17) Building 20 Asbestos Survey 2011.pdf

PDF 286 KB Posted

Attached to
Z1DZ--EHRM Training and Admin Space - Construction Phase 1 - Hines, IL (VA-21-00027896)
Solicitation number
36C77621B0006
Issued by

About this file

This document is a presolicitation notice for a firm-fixed-price construction contract to renovate the building enclosure and perform selective interior demolition of Building 20 at the Hines VA Medical Center in Hines, Illinois. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses. The solicitation will be issued as an Invitation for Bid on or around February 22, 2021, with a response deadline of 90 days. The period of performance is 120 calendar days from notice to proceed. The construction value is between $1 million and $2 million. Questions must be submitted in writing by the specified deadline to the identified point of contact.

View the file

Other files

File Type Posted
578-21-703 sign in pre bid.pdf PDF
36C77621B0006 0004.docx DOCX document
36C77621B0006 0003.docx DOCX document
21) Revised 578-21-703 Specification Book r20210317.pdf PDF
36C77621B0006 0002.docx DOCX document
Attachment 26 - Hines Underground Utility Plan.pdf PDF
S05 - Technical Question and Answers Hines IFB 36C77621B0006.docx DOCX document
36C77621B0006 0001.docx DOCX document
Attachment 24 - SOW 578-21-703 EHRM Training and Admin Space Support - Phase 1 - Hines IL 2020-12-30.docx DOCX document
Attachment 27 - Inspection Summary Report Bldg 20 - 2010.pdf PDF
Attachment 25 - 578-21-703 ASK-01 Metal Panel Detail.pdf PDF
Attachment 28 - BLDG 20 R2010.xls XLS spreadsheet
Attachment 20 Revised - 578-21-703 Combined Drawing Set.pdf PDF
S02 - Solicitation 36C77621B0006 Final Released.docx DOCX document
23) Wage Determination DBA - Cook County.pdf PDF
2) Hines Underground Utility Plan.pdf PDF
1) Hines VA Campus Site Plan.pdf PDF
15) Infection Control Barrier Sample.pdf PDF
19) 578-21-703 Photos of Current Conditions.pdf PDF
3) Pre-Construction Checklist.pdf PDF
21) 578-21-703 Specification Book.pdf PDF
12) Contractor Parking.pdf PDF
9) Interim Life Safety Measures (ILSM).pdf PDF
18) Hines COVID-19 Guidelines.pdf PDF
7) Above Ceiling Entry and Wall Construction Permits.pdf PDF
5) Cutting Welding and Other Hot Work.pdf PDF
36C77621B0006.docx DOCX document
14) No Smoking Policy 10-1-19.pdf PDF
6) Dig Permit SOP Form.pdf PDF
11) Contractor PIV Instructions and Form.pdf PDF
20) 578-21-703 Combined Drawing Set.pdf PDF
16) Building 20 Renovation from 1989.pdf PDF
13) OIT Horizontal Cable Requirements.pdf PDF
8) Pre-Construction Risk Assessment (PCRA).pdf PDF
4) Safety and Health During Construction Activities.pdf PDF
22) CONTRACTOR SAFETY AND ENVIRONMENTAL RECORD EVALUATION FORM.docx DOCX document
10) Infection Control Risk Assessment (ICRA).pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

20-1

BUILDING 20

INSPECTION SUMMARY

In September 2010, an asbestos re-inspection of Building 20 was conducted by MC Consulting Inc. (MC2).

The asbestos re-inspection was conducted by an Illinois Department of Public Health (IDPH) Licensed

Asbestos Building Inspector, Roberto Rivera (IDPH License No. 100-06327). A copy of the inspector’s license is provided in the Appendix.

Prior to the field inspection, the following document was reviewed.

* 2006 asbestos re-inspection for Building 20.

The 2010 asbestos re-inspection was performed on the basis of the 2006 re-inspection information. The following was observed.

* During MC2’s visual re-inspection of Building 20, no new building materials were observed since the last re-inspection.

* Overall, suspect asbestos-containing materials (ACM) remained in good condition at the time of the inspection.

* Asbestos pipe insulation is likely to be concealed behind walls, within suspended or plaster ceilings, or in other inconspicuous locations throughout the building.

* The findings of the 2010 re-inspection are summarized in the 2010 reevaluation tables.

Abatement History:

The information collected from the existing abatement reports revealed that the following asbestos abatement was conducted at Building 20.

* Asbestos-containing floor tile and mastic were removed in the Motor Pool Office under negative air pressure; the removal was performed in April 2008.

20-2

BUILDING 20

RECOMMENDATIONS

Floor Tile

The 12” x 12” and 9” x 9” floor tiles and mastic were in good condition at the time of the inspection.

These materials were found to contain asbestos according to previous reports, and may be accessible to building occupants and maintenance personnel. It is recommended that the Hines VA continue to monitor the condition of these materials under an Operation and Maintenance Program. The materials can remain in place until major renovation or demolition requires their removal.

Pipe Insulation

Asbestos pipe insulation and associated fittings were in good condition at the time of the inspection. These materials were found to contain asbestos according to previous reports. These materials may be accessible to building occupants and maintenance personnel. Suspect ACMs are likely to be concealed behind walls, within suspended or plaster ceilings, or in other inconspicuous locations throughout the building. These materials can remain in place until major renovation or demolition requires their removal.

General Recommendations

The Hines VA should continue to follow its Asbestos Management Plan’s Operation and Maintenance

Program. It is also recommended that Hines VA prepare an Asbestos Removal Project Design prior to initiating any renovation activities in which ACM may be impacted. The asbestos design plan and specifications should be prepared and signed by an IDPH-licensed Asbestos Project Designer in accordance with IDPH and federal regulations. Asbestos abatement work should be conducted by a licensed abatement contractor under the supervision of a licensed Asbestos Project Manager, in accordance with all applicable federal, state, and local regulations.

Triennial Asbestos Re-Inspection Report Edward Hines Jr. VA Hospital 5000 South 5th Avenue, Hines, IL

MC Consulting Inc. January 2011

ABBREVIATIONS

MC Consulting Inc. A - January 2011

ABBREVIATIONS

This section defines the abbreviations used in the spreadsheets that list and assess, room-by-room, the asbestos-containing materials in each re-inspected building. Spreadsheet information includes:

* Type and percent of asbestos found in asbestos-containing materials (ACM)

* Quantity and condition of the ACM

* Description of the ACM

* Potential for ACM disturbance

* Other parameters needed for assessing and prioritizing response actions

Additional terminology used in the spreadsheets for prioritizing response actions is described in the Glossary of Terms.

TABLE HEADINGS QUANTITY

ACM Asbestos-Containing Material LF Lineal Feet

COND Condition PIPE DIA Diameter in Inches

POT FOR Potential for of Actual Pipe

DIST Disturbance SF Square Feet

QTY Quantity THICKNESS Inches

BUILDING AREA TYPE

ATTC Attic ACT Actinolite

BSMT Basement AM Amosite

CRWL Crawl Space ANT Anthophyllite

EXT Exterior CC Crocidolite

OTHR Other (Describe) CHR Chrysotile

PENT Penthouse MIX Mixture

TUNN Tunnel TM Tremolite

TREN Trench

FUNCTION

ACT Ceiling Tile PIPE-F-CHW Pipe Fitting Chilled Water

BO / FU Boiler / Furnace Insulation PIPE F-CON Pipe Fitting Condensate

DOOR Door PIPE F-DCW Pipe Fitting Domestic Cold Water

DUCT Duct Insulation PIPE F-DHW Pipe Fitting Domestic Hot Water

DUST Debris / Settled Dust PIPE F-HTHW Pipe Fitting High Temp. Hot Water

EXT Exterior Construction PIPE F-STM Pipe Fitting Steam

FP Fireproofing PIPE-HTHW Pipe High Temperature Hot Water

FS Fire Stop PIPE-STM Pipe Steam

NSCM Nonsuspect Ceiling Material PLAS-A Acoustical Insulation / Plaster

NSFM Nonsuspect Floor Material PLAS-W Wall Plaster / Spackling

NSINS Nonsuspect Pipe Material RFNG Roofing

NSWM Nonsuspect Wall Material SHNG Shingles

OTHR Other (Describe) SUR Surface Application

PIPE Pipe Other TANK Tank Insulation

PIPE-CHW Pipe Chilled Water System VFT Floor Tile / Sheet

PIPE-COND Pipe Condensate VIB Vibration Damper

PIPE-DCW Pipe Domestic Cold Water WALL-BRD Wall Board

PIPE-DHW Pipe Domestic Hot Water WALL-INS Wall Insulation

PIPE-DRN Pipe Drain

MATERIAL DESCRIPTION

BLK Black FLKS Flecks

BLUE Blue GRN Green

BRN Brown GRY Gray

BSBRD Baseboard IRREG Irregular

BUR Burgundy LT Light

CMNT Cement MAR Maroon

CRM Cream MOT Mottled

DK Dark MSTC Mastic

DUCT INS NS Duct Insulation Nonsuspect MVE Mauve

FG Fiberglass N-ACC Non-Accessible

MATERIAL DESCRIPTION (Continued)

NSCM Nonsuspect Ceiling Material RED Red

NSFM Nonsuspect Floor Material RUST Rust

NSINS Nonsuspect Pipe Insulation SHT Sheet

NSWM Nonsuspect Wall Material SMTH Smooth

OLV Olive STRK Streaks

ORG Orange SWL Swirl

PAT Pattern TAN Tan

PERF Perforations TEXT Texture

PNHL Pinhole VAT Vinyl Asbestos Tile

PNK Pink VIO Violet

PVC Polyvinyl Chloride W / With

PURPLE Purple WHT While

RAN Random YEL Yellow

MC Consulting Inc. G - January 2011

GLOSSARY OF TERMS

This section defines the terms used in assessing and prioritizing response actions to asbestos-containing materials (ACM) as presented in the spreadsheets. The assessment of an ACM’s potential to release asbestos fibers into air was based on a visual inspection of its physical condition. Pertinent physical characteristics include the ACM’s friability, degree of damage or deterioration, and potential for disturbance. Response actions were prioritized based on a ranking of the ACM’s physical characteristics in accordance with the U.S. Environmental Protection Agency’s Asbestos Hazard Emergency Response Act (AHERA) regulations.

The following sections describe the following:

* ACM Friability

* ACM Condition

* Potential for ACM Disturbance

* Priority Action Ranking

* Nonsuspect Materials

* Not Accessible

ACM Friability

Y: Material that crumbled when hand pressure was applied, ranging from high friability—very soft material that crumbled with light hand pressure—to low friability—material that crumbled after exerting substantial hand pressure

N: Nonfriable material that could not be crumbled, lightly abraded, or powdered by exertion of hand pressure

ACM Condition

Good: No apparent damage to the material

Fair: Material had less than 10 percent overall damage or less than 25 percent localized damage

Poor: Material had 10 percent or more overall damage or 25 percent or more localized damage

Potential for ACM Disturbance

High: 1. Friable ACM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.

2. There is a reasonable likelihood that the ACM or its covering will become damaged, deteriorated, or delaminated due to factors such as recurrent damage or changes in the building’s use, operation and maintenance (O&M), or occupancy.

3. The ACM is subject to major or continuing disturbance due to factors such as accessibility, vibration, or air erosion.

Moderate: 1. Friable ACM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.

2. There is a reasonable likelihood that the ACM or its covering will become damaged, deteriorated, or delaminated due to factors such as recurrent damage or changes in the building’s use, operation and maintenance (O&M), or occupancy.

Low: The potential for contact with the ACM, influence of vibration, and potential for air erosion are assessed to be low.

Priority Action Ranking

1: Isolate the area and restrict access to necessary personnel. Remove or repair the material as soon as possible.

2: Repair or remove the material, or reduce the potential for disturbance as soon as possible. Follow up with an O&M program.

3 or 4: Repair the material and follow up with an O&M program.

5: Follow up with an O&M program, and reduce the material’s potential for disturbance.

6: Follow up with an O&M program, and further reduce the potential for disturbance.

7: Follow up with an O&M program, and take precautions to prevent the material from becoming friable during maintenance activities.

Nonsuspect Material

Nonsuspect material is building material that should be asbestos-free, and is coded NSFM, NSWM, NSCM, and NSINS, as defined in the abbreviations section. Nonsuspect materials were not sampled.

Not Accessible

Not accessible material is building material that cannot be accessed without breaking the integrity of the containing structure, and is denoted as N-ACC in the spreadsheet.

MC Consulting Inc. Building 20

LOCATION ACM % TYPE QTY SAMPLE MATERIAL DESCRIPTION REEVALUATION 2010 COMMENTS

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

AREA 1ST FLOOR

ROOM 100

BSBRD 0 NA 23 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 280 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 280 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 23 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

ACT 0 NA 280 SF 97786- 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 680 SF 97785- WALL BRD Y GOOD MOD NO CHANGE

ROOM 100A

ACT 0 NA 288 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 720 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 24 SF 97783- 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 288 SF 97781- 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 288 SF 97782- MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 24 SF 97784- MSTC FOR 97783 N GOOD LOW NO CHANGE

ROOM 102

ACT 0 NA 108 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 480 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 16 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 16 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 104

ACT 0 NA 448 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 880 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 29 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 29 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

ROOM 106

ACT 0 NA

SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA

SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

ACT 0 NA 50 SF 97787- 2'X4' WRM W PNHL GOOD NO CHANGE

ROOM 108

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

ACT 0 NA 144 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 480 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 16 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 16 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

BSBRD 0 NA 16 SF 97788- 4" TAN BSBRD N POOR LOW NO CHANGE

MSTC NA NA 16 SF 97789- MSTC FOR 97788 N FAIR LOW NO CHANGE

ROOM 110

ACT 0 NA 60 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 320 SF 97785-X WALL BRD N GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 11 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 60 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 60 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 11 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings

ROOM 112 NO CHANGE

ACT 0 NA 60 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 60 SF 97785-X WALL BRD Y FAIR MOD NO CHANGE

BSBRD 0 NA 11 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 60 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 60 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 11 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

R00M 114

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

WALL-BRD 0 NA 400 SF 97785-X WALL BRD Y FAIR MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 30 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 30 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 116

ACT 0 NA 280 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 118

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

ACT 0 NA 280 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

7 VFT 10 CHR 280 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 280 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

ROOM 120

ACT 0 NA 800 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 140 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 140 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 122

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 30 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 NA 600 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 600 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 30 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

ROOM 124

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

ROOM 125

ACT 0 NA 920 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

7 VFT 10 CHR NA 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR NA 97782-X MSTC FOR 97881 N GOOD LOW NO CHANGE

ROOM 126

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

CON 50 CHR NA 1 EA 97205-X CMNT COND FTG Y GOOD LOW NO CHANGE

STM 50 CHR NA 1 EA 97205-X CMNT FTG STM Y GOOD LOW NO CHANGE

2 COND 65 CHR NA 84 LF 97207- AIRCELL COND Y GOOD LOW NO CHANGE

Y/N DIST

60 CHR NA 12 LF 97204- AIRCELL W/PAPER WRAP STM Y GOOD LOW NO CHANGE

65 CHR NA 72 LF 97206- AIRCELL Y GOOD LOW NO CHANGE

STM 50 CHR NA 1 EA 97205- CMNT STM Y GOOD LOW NO CHANGE

ROOM 128

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 130

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 140

PLAS-A 0 NA 48 SF 97201-X PLAS Y GOOD MOD NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings

PLAS-W 0 NA 300 SF 97201- PLAS Y GOOD MOD NO CHANGE

ROOM 142

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 150

ACT 0 NA 72 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 360 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 12 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

VFT <1 CHR 72 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE

MSTC 0 NA 12 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 MSTC 20 CHR 72 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE

ROOM 152

ACT 0 NA 168 SF 97790-X 2'X4' PAT FLKS Y GO0D LOW NO CHANGE

PLAS-W 0 NA 500 SF 97201-X PLAS Y GOOD MOD NO CHANGE

BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

VFT <1 CHR 168 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE

MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 MSTC 20 CHR 168 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE

ROOM 154

PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 MSTC 20 CHR 50 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings

ACT 0 NA 50 SF 97790- 2'X4' PAT FLKS Y GOOD LOW NO CHANGE

VFT <1 CHR 50 SF 97791- 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE

ROOM 156

ACT 0 NA 126 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE

PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE

WALL-BRD 0 NA 150 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0' NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

VFT <1 CHR 126 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 MSTC 20 CHR 126 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE

ROOM 158

ACT 0 NA 240 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE

PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

VFT <1 CHR 240 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 240 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE

ROOM 160

ACT 0 NA 128 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE

PLAS-W 0 NA 450 SF 97201-X PLAS Y GOOD MOD NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 VFT 20 CHR 64 SF 97792- 9"X9" MAR W/CRM STRK N FAIR LOW NO CHANGE

7 VFT 10 CHR 64 SF 97793- 9"X9" CRM W/BLK STRK N FAIR LOW NO CHANGE

7 MSTC 20 CHR 128 SF 97794- MSTC FOR 97792 & 97793 N FAIR LOW NO CHANGE

ROOM 162

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 164

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

Y/N DIST

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

R00M 168

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 170

WALL-BRD 0 280 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NSFM NA NA NA NO CHANGE

7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y GOOD LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y GOOD LOW Presume behind walls & above ceilings

ROOM 172

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 174

WALL-BRD 0 NA 288 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

MSTC 0 NA 288 SF 97795-X MSTC FOR 97795 LAB RESULTS N FAIR LOW NO CHANGE

VFT 0 NA 288 SF 97795- 1'X1'BRN W/CRM & BLK STRK N FAIR MOD NO CHANGE

ROOM 176

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

* ROOM 178

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM HW1

ACT 0 NA 198 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 198 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

7 VFT 10 CHR 198 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 198 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

ROOM SW1

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

VFT 0 NA 56 SF 97203- CRM STAIR GUARD N GOOD LOW NO CHANGE

MSTC 0 NA 56 SF 97202- MSTC FOR 97203 N GOOD LOW NO CHANGE

ROOM SW2

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM SW3

PLAS-A 0 NA 60 SF 97201-X PLAS Y GOOD MOD NO CHANGE

PLAS-W 0 NA 120 SF 97201-X PLAS Y FAIR MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM SW4

ACT 0 NA 36 SF 97787-X 2'X4' WRM W/PNHL Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

VFT 0 NA 56 SF 97796- BLK STAIR GUARD N FAIR LOW NO CHANGE

AREA 2ND FLOOR

ROOM 200

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 202

ACT 0 NA 840 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 840 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

PLAS-W 0 NA 200 SF 97201-X PLAS Y GOOD MOD NO CHANGE

WALL-BRD 0 NA 200 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 40 SF 97788-X 4" TAN BSBRD N GOOD LOW NO CHANGE

7 MSTC 20 CHR 840 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE

MSTC 0 NA 40 SF 97789-X MSTC FOR 97788 N GOOD LOW NO CHANGE

7 VFT 10 CHR 840 SF 97401- 1'X1'CRM W/ GLD FLKS N GOOD MOD NO CHANGE

ROOM 204

ACT 0 NA 120 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 120 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

PLAS-W 0 NA 100 SF 97201-X PLAS Y GOOD MOD NO CHANGE

WALL-BRD 0 NA 100 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 15 SF 97788-X 4" TAN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 120 SF 97401-X 1'X1'CRM W/ GLD FLKS N GOOD LOW NO CHANGE

Y/N DIST

7 MSTC 20 CHR 120 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE

MSTC 0 NA 15 SF 97789-X MSTC FOR 97788 N GOOD LOW NO CHANGE

ROOM 206

ACT 0 NA 100 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 100 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

ROOM 208

ACT 0 NA 48 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 50 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings

ROOM 210

ACT 0 NA 270 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 350 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 30 SF 97406-X 4" GRY BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 30 SF 97406-X MSTC FOR 97406 LAB RESULTS N GOOD LOW NO CHANGE

VFT <1 CHR 270 SF 97404- 1'X1'GRY W/WHT STRK N GOOD MOD NO CHANGE

7 MSTC 20 CHR 270 SF 97405- MSTC FOR 97404 N GOOD LOW NO CHANGE

ROOM 212

ACT 0 NA 288 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 350 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

VFT <1 CHR 290 SF 97404-X 1'X1'GRY W/WHT STRK N GOOD MOD NO CHANGE

7 MSTC 20 CHR 290 SF 97405-X MSTC FOR 97404 N GOOD LOW NO CHANGE

MSTC 0 NA 30 SF 97406-X MSTC FOR 97406 LAB RESULTS N GOOD LOW NO CHANGE

BSBRD 0 NA 30 SF 97406- 4" GRY BSBRD N GOOD LOW NO CHANGE

ROOM 214

ACT 0 NA 384 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 190 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

RANK FUNCTION FRIABLE COND POT FOR

Y/N DIST

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 200 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 200 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

ROOM 216

ACT 0 NA 400 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE

ACT 0 NA 400 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 600 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE

BSBRD 0 NA 40 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

7 VFT 10 CHR 800 SF 97401-X 1'X1'CRM W/ GLD FLKS N GOOD LOW NO CHANGE

7 MSTC 20 CHR 800 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE

MSTC 0 NA 40 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

ROOM 218

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 222

ACT 0 NA 288 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 226

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 230

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

ROOM 250

ACT 0 NA 400 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

PLAS-W 0 NA 800 SF 97201-X PLAS Y GOOD LOW NO CHANGE

WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE

BSBRD 0 NA 60 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 60 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

Y/N DIST

ACT 0 NA 400 SF 97402- 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE

F 0 NA 400 SF 97403- FIREPROOFING Y GOOD LOW NO CHANGE

ROOM 299

ACT 0 NA 648 SF 97787-X 2'X4' WRM W/PNHL Y LOW NO CHANGE

WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE

BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE

MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE

VFT <1 CHR 60 SF NA 'X CRM W/WHT STRK N GOOD MOD NO CHANGE

7 MSTC 20 CHR 600 SF 97408- MSTC FOR 97407 N GOOD LOW NO CHANGE

ROOM SW10

NSCM NA NA NA NA NSCM NA NA NA NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

7 VFT 10 CHR 25 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 25 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

ROOM SW20

ACT 0 NA 192 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE

F 0 NA 84 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE

7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE

AREA PENTHOUSE

ROOM PENT

NSWM NA NA NA NA NSWM NA NA NA NO CHANGE

NSFM NA NA NA NA NSFM NA NA NA NO CHANGE

NSINS NA NA NA NA NSINS NA NA NA NO CHANGE

AREA EXTERIOR

ROOM EXT

BLDG 20
Asbesto Survey Glossary (when applicable).pdf
Asbestos Survey Abbreviations
Asbestos Survey Glossary