Section 16403 - Battery Specification.pdf
PDF 1 MB Posted
- Solicitation number
- 127EAX22Q0058
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
II®THE
SERIES VRLA BATTERY
THE TRUE LONG LIFE BATTERY TM
UL-Recognized Component
ADVANCED SYSTEM FEATURES
• Modular design for ease of installation and stacking flexibility
• Space saving design for the greatest amount of power in a small footprint
• Certified as NEBS Level 3 and compliant to Earthquake Risk Zone 4 in various system configurations
• Exceeds 1997 UBC Zone 4 seismic requirements for at or below grade installations
• Exceeds 2006 IBC requirements up to 300% g level and 2007 CBC compliant
• Tin-plated copper alloy connectors minimize maintenance
• New C&D Ohmic Ring® for ease of maintenance readings. With specially adapted probes only one technician is required to take readings.
ADVANCED MATERIALS
• Advanced micro-porous Absorbed Glass Mat separators for ultra-low float current — reduces grid corrosion for a long, usable service life
• Proprietary calcium alloys to minimize positive grid corrosion and growth — maximizes battery life
• Robust polypropylene container and cover — enhances product quality and improves strength of materials for safe operation with flammability rating
UL94 VO, LOI>28%
The msEndur II is the latest advancement in battery technology with enhanced features for TEL applications.
By combining the service life reliability of a flooded battery with the performance energy density of a valve-regulated battery, C&D has created the msEndur II — The True Long-Life Battery™.
The msEndur II series of batteries are unmatched in power density with space saving modular designs and have a 20-year design life to reduce the total cost of ownership.
With its much lower float current, the msEndur II yields significant electrical costs savings over its life making it the most environmentally 2V VRLA battery.
APPLICATIONS
• Wireless
• Wireline
• Central Office
• Mobile Switching Centers
• PBX Systems
• Microwave
• Broadband Headend
• Network Operation Ctrs
• Data Centers
For Standby Telecom Applications
CAPACITIES FROM 345 - 2180 AMPERE-HOURS
12-1008
• Highly efficient, proprietary plate processing for high utilization of active material — results in high energy density and low float current
ADVANCED PROCESSES
• Advanced formation process results in a narrow float voltage window making on-site float matching unnecessary
• Highly controlled manufacturing processes for exceptional and consistent plate quality
ADVANCED SERVICE LIFE & WARRANTY
• Proprietary cell design and manufacturing process provides for 20 year design life and documented long-lasting service life
• Industry leading warranty
ADVANCED EXPERIENCE
• Over 100 years of experience in the battery industry
• The only producer and marketer of complete battery and electronics systems for total power solutions
• Fully backed by a worldwide network for local service
FEATURES & BENEFITS
12-1008/1015/CD www.cdtechno.com
FV/Cell Models 1 hr 2 hr 3 hr 4 hr 5 hr 6 hr 8 hr 10 hr 12 hr 24 hr
AT-07P 189 123 93 75 63 55 43 36 30 16
AT-09P 259 170 129 104 88 76 60 50 42 23
AT-11P 324 213 161 130 110 95 75 62 53 28
AT-13P 352 228 172 139 117 101 80 66 56 30
AT-15P 454 298 225 182 154 133 105 87 74 40
AT-17P 505 327 247 200 168 145 115 95 81 43
AT-19P 583 383 290 234 198 171 135 112 95 51
1.75 AT-21P 631 409 309 250 210 182 144 119 101 54
AT-23P 713 468 354 287 241 209 165 136 116 62
AT-25P 757 491 370 299 252 218 172 143 122 65
AT-27P 843 553 418 339 285 247 195 161 138 73
AT-29P 884 573 432 349 294 255 201 166 142 76
AT-35P 1102 723 547 443 373 323 255 211 180 96
AT-39P 1199 777 586 474 399 345 273 226 193 103
AMPERES @ 77°F (25°)
Constant Current Discharge Ratings
Constant Power Discharge Ratings
Please refer to the msEndur ll Stackable Module System with Module Dimensions and Weights brochure, 12-1014, for a listing of typical msEndur ll Module Systems dimensions and weights.
Please refer to the msEndur II Performance Specifications Brochure, 12-1015, for an expanded list of constant power and constant current ratings and end voltages.
You may also access the product ratings by logging onto the C&D Battery Sizing Program at www.cdstandbypower.net
Specifications and Characteristics
AT-07P
ATL-07P AT-09P
ATL-09P AT-11P
ATL-11P AT-13P
ATL-13P AT-15P
ATL-15P
AT-17P
ATL-17P AT-19P
ATL-19P AT-21P
ATL-21P AT-23P
ATL-23P AT-25P
ATL-25P AT-27P
ATL-27P AT-29P
ATL-29P AT-35P
ATL-35P AT-39P
ATL-39P
Number of Terminals 2 2 2 2 2 2 4 4 4 4 4 4 4 4
8 Hr AH Rate to 1.75 v/c @ 77°F (25°C)
345 / 295 480 / 390 600 / 490 640 / 515 840 / 685 920 / 780 1080 / 880 1150 / 980 1320 / 1075 1380 / 1175 1560 / 1270 1605 / 1370 2040 / 1660 2180 / 1855
10 Hr AH Rate to 1.80 v/c @ 68°F (20°C)
330 / 275 460 / 365 575 / 460 610 / 485 800 / 645 875 / 735 1030 / 825 1095 / 920 1315 / 1100 1490 / 1195 1535 / 1285 1945 / 1560 2085 / 1745
AT-P = 2.25 - 2.27 volts per cell average @ 77°F (25°C) ATL-P = 2.17 - 2.22 volts per cell average @ 77°F (25°C) (-)2 mV/cell/°F above 77°F (-3.6 mV/cell /°C above 25°C) +2 mV/cell/°F below 77°F (+3.6 mV/cell/°C below 25°C)
Recommended Float Charging Voltage (ATL Recommended Float Voltage) Charger Compensation Temperature / Voltage
Cells, Voltage per Unit 1 cell, 2 VDC Energy Saving Operating Temperature Connection Torque: 77°F (25°C)
Initial: 160 in-lbs (18 N-m), Re-torque: 125 in-lbs (14 N-m)
1260 / 1010
FV/Cell Models 1 min 5 min 10 min 15 min 20 min 30 min 45 min 1 hr
AT-07P 0.837 0.791 0.730 0.669 0.612 0.520 0.430 0.373
AT-09P 1.117 1.055 0.973 0.892 0.816 0.693 0.574 0.497
AT-11P 1.396 1.318 1.217 1.115 1.020 0.866 0.717 0.622
AT-13P 1.558 1.471 1.358 1.244 1.138 0.967 0.800 0.694
AT-15P 1.954 1.846 1.704 1.561 1.427 1.213 1.004 0.870
AT-17P 2.233 2.110 1.947 1.784 1.631 1.386 1.147 0.995
AT-19P 2.512 2.373 2.190 2.007 1.835 1.559 1.291 1.119
AT-21P 2.792 2.637 2.434 2.230 2.039 1.733 1.434 1.243
AT-23P 3.071 2.901 2.677 2.452 2.243 1.906 1.578 1.368
AT-25P 3.350 3.164 2.920 2.675 2.447 2.079 1.721 1.492
AT-27P 3.629 3.428 3.164 2.898 2.651 2.253 1.864 1.617
AT-29P 3.908 3.692 3.407 3.121 2.855 2.426 2.008 1.741
AT-35P 2.946 2.438 2.114
AT-39P 2.725 2.363
KILOWATTS PER CELL @ 77°F (25°C)
1.67
12-1008/1015/CD 2 www.cdtechno.com
AT-15P through AT-39P
Cells Wide/Module 3
Modules High 84
AT-07P through AT-21P
Thick Walled Flame Retardant Polypropylene container & cover - UL VO – 28 LOI. More than 20 years proven field history.
Retains durability with age and in cold environments
Container to Cover Seal Thermally Welded with Joint Skirt ensuring leak free operation
Color coded terminal polarity
Pressure Release Vent with proven service in the field for over 15 years
High Capacity tin plated Copper Insert 0.75” Diameter (20% larger than msEndur)
Interlocking Rib
Molded in Heat Dissipation Channel
MSE-AT Active Material Low Float Current Design SR-4228 Tested
Absorbent Glass Mat separator C-wrapped to ensure plate isolation & optimized to reduce oxygen transfer
Molded in Tin-lead bushing with multiple seal rings to ensure a leak free seal
Outward protruding tin plated copper terminal with C&D Ohmic Ring® for ease of measurements during maintenance
Thermal bonded case to cover seal 100% factory tested with Helium Leak Detection & High Voltage leak testing.
Terminal post
Flame Retardant Polypropylene V-0 Cover
Flame Retardant Polypropylene V-0 Container msEndur II cells are designed to be mounted in stackable modules of either 3, 4, 5, 6, 8 &10 cells.
The most popular module sizes and configurations for Telecom systems are:
Modules
The specific cell wide x module high system configuration is flexible and can be configured to best match the physical requirements of the customer’s site.
Detailed system dimensions and combinations are available in the msEndur II Module Brochure 12-1014.
12-1008/1015/CD 3 www.cdtechno.com
12-1008 1015/CD
The msEndur II is the latest advancement in battery technology. By combining the service life reliability of a flooded battery with the performance energy density of a valve-regulated battery C&D has created the msEndur II — The True Long-Life Battery™. The msEndur II series of batteries are unmatched in power density with space saving modular designs and have a 20-year design life to reduce the total cost of ownership.
Pe rf or m an ce
E ne rg y D en si ty
Lo w
H ig h
Low High Service Life - Reliability
The msEndur II VRLA battery is the environmentally friendly battery that saves you money in normal operation.
The same low float current that ensures a twenty year life, is good for the environment and saves money
• Up to 75% lower float current
• Consumes up to 75% less electricity
• Lower float current generates less heat
• Less heat generated reduces required air conditioning
• Less electricity consumed in float charging and air conditioning = reduce carbon emissions msEndur II
2V VRLA
Traditional
2V VRLA
Flooded 2V
BEST
Has the light turned on yet?
Both devices can save you 75%
Standard 2V VRLA msEndur II
File details come from the government source that posted it. Updated .