This document package includes mechanical drawings and specifications for infrastructure upgrades at the Iowa City VA Medical Center. The drawings depict demolition and new construction plans for the ninth floor, including removal and replacement of ductwork, piping, grilles, diffusers and fan coil units serving multiple rooms. Mechanical schedules and notes provide requirements for cleaning existing ductwork, balancing dampers, coordination with other trades, insulation, and thermostats. The related federal contract opportunity is a solicitation issued by the VA Technology Acquisition Center for design-bid-build construction services for infrastructure upgrades at the Iowa City facility. The response due date is not provided.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANTRY
9W13
TR
9W100
CORRIDOR
9CW100
9W07
8"Ø x8
CH
WS
CH
WR HW
S
HW
R
CO
ND
CHWS
CHWR
HWS
HWR
COND
8"Ø
10x x8
10x x8 x8
8"Ø
OFFICE
9E34
TR
9E21
MED ROOM
9E20
8"Ø
2"
10X6
EXISTING PIPING SERVING 9E19
TO REMAIN. PROTECT DURING
CONSTRUCTION.
10"Ø
CHWS
CHWR
HWS
HWR
COND
CHWS
CHWR
HWS
HWR
COND
CHWS
CHWR
HWS
HWR
COND
1 1/2"
1 1/4"
2"
3/4"3/4"1 1/4"
1 1/2" 2" 5
MECHANICAL KEY NOTES
1. FURNISH AND INSTALL NEW FAN COIL UNIT PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
2. EXISTING DIFFUSER, REGISTER, OR GRILLE TO REMAIN.
3. CONTRACTOR TO PROVIDE NEW DIFFUSER/GRILLE AND BALANCE TO PRE-AIRFLOW
PER TEST.
4. EXISTING FAN COIL UNIT TO REMAIN.
5. CONTRACTOR TO ROUTE NEW CHILLED WATER AND CONDENSATE DRAIN PIPING TO
MAIN PIPING IN ADJACENT CORRIDOR. FIELD DETERMINE EXACT LOCATION.
MECHANICAL GENERAL NOTES
X
A. CLEAN AND SEAL ALL EXISTING DUCTWORK THAT WILL BE REUSED.
B. PROVIDE BALANCING DAMPER AT ALL SUPPLY DIFFUSER AND RETURN/EXHAUST
GRILLES WHETHER OR NOT SHOWN ON DRAWINGS.
C. COORDINATE CEILING MOUNTED GRILLES AND DIFFUSERS WITH SPRINKLER HEADS,
LIGHTING FIXTURES AND ALL CEILING MOUNTED DEVICES. REFER TO ARCHITECTURAL
CEILING GRID DRAWINGS FOR LOCATIONS.
D. CEILING ACCESS SHALL BE PROVIDED FOR ALL HVAC EQUIPMENT AND COMPONENTS
LOCATED ABOVE THE CEILING THAT REQUIRE OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION.
E. DURING CONSTRUCTION, PROVIDE TEMPORARY CLOSURES ON ALL SUPPLY AND
RETURN AIR DUCT OPENINGS BY SEALING WITH A DISPOSABLE POLYETHYLENE
SHEETING TO PREVENT CONSTRUCTION DUST FROM ENTERING DUCTWORK SYSTEM
OR AIR TERMINAL UNITS.
F. CONTRACTOR SHALL REPAIR AND/OR REPLACE ALL INSULATION AT EXISTING SHEET
METAL DUCTWORK WHICH BECOMES DAMAGED DURING CONSTRUCTION ACTIVITIES
AND SHALL REPAIR OR REPLACE ANY INSULATION AT NEW AND OLD DUCT
CONNECTIONS AND ANY MISSING OR DAMAGED INSULATION ON REUSED OR EXISTING
DUCTWORK.
G. CONTRACTOR TO REWORK AND REROUTE EXISTING DUCTWORK AND PIPING TO
ACCOMMODATE NEW CABLE TRAY. REFER ARCHITECTURAL DRAWINGS FOR EXACT
ROUTING.
H. CONTRACTOR TO PROVIDE A 14X6 SUPPLY/EXHAUST/RETURN GRILLE TO ALL
PROPOSED GRILLES UNLESS OTHERWISE NOTED.
I. CONTRACTOR TO PROVIDE WALL MOUNTED THERMOSTAT TO SERVE ALL DESIGNATED
FAN COIL UNIT. FINAL LOCATION TO BE DETERMINED DUE TO FIELD CONDITIONS.
MECHANICAL DEMOLITION
KEY NOTES
1. REMOVE EXISTING THERMOSTAT.
2. REMOVE EXISTING DIFFUSER, REGISTER, OR GRILLE AND ALL ASSOCIATED
DUCTWORK BACK TO MAIN. PATCH AND SEAL OPENING AT MAIN.
3. EXISTING FAN COIL UNIT TO REMAIN. PROTECT DURING CONSTRUCTION.
4. EXISTING DIFFUSER, REGISTER, OR GRILLE TO REMAIN.
5. EXISTING MECHANICAL PIPING SERVING EXISTING FAN COIL UNIT TO REMAIN.
PROTECT DURING CONSTRUCTION.
A. ANY DUCTWORK THAT IS EXISTING TO REMAIN, WHETHER OR NOT SHOWN ON THESE
DRAWINGS, THAT IS CRUSHED OR DAMAGED IN ITS CURRENT CONDITION OR AS A
RESULT OF CONSTRUCTION, SHALL BE REPLACED WITH NEW.
B. REMOVE ALL DUCTWORK, DIFFUSERS, GRILLES, INCLUDING ASSOCIATED INSULATION,
HANGERS, SUPPORTS, ETC. SHOWN DASHED UNLESS NOTED OTHERWISE.
C. REMOVE ALL HWS AND HWR PREHEAT COIL PIPING INCLUDING ASSOCIATED
INSULATION, HANGERS, SUPPORTS, VALVES, ETC. SHOWN DASHED UNLESS NOTED
OTHERWISE.
D. CLEAN, SANITIZE AND SEAL ALL EXISTING DUCTWORK THAT WILL BE REUSED.
E. CONTRACTOR SHALL PERFORM AN AIRFLOW TEST ON ALL OUTLETS AND INLETS
SERVING EXISTING TR SPACES FROM THE EXISTING AIR HANDLING UNITS AND REPORT
TO ARCHITECT AND ENGINEER FOR REVIEW.
MECHANICAL DEMOLITION
GENERAL NOTES
X
PANTRY
9W13
CH
WS
CH
WR
9W100
1 FCU-9W07
1600 CFM
CO
ND
CORRIDOR
9CW100
TR
9W07
CH
WS
CH
WR HW
S
HW
R
CO
ND
CHWS
CHWR
HWS
HWR
COND
8"Ø
10x x8
10x x8 x8
8"Ø x8
1 1/4"
3/4"
24x24
SA
24x24
SA
24x24
RC
9E21
TR
9E20
2 2 2
CH
WS
CH
WR HW
S
HW
R
1 FCU-9E20
1600 CFM
CO
ND
9E34
8"Ø
10X6
EXISTING PIPING SERVING 9E19
TO REMAIN. PROTECT DURING
CONSTRUCTION.
CHWS
CHWR
HWS
HWR
COND
CHWS
CHWR
HWS
HWR
COND
CHWS
CHWR
HWS
HWR
COND
2"
EXISTING PIPING SERVING 9E19
TO REMAIN. PROTECT DURING
CONSTRUCTION.
1 1/2"
1 1/4" 3/4"3/4"1 1/4"
1 1/2" 2"
1 1/4" 3/4"
12x12
SA
12x12
RC
MECHANICAL - ENLARGED PLAN -
BUILDING 01 - NINTH FLOOR
RH IL 01- M415
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \3
6C
1R
EH
R M
Io w a
C ity
, I A\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A C
AD
\3
6C -1
8-
1-
-M -F
LR
.d w g 5/
/2
3:
:0
PM
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
IOWA CITY, IA
636A8-21-700
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 18-121
3300 Dundee Rd. Suite D Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. 36C77621N281535% SCHEMATIC DESIGN SUBMISSION 07-15-21
75% DESIGN DEVELOPMENT SUBMISSION 08-19-21
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-21-21
100% CONSTRUCTION DOCUMENTS SUBMISSION 11-09-21
CONSTRUCTION BID DOCUMENTS 04-08-2022
04/08/2022
0 4'2'1' 6'3/8"=1'-0"1 BUILDING 1 - NINTH FLOOR RM 9W100 - 9W07 - DEMOLITION
NORTH
0 4'2'1' 6'3/8"=1'-0"3 BUILDING 1 - NINTH FLOOR RM 9E21 - 9E20 - 9E34 - DEMOLITION
NORTH KEY PLAN
N
0 4'2'1' 6'3/8"=1'-0"2 BUILDING 1 - NINTH FLOOR RM 9W100 - 9W07 - NEW WORK
NORTH
0 4'2'1' 6'3/8"=1'-0"4 BUILDING 1 - NINTH FLOOR RM 9E21 - 9E20 - 9E34 - NEW WORK
NORTH
ADDENDUM #1 05-27-2022