This document is a presolicitation notice for a firm-fixed-price construction contract to renovate the building enclosure and perform selective interior demolition of Building 20 at the Hines VA Medical Center in Hines, Illinois. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses. The solicitation will be issued as an Invitation for Bid on or around February 22, 2021, with a response deadline of 90 days. The period of performance is 120 calendar days from notice to proceed. The construction value is between $1 million and $2 million. Questions must be submitted in writing by the specified deadline to the identified point of contact.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
20-1
BUILDING 20
INSPECTION SUMMARY
In September 2010, an asbestos re-inspection of Building 20 was conducted by MC Consulting Inc. (MC2).
The asbestos re-inspection was conducted by an Illinois Department of Public Health (IDPH) Licensed
Asbestos Building Inspector, Roberto Rivera (IDPH License No. 100-06327). A copy of the inspector’s license is provided in the Appendix.
Prior to the field inspection, the following document was reviewed.
* 2006 asbestos re-inspection for Building 20.
The 2010 asbestos re-inspection was performed on the basis of the 2006 re-inspection information. The following was observed.
* During MC2’s visual re-inspection of Building 20, no new building materials were observed since the last re-inspection.
* Overall, suspect asbestos-containing materials (ACM) remained in good condition at the time of the inspection.
* Asbestos pipe insulation is likely to be concealed behind walls, within suspended or plaster ceilings, or in other inconspicuous locations throughout the building.
* The findings of the 2010 re-inspection are summarized in the 2010 reevaluation tables.
Abatement History:
The information collected from the existing abatement reports revealed that the following asbestos abatement was conducted at Building 20.
* Asbestos-containing floor tile and mastic were removed in the Motor Pool Office under negative air pressure; the removal was performed in April 2008.
20-2
BUILDING 20
RECOMMENDATIONS
Floor Tile
The 12” x 12” and 9” x 9” floor tiles and mastic were in good condition at the time of the inspection.
These materials were found to contain asbestos according to previous reports, and may be accessible to building occupants and maintenance personnel. It is recommended that the Hines VA continue to monitor the condition of these materials under an Operation and Maintenance Program. The materials can remain in place until major renovation or demolition requires their removal.
Pipe Insulation
Asbestos pipe insulation and associated fittings were in good condition at the time of the inspection. These materials were found to contain asbestos according to previous reports. These materials may be accessible to building occupants and maintenance personnel. Suspect ACMs are likely to be concealed behind walls, within suspended or plaster ceilings, or in other inconspicuous locations throughout the building. These materials can remain in place until major renovation or demolition requires their removal.
General Recommendations
The Hines VA should continue to follow its Asbestos Management Plan’s Operation and Maintenance
Program. It is also recommended that Hines VA prepare an Asbestos Removal Project Design prior to initiating any renovation activities in which ACM may be impacted. The asbestos design plan and specifications should be prepared and signed by an IDPH-licensed Asbestos Project Designer in accordance with IDPH and federal regulations. Asbestos abatement work should be conducted by a licensed abatement contractor under the supervision of a licensed Asbestos Project Manager, in accordance with all applicable federal, state, and local regulations.
Triennial Asbestos Re-Inspection Report Edward Hines Jr. VA Hospital 5000 South 5th Avenue, Hines, IL
MC Consulting Inc. January 2011
ABBREVIATIONS
MC Consulting Inc. A - January 2011
ABBREVIATIONS
This section defines the abbreviations used in the spreadsheets that list and assess, room-by-room, the asbestos-containing materials in each re-inspected building. Spreadsheet information includes:
* Type and percent of asbestos found in asbestos-containing materials (ACM)
* Quantity and condition of the ACM
* Description of the ACM
* Potential for ACM disturbance
* Other parameters needed for assessing and prioritizing response actions
Additional terminology used in the spreadsheets for prioritizing response actions is described in the Glossary of Terms.
TABLE HEADINGS QUANTITY
ACM Asbestos-Containing Material LF Lineal Feet
COND Condition PIPE DIA Diameter in Inches
POT FOR Potential for of Actual Pipe
DIST Disturbance SF Square Feet
QTY Quantity THICKNESS Inches
BUILDING AREA TYPE
ATTC Attic ACT Actinolite
BSMT Basement AM Amosite
CRWL Crawl Space ANT Anthophyllite
EXT Exterior CC Crocidolite
OTHR Other (Describe) CHR Chrysotile
PENT Penthouse MIX Mixture
TUNN Tunnel TM Tremolite
TREN Trench
FUNCTION
ACT Ceiling Tile PIPE-F-CHW Pipe Fitting Chilled Water
BO / FU Boiler / Furnace Insulation PIPE F-CON Pipe Fitting Condensate
DOOR Door PIPE F-DCW Pipe Fitting Domestic Cold Water
DUCT Duct Insulation PIPE F-DHW Pipe Fitting Domestic Hot Water
DUST Debris / Settled Dust PIPE F-HTHW Pipe Fitting High Temp. Hot Water
EXT Exterior Construction PIPE F-STM Pipe Fitting Steam
FP Fireproofing PIPE-HTHW Pipe High Temperature Hot Water
FS Fire Stop PIPE-STM Pipe Steam
NSCM Nonsuspect Ceiling Material PLAS-A Acoustical Insulation / Plaster
NSFM Nonsuspect Floor Material PLAS-W Wall Plaster / Spackling
NSINS Nonsuspect Pipe Material RFNG Roofing
NSWM Nonsuspect Wall Material SHNG Shingles
OTHR Other (Describe) SUR Surface Application
PIPE Pipe Other TANK Tank Insulation
PIPE-CHW Pipe Chilled Water System VFT Floor Tile / Sheet
PIPE-COND Pipe Condensate VIB Vibration Damper
PIPE-DCW Pipe Domestic Cold Water WALL-BRD Wall Board
PIPE-DHW Pipe Domestic Hot Water WALL-INS Wall Insulation
PIPE-DRN Pipe Drain
MATERIAL DESCRIPTION
BLK Black FLKS Flecks
BLUE Blue GRN Green
BRN Brown GRY Gray
BSBRD Baseboard IRREG Irregular
BUR Burgundy LT Light
CMNT Cement MAR Maroon
CRM Cream MOT Mottled
DK Dark MSTC Mastic
DUCT INS NS Duct Insulation Nonsuspect MVE Mauve
FG Fiberglass N-ACC Non-Accessible
MATERIAL DESCRIPTION (Continued)
NSCM Nonsuspect Ceiling Material RED Red
NSFM Nonsuspect Floor Material RUST Rust
NSINS Nonsuspect Pipe Insulation SHT Sheet
NSWM Nonsuspect Wall Material SMTH Smooth
OLV Olive STRK Streaks
ORG Orange SWL Swirl
PAT Pattern TAN Tan
PERF Perforations TEXT Texture
PNHL Pinhole VAT Vinyl Asbestos Tile
PNK Pink VIO Violet
PVC Polyvinyl Chloride W / With
PURPLE Purple WHT While
RAN Random YEL Yellow
MC Consulting Inc. G - January 2011
GLOSSARY OF TERMS
This section defines the terms used in assessing and prioritizing response actions to asbestos-containing materials (ACM) as presented in the spreadsheets. The assessment of an ACM’s potential to release asbestos fibers into air was based on a visual inspection of its physical condition. Pertinent physical characteristics include the ACM’s friability, degree of damage or deterioration, and potential for disturbance. Response actions were prioritized based on a ranking of the ACM’s physical characteristics in accordance with the U.S. Environmental Protection Agency’s Asbestos Hazard Emergency Response Act (AHERA) regulations.
The following sections describe the following:
* ACM Friability
* ACM Condition
* Potential for ACM Disturbance
* Priority Action Ranking
* Nonsuspect Materials
* Not Accessible
ACM Friability
Y: Material that crumbled when hand pressure was applied, ranging from high friability—very soft material that crumbled with light hand pressure—to low friability—material that crumbled after exerting substantial hand pressure
N: Nonfriable material that could not be crumbled, lightly abraded, or powdered by exertion of hand pressure
ACM Condition
Good: No apparent damage to the material
Fair: Material had less than 10 percent overall damage or less than 25 percent localized damage
Poor: Material had 10 percent or more overall damage or 25 percent or more localized damage
Potential for ACM Disturbance
High: 1. Friable ACM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
2. There is a reasonable likelihood that the ACM or its covering will become damaged, deteriorated, or delaminated due to factors such as recurrent damage or changes in the building’s use, operation and maintenance (O&M), or occupancy.
3. The ACM is subject to major or continuing disturbance due to factors such as accessibility, vibration, or air erosion.
Moderate: 1. Friable ACM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
2. There is a reasonable likelihood that the ACM or its covering will become damaged, deteriorated, or delaminated due to factors such as recurrent damage or changes in the building’s use, operation and maintenance (O&M), or occupancy.
Low: The potential for contact with the ACM, influence of vibration, and potential for air erosion are assessed to be low.
Priority Action Ranking
1: Isolate the area and restrict access to necessary personnel. Remove or repair the material as soon as possible.
2: Repair or remove the material, or reduce the potential for disturbance as soon as possible. Follow up with an O&M program.
3 or 4: Repair the material and follow up with an O&M program.
5: Follow up with an O&M program, and reduce the material’s potential for disturbance.
6: Follow up with an O&M program, and further reduce the potential for disturbance.
7: Follow up with an O&M program, and take precautions to prevent the material from becoming friable during maintenance activities.
Nonsuspect Material
Nonsuspect material is building material that should be asbestos-free, and is coded NSFM, NSWM, NSCM, and NSINS, as defined in the abbreviations section. Nonsuspect materials were not sampled.
Not Accessible
Not accessible material is building material that cannot be accessed without breaking the integrity of the containing structure, and is denoted as N-ACC in the spreadsheet.
MC Consulting Inc. Building 20
LOCATION ACM % TYPE QTY SAMPLE MATERIAL DESCRIPTION REEVALUATION 2010 COMMENTS
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
AREA 1ST FLOOR
ROOM 100
BSBRD 0 NA 23 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 280 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 280 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 23 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
ACT 0 NA 280 SF 97786- 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 680 SF 97785- WALL BRD Y GOOD MOD NO CHANGE
ROOM 100A
ACT 0 NA 288 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 720 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 24 SF 97783- 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 288 SF 97781- 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 288 SF 97782- MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 24 SF 97784- MSTC FOR 97783 N GOOD LOW NO CHANGE
ROOM 102
ACT 0 NA 108 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 480 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 16 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 16 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 104
ACT 0 NA 448 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 880 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 29 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 29 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
ROOM 106
ACT 0 NA
SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA
SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
ACT 0 NA 50 SF 97787- 2'X4' WRM W PNHL GOOD NO CHANGE
ROOM 108
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
ACT 0 NA 144 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 480 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 16 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 16 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
BSBRD 0 NA 16 SF 97788- 4" TAN BSBRD N POOR LOW NO CHANGE
MSTC NA NA 16 SF 97789- MSTC FOR 97788 N FAIR LOW NO CHANGE
ROOM 110
ACT 0 NA 60 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 320 SF 97785-X WALL BRD N GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 11 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 60 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 60 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 11 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings
ROOM 112 NO CHANGE
ACT 0 NA 60 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 60 SF 97785-X WALL BRD Y FAIR MOD NO CHANGE
BSBRD 0 NA 11 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 60 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 60 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 11 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
R00M 114
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
WALL-BRD 0 NA 400 SF 97785-X WALL BRD Y FAIR MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 30 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 30 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 116
ACT 0 NA 280 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 118
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
ACT 0 NA 280 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
7 VFT 10 CHR 280 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 280 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
ROOM 120
ACT 0 NA 800 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 140 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 140 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 122
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 30 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 NA 600 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 600 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 30 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
ROOM 124
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
ROOM 125
ACT 0 NA 920 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
7 VFT 10 CHR NA 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR NA 97782-X MSTC FOR 97881 N GOOD LOW NO CHANGE
ROOM 126
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
CON 50 CHR NA 1 EA 97205-X CMNT COND FTG Y GOOD LOW NO CHANGE
STM 50 CHR NA 1 EA 97205-X CMNT FTG STM Y GOOD LOW NO CHANGE
2 COND 65 CHR NA 84 LF 97207- AIRCELL COND Y GOOD LOW NO CHANGE
Y/N DIST
60 CHR NA 12 LF 97204- AIRCELL W/PAPER WRAP STM Y GOOD LOW NO CHANGE
65 CHR NA 72 LF 97206- AIRCELL Y GOOD LOW NO CHANGE
STM 50 CHR NA 1 EA 97205- CMNT STM Y GOOD LOW NO CHANGE
ROOM 128
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 130
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 140
PLAS-A 0 NA 48 SF 97201-X PLAS Y GOOD MOD NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings
PLAS-W 0 NA 300 SF 97201- PLAS Y GOOD MOD NO CHANGE
ROOM 142
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 150
ACT 0 NA 72 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 360 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 12 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
VFT <1 CHR 72 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE
MSTC 0 NA 12 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 MSTC 20 CHR 72 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE
ROOM 152
ACT 0 NA 168 SF 97790-X 2'X4' PAT FLKS Y GO0D LOW NO CHANGE
PLAS-W 0 NA 500 SF 97201-X PLAS Y GOOD MOD NO CHANGE
BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
VFT <1 CHR 168 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE
MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 MSTC 20 CHR 168 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE
ROOM 154
PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 MSTC 20 CHR 50 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings
ACT 0 NA 50 SF 97790- 2'X4' PAT FLKS Y GOOD LOW NO CHANGE
VFT <1 CHR 50 SF 97791- 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE
ROOM 156
ACT 0 NA 126 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE
PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE
WALL-BRD 0 NA 150 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0' NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
VFT <1 CHR 126 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 MSTC 20 CHR 126 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE
ROOM 158
ACT 0 NA 240 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE
PLAS-W 0 NA 300 SF 97201-X PLAS Y GOOD MOD NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
VFT <1 CHR 240 SF 97791-X 1'X1' CRM W/BRN & GRY STRKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 240 SF 97791-X MSTC FOR 97791 LAB RESULTS N GOOD LOW NO CHANGE
ROOM 160
ACT 0 NA 128 SF 97790-X 2'X4' PAT FLKS Y GOOD LOW NO CHANGE
PLAS-W 0 NA 450 SF 97201-X PLAS Y GOOD MOD NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 VFT 20 CHR 64 SF 97792- 9"X9" MAR W/CRM STRK N FAIR LOW NO CHANGE
7 VFT 10 CHR 64 SF 97793- 9"X9" CRM W/BLK STRK N FAIR LOW NO CHANGE
7 MSTC 20 CHR 128 SF 97794- MSTC FOR 97792 & 97793 N FAIR LOW NO CHANGE
ROOM 162
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 164
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
Y/N DIST
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
R00M 168
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 170
WALL-BRD 0 280 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NSFM NA NA NA NO CHANGE
7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y GOOD LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y GOOD LOW Presume behind walls & above ceilings
ROOM 172
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 174
WALL-BRD 0 NA 288 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
MSTC 0 NA 288 SF 97795-X MSTC FOR 97795 LAB RESULTS N FAIR LOW NO CHANGE
VFT 0 NA 288 SF 97795- 1'X1'BRN W/CRM & BLK STRK N FAIR MOD NO CHANGE
ROOM 176
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
* ROOM 178
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM HW1
ACT 0 NA 198 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 198 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
7 VFT 10 CHR 198 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 198 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
ROOM SW1
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
VFT 0 NA 56 SF 97203- CRM STAIR GUARD N GOOD LOW NO CHANGE
MSTC 0 NA 56 SF 97202- MSTC FOR 97203 N GOOD LOW NO CHANGE
ROOM SW2
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM SW3
PLAS-A 0 NA 60 SF 97201-X PLAS Y GOOD MOD NO CHANGE
PLAS-W 0 NA 120 SF 97201-X PLAS Y FAIR MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM SW4
ACT 0 NA 36 SF 97787-X 2'X4' WRM W/PNHL Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
VFT 0 NA 56 SF 97796- BLK STAIR GUARD N FAIR LOW NO CHANGE
AREA 2ND FLOOR
ROOM 200
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 202
ACT 0 NA 840 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 840 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
PLAS-W 0 NA 200 SF 97201-X PLAS Y GOOD MOD NO CHANGE
WALL-BRD 0 NA 200 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 40 SF 97788-X 4" TAN BSBRD N GOOD LOW NO CHANGE
7 MSTC 20 CHR 840 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE
MSTC 0 NA 40 SF 97789-X MSTC FOR 97788 N GOOD LOW NO CHANGE
7 VFT 10 CHR 840 SF 97401- 1'X1'CRM W/ GLD FLKS N GOOD MOD NO CHANGE
ROOM 204
ACT 0 NA 120 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 120 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
PLAS-W 0 NA 100 SF 97201-X PLAS Y GOOD MOD NO CHANGE
WALL-BRD 0 NA 100 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 15 SF 97788-X 4" TAN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 120 SF 97401-X 1'X1'CRM W/ GLD FLKS N GOOD LOW NO CHANGE
Y/N DIST
7 MSTC 20 CHR 120 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE
MSTC 0 NA 15 SF 97789-X MSTC FOR 97788 N GOOD LOW NO CHANGE
ROOM 206
ACT 0 NA 100 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 100 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
ROOM 208
ACT 0 NA 48 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 50 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
7 PIPE-DCW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings 7 PIPE-DHW >1 NA NA NA N-ACC ASSUME POSITIVE Y NA LOW Presume behind walls & above ceilings
ROOM 210
ACT 0 NA 270 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 350 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 30 SF 97406-X 4" GRY BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 30 SF 97406-X MSTC FOR 97406 LAB RESULTS N GOOD LOW NO CHANGE
VFT <1 CHR 270 SF 97404- 1'X1'GRY W/WHT STRK N GOOD MOD NO CHANGE
7 MSTC 20 CHR 270 SF 97405- MSTC FOR 97404 N GOOD LOW NO CHANGE
ROOM 212
ACT 0 NA 288 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 350 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
VFT <1 CHR 290 SF 97404-X 1'X1'GRY W/WHT STRK N GOOD MOD NO CHANGE
7 MSTC 20 CHR 290 SF 97405-X MSTC FOR 97404 N GOOD LOW NO CHANGE
MSTC 0 NA 30 SF 97406-X MSTC FOR 97406 LAB RESULTS N GOOD LOW NO CHANGE
BSBRD 0 NA 30 SF 97406- 4" GRY BSBRD N GOOD LOW NO CHANGE
ROOM 214
ACT 0 NA 384 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 190 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
RANK FUNCTION FRIABLE COND POT FOR
Y/N DIST
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
BSBRD 0 NA 25 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 200 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 200 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
MSTC 0 NA 25 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
ROOM 216
ACT 0 NA 400 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE
ACT 0 NA 400 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 600 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE
BSBRD 0 NA 40 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
7 VFT 10 CHR 800 SF 97401-X 1'X1'CRM W/ GLD FLKS N GOOD LOW NO CHANGE
7 MSTC 20 CHR 800 SF 97401-X MSTC FOR 97401 LAB RESULT N GOOD LOW NO CHANGE
MSTC 0 NA 40 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
ROOM 218
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 222
ACT 0 NA 288 SF 97402-X 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 226
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 230
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
ROOM 250
ACT 0 NA 400 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
PLAS-W 0 NA 800 SF 97201-X PLAS Y GOOD LOW NO CHANGE
WALL-BRD 0 NA 300 SF 97785-X WALL BRD Y GOOD LOW NO CHANGE
BSBRD 0 NA 60 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 60 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
Y/N DIST
ACT 0 NA 400 SF 97402- 2'X4' "Y" WRM W/ PNHL Y GOOD LOW NO CHANGE
F 0 NA 400 SF 97403- FIREPROOFING Y GOOD LOW NO CHANGE
ROOM 299
ACT 0 NA 648 SF 97787-X 2'X4' WRM W/PNHL Y LOW NO CHANGE
WALL-BRD 0 NA 500 SF 97785-X WALL BRD Y GOOD MOD NO CHANGE
BSBRD 0 NA 20 SF 97783-X 4" BRN BSBRD N GOOD LOW NO CHANGE
MSTC 0 NA 20 SF 97784-X MSTC FOR 97783 N GOOD LOW NO CHANGE
VFT <1 CHR 60 SF NA 'X CRM W/WHT STRK N GOOD MOD NO CHANGE
7 MSTC 20 CHR 600 SF 97408- MSTC FOR 97407 N GOOD LOW NO CHANGE
ROOM SW10
NSCM NA NA NA NA NSCM NA NA NA NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
7 VFT 10 CHR 25 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 25 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
ROOM SW20
ACT 0 NA 192 SF 97786-X 2'X4' POCK MARK Y GOOD LOW NO CHANGE
F 0 NA 84 SF 97403-X FIREPROOFING Y GOOD LOW NO CHANGE
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
7 VFT 10 CHR 100 SF 97781-X 1'X1' CRM W/TAN FLKS N GOOD MOD NO CHANGE
7 MSTC 20 CHR 100 SF 97782-X MSTC FOR 97781 N GOOD LOW NO CHANGE
AREA PENTHOUSE
ROOM PENT
NSWM NA NA NA NA NSWM NA NA NA NO CHANGE
NSFM NA NA NA NA NSFM NA NA NA NO CHANGE
NSINS NA NA NA NA NSINS NA NA NA NO CHANGE
AREA EXTERIOR
ROOM EXT