This is a Golightly Assessment Report prepared for Detroit Public Schools regarding roof conditions at the Golightly Education Center located at 5536 St. Antoine Street in Detroit, Michigan. The visual inspection conducted on March 9, 2026, evaluated 21 distinct roof areas (labeled A through U) to determine remaining surface life and identify necessary replacement requirements. The facility contains multiple roof system types, including built-up roofs (BUR) with aggregate surfaces over concrete decks, modified bitumen systems over wood decks, and varying insulation configurations. The assessment recommends complete roof system removal and replacement for 14 roof areas (A, B, C, E, F, G, H, I, J, K, L, S, T, and U) with new self-adhering underlayment, polyiso insulation layers, and fully adhered 60-mil EPDM membranes. Roof Area D, situated over a steel deck, requires a modified replacement approach. Roof Areas M, N, O, P, Q, and R were inspected but specific replacement recommendations were not detailed in the summary sections.
The estimated construction cost for the recommended R-30 insulation system with fully-adhered 60-mil EPDM membrane is $792,693.00. The report documents that all evaluated roof areas were installed prior to 1995, with visual evidence of severe deterioration including membrane damage, felts exposure, blistering, failed repairs, perimeter edge deterioration, and flashing failures. Roof heights range from 12 feet to 55 feet, with structural slopes varying from 1/8 inch per foot to 2:12 per foot. Drainage systems consist of roof drains, gutters, or eave systems depending on the specific roof area. The assessment assumes no maintenance has been performed on the existing systems in determining the remaining life estimates.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Detroit Public Schools – Golightly Education Center
5536 St. Antoine Street Detroit, MI 48202
March 9th, 2026
Detroit Public Schools – Golightly Education Center
Table of Contents
Executive Summary Page 3
Roof Plan Page 4
Roof Area Descriptions Page 5
Roof Area Photos Page 12
EXECUTIVE SUMMARY
On March 9, 2026 a visual inspection of the existing roof system was performed. The purpose of this inspection was to determine the estimated surface life left of the existing roof system. Roof Areas A, B, C, E, F, G, H, I, J, K, L, S, T & U existing systems consisted of an existing BUR aggregate surface, 1-inch fiber glass insulation over concrete deck. Roof Area D existing system consisting of a BUR aggregate surface, 1/2-inch perlite, 2-1/2 inch polyiso over a steel deck. Roof Areas N, O, P, Q & R consisting of 2-ply modified bitumen with granular surface, 1-inch fiberglass over wood deck.
Observations & Recommendations:
Roof Areas A, B, C, E, F, H, K, L & T: Remove existing roof system down to the existing structural concrete deck. Install new self-adhering underlayment, 2-layers of 2-1/2 inch polyiso, 1/2-inch high density polyiso and a fully adhered 60-mil EPDM membrane.
Roof Area D: Remove existing roof system down to the existing structural steel deck. Install one layer of 2-1/2 inch polyiso, 1/8-inch per foot tapered polyiso, 1/2-inch high density polyiso and fully-adhered 60-mil EPDM membrane.
Roof Areas G, I, J, S & U: Remove existing roof system down to the existing structural Concrete deck. Install new self-adhering underlayment, one layer of 2-1/2 inch polyiso, 1/8-inch per foot tapered polyiso, 1/2-inch high density polyiso and fully-adhered 60-mil EPDM membrane.
Estimated Construction Costs:
R-30 Insulation System with a fully-adhered 60-mil EPDM: $792,693.00
ROOF PLAN:
Note: Remaining life of existing roof systems is based on the estimated age of the roofs, visual inspection and assuming no maintenance being performed.
ROOF AREA DESCRIPTIONS:
Roof Area ID: A
Size: 11,590 sf.
Year Installed: Pre 1995
Height: 45 ft
Structural Slope: 5/8” per foot
Drainage: Roof Drains/Gutter
Roof Area ID: B
Size: 2,914 sf.
Year Installed: Pre 1995
Height: 28 ft.
Structural Slope: 1/4" per foot
Drainage: Roof Drains
Roof Area ID: C
Size: 2,914 sf.
Year Installed: Pre 1995
Height: 28 ft.
Structural Slope: 1/4" per foot.
Roof Area ID: D
Size: 3,354 sf.
Year Installed: Pre 1995
Height: 20 ft
Structural Slope: 1/8 per foot min.
Drainage: Gutter
Roof Area ID: E
Size: 783 sf.
Year Installed: Pre 1995
Height: 55 ft.
Structural Slope: 1/4 per foot min.
Roof Area ID: F
Size: 626 sf.
Year Installed: Pre 1995
Height: 28 ft.
Structural Slope: 1/8” per foot.
Roof Area ID: G
Size: 896 sf.
Year Installed: Pre 1995
Height: 20 ft
Structural Slope: 1/8” per foot
Roof Area ID: H
Size: 1,462 sf.
Year Installed: Pre 1995
Height: 12 ft.
Roof Area ID: I
Size: 40 sf.
Year Installed: Pre 1995
Height: 12 ft.
Roof Area ID: J
Size: 317 sf.
Year Installed: Pre 1995
Height: 12 ft.
Structural Slope: 1/8” per foot .
Roof Area ID: K
Size: 99 sf.
Year Installed: Pre 1995
Height: 48 ft.
Structural Slope: 1/4” per foot
Drainage: Eave
Roof Area ID: L
Size: 80 sf.
Year Installed: Pre 1995
Height: 21 ft.
Roof Area ID: M
Size: 124 sf.
Year Installed: Pre 1995
Height: 14 ft.
Structural Slope: 2:12 per foot
Roof Area ID: N
Size: 207 sf.
Year Installed: Pre 1995
Height: 14 ft.
Roof Area ID: O
Size: 70 sf.
Year Installed: Pre 1995
Height: 14 ft.
Roof Area ID: P
Year Installed: Pre 1995
Height: 14 ft.
Roof Area ID: Q
Year Installed: Pre 1995
Height: 14 ft.
Roof Area ID: R
Size: 36 sf.
Year Installed: Pre 1995
Height: 14 ft.
Roof Area ID: S
Size: 48 sf.
Year Installed: Pre 1995
Height: 12 ft.
Drainage: Roof Drain
Roof Area ID: T
Size: 1,310 sf.
Year Installed: Pre 1995
Height: 12 ft.
Structural Slope: 1/8” per foot.
Roof Area ID: U
Size: 80 sf.
Year Installed: Pre 1995
Height: 36 ft.
Drainage: Gutter
ROOF AREA PHOTOS:
Failed repair Severe membrane deterioration/felts showing
Severe membrane
Large repair along gutter edge
Membrane blister
Membrane & flashing deterioration
Repairs made to masonry wall overview
Severe deterioration along perimeter edge
Failed repairs to masonry wall