08 14 00.pdf
PDF 21 KB Posted
- Attached to
- Renovate Operations Building 2A - Scotia, NY
- Solicitation number
- W50S8J-21-R-0004
About this file
This document contains a solicitation for the renovation of Operations Building 2A located in Scotia, New York along with an amendment providing specifications for wood doors to be installed as part of the renovation. Key details include:
-
The solicitation is for the renovation of Operations Building 2A at Stratton Air National Guard Base in Scotia, New York. Interested parties should attend a combined pre-proposal conference and site visit on April 28, 2021 at 10:00 AM to view the building and limits will be placed on attendance due to COVID-19. Proposers must register by April 26, 2021.
-
The amendment provides specifications for wood doors to be installed as part of the renovation. Requirements include sound transmission class ratings, certified sustainably harvested wood, indoor air quality certification, and factory finishing. Cycle-slam and hinge loading resistance testing results must be submitted.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VBDZ192001 Renovate Operations Building 2A 101418 STRATTON ANGB, SCOTIA, NY Amendment #1 5/12/2021
SECTION 08 14 00
WOOD DOORS
08/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN FOREST FOUNDATION (AFF)
ATFS STANDARDS (2015) American Tree Farm System Standards of Sustainability 2015-2020
ASTM INTERNATIONAL (ASTM)
ASTM E90 (2009; R2016) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
CALIFORNIA AIR RESOURCES BOARD (CARB)
CARB 93120 (2007) Airborne Toxic Control Measure (ATCM) to Reduce Formaldehyde Emissions from Composite Wood Products
CSA GROUP (CSA)
CSA Z809-08 (R2013) Sustainable Forest Management
FOREST STEWARDSHIP COUNCIL (FSC)
FSC STD 01 001 (2015) Principles and Criteria for Forest Stewardship
PROGRAMME FOR ENDORSEMENT OF FOREST CERTIFICATION (PEFC)
PEFC ST 2002:2013 (2015) PEFC International Standard Chain of Custody of Forest Based Products Requirements
SUSTAINABLE FOREST INITIATIVE (SFI)
SFI 2015-2019 (2015) Standards, Rules for Label Use, Procedures and Guidance
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 770 Formaldehyde Standards for Composite Wood Products
SECTION 08 14 00 Page 1
WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)
ANSI/WDMA I.S.1A (2013) Interior Architectural Wood Flush Doors
ANSI/WDMA I.S.6A (2013) Interior Architectural Stile and Rail Doors
WOODWORK INSTITUTE (WI)
NAAWS 3.1 (2017; 2018 Errata Edition) North American Architectural Woodwork Standards
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Doors; G
Submit drawings or catalog data showing each type of door unit.
Indicate within drawings and data the door types and construction, sizes, thickness, methods of assembly and glazing.
SD-03 Product Data
Doors; G
Accessories
Water-resistant Sealer
Sample Warranty
Sound Transmission Class Rating; G
SD-04 Samples
Doors
Prior to the delivery of wood doors, submit a sample section of each type of door which shows the stile, rail, veneer, finish, and core construction.
Door Finish Colors; G
Submit a minimum of three color selection samples, minimum 3 by 5 inches in size representing wood stain for selection by the Contracting Officer.
SD-06 Test Reports
Cycle-Slam
SECTION 08 14 00 Page 2
Hinge Loading Resistance
Submit cycle-slam test report for doors tested in accordance with ANSI/WDMA I.S.1A , and hinge loading resistance test report for doors tested in accordance with ANSI/WDMA I.S.6A .
SD-07 Certificates
Certificates of Grade
Certified Sustainably Harvested Stile and Rail Wood Doors; S
Certified Sustainably Harvested Flush Wood Doors; S
SD-11 Closeout Submittals
Warranty
1.3 CERTIFICATIONS
1.3.1 Certified Wood Grades
Provide certificates of grade from the grading agency on acoustical doors.
1.3.2 Certified Sustainably Harvested Wood
Provide wood certified as sustainably harvested by FSC STD 01 001 , ATFS STANDARDS, CSA Z809-08 , SFI 2015-2019 , or other third party program certified by PEFC ST 2002:2013 . Provide a letter of Certification of Sustainably Harvested Wood signed by the wood supplier. Identify certifying organization and their third party program name and indicate compliance with chain-of-custody program requirements. Submit sustainable wood certification data; identify each certified product on a line item basis. Submit copies of invoices bearing certification numbers.
1.3.3 Indoor Air Quality Certification
1.3.3.1 Composite Wood, Wood Structural Panel and Agrifiber Products
For purposes of this specification, composite wood and agrifiber products include particleboard, medium density fiberboard (MDF), wheatboard, strawboard, panel substrates, and door cores. Provide products certified to meet requirements of both 40 CFR 770 and CARB 93120 . Provide current product certification documentation from certification body.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the site in an undamaged condition and protect against damage and dampness. Stack doors flat under cover. Support on blocking, a minimum of 4 inch thick, located at each end and at the midpoint of the door. Store doors in a well-ventilated building so that they will not be exposed to excessive moisture, heat, dryness, direct sunlight, or extreme changes of temperature and humidity. Replace defective or damaged doors with new ones.
1.5 WARRANTY
Warrant doors free of defects as set forth in the door manufacturer's
SECTION 08 14 00 Page 3 standard door warranty.
PART 2 PRODUCTS
2.1 DOORS
Provide doors of the types, sizes, and designs indicated free of urea-formaldehyde resins.
2.1.1 Flush Doors
Conform to ANSI/WDMA I.S.1A for flush doors. Provide hollow core doors with lock blocks and 1 inch minimum thickness hinge stile. Hardwood stile edge bands of doors receives a natural finish, compatible with face veneer. Provide mill option for stile edge of doors scheduled to be painted. No visible finger joints will be accepted in stile edge bands.
When used, locate finger-joints under hardware. Provide certified sustainably harvested flush wood doors.
2.1.1.1 Interior Flush Doors
Provide particleboard core, Type II flush doors conforming to ANSI/WDMA I.S.1A with faces of sound grade hardwood or hardboard for painted finish premium grade red oak. Hardwood veneers must be rotary cut book matched. Products must contain no added urea-formaldehyde resins.
Provide certification of indoor air quality for particleboard and agrifiber door cores.
2.1.2 Acoustical Doors
ANSI/WDMA I.S.1A , solid core, constructed to provide Sound Transmission Class rating of 45 when tested in accordance with ASTM E90.
2.2 ACCESSORIES
2.2.1 Door Light Openings
Provide glazed openings with the manufacturer's standard wood moldings.
Provide moldings for doors to receive natural finish of the same wood species and color as the wood face veneers. Lip type moldings for flush doors.
2.2.2 Additional Hardware Reinforcement
Provide the minimum lock blocks to secure the specified hardware. The measurement of top, bottom, and intermediate rail blocks are a minimum 125 mm 5 inch by full core width. Comply with the manufacturer's labeling requirements for reinforcement blocking, but not mineral material similar to the core.
2.3 FABRICATION
2.3.1 Marking
Stamp each door with a brand, stamp, or other identifying mark indicating quality and construction of the door.
SECTION 08 14 00 Page 4
2.3.2 Quality and Construction
Identify the standard on which the construction of the door was based and identify doors having a Type I glue bond.
2.3.3 Preservative Treatment
Treat doors scheduled for restrooms, janitor closets and other possible wet locations including exterior doors with a water-repellent preservative treatment and so marketed at the manufacturer's plant.
2.3.4 Adhesives and Bonds
ANSI/WDMA I.S.1A . Use Type I bond for exterior doors and Type II bond for interior doors. Provide a nonstaining adhesive on doors with a natural finish.
2.3.5 Prefitting
Provide factory finished and factory prefitted doors for the specified hardware, door frame and door-swing indicated. Machine and size doors at the factory by the door manufacturer in accordance with the standards under which the doors are produced and manufactured. The work includes sizing, beveling edges, mortising, and drilling for hardware and providing necessary beaded openings for glass and louvers. Provide the door manufacturer with the necessary hardware samples, and frame and hardware schedules to coordinate the work.
2.3.6 Finishes
2.3.6.1 Factory Finish
Provide doors finished at the factory by the door manufacturer as follows: NAAWS 3.1 Section 1500, specification for System No. 4 Conversion varnish alkyd urea or System No. 5 Vinyl catalyzed. The coating is NAAWS 3.1 premium, medium rubbed sheen, closed grain effect.
Use stain when required to produce the finish specified for color. Seal edges, cutouts, trim, and wood accessories, and apply two coats of finish compatible with the door face finish. Touch-up finishes that are scratched or marred, or where exposed fastener holes are filled, in accordance with the door manufacturer's instructions. Match color and sheen of factory finish using materials compatible for field application.
2.3.6.2 Color
To match existing wood doors.
2.3.7 Water-Resistant Sealer
Provide manufacturer's standard water-resistant sealer compatible with the specified finish.
2.4 SOURCE QUALITY CONTROL
Meet or exceed the following minimum performance criteria of stiles of "B" and "C" label fire doors utilizing standard mortise leaf hinges:
a. Cycle-slam: Heavy Duty Doors: 500,000 cycles with no loose hinge screws or other visible signs of failure when tested in accordance
SECTION 08 14 00 Page 5 with the requirements of ANSI/WDMA I.S.1A .
b. Hinge loading resistance: Averages of ten test samples not less than Heavy Duty doors: 475 pounds force when tested for direct screw withdrawal in accordance with ANSI/WDMA I.S.6A using a No. 12, 1-1/4 inch long, steel, fully threaded wood screw. Drill 5/32-inch pilot hole, use 1-1/2 inch opening around screw for bearing surface, and engage screw full, except for last 1/8-inch. Do not use a steel plate to reinforce screw area.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Before installation, seal top and bottom edges of doors with the approved water-resistant sealer. Seal cuts made on the job immediately after cutting using approved water-resistant sealer. Fit, trim, and hang doors with a 1/16-inch minimum, 1/8-inch maximum clearance at sides and top, and a 3/16-inch minimum, 1/4-inch maximum clearance over thresholds. Provide 3/8-inch minimum, 7/16-inch maximum clearance at bottom where no threshold occurs. Bevel edges of doors at the rate of 1/8-inch in 2 inch. Door warp must not exceed 1/4-inch when measured in accordance with
ANSI/WDMA I.S.1A .
-- End of Section --