083323 overhead coiling doors.pdf

PDF 31 KB Posted

Attached to
CONSTRUCT CSMS PHASE II Federal contract opportunity
Solicitation number
W91364-09-B-0002
Issued by
Department of the Army Ohio Army National Guard

About this file

09B000283323 overhead coiling doors.pdf

View the file

Other files for this federal contract opportunity

Other files attached to CONSTRUCT CSMS PHASE II, newest first.
File Type Posted
e1w13300.PDF PDF
CSM-A705W .pdf PDF
L100.pdf PDF
CSM-A415W .pdf PDF
CSMM366W.pdf PDF
CSMM316aW.pdf PDF
CSMFA318W.pdf PDF
CSMM317bW.pdf PDF
CSMS203W Layout1 —
CSMFA501W.pdf PDF
CSM-G140W .pdf PDF
CSMM406W.pdf PDF
C000.pdf PDF
CSMS304W Layout1 —
E-103.pdf PDF
CSMM101W.pdf PDF
E-102.pdf PDF
CSM-A405W .pdf PDF
CSM-A218bW .pdf PDF
CSMM006W.pdf PDF
CSM-A324W .pdf PDF
ED-101.pdf PDF
CSMM410W.pdf PDF
CSM-A816W .pdf PDF
CSMM401W.pdf PDF
CSMS305W Layout1 —
CSMM319aW.pdf PDF
CSM-G129W .pdf PDF
CSM-A804W .pdf PDF
042000 unit masonry.pdf PDF
223300 electric domestic water heaters.pdf PDF
092216 non-structural metal framing.pdf PDF
230553 identification for hvac piping and equipment.pdf PDF
235100 breechings chimneys and stacks.pdf PDF
232100 glycol makeup system.pdf PDF
260923 lighting control devices.pdf PDF
238126 split-system air-conditioners.pdf PDF
079200 joint sealants.pdf PDF
233300 air duct accessories.pdf PDF
102800 toilet bath and laundry accessories.pdf PDF
323113 chain link fences and gates —
055300 metal gratings.pdf PDF
099113 exterior painting.pdf PDF
083113 access doors and frames.pdf PDF
018113 sustainable design requirements.pdf PDF
271500 communications horizontal cabling.pdf PDF
260533 raceway and boxes for electrical systems.pdf PDF
010001 affirmative procurement.pdf PDF
232113 hydronic piping.pdf PDF
260526 grounding and bonding for electrical systems.pdf PDF
Show all 50

CONSTRUCT CSMS PHASE II has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61607 Combined Support Maintenance Shop - Phase II Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 1

SECTION 083323 - OVERHEAD COILING DOORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplemen-tary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Service doors.

2. Insulated service doors.

B. Related Sections:

1. Division 05 Section "Metal Fabrications" for miscellaneous steel supports.

2. Division 09 Section "Interior Painting" for finish painting of factory-primed doors.

3. Division 26 Sections for electrical service and connections for powered opera-tors and accessories.

1.3 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design overhead coiling doors, including comprehensive engi-neering analysis by a qualified professional engineer, using performance require-ments and design criteria indicated.

B. Seismic Performance: Overhead coiling doors shall withstand the effects of earth-quake motions determined according to SEI/ASCE 7.

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified

2. Seismic Component Importance Factor: 1.5.

C. Operation Cycles: Provide overhead coiling door components and operators capa-ble of operating for not less than number of cycles indicated for each door. One op-eration cycle is complete when a door is opened from the closed position to the fully open position and returned to the closed position.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 2

1.4 SUBMITTALS

A. Product Data: For each type and size of overhead coiling door and accessory. In-clude the following:

1. Construction details, material descriptions, dimensions of individual compo-nents, profiles for slats, and finishes.

2. Rated capacities, operating characteristics, electrical characteristics, and fur-nished accessories.

B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data. Include plans, elevations, sections, de-tails, and attachments to other work.

1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

2. Show locations of replaceable fusible links.

3. Wiring Diagrams: For power, signal, and control wiring.

C. Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below.

1. Curtain Slats: 12 inches long.

2. Bottom Bar: 6 inches long with sensor edge.

3. Guides: 6 inches long.

4. Brackets: 6 inches square.

5. Hood: 6 inches square.

D. Delegated-Design Submittal: For overhead coiling doors indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

1. Detail fabrication and assembly of seismic restraints.

2. Summary of forces and loads on walls and jambs.

E. Qualification Data: For qualified Installer.

F. Seismic Qualification Certificates: For overhead coiling doors, accessories, and components, from manufacturer.

G. Oversize Construction Certification: For door assemblies required to be fire-rated and that exceed size limitations of labeled assemblies.

H. Maintenance Data: For overhead coiling doors to include in maintenance manuals.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 3

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for both installation and maintenance of units required for this Project.

B. Source Limitations: Obtain overhead coiling doors from single source from single manufacturer.

1. Obtain operators and controls from overhead coiling door manufacturer.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and appli-cation.

PART 2 - PRODUCTS

2.1 DOOR CURTAIN MATERIALS AND CONSTRUCTION

A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to withstand wind loading indicated, in a continuous length for width of door without splices. Unless otherwise indicated, provide slats of thickness and me-chanical properties recommended by door manufacturer for performance, size, and type of door indicated, and as follows:

1. Steel Door Curtain Slats: Zinc-coated (galvanized), cold-rolled structural steel sheet; complying with ASTM A 653/A 653M, with G90 (Z275) zinc coating;

nominal sheet thickness (coated) of 0.028 inch (0.71 mm) and as required to meet requirements.

2. Insulation: Fill slats for insulated doors with manufacturer's standard thermal insulation complying with maximum flame-spread and smoke-developed in-dexes of 75 and 450, respectively, according to ASTM E 84. Enclose insulation completely within slat faces.

3. Metal Interior Curtain-Slat Facing: Match metal of exterior curtain-slat face.

4. Gasket Seal: Provide insulated slats with manufacturer's standard interior-to-exterior thermal break or with continuous gaskets between slats.

B. Endlocks and Windlocks for Service Doors: Malleable-iron casings galvanized after fabrication, secured to curtain slats with galvanized rivets or high-strength nylon.

Provide locks on not less than alternate curtain slats for curtain alignment and resis-tance against lateral movement.

C. Bottom Bar for Service Doors: Consisting of two angles, each not less than 1-1/2 by 1-1/2 by 1/8 inch thick; fabricated from manufacturer's standard hot-dip galvanized steel, stainless steel, or aluminum extrusions to match curtain slats and finish.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 4

D. Astragal for Interior Doors: Equip each door bottom bar with a replaceable, adjust-able, continuous, compressible gasket of flexible vinyl, rubber, or neoprene as a cushion bumper.

E. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes for guide adjustment. Provide removable stops on guides to prevent over travel of curtain, and a continuous bar for holding windlocks.

2.2 HOOD

A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached.

Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to pre-vent sagging.

1. Galvanized Steel: Nominal 0.028-inch- thick, hot-dip galvanized steel sheet with G90 (Z275) zinc coating, complying with ASTM A 653/A 653M.

2. Include automatic drop baffle on fire-rated doors to guard against passage of smoke or flame.

2.3 LOCKING DEVICES

A. Slide Bolt: Fabricate with side-locking bolts to engage through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.

B. Safety Interlock Switch: Equip power-operated doors with safety interlock switch to disengage power supply when door is locked.

2.4 CURTAIN ACCESSORIES

A. Smoke Seals: Equip each fire-rated door with smoke-seal perimeter gaskets for smoke and draft control as required for door listing and labeling by a qualified testing agency.

2.5 COUNTERBALANCING MECHANISM

A. General: Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted around a steel shaft

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 5

and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed bearings or self-lubricating graphite bearings for rotating members.

B. Counterbalance Barrel: Fabricate spring barrel of manufacturer's standard hot-formed, structural-quality, welded or seamless carbon-steel pipe, of sufficient diame-ter and wall thickness to support rolled-up curtain without distortion of slats and to limit barrel deflection to not more than 0.03 in./ft. of span under full load.

C. Spring Balance: One or more oil-tempered, heat-treated steel helical torsion springs. Size springs to counterbalance weight of curtain, with uniform adjustment accessible from outside barrel. Secure ends of springs to barrel and shaft with cast-steel barrel plugs.

D. Torsion Rod for Counterbalance Shaft: Fabricate of manufacturer's standard cold-rolled steel, sized to hold fixed spring ends and carry torsional load.

E. Brackets: Manufacturer's standard mounting brackets of either cast iron or cold-rolled steel plate.

2.6 ELECTRIC DOOR OPERATORS

A. General: Electric door operator assembly of size and capacity recommended and provided by door manufacturer for door and operation-cycles requirement specified, with electric motor and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake, clutch, remote-control stations, control devices, integral gearing for locking door, and accessories required for proper operation.

1. Comply with NFPA 70.

2. Provide control equipment complying with NEMA ICS 1, NEMA ICS 2, and

NEMA ICS 6, with NFPA 70 Class 2 control circuit, maximum 24 V, ac or dc.

B. Usage Classification: Electric operator and components capable of operating for not less than number of cycles per hour indicated for each door.

C. Door Operator Location(s): Operator location indicated for each door.

1. Wall Mounted: Operator is mounted to the inside front wall on the left or right side of door and connected to door drive shaft with drive chain and sprockets.

Side room is required for this type of mounting. Wall mounted operator can also be mounted above or below shaft; if above shaft, headroom is required.

D. Electric Motors: Comply with NEMA designation, temperature rating, service factor, enclosure type, and efficiency requirements specified in Division 11 Section "Com-mon Motor Requirements for Equipment" unless otherwise indicated.

1. Electrical Characteristics:

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 6

a. Phase: Polyphase.

b. Volts: 460 V./3 Phase

c. Hertz: 60.

2. Motor Type and Controller: Reversible motor and controller (disconnect switch) for motor exposure indicated.

3. Motor Size: Minimum size as indicated. If not indicated, large enough to start, accelerate, and operate door in either direction from any position, at a speed not less than 8 in./sec. (203 mm/s) and not more than 12 in./sec. (305 mm/s), without exceeding nameplate ratings or service factor.

4. Operating Controls, Controllers (Disconnect Switches), Wiring Devices, and Wiring: Manufacturer's standard unless otherwise indicated.

5. Coordinate wiring requirements and electrical characteristics of motors and other electrical devices with building electrical system and each location where installed.

E. Limit Switches: Equip each motorized door with adjustable switches interlocked with motor controls and set to automatically stop door at fully opened and fully closed po-sitions.

F. Obstruction Detection Device: Equip motorized door with indicated external auto-matic safety sensor capable of protecting full width of door opening. For non-fire-rated doors, activation of device immediately stops and reverses downward door travel. For fire-rated doors, activation delays closing.

1. Sensor Edge: Automatic safety sensor edge, located within astragal or weather stripping mounted to bottom bar. Contact with sensor activates device. Con-nect to control circuit using manufacturer's standard take-up reel or self-coiling cable.

a. Self-Monitoring Type: Four-wire configured device designed to interface with door operator control circuit to detect damage to or disconnection of sensor edge.

G. Remote-Control Station: Momentary-contact, three-button control station with push-button controls labeled "Open," "Close," and "Stop."

1. Interior units, full-guarded, surface-mounted, heavy-duty type, with general-purpose NEMA ICS 6, Type 1 enclosure.

H. Emergency Manual Operation: Equip each electrically powered door with capability for emergency manual operation. Design manual mechanism so required force for door operation does not exceed 25 lbf (111 N).

I. Emergency Operation Disconnect Device: Equip operator with hand-operated dis-connect mechanism for automatically engaging manual operator and releasing brake for emergency manual operation while disconnecting motor without affecting timing of limit switch. Mount mechanism so it is accessible from floor level. Include inter-

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 7

lock device to automatically prevent motor from operating when emergency operator is engaged.

J. Motor Removal: Design operator so motor may be removed without disturbing limit-switch adjustment and without affecting emergency manual operation.

K. Audible and Visual Signals: Audible alarm and visual indicator lights in compliance with regulatory requirements for accessibility.

L. Radio-Control System: Consisting of the following:

1. Three-channel universal coaxial receiver to open, close, and stop door; one per operator.

2. Multifunction remote control.

3. Remote-antenna mounting kit.

2.7 DOOR ASSEMBLY

A. Service Door: Overhead coiling door formed with curtain of interlocking metal slats.

1. Basis-of-Design Product: Subject to compliance with requirements, provide product by one of the following:

a. ACME Rolling Doors.

b. Alpine Overhead Doors, Inc.

c. AlumaTek, Inc.

d. C.H.I. Overhead Doors.

e. City-Gates.

f. Cookson Company.

g. Cornell Iron Works, Inc.

h. Dynamic Closures Corp.

i. Lawrence Roll-Up Doors, Inc.

j. Mahon Door Corporation.

k. McKeon Rolling Steel Door Company, Inc.

l. Metro Door.

m. Overhead Door Corporation.

n. QMI Security Solutions.

o. Raynor.

p. Southwestern Steel Rolling Door Co.

q. Wayne-Dalton Corp.

r. Windsor Door.

B. Operation Cycles: Not less than 10,000.

1. Include tamperproof cycle counter.

C. Curtain R-Value: 7

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 8

D. Door Curtain Material: Galvanized steel.

E. Door Curtain Slats: Flat profile slats of 2-5/8-inch center-to-center height.

1. Insulated-Slat Interior Facing: Metal.

F. Curtain Jamb Guides: Galvanized steel with exposed finish matching curtain slats. Provide continuous integral wear strips to prevent metal-to-metal contact and to minimize operational noise.

G. Hood: Galvanized steel.

1. Shape: Round.

2. Mounting: Face of wall.

H. Integral Frame, Hood, and Fascia for Counter Door: Galvanized steel

1. Mounting: Face of wall.

I. Sill Configuration for Counter Door: No sill

J. Locking Devices: Equip door with locking device assembly.

K. Electric Door Operator:

1. Usage Classification: Standard duty, up to 60 cycles per hour

2. Operator Location: Wall.

3. Motor Exposure: Interior.

4. Emergency Manual Operation: Chain type.

5. Obstruction-Detection Device: Automatic pneumatic sensor edge on bottom bar; self-monitoring type.

a. Sensor Edge Bulb Color: As selected by Architect from manufacturer's full range.

6. Other Equipment: Radio-control system.

L. Door Finish:

1. Factory Prime Finish: Manufacturer's standard color.

2.8 GENERAL FINISH REQUIREMENTS

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 9

B. Appearance of Finished Work: Noticeable variations in same piece are not accept-able. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

2.9 STEEL AND GALVANIZED-STEEL FINISHES

A. Factory Prime Finish: Manufacturer's standard primer, compatible with field-applied finish. Comply with coating manufacturer's written instructions for cleaning, pre-treatment, application, and minimum dry film thickness.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates areas and conditions, with Installer present, for compliance with requirements for substrate construction and other conditions affecting performance of the Work.

B. Examine locations of electrical connections.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install overhead coiling doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manu-facturer's written instructions and as specified.

B. Install overhead coiling doors, hoods, and operators at the mounting locations indi-cated for each door.

C. Accessibility: Install overhead coiling doors, switches, and controls along accessible routes in compliance with regulatory requirements for accessibility.

D. Smoke-Control Doors: Install according to NFPA 80 and NFPA 105.

3.3 STARTUP SERVICE

A. Engage a factory-authorized service representative to perform startup service.

1. Perform installation and startup checks according to manufacturer's written in-structions.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

OVERHEAD COILING DOORS 083323 - 10

2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3. Test door closing when activated by detector or alarm-connected fire-release system. Reset door-closing mechanism after successful test.

4. Send report of startup to Contracting Officer.

3.4 ADJUSTING

A. Adjust hardware and moving parts to function smoothly so that doors operate easily, free of warp, twist, or distortion.

B. Lubricate bearings and sliding parts as recommended by manufacturer.

C. Adjust seals to provide weathertight fit around entire perimeter.

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain overhead coiling doors.

END OF SECTION 083323