACCEPTABLE PRODUCTS FOR ANCHORS NOT EXPOSED TO WEATHER ARE AS
FOLLOWS:
a. EXPANSION ANCHORS FOR NON-CRACKED CONCRETE ONLY:
• WEDGE-ALL (WA) BY SIMPSON STRONG-TIE
• KWIK BOLT 3 BY HILTI
b. CRACKED CONCRETE MECHANICAL ANCHORS:
• STRONG-BOLT (STB) BY SIMPSON STRONG-TIE
• KWIK BOLT (TZ) BY HILTI
c. SCREW ANCHORS:
• TITEN HD (THD) BY SIMPSON STRONG-TIE
• HUS-H BY HILTI
d. ADHESIVE ANCHORS INTO SOLID CONCRETE OR FULLY GROUTED CMU:
• ACRYLIC –TIE (AT)
• SET EPOXY-TIE (SET) WITH RETROFIT BOLTS (RFB) BY SIMPSON STRONG-TIE
• HY 200 MAX BY HILTI
e. FOR ANCHORING INTO HOLLOW BASE MATERIAL:
• CONTACT ENGINEER
G. ACCEPTABLE PRODUCTS FOR ANCHORS EXPOSED TO WEATHER OR FOR
ENVIRONMENTAL STRUCTURES ARE AS FOLLOWS:
a. CONCRETE MECHANICAL ANCHORS:
• TRUBOLT BY ITW REDHEAD - AISI 316 STAINLESS STEEL
• KWIK BOLT 3 BY HILTI - AISI 316 STAINLESS STEEL
• POWER STUD BY POWERS - AISI 316 STAINLESS STEEL
b. SCREW ANCHORS:
• TAPPER BY POWERS - AISI 316 STAINLESS STEEL
• HUS-H BY HILTI
c. CONCRETE OR SOLID GROUTED CMU ADHESIVE ANCHORS:
• HY 200 MAX BY HILTI - AISI 316 STAINLESS STEEL
13120 PRE-ENGINEERED METAL BUILDING:
A. THE PRE-ENGINEERED METAL BUILDING SHALL CONSIST OF ROOF DECK, RIGID
FRAMES, BRACING, CANOPY FRAMING, AND FLASHING. DEVIATION FROM BAY
SPACING SHOWN ON THE PLANS SHALL NOT BE PERMITTED TO SUIT
MANUFACTURERS STANDARDS.
B. THE SYSTEM SHALL BE DESIGNED AND DETAILED BY THE MANUFACTURER TO
SUSTAIN THE DESIGN LOADS SPECIFIED AS A STAND ALONE STRUCTURE. THE
DESIGN SHALL BE IN ACCORDANCE TO AISC AND AISI SPECIFICATIONS AND MBMA
"METAL BUILDING SYSTEMS MANUAL" DESIGN PRACTICES, LATEST ISSUES.
C. THE MANUFACTURER SHALL BE REGULARLY ENGAGED IN METAL BUILDING DESIGN
AND MANUFACTURING. CURRENT MBMI BUILDINGS ARE APPROVED, OTHERS
SHALL SUBMIT PRODUCT DATA FOR REVIEW.
D. SHOP DRAWINGS AND A LETTER OF CERTIFICATION SHALL BE SUBMITTED FOR
REVIEW AND APPROVAL PRIOR TO FABRICATION, AND SHOP DRAWINGS SHALL
BEAR THE SIGNATURE AND IMPRESSED SEAL OF A REGISTERED PROFESSIONAL
ENGINEER WITHIN THE JURISDICTION OF THE PROJECT. SHOP DRAWINGS SHALL
INDICATE THE DESIGN LOADS, LOAD PATH AND JOB NAME AND NUMBER. THEY
SHALL INCLUDE DRAWINGS OF THE FRAMING MEMBERS WITH THE CONNECTIONS,
THE ANCHOR BOLT PLAN AND REACTIONS. STANDARD CUT SHEETS OF THE ABOVE
ARE NOT ACCEPTABLE. STANDARD CUT SHEETS MAY BE SUBMITTED FOR
SECONDARY FRAMING CONNECTION DETAILS, FLASHING AND SHEETING DETAILS,
ETC.
E. ANCHOR BOLTS SHALL BE HEADED BOLTS WITH DIAMETER AND LOCATION
SPECIFIED BY THE METAL BUILDING DESIGNER. ANCHOR BOLT LENGTHS TO BE
SPECIFIED BY STRUCTURAL ENGINEER AFTER REACTIONS, DIAMETER, AND
LOCATIONS ARE PROVIDED. ANCHOR BOLTS SHALL BE PURCHASED AND
INSTALLED BY THE GENERAL CONTRACTOR.
F. BEFORE FOOTING INSTALLATION, THE ANCHOR BOLT EMBEDMENT LENGTHS MUST
BE VERIFIED BY THE STRUCTURAL ENGINEER. THE FOOTING DEPTH SHALL BE THE
SCHEDULED DEPTH OR THE ANCHOR BOLT EMBEDMENT LENGTH PLUS 3 INCHES,
WHICHEVER IS GREATER.
G. HORIZONTAL FORCE TRANSFER FROM METAL BUILDING COLUMN BASE TO
CONCRETE BY THE METAL BUILDING SUPPLIER.
H. METAL BUILDING FRAMES AND COMPONENTS RESISTING LATERAL LOAD AND
CONNECTED TO OR SUPPORTING MASONRY (CMU AND/OR BRICK) SHALL BE
DESIGNED TO LIMIT LATERAL DEFLECTIONS AS NOTED BELOW, BASED ON ASCE
7-16 WIND PRESSURES. THE DESIGN CERTIFICATION LETTER SHALL INDICATE THAT
THE DESIGN MEETS THESE REQUIREMENTS.
a. MAIN BUILDING FRAMES:
• LIMIT DRIFT TO H/100 WITH V=105 MPH MRI=50 YEARS
b. X- BRACE OR PORTAL FRAMES:
• LIMIT DRIFT TO H/100 WITH V=105 MPH MRI=50 YEARS
c. STRUCTURAL ROOFING AND SIDING MADE OF METAL SHEETS:
• LIMIT TOTAL DEFLECTION TO L/60
d. STRUCTURAL ROOF PURLINS:
• LIMIT LIVE LOAD DEFLECTION TO L/150 WHEN SUPPORTING METAL ROOFING
e. FOR METAL BUILDING GIRTS:
• LIMIT WIND* DEFLECTION TO L/90
• * COMPONENTS AND CLADDING WIND FORCES MAY BE MULTIPLIED BY 0.42
TIMES ULTIMATE PRESSURES FOR COMPUTING WIND DEFLECTION.
f. FOR OTHER LIMITS OF DEFLECTION SEE 2020 FLORIDA BUILDING CODE
g. ALLOWABLE STRESS INCREASES FOR SHORT TERM WIND LOADINGS IS NOT
PERMITTED
I. METAL BUILDING SYSTEM NOT DESIGNED TO SUPPORT FUTURE MECHANICAL
EQUIPMENT, CRANES, AND IS NOT DESIGNED FOR ANY FUTURE EQUIPMENT. METAL
BUILDING COLUMNS ARE DESIGNED FOR MEZZANINES WITH LOADS LISTED IN
GENERAL NOTES AND WITH LIMITS MEZZANINE DEFINED ON MEZZANINE FRAMING
PLAN.
ABBREVIATIONS
FS - FAR SIDE
FT - FOOT
F# - FOOTING
FTG - FOOTING
FV - FIELD VERIFY
GA - GAUGE
GALV - GALVANIZED
GC - GENERAL CONTRACTOR
GT - GIRDER TRUSS
HC - HOLLOW CORE
HCP - HOLLOW CORE PLANK
HDG - HOT DIPPED GALVANIZED
HG - HIP GIRDER
HK - HOOK
HORIZ - HORIZONTAL
HP - HIGH POINT
HS - HIGH STRENGTH
IJ - ISOLATION JOINT
INFO - INFORMATION
INS - INSULATION
INT - INTERIOR
IRR - IRREGULAR
JB - JOIST BEARING
JBE - JOIST BEARING ELEVATION
JR - JAMB REINFORCING
JT - JOINT
K - KIP(s), 1000 POUNDS
KLF - KIPS PER LINEAR FOOT
KJ - CONSTRUCTION JOINT
L - ANGLE
LG - LONG
LLH - LONG LEG HORIZONTAL
LLV - LONG LEG VERTICAL
LP - LOW POINT
LW - LONG WAY
LWT - LIGHTWEIGHT
MFR - MANUFACTURER
MAS - MASONRY
MO - MASONRY OPENING
MATL - MATERIAL
MAX - MAXIMUM
MECHL - MECHANICAL
MTL - METAL
MIN - MINIMUM
MISC - MISCELLANEOUS
NS - NEAR SIDE
NIC - NOT IN CONTRACT
NTS - NOT TO SCALE
NW - NORMAL WEIGHT
OC - ON CENTER
OH - OPPOSITE HAND
OPNG - OPENING
PAF - POWER ACTUATED FASTENERS
PART - PARTITION
PARTL - PARTIAL
PCJ - PRECAST CONCRETE JOIST
PJP - PARTIAL JOINT PENETRATION
PL - PLATE
PLF - POUNDS PER LINEAR FOOT
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PT - POST TENSIONED
PrT - PRESSURE TREATED
PNL - PANEL
R - RADIUS
REG - REGULAR
REINF - REINFORCING
REM - REMAINDER
REQD - REQUIRED
REV - REVISED/REVISION
RM - ROOM
RO - ROUGH OPENING
RQMTS - REQUIREMENTS
SCHED - SCHEDULE
SECT - SECTION
SIM - SIMILAR
SL - SLOPE
SOG - SLAB-ON-GRADE
SP - SPIRAL
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STL - STEEL
STRUCTL - STRUCTURAL
SW# - SHEARWALL
SW - SHORT WAY
T/ - TOP OF
TB - TIE BEAM
TC - TIE COLUMN
TEMP - TEMPERATURE
TG - TRUSS GIRDER
TH - TRUSS HIP
THK - THICK
TJ - TRUSS JACK
TR - TRUSS
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VERT - VERTICAL
W/ - WITH
W/O - WITHOUT
WD - WOOD
WF - WALL FOOTING
WP - WORK POINT
WWR - WELDED WIRE REINFORCING
ADDL - ADDITIONAL
AR - ANCHOR ROD
ALT - ALTERNATE
APPROX - APPROXIMATELY
ARCH - ARCHITECT
ARCHL - ARCHITECTURAL
B/ - BOTTOM OF
BC - BOTTOM CHORD
BLDG - BUILDING
BM - BEAM
BOTT - BOTTOM
BRG - BEARING
C/C - CENTER TO CENTER
CF - CONTINUOUS FOOTING
CIP - CAST IN PLACE
CJ - CONTRACTION JOINT
CJP - COMPLETE JOINT PENETRATION
CL, - CENTERLINE
CLR - CLEAR
CMU - CONCRETE MASONRY UNIT
COL - COLUMN
CONC - CONCRETE
CONFIG - CONFIGURATION
CONT - CONTINUOUS
CONTR - CONTRACTOR
CTR - CENTER
DBL - DOUBLE
DD - DECK DRAIN
DTL - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DR - DRAIN
DWG - DRAWING
EA - EACH
EE - EACH END
EF - EACH FACE
EJ - EXPANSION JOINT
EL - ELEVATION
ELEV - ELEVATOR
ENGR - ENGINEER
EOR - ENGINEER OF RECORD
EOS - EDGE OF SLAB
EQ - EQUAL
EW - EACH WAY
EXIST - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FIN - FINISH
FLR - FLOOR
FD - FLOOR DRAIN
FND - FOUNDATION
FOM - FACE OF MASONRY
CL
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:3
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-102
S T
R U
C T
U R
A L
N O
T E
S
A B
B R
E V
IA
T
IO
N
S
RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
S-107
WEST ELEVATION
S-107
S-107
S-107
N O
R T
H E
L E
V A
T
IO
N
S O
U T
H E
L E
V A
T
IO
N
EAST ELEVATION
T/SLAB
0'-0"
1 2 3 4
A
D
4 4
4 4
83'-10"
S-105
S-105
S-105
2'-3" 25'-8" 27'-11" 25'-8" 2'-4"
T/
O P
N G
O P
N G
6'-10"
OPNG
12'-0" 6'-10"
3'-0"3'-0"
F6.0
F6.0
F5.0 F5.0
F5.0 F5.0
B
C
/8
/8
/8
S-104
S-105
S-105
S-105
S L O
P E
D N
147 7
C J
C J
C
JC
J
C J
C J
C
JC
JC
J
1 2 3 4
A
D
S-106
S-106
S-106
S-106
S-104
79'-3"
B
C
S L O
P E
D N
S
L O
P E
D N
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:3
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-103
F O
U N
D A
T
IO
N A
N D
R O
O F
P L
A N
S
KLI / RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
1/8" = 1'-0"S-103
1 FOUNDATION PLAN
FOOTING SCHEDULE
MARK LENGTH WIDTH THICKNESS
BOTTOM
REINFORCING
LW
BOTTOM
REINFORCING
SW
TOP
REINFORCING
LW
TOP
REINFORCING
SW COMMENTS
F5.0 5'-0" 5' - 0" 1'-4" (6) #6 (6) #6 (6) #6 (6) #6
F6.0 CONT 6' - 0" 2'-6" (6) #6 #6@12" OC (6) #6 #6@12" OC
1/8" = 1'-0"S-103
2 ROOF PLAN
KEYNOTES
KEY DESCRIPTION
1 EXISTING 4" THICK CONCRETE SLAB ON GRADE
2 EDGE OF EXISTING SLAB
3 PEMB FRAME COLUMNS
4 PEMB PORTAL FRAME COLUMNS
5 PEMB WIND COLUMN MINIMUM BASE SIZE = 8" DEPTH
6 CONTINUOUS CONCRETE CURB
7 PIPE BOLLARD, SEE 7/S-105
8 (2) PURLINS @3'-0" OC MAX
9 PEMB ROOF BRACING
10 PEMB PORTAL FRAME
11 PEMB STANDING SEAM ROOF
12 PEMB MFR TO PROVIDE 6" GUTTER WITH DOWNSPOUTS ALONG EAST AND WEST
EDGE OF STRUCTURE ABOVE VEHICLE ENTRANCE
13 6" THICK 4,000 PSI(NW 145 PCF) CONCRETE SLAB ON GRADE AT SOUTH SIDE
VEHICLE ENTRACE W/ 2% DOSE OF EUCLID EUCON SRA FLOOR. PROVIDE 6x6 W1.4xW1.4 WELDED WIRE REINFORCING (WWR) IN SHEETS NOT ROLLS CHAIRED
TO TOP OF SLAB, SEE 11/S-105.
14 GUTTER, DOWNSPOUT AND SPLASH BLOCK PER PEMB MFR.
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
M
IN
C L E
A R
A N
C E
M
IN
C
L E
A R
A N
C E
M
IN
C
L E
A R
A N
C E
56'-11"
MIN
8"
MIN
8"
MIN 1 3/4" / FT MIN 1 3/4" / FT
EQ EQ EQ EQ
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:3
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-104
P E
M B
F R
A M
E E
L E
V A
T
IO
N
RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
1/2" = 1'-0"S-104
1 TYPICAL PEMB FRAME ELEVATION
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
3"
#3@8" OC W/ 3" EMBED INTO
EXIST, EXTEND TO FAR SIDE
OF FTG AS SHOWN
EXIST
SOG
CONC FTG, SEE PLAN
SAWCUT EXIST
SLAB FOR FTG
INSTALLATION,
ROUGHEN EXIST
SURFACE TO 1/4"
AMPLITUDE ICRI
CSP 6, TYP
EXIST SOG
E Q
E Q
N T
S
E Q
E Q
N T
S
TYP
3" CLR,
C L R
C L R
N
T S
1'-6"
6"ø SCHED 40
GALV PIPE FILLED
W/ CONC
SEE PLAN
CROWN FILL TO
DRAIN
SLOPE 1/2" AROUND
PERIMETER TO DRAIN
SET POST IN MIN
3,000 PSI CONC
FINISH COAT
OSHA SAFETY
YELLOW
DOOR
NUMBER
WIDTH
12'-0"
3'-0"
HEIGHT
12'-0"
7'-0"
DOOR
THICKNESS
3"
1 3/4"
MANUFACTURER
OVERHEAD DOOR
COORPORATION
SCHLAGE LOCK
CONPANY, LLC
SERIES
626 STEEL
ROLLING DOOR
STEELCRAFT H
SERIES
NOA NUMBER
FL15960 R9
23-0821.18
REMARKS
INSULATED
WITH 10"x1"
VISION
LITES
CLOSER
(2) UL RATED STAINLESS STEEL
(304) SELF CLOSING HINGES PER
DOOR. MUST MEET ANSI/BHMA
A156 17 GRADE 1 REQUIREMENTS
LOCK TYPE
RIM EXIT DEVICE
MODEL XP98/99 (F) W/
STRIKE MODEL 909/954
BY VON DUPRIN
DESIGN
PRESSURE (PSF)
NEGATIVE
DESIGN
PRESSURE (PSF)
POSITIVE
RATED
PRESSURE (PSF)
POSITIVE
RATED
PRESSURE (PSF)
POSITIVE
S E
E S
C H
E D
U L E
12'-0"
3'-0"
DOOR FRAME TYPE DOOR TYPES
6"x30"
VIEW
LITE
A 2
2" 3'-0" 2"
INSULATED
METAL WALL
PANEL BY PEMB
CONC CURB TO BE PLACED
MONOLITHICALLY W/ FTG
EXIST
SOG
E Q
E Q
2"
#3@8" OC x3'-0" LG W/ 3"
EMBED INTO EXIST SLAB
CONC FTG,
SEE PLAN
ROUGHEN EXIST
SURFACE TO 1/4"
AMPLITUDE ICRI
CSP 6, TYP
8"
C L R
C L R
TYP
3" CLR,
(1) #5 CONT #5@12" OC W/ 90°
HOOK EA END
8" GIRT BY PEMB
FINISHED GRADE
SLOPE
SOG (REINF NOT
SHOWN), SEE PLAN
FACE OF ABUTTING
STRUCTURE
3/8" THK SONOBORN
SONOLASTIC 150
SEALANT OR
APPROVED EQUAL
1"ø BACKER ROD
COMPRESSED
INTO JT
3/4" PRE-MOLDED
JT FILLER
NOTES:
1. PROVIDE SEALANT FOR EXTERNAL JOINTS ONLY.
2. CLEAN AND PREPARE SURFACES TO RECEIVE SEALANT
IN ACCORDANCE W/ MFR'S RECOMMENDATIONS.
VAPOR RETARDER
INSULATED
METAL WALL
PANEL BY PEMB
CONC CURB, SEE
FOR REINF. REDUCE
CURB WIDTH TO 7" AT
PEMB FRAME COLUMNS
EXIST
SOG 8
7"
8" GIRT BY PEMB
/5 S-105CONNECTION BY
PEMB MFR
SEE . FOR
ADDL INFO
/5 S-105
PEMB FRAME
COLUMN
BEYOND
8" CURB
FINISHED
GRADE
SLOPE
INSULATED
METAL WALL
PANEL BY PEMB
8"
CLR
2"
EXIST
SOG
#3@8" OC STAGGERED W/ HILTI
HY200 V3 ADHESIVE EMBED
/8
ROUGHEN EXIST SURFACE TO
1/4" AMPLITUDE ICRI CSP 6, TYP
BASE ANGLE
BASE TRIM
CLOSURE
INSULATED
METAL WALL
PANEL BY
PEMB
/2
EXIST
SOG
E Q
E Q
2"
#3@8" OC x3'-0" LG W/ 3"
EMBED INTO EXIST SLAB
CONC FTG,
SEE PLAN
ROUGHEN EXIST
SURFACE TO 1/4"
AMPLITUDE ICRI
CSP 6, TYP
C L R
TYP
3" CLR,
WEST SIDE ONLY
APPROACH SLAB,
SEE PLAN
SLOPE
2"
NOTE: FOR NORTH SIDE
FINISH GRADE, SEE CIVIL
WWR, PROVIDE IN
SHEETS NOT ROLLS
PROVIDE CHAIRS OR
SUPPORT BARS TO
AVOID DRAPE
VAPOR RETARDER,
SEE PLAN
PREPARED
SUBGRADE, SEE
GEOTECHNICAL
REPORT
SOG, SEE PLAN
P L A
N
S E
E
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:4
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-105
F O
U N
D A
T
IO
N S
E C
T
IO
N S
A N
D D
E T
A
IL
S
RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
1" = 1'-0"S-105
3 FOOTING AT EXISTING SLAB ON GRADE
3/4" = 1'-0"S-105
7 PIPE BOLLARD
1/4" = 1'-0"S-105
1 DOOR SCHEDULE
1/4" = 1'-0"S-105
2 DOOR DETAILS
1" = 1'-0"S-105
5 SECTION AT CURB
3" = 1'-0"S-105
4 ISOLATION JOINT AT SOG (IJ)
1" = 1'-0"S-105
6 SECTION AT PEMB FRAME COLUMN
1" = 1'-0"S-105
8 CONCRETE CURB AT EXISTING SLAB
1 1/2" = 1'-0"S-105
9 WALL PANEL BASE DETAIL
1" = 1'-0"S-105
10 SECTION
1" = 1'-0"S-105
11 WWR AT SOG
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
1/2" OPEN 1/2" OPEN
5 1/2" 5 1/2"
STANDING SEAM
METAL ROOF
TAPE CAULK
AND FASTEN
Z CLOSURE
4 3/4"
1 3/4"
1/2"
7/8"
/4
3/ 4"
1/ 2"
SELF DRILLER
FASTENER
GABLE TRIM,
SEE 2/S5
SELF DRILLER
FASTENER
BUTYL MASTIC
TAPE
STITCH SCREW
SELF DRILLER
EAVE TRIM
INSIDE CLOSURE W/ CONT
TAPE SEAL TOP & BOTT MEMBER SCREW
INSULATED
ROOF
PANEL
POP RIVET
MEMBER
SCREW
EAVE STRUT
MEMBER SCREW
STITCH SCREW
RAKE / EAVE SPACER TRIM
EL VARIES
ENDWALL RAFTER
(SHAPE VARIES)
PURLIN
INSULATED ROOF PANEL
RAKE FASCIA
RAKE SUPPORT
RAKE SLIDE
CLOSURE
RAKE ANGLE
INSULATED
METAL WALL
PANEL
ENDWALL COLUMN
BEYOND
EAVE
STRUT
INSULATED ROOF PANEL
SLOPE DN
CLOSURE TRIM
INSULATED
METAL WALL
PANEL
CLOSURE
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:4
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-106
R O
O F
S E
C T
IO
N
S A
N D
D E
T A
IL
S
KLI / RHE
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
3" = 1'-0"S-106
1 TYPICAL RIDGE CAP (UNVENTED)
6" = 1'-0"S-106
2 TYPICAL GABLE TRIM DETAIL
6" = 1'-0"S-106
3 GABLE END DETAIL
6" = 1'-0"S-106
4 TYPICAL EAVE FLASHING
1" = 1'-0"S-106
5 ENDWALL SECTION
1 1/2" = 1'-0"S-106
6 SIDEWALL SECTION
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
Level 1 0' - 0"
Level 2 15' - 1"
A DB C
7 7
Level 1 0' - 0"
Level 2 15' - 1"
AD BC
5'-1" 3'-0" 42'-11" 3'-0" 5'-1"
Level 1 0' - 0"
Level 2 15' - 1"
1 2 3 4
7'-11" 12'-0"
7'-11"
77 7
Level 1 0' - 0"
Level 2 15' - 1"
CERTIFICATE OF AUTHORIZATION NO. 35826
PROJ No.
www.trcww.com
- TRC Worldwide Engineering All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
CHKD:
M A
R K
DRWN:
DESN:
PROJ:
Bar Measures 1 inch, otherwise drawing not to scale
C o p y ri g h t:
T e tr a T e c h
D A
T E
D E
S C
R
IP
T
IO
N B
Y
1 2 3 4 5 6 7
A
B
C
D
E
F
/7
/2
:2
:4
A M
A u to d e s k D o c s /T
R C
F lo ri d a R e v it
/2
F T
M
-R
W B
P C a n o p y R
.r v t
S-107
E L
E V
A T
IO
N
S
TRC
PSM
R A
W W
A T
E R
B O
O S
T E
R P
U M
P S
T A
T
IO
N
P A
R K
IN
G
C A
N O
P Y
100% SUBMITTAL
C O
L L
IE
R C
O U
N T
Y P
U B
L
IC
U T
IL
IT
IE
S
200-08486-24001
PSM
24FTM225
1/8" = 1'-0"S-107
1 NORTH ELEVATION
1/8" = 1'-0"S-107
2 SOUTH ELEVATION
1/8" = 1'-0"S-107
3 WEST ELEVATION
1/8" = 1'-0"S-107
4 EAST ELEVATION
KEYNOTES
KEY DESCRIPTION
7 PIPE BOLLARD, SEE 7/S-105
14 GUTTER, DOWNSPOUT AND SPLASH BLOCK PER PEMB MFR.
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the
| S-101 - STRUCTURAL NOTES & DESIGN CRITERIA |
| S-102 - STRUCTURAL NOTES & ABBREVIATIONS |
| S-103 - FOUNDATION AND ROOF PLANS |
| S-104 - PEMB FRAME ELEVATION |
| S-105 - FOUNDATION SECTIONS AND DETAILS |
| S-106 - ROOF SECTIONS AND DETAILS |
| S-107 - ELEVATIONS |
| 2025-04-09T15:15:51-0400 | |
| Paul Moerschel |
File details come from the government source that posted it. Updated .