Section 16404 - Cerro Pelado Battery System.pdf
PDF 29 KB Posted
- Solicitation number
- 127EAX22Q0058
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C&D TECHNOLOGIES, INC.
1400 UNION MEETING ROAD
BLUE BELL, PA 19422
(215) 619-2700
FAX: (215) 619-7840
Project Information
Title: Cerro Pelado
Company: NGH Power
Sized By: Tom Cleveland
Date: Friday 29th May 2020
Reference No.:
Key Parameters
Number of Cells: 24 Minimum Temperature: 77 °F
Number of Jars: 24 Design Margin: 1.00
Final volts per cell: 1.75 vpc (average) Aging Factor: 1.00
Parallel Strings: 1
Load Information
Profile: Constant Current
Amps: 25.90
Duration: 1440 Minutes
AH Removed: 621.60
Battery
Model: AT-23P
Specific Gravity: 1.300
Type: VRLA 20 year
Product Line: msEndur II AT-P
Selection Criteria: By Product Line - msEndur II AT-P
% of Requirement: 239.73%
Runtime: > 24 hr Runtime is based on 100% battery capacity adjusted to user-selected minimum design temperature.
Number of Jars: 24
Jar Length: 23.19 in.
Jar Width: 8.80 in.
Jar Height: 9.04 in.
No. Plates: 23
*Float vpc: 2.26 volts per cell
*Max vpc: 2.33 volts per cell
Jar Weight: 184.0 lbs
Battery Weight: 4,416.00 lbs
Accessory Kits
Std. Accessory Kit: Please call C&D Applications Dept for accessory kit information
* Nominal values only, see Installation and Operations Manual for details.
The C&D Sizing Program adheres to the battery sizing methodologies found in the current versions of IEEE-485, Recommended Practice for Sizing Lead-Acid Batteries for Stationery Applications and IEEE-1184, Guides for Batteries for Uninterruptible Power Supply Systems
Monday 8th June 2020 ©2020 C&D Technologies, Inc. www.cdtechno.com
All critical calculations must be verified with C&D Applications Specifications are subject to change without notice
File details come from the government source that posted it. Updated .