27-0001 Attachment C - Davison Drawings IFB.pdf
PDF 3 MB Posted
- Solicitation number
- RFP DET 260000002534 1
- Issued by
- Wayne County, Detroit City, Michigan
About this file
This document is a comprehensive set of construction drawings and specifications for the roof replacement project at Davison Elementary-Middle School in Detroit, Michigan, prepared for Detroit Public Schools by Testing Engineers & Consultants. The project encompasses roof replacement work across nine distinct roof areas (A through I) totaling approximately 32,719 square feet, including removal of existing built-up roofing systems down to structural decks, installation of new polyisocyanurate insulation layers ranging from 1 to 5 inches depending on area, placement of 1/2-inch high-density polyiso cover boards, and application of fully-adhered 60-mil EPDM roofing membranes with 6-inch seams. Roof Area H requires a complete asphalt shingle system, while other areas receive the EPDM system. The drawings detail extensive flashing requirements including curb flashings, roof hatch replacements, roof drain sumps, tubular penetration flashings, parapet wall treatments, and gutter edge details, along with specifications for wood blocking, sealant applications, and stone coping joint resealing. Acceptable EPDM manufacturers include Carlisle, Johns Manville, and Elevate (Firestone), with an alternate price option required for a 20-year "Total System Warranty."
The specifications require contractor verification of existing site conditions including building dimensions, roof area dimensions, drainage component locations, roof penetrations, existing roof system composition, and repair quantities prior to proposal submission. Contractors must comply with all applicable federal, state, and local codes and regulations and notify the owner of any conflicts between design specifications and manufacturer requirements or governing ordinances. The contractor is responsible for asbestos laboratory analysis per referenced sections, removal and disposal of non-friable asbestos if present, temporary displacement and reinstallation of rooftop equipment by appropriately licensed contractors, closure of abandoned mechanical, plumbing, and electrical openings, and implementation of debris containment measures. A tapered drainage sump system with minimum 1/4-inch per foot slope must be created at roof drain locations, existing curbs must be raised to achieve minimum 8-inch flashing heights, existing roof hatches must be replaced with new units featuring integrated safety bars and internal ladders, and existing stone coping joints require raking and resealing.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLIENT
PROFESSIONAL
PROJECT
DESCRIPTIONDATE
ISSUE
Drawn By: PD
Checked By: SH
SHEET TITLE
File Name:
STAMP
SHEET 01 OF 05
TITLE SHEET
PROJECT LOCATION MAP
ROOF PLAN SYMBOL LEGEND:
ORD
INS
C
S SKYLIGHT CURB
CAPPED CURB
ROOF HATCH
ROOF CURB
SUPPORT CURBS
ROOF DRAIN
ROOF DRAIN WITH INSERT
OVERFLOW ROOF DRAIN
THROUGH-WALL SCUPPER
OVERFLOW ROOF SCUPPER
ORS
SANITARY VENT
TUBULAR PENETRATION
HOT STACK
PIPE CHASE BOX
PERIMETER OR CURBED EDGE
PARAPET WALL OR AREA DIVIDER
EXPANSION JOINT
GUTTER EDGE
PITCH PAN
ROOF-TO-WALL TRANSITION
AREA TRANSITION
SATELLITE DISH ON ROOF
WALKPADW
WALKWAY
SUPPLY OR CONDENSATE LINE
LADDER
SLOPE DIRECTION
RIDGE LINE
DUCT WORK
R RAISED EQUIPMENT
DOWNSPOUT SPLASHBLOCKS
SUMP AREA
DOWNSPOUTCHIMNEY
THROUGH-FASCIA SCUPPER
SCUPPER WITH CONDUCTOR BOX DETAIL NUMBER CALLOUT
SHEET NUMBER CALLOUT
SCOPE OF REPLACEMENT MAP
GENERAL NOTES:
1. DRAWINGS ARE PRODUCED AT ARCH D (24-INCH BY 36-INCH) SIZE.
PLEASE NOTE AND VERIFY THE SCALE INDICATED ON EACH DRAWING.
NOTE THAT ROOF PLANS AND OTHER PROJECT DRAWINGS PRODUCED
ON OTHER PAPER SIZES MAY NOT BE CORRECTLY SCALED.
2. ALL COMPONENTS SHOWN ON PROJECT DRAWINGS ARE NEW UNLESS
SPECIFICALLY INDICATED AS EXISTING.
3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXISTING
PROJECT SITE CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT
LIMITED TO: BUILDING DIMENSIONS AND PROPOSED PROJECT STAGING
LOCATIONS, ROOF REPLACEMENT AREA DIMENSIONS, ROOF DRAINAGE
COMPONENT LOCATIONS, ROOF PENETRATION LOCATIONS, EXISTING
ROOF SYSTEM COMPONENT MAKE-UP AND THICKNESS, AND PROJECT
REPAIR QUANTITIES (IF APPLICABLE). THE CONTRACTOR SHALL VISIT
AND BECOME FAMILIAR WITH THE SITE AND BUILDING PRIOR TO
PROPOSAL SUBMISSION. INCLUDE THE COST OF ALL WORK DESCRIBED
IN THE BIDDING DOCUMENTS AND THAT IS REQUIRED OR REASONABLY
IMPLIED TO ACHIEVE THE DESIGN INTENT OF THE BIDDING DOCUMENTS.
NOTIFY THE ROOF CONSULTANT OF ANY CONFLICTS BETWEEN EXISTING
CONDITIONS AND THE NEW WORK, OF ANY OMISSIONS OR CONFLICTS IN
THE DRAWINGS AND ANY RESTRICTIONS RELATED TO THE EXECUTION
OF THE WORK INCLUDING THE COORDINATION WITH OTHER TRADES.
4. PRODUCTS PROPOSED FOR USE AND PROJECT WORK SHALL BE IN
ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL
GOVERNING ORDINANCES, CODES AND REGULATIONS. NOTIFY THE
OWNER IMMEDIATELY OF CONFLICTS BETWEEN THE SPECIFIED
PRODUCTS AND/OR PROJECT WORK REQUIREMENTS AND CODES,
ORDINANCES AND/OR REGULATIONS.
5. IF DISCREPANCIES ARE DISCOVERED WITHIN THE PROJECT MANUAL OR
DRAWINGS; THE OWNER, NOT THE CONTRACTOR, SHALL DETERMINE
THE INTENT OF THE DESIGN AND PROVIDE CLARIFICATION. NO
ALLOWANCE SHALL BE MADE FOR CONTRACTOR MISINTERPRETATION
OR IMPLIED MISINTERPRETATION OF THE PROJECT MANUAL AND
DRAWINGS.
6. REFER TO THE PROJECT MANUAL AND ROOFING SYSTEM
MANUFACTURER WRITTEN INSTRUCTIONS FOR FURTHER CLARIFICATION
OF PROJECT REQUIREMENTS. NOTIFY THE OWNER IMMEDIATELY OF
CONFLICTS BETWEEN THE SPECIFIED DESIGN REQUIREMENTS AND THE
WRITTEN REQUIREMENTS AND RECOMMENDATIONS OF THE ROOFING
SYSTEM MANUFACTURER.
7. CLOSE AND SEAL ABANDONED OPENINGS TO MATCH EXISTING
ADJACENT SURFACES WHERE MECHANICAL, PLUMBING, AND/OR
ELECTRICAL ITEMS ARE REMOVED.
8. CONTRACTOR SHALL TAKE NORMAL PRECAUTIONS SO THAT DEBRIS,
ROOFING MATERIAL, ETC., DOES NOT FALL INTO THE BUILDING OR ON
EQUIPMENT PER SECTIONS 014000 AND 015000.
SUMMARY OF ROOF REPLACEMENT WORK - AREAS A-I
A. ASBESTOS LABORATORY ANALYSIS REPORT: REFER TO SECTION 022623 FOR INFORMATION
RELATING TO THE LOCATION OF ACM, IF APPLICABLE, WITHIN PROJECT AREAS. IF POSITIVE, REFER
TO SECTIONS 013543 AND 028233 FOR PROCEDURES AND REQUIREMENTS RELATED TO THE
REMOVAL AND DISPOSAL OF NON-FRIABLE ASBESTOS RELATED TO THIS PROJECT.
B. ROOF REMOVAL AND SUBSTRATE PREPARATION: REMOVE EXISTING ROOF SYSTEM DOWN TO THE
STRUCTURAL DECK, INCLUDING ROOF MEMBRANE(S), AND UNDERLYING INSULATION,
UNDERLAYMENTS, AND ADDITIONAL ROOF MEMBRANES. INSPECT THE EXISTING STRUCTURAL
DECK, AND INFORM THE OWNER IMMEDIATELY OF OBSERVED DAMAGE AND OR DETERIORATION.
TEMPORARILY DISPLACE ROOFTOP EQUIPMENT AS NECESSARY TO COMPLETE THE SPECIFIED
WORK. REFER TO SECTIONS 024100 & 024102.
C. AFTER ROOF REMOVAL AND INSPECTION OF THE EXISTING STRUCTURAL DECK AND PERIMETER
WOOD BLOCKING, PERFORM REPAIRS TO THE STRUCTURAL DECK, AS DETERMINED NECESSARY
BY THE OWNER. REFER TO SECTIONS 030150 & 061516 & . REPLACE DAMAGED OR DETERIORATED
WOOD BLOCKING, AS DETERMINED NECESSARY BY THE OWNER. REFER TO SECTION 061053.
D. PROVIDE REQUIRED WOOD BLOCKING WHERE INDICATED ON THE PROJECT DRAWINGS. REFER TO
SECTION 061053.
E. ROOF AREAS A, B, C, D, E, F, H & I: PROVIDE AN UNDERLAYMENT CONSISTING OF A
SELF-ADHERING MEMBRANE. PRIOR TO APPLICATION, PREPARE AND PRIME THE DECK AS
REQUIRED BY THE ROOFING MEMBRANE MANUFACTURER. REFER TO SECTION 072215.
F. ROOF AREAS A, B, C & D: PROVIDE TWO LAYERS OF 2-1/2 INCH POLYISOCYANURATE INSULATION (5-INCHES TOTAL). IF INDICATED ON THE PROJECT DRAWINGS, PROVIDE INSULATION SADDLES
AND CRICKETS WHERE SHOWN. REFER TO SECTIONS 072221 FOR ADDITIONAL INSULATION
PRODUCT AND INSTALLATION REQUIREMENTS.
G. ROOF AREAS E, F & I: PROVIDE A TAPERED POLYISOCYANURATE INSULATION SYSTEM WITH AN INSULATION SYSTEM SLOPE OF 1/8-INCH PER FOOT, AND A STARTING THICKNESS OF 1/2-INCH
OVER A BASE LAYER OF 2-1/2 INCH POLYISOCYANURATE INSULATION. IF INDICATED ON THE
PROJECT DRAWINGS, PROVIDE INSULATION SADDLES AND CRICKETS WHERE SHOWN. REFER TO
SECTION 072221 FOR ADDITIONAL INSULATION PRODUCT AND INSTALLATION REQUIREMENTS.
H. ROOF AREA G: PROVIDE A LAYER OF 1-INCH POLYISOCYANURATE INSULATION. IF INDICATED ON
THE PROJECT DRAWINGS, PROVIDE INSULATION SADDLES AND CRICKETS WHERE SHOWN. REFER
TO SECTIONS 072221 FOR ADDITIONAL INSULATION PRODUCT AND INSTALLATION REQUIREMENTS.
I. ROOF AREA H: PROVIDE A COMPLETE ASPHALT SHINGLE ROOF SYSTEM; INCLUDING
UNDERLAYMENT, SELF-ADHERING MEMBRANE (ON ENTIRE ROOF SURFACE), ASPHALT SHINGLES,
AND BITUMINOUS AND SHEET METAL FLASHING ACCESSORIES. REFER TO SECTION 073113 FOR
PRODUCT AND INSTALLATION REQUIREMENTS.
J. ROOF AREAS A, B, C, D, E, F, G & I: PROVIDE A 1/2-INCH HIGH DENSITY POLYISO COVER BOARD OVER THE UNDERLYING INSULATION. REFER TO SECTIONS 072221 FOR ADDITIONAL PRODUCT AND
INSTALLATION REQUIREMENTS.
K. ROOF AREAS A, B, C, D, E, F, G & I: PROVIDE A FULLY-ADHERED, NOMINAL 60-MIL EPDM ROOF SYSTEM. AFTER INSTALLATION OF SPECIFIED INSULATION AND COVER BOARD, INSTALL THE EPDM
ROOFING MEMBRANE IN BONDING ADHESIVE. PROVIDE EPDM AND SHEET METAL FLASHINGS AS
SPECIFIED. PROVIDE AN ALTERNATE PRICE FOR A 20-YEAR, “TOTAL SYSTEM WARRANTY” FOR THE
ROOF SYSTEM. REFER TO SECTIONS 075323 AND 076205 FOR PRODUCT AND INSTALLATION
REQUIREMENTS.
1. ACCEPTABLE MANUFACTURERS:
a. CARLISLE
b. JOHNS MANVILLE
c. ELEVATE (FIRESTONE)
L. PROVIDE SEALANTS AT LOCATIONS INDICATED ON THE PROJECT DRAWINGS. REFER TO SECTION 079201.
M. EXISTING STONE COPINGS: CONTRACTOR SHALL RAKE AND RESEAL ALL VERTICAL AND
HORIZONTAL STONE COPING JOINTS.
INDEX OF DRAWINGS:
SHEET 01 OF 05
SHEET 02 OF 05
SHEET 03 OF 05
SHEET 04 OF 05
SHEET 05 OF 05
TITLE SHEET
GENERAL INFORMATION SHEET 01 OF 01
ROOF PLAN - AREAS A-I
ROOF PLAN DETAILS 01-09
ROOF PLAN DETAILS 10-15
XX
X
Testing Engineers & Consultants
1343 Rochester Road Troy, MI 48083
75% Design Review Set
Detroit Public Schools
3011 W. Grand Blvd Detroit, MI 48202
03-25-2026
Davison Elementary-Middle School
2800 E. Davison Detroit, MI 48212 roof hatch ladder replacement down ladder to area E possible down ladder to area D no building ladder for boiler building
PROFESSIONAL
PROJECT
DESCRIPTIONDATE
ISSUE
Drawn By: PD
Checked By: SH
SHEET TITLE
File Name:
STAMP
SHEET 02 OF 05
GENERAL
INFORMATION
SHEET 01 OF 01
PROJECT SPECIFIC KEY NOTES:
PROVIDE TAPERED DRAINAGE SUMPS AT ROOF DRAIN LOCATIONS INDICATED ON THE ROOF PLAN.
REFER TO DETAILS 03 AND SECTION 072221 FOR PRODUCT AND INSTALLATION REQUIREMENTS.
EXISTING CURBS: CONTRACTOR SHALL RAISE CURBS AS NEEDED TO ACHIEVE A MINIMUM FLASHING HEIGHT OF 8-INCHES. WHERE EXISTING CONDITIONS DO NOT ALLOW FOR THE RAISING OF CURBS, CONTRACTOR SHALL SEAL THE TOP EDGE OF THE FLASHING MEMBRANE AND TERM BAR WITH
MEMBRANE MANUFACTURER'S LIQUID APPLIED FLASHING SYSTEM.
AT LOCATIONS INDICATED ON THE ROOF PLAN, INSTALL SPECIFIED WALKWAY PAD APPROVED BY THE
ROOFING MEMBRANE MANUFACTURER. REFER TO THE ROOFING MEMBRANE SECTION FOR PRODUCT
AND INSTALLATION REQUIREMENTS.
EXISTING STONE COPINGS - CONTRACTOR SHALL RAKE & RESEAL ALL VERTICAL & HORIZONTAL
JOINTS - REFER TO DETAIL 07 & SECTION 079201
EXISTING ROOF HATCH - CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING ROOF HATCH AND CURB - PROVIDE NEW ROOF HATCH WITH INTEGRATED, LADDER-UP SAFETY BAR & INTERNAL WALL
MOUNTED LADDER - REFER TO SECTION 075323 FOR PRODUCT REQUIREMENTS.
EXISTING CONCRETE CRICKETS & SADDLES - CONTRACTOR SHALL PROVIDE ADDITIONAL TAPERED
INSULATION TO ENHANCE CONCRETE CRICKETS & SADDLES FOR BETTER DRAINAGE.
EXISTING CLAY TILE COPINGS - CONTRACTOR TO REMOVE AND DISPOSE OF EXISTING CLAY TILE
COPING CAPS - PROVIDE THE NECESSARILY SUPPORT TO INSTALL WOOD NAILERS AND METAL
COPING CAPS - REFER TO DETAIL 09.
EXISTING CONDUIT/PIPING: CONTRACTOR SHALL TEMPORARILY DISPLACE TO ALLOW FOR
INSTALLATION OF NEW ROOFING SYSTEM - REINSTALL AND SET ON PRE-FABRICATED PIPE SUPPORTS
SET ON WALK PADS - REFER TO SECTION 075323 FOR PRODUCT REQUIREMENTS.
ROOF AREA H - CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING FASCIA BOARD - PROVIDE
ALL NEW WOOD FASCIA BOARD.
A
Testing Engineers & Consultants
1343 Rochester Road Troy, MI 48083
COVER BOARD, INSULATION & UNDERLAYMENT ATTACHMENT
REQUIREMENTS:
PERIMETER AND CORNER DIMENSIONS OF A ROOF LESS THAN OR EQUAL TO 60 FEET IN HEIGHT ARE
DEFINED AS THE SMALLER OF:
· 0.1 TIMES THE BUILDING LESSER PLAN DIMENSION
· 0.4 TIMES THE EAVE HEIGHT
· THE TWO ABOVE DIMENSIONS ARE SUBJECT TO A MINIMUM WIDTH OF 4 PERCENT THE PLAN
DIMENSION OR 3 FEET
FIELD OF ROOF PERIMETERS CORNERS
COVER BOARD ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
12" O.C.
UNDERLAYMENT PRIME DECK (IF REQ'D
BY MANUFACTURER
AND ADHERE.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
6" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
4" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
12" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
6" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
4" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
12" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
6" O.C.
ADHERED IN TWO-PART
URETHANE FOAM
ADHESIVE 3/4" BEADS
4" O.C.
PRIME DECK (IF REQ'D
BY MANUFACTURER
AND ADHERE.
PRIME DECK (IF REQ'D
BY MANUFACTURER
AND ADHERE.
TOP INSULATION
LAYER
BOTTOM AND
INTERMEDIATE
INSULATION LAYER(S)
ATTACHMENT FOR
CONCRETE DECKS
EXISTING CONDITIONS:
NOTE: THE INFORMATION BELOW IS BASED ON RANDOM, LIMITED TEST CORES
MADE INTO THE ROOFING SYSTEM. CONDITIONS AT THE TEST CORE
LOCATIONS MAY NOT BE REPRESENTATIVE OF THE ENTIRE ROOF AREA.
IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
EXISTING ROOF SYSTEM COMPONENTS AND SLOPE.
ROOF AREAS A, B, C & D
· BUR AGGREGATE
· 1-INCH FIBERGLASS
· HEAVY ASPHALT MOPPING
· CONCRETE DECK - 1/4-INCH OR GRATER PER FOOT SLOPE IN DECK
PROPOSED ROOF SYSTEMS:
NOTE: REFER TO SECTION 011000 - SUMMARY OF WORK, AND RELATED PROJECT
MANUAL SECTIONS FOR ADDITIONAL PRODUCT AND INSTALLATION
REQUIREMENTS FOR THE PROJECT.
PROPOSED ROOF SYSTEM - ROOF AREAS A, B, C & D (APPROX. 29,295 SF.):
· FULLY-ADHERED 60-MIL EPDM WITH 6-INCH SEAMS
· 1/2-INCH HIGH DENSITY POLYISO COVERBOARD - ADHERED AS SPECIFIED
· 2-1/2 INCH POLYISOCYANURATE INSULATION - ADHERED AS SPECIFIED
· 2-1/2 INCH POLYISOCYANURATE INSULATION - ADHERED AS SPECIFIED
· SELF-ADHERING UNDERLAYMENT
· EXISTING CONCRETE DECK - 1/4-INCH OR GREATER PER FOOT SLOPE IN DECK
Detroit Public Schools
3011 W. Grand Blvd Detroit, MI 48202
RECOMMENDED MAXIMUM L:W RATIOS FOR SADDLES AND CRICKETS
ROOF SLOPE SADDLE MATERIAL
SLOPE L:W RATIO
1/8 1/4 2:1
1/4 1/2 3:1
1/2 1 4:1
L
W
CRICKET DRAIN SUMP AREA
SADDLE
ROOF CURB
CRICKETS MUST BE USED ON THE UPHILL SLOPE OF
ANY CURB THAT IS GREATER THAN 24-INCHES
L
W
B
C
D
E
F
G
H
PROPOSED ROOF SYSTEM - ROOF AREAS E, F & I (APPROX. 2,625 SF.):
· FULLY-ADHERED 60-MIL EPDM WITH 6-INCH SEAMS
· 1/2-INCH HIGH DENSITY POLYISO COVERBOARD - ADHERED AS SPECIFIED
· 1/8-INCH PER FOOT TAPERED POLYISOCYANURATE INSULATION WITH A 1/2-INCH
STARTING THICKNESS- ADHERED AS SPECIFIED
· 2-1/2 INCH POLYISOCYANURATE INSULATION - ADHERED AS SPECIFIED
· SELF-ADHERING UNDERLAYMENT
· EXISTING CONCRETE DECK - 1/8-INCH OR PER FOOT SLOPE IN DECK
75% Design Review Set03-25-2026
Davison Elementary-Middle School
2800 E. Davison Detroit, MI 48212
I
PROPOSED ROOF SYSTEM - ROOF AREA G (APPROX. 299 SF.):
· FULLY-ADHERED 60-MIL EPDM WITH 6-INCH SEAMS
· 1/2-INCH HIGH DENSITY POLYISO COVERBOARD - ADHERED AS SPECIFIED
· 1-INCH POLYISOCYANURATE INSULATION - ADHERED AS SPECIFIED
· SELF-ADHERING UNDERLAYMENT
· EXISTING CONCRETE DECK - 1/8-INCH OR PER FOOT SLOPE IN DECK
PROPOSED ROOF SYSTEM - ROOF AREA H (APPROX. 100 SF.):
· SPECIFIED ASPHALT SHINGLES
· SELF-ADHERING UNDERLAYMENT
· EXISTING WOOD DECK - 4:12 SLOPE IN DECK
ROOF AREAS E, F, G & I
· BUR AGGREGATE
· 1-INCH FIBERGLASS
· HEAVY ASPHALT MOPPING
· CONCRETE DECK - 1/8-INCH OR GRATER PER FOOT SLOPE IN DECK
ROOF AREA H
· ASPHALT SHINGLES
· UNDERLAYMENTS
· WOOD DECK - 4:12 SLOPE IN DECK
ROOF PLAN - AREAS A-I
PROFESSIONAL
PROJECT
DESCRIPTIONDATE
ISSUE
Drawn By: PD
Checked By: SH
SHEET TITLE
File Name:
STAMP
SHEET 03 OF 05
ROOF PLAN
AREAS A-I
Testing Engineers & Consultants
1343 Rochester Road Troy, MI 48083
Detroit Public Schools
3011 W. Grand Blvd Detroit, MI 48202
76' 178'-6"
23'
13'-6"
25'-6"
62'
44'
10'
16'
4'-6"
43'
41'-6"
59'
12'
29'-6" 16'
20'
12'-6"
30' 40'
7'-6"
5'-6"
33'
11'
26'
14'-6"
12'
6'-6"
104'-6"
149'-6"102'-6"
23'-6"
8'8'
12'-6"
50'
23'-6"
1'-6"
75% Design Review Set03-25-2026
Davison Elementary-Middle School
2800 E. Davison Detroit, MI 48212
04 TYP.
3 SIDES
04 TYP.
04TYP.
04 TYP.
04 TYP.
04TYP.
04 TYP.
04 07
04 TYP.
TYP.
4 SIDES
04 07
TYP.
4 SIDES
ROOF AREA B
3,594 SF.
ROOF AREA A
11,125 SF.
ROOF AREA I
1,977 SF.
ROOF AREA C
13,951 SF.
ROOF AREA D
625 SF.
ROOF AREA G
299 SF.
ROOF AREA H
100 SF.
TYP.
4 SIDES
ROOF AREA F
493 SF.
ROOF AREA E
155 SF.
ATYP. ATYP.
ATYP.
ATYP.
BTYP.
B
C
E
G
FTYP.
FTYP.
D
D
D
D
D
I
WOOD BLOCKING - IF NECESSARY TO ACHIEVE
8-INCH MINIMUM FLASHING HEIGHT. SECURE TO
SUBSTRATE 18-INCHES O.C. AND WITHIN 2-INCHES
OF EACH END.
EXISTING ROOFTOP UNIT - TEMPORARILY DISPLACE
TO ALLOW FOR INSTALLATION OF NEW ROOF
SYSTEM AND RELATED FLASHING COMPONENTS.
REINSTALL TO ORIGINAL POSITION AFTER
COMPLETION OF WORK. RE-SECURE TO EXISTING
CURB WITH GASKETED FASTENERS 12-INCHES O.C.
MAX., AND WITHIN 2-INCHES OF EACH CORNER.
CURB INSULATION - IF EXISTING
CURB IS INSULATED, AND
EXISTING INSULATION CANNOT BE
SALVAGED, PROVIDE CURB
INSULATION TO MATCH EXISTING.
PREFINISHED 24 GA. GALV. STEEL
SURFACE-MOUNTED
COUNTERFLASHING. SECURE TO
EXISTING CURB COUNTERFLASHING
AS SHOWN USING GASKETED
FASTENERS 12-INCHES O.C. MAX.,
AND WITHIN 2-INCHES OF EACH END.
SELF-ADHERING MEMBRANE
COMPATIBLE WITH EXISTING
SUBSTRATE(S)
REFER TO DETAILS BELOW FOR
FLASHING REQUIREMENTS.
ALT. COUNTERFLASHING NO. 2
FOR USE WHERE APPROVED AND WHERE
EXISTING CURB IS SEPARATED FROM THE
EXISTING ROOFTOP PENETRATION
BUTYL TAPE - INSTALL BEHIND
COUNTERFLASHING
SEALANT
NOTE: SECURE TOP EDGE OF FLASHING USING AN
ALUMINUM TERMINATION BAR SECURED
12-INCHES O.C., MAX., AND WITHIN
2-INCHES OF EACH END. PRIOR TO
TERMINATION BAR INSTALLATION, INSTALL
MANUFACTURERS RECOMMENDED
SEALANT BEHIND FLASHING WHERE
TERMINATION BAR WILL BE PLACED. SEAL
TOP EDGE OF FLASHING AND TERMINATION
BAR AFTER INSTALLATION.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING
CORNERS FOLLOWING THE
RECOMMENDATIONS AND REQUIREMENTS
OF THE ROOFING MEMBRANE
MANUFACTURER. PROVIDE "T-JOINT
COVERS" AT THE BASE OF THE CURB AT
FLASHING PIECE INTERSECTIONS.
ALT. VERTICAL MEMBRANE TERMINATION
FOR USE WHERE HORIZONTAL TERMINATION OF
EPDM MEMBRANE IS NOT POSSIBLE
4" M
IN
4" M
IN
8" M
IN
FL
AS
H
IN
G H
EI
G
H T
NOTE: DIS-CONNECTIONS AND RE-CONNECTIONS
OF ELECTRICAL, PLUMBING OR
MECHANICAL CONNECTIONS RELATED TO
THE DISPLACEMENT AND RE-INSTALLATION
OF ROOFTOP UNITS SHALL BE PERFORMED
BY A CONTRACTOR LICENSED TO PERFORM
SUCH WORK. COORDINATE THIS WORK
WITH THE OWNER.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT
SHOWN FOR CLARITY.
EXISTING STRUCTURAL DECK
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING STRIP WITH
FACTORY-LAMINATED SEAM TAPE. PRIME EPDM
MEMBRANE PRIOR TO APPLICATION TO REINFORCED
FASTENING STRIP.
FASTENERS AND 2-INCH PLATES, 6-INCHES O.C. MAX.
EPDM MEMBRANE, 8" MIN. HEIGHT, FULLY
ADHERED TO CURB. REFER TO NOTE
REGARDING SECUREMENT OF MEMBRANE.
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING STRIP WITH
FACTORY-LAMINATED SEAM TAPE. PRIME EPDM
MEMBRANE PRIOR TO APPLICATION TO REINFORCED
FASTENING STRIP.
BATTEN STRIP OR FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
1-1/4" 1/2"
APPR
O
X.
2-3/4"
EPDM MEMBRANE, FULLY ADHERED TO CURB. 8" MIN.
HEIGHT, REFER TO NOTE REGARDING SECUREMENT
OF FLASHING.
APPROX.
1/2"
ALT. VERTICAL TERMINATION -
TWO PIECE FLASHING
FOR USE WHERE HORIZONTAL TERMINATION OF
EPDM MEMBRANE IS NOT POSSIBLE
APPROX.
1/2"
EPDM ROOFING MEMBRANE
SEAM TAPE - 6-INCH WIDTH. APPLY PRIMER TO
UNDERLYING EPDM ROOF MEMBRANE AND OVERLYING
EPDM FLASHING MEMBRANE PRIOR TO APPLICATION.
1-1/4" 1/2"
2-3/4"
2"
PRESSURE-SENSITIVE OUTERSEAM FLASHING;
MINIMUM 5-INCH WIDTH. SEAL EDGES AS SHOWN.
EPDM ROOFING MEMBRANE
SEAM TAPE - 6-INCH WIDTH. APPLY PRIMER
TO UNDERLYING EPDM ROOF MEMBRANE
AND OVERLYING EPDM FLASHING
MEMBRANE PRIOR TO APPLICATION.
BATTEN STRIP OR FASTENERS AND 2-INCH
PLATES, 12-INCHES O.C. MAX.
PRESSURE-SENSITIVE OUTERSEAM
FLASHING; MIN. 5-INCH WIDTH. SEAL
EDGES AS SHOWN.
4" M
IN
WRAP EPDM MEMBRANE FLASHING OVER
THE TOP OF THE CURB AND SECURE TO
THE INSIDE OF THE CURB WITH 1" METAL
CAP NAILS AT 6" O.C. MAXIMUM.
MEMBRANE SECUREMENT
ALT. TWO-PIECE FLASHING
PREFINISHED 24 GA. GALV.
STEEL SLIP COUNTERFLASHING.
SECURE TO EXISTING CURB
COUNTERFLASHING AS SHOWN
USING GASKETED FASTENERS
12-INCHES O.C. MAX., AND
WITHIN 2-INCHES OF EACH END.
EXISTING ROOFTOP UNIT
COUNTERFLASIHNG
REFER TO DETAILS BELOW FOR
FLASHING REQUIREMENTS.
ALT. COUNTERFLASHING NO. 1
FOR USE WHERE APPROVED AND WHERE EXISTING
ROOFTOP UNIT CANNOT BE DISPLACED TO ALLOW FOR
FLASHING, OR WHERE GAP BETWEEN EXISTING
ROOFTOP UNIT COUNTERFLASHING AND CURB IS TOO
NARROW TO ACCOMMODATE FLASHING
4" M
IN
8" M
IN
FL
AS
H
IN
G H
EI
G
H T
EXIST. ROOFTOP PENETRATION
EPDM FLASHING, 8" MIN. HEIGHT, FULLY
ADHERED TO CURB. REFER TO NOTE
REGARDING SECUREMENT OF MEMBRANE.
ALT. NOTE:
ALT. SECUREMENT
SPECIFIED POLYISO. INSULATION
UNDERLAYMENT - CONCRETE DECKS ONLY
APPR
O
X.
2-3/4"
8" M
IN
IM
U M
H
EI
G H
T
NOTE: DIS-CONNECTIONS AND RE-CONNECTIONS OF ELECTRICAL,
PLUMBING OR MECHANICAL COMPONENTS RELATED TO
THE DISPLACEMENT AND RE-INSTALLATION OF ROOFTOP
UNITS SHALL BE PERFORMED BY A CONTRACTOR LICENSED
TO PERFORM SUCH WORK. COORDINATE THIS WORK WITH
THE OWNER.
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER
THE REQUIREMENTS AND RECOMMENDATIONS OF THE
EPDM ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS
FOLLOWING THE RECOMMENDATIONS AND REQUIREMENTS
OF THE ROOFING MEMBRANE MANUFACTURER. PROVIDE
"T-JOINT COVERS" AT THE BASE OF THE CURB AT FLASHING
PIECE INTERSECTIONS.
NOTE: APPLY WATER CUT OFF MASTIC TO THE BACKSIDE OF
FLASHING PRIOR TO COUNTERFLASIHNG INSTALLATION.
USE COUNTERFLASHING AS SECUREMENT PIECE FOR
FLASHING AS SHOWN.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
APPROX.
1/2"
EPDM FLASHING MEMBRANE, FULLY ADHERED TO CURB. REFER TO
NOTE REGARDING SECUREMENT OF FLASHING.
REINFORCED PERIMETER FASTENING STRIP WITH FACTORY-LAMINATED
SEAM TAPE. PRIME EPDM MEMBRANE PRIOR TO APPLICATION TO REINFORCED
FASTENING STRIP.
FASTENERS AND 2-INCH PLATES, 12-INCHES O.C. MAX.
NEW ROOF HATCH ON CURB -
RAISE TO ACCOMMODATE NEW
ROOF SYSTEM ELEVATION, AND
RE-SECURE FLANGE TO WOOD
BLOCKING AS SHOWN. PROVIDE
INTERIOR FINISH REPAIRS AS
NEEDED TO ACCOMMODATE
RAISING OF CURB.
NOMINAL WOOD BLOCKING.
THICKNESS TO MATCH EXISTING
COVER BOARD AND INSULATION
THICKNESS; WIDTH GREATER
THAN ROOF HATCH CURB AND
CURB FLANGE. SECURE TO
SUBSTRATE 18-INCHES O.C.
WITH SPECIFIED FASTENERS
APPROPRIATE FOR THE
SUBSTRATE ENCOUNTERED.
PREFINISHED 24 GA. GALV.
STEEL SLIP COUNTERFLASHING.
SECURE TO EXISTING CURB
COUNTERFLASHING AS SHOWN
USING GASKETED FASTENERS
12-INCHES O.C. MAX., AND
WITHIN 2-INCHES OF EACH END.
APPLY SEALANT TO BACKSIDE
OF COUNTERFLASHING PRIOR
TO INSTALLATION.
CL
NOTE: PRIOR TO SOLDERING OF STAINLESS STEEL, CLEAN WORK AREA USING SOLVENTS
AND WIRE BRUSH; REMOVING DIRT, OIL, GREASE, AND OTHER CONTAMINANTS FROM
THE WORK AREA. TIN THE WORK AREA BY APPLYING ACID (FLUX). PERFORM
SOLDERING WORK. AFTER COMPLETION OF WORK, REMOVE EXCESS ACID (FLUX)
FROM THE WORK AREA.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
CL
MIN. 1" AIR
GAP OR MATCH
EXIST. - WHICHEVER
IS GREATER
4" M
IN
8" M
IN
. F
LA
SH
IN
G
H
EI
G H
T
FIELD-FABRICATED
FLASHING
HOT STACK
NOTE: APPLY PRIMER TO ALL SURFACES WHICH WILL
RECEIVE PRESSURE SENSITIVE OUTER SEAM
FLASHING PRIOR TO APPLICATION.
3" MIN3" MIN
2 1/2"
NOTE: WHEN OUTSIDE DIAMETER OF THE PIPE
EXCEEDS 18", ADDITIONAL FIELD MEMBRANE
SECUREMENT REQUIRED. REFER TO
MANUFACTURER'S DETAILS.
PRESSURE-SENSITIVE
FLASHING - 12-INCH WIDTH.
PRESSURE-SENSITIVE
FLASHING - 9-INCH WIDTH.
PRESSURE-SENSITIVE
FLASHING - 5 OR 6-INCH
WIDTH.
PRESSURE-SENSITIVE
OUTERSEAM FLASHING;
6-INCH WIDTH. SEAL
EDGES AS SHOWN.
PRE-FABRICATED
BOOT FLASHING
EXISTING TUBULAR
PENETRATION
PIPE EXTENSION (IF NECESSARY) TO
ACHIEVE 8" MIN. FLASHING HEIGHT.
PROVIDE SEALANT AT INTERSECTION
BETWEEN EXISTING TUBULAR
PENETRATION AND EXTENSION.
24 GA. STAINLESS STEEL STORM COLLAR
SOLDER ALL LAPS AND SEAMS WATERTIGHT.
REFER TO NOTE REGARDING SOLDERING.
INSTALL BUTYL TAPE BEHIND COLLAR AS
SHOWN PRIOR TO INSTALLATION OF CLAMP.
SEAL TOP OF HOOD AS SHOWN.
SEALANT - TYP
STAINLESS STEEL CLAMPING
BAND
STAINLESS STEEL CLAMPING BAND.
PRIOR TO INSTALLATION, APPLY
MANUFACTURERS RECOMMENDED
SEALANT BEHIND EPDM FLASHING.
SEAL TOP OF FLASHING AND BAND
AFTER INSTALLATION.
EXISTING HIGH-TEMPERATURE
TUBULAR PENETRATION
PRESSURE-SENSITIVE FLASHING - 12-INCH
WIDTH.
PRESSURE-SENSITIVE FLASHING - 9-INCH
WIDTH.
PRESSURE-SENSITIVE FLASHING - 5 OR
6-INCH WIDTH.
PRESSURE-SENSITIVE OUTERSEAM
FLASHING; 6-INCH WIDTH. SEAL EDGES
AS SHOWN.
HIGH TEMPERATURE
SEALANT - TYP
STAINLESS STEEL
CLAMPING BAND
SPECIFIED POLYISOCYANURATE INSULATION - TYP.
EXISTING STRUCTURAL DECK - TYP.
COVER BOARD - 1/2-INCH THICK - TYP.
EPDM ROOFING MEMBRANE - TYP.
UNDERLAYMENT - TYP. - CONCRETE DECKS ONLY
24 GA. STAINLESS STEEL STORM COLLAR
SOLDER ALL LAPS AND SEAMS
WATERTIGHT. REFER TO NOTE
REGARDING SOLDERING. INSTALL BUTYL
TAPE BEHIND COLLAR AS SHOWN PRIOR
TO INSTALLATION OF CLAMP. SEAL TOP
OF HOOD AS SHOWN.
24 GA. STAINLESS STEEL FLANGED
SLEEVE. SOLDER ALL LAPS AND SEAMS
WATERTIGHT. REFER TO NOTE
REGARDING SOLDERING. SECURE TO
STRUCTURAL DECK AS SHOWN.
NOTE: EXISTING FLANGED SLEEVE
COMPONENTS DETERMINED TO BE IN
GOOD CONDITION AND FREE OF
BITUMINOUS CONTAMINATION MAY BE
CONSIDERED FOR RE-USE.
POURABLE SEALER - SLOPE TO ALLOW FOR PROPER DRAINAGE.
NON-SHRINK GROUT - FILL TO 2" BELOW RIM OF PITCH PAN.
EXISTING IRREGULAR PENETRATION - SIZE AND SHAPE VARIES.
NOTE: DO NOT USE PITCH PANS AT TUBULAR PENETRATIONS
WITHOUT PRIOR OWNER APPROVAL.
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
4" M
IN
NOTE: PRIOR TO SOLDERING OF STAINLESS STEEL, CLEAN WORK
AREA USING SOLVENTS AND WIRE BRUSH; REMOVING DIRT,
OIL, GREASE, AND OTHER CONTAMINANTS FROM THE WORK
AREA. TIN THE WORK AREA BY APPLYING ACID (FLUX).
PERFORM SOLDERING WORK. AFTER COMPLETION OF
WORK, REMOVE EXCESS ACID (FLUX) FROM THE WORK
AREA.
AT LOCATIONS WHERE POSSIBLE, PROVIDE A 24 GA. STAINLESS
STEEL JUNCTION/FLASHING BOX. FABRICATE BOX WITH A SLOPED
TOP TO SHED WATER. SOLDER ALL LAPS AND SEAMS WATERTIGHT.
SEAL PENETRATION EXIT OPENINGS WATERTIGHT.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
PRESSURE-SENSITIVE FLASHING - WIDTH AS NECESSARY TO RESULT
IN CONDITION SHOWN.
PRESSURE-SENSITIVE OUTERSEAM FLASHING; WIDTH AS NECESSARY TO
RESULT IN CONDITION SHOWN. SEAL EDGES AS SHOWN.
NOMINAL 6-INCH WOOD BLOCKING AS NECESSARY TO MATCH COVER
BOARD AND INSULATION THICKNESS. SECURE TO SUBSTRATE
18-INCHES O.C. MAX., AND WITHIN 2-INCHES OF EACH END.
4" MIN.
24 GA. STAINLESS STEEL PITCH PAN WITH 6-INCH FLANGE AND ROUNDED
CORNERS. SOLDER ALL SEAMS AND LAPS WATERTIGHT - REFER TO NOTE
REGARDING SOLDERING.
2" MIN. ALL SIDES
NOTE: APPLY PRIMER TO ALL SURFACES WHICH WILL
RECEIVE PRESSURE SENSITIVE OUTER SEAM
FLASHING PRIOR TO APPLICATION..
UNDERLAYMENT
4" M
IN
8" M
IN
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
APPROX.
1/2"
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE CURB AT FLASHING PIECE INTERSECTIONS.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS FOR THE
PRESENCE OF MASONRY WEEPS AND OTHER WALL DRAINAGE
MECHANISMS. DO NOT COVER WEEPS, OR IMPEDE THE ABILITY
OF MOISTURE TO EXIT WALL SYSTEMS.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
3/4-INCH PLYWOOD MECHANICALLY ATTACHED TO EXISTING
WALL WITH PROPER SUBSTRATE FASTENERS - TWO ROWS
24-INCHES O.C., STAGGERED
CUT REGLET INTO WALL AS SHOWN.
REFER TO ENLARGED REGLET DETAIL
FOR FURTHER CLARIFICATION.
PREFINISHED 24 GA. GALV. STEEL
COUNTERFLASHING, SPRING-LOCKED INTO
REGLET AND SECURED WITH GASKETED
FASTENERS APPROPRIATE FOR THE
SUBSTRATE 12-INCHES O.C. MAX. REFER TO
ENLARGED REGLET DETAIL.
EXISTING WALL
ENLARGED REGLET
DETAIL
SCALE: NONE
CUT REGLET INTO WALL
AS SHOWN
SEALANT
PREFINISHED 24 GA. GALV.
STEEL COUNTERFLASHING,
SPRING-LOCKED INTO REGLET
AND SECURED WITH GASKETED
FASTENERS APPROPRIATE FOR
THE SUBSTRATE 12-INCHES O.C.
MAX.
FU
LL W
ID
TH
O F M
ASO
N
R Y
G R
O U
T JO
IN
T
APPR
O
X.
1-1/4"
APPROX. 1"
DEEP
UNDERLAYMENT
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER THE
REQUIREMENTS AND RECOMMENDATIONS OF THE EPDM
ROOFING MEMBRANE MANUFACTURER.
SECURE TOP EDGE OF FLASHING USING AN ALUMINUM
TERMINATION BAR SECURED 12-INCHES O.C., MAX., AND WITHIN
2-INCHES OF EACH END. PRIOR TO TERMINATION BAR
INSTALLATION, INSTALL MANUFACTURERS RECOMMENDED
SEALANT BEHIND FLASHING WHERE TERMINATION BAR WILL BE
PLACED. SEAL TOP EDGE OF FLASHING AND TERMINATION BAR
AFTER INSTALLATION.
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER
THE REQUIREMENTS AND RECOMMENDATIONS OF THE
EPDM ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE CURB AT FLASHING PIECE INTERSECTIONS.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS FOR THE
PRESENCE OF MASONRY WEEPS AND OTHER WALL DRAINAGE
MECHANISMS. DO NOT COVER WEEPS, OR IMPEDE THE ABILITY
OF MOISTURE TO EXIT WALL SYSTEMS.
4" M
IN
8" M
IN
IM
U M
JOINT WIDTH
SEALANT DEPTH: WHEN JOINT WIDTH IS LESS THAN
OR EQUAL TO 1/2-INCH, SEALANT DEPTH SHALL BE
1/4-INCH. WHEN JOINT WIDTH IS BETWEEN 1/2-INCH
AND 1-INCH, SEALANT DEPTH SHALL EQUAL
ONE-HALF THE JOINT WIDTH. WHEN JOINT WIDTH IS
BETWEEN 1-INCH AND 2-INCHES, SEALANT DEPTH
SHALL EQUAL 1/2-INCH.
SEALANT
COMPRESSIBLE BACKER ROD
EXISTING STONE COPING - BOTH
SIDES OF JOINT. PREPARE SURFACES
ADJACENT TO JOINT AS REQ'D BY SEALANT
MANUFACTURER. PRIME SURFACES IF
REQUIRED BY SEALANT MANUFACTURER.
EXISTING COPING JOINT - REMOVE EXISTING
SEALANT AND OTHER REPAIR MATERIALS
PRIOR TO INSTALLATION OF NEW MATERIALS.
STONE COPING SEALANT JOINT RAKE AND
RE-SEAL DETAIL
FOR USE WHERE VERTICAL AND HORIZONTAL STONE COPING JOINTS
ARE TO BE RE-SEALED.
1- 1/
2" M
IN
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
APPROX.
1/2"
3/4-INCH PLYWOOD MECHANICALLY ATTACHED TO EXISTING
WALL WITH PROPER SUBSTRATE FASTENERS - TWO ROWS
24-INCHES O.C., STAGGERED
SPECIFIED UNDERLAYMENT - CONCRETE DECKS ONLY
PREFINISHED 24 GA. GALV. STEEL SURFACE
MOUNTED COUNTERFLASHING. SECURE TO
EXISTING WALL AS SHOWN USING GASKETED
FASTENERS 12-INCHES O.C. MAX., AND WITHIN
2-INCHES OF EACH END.
SEALANT
EXISTING STONE COPING CAP. RAKE AND RE-SEAL
VERTICAL AND HORIZONTAL JOINTS IN CAP. REFER
TO ADJACENT DETAIL FOR FURTHER
CLARIFICATION.
SECURE TOP EDGE OF FLASHING USING AN ALUMINUM
TERMINATION BAR SECURED 12-INCHES O.C., MAX., AND
WITHIN 2-INCHES OF EACH END. PRIOR TO TERMINATION
BAR INSTALLATION, INSTALL MANUFACTURERS
RECOMMENDED SEALANT BEHIND FLASHING WHERE
TERMINATION BAR WILL BE PLACED. SEAL TOP EDGE OF
FLASHING AND TERMINATION BAR AFTER INSTALLATION.
CREATE A 3-FOOT ENHANCED DRAINAGE AREA WITH A MINIMUM FINISH SLOPE OF 1/2-INCH PER FOOT
AT GUTTER EDGES. CONSTRUCT THE AREA USING A TAPERED POLYISOCYANURATE INSULATION
"Q-PANEL" CUT TO CREATE A FLUSH CONDITION AT THE EDGE NAILER(S) AND INSULATION.
8"
8"
3" M
IN
2" M
IN
. O
R T
O M
AT
C
H E
XI
ST
IN
G
E
LE
VA
TI
O N
W H
IC
H
EV
ER
IS
G
R
EA
TE
R
2"2" M
IN
4"
1/2" HUG
GUTTER EDGE FLANGE CONFIGURATION
AND NAILING PATTERN DIAGRAM
SCALE: NONE
NOTE: THE PURPOSE OF THIS DIAGRAM IS
TO SHOW GUTTER EDGE FASCIA FLANGE
FASTENING PATTERNS AND NAILER
CONFIGURATION. THE ACTUAL FASCIA
CONFIGURATION, SIZE OF NAILERS, AND
NUMBER OF NAILERS REQUIRED TO
ACHIEVE THE REQUIREMENTS SHOWN IN
THE DETAIL BELOW WILL VARY.
3" MIN.
4" FLANGE
1/2" HUG
6" MIN.
1/2" MIN.
NOTE: EXTEND EPDM ROOFING MEMBRANE OVER AND DOWN
PERIMETER EDGE AS SHOWN. SECURE WITH ROOFING
NAILS AFFIXED WITH 1" DIAMETER METAL CAPS 12" O.C.
MAX.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
DOWNSPOUT RECEIVER PIECE - FABRICATE USING PREFINISHED 24 GA.
GALV. STEEL. FASTEN AND SEAL TO GUTTER AS SHOWN.
PREFINISHED 24 GA. GALV. STEEL FASCIA EXTENSION PIECE. SECURE
TO SUBSTRATE WITH SPECIFIED FASTENER APPROPRIATE FOR THE
SUBSTRATE ENCOUNTERED 12" O.C. MAX.
PROVIDE GUTTER HANGERS 30-INCHES O.C. - FABRICATE FROM 1-INCH X
1/8-INCH GALV. STEEL, PAINTED TO MATCH GUTTER. SECURE TO
SUBSTRATE WITH FASTENERS APPROPRIATE FOR THE SUBSTRATE
ENCOUNTERED. SECURE WITH TWO FASTENERS, MINIMUM, PER HANGER.
UNDERLAYMENT - CONCRETE DECKS ONLY
PRESSURE-SENSITIVE OUTER SEAM FLASHING - 5-INCH OR
6-INCH WIDTH.
NOTE: AT A MINIMUM, PROVIDE AN ADDITIONAL 6" WIDE
REINFORCEMENT PIECE AT SHEET METAL FASCIA JOINTS.
REFER TO ROOFING MEMBRANE MANUFACTURER
REQUIREMENTS FOR ADDITIONAL REQUIREMENTS AND
RECOMMENDATIONS AT SHEET METAL FASCIA JOINTS.
NOMINAL 6-INCH WOOD BLOCKING - THICKNESS AS NECESSARY TO
MATCH MAXIMUM ROOF AREA INSULATION AND COVER BOARD
THICKNESS WITH A CONSISTENT FINAL NAILER ELEVATION. SECURE
TO SUBSTRATE 18-INCHES O.C. MAX. DECREASE FASTENER SPACING
TO 9-INCHES O.C. WITHIN 10-FEET OF A BUILDING CORNER.
EXISTING STRUCTURAL DECK
SPECIFIED POLYISOCYANURATE INSULATION
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
TAPERED POLYISOCYANURATE INSULATION
MINIMUM STARTING THICKNESS OF 1-INCH
GUTTER FABRICATED FROM 24 GA.
PREFINISHED GALV. STEEL. OVERLAP
GUTTER SECTIONS 1-1/2 INCH, SEAL, AND
POP RIVET SECTIONS WITH TWO ROWS OF
POP RIVETS, SPACED 1/2"-3/4" O.C. IN EACH
ROW. SECURE BACK VERTICAL FLANGE
TO SUBSTRATE 18" O.C. MAX.
GUTTER SPACERS - 1/8-NCH THICK X 1-INCH
WIDE, 30-INCHES O.C. MAX. FABRICATE
FROM GALVANIZED STEEL. PAINT SPACERS
TO MATCH GUTTER COLOR. SEAL AND
SECURE TO GUTTER.
PREFINISHED 24 GA. GALV. STEEL FASCIA
PIECE. FABRICATE WITH 4-INCH FLANGE
AND 1/2-INCH HUG AS SHOWN. SECURE
FLANGE WITH NAILS 3-INCHES O.C. MAX. IN
TWO STAGGERED ROWS AS SHOWN IN
DIAGRAM AT TOP RIGHT CORNER OF
SHEET.
PRESSURE-SENSITIVE OUTER SEAM
FLASHING - 9-INCH WIDTH. SEAL EDGES
AS SHOWN AFTER COMPLETION OF
WORK.
PREFINISHED 24 GA. GALV. STEEL RECTANGULAR DOWNSPOUT.
FABRICATE AND INSTALL DOWNSPOUTS IN ACCORDANCE WITH
“SMACNA ARCHITECTURAL SHEET METAL MANUAL, 7TH EDITION”.
SECURE DOWNSPOUT TO WALL WITH BRACKETS AND
FASTENERS APPROPRIATE FOR THE SUBSTRATE ENCOUNTERED.
TERMINATE BOTTOM OF DOWNSPOUT TO MATCH EXISTING.
LCC
PLAN VIEW OF ROOF SUMP AREA
SCALE: NONE
TAPERED INSULATION/EDGE STRIPS AS NEEDED
TO RESULT IN 8'-0" X 8'-0" SUMP AREA
ROOF DRAIN
NOTE: EXTEND EPDM ROOFING MEMBRANE UNDER CLAMPING
RING AND INTO THE ROOF DRAIN. TIGHTLY SECURE
CLAMPING RING AFTER INSTALLATION OF ROOF DRAIN
FLASHING COMPONENTS.
CUT DRAINAGE HOLE IN MEMBRANE MIN. 1/2" GREATER
THAN DRAIN PIPE DIAM. ON ALL SIDES
EXTEND MEMBRANE 1" MIN.
BEYOND CLAMPING RING
IN
ST
AL
L
TA
PE
R
ED
P O
LY
IS
O C
YA
N
U R
AT
E
IN
SU
LA
TI
O N
A N
D /O
R T
AP
ER
ED
E
D G
E
ST
R
IP
T O
R
ES
U
LT
IN
' x
' S U
M P
AR
EA
(T
YP
APPROX. 4'-0" - REFER TO NOTE ABOVE REGARDING ROOF SUMP AREA
CONSTRUCTION AND SLOPE REQUIREMENTS
IN
ST
AL
L
TA
PE
R
ED
P O
LY
IS
O C
YA
N
U R
AT
E
IN
SU
LA
TI
O N
A N
D /O
R T
AP
ER
ED
E
D G
E
ST
R
IP
T O
R
ES
U
LT
IN
' x
' S U
M P
AR
EA
(T
YP
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
EXISTING STRUCTURAL DECK
SPECIFIED POLYISOCYANURATE INSULATION
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
TAPERED POLYISOCYANURATE INSULATION, AND/OR
TAPERED EDGE STRIP(S) AS NECESSARY TO RESULT IN A
8-FOOT BY 8-FOOT MINIMUM TAPERED ROOF DRAIN SUMP
AREA WITH A MINIMUM SLOPE OF 1/4-INCH PER FOOT.
EXISTING ROOF DRAIN ASSEMBLY. CLEAN BOWL FREE OF ALL
EXISTING FLASHING MATERIALS AND BITUMINOUS RESIDUE PRIOR
TO INSTALLATION OF EPDM ROOFING MEMBRANE AND
MANUFACTURER'S RECOMMENDED SEALANT. INSPECT DRAIN
BOWL, CLAMPING RING, AND OTHER ASSEMBLY COMPONENTS FOR
DAMAGE. REPLACE DAMAGED COMPONENTS AS NECESSARY PER
SECTION 024100.
EXISTING ROOF DRAIN STRAINER. REMOVE AND DISCARD
DAMAGED, BROKEN OR PLASTIC-TYPE STRAINER(S).
REPLACE DISCARDED STRAINERS WITH CAST IRON
STRAINERS. REFER TO SECTION 024100.
NOTE: EXTEND EPDM ROOFING MEMBRANE UNDER CLAMPING
RING AND INTO THE ROOF DRAIN. TIGHTLY SECURE
CLAMPING RING AFTER INSTALLATION OF ROOF DRAIN
FLASHING COMPONENTS.
MANUFACTURER'S RECOMMENDED SEALANT. INSTALL ONE TUBE,
MINIMUM, UNDER EPDM ROOFING MEMBRANE AT CLAMPING RING,
CONTINUOUS BEAD - TO ROOF DRAIN ASSEMBLY INTERSECTION.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
NOTE: IF FIELD SEAM EDGE IS WITHIN 9" OF DRAIN COMPRESSION
RING, EPDM TARGET PATCH REQUIRED.
UNDERLAYMENT
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER
THE REQUIREMENTS AND RECOMMENDATIONS OF THE
EPDM ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE WALL AT FLASHING PIECE INTERSECTIONS.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS FOR THE
PRESENCE OF MASONRY WEEPS AND OTHER WALL DRAINAGE
MECHANISMS. DO NOT COVER WEEPS, OR IMPEDE THE ABILITY
OF MOISTURE TO EXIT WALL SYSTEMS.
PREFINISHED 24 GA. GALV. STEEL REGLETED
COUNTERFLASHING. SECURE TO SUBSTRATE WITH
GASKETED FASTENERS 12-INCHES O.C., MIN. 2
FASTENERS.
SEALANT
CUT SIDING TO WALL
2" M
IN
1" M
IN
PREFINISHED 24 GA. GALV. STEEL PARAPET CAP.
TURN UP WALL 2-INCHES, MIN., INSTALL BUTYL TAPE
BEHIND TURN-UP, AND SECURE.
FULLY-ADHERED EPDM FLASHING MEMBRANE
COPING CAP TERMINATION
AT END WALLS
FOR USE WHERE PARAPET WALLS AND
RELATED COPING CAPS TERMINATE
INTO VERTICAL WALLS.
PREFINISHED 24 GA. GALV. STEEL REGLETED
COUNTERFLASHING. SECURE TO SUBSTRATE WITH
GASKETED FASTENERS 12-INCHES O.C., MIN. 2
FASTENERS.
SEALANT
CUT REGLET INTO WALL
2" M
IN
1" M
IN
PREFINISHED 24 GA. GALV. STEEL PARAPET CAP.
TURN UP WALL 2-INCHES, MIN., INSTALL BUTYL TAPE
BEHIND TURN-UP, AND SECURE.
FULLY-ADHERED EPDM FLASHING MEMBRANE
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
NOTE: MEMBRANE MUST BE EXTENDED TO CORNERS TO PROVIDE
COMPLETE COVERAGE OF THE WALL SURFACE.
COPING CAP JOINT PROFILE
SINGLE-LOCK STANDING SEAM; FOR USE WHERE
ADJACENT COPING CAPS ARE TO BE JOINED, BUTTON PUNCH.
1"
SEALANT - SEAL BOTH ENDS OF
STANDING SEAM
PARAPET WALL STEEL COPING CAP
BUTTON PUNCH
3" M
IN
2" M
IN
. O
R T
O M
AT
C
H
EX
IS
TI
N G
E
LE
VA
TI
O N
W H
IC
H
EV
ER
IS
G
R
EA
TE
R
3/4
5/8
7- 1/
IN
C H
M
AX
PREFINISHED 24 GA. GALV. STEEL COPING CAP.
HOOK OUTSIDE FACE TO CONTINUOUS CLEAT,
AND SECURE INNER FACE WITH GASKETED
FASTENERS APPROPRIATE FOR THE
SUBSTRATE ENCOUNTERED 18-INCHES O.C.
MAX., AND WITHIN 2-INCHES OF EACH END.
JOIN ADJACENT CAP SECTIONS USING 1-INCH
HIGH, SINGLE-LOCK STANDING SEAMS.
BUTTON PUNCH BOTH ENDS.
EXISTING STRUCTURAL DECK
SPECIFIED POLYISO. INSULATION
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
3/4-INCH PLYWOOD MECHANICALLY ATTACHED TO
EXISTING WALL WITH PROPER SUBSTRATE FASTENERS;
TWO ROWS 24-INCHES O.C., STAGGERED
SPECIFIED UNDERLAYMENT - CONCRETE DECKS ONLY
22 GA. GALV. STEEL CONTINUOUS CLEAT. FABRICATE AS SHOWN TO
CREATE 1/2-INCH PER FOOT SLOPE TOWARD INNER FACE. SECURE
HORIZONTAL FLANGE AND VERTICAL FACE WITH RING SHANK COATED
NAILS 6-INCHES O.C. MAX.
EXTEND FULLY-ADHERED EPDM FLASHING MEMBRANE UP AND
OVER PARAPET WALL, AND DOWN OUTSIDE FASCIA. APPLY
SEALANT TO BACK SIDE OF FLASHING MEMBRANE, AND SECURE
12" O.C. MAX.
H
EI
G H
T
VA
R
IE
S;
-IN
C
H M
IN
IM
U M
NOMINAL 2-INCH THICK WOOD BLOCKING - WIDTH AS NECESSARY
TO MATCH EXISTING PARAPET WALL WIDTH. THICKNESS AS
NECESSARY TO ACHIEVE 4-INCH MINIMUM FLASHING HEIGHT.
SECURE TO SUBSTRATE 18-INCHES O.C. MAX. DECREASE
FASTENER SPACING TO 9-INCHES O.C. WITHIN 10-FEET OF A
BUILDING CORNER.
BUTYL
SEALANT - TYP
CLIENT
PROFESSIONAL
PROJECT
DESCRIPTIONDATE
ISSUE
Drawn By: PD
Checked By: SH
SHEET TITLE
File Name:
STAMP
SHEET 04 OF 05
ROOF PLAN
DETAILS 01-09
Testing Engineers & Consultants
1343 Rochester Road Troy, MI 48083
DETAIL 01 -
SCALE: NONE
ROOF CURB FLASHING DETAIL 02 -
SCALE: NONE
ROOF HATCH FLASHING DETAIL 03 -
SCALE: NONE
ROOF DRAIN FLASHING
DETAIL 04 -
SCALE: NONE
DETAIL 05 -
SCALE: NONE
DETAIL 06 -
SCALE: NONE
ROOF-TO-WALL FLASHING
DETAIL 07 -
SCALE: NONE
PARAPET WALL FLASHING DETAIL 08 -
SCALE: NONE
GUTTER EDGE FLASHING
DETAIL 09 -
SCALE: NONE
PARAPET WALL FLASHING
Detroit Public Schools
3011 W. Grand Blvd Detroit, MI 48202
PITCH PAN FLASHING TUBULAR PENETRATION FLASHING
75% Design Review Set03-25-2026
Davison Elementary-Middle School
2800 E. Davison Detroit, MI 48212
NOTE: DIS-CONNECTIONS AND RE-CONNECTIONS OF
ELECTRICAL, PLUMBING OR MECHANICAL
CONNECTIONS RELATED TO THE DISPLACEMENT
AND RE-INSTALLATION OF ROOFTOP UNITS SHALL
BE PERFORMED BY A CONTRACTOR LICENSED TO
PERFORM SUCH WORK. COORDINATE THIS
WORK WITH THE OWNER.
NOTE: AT ROOF CURB FLASHING HEIGHTS GREATER THAN 24-INCHES: PROVIDE
INTERMEDIATE SECUREMENT PER THE REQUIREMENTS AND RECOMMENDATIONS
OF THE EPDM ROOFING MEMBRANE MANUFACTURER.
4" M
IN
8" M
IN
PLAN VIEW OF CURB CAP
18 GA. STAINLESS STEEL CURB CAP WITH
WELDED SEAMS
PROVIDE DIAMOND CROSS-BREAK TO ELIMINATE
POTENTIAL FOR PONDING WATER ON CURB CAP.
FI
EL
D V
ER
IF
Y C
U R
B D
IM
EN
SI
O
N S)
FIELD VERIFY CURB DIMENSIONS)
SCALE: NONE
SLOPE SLOPE
SLO
PE
SLO
PE
WOOD BLOCKING - IF NECESSARY TO ACHIEVE 8-INCH MINIMUM
FLASHING HEIGHT. SECURE TO SUBSTRATE 18-INCHES O.C. AND WITHIN
2-INCHES OF EACH END.
CURB INSULATION - IF EXISTING CURB IS INSULATED, AND EXISTING INSULATION
CANNOT BE SALVAGED, PROVIDE CURB INSULATION TO MATCH EXISTING.
NOTE: SECURE TOP EDGE OF FLASHING WITH 1-INCH BY 1/8-INCH
ALUMINUM ANCHOR BAR SECURED 12-INCHES O.C. MAX. AND
WITHIN 2-INCHES OF EACH END. APPLY WATER CUT OFF
MASTIC TO THE BACKSIDE OF FLASHING PRIOR TO ANCHOR
BAR INSTALLATION. APPLY SEALANT TO TOP EDGE OF
FLASHING AND ANCHOR BAR AFTER COMPLETION OF WORK. IF
SUBSTRATE IS WOOD, NAILS AFFIXED WITH 1-INCH METAL
CAPS, 6-INCHES O.C. MAX., MAY BE USED IN LIEU OF
TERMINATION BAR.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR CLARITY.
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
APPROX.
1/2"
EPDM FLASHING MEMBRANE, FULLY ADHERED TO CURB. REFER TO
NOTE REGARDING SECUREMENT OF FLASHING.
REINFORCED PERIMETER FASTENING STRIP WITH FACTORY-LAMINATED
SEAM TAPE. PRIME EPDM MEMBRANE PRIOR TO APPLICATION TO REINFORCED
FASTENING STRIP.
FASTENERS AND 2-INCH PLATES, 12-INCHES O.C. MAX.
NOTE: ALTERNATE FLASHING CONFIGURATIONS SHOWN ON ROOF CURB DETAIL SHEET
ARE ACCEPTABLE.
PROVIDE ADDITIONAL UNDERLYING
CURB CAP SUPPORT, IF NECESSARY
3/4-INCH PLYWOOD - SECURE TO
SUBSTRATE 18-INCHES O.C., MAX.
18 GA. GALVANIZED STEEL CURB CAP WITH
WELDED SEAMS. CROSSBREAK CAP TO PROVIDE
SLOPE ADEQUATE TO REMOVE STANDING WATER
FROM TOP OF CAP. SECURE VERTICAL FACE OF
CAP WITH GASKETED FASTENERS, 12-INCHES
O.C. MAX., AND WITHIN 2-INCHES OF EACH END.
FULLY-ADHERED EPDM MEMBRANE
2X4 WOOD BLOCKING/INSULATION STOP AT
PERIMETER OF CURB TOP. SECURE TO SUBSTRATE
18-INCHES O.C. AND WITHIN 2-INCHES OF EACH END.
1-1/2 INCH POLYISOCYANURATE INSULATION
4" M
IN
8" M
IN
2" M
IN
4" M
IN
M
AX
. H
EI
G H
T
PO
SS
IB
LE
1" M
IN
ALTERNATE COUNTERFLASHING NO. 1
FOR USE BELOW EXISTING METAL WALL SIDING WHERE 8-INCH
MINIMUM FLASHING HEIGHT CAN BE ACHIEVED.
ALTERNATE COUNTERFLASHING NO. 2
FOR USE BELOW EXISTING METAL WALL SIDING WHERE 8-INCH
MINIMUM FLASHING HEIGHT CANNOT BE ACHIEVED.
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER
THE REQUIREMENTS AND RECOMMENDATIONS OF THE
EPDM ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE CURB AT FLASHING PIECE INTERSECTIONS.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS
FOR THE PRESENCE OF MASONRY WEEPS AND
OTHER WALL DRAINAGE MECHANISMS. DO NOT
COVER WEEPS, OR IMPEDE THE ABILITY OF
MOISTURE TO EXIT WALL SYSTEMS.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
APPROX.
1/2"
3/4-INCH PLYWOOD MECHANICALLY ATTACHED TO EXISTING
WALL WITH PROPER SUBSTRATE FASTENERS - TWO ROWS
24-INCHES O.C., STAGGERED
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
APPROX.
1/2"
3/4-INCH PLYWOOD MECHANICALLY ATTACHED TO EXISTING
WALL WITH PROPER SUBSTRATE FASTENERS - TWO ROWS
24-INCHES O.C., STAGGERED
UNDERLAYMENTUNDERLAYMENT
PREFINISHED 24 GA. GALV. STEEL SLIP
COUNTERFLASHING. SECURE TO EXISTING
COUNTERFLASHING AS SHOWN USING GASKETED
FASTENERS 12-INCHES O.C. MAX., AND WITHIN
2-INCHES OF EACH END.
EXISTING COUNTERFLASHING
EXISTING METAL SIDING - DO NOT DISTURB.
PREFINISHED 24 GA. GALV. STEEL SLIP
COUNTERFLASHING. SECURE TO EXISTING
COUNTERFLASHING AS SHOWN USING GASKETED
FASTENERS 12-INCHES O.C. MAX., AND WITHIN
2-INCHES OF EACH END.
EXISTING COUNTERFLASHING - CUT AS SHOWN.
EXISTING METAL SIDING - DO NOT DISTURB.
SECURE TOP EDGE OF FLASHING USING AN ALUMINUM
TERMINATION BAR SECURED 12-INCHES O.C., MAX., AND
WITHIN 2-INCHES OF EACH END. PRIOR TO TERMINATION
BAR INSTALLATION, INSTALL MANUFACTURERS
RECOMMENDED SEALANT BEHIND FLASHING WHERE
TERMINATION BAR WILL BE PLACED. SEAL TOP EDGE OF
FLASHING AND TERMINATION BAR AFTER INSTALLATION.
SECURE TOP EDGE OF FLASHING USING AN ALUMINUM
TERMINATION BAR SECURED 12-INCHES O.C., MAX., AND
WITHIN 2-INCHES OF EACH END. PRIOR TO TERMINATION
BAR INSTALLATION, INSTALL MANUFACTURERS
RECOMMENDED SEALANT BEHIND FLASHING WHERE
TERMINATION BAR WILL BE PLACED. SEAL TOP EDGE OF
FLASHING AND TERMINATION BAR AFTER INSTALLATION.
22 GA. GALV. STEEL CONTINUOUS CLEAT.
FABRICATE WITH A 2-INCH FLANGE. SECURE
FLANGE AND VERTICAL FACE WITH RING SHANK
COATED NAILS 12-INCHES O.C. MAX. DECREASE
FASTENER SPACING TO 6-INCHES O.C. WITHIN
10-FEET OF A BUILDING CORNER.
2" M
IN
. O
R T
O M
AT
C
H
EX
IS
TI
N G
E
LE
VA
TI
O N
W H
IC
H
EV
ER
IS
G
R
EA
TE
R
3/4"
5/8"
7- 1/
2" M
AX
. F
AC
E
3/4-INCH PLYWOOD MECHANICALLY
ATTACHED TO EXISTING WALL WITH PROPER
SUBSTRATE FASTENERS - TWO ROWS
24-INCHES O.C., STAGGERED
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
COVER BOARD - 1/2-INCH THICK
APPROX.
1/2"
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER THE
REQUIREMENTS AND RECOMMENDATIONS OF THE EPDM
ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE CURB AT FLASHING PIECE INTERSECTIONS.
NOTE: SECURE TOP EDGE OF FLASHING USING AN ALUMINUM
TERMINATION BAR SECURED 12-INCHES O.C., MAX., AND WITHIN
2-INCHES OF EACH END. PRIOR TO TERMINATION BAR
INSTALLATION, INSTALL MANUFACTURERS RECOMMENDED
SEALANT BEHIND FLASHING WHERE TERMINATION BAR WILL BE
PLACED. SEAL TOP EDGE OF FLASHING AND TERMINATION BAR
AFTER INSTALLATION.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS FOR THE
PRESENCE OF MASONRY WEEPS AND OTHER WALL DRAINAGE
MECHANISMS. DO NOT COVER WEEPS, OR IMPEDE THE ABILITY
OF MOISTURE TO EXIT WALL SYSTEMS.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
4" FLANGE
1/2" HUG
PREFINISHED 24 GA. GALV. STEEL PERIMETER
EDGE FASCIA PIECE. FABRICATE WITH 1/2-INCH
HUG AT EDGE OF FLANGE AS SHOWN. SECURE
FLANGE WITH NAILS 3-INCHES O.C. MAX. IN TWO
STAGGERED ROWS. HOOK BOTTOM EDGE TO
CONTINUOUS CLEAT.
PRESSURE-SENSITIVE OUTER SEAM FLASHING - 9-INCH WIDTH. SEAL EDGES
AS SHOWN AFTER COMPLETION OF WORK.
PRESSURE-SENSITIVE OUTER SEAM FLASHING - 5-INCH OR 6-INCH WIDTH.
NOTE: AT A MINIMUM, PROVIDE AN ADDITIONAL 6" WIDE REINFORCEMENT
PIECE AT SHEET METAL FASCIA JOINTS. REFER TO ROOFING MEMBRANE
MANUFACTURER REQUIREMENTS FOR ADDITIONAL REQUIREMENTS AND
RECOMMENDATIONS AT SHEET METAL FASCIA JOINTS.
UNDERLAYMENT
EXISTING STRUCTURAL DECK
SPECIFIED POLYISOCYANURATE INSULATION
COVER BOARD - 1/2-INCH THICK
EPDM ROOFING MEMBRANE
SPECIFIED UNDERLAYMENT
2" M
IN
. O
R T
O M
AT
C
H
EX
IS
TI
N G
E
LE
VA
TI
O N
W H
IC
H
EV
ER
IS
G
R
EA
TE
R
7- 1/
2" M
AX
3/4
5/8
APPROX.
1/2"
NOTE: AT ROOF CURB/WALL FLASHING HEIGHTS GREATER THAN
24-INCHES: PROVIDE INTERMEDIATE SECUREMENT PER
THE REQUIREMENTS AND RECOMMENDATIONS OF THE
EPDM ROOFING MEMBRANE MANUFACTURER.
NOTE: INSTALL INSIDE AND OUTSIDE FLASHING CORNERS FOLLOWING
THE RECOMMENDATIONS AND REQUIREMENTS OF THE ROOFING
MEMBRANE MANUFACTURER. PROVIDE "T-JOINT COVERS" AT THE
BASE OF THE CURB AT FLASHING PIECE INTERSECTIONS.
NOTE: PRIOR TO INSTALLATION OF NEW FLASHING AND
COUNTERFLASHING, INSPECT EXISTING WALLS FOR THE
PRESENCE OF MASONRY WEEPS AND OTHER WALL DRAINAGE
MECHANISMS. DO NOT COVER WEEPS, OR IMPEDE THE ABILITY
OF MOISTURE TO EXIT WALL SYSTEMS.
PREFINISHED 24 GA. GALV. STEEL COPING CAP. HOOK OUTSIDE
FACE TO CONTINUOUS CLEAT, AND SECURE INNER FACE WITH
GASKETED FASTENERS APPROPRIATE FOR THE SUBSTRATE
ENCOUNTERED 18-INCHES O.C. MAX., AND WITHIN 2-INCHES OF
EACH END. JOIN ADJACENT CAP SECTIONS USING 1-INCH HIGH
STANDING SEAMS.
22 GA. GALV. STEEL CONTINUOUS CLEAT. FABRICATE AS SHOWN TO
CREATE 1/2-INCH PER FOOT SLOPE TOWARD INNER FACE. SECURE
HORIZONTAL FLANGE AND VERTICAL FACE WITH RING SHANK COATED
NAILS 6-INCHES O.C. MAX.
NOTE: TAPERED INSULATION, IF SPECIFIED, IS NOT SHOWN FOR
CLARITY.
SPECIFIED POLYISOCYANURATE INSULATION
EXISTING STRUCTURAL DECK
EPDM ROOFING MEMBRANE
REINFORCED PERIMETER FASTENING
STRIP WITH FACTORY-LAMINATED SEAM
TAPE. PRIME EPDM MEMBRANE PRIOR TO
APPLICATION TO REINFORCED FASTENING
STRIP.
EPDM FLASHING MEMBRANE, FULLY
ADHERED TO CURB
FASTENERS AND 2-INCH PLATES,
12-INCHES O.C. MAX.
EXTEND FULLY-ADHERED EPDM FLASHING MEMBRANE UP AND OVER
PARAPET WALL, AND DOWN OUTSIDE FASCIA. SECURE WITH ROOFING
NAILS AFFIXED WITH 1-INCH DIAMETER METAL CAPS 12" O.C. MAX.
COVER BOARD - 1/2-INCH THICK
UNDERLAYMENT
PREFINISHED 24 GA. GALV. STEEL PARAPET CAP.
TURN UP WALL 2-INCHES, MIN., INSTALL BUTYL TAPE
BEHIND TURN-UP, AND SECURE.
FULLY-ADHERED EPDM FLASHING MEMBRANE
COPING CAP TERMINATION
AT END WALLS
FOR USE WHERE PARAPET WALLS AND
RELATED COPING CAPS TERMINATE
INTO VERTICAL WALLS.
PREFINISHED 24 GA. GALV. STEEL REGLETED
COUNTERFLASHING. SECURE TO SUBSTRATE WITH
GASKETED FASTENERS 12-INCHES O.C., MIN. 2
FASTENERS.
SEALANT
CUT REGLET INTO WALL
2" M
IN
1" M
IN
1"
SEALANT - SEAL BOTH ENDS OF
STANDING SEAM
PARAPET WALL STEEL COPING CAP
BUTTON PUNCH
COPING CAP JOINT PROFILE
SINGLE-LOCK STANDING SEAM; FOR USE
WHERE ADJACENT COPING CAPS ARE TO BE
JOINED, BUTTON PUNCH.
FIELD VERIFY WALL WIDTH
H
EI
G H
T
VA
R
IE
S;
-IN
C
H M
IN
IM
U M
NOMINAL 2-INCH THICK WOOD BLOCKING - WIDTH AS NECESSARY
TO MATCH EXISTING PARAPET WALL WIDTH. THICKNESS AS
NECESSARY TO ACHIEVE 4-INCH MINIMUM FLASHING HEIGHT.
SECURE TO SUBSTRATE 18-INCHES O.C. MAX. DECREASE
FASTENER SPACING TO 9-INCHES O.C. WITHIN 10-FEET OF A
BUILDING CORNER.
3" M
IN
SELF-ADHERING MEMBRANE - LAP 4-INCHES OVER
UNDERLAYMENT
ASPHALT SHINGLES. SECURE EACH FULL-LENGTH
SHINGLE WITH SIX ROOFING NAILS.
EXISTING STRUCTURAL DECK
ASPHALT HIP SHINGLES. SECURE WITH ROOFING
NAILS. SEAL EXPOSED NAILS.
RIDGE FLASHING DETAIL
NOTE: DO NOT INSTALL ASPHALT SHINGLES CONFIGURED WITH RIDGE VENTS AT
HIPS. EXTEND SELF-ADHERING MEMBRANE OVER HIP (18-INCHES ON EACH SIDE
OF HIP, AND OVERLAP OVER UNDERLAYMENT 4-INCHES, MIN.).
18" MIN.BOTH SIDESOF RIDGE
4"
LAP
FASTERNERS TO PENETRATE
THROUGH ALL LAYERS OF ROOFING
MATERIAL AND INTO DECK
RIDGE SHINGLES
SEALING STRIPS
SELF-ADHERING
MEMBRANE. WRAP
OVER RIDGE
UNDERLAYMENT
SELF-ADHERING
MEMBRANE
ASPHALT SHINGLES
SELF-ADHERING MEMBRANE - LAP 4-INCHES OVER
UNDERLAYMENT
ASPHALT SHINGLES. SECURE EACH FULL-LENGTH
SHINGLE WITH SIX ROOFING NAILS.
EXISTING STRUCTURAL DECK
ASPHALT HIP SHINGLES. SECURE WITH ROOFING
NAILS. SEAL EXPOSED NAILS.
HIP FLASHING DETAIL
NOTE: DO NOT INSTALL ASPHALT SHINGLES CONFIGURED WITH RIDGE VENTS AT
HIPS. EXTEND SELF-ADHERING MEMBRANE OVER HIP (18-INCHES ON EACH SIDE
OF HIP, AND OVERLAP OVER UNDERLAYMENT 4-INCHES, MIN.).
18" MIN.
BOTH SIDES OF HIP 4"
LAP
UNDERLAYMENT
SELF-ADHERING MEMBRANE.
EXTEND UPSLOPE 24-INCHES MIN.,
BEYOND INTERIOR WALL OF THE
BUILDING ENVELOPE AS SHOWN.
EXTEND SELF-ADHERING MEMBRANE
OVER FLANGE OF PERIMETER EDGE
FASCIA METAL AS…
This is the start of the file's text. The full file is on GovTribe.