REQUEST FOR INFORMATION (RFI)
36C25018B0816
| PROJECT NUMBER: |
| 610-17-101 |
| Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner. |
| PROJECT TITLE: |
| Renovate 4th Floor, Bldg. 138 |
| PROJECT LOCATION: |
| Department of Veterans Affairs |
VA Northern Indiana HCS 1700 E. 38th Street Marion, IN 46953
| SUBMITTED BY: |
| John Johnson at Valiant Construction |
| CITY/STATE: |
| Louisville, KY |
| PHONE: |
| (502) 562-0037 ext. 2022 |
TO:
Felecia Beamen, Contracting Officer Department of Veterans Affairs Network 10 Contracting Office
8888 Keystone Crossing, Suite 1100
Indianapolis, IN 46240 Felecia.Beamen@va.gov
| RFI NO.: three (3) |
| DATE: 9/24/18 |
| SPEC/DWG. REFERENCE(s): |
REPLY NEEDED BY: 9/26/18
INFORMATION NEEDED:
1. On Sheet A-104.2, Rooms 446B “CT”, 450 and 452 “Oral Surg.” show Lead lined partitions for the interior walls. The door 446B is shown to be Lead Lined on the Door Schedule Dwg A-601. However, doors 450 and 452 do not have the designation on the Door Schedule. According to Sheet A-701 on the radiation shielding General Notes for partitions and doors located in a Room type 5 “Oral Surgery Room”, the doors shall have a Lead line thickness of 1mm. Should doors 450 and 452 be Lead Lined ?
2. On Equipment Schedule Dwg Q-100, Please provide the responsibility of who is to provide and install items: _0032, _0033, _0034, and A5220 not listed in the Acquisition/Installation column.
REPLY:
RFI’s will be answered by amendment(s) posted to fbo.gov.
1. Yes, doors 450 and 542 to Oral Surgery rooms shall receive lead lining as referenced on line 5 of requirements, on sheet A-701 Wall Types.
2. Typical equipment ACQ/INS codes to be applied to sheet Q-100, Q-101 as well as Q601/Q-602:
a. _0032: VV
b. _0033: VV
c. _0034: VV
d. A5220: CC