Fume hood cctf upgrade dugway proving ground
Award Notice Posted
- Solicitation number
- 17-233-SOL-00311
- Agency
-
Program Support Center
Department of Health and Human Services
- Awarded
- to Maden TECH Consulting, Inc.
- Set-aside
- Total Small Business
Opportunity facts
- Contract number
- HHSP233201750072A Federal contract award
- NAICS code
- 333413 Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing
- PSC
- Not on record
- Place of performance
- Dugway Proving Ground Combined Chemical Test Facility Dugway, Utah 84022, United States
Notice details come from SAM.gov. Updated .
Notice text
3 versions
Update #3 · Latest ·
17-233-SOL-00311
QUESTION: During review of the prototype; a question was asked about having bubble tight dampers on the supply side.
ANSWER:
The answer was that we don't need to isolate the supply side ducts.
The COR, double-checked the PWS; which has ...install new digital Variable Air Volume valves (VAVs), ductwork, and bubble tight dampers for selected supply/return lines, hoods, and snorkels (Appendix A1 - Layout).
Clarification:
The bubble tight dampers are only required on the exhaust side not the supply side with the purpose of being able to isolate each room.
Update #2 ·
The purpose of this effort is to layout and install an upgraded digital air supply/return, hood exhaust, and snorkel valve/damper systems for selected rooms within B4156 Combined Chemical Test Facility (CCTF) and connect the digital controls for these devices to an existing micro-processor plug-in unit to the Building Management System.
1.2 Scope
The Contractor for this contract is performing basic equipment layout, fabrication, and installation with minor construction/remodel services to the Building 4156 upgraded digital supply/return, hood exhaust, and snorkel for selected rooms within B4156 Combined Chemical Test Facility (CCTF) and connecting the digital controls for these devices to an existing micro-processor plug-in unit to the Building Management System.
• The use professional standards and practices to layout and install new digital Variable Air Volume valves (VAVs), ductwork, and bubble tight dampers for selected supply/return lines, hoods, and snorkels (Appendix A1 - Layout)
• Reconfigure existing circuits to supply electrical power to the new digital VAVs.
• Connecting digital controls signals to the BMS that allows controls and balancing operations of the valves and dampers for the new digital equipment and remaining old pneumatic equipment.
• Demonstrating control of the new equipment in concert with all existing equipment response time and functionality as defined
ANNOUCEMENT OF SITE VISIT
Solicitation is Forth Coming. This to annouce the site visit in advance.
Email: patricia.natividad@psc.hhs.gov
4. Site Visit. The Government will hold a site visit at Dugway Proving Ground on 23 May 2017 beginning at 1000 in building Chemical Test Facility at DITTO. All interested firms may attend with a limit of three (3) attendees per firm. Please submit, in writing, the names of attendees to the KO by Thursday May 18, 2017. There will be a Pre-Proposal Conference held at the conclusion of the site visit and will be held at 0900 in building CCTF at DITTO, Dugway Proving Grounds is remotely location roughly 100 miles from Salt Lake City, UT. Technical questions will be addressed during the course of the site visit. If the Government responses to technical questions affect the Performance Work Statement requirements or any other portion of the solicitation, then an Amendment of Solicitation will be issued.
The following websites are only for your familiarization.
http://www.dugway.army.mil/
http://www.dugway.army.mil/documents/DPG%20Visitor%20Guide.pdf?dt=1
If you require lodging the closest lodging is on post and fills up fast. No dining facilities are available after hours normally or extremely limited. The closest town to seek lodging and dining is 40 miles from Dugway called Tooele, UT or Lake Point, UT. Please allow time for traveling to Dugway for badging etc. The Salt Lake City airport is 2 hours from Dugway and has adequate lodging and food opportunities. There is a security requirement for accessing the post. Please see the Performance of Work for more details. For the following site visit, Please email the POC for this solicitation to find out more details on what is required.
Update #1 ·
ANNOUCEMENT OF SITE VISIT
Solicitation is Forth Coming. This to annouce the site visit in advance.
Email: patricia.natividad@psc.hhs.gov
4. Site Visit. The Government will hold a site visit at Dugway Proving Ground on 23 May 2017 beginning at 1000 in building Chemical Test Facility at DITTO. All interested firms may attend with a limit of three (3) attendees per firm. Please submit, in writing, the names of attendees to the KO by Thursday May 18, 2017. There will be a Pre-Proposal Conference held at the conclusion of the site visit and will be held at 0900 in building CCTF at DITTO, Dugway Proving Grounds is remotely location roughly 100 miles from Salt Lake City, UT. Technical questions will be addressed during the course of the site visit. If the Government responses to technical questions affect the Performance Work Statement requirements or any other portion of the solicitation, then an Amendment of Solicitation will be issued.
The following websites are only for your familiarization.
http://www.dugway.army.mil/
http://www.dugway.army.mil/documents/DPG%20Visitor%20Guide.pdf?dt=1
If you require lodging the closest lodging is on post and fills up fast. No dining facilities are available after hours normally or extremely limited. The closest town to seek lodging and dining is 40 miles from Dugway called Tooele, UT or Lake Point, UT. Please allow time for traveling to Dugway for badging etc. The Salt Lake City airport is 2 hours from Dugway and has adequate lodging and food opportunities. There is a security requirement for accessing the post. Please see the Performance of Work for more details. For the following site visit, Please email the POC for this solicitation to find out more details on what is required.
Files
Show all 29
Notice history
| Notice | Type | Posted |
|---|---|---|
| This notice | Award Notice | |
| Fume hood upgrade at combined chemical test facility (cctf) | Award Notice |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity