TE_5.5-002-_Chlorofluorocarbon_(CFC)_Control.pdf
PDF 9 KB Posted
- Attached to
- Sources Sought - Fort Benning, GA Base Operations Federal contract opportunity
- Solicitation number
- W911SF-16-R-0012
View the file
Other files for this federal contract opportunity
Show all 50
Sources Sought - Fort Benning, GA Base Operations has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Exhibit C-7.5.5-002-1 Fort Benning
TECHNICAL EXHIBIT 5.5-002
CHLOROFLUOROCARBON (CFC) CONTROL
1. In accordance with EPA regulations, the Contractor shall fill out and maintain a Refrigerant Recovery and Refrigerant Usage Log for all uses and recovery of all refrigerants.
2. The Contractor shall complete and maintain an Accidental, Unintentional Venting log sheet any time a leak is discovered and when a system looses any refrigerant during repairs. The immediate notification to the KO is required upon a leak or accidental, unintentional venting.
All leaks must be repaired within 30 calendar days in accordance with 40 CFR Part 82. The Contractor shall review all recorded leaks and leak repairs on an annual basis to highlight equipment and areas requiring corrective action.
File details come from the government source that posted it. Updated .