24029A-06 10 53-Miscellaneous Rough Carpentry.pdf

PDF 182 KB Posted

Attached to
RIARNG CAMP VARNUM T-18 RENOVATIONS
Solicitation number
RFQ26006763
Issued by
Providence County, Rhode Island

About this file

This is a specification document for miscellaneous rough carpentry work associated with the Rhode Island Army National Guard's Building T-18 renovation project at Camp Varnum in Narragansett, Rhode Island. The specification outlines materials and construction standards for framing with dimension lumber, wood blocking, cants, nailers, wood furring, wood sleepers, PVC exterior trim, composite decking and fastening systems, composite porch railings, and plywood wall and floor panels. Key products include AZEK Building Products TimberTech composite decking (1 by 5-1/2 inches) with matching fascia boards and stair risers, vinyl railings at 42 inches high with standard support rails and balusters, and PVC trim boards in 1-inch and 5/4-inch nominal thickness. All lumber must comply with DOC PS 20 standards with a maximum moisture content of 19 percent for 2-inch nominal thickness or less, and must be graded by agencies certified by the ALSC Board of Review. Wood-preservative-treated materials must meet AWPA U1 standards with Use Category designations based on application, and fire-retardant-treated materials must achieve a flame spread index of 25 or less per ASTM E 84 testing. Plywood wall panels must be DOC PS 1, Exposure 1, C-D Plugged, fire-retardant treated, with minimum 5/8-inch nominal thickness, while flooring must utilize Sturdy-I-Floor panels with Class II or C flame spread classification.

Material delivery and storage requirements mandate that lumber be stacked flat with spacers to allow air circulation and protected from weather with waterproof sheeting. Certified wood from FSC-accredited forests is required, and all treated materials must include manufacturer certifications and warranties. Product data submittals are required for each type of process and factory-fabricated product, including documentation from chemical treatment manufacturers certifying compliance with specifications and physical property testing results. The specification references Section 017419 for construction waste management requirements and mandates that all materials bearing classification markings be representative of tested materials. Installation products for PVC trim include structural and flexible adhesive options and gap filler compounds. The project timeline indicates construction is anticipated to commence in September 2026, with substantial completion required 16 months after the start date and final completion within 60 days thereafter.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

24029A – 06 10 53 Camp Varnum Building T-18 Renovations

Rhode Island Army National Guard

Narragansett, Rhode Island

07.08.26 MISCELLANEOUS ROUGH CARPENTRY 06 10 53 - 1

SECTION 061053 - MISCELLANEOUS ROUGH CARPENTRY

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Framing with dimension lumber.

2. Wood blocking, cants, and nailers.

3. Wood furring.

4. Wood sleepers.

5. PVC Exterior Trim

6. Composite decking and fastening system

7. Composite porch railings

8. Plywood wall panels.

9. Plywood Flooring.

B. Related Requirements:

1. Section 017419 “Construction Waste Management Plan” for provision of waste management.

1.3 DEFINITIONS

A. Dimension Lumber: Lumber of 2 inches nominal (38 mm actual) or greater but less than 5 inches nominal (114 mm actual) in least dimension.

B. Lumber grading agencies, and the abbreviations used to reference them, include the following:

1. NeLMA: Northeastern Lumber Manufacturers' Association.

2. NHLA: National Hardwood Lumber Association.

3. NLGA: National Lumber Grades Authority.

4. SPIB: The Southern Pine Inspection Bureau.

5. WCLIB: West Coast Lumber Inspection Bureau.

6. WWPA: Western Wood Products Association.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.

06 10 53 - 2 MISCELLANEOUS ROUGH CARPENTRY 07.08.26

1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.

2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency.

3. For fire-retardant treatments, include physical properties of treated lumber both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency according to ASTM D 5664.

4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.

5. Include copies of warranties from chemical treatment manufacturers for each type of treatment.

1.5 INFORMATIONAL SUBMITTALS

A. Evaluation Reports: For the following, from ICC-ES:

1. Preservative-treated wood.

2. Fire-retardant-treated wood.

1.6 QUALITY ASSURANCE

A. Testing Agency Qualifications: For testing agency providing classification marking for fire-retardant treated material, an inspection agency acceptable to authorities having jurisdiction that periodically performs inspections to verify that the material bearing the classification marking is representative of the material tested.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Stack lumber flat with spacers beneath and between each bundle to provide air circulation.

Protect lumber from weather by covering with waterproof sheeting, securely anchored. Provide for air circulation around stacks and under coverings.

PART 2 - PRODUCTS

2.1 WOOD PRODUCTS, GENERAL

A. Certified Wood: Lumber and plywood shall be produced from wood obtained from forests certified by an FSC-accredited certification body to comply with FSC STD-01-001, "FSC Principles and Criteria for Forest Stewardship."

B. Lumber: DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, provide lumber that complies with the applicable rules of any rules-writing agency certified by the ALSC Board of Review. Provide lumber graded by an agency certified by the ALSC Board of Review to inspect and grade lumber under the rules indicated.

1. Factory mark each piece of lumber with grade stamp of grading agency.

2. Where nominal sizes are indicated, provide actual sizes required by DOC PS 20 for moisture content specified. Where actual sizes are indicated, they are minimum dressed sizes for dry lumber.

07.08.26 MISCELLANEOUS ROUGH CARPENTRY 06 10 53 - 3

3. Provide dressed lumber, S4S, unless otherwise indicated.

C. Maximum Moisture Content of Lumber: 19 percent for 2-inch nominal (38-mm actual) thickness or less, no limit for more than 2-inch nominal (38-mm actual) thickness unless otherwise indicated.

2.2 WOOD-PRESERVATIVE-TREATED MATERIALS

A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 for interior construction not in contact with the ground, Use Category UC3b for exterior construction not in contact with the ground, and Use Category UC4a for items in contact with the ground.

1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium. Do not use inorganic boron (SBX) for sill plates.

B. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or does not comply with requirements for untreated material.

C. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.

D. Application: Treat items indicated on Drawings, and the following:

1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

2. Wood sills, sleepers, blocking, furring, stripping, and similar concealed members in contact with masonry or concrete.

3. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.

4. Wood framing members that are less than 18 inches (460 mm) above the ground in crawl spaces or unexcavated areas.

5. Wood floor plates that are installed over concrete slabs-on-grade.

2.3 FIRE-RETARDANT-TREATED MATERIALS

A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article, that are acceptable to authorities having jurisdiction, and with fire-test-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency.

B. Fire-Retardant-Treated Lumber and Plywood by Pressure Process: Products with a flame spread index of 25 or less when tested according to ASTM E 84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet (3.2 m) beyond the centerline of the burners at any time during the test.

1. Use treatment that does not promote corrosion of metal fasteners.

2. Exterior Type: Treated materials shall comply with requirements specified above for fire-retardant-treated lumber and plywood by pressure process after being subjected to accelerated weathering according to ASTM D 2898. Use for exterior locations and where indicated.

06 10 53 - 4 MISCELLANEOUS ROUGH CARPENTRY 07.08.26

3. Interior Type A: Treated materials shall have a moisture content of 28 percent or less when tested according to ASTM D 3201 at 92 percent relative humidity. Use where exterior type is not indicated.

C. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Kiln-dry plywood after treatment to a maximum moisture content of 15 percent.

D. Identify fire-retardant-treated wood with appropriate classification marking of testing and inspecting agency acceptable to authorities having jurisdiction. At a minimum, identify fire retardant treated wood with the Underwriters Laboratories label or stamp attesting to the FRS rating or flame spread and smoke index rating, or the ESR Building Code Approval.

E. Application: Treat items indicated on Drawings, and the following:

1. Framing for raised platforms.

2. Concealed blocking in fire rated construction.

3. Plywood backing panels.

2.4 COMPOSITE DECKING

A. Basis of Design: Subject to compliance with requirements, provide AZEK Building Products;

“TimberTech” - Harvest Collection or comparable product by one of the following:

1. CertainTeed Corporation

2. Fiberon

3. Trex Company, Inc.

B. Composite Decking: Solid capped four-sided shapes made from a mixture of cellulose fiber and polyethylene or polypropylene.

1. Decking Standard: ICC-ES AC174

2. Decking Size: 1 by 5-1/2 inches (24 by 136 mm)

3. Decking Length: As needed full length where possible.

4. Configuration: Provide product with grooved edges designed for fastening with concealed deck fasteners.

5. Surface Texture: Embossed woodgrain.

6. Color: As selected from manufacturers full range.

7. Fascia Board: ½’ by 11-3/4” matching decking color.

8. Stair Riser Board: 7.25” by length needed matching decking color.

2.5 DECKING FASTENING SYSTEM

A. Basis of Design Product: Subject to compliance with requirement, provide AZEK Building Products; Cortex, Fusionloc, or comparable product by one of the following.

1. Blue Heron Enterprises, LLC

2. Grabber Construction Products

3. KK Mfg. Co. Inc.

4. M.M. Products, Inc.

2.6 VINYL RAILINGS

A. Basis of Design Product: Subject to compliance with requirement, provide TimberTech Limited, 894 Prairie Avenue, Wilmington, Ohio 45177, or comparable product.

B. Structural Performance Requirements: BuilderRail systems performance must meet or exceed design loading specified in Chapter 16 of the IBC, Section R301 of IRC and UBC Chapter 16 when tested in accordance with ICC-ES AC174.

07.08.26 MISCELLANEOUS ROUGH CARPENTRY 06 10 53 - 5

C. Fire Test-Response Characteristics per ASTM E-84.

D. Railings (Color – To be selected from Manufacturers standard selection).

a. 42 inch high.

b. Top Rail, 6’-0” or 8’-0”.

c. Support Rail, 6’-0” or 8’-0”.

d. Balusters, 42” high for Guardrails, 34-38” high at stairs.

e. Bottom Rail, 6’-0” or 8’-0”.

f. Foot Blocks, Provide manufacturers standard.

g. Mounting Hardware, Provide manufacturers standard.

h. Accessories, Provide manufacturers standard Post Covers, Post Skirts and Post Caps.

2.7 PVC TRIM

A. Basis-of-Design Product: Azek Building Products, Inc. 5215 Old Orchard Road, Suite 725, Skokie, IL 60077 - 1-800-275-2935

B. Trim Boards: 1” and 5/4” nominal thickness x widths as indicated on drawings.

C. Installation Products:

1. Bond & Fill STRUCTURAL: Structural silicone.

2. Bond & Fill FLEX: flexible adhesive.

3. Bond & Fill FOR PAINTERS: nail hole and gap filler compound.

2.7 MISCELLANEOUS LUMBER

A. General: Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following:

1. Blocking.

2. Nailers.

3. Cants.

4. Furring.

5. Grounds.

B. For items of dimension lumber size, provide Construction or No. 2 grade lumber of any species.

C. For concealed boards, provide lumber with 19 percent maximum moisture content and any of the following species and grades:

1. Mixed southern pine, No. 2 grade; SPIB.

2. Eastern softwoods, No. 2 Common grade; NELMA.

06 10 53 - 6 MISCELLANEOUS ROUGH CARPENTRY 07.08.26

3. Northern species, No. 2 Common grade; NLGA.

4. Western woods, Construction or No. 2 Common grade; WCLIB or WWPA.

D. For blocking not used for attachment of other construction, Utility, Stud, or No. 3 grade lumber of any species may be used provided that it is cut and selected to eliminate defects that will interfere with its attachment and purpose.

E. For blocking and nailers used for attachment of other construction, select and cut lumber to eliminate knots and other defects that will interfere with attachment of other work.

F. For furring strips for installing plywood or hardboard paneling, select boards with no knots capable of producing bent-over nails and damage to paneling.

2.8 PLYWOOD WALL PANELS

A. Wall Panels: DOC PS 1, Exposure 1, C-D Plugged, fire-retardant treated, in thickness indicated or, if not indicated, not less than 5/8-inch (19-mm) nominal thickness.

2.9 PLYWOOD FLOORS

A. Flooring: Sturdy-I-Floor panels (Basis of Design)

1. Primary Species: Southern Yellow Pine and Western Species

2. Testing Agency: APA – The Engineered Wood Association

3. Classification: Exposure 1 – Plywood suitable for uses not permanently exposed to weather.

4. Flame Spread Classification: Class II or C based on the ASTM E-84/UL723 “Test for

Surface Burning Characteristics of Building Materials”

5. Flame Spread Rating: Flame spread Index 76 to 200, smoke developed index <200

6. Building Code Compliance: PS 1-09

7. Performance Category: 1 1/8 PERF CAT (1.091” panel thickness)

2.10 FASTENERS

B. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacture.

1. Where carpentry is exposed to weather, in ground contact, pressure-preservative treated, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A 153/A 153M or of Type 304 stainless steel.

C. Nails, Brads, and Staples: ASTM F 1667.

D. Power-Driven Fasteners: NES NER-272.

E. Wood Screws: ASME B18.6.1.

F. Screws for Fastening to Metal Framing: ASTM C 1002, length as recommended by screw manufacturer for material being fastened.

G. Lag Bolts: ASME B18.2.1 (ASME B18.2.3.8M).

H. Bolts: Steel bolts complying with ASTM A 307, Grade A (ASTM F 568M, Property Class 4.6);

with ASTM A 563 (ASTM A 563M) hex nuts and, where indicated, flat washers.

07.08.26 MISCELLANEOUS ROUGH CARPENTRY 06 10 53 - 7

I. Expansion Anchors: Anchor bolt and sleeve assembly of material indicated below with capability to sustain, without failure, a load equal to 6 times the load imposed when installed in unit masonry assemblies and equal to 4 times the load imposed when installed in concrete as determined by testing per ASTM E 488 conducted by a qualified independent testing and inspecting agency.

1. Material: Carbon-steel components, zinc plated to comply with ASTM B 633, Class Fe/Zn 5.

2. Material: Stainless steel with bolts and nuts complying with ASTM F 593 and ASTM F 594, Alloy Group 1 or 2 (ASTM F 738M and ASTM F 836M, Grade A1 or A4).

3 EXECUTION

3.7.1.1 INSTALLATION, GENERAL

A. Set carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Fit carpentry to other construction; scribe and cope as needed for accurate fit.

Locate[ furring,] nailers, blocking, and similar supports to comply with requirements for attaching other construction.

B. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking.

C. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame Construction," unless otherwise indicated.

D. Install plywood backing panels by fastening to studs; coordinate locations with utilities requiring backing panels. Install fire-retardant treated plywood backing panels with classification marking of testing agency exposed to view.

E. Metal Framing Anchors: Install metal framing anchors to comply with manufacturer's written instructions. Install fasteners through each fastener hole.

F. Do not splice structural members between supports unless otherwise indicated.

G. Provide blocking and framing as indicated and as required to support facing materials, fixtures, specialty items, and trim.

1. Provide metal clips for fastening gypsum board or lath at corners and intersections where framing or blocking does not provide a surface for fastening edges of panels. Space clips not more than 16 inches (406 mm) o.c.

H. Provide fire blocking in furred spaces, stud spaces, and other concealed cavities as indicated and as follows:

1. Fire block furred spaces of walls, at each floor level, at ceiling, and at not more than 96 inches (2438 mm) o.c. with solid wood blocking or noncombustible materials accurately fitted to close furred spaces.

2. Fire block concealed spaces of wood-framed walls and partitions at each floor level, at ceiling line of top story, and at not more than 96 inches (2438 mm) o.c. Where fire blocking is not inherent in framing system used, provide closely fitted solid wood blocks of same width as framing members and 2-inch nominal (38-mm actual) thickness.

06 10 53 - 8 MISCELLANEOUS ROUGH CARPENTRY 07.08.26

3. Fire block concealed spaces between floor sleepers with same material as sleepers to limit concealed spaces to not more than 100 sq. ft. (9.3 sq. m) and to solidly fill space below partitions.

4. Fire block concealed spaces behind combustible cornices and exterior trim at not more than 20 feet (6 m) o.c.

I. Sort and select lumber so that natural characteristics will not interfere with installation or with fastening other materials to lumber. Do not use materials with defects that interfere with function of member or pieces that are too small to use with minimum number of joints or optimum joint arrangement.

J. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber.

1. Use inorganic boron for items that are continuously protected from liquid water.

2. Use copper naphthenate for items not continuously protected from liquid water.

K. Securely attach carpentry work to substrate by anchoring and fastening as indicated, complying with the following:

1. NES NER-272 for power-driven fasteners.

2. Table 2304.9.1, "Fastening Schedule," in ICC's International Building Code.

L. Use steel common nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections between members. Install fasteners without splitting wood. Drive nails snug but do not countersink nail heads unless otherwise indicated.

M. Stair and Porch Railing System: Install according to manufacturers instructions. Cut, and rout using carbide tipped blades. Pre-drill holes and cut ends square.

N. Composite Decking:

1. Concealed Decking Clips: Black-oxide-coated, stainless-steel clips designed to secure decking material and provide uniform spacing of decking material.

2. Fasteners: Stainless steel screws, minimum #7 size, in sufficient length to penetrate not less than 1-1/4” into wood framing substrate.

O. PVC TRIM

1. Install PVC trim in strict accordance with manufacturer’s written instructions.

2. Where possible, attach trim utilizing nailing clips provided by manufacturer to avoid face nailing.

3. Use a hidden fastener system where necessary to face fasten through trim and sheet materials.

4. Hidden fastener system shall of be equal to “FastenMaster Cortex Concealed

Fastening System”.

07.08.26 MISCELLANEOUS ROUGH CARPENTRY 06 10 53 - 9

5. Contact Information: 800.518.3569 – info@fastenmaster.com

6. Butted joints shall be glued with Bond & Fill STRUCTURAL Adhesive to eliminate separation of joint.

P. WOOD BLOCKING, AND NAILER INSTALLATION

A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved.

B. Attach items to substrates to support applied loading. Recess bolts and nuts flush with surfaces unless otherwise indicated.

END OF SECTION 061053

mailto:info@fastenmaster.com

PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Framing with dimension lumber.
2. Wood blocking, cants, and nailers.
3. Wood furring.
4. Wood sleepers.
5. PVC Exterior Trim
6. Composite decking and fastening system
7. Composite porch railings
8. Plywood wall panels.
9. Plywood Flooring.
B. Related Requirements:
1. Section 017419 “Construction Waste Management Plan” for provision of waste management.
1.3 DEFINITIONS
A. Dimension Lumber: Lumber of 2 inches nominal (38 mm actual) or greater but less than 5 inches nominal (114 mm actual) in least dimension.
B. Lumber grading agencies, and the abbreviations used to reference them, include the following:
1. NeLMA: Northeastern Lumber Manufacturers' Association.
2. NHLA: National Hardwood Lumber Association.
3. NLGA: National Lumber Grades Authority.
4. SPIB: The Southern Pine Inspection Bureau.
5. WCLIB: West Coast Lumber Inspection Bureau.
6. WWPA: Western Wood Products Association.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.
1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.
2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified in...
3. For fire-retardant treatments, include physical properties of treated lumber both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency according to ASTM D 5664.
4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.
5. Include copies of warranties from chemical treatment manufacturers for each type of treatment.
1.5 INFORMATIONAL SUBMITTALS
A. Evaluation Reports: For the following, from ICC-ES:
1. Preservative-treated wood.
2. Fire-retardant-treated wood.
1.6 QUALITY ASSURANCE
A. Testing Agency Qualifications: For testing agency providing classification marking for fire-retardant treated material, an inspection agency acceptable to authorities having jurisdiction that periodically performs inspections to verify that the ma...
1.7 DELIVERY, STORAGE, AND HANDLING
A. Stack lumber flat with spacers beneath and between each bundle to provide air circulation. Protect lumber from weather by covering with waterproof sheeting, securely anchored. Provide for air circulation around stacks and under coverings.
PART 2 - PRODUCTS
2.1 WOOD PRODUCTS, GENERAL
A. Certified Wood: Lumber and plywood shall be produced from wood obtained from forests certified by an FSC-accredited certification body to comply with FSC STD-01-001, "FSC Principles and Criteria for Forest Stewardship."
B. Lumber: DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, provide lumber that complies with the applicable rules of any rules-writing agency certified by the ALSC Board of Review. Provide lumber gra...
1. Factory mark each piece of lumber with grade stamp of grading agency.
2. Where nominal sizes are indicated, provide actual sizes required by DOC PS 20 for moisture content specified. Where actual sizes are indicated, they are minimum dressed sizes for dry lumber.
3. Provide dressed lumber, S4S, unless otherwise indicated.

C. Maximum Moisture Content of Lumber: 19 percent for 2-inch nominal (38-mm actual) thickness or less, no limit for more than 2-inch nominal (38-mm actual) thickness unless otherwise indicated.

2.2 WOOD-PRESERVATIVE-TREATED MATERIALS
A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 for interior construction not in contact with the ground, Use Category UC3b for exterior construction not in contact with the ground, and Use Category UC4a for items in contact ...
1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium. Do not use inorganic boron (SBX) for sill plates.
B. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or does not comply with requirements for untreated material.
C. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.
D. Application: Treat items indicated on Drawings, and the following:
1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.
2. Wood sills, sleepers, blocking, furring, stripping, and similar concealed members in contact with masonry or concrete.
3. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.
4. Wood framing members that are less than 18 inches (460 mm) above the ground in crawl spaces or unexcavated areas.
5. Wood floor plates that are installed over concrete slabs-on-grade.
2.3 FIRE-RETARDANT-TREATED MATERIALS
A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article, that are acceptable to authorities having jurisdiction, and with fire-test-response characteristics specified as determined b...
B. Fire-Retardant-Treated Lumber and Plywood by Pressure Process: Products with a flame spread index of 25 or less when tested according to ASTM E 84, and with no evidence of significant progressive combustion when the test is extended an additional ...
1. Use treatment that does not promote corrosion of metal fasteners.
2. Exterior Type: Treated materials shall comply with requirements specified above for fire-retardant-treated lumber and plywood by pressure process after being subjected to accelerated weathering according to ASTM D 2898. Use for exterior locations...
3. Interior Type A: Treated materials shall have a moisture content of 28 percent or less when tested according to ASTM D 3201 at 92 percent relative humidity. Use where exterior type is not indicated.
C. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Kiln-dry plywood after treatment to a maximum moisture content of 15 percent.
D. Identify fire-retardant-treated wood with appropriate classification marking of testing and inspecting agency acceptable to authorities having jurisdiction. At a minimum, identify fire retardant treated wood with the Underwriters Laboratories labe...
E. Application: Treat items indicated on Drawings, and the following:
1. Framing for raised platforms.
2. Concealed blocking in fire rated construction.
3. Plywood backing panels.
2.4 COMPOSITE DECKING
A. Basis of Design: Subject to compliance with requirements, provide AZEK Building Products; “TimberTech” - Harvest Collection or comparable product by one of the following:
1. CertainTeed Corporation
2. Fiberon
3. Trex Company, Inc.
B. Composite Decking: Solid capped four-sided shapes made from a mixture of cellulose fiber and polyethylene or polypropylene.
1. Decking Standard: ICC-ES AC174
2. Decking Size: 1 by 5-1/2 inches (24 by 136 mm)
3. Decking Length: As needed full length where possible.
4. Configuration: Provide product with grooved edges designed for fastening with concealed deck fasteners.
5. Surface Texture: Embossed woodgrain.
6. Color: As selected from manufacturers full range.
7. Fascia Board: ½’ by 11-3/4” matching decking color.
8. Stair Riser Board: 7.25” by length needed matching decking color.
2.5 DECKING FASTENING SYSTEM
A. Basis of Design Product: Subject to compliance with requirement, provide AZEK Building Products; Cortex, Fusionloc, or comparable product by one of the following.
1. Blue Heron Enterprises, LLC
2. Grabber Construction Products
3. KK Mfg. Co. Inc.
4. M.M. Products, Inc.
2.6 VINYL RAILINGS
A. Basis of Design Product: Subject to compliance with requirement, provide TimberTech Limited, 894 Prairie Avenue, Wilmington, Ohio 45177, or comparable product.
B. Structural Performance Requirements: BuilderRail systems performance must meet or exceed design loading specified in Chapter 16 of the IBC, Section R301 of IRC and UBC Chapter 16 when tested in accordance with ICC-ES AC174.
C. Fire Test-Response Characteristics per ASTM E-84.
D. Railings (Color – To be selected from Manufacturers standard selection).
a. 42 inch high.
b. Top Rail, 6’-0” or 8’-0”.
c. Support Rail, 6’-0” or 8’-0”.
d. Balusters, 42” high for Guardrails, 34-38” high at stairs.
e. Bottom Rail, 6’-0” or 8’-0”.
f. Foot Blocks, Provide manufacturers standard.
g. Mounting Hardware, Provide manufacturers standard.
h. Accessories, Provide manufacturers standard Post Covers, Post Skirts and Post Caps.
2.7 PVC TRIM
A. Basis-of-Design Product: Azek Building Products, Inc. 5215 Old Orchard Road, Suite 725, Skokie, IL 60077 - 1-800-275-2935
B. Trim Boards: 1” and 5/4” nominal thickness x widths as indicated on drawings.
C. Installation Products:
1. Bond & Fill STRUCTURAL: Structural silicone.
2. Bond & Fill FLEX: flexible adhesive.
3. Bond & Fill FOR PAINTERS: nail hole and gap filler compound.
2.7 MISCELLANEOUS LUMBER
A. General: Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following:
1. Blocking.
2. Nailers.
3. Cants.
4. Furring.
5. Grounds.
B. For items of dimension lumber size, provide Construction or No. 2 grade lumber of any species.
C. For concealed boards, provide lumber with 19 percent maximum moisture content and any of the following species and grades:
1. Mixed southern pine, No. 2 grade; SPIB.
2. Eastern softwoods, No. 2 Common grade; NELMA.
3. Northern species, No. 2 Common grade; NLGA.
4. Western woods, Construction or No. 2 Common grade; WCLIB or WWPA.
D. For blocking not used for attachment of other construction, Utility, Stud, or No. 3 grade lumber of any species may be used provided that it is cut and selected to eliminate defects that will interfere with its attachment and purpose.
E. For blocking and nailers used for attachment of other construction, select and cut lumber to eliminate knots and other defects that will interfere with attachment of other work.
F. For furring strips for installing plywood or hardboard paneling, select boards with no knots capable of producing bent-over nails and damage to paneling.
2.8 PLYWOOD WALL PANELS
A. Wall Panels: DOC PS 1, Exposure 1, C-D Plugged, fire-retardant treated, in thickness indicated or, if not indicated, not less than 5/8-inch (19-mm) nominal thickness.
2.9 PLYWOOD FLOORS
A. Flooring: Sturdy-I-Floor panels (Basis of Design)
1. Primary Species: Southern Yellow Pine and Western Species
2. Testing Agency: APA – The Engineered Wood Association
3. Classification: Exposure 1 – Plywood suitable for uses not permanently exposed to weather.
4. Flame Spread Classification: Class II or C based on the ASTM E-84/UL723 “Test for Surface Burning Characteristics of Building Materials”
5. Flame Spread Rating: Flame spread Index 76 to 200, smoke developed index <200
6. Building Code Compliance: PS 1-09
7. Performance Category: 1 1/8 PERF CAT (1.091” panel thickness)
2.10 FASTENERS
B. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacture.
1. Where carpentry is exposed to weather, in ground contact, pressure-preservative treated, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A 153/A 153M or of Type 304 stainless steel.
C. Nails, Brads, and Staples: ASTM F 1667.
D. Power-Driven Fasteners: NES NER-272.
E. Wood Screws: ASME B18.6.1.
F. Screws for Fastening to Metal Framing: ASTM C 1002, length as recommended by screw manufacturer for material being fastened.
G. Lag Bolts: ASME B18.2.1 (ASME B18.2.3.8M).
H. Bolts: Steel bolts complying with ASTM A 307, Grade A (ASTM F 568M, Property Class 4.6); with ASTM A 563 (ASTM A 563M) hex nuts and, where indicated, flat washers.
I. Expansion Anchors: Anchor bolt and sleeve assembly of material indicated below with capability to sustain, without failure, a load equal to 6 times the load imposed when installed in unit masonry assemblies and equal to 4 times the load imposed wh...
1. Material: Carbon-steel components, zinc plated to comply with ASTM B 633, Class Fe/Zn 5.
2. Material: Stainless steel with bolts and nuts complying with ASTM F 593 and ASTM F 594, Alloy Group 1 or 2 (ASTM F 738M and ASTM F 836M, Grade A1 or A4).
3 EXECUTION
3.7.1.1 INSTALLATION, GENERAL
A. Set carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Fit carpentry to other construction; scribe and cope as needed for accurate fit. Locate[ furring,] nailers, blocking, and similar supports to comply wi...
B. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking.
C. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame Construction," unless otherwise indicated.
D. Install plywood backing panels by fastening to studs; coordinate locations with utilities requiring backing panels. Install fire-retardant treated plywood backing panels with classification marking of testing agency exposed to view.
E. Metal Framing Anchors: Install metal framing anchors to comply with manufacturer's written instructions. Install fasteners through each fastener hole.
F. Do not splice structural members between supports unless otherwise indicated.
G. Provide blocking and framing as indicated and as required to support facing materials, fixtures, specialty items, and trim.
1. Provide metal clips for fastening gypsum board or lath at corners and intersections where framing or blocking does not provide a surface for fastening edges of panels. Space clips not more than 16 inches (406 mm) o.c.
H. Provide fire blocking in furred spaces, stud spaces, and other concealed cavities as indicated and as follows:
1. Fire block furred spaces of walls, at each floor level, at ceiling, and at not more than 96 inches (2438 mm) o.c. with solid wood blocking or noncombustible materials accurately fitted to close furred spaces.
2. Fire block concealed spaces of wood-framed walls and partitions at each floor level, at ceiling line of top story, and at not more than 96 inches (2438 mm) o.c. Where fire blocking is not inherent in framing system used, provide closely fitted sol...
3. Fire block concealed spaces between floor sleepers with same material as sleepers to limit concealed spaces to not more than 100 sq. ft. (9.3 sq. m) and to solidly fill space below partitions.
4. Fire block concealed spaces behind combustible cornices and exterior trim at not more than 20 feet (6 m) o.c.
I. Sort and select lumber so that natural characteristics will not interfere with installation or with fastening other materials to lumber. Do not use materials with defects that interfere with function of member or pieces that are too small to use w...
J. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber.
1. Use inorganic boron for items that are continuously protected from liquid water.
2. Use copper naphthenate for items not continuously protected from liquid water.
K. Securely attach carpentry work to substrate by anchoring and fastening as indicated, complying with the following:
1. NES NER-272 for power-driven fasteners.
2. Table 2304.9.1, "Fastening Schedule," in ICC's International Building Code.
L. Use steel common nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections between members. Install faste...
M. Stair and Porch Railing System: Install according to manufacturers instructions. Cut, and rout using carbide tipped blades. Pre-drill holes and cut ends square.
N. Composite Decking:
1. Concealed Decking Clips: Black-oxide-coated, stainless-steel clips designed to secure decking material and provide uniform spacing of decking material.
2. Fasteners: Stainless steel screws, minimum #7 size, in sufficient length to penetrate not less than 1-1/4” into wood framing substrate.
O. PVC TRIM
1. Install PVC trim in strict accordance with manufacturer’s written instructions.
2. Where possible, attach trim utilizing nailing clips provided by manufacturer to avoid face nailing.
3. Use a hidden fastener system where necessary to face fasten through trim and sheet materials.
4. Hidden fastener system shall of be equal to “FastenMaster Cortex Concealed Fastening System”.
5. Contact Information: 800.518.3569 – info@fastenmaster.com

6. Butted joints shall be glued with Bond & Fill STRUCTURAL Adhesive to eliminate separation of joint.

P. WOOD BLOCKING, AND NAILER INSTALLATION
A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved.
B. Attach items to substrates to support applied loading. Recess bolts and nuts flush with surfaces unless otherwise indicated.