power.cummins.com ©2019 Cummins Inc. | S-6344-EN | PDA060J523 (09/19)
Specification Sheet
POWERCOMMAND CLOUD™
REMOTE MONITORING SYSTEM
“Cummins Digital Solutions will provide customers with the ability to manage their power system assets, globally”
Description
The PowerCommand Cloud™ is a robust and reliable remote monitoring system that provides information and send notifications to ensure your equipment is available when you need it.
With easy-to-use mobile and web application giving you instant access to your equipment enabling real-time monitoring and control so you can make the right decisions, right away
— thus minimizing downtime and maximizing power system performance along with asset availability.
Highlights
• Site and asset status at a glance
• Notifications
• Real-time Remote Monitoring through PowerCommand Cloud™
• Asset Control
• Convenient access through Web UI and Mobile app with multi-language support
• Multiple site and fleet management
• Secure data transmission and storage
• Data Trending with export capability
• Maintenance Alert based on recommended service interval
• PowerCommand Controls are supported by a worldwide network of independent distributors who provide parts, service and warranty support
Features
◼ Connectivity: PowerCommand 500/550 Cloud Link N
(CLN) supports Ethernet or Cellular.
◼ Communication: The PowerCommand 500/550 CL
N communicates directly with the Power Generation
Asset by communicating telemetry data and remote-control capability to the PowerCommand Cloud™.
◼ Monitoring: The PowerCommand Web and Mobile app monitors customer account and site information along with monitoring asset data (generator, transfer switch, DMC products and sensors).
◼ Integration with the QuietConnect™ Home
Standby Generator: PowerCommand Cloud solution is integrated within the Cummins Connect Cloud™
Web and Mobile App.
◼ Asset Control: The PowerCommand Web and
Mobile app can control the Power Generation Asset via start, stop, exercise scheduler and fault reset commands.
◼ Notification: The PowerCommand Cloud has the capability to notify users of Warnings and Faults via email, push notification and indirect SMS (if supported by wireless carrier).
◼ Account & Fleet Management: The
PowerCommand Web and Mobile app offers fleet management capability by giving visibility and remote control of Customer’s assets.
◼ Event Storage and Export: The PowerCommand
Cloud stores the event log while the web and mobile app enables the user to monitor the event logs.
◼ Data Trending (Storage and Export): The
PowerCommand Cloud stores the data and the web app enables data export and graphing of data trends.
◼ On Device Diagnostics: The PowerCommand
500/550 Cloud Link N offers on-device diagnostics.
◼ Software Update: The PowerCommand 500/550
Cloud Link N enable gateway software update capability.
◼ PC500/550 Remote Software Update:
PowerCommand Cloud Web app enables execution of remote software updates on the asset.
◼ Supported Language: The PowerCommand Cloud supports English, French, Spanish, Chinese
(Simplified) and Brazilian-Portuguese.
◼ Mobile App Support: PowerCommand Cloud supports the following Mobile Apps for both iOS and Android:
Connect Cloud and PowerCommand Cloud.
◼ Third-Party Genset Support: Integrate third-party power system equipment (Generator, Auto Transfer
Switch) using CCM-G, CCM-T or Wired Genset solution to accomplish remote monitoring/controlling capabilities.
◼ Maintenance Warning: The PowerCommand Cloud supports user-configurable maintenance alerts with notification capability for all assets. The reminder interval can be based on Engine Hours or time.
PowerCommand CloudTM User Interface Users can remotely access real-time information using mobile and web app.
The web Dashboard allows users to view the status of all configured devices in one glance.
The Dashboard provides an overall system status at a glance that may include multiple sites and devices connected to the cloud. Users have the flexibility to filter assets by status and location and then access information about specific sites and equipment.
Genset Information
• Asset Details: Easy access to Generator’s details such as model, serial number, and control model.
• Annunciator Data: This section displays the key status, warning and fault events where color coding is used (green, amber, red) depending on the event severity according to NFPA110.
• Alternator Data: User can access vital electrical genset information.
• Engine Data: Engine information is available in this section.
• Exercise Scheduler: User can set the Exercise Schedule for each asset.
• Maintenance Alert: PowerCommand Cloud will alert the user when Maintenance is required based on Engine Hours.
The genset status and telemetry information is available via both the mobile app and web app.
• Data Trending: The user can create graphs for a device by selecting a parameter and duration. In addition, asset data can be exported to .csv files.
Automatic Transfer Switch (ATS) Information
ATS status and telemetry information is available on the ATS page. The user can also to create data trend graphs for a particular device by selecting a parameter and duration.
• Asset Details: Easy access to ATS’s details such as model, serial number, and control model.
• Annunciator Data: This section displays the key status, warning and fault events where color coding is used (green, amber, red) depending on the event severity according to NFPA110.
• Sources Data: User can access vital electrical source information including status.
• Load Data: Load information is available in this section.
• Data Trending: The user can create graphs for a particular device by selecting a parameter and duration. In addition, asset data can be exported to .csv files.
• Maintenance Alert: PowerCommand Cloud will alert the user when Maintenance is required based on the recommended service intervals.
Digital Master Control (DMC) Information
DMC status and telemetry information is available on the DMC page. The user can also to create data trend graphs for a particular device by selecting a parameter and duration.
• Asset Details: Easy access to DMC details such as model, serial number, control model along with system information.
• Events: View operational events including Warning & Shutdowns along with the associated timestamps.
• Data Trending: The user can create graphs for a particular device by selecting a parameter and duration. In addition, asset data can be exported to .csv files.
• Maintenance Alert: PowerCommand Cloud will alert the user when Maintenance is required based on the recommended service intervals.
Sensors By selecting the Sensors tab the user can view all configured sensors in the inputs. In addition to device specific Inputs, the user can add an AUX 101 (8-configurable inputs) and an AUX 102 (4-non configurable discrete inputs) for additional remote monitoring capability. The Sensors Page displays configured sensors (states/values, low warnings and high warnings). Similar to the generator set and transfer switch data, the user can access specific event logs associated with all configured sensors.
Notifications Get notified when your equipment needs attention. PowerCommand CloudTM sends notifications and gives you instant access to your equipment enabling real-time monitoring and control so you can make the right decisions, right away
— thus minimizing downtime and maximizing power system performance.
Certifications
ICES-003B
Dimensions of the PC 500/550 Cloud Link N
Dimensions are millimeters (inches)
System Requirements Web App
PC or Macintosh computer, tablet, smart phone
Browser: Internet Explorer, version 9.0 or later, Google Chrome, Firefox, Safari.
Minimum screen resolution, 1024 x 768
Gateway
Browser: Internet Explorer, version 9.0 or later.
Operating System: Microsoft Windows, Mac OS X or Linux
HTML5 Support
Windows Mobile Device Center
Minimum screen resolution, 1024 x 768
Network: 10/100-megabit Ethernet for the primary physical connection
Port Specification:
o MQTTS outgoing 168.61.54.255 uses port 8883 TCP o HTTPS outgoing 40.114.00.153 uses port 443 TCP
The cellular service provider must have a network to support 3G service.
o Frequency Band: 850/900/1700
(AWS)/1900/2100
Language The user interface and manuals are available in English, French, Spanish, Brazilian-Portuguese, and Chinese (Simplified).
Hardware Requirements For installation and communication, the following additional hardware may be required:
SIM card (GSM)
Modbus cable
Antenna extension cable
PowerCommand Input/Output AUX 101 Module
PowerCommand Input/Output AUX 102 Expansion
Module
Modbus Controls
There is no additional hardware required for Modbus controls: PS0500, PS0600, DMC1000, PCC1301, 1302, 2300 and 3300.
LonWorks Controls
Required hardware for LonWorks-based controls:
PCC2100, 3100, 3200 and 3201 generator set controls and OTPC, BTPC, OHPC and CHPC transfer switch controls:
PowerCommand Lon Gateway S-6191
PowerCommand Network Communications Module
(NCM)
ModLon Connection Cable
Additional hardware required for non-communicating
OTEC, GTEC or third-party transfer switch controls and third-party generator set controls:
PowerCommand Lon Gateway LonWorks to
Modbus Converter
PowerCommand Network Communication Module
(CCM-G)
PowerCommand Control Communication Module
(CCM-T)
PowerCommand Input/Output AUX 101 Module
PowerCommand Input/Output AUX 102 Expansion
Module
Modbus Communications
A shielded twisted pair cable, Belden 9729 cable or equivalent, is recommended for Modbus communication between the PowerCommand 500/550
Cloud Link N and any configured devices.
Power Supply Requirements
The use of a power supply, with the following specification, is recommended. It is also recommended to connect the power supply and PowerCommand
500/550 Cloud Link N to an uninterruptible power supply (UPS).
Voltage range 12 to 24VDC
Current (12V typical) 250mA
Current (24V typical) 125mA
Power (typical) 3.0W
Power (maximum) 5.0W
Environment
Operating temperature -20°C to 70°C
(-4°F to 158°F)
Storage temperature -40°C to 85°C
(-40°F to 185°F)
Humidity 85% RH, non-condensing
Mounting and Installation
PowerCommand 550/500 is DIN rail mountable and should be installed in a location suitable for telecommunications, information technology or networking equipment.
For more information contact your local Cummins distributor or visit power.cummins.com
©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-6344-EN | A060J523 (09/19)
Standard Product Contents PowerCommand 500 or 550 Cloud Link N
Antenna (GSM)
USB On-The-Go (OTG) cable
Ethernet cable
Quick Start Guide
Quick Troubleshooting Guide
Warranty Statement
CD containing Owner’s Manual, Quick Start Guide, Quick Troubleshooting Guide and Warranty
Statement in English
Accessories
A035C381 Antenna Extension (12ft)
0541-1291 PowerCommand Input/Output AUX 101
Module
0541-0772 PowerCommand Input/Output AUX 102
Expansion Module
A054V134 Lon Gateway - LonWorks to Modbus
Converter
0541-0770 Network Genset Communications
Module (NCM) for PCC 2100
0541-0813 Network Genset Communications
Module (GCM) for PCC 3100
0541-0809 Network Genset Communications
Module (NCM) for PCC 3200/3201
0541-0810 Controls Communications Module, generator set (CCM-G)
0541-0811 Controls Communications Module, transfer switch (CCM-T)
0541-0868 Network Communications Module
(NCM) for OTPC/BTPC, >1000 A
Ordering Information Part number Description
A059Y211 PC 500 Cloud Link N (up to 2 devices)
A059Y210 PC 550 Cloud Link N (up to 12 devices) http://power.cummins.com/