Text version

C&D TECHNOLOGIES, INC.

1400 UNION MEETING ROAD

BLUE BELL, PA 19422

(215) 619-2700

FAX: (215) 619-7840

Project Information

Title: US Forest Service

Company: NGH Power Systems

Sized By: Tom Cleveland

Date: Wednesday 19th February 2020

Reference No.: Teseque Peak

Key Parameters

Number of Cells: 24 Minimum Temperature: 77 °F

Number of Jars: 24 Design Margin: 1.00

Final volts per cell: 1.75 vpc (average) Aging Factor: 1.00

Parallel Strings: 1

Load Information

Profile: Constant Current

Amps: 25.90

Duration: 1440 Minutes

AH Removed: 621.60

Battery

Model: AT-21P

Specific Gravity: 1.300

Type: VRLA 20 year

Product Line: msEndur II AT-P

Selection Criteria: By Product Line - msEndur II AT-P

% of Requirement: 208.94%

Runtime: > 24 hr Runtime is based on 100% battery capacity adjusted to user-selected minimum design temperature.

Number of Jars: 24

Jar Length: 23.19 in.

Jar Width: 7.49 in.

Jar Height: 9.04 in.

No. Plates: 21

*Float vpc: 2.26 volts per cell

*Max vpc: 2.33 volts per cell

Jar Weight: 155.0 lbs

Battery Weight: 3,720.00 lbs

Accessory Kits

Std. Accessory Kit: Please call C&D Applications Dept for accessory kit information

* Nominal values only, see Installation and Operations Manual for details.

The C&D Sizing Program adheres to the battery sizing methodologies found in the current versions of IEEE-485, Recommended Practice for Sizing Lead-Acid Batteries for Stationery Applications and IEEE-1184, Guides for Batteries for Uninterruptible Power Supply Systems

Wednesday 19th February 2020 ©2020 C&D Technologies, Inc. www.cdtechno.com

All critical calculations must be verified with C&D Applications Specifications are subject to change without notice

File details come from the government source that posted it. Updated .