B1W3 Customization MEP 100 CD Binder

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTION

LOW PRESSURE CONDENSATE RETURN PIPING

HOT WATER SUPPLY PIPING

HOT WATER RETURN PIPING

HIGH TEMPERATURE HOT WATER SUPPLY PIPING

HIGH TEMPERATURE HOT WATER RETURN PIPING

CHILLED WATER SUPPLY PIPING

CHILLED WATER RETURN PIPING

SUPPLY DUCT UP / SUPPLY DUCT DOWN

RETURN DUCT UP / RETURN DUCT DOWN

FLEXIBLE DUCT CONNECTION

BACKDRAFT DAMPER

TEMP. CONTROL DAMPER-OPPOSED BLADE

LOUVER WITH SCREEN

MANUAL VOLUME DAMPER

MOTOR OPERATED DAMPER

SPIN-IN FITTING WITH MVD

CONDENSER WATER SUPPLY PIPING

LOW PRESSURE STEAM SUPPLY PIPING (0 - 15#)

ROUND DUCT UP / ROUND DUCT DOWN

INDICATES FLAT OVAL DUCTWORK

ABBR. SYMBOL

COOLING COIL DRAIN PAN PIPING

TEMP. CONTROL DAMPER- PARELLEL BLADE

LPS

LPC

MPS

MVD

MPC

BBD

BF

RL

RS

RHG

TT

MEDIUM PRESSURE STEAM SUPPLY PIPING (16# - 60#)

MEDIUM PRESSURE CONDENSATE RETURN PIPING

HIGH PRESSURE STEAM SUPPLY PIPING (61# - 125#)

HIGH PRESSURE CONDENSATE RETURN PIPING

PUMPED CONDENSATE PIPING

BOILER BLOWDOWN PIPING

REFRIGERANT SUCTION PIPING

BOILER FEED WATER PIPING

FLOAT AND THERMOSTATIC STEAM TRAP

REFRIGERANT LIQUID PIPING

REFRIGERANT HOT GAS PIPING

TCD

FD

FSD

SD

DAD

TEMPERATURE SENSOR

DUCT FIRE DAMPER

COMBINATION DUCT SMOKE & FIRE DAMPER

DUCT SMOKE DAMPER

DUCT SMOKE DETECTOR

DUCT ACCESS DOOR

ELECTRIC-PNEUMATIC CONTROL VALVE

TURNING VANES IN DUCT ELBOW

WALL MOUNTED THERMOSTAT

PNEUMATIC-ELECTRIC CONTROL SWITCH

LOUVER

HUMIDISTAT

DUCT RISE

UNIT MOUNTED THERMOSTAT

UNDERCUT DOOR

THERMOSTATIC STEAM TRAP

DUCT DROP

HWS

HWR

HTWS

HTWR

CWS

CWR

D

C

CR

HPS

HPC

PC

F&T

IBT

TCV

MAV

AAV

FS

EJ

BJ

RSV

DPS

(2 OR 3-WAY) TEMPERATURE CONTROL VALVE

INVERTED BUCKET STEAM TRAP

VENTURI METER

CALIBRATED BALANCING VALVE

REFRIGERANT SERVICE VALVE

AUTOMATIC AIR VENT

DIFFERENTIAL PRESSURE SWITCH

MANUAL AIR VENT

FLOW SWITCH

EXPANSION JOINT

CONDENSER WATER RETURN PIPING

BALL JOINT EXPANSION COMPENSATOR

LPS

LPC

MPS

MPC

BBD

BF

RL

RS

RHG

HWS

HWR

HTWS

HTWR

CWS

CWR

D

C

CR

HPS

HPC

PC

SUPPLY & RETURN BRANCH

PIPING TO TERMINAL UNIT

C W

R ,H

W R

C W

S ,H

W S

CWS,CWR/HWS,HWR

ACOUSTICALLY LINED DUCTWORK

TEMPERATURE CONTROL OUTSIDE AIR DAMPER

TEMPERATURE CONTROL RETURN AIR DAMPER

TEMPERATURE CONTROL EXHAUST AIR DAMPER

STATIC PRESSURE IN INCHES WATER COLUMN

SUPPLY AIR DEVICE

RETURN AIR DEVICE

M

TS

F

T

T

H

U

L

R

D

SD

RG

SP IN WC

TCEAD

TCRAD

TCOAD

A.L.

48F12

TCD

BDD

EP

PE

DOUBLE/SINGLE LINE DUCT LEGEND

45° TEE (ROUND) FLEX DUCT 90° RADIUS ELBOW

RIGID FLEX

45° TEE (RECTANGULAR) 90° TEE (ROUND) MANUAL VOLUME DAMPER 90° ELBOW

DUCT SPLIT REDUCER 45° ELBOWGRD RUNOUT

90° TEE (RECTANGULAR)

SEE DUCT

TAKE-OFF DETAIL

CONICAL

TEE

VOLUME

DAMPER

PLUMBING LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTION

ACID RESISTANT WASTE PIPING (ABOVE FLOOR IN BUILDING)

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER CIRC. PIPING

SOFTENED DOMESTIC COLD WATER PIPING

SOFTENED DOMESSTIC HOT WATER PIPING

DOMESTIC HOT WATER PIPING @ TEMPERATURE SHOWN

SURFACE CLEANOUT

FLOOR CLEANOUT

LINE CLEANOUT

FIXTURE OR DRAIN P-TRAP

AREA DRAIN

FLOOR SINK (SQUARE GRATE)

ROOF DRAIN OR OVERFLOW DRAIN

GAS PRESSURE REDUCING VALVE

ATMOSPHERIC VACUUM BREAKER

ACID RESISTANT VENT PIPING

WASTE PIPING (ABOVE FLOOR IN BUILDING)

WASTE PIPING (BELOW FLOOR IN BUILDING)

WALL CLEANOUT

CLEANOUT TEE

ABBR. SYMBOL

VENT PIPING

FLOOR DRAIN (ROUND GRATE)

HW

HWC

C-SW

140° HW

V

H-SW

AV

W

W

AW

AW

CW

FS

RD / OD

VB

AV

W

W

AW

AW

GD

IW

S

ST

SSD

SD

SD

OD

OD

A

G G

ACID RESISTANT WASTE PIPING (BELOW FLOOR IN BUILDING)

IW

S

ST

SSD

SD

GD

SD

OD

OD

A COMPRESSED AIR

GREASE DRAIN (WASTE LINE TO GREASE INTERCEPTOR)

INDIRECT WASTE PIPING

SANITARY SEWER PIPING (OUTSIDE BUILDING)

STORM SEWER PIPING (BELOW GRADE OUTSIDE BUILDING)

SUB-SURFACE DRAIN PIPING

OVERFLOW DRAIN PIPING (ABOVE FLOOR IN BUILDING)

STORM DRAIN PIPING (ABOVE FLOOR IN BUILDING)

STORM DRAIN PIPING (BELOW FLOOR IN BUILDING)

OVERFLOW DRAIN PIPING (BELOW FLOOR IN BUILDING)

FCO

WCO

COT

AD

LCO

FD

SCO

BFP

SA

GC

FC

WH

HB

YH

MH

CI

MANHOLE

DOUBLE CHECK BACKFLOW PREVENTER

SHOCK ARRESTOR W / ISOLATION VALVE

GAS SHUT-OFF VALVE

STOP AND DRAIN VALVE

HOSE BIBB

HWC BALANCING VALVE

CAST IRON

WALL HYDRANT

YARD HYDRANT

INVERT ELEVATION

CATCH BASIN

POLYVINYL CHLORIDE

VITRIFIED CLAY PIPE

VENT THRU ROOF

VCP

CB

VTR

IE

PVC

SW

SW

140°

GENERAL LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTION

NEW

SECTION DESIGNATION

SECTION DRAWN ON THIS SHEET

SECTION CUT ON THIS SHEET

RISER DIAGRAM NUMBER

SHEET RISER IS DRAWN ON

EQUIPMENT UNIT IDENTIFICATION

CAP END OF PIPE

PITCH DOWN IN DIRECTION OF ARROW

UNION OR FLANGE

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE AND/OR TEMPERATURE RELIEF VALVE

PLUG VALVE

GATE VALVE

VERTICAL PIPE VALVE

DIFFUSER IDENTIFICATION

DIFFUSER NECK DIAMETER

DIFFUSER CFM

EXISTING

PIPE ANCHOR

PIPE ALIGNMENT GUIDE

ABBR. SYMBOL

EQUIPMENT UNIT NUMBER

PRESSURE REDUCING VALVE

(E)

(N)

(R)

PTRV

(F)

DIA

WAD

NIC

AFF

GC

MC

EC

RELOCATED

FUTURE

POINT OF CONNECTION, NEW TO EXISTING

DIRECTION OF FLOW IN PIPE

DUCTWORK, PIPING AND EQUIPMENT TO BE REMOVED

DIAMETER

ABOVE FINISHED FLOOR

WALL ACCESS DOOR

ELECTRICAL CONTRACTOR

NOT IN CONTRACT

GENERAL CONTRACTOR

PRV

GLV

BFV

BV

CV

P/T

STRAINER W/ BLOWDOWN

GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CHECK VALVE

SOLENOID VALVE

PRESSURE / TEMPERATURE TAP

BUTTERFLY SOLENOID VALVE

FLEXIBLE PIPE CONNECTOR

HOSE END DRAIN VALVE

STRAINER

CEILING ACCESS PANEL

PRESSURE GAUGE

PUMP

THERMOMETER

SIGHT GLASS

C.A.P.

TB

MECHANICAL CONTRACTOR

UNIT

M-X

X

X.X X.X

X

GV

THRUST BLOCK

XX

P/T

DETAIL SHEETS PLAN SHEETS

XX

NATURAL GAS PIPING

(Not all symbols listed below are used on these drawings) (Not all symbols listed below are used on these drawings)

(Not all symbols listed below are used on these drawings)

NECK

CFM

X

EXHAUST DUCT UP / EXHAUST DUCT DOWN

WALL MOUNTED CARBON DIOXIDE SENSORC

EXHAUST AIR DEVICEEG

KEYNOTE

SINGLE LINEDOUBLE LINEDOUBLE LINESINGLE LINE SINGLE LINE

FLEXRIGID

SINGLE LINE DOUBLE LINE DOUBLE LINE

(Not all symbols listed below are used on these drawings)

DP

T

IBT

F&T

TT

R N

D

R E

C

45° TAKEOFF

SPIN IN

X

RETURN AIR DEVICE WITH SOUND BOOTRG

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n A

A c re e .r v t

/3

/2

:3 :5

P

M

MECHANICAL

LEGENDS & NOTES

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

M0.1.0

201009.006

AJA

3/30/16

B ro a d w a y

B o u ld e r, C O

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS

TO REMAIN ARE DENOTED LIGHTLY.

A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTION

ACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, OWNER'S EQUIPMENT OR

VALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; OR

ESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING

CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THE

ENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.

COORDINATE WORK WITH ALL TRADES.

CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANY

ROOF OPENING NOT COMPLETED DURING WORKING HOURS.

COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.

CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTED

EQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BE

TAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFT

OPERATIONAL.

CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMS

WITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.

HVAC PLAN NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWN

OTHERWISE.

DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE AS NECK

SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.

ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINAL BOXES

SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFS FROM MAINS

SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.

BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAME SIZE

AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE. BRANCH DUCTS TO

TERMINAL BOXES EXCEEDING 15' OR TWO ELBOWS, SHALL BE UP-SIZED TO NEXT

STANDARD DIAMETER.

UNLESS OTHERWISE NOTED, ALL SUPPLY AIR DUCTWORK SHALL BE

EXTERNALLY WRAPPED TO THICKNESS AS STATED IN SPECIFICATIONS. RETURN

AND EXHAUST DUCTWORK IS NEITHER LINED NOR WRAPPED.

PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) AT THE

DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.

PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING AS REQUIRED

WHICH MAY NOT NECESSARILY BE SHOWN.

ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROM MAINS

SHALL BE TOP TAKE-OFFS WITH SWING JOINTS.

PLUMBING NOTES:

1.

2.

3.

4.

CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY

SYSTEMS/SERVICES WITHOUT FIRST COORDINATING WITH OWNER.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING

CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOR RESOLUTIONS.

THIS CONTRACTOR SHALL COORDINATE LOCATIONS OF PIPING WITH OTHER

TRADES AND ADVISE ARCHITECT/ENGINEER OF ANY POSSIBLE CONFLICTS.

VERIFY EXACT LOCATIONS, ELEVATIONS AND DIMENSIONS OF STRUCTURAL

MEMBERS AND OPENINGS.

ALL LAB GAS PIPING SHALL HAVE TOP TAKE-OFFS WHENEVER POSSIBLE.

ISSUE FOR CONSTRUCTION 03/30/161

540-1 845-01 510-04

PRESSURE INDEPENDENT CONTROL VALVES

FOR SMALL CHILLED WATER VALVES (TYP.)

REFER TO WATER COOLED EQUIPMENT

PIPING DETAIL.

PCWR (LAB)

CWR PCWS

PCWS (LAB)

CWS

DP

ET

PCWP

PFHX

PCWP

VFD

VFD

COUPON RACK

POT FEEDER

EXP.

TANK

SEPARATOR

AIR

M

TO DRAIN

RPBFP

TURBINE

FLOW

METER

P.I. CONTROL VALVE

(BACKUP DOMESTIC WATER COOLING)

1-1/2"CW

2"

PROCESS CHILLED WATER

TO LAB EQUIPMENT (TYP.)

MINIMUM FLOW VALVE

(20 GPM). RE: FLOOR

PLANS FOR LOCATION.

2" 4"

3/4"CW

1-1/2"

ATTACH PUMP TO CONCRETE

HOUSEKEEPING PAD PER MFR.

INSTRUCTIONS.

1/2"

HOSE END

DRAIN

VALVE

AIR

CHARGING

PORT

(MECH SYSTEM MAKEUP)

WATER METER

1-1/2"CW

PROCESS COOLING 1-LINE DIAGRAM

IN-LINE PUMP PIPING DETAIL EXCHANGER PIPING DETAIL

PLATE AND FRAME HEAT

EXPANSION TANK DETAIL

SCALE: NONE

SCALE: NONE

PUMP

PORTS ON PUMP

FLANGE

P/T

PRESSURE GAUGE

PROVIDE FLOW

DEVICE AND BALANCING

COCK PER SPEC

CHECK VALVE

P/T

1/2" TUBING OR

IPS. SAME MATERIAL

AS TRANSPORT PIPING

SCALE: NONE

P C

H W

S

LTCHWSPCHWS

UNION

PCHWR

THERMOMETER

LTCHWR

PRESSURE GAUGE

L T

C H

W S

PRESSURE

INDEPENDENT

CONTROL VALVE.

SAME-SIDE, COUNTER-FLOW

MANUAL AIR

VENT (TYP)

3/4" DRAIN VALVE

W/HOSE END CONN.

COORDINATE PIPE CONNECTION ARRANGMENT WITH MANUFACTURER'S REQUIREMENTS.

HOUSEKEEPING

PAD

P/T P/T

P/T P/T

SCALE: NONE

FLOOR

AIR SEPARATOR

PUMP

N.O.

HIGH

CAPACITY

AUTO AIR

VENT

BACKFLOW PREVENTER @ 5' A.F.F.

MAX. WITH DRAIN FUNNEL AND DRAIN

PIPED TO DRAIN. SEE PLUMBING PLANS

DOMESTIC

MAKE-UP

WATER

TO

SYSTEM

3/4" FEMALE

HOSE

CONNECTION

FOR QUICK FILL

OUTLET SIZE

BLOW DOWN

VALVE W/HOSE END

EXPANSION

TANK SEE PUMP DETAIL

FOR ADDITIONAL

DATA

FROM

SYSTEM

FULL-SIZE DISCHARGE

PIPE FROM AIR VENT TO

FLOOR DRAIN W/AIR GAP

PRESSURE

REDUCING VALVE

ASSEMBLY

PLATE AND FRAME HEAT EXCHANGER SCHEDULE

HEAT PLATES HIGHER TEMPERAURE SIDE LOWER TEMPERATURE SIDE SIZE (INCHES)

DESIG. MFR. MODEL SERVICE TRANSFER MBH NUMBER EXTENSION EWT LWT GPM PROP WATER EWT LWT GPM PROP WATER L W H OPER REMARKS

AREA TRANSFER FOR CAPACITY °F °F GLYCOL P.D. °F °F GLYCOL P.D. WEIGHT

(SF) DESIGN % (FT WC) % (FT WC) (LBS)

PFHX-1 ALFA LAVAL AQ2L

PROCESS

CHILLED WATER

376 1,300 139 43 68 48 130 0% 11.0 44 64 130 0% 11.0 40 13 51 900

REMARKS:

1. PROVIDE INSULATED COVERING OVER PLATES WITH ALUMINUM COVER.

3/29/2016 17:37 P:\2016\2016-068 NIST Wing 3 Customization\Cad\Mech\Mschedules\[M-2016-068.xlsx]S970-4 Tmp Mtrx

PUMP SCHEDULE

MAX MOTOR VIBRATION INLET OUTLET OPER.

DESIG. MFR. MODEL PUMP TYPE SERVICE PUMP PROP GPM PRESSURE NPSH EFF. MIN. RPM VFD/ VFD ISOLATOR SIZE SIZE WEIGHT REMARKS

OPER GLYCOL (FT HD) (FT HD) % HP AT RELAY/ BYPASS TYPE (IN.) (IN.) LBS.

°F (%) 60HZ STARTER (YES/

NO)

PCWP-1 GRUNDFOS CR20-5

VERTICAL

MULTISTAGE

PROCESS

CHILLED WATER

125 0% 130 220 14.5 68 15.0 3500 VFD NO -- 2 2 305

PCWP-2 GRUNDFOS CR20-5

VERTICAL

MULTISTAGE

PROCESS

CHILLED WATER

125 0% 130 220 14.5 68 15.0 3500 VFD NO -- 2 2 305

APPLIES TO ALL:

> REFER TO ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.

REMARKS:

1. PUMPS OPERATING THRU VFDS: UPON SELECTING THE PUMP FOR THE SPECIFIED DUTY POINT, THE SUPPLIER SHALL PROVIDE THE PUMP WITH THE LARGEST IMPELLER SIZE AVAILABLE FOR THE CASING THAT DOES NOT EXCEED THE DUTY POINT MOTOR HP AT THE RIGHT END OF THE CURVE. SUBMITTAL DATA SHALL SHOW ALL IMPELLER CURVES AVAILABLE FOR THE PUMP MODEL. THIS APPLIES TO ALL MANUFACTURERS.

2. UNLESS INDICATED BY PUMP MODEL NUMBER, VARIABLE FREQUENCY DRIVE (VFD) IS REMOTE-MOUNTED RATHER THAN PUMP MOUNTED WHEN REQUIRED.

3. PROVIDE SHAFT GROUNDING RINGS FOR EACH BEARING ON MOTORS POWERED THROUGH VARIABLE FREQUENCY DRIVES.

3/29/2016 17:37 P:\2016\2016-068 NIST Wing 3 Customization\Cad\Mech\Mschedules\[M-2016-068.xlsx]S970-4 Tmp Mtrx

EXPANSION TANK SCHEDULE

CAPACITY PRE-CHARGE OPER.

DESIGNATION MANUFACTURER MODEL ACCEPT. TANK SERVICE PRESSURE WEIGHT REMARKS

VOL. VOL. (PSIG) (LBS)

ET-1 B&G D-80 22.6 44.4

PROCESS CHILLED

WATER

30 516 NOTE 1

NOTES:

1. PROVIDE ASME RATED TANK.

3/29/2016 17:37 P:\2016\2016-068 NIST Wing 3 Customization\Cad\Mech\Mschedules\[M-2016-068.xlsx]S970-4 Tmp Mtrx

TEMPERATURE CONTROL MATRIX

POINT TYPE ANALOG IND. ALARM

POINTS LIST: N

O

O

F U

N

IT

S

D

IG

IT

A

L I N

P U

T

D

IG

IT

A

L O

U T

P U

T

A N

A L

O G

I N

P U

T

A N

A L

O G

O U

T P

U T

T E

M P

E R

A T

U R

E

R E

L H

U M

ID

IT

Y

P O

S

IT

IO

N

/S P

E E

D /L

E V

E L

P R

E S

S U

R E

S T

A T

U S

H

IG

H

L O

W

M A

IN

T

E N

A N

C E

P K

G D

E

Q U

IP

A

L A

R M

E M

S P

R O

G R

A M

S

REMARKS

PROCESS CHILLED WATER SYSTEM

Process Cooling Pump Start/Stop 2 X

Process Cooling Pump Status 2 X X

Process Cooling Pump VFD Speed 2 X X

Process Cooling Pump VFD Fault 2 X X

HX Control Valve 1 X X

Process Cooling Supply Temp 1 X X

Process Cooling Return Temp 1 X X

Process Cooling System dP 1 X X

Process Cooling Makeup Water Meter Flow 1 X

Process Cooling Min Flow Valve 1 X X

Process Cooling Flow Meter 1 X X

LTCHWS Isolation Valve 1 X X

LTCHWR Isolation Valve 1 X X

Backup Cooling Supply Isolation Valve 1 X X

Backup Cooling Supply Control Valve 1 X X

NOTES:

(Notes that are not explicitly referenced in the above schedule are to be considered general notes that apply to all items in the schedule.)

1. The Temperature Control Matrix, Control Diagrams, and the Sequence of Operation are all binding. If there is a discrepancy between them, the worst case scenario shall be used for bidding purposes. Additional costs will not be allowed for discrepancies between the specifications and the drawings.

2. See plans for quantity.

AIR SEPARATOR SCHEDULE

PRESSURES SIZE (INCHES)

DESIG. SERVICE MANUFACTURER MODEL NO. STYLE GPM PROP WPD STRAINER INLET/ RATED OPER LxW HEIGHT OPER REMARKS

GLYCOL (FT HD) (YES/NO) OUTLET (PSIG) (PSIG) WEIGHT

% SIZE (LBS)

(IN)

AS-1

PROCESS CHILLED

WATER

SPIROTHERM VSR400

STANDARD AIR

MICRO-BUBBLE

130 0% 1.0 N/A 4 150 32 21x9 24 145 1,2,3

REMARKS:

1. PROVIDE AUTOMATIC AIR VENT INTEGRAL OR SEPARATELY.

2. ASME CONSTRUCTION.

3. STANDARD VELOCITY MODEL.

3/8/2016 P:\2016\2016-068 NIST Wing 3 Customization\Cad\Mech\Mschedules\[M-2016-068.xlsx]S120-2 AirSep

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n A

A c re e .r v t

/3

/2

:3 :5

P

M

MECHANICAL

SCHEDULES AND

DETAILS

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

M0.2.0

201009.006

AJA

3/30/16

B ro a d w a y

B o u ld e r, C O

MAINT.

ACCESS

MAINT.

ACCESS

4"ø MTCHWR

3"ø HHWS

1 1/4"ø LTCHWR

/4

"ø C

D

"ø

L T

C H

W S

"ø

L T

C H

W R

1 1/4"ø LTCHWS

3"ø HHWR 2 1/2"ø HHWR 2 1/2"ø HHWS

3"ø MTCHWR

1"ø HHWR 1"ø HHWS

3"ø HHWR

4"ø MTCHWS

2 1/2"ø MTCHWR

2 1/2"ø MTCHWS

3"ø MTCHWS

2"ø HHWR

2"ø HHWS

RGRFRERDRCRBRANLKH

37.137

32.1

MEN

WOMEN

JAN

3303INTERACTION

MECH

CIRCULATION

CO-12-3

CIRCULATION

ST-7-3

INTERACTION

IDF

CONFERENCE

PRIVATE

OFFICE

OPEN OFFICE

3312 PRIVATE

OFFICE

PRIVATE

OFFICE

OPEN OFFICE

PRIVATE

OFFICE

OPEN OFFICE

LAB

LAB

LAB

ELEC

SERVICE CORRIDOR

SC-1-3

CIRCULATION

CO-1-3

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

2" PCHWR

3" PCHWS

3" PCHWR

2" PCHWS

2" PCHWR

2" PCHWS

Q1 Q1Q1

Q1

Q4

6"ø LTCHWS

6"ø LTCHWR

6"ø MTCHWR

6"ø MTCHWS

3/4"ø CD

1"ø LTCHWR

1"ø LTCHWS

2"ø HHWR 2"ø HHWS

1 1/2"ø HHWR 1 1/2"ø HHWS

RN.1RNRMRLRKRJRHRG

37.137

32.1

CIRCULATION

CO-12-3

BREAK ROOM

OPEN OFFICE

IDF

OPEN OFFICE

OPEN OFFICE

PRIVATE

OFFICE

PRIVATE

OFFICE

CONFERENCE/

PHONE

INTERACTION

MECH

3353A

MECH

3353B

LAB

LAB

LAB

LAB

4" PCHWS

4" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

1 1/2" PCHWS

1 1/2" PCHWR

4" PCHWR

4" PCHWS

3" PCHWR

3" PCHWS

Q1Q1Q1Q1Q1

M1.1.3

RN

PFHX

4" LTCHWR

4" LTCHWS

PCHWP

PCHWP

AIR SEPARATOR

AS-1

CHILLED WATER

PUMP VFD'S

ET

(BELOW)

4" PCHWS

4" PCHWR

Q2Q3

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n A

A c re e .r v t

/3

/2

:3 :5

P

M

WING 3 - LEVEL 3 -

HVAC PIPING PLAN

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

M1.1.3

201009.006

AJA

3/30/16

B ro a d w a y

B o u ld e r, C O

KEYNOTES

Q1 1-1/2"PCHWS/R DN TO 4FT A.F.F. TERMINATE WITH THREADED END

BALL VALVE WITH PLUG FOR CONNECTION TO LAB EQUIPMENT BY

OTHERS.

Q2 4" LTCHWS/R AND 4" PCHWS/R DN TO HX. TRANSITION TO HX NOZZLE

CONNECTION SIZE AS CLOSE TO HX AS PRACTICAL.

Q3 CONNECT TO (E) 6" LTCHWS/R PIPING.

Q4 LOCATION OF BYPASS VALVE AND SYSTEM DP SENSOR.

SCALE: 1/8" = 1'-0"

WING 3 - LEVEL 3 - HVAC PIPING PLAN - AREA A

SCALE: 1/8" = 1'-0"

WING 3 - LEVEL 3 - HVAC PIPING PLAN - AREA B

1/4" = 1'-0"

3 ENLARGED MECHANICAL ROOM PIPING PLAN

DN

2"ø

2"ø

3"ø

RGRFRERDRCRBRANLKH

37.137

32.1

MEN

WOMEN

JAN

3303INTERACTION

MECH

CIRCULATION

CO-12-3

CIRCULATION

ST-7-3

INTERACTION

IDF

CONFERENCE

PRIVATE

OFFICE

OPEN OFFICE

3312 PRIVATE

OFFICE

PRIVATE

OFFICE

OPEN OFFICE

PRIVATE

OFFICE

OPEN OFFICE

LAB

LAB

LAB

ELEC

SERVICE CORRIDOR

SC-1-3

CIRCULATION

CO-1-3

3/4" LA

G1

3/4" LA 3/4" LA3/4" LA

G1 G1 G1

3"ø

RN.1RNRMRLRKRJRHRG

37.137

32.1

CIRCULATION

CO-12-3

BREAK ROOM

PRIVATE

OFFICE

OPEN OFFICE

IDF

OPEN OFFICE

OPEN OFFICE

PRIVATE

OFFICE

PRIVATE

OFFICE

CONFERENCE/

PHONE

INTERACTION

MECH

3353A

MECH

3353B

LAB

LAB

LAB

LAB

3/4" LA 3/4" LA 3/4" LA 3/4" LA 3/4" LA

BFP

CONNECT 1-1/2"CW &

2"D TO MECH. CHW

SYSTEM. REFER TO

DETAILS.

1 1/2" CW

1 1/2" CW

2"D DN TO FS

G1 G1 G1 G1 G1

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n A

A c re e .r v t

/3

/2

:3 :4

P

M

WING 3 - LEVEL 3 -

PLUMBING PLAN

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

M1.2.3

201009.006

AJA

3/30/16

B ro a d w a y

B o u ld e r, C O

KEYNOTES

G1 3/4"LA DN TO 4FT A.F.F. TERMINATE WITH THREADED END BALL VALVE

WITH PLUG FOR CONNECTION TO LAB EQUIPMENT BY OTHERS.

SCALE: 1/8" = 1'-0"

WING 3 - LEVEL 3 - PLUMBING PLAN - AREA A

SCALE: 1/8" = 1'-0"

WING 3 - LEVEL 3 - PLUMBING PLAN - AREA B

POWER LEGEND

(Not all symbols listed below are used on these drawings)

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE, HALF SWITCHED

DUPLEX RECEPTACLE, CEILING MOUNTED

DUPLEX RECEPTACLE, FLOOR MOUNTED

DOUBLE DUPLEX RECEPTACLE, FLOOR MOUNTED

SPECIAL RECEPTACLE

SPECIAL RECEPTACLE, FLOOR MOUNTED

JUNCTION BOX, WALL OR CEILING MOUNTED

JUNCTION BOX, FLOOR MOUNTED

DISCONNECT SWITCH (NON-FUSED)

DISCONNECT SWITCH (FUSED)

VARIABLE SPEED DRIVE WITH DISCONNECT

UTILITY METER

ELECTRICAL PANELBOARD, CONTROL PANEL, OR OTHER

CABINET AS NOTED

PLUG MOLD (MULTI-OUTLET ASSEMBLY)

CONDUIT EXPOSED

CONDUIT TURNING DOWN

CONDUIT TURNING UP

CONDUIT CAPPED

MAIN SWITCHBOARD/DISTRIBUTION CENTER

CURRENT TRANSFORMER

GENERATOR ANNUNCIATOR PANEL

CONDUIT, UNDERGROUND OR CONCEALED IN FLOOR

AS ALLOWED PER SPECIFICATIONS

BRANCH CIRCUIT HOME RUN, NUMBER OF ARROWS INDICATES

NUMBER OF CIRCUITS, SUBSCRIPTS INDICATE PANEL & CIRCUITS

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

CLG

J

J

M

WM

A-1,3,5

T

CT

GANN

MOTOR

CONDUIT CONCEALED

GROUND BAR

TRANSFORMER

THERMOSTAT

SINGLE POLE SWITCH (SUBSCRIPT DENOTES SWITCHING)

TWO POLE SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

KEY OPERATED SWITCH

MANUAL SWITCH, HORSEPOWER RATE

DIMMER SWITCH

LOW VOLTAGE SWITCH

VARIABLE SPEED/SPEED CONTROLLER SWITCH

EXPLOSION PROOF SWITCH

THERMAL OVERLOAD SWITCH

MOMENTARY CONTACT SWITCH

COMBINATION SWITCH AND DUPLEX RECEPTACLE

PHOTOCELL

TIME CLOCK

SWITCH WITH PILOT LIGHT LOCATOR

(CONTINUOUSLY LIGHTED HANDLE)

PUSH BUTTON

OCCUPANCY SENSOR - WALL MOUNTED

IR=INFRARED, US=ULTRASONIC, DT=DUAL TECHNOLOGY

Sa

S2

S3

S4

SK

SM

SD

SPI

SP

SLV

SVS

SEP

STO

SMC

S

TC

ABBREVIATIONS LEGEND

AMPERES

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

ANNUNCIATOR

ABOVE RAISED FLOOR

AIR SAMPLING SMOKE DETECTION

AUTOMATIC TRANSFER SWITCH

BELOW FINISHED GRADE

MOTOR CIRCUIT PROTECTOR

SEE MECHANICAL EQUIPMENT SCHEDULE

MINIMUM

MAIN LUGS ONLY

MANUAL TRANSFER SWITCH

NORMALLY CLOSED

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALECONDUIT

CABLE TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

EXISTING

EMERGENCY

EMERGENCY MAIN DISTRIBUTION CENTER

EXPLOSION PROOF

EMERGENCY POWER OFF

EMERGENCY VENTILATION ON/OFF

ELECTRIC WATER COOLER

FIRE ALARM

GROUND

GENERATOR CONTROL PANEL

GROUND FAULT CIRCUIT INTERRUPTER

HAND OFF AUTOMATIC

ISOLATED GROUND

MAXIMUM

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION CENTER TRANSFORMER

WEATHER PROOF

WITHOUT

WITH

VARIABLE FREQUENCY DRIVE

VOLTS

UNINTERRUPTIBLE POWER SUPPLY

UNLESS OTHERWISE NOTED

UNDER GROUND

UNDER FLOOR

TYPICAL

TRANSIENT VOLTAGE SURGE SUPPRESSER

TAMPER PROOF

SUB-DISTRIBUTION CENTER

STAND-BY

PULL BOX

ON SITE WORK FORCE

OWNER FURNISHED, OWNER INSTALLED

OWNER FURNISHED, CONTRACTOR INSTALLED

ON CENTER

ABOVE COUNTER, MOUNT HORIZONTALLY TO CENTERLINE

OF DEVICE, +6" ABOVE COUNTER OR BACK SPLASH

NOT IN CONTRACT

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

REFERENCE SYMBOLS LEGEND

(Not all symbols listed below are used on these drawings)

KITCHEN/OWNER/MEDICAL EQUIPMENT REFERENCE

MECHANICAL EQUIPMENT REFERENCE

EXISTING TO REMAIN

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

EXISTING TO REMAIN - REPLACE DEVICE

DESCRIPTION DESCRIPTIONSYMBOL

A-1

LC1

UH

E

R

RL

ER

ONE-LINE DIAGRAM LEGEND

(Not all symbols listed below are used on these drawings)

DISCONNECT SWITCH

DISCONNECT SWITCH, FUSED

CIRCUIT BREAKER

PANELBOARD "A"

EM=ENERGY METER, PM=POWER METER, CM=CIRCUIT MONITOR

VOLTMETER TEST SWITCH

AMMETER TEST SWITCH

VOLTMETER

AMMETER

ENGINE GENERATOR

CONTACTOR/RELAY/CAPACITOR (AS NOTED)

TRANSFER SWITCH - ATS=AUTOMATIC, MTS=MANUAL

GROUND FAULT INTERRUPTER

TRANSIENT VOLTAGE SURGE SUPPRESSER

SHUNT TRIP

TERMINATIONS LB=LOAD BREAK, NLB=NO LOAD BREAK

DRAW-OUT DEVICE

PLUG-IN DEVICE

ELECTRICALLY OPERATEDMECHANICAL INTERLOCK

ELECTRICAL INTERLOCK, SUBSCRIPT INDICATES INTERLOCKED GROUP

KIRK KEY INTERLOCK, SUBSCRIPT INDICATES INTERLOCKED GROUP

SHORT CIRCUIT CURRENT AVAILABLE

SERVICE WEATHERHEAD

EQUIPMENT ENCLOSURE

METER

SERVICE ENTRANCE TRANSFORMER

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

STEP DOWN TRANSFORMER, ## INDICATES KVA

GROUND

FUSE

K-RATED STEP DOWN TRANSFORMER

## INDICATES KVA, # INDICATES K RATING

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

T

OR

ISCA

K a

E a

M

A

PM

VS

V

GFI

XXX

SYMBOL

M

(Not all symbols listed below are used on these drawings)

T

PM

CONTROLS LEGEND

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

(Not all symbols listed below are used on these drawings)

TK

AS

A

G

TVSS

ST

EO

P

MDC

MCC

MCB

MAX

IG

HOA

GFCI

GCP

G

FA

EWC

EVO

EPO

EP

EMDC

EM

(E)

CCTV

CB

CATV

C

BFG

ATS

ASSD

ARF

ANN

AFG

AFF

AC

A

XFMR

WP

W/O

W/

VFD

V

UPS

UON

UG

UF

TYP

TVSS

TP

SDC

SB

PB

OSWF

OFOI

OFCI

OC

NTS

NO

NL

NIC

NC

MTS

MLO

MIN

MEC

MCP

WIREMOLD (SURFACE RACEWAY)

SHADING INDICATES EMERGENCY SYSTEM

TEXT INDICATES PANEL AND CIRCUIT DESIGNATION

SWITCH WITH PILOT LIGHT

(PILOT LIGHT IS 'ON' WHEN SWITCH IS 'ON')

SEE FEEDER/MEC/TRANSFORMER SCHEDULES FOR FEEDER SIZE

KEY NOTE REFERENCE

M

LPA-# TYPICAL CIRCUIT NUMBER

TYPICAL LUMINAIRE TYPE

TG#

LIGHTING CONTROL / EQUIPMENT REFERENCE

TYPICAL ROOM REFERENCE (TOP = RM #, BOTTOM = FLR)

X

X

EXISTING TO BE REMOVED AND REPLACEDRR

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n J H a fe r.

rv t

/3

/2

:3 :5

P

M

ELECTRICAL

LEGENDS & NOTES

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

E0.1.0

201009.006

JAH

JAH

03/30/16

B ro a d w a y

B o u ld e r, C O

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

FOR REMODELING, WORK INCLUDED IS DENOTED IN BOLD. EXISTING CONDITIONS

TO REMAIN ARE DENOTED LIGHTLY.

PROTECT STRUCTURE AND OWNER EQUIPMENT FROM DAMAGE. IMMEDIATELY

REPLACE OR REPAIR, TO ORIGINAL CONDITION, DAMAGE CAUSED BY THE

CONTRACTOR WHETHER EQUIPMENT APPEARS TO BE CURRENTLY IN USE OR NOT,

UNLESS WRITTEN AUTHORIZATION FROM THE OWNER INDICATED OTHERWISE.

PREPARE LISTING OF ALL EXISTING DAMAGED ITEMS AND SUBMIT TO OWNER PRIOR

TO BEGINNING WORK.

FIRE SEAL ALL FIRE RATED WALL AND FLOOR PENETRATIONS. REFER TO

ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS.

COORDINATE EXACT REQUIREMENTS AND LOCATIONS OF MECHANICAL EQUIPMENT

WITH MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN

AND ORDERING MATERIALS OR EQUIPMENT.

A DETAILED WRITTEN METHOD OF PROCEDURE IS REQUIRED WHEN A

CONSTRUCTION ACTIVITY OR AN OUTAGE AFFECTS THE SAFETY OF OCCUPANTS,

TELEPHONE/DATA/FIRE ALARM EQUIPMENT OR COMPONENTS OF ANY SYSTEM

WHICH SUPPORTS THIS EQUIPMENT OR ESSENTIALLY AFFECTS THE BUILDING

MANAGEMENT, OPERATIONS OR SECURITY. SEE SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

EXISTING INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM

OWNER FURNISHED DRAWINGS AND/OR LIMITED FIELD OBSERVATIONS. CATOR,

RUMA & ASSOCIATES IS NOT RESPONSIBLE FOR THE ACCURACY OF ANY

INFORMATION OR THE ADEQUACY, SAFETY AND CONFORMANCE TO CURRENT

PREVAILING CODES OF ANY WORK SHOWN AS EXISTING ON THESE DRAWINGS.

PROVIDE SEPARATE INSULATED GROUNDING CONDUCTOR IN ALL FEEDER,

HOMERUN AND BRANCH CIRCUITS.

CONTRACTOR SHALL PROVIDE PRE-PAINTED CONDUIT. COLOR SCHEME TO MATCH

NIST'S STANDARDS AS FOLLOWS. THIS REQUIREMENT APPLIES TO BOTH FEEDERS

AND BRANCH CIRCUITS.

- BLUE: MECHANICAL CONTROLS (24-VOLT)

- WHITE: NORMAL RESEARCH POWER

- GREY (UNPAINTED): NORMAL BRANCH POWER

PROVIDE LAMACOID/PHENOLIC LABLES ON ALL PANELBOARDS, TRANSFORMERS,

DISCONNECT SWITCHES, CIRCUIT BREAKERS, VARIABLE FREQUENCY DRIVES, ETC.

TO MATCH EXISTING LABELING: PROVIDE LAMACOID/PHENOLIC LABES WITH THE

FOLLOWING COLOR SCHEME:

- BLUE WITH WHITE LETTERING: MECHANICAL CONTROL DEVICES

- WHITE WITH BLACK LETERING: NORMAL RESEARCH POWER

- GREY WITH WHITE LETTERING: NORMAL BRANCH POWER

POWER PLAN NOTES:

1.

2.

3.

4.

MAKE ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT REQUIRING

ELECTRICAL CONNECTION. THIS SHALL INCLUDE BUT NOT BE LIMITED TO ALL

MECHANICAL AND OTHER EQUIPMENT INCLUDED IN THIS PROJECT.

COORDINATE EXACT REQUIREMENTS AND LOCATIONS OF MECHANICAL

EQUIPMENT WITH MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR

PRIOR TO ROUGH-IN.

PROVIDE FUSES SIZED PER EQUIPMENT MANUFACTURER'S REQUIREMENTS.

DISCONNECT SWITCH LOCATIONS ARE SHOWN DIAGRAMMATICALLY AND SHALL

BE INSTALLED IN ACCESSIBLE LOCATIONS TO SUIT EQUIPMENT AND SPACE.

DISCONNECT SWITCHES SHALL BE WITHIN SIGHT OF THE EQUIPMENT THEY

SERVE AND MOUNTED AT 6'-3", MAXIMUM, TO TOP OF CABINET. MAINTAIN NEC

WORK SPACE REQUIREMENTS.

Key # Item HP FLA Load Eq Load (VA) Voltage

Feeders Protection

NotesWire Ground Conduit Breaker Disconnect Fuse

PCHWP 1 PROCESS CHILLED WATER

PUMP

15 0 A 0 VA 16732 VA 480V 3ph 3#10 #10G 3/4” 40 A 60 A 35 A 2

PCHWP 2 PROCESS CHILLED WATER

PUMP

15 0 A 0 VA 16732 VA 480V 3ph 3#10 #10G 3/4” 40 A 60 A 35 A 2

M E C H A N I C A L E Q U I P M E N T S C H E D U L E

NOTES:

1. REFER TO FLOOR PLAN FOR EQUIPMENT CIRCUITING.

2. VFD (VARIABLE FREQUENCY DRIVE) FURNISHED WITH EQUIPMENT. PROVIDE

DISCONNECTING MEANS AS INDICATED. DISCONNECTING MEANS SHALL BE

EQUIPPED WITH AUXILARY CONTACTS FOR VFD SHUTDOWN/COMMUNICATION.

COORDINATE WITH THE MECHANICAL CONTRACTOR.

BUS DUCT LOAD SUMMARY (DB3-1A)

BUS DUCT LOAD SUMMARY (DB3-1B)

BUS DUCT RATING 600 AMPS

* EXISTING LOAD (PANEL L3C-A1) 28.2 KVA

* EXISTING LOAD (PANEL L3C-A2) 30.0 KVA

** NEW LOAD ADDED (PANEL L3C-A3) 34.5 KVA

** NEW LOAD ADDED (PANEL L3C-A4) 51.8 KVA

TOTAL LOAD 144.5 KVA

( 174 AMPS)

* EXISTING LOAD TAKEN FROM THE "CONNECTED LOAD"

INDICATED ON THE ORIGINAL CONTRUCTION DOCUMENTS.

** NEW LOAD IS ANTICIPATED FOR FINAL BUILDOUT OF LAB

SPACE UNDER FUTURE PHASE OF WORK.

BUS DUCT RATING 600 AMPS

* EXISTING LOAD (PANEL L3C-B2) 19.4 KVA

* EXISTING LOAD (PANEL L3C-B3) 27.2 KVA

* EXISTING LOAD (PANEL L3C-B4) 29.0 KVA

** NEW LOAD ADDED (PANEL L3C-B5) 63.0 KVA

** NEW LOAD ADDED (PANEL L3C-A6) 51.8 KVA

TOTAL LOAD 190.4 KVA

( 229 AMPS)

* EXISTING LOAD TAKEN FROM THE "CONNECTED LOAD"

INDICATED ON THE ORIGINAL CONTRUCTION DOCUMENTS.

** NEW LOAD IS ANTICIPATED FOR FINAL BUILDOUT OF LAB

SPACE UNDER FUTURE PHASE OF WORK.

FEEDERS FROM SPOT NETWORK

DISTRIBUTION BOARD

(WING 3/SPINE)

SES-H3PDU-A (WING 3/SPINE)

ELECTRICAL ROOM #3351

1,600AMPS 277/480V., 3PH, 4W, NEMA 1

65,000 SCIR MIN

600/3

DB3-1A - 600A NORMAL BUS WING 3

DB3-2A - 600A

NORMAL BUS SPINE

DB3-1B - 600A NORMAL BUS WING 3

400/3 225/3

1,600AMP

800/3

SPARE

ST GFP

H3SB-A1

400A

MCB

SES-H3PDU-B (WING 3/SPINE)

ELECTRICAL ROOM #3351

1,600AMPS 277/480V., 3PH, 4W, NEMA 1

65,000 SCIR MIN

1,600AMP

STGFP800/3

H3LS-A1

225A

MLO

45KVA

225/3

H3EQ-B1

225A

MLO

L3LS-A1

150A

MCB

M M

75KVA

K-RATED

L3SB-B1

225A

MCB

600/3

H3SB-B1

600A

MCB

ST

GFP

ST

GFP

ST

GFP

60/3

TVSS

60/3

TVSS

SPARE

N N

G G

GROUNDED

CONDUCTOR

GROUNDED

CONDUCTOR

225/3

SPARE

SPARE

225/3600/3600/3

100/3AMP

75KVA

K-RATED

L3C-A1 225A

MCB

X

100/3AMP

75KVA

K-RATED

L3C-A2 225A

MCB

X

100/3AMP

75KVA

K-RATED

L3C-B2 225A

MCB

X

100/3AMP

75KVA

K-RATED

L3C-B3 225A

MCB

X

100/3AMP

75KVA

K-RATED

L3C-B4 225A

MCB

X

75KVA

K-RATED

L3C-B1 225A

MCB

110/3

T3C-A1

T3C-B2

T3SB-B1

T3C-B3

T3C-B4

T3LS-A1

T3C-A2

ST

GFP

600/3

T3C-B5

FUTURE

STANDBY BUSWAY

CT

125/3AMP

75KVA

K-RATED

FUTURE

SPINE

225A

MCB

X

T3C-X

H3-L1 225A

MCB

LIGHTING

75KVA

L3-B2 225A

MCB

110/3

T3-B1

600/3AMP

H3SB-A2

400A

MLO

X

5341A

X

5341A X31281A

X

5133A

51035A

X

X 51035A

X

51035A

3385A 3385A 3385A 3329A 3329A

3329A

X X

49844A

X

41866A

X

49844A

X

31281A

X

4185A

H3SB-B2

600A

MLO

51035A

X

FTL

60527A

X

70/3

EWH-1

WATER

HEATER

X

125/3

200/3AMP

J

3840A

X

(FUTURE)

FUTURE

STANDBY BUSWAY

51035A

60527A

TYP TYP

EQUIPMENT GROUND FAULT

PROTECTION

SHUNT-TRIP CIRCUIT INTERRUPTERST

GFP

ONE-LINE SYMBOLS

VFD

MOTOR I.D.; I.E., RAF-A-2, 30HP

VARIABLE FREQUENCY DRIVE

CT ELECTRICAL BUS CENTER TAP

M ELECTRICAL METER

FAULT CURRECT NOTE:

FAULT CURRENT VALUES FOR THIS PROJECT HAVE BEEN OBTAINED

BY USING SKM SYSTEMS ANALYSIS, INC. SOFTWEAR.

PRELIMINARY COORDINATION STUDY RESULTS (PROVIDE FINAL STUDY

WITH EQUIPTMENT INSTALLED):

• PLUG IN CIRCUIT BREAKERS FOR THE 600A BUSDUCT SHALL HAVE FIELD-ADJUSTABLE

TIME CURRENT CHARACTERISTICS.

• MAIN CIRCUIT BREAKERS AND FEEDER CIRCUIT BREAKERS 100A AND LARGER SHALL HAVE

FIELD-ADJUSTABLE TIME CURRENT CHARACTERISTICS (LSI TYPE BREAKERS).

SELECTIVE COORDINATION NOTE:

THE ELECTRICAL CONTRACTOR SHALL SUBMIT A COORDINATION STUDY PROVIDED BY SELECTED

EQUIPMENT MANUFACTURER IN COMPLIANCE WITH NEC ARTICLES 620.62, 700.27, AND 701.18 FOR SLECTIVE COORDINATION OF ELEVATORS, EMERGENCY SYTEMS AND LEGALLY REQUIRED STANDBY SYSTEMS. THIS REPORT SHALL BE SUBMITTED, REVIEWED AND APPROVED BY THE ENGINEER OF RECORD PRIOR TO THE ORDER OF EQUIPMENT, PURCHASE AND INSTALL. REFER TO SPECIFICAITON

SECTION 26 05 73 FOR ADDITONAL INFORMATION.

(FUTURE)

(FUTURE)

(FUTURE)

H3C-B1 600A

MLO

PROVIDE CONNECTION TO AVAILABLE "SPARE"

CIRCUIT BREAKER. SET CIRCUIT BREAKER TRIP

AT 600-AMPS.

2[4#350, 1#1G, 3"C.]

100/3AMP

75KVA

K-RATED

L3C-B6 225A

MCB

T3C-B6

100/3AMP

75KVA

K-RATED

L3C-A3 225A

MCB

T3C-A3

100/3AMP

75KVA

K-RATED

L3C-A4 225A

MCB

T3C-A4

100/3AMP

75KVA

K-RATED

L3C-B5 225A

MCB

T3C-B5T3C-B7

3#1, 1#6G, 1-1/2"C.

(TYPICAL)

4#250, 1#2G, 1#2IG, 2-1/2"C.

(TYPICAL)

1#2, 3/4"C.

(TYPICAL)

AREA OF WORK AREA OF WORK AREA OF WORK

FUSED FUSED

FUSED

FUSED

4#250, 1#2G, 1#2IG, 2-1/2"C.

(TYPICAL)

3#1, 1#6G, 1-1/2"C.

(TYPICAL)

1#2, 3/4"C.

(TYPICAL)

X

3329A

X

3329A

X

3329A

X

3329A

X51035A

PROVIDE PANELBOARD WITH

ISOLATED GROUND (IG) BUS,

SPD AND POWER MONITOR

PROVIDE PANELBOARD WITH

ISOLATED GROUND (IG) BUS,

SPD AND POWER MONITOR

PROVIDE PANELBOARD WITH

SPD AND POWER MONITOR

ONE-LINE DIAGRAM NOTES:

1.

2.

3.

PANELBOARDS INDICATED ON ONE LINE DIAGRAMS DO NOT SHOW ALL

BRANCH CIRCUITS. REFER TO PANELBOARD SCHEDULE(S).

NEW WORK REQUIRED BY THE CONTRACTOR IS INDICATED BY THE SCOPE

OF WORK BOXES.

NEW PANELBOARDS SHALL BE PROVIDE WITH POWER MONITORS (SIEMENS

#SENTRON PAC3200) AND INTEGRAL SURGE PROTECTIVE DEVICES TO

MATCH EXISTING INSTALLED EQUIPMENT. PROVIDE LOW VOLTAGE

CONNECTION FROM THE POWER MONITORS TO THE EXISTING POWER

MONITORING EQUIPMENT LOCATED IN THE MAIN ELECTRIC ROOM. FIELD

VERIFY EXACT REQUIREMENTS.

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n J H a fe r.

rv t

/3

/2

:3 :5

P

M

ELECTRICAL

ONE-LINE DIAGRAM

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

E0.2.0

201009.006

JAH

JAH

03/30/16

B ro a d w a y

B o u ld e r, C O

SCALE: 1" = 1'-0"

ELECTRICAL ONE-LINE DIAGRAM

PANELEXISTING " H3SB-B1 "

Panel Notes:

600 A MAIN CIRCUIT BREAKER VOLTAGE 277 / 480 V 1. NEW LOAD ON EXISTING CIRCUIT BREAKER. 7. PROVIDE GFCI CIRCUIT BREAKER.

600 A BUS PHASE 3 PH 2. PROVIDE CIRCUIT BREAKER IN SPACE TO MATCH EXISTING. 8. PROVIDE SHUNT-TRIP CIRCUIT BREAKER.

WIRE 4 W 3. REPLACE EXISTING CIRCUIT BREAKER WITH NEW CIRCUIT BREAKER.

MFR : 4. EXISTING LOAD ON NEW CIRCUIT BREAKER. LOAD IS ESTIMATED.

MTG. : SURFACE 65,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 5. EXISTING LOAD REMOVED.

6. PROVIDE 30mA GROUND FAULT CIRCUIT BREAKER.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

VFD/CWP-3-1 2,922 2922 20 / 1 A 2 20 / 2922 2,922 VFD/CWP-3-2

" 2,922 2922 / 3 B 4 / 2922 2,922 "

" 2,922 2922 / 3 5 C 6 / 3 2922 2,922 "

DDC-1 167 167 20 / 7 A 8 20 / 167 167 DDC-2

" 167 167 / 9 B 10 / 167 167 "

" 167 167 / 3 11 C 12 / 3 167 167 "

DDC-3 167 167 20 / 13 A 14 20 / 167 167 DDC-4

" 167 167 / 15 B 16 / 167 167 "

" 167 167 / 3 17 C 18 / 3 167 167 "

FUTURE CONTROL 167 167 20 / 19 A 20 20 / 167 167 FUTURE CONTROL

PANEL 1 167 167 / 21 B 22 / 167 167 PANEL 2

" 167 167 / 3 23 C 24 / 3 167 167 "

FC-3353B MECH 3353 665 665 20 / 1 25 A 26 20 / 2922 2,922 VFD/CHWP-3-2

SPACE 0 / 27 B 28 / 2922 2,922 "

SPACE 0 / 29 C 30 / 3 2922 2,922 "

VFD/CHWP-3-3 2,922 2922 20 / 31 A 32 40 / 5577 5,577 VFD/PCHWP-1 2

" 2,922 2922 / 33 B 34 / 5577 5,577 (MECH 3353B)

" 2,922 2922 / 3 35 C 36 / 3 5577 5,577 "

3 VFD/PCHWP-2 5,577 5577 40 / 37 A 38 / 6306 6,306 PANEL H3SB-B2

(MECH 3353B) 5,577 5577 / 39 B 40 / 6064 6,064 (VIA FEED THRU

" 5,577 5577 / 3 41 C 42 / 5944 5,944 LUGS)

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 29,813.0 28,906.0 28,786.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 90%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 1,002.0 1,002.0 1,002.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 30,815.0 29,908.0 29,788.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 108.9

NEC CALCULATED LARGEST 16.7 KVA x 125% = 20.9 KVA x 90% = 18.8 KW

PHASE AMPACITY 116.7 113.3 112.7 REMAINDER 70.8 KVA x 100% = 70.8 KVA x 90% = 63.7 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

600.0 GENERAL 3.0 KVA x 100% = 3.0 KVA x 100% = 3.0 KW 113.9

PHASE BALANCE A-B B-C C-A

3% 0% 3% TOTAL 90.5 KVA 94.7 KVA 85.5 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

PANELNEW " H3C-B1 " SERVES LAB #3317

Panel Notes:

600 A M.L.O. VOLTAGE 277 / 480 V 1. PANELBOARD SCHEDULE SHOWN FOR REQUIRED RATINGS, CIRCUIT BREAKER SIZES

600 A BUS PHASE 3 PH AND CIRCUIT BREAKER QUANTITIES ONLY.

WIRE 4 W 2. LOAD IS ESTIMATED.

MFR : 3. PROVIDE PANELBOARD WITH INTEGRAL SURGE PROTECTIVE DEVICE

MTG. : SURFACE 65,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 4. PROVIDE POWER MONITOR (SIEMENS #SENTROL PAC 3200) TO MATCH EXISTING POWER MONITORING DEVICES.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

2 LAB 3317 EQUIP 20,000 20000 100 / 1 A 2 100 / 20000 20,000 LAB 3317 EQUIP 2

" 20,000 20000 / 3 B 4 / 20000 20,000 "

" 20,000 20000 / 3 5 C 6 / 3 20000 20,000 "

2 LAB 3317 EQUIP 9,500 9500 50 / 7 A 8 50 / 9500 9,500 LAB 3317 EQUIP 2

" 9,500 9500 / 9 B 10 / 9500 9,500 "

" 9,500 9500 / 3 11 C 12 / 3 9500 9,500 "

2 LAB 3317 EQUIP 9,500 9500 50 / 13 A 14 50 / 9500 9,500 LAB 3317 EQUIP 2

" 9,500 9500 / 15 B 16 / 9500 9,500 "

" 9,500 9500 / 3 17 C 18 / 3 9500 9,500 "

SPACE 0 / 19 A 20 / 0 SPACE

SPACE 0 / 21 B 22 / 0 SPACE

SPACE 0 / 23 C 24 / 0 SPACE

SPACE 0 / 25 A 26 / 0 SPACE

SPACE 0 / 27 B 28 / 0 SPACE

SPACE 0 / 29 C 30 / 0 SPACE

SPACE 0 / 31 A 32 / 0 SPACE

SPACE 0 / 33 B 34 / 0 SPACE

SPACE 0 / 35 C 36 / 0 SPACE

SPACE 0 / 37 A 38 / 0 SPACE

SPACE 0 / 39 B 40 / 0 SPACE

SPACE 0 / 41 C 42 / 0 SPACE

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 0.0 0.0 0.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 100%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 78,000.0 78,000.0 78,000.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 78,000.0 78,000.0 78,000.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 281.5

NEC CALCULATED LARGEST 0.0 KVA x 125% = 0.0 KVA x 90% = 0.0 KW

PHASE AMPACITY 281.1 281.1 281.1 REMAINDER 0.0 KVA x 100% = 0.0 KVA x 90% = 0.0 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

600.0 GENERAL 234.0 KVA x 100% = 234.0 KVA x 100% = 234.0 KW 281.5

PHASE BALANCE A-B B-C C-A

0% 0% 0% TOTAL 234.0 KVA 234.0 KVA 234.0 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

PANELNEW " L3C-A3 " SERVES LAB #3317

Panel Notes:

225 A MAIN CIRCUIT BREAKER VOLTAGE 120 / 208 V 1. PANELBOARD SCHEDULE SHOWN FOR REQUIRED RATINGS, CIRCUIT BREAKER SIZES

225 A BUS PHASE 3 PH AND CIRCUIT BREAKER QUANTITIES ONLY.

WIRE 4 W 2. LOAD IS ESTIMATED.

MFR : 3. PROVIDE PANELBOARD WITH INTEGRAL SURGE PROTECTIVE DEVICE

MTG. : SURFACE 10,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 4. PROVIDE POWER MONITOR (SIEMENS #SENTROL PAC 3200) TO MATCH EXISTING POWER MONITORING DEVICES.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

2 LAB 3317 EQUIP 2,878 2878 30 / 1 A 2 30 / 2878 2,878 LAB 3317 EQUIP 2

" 2,878 2878 / 3 B 4 / 2878 2,878 "

" 2,878 2878 / 3 5 C 6 / 3 2878 2,878 "

2 LAB 3317 EQUIP 2,878 2878 30 / 7 A 8 30 / 2878 2,878 LAB 3317 EQUIP 2

" 2,878 2878 / 9 B 10 / 2878 2,878 "

" 2,878 2878 / 3 11 C 12 / 3 2878 2,878 "

SPACE 0 / 13 A 14 / 0 SPACE

SPACE 0 / 15 B 16 / 0 SPACE

SPACE 0 / 17 C 18 / 0 SPACE

SPACE 0 / 19 A 20 / 0 SPACE

SPACE 0 / 21 B 22 / 0 SPACE

SPACE 0 / 23 C 24 / 0 SPACE

SPACE 0 / 25 A 26 / 0 SPACE

SPACE 0 / 27 B 28 / 0 SPACE

SPACE 0 / 29 C 30 / 0 SPACE

SPACE 0 / 31 A 32 / 0 SPACE

SPACE 0 / 33 B 34 / 0 SPACE

SPACE 0 / 35 C 36 / 0 SPACE

SPACE 0 / 37 A 38 / 0 SPACE

SPACE 0 / 39 B 40 / 0 SPACE

SPACE 0 / 41 C 42 / 0 SPACE

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 0.0 0.0 0.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 100%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 11,512.0 11,512.0 11,512.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 11,512.0 11,512.0 11,512.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 95.9

NEC CALCULATED LARGEST 0.0 KVA x 125% = 0.0 KVA x 90% = 0.0 KW

PHASE AMPACITY 95.7 95.7 95.7 REMAINDER 0.0 KVA x 100% = 0.0 KVA x 90% = 0.0 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

225.0 GENERAL 34.5 KVA x 100% = 34.5 KVA x 100% = 34.5 KW 95.9

PHASE BALANCE A-B B-C C-A

0% 0% 0% TOTAL 34.5 KVA 34.5 KVA 34.5 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

PANELNEW " L3C-A4 " SERVES LAB #3321/3325

Panel Notes:

225 A MAIN CIRCUIT BREAKER VOLTAGE 120 / 208 V 1. PANELBOARD SCHEDULE SHOWN FOR REQUIRED RATINGS, CIRCUIT BREAKER SIZES

225 A BUS PHASE 3 PH AND CIRCUIT BREAKER QUANTITIES ONLY.

WIRE 4 W 2. LOAD IS ESTIMATED.

MFR : 3. PROVIDE PANELBOARD WITH INTEGRAL SURGE PROTECTIVE DEVICE

MTG. : SURFACE 10,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 4. PROVIDE POWER MONITOR (SIEMENS #SENTROL PAC 3200) TO MATCH EXISTING POWER MONITORING DEVICES.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

LAB 3325 EQUIP 2,878 2878 50 / 1 A 2 50 / 2878 2,878 LAB 3325 EQUIP

" 2,878 2878 / 3 B 4 / 2878 2,878 "

" 2,878 2878 / 3 5 C 6 / 3 2878 2,878 "

LAB 3325 EQUIP 2,878 2878 30 / 7 A 8 30 / 2878 2,878 LAB 3325 EQUIP

" 2,878 2878 / 9 B 10 / 2878 2,878 "

" 2,878 2878 / 3 11 C 12 / 3 2878 2,878 "

LAB 3321 EQUIP 2,878 2878 30 / 13 A 14 30 / 2878 2,878 LAB 3321 EQUIP

" 2,878 2878 / 15 B 16 / 2878 2,878 "

" 2,878 2878 / 3 17 C 18 / 3 2878 2,878 "

SPACE 0 / 19 A 20 / 0 SPACE

SPACE 0 / 21 B 22 / 0 SPACE

SPACE 0 / 23 C 24 / 0 SPACE

SPACE 0 / 25 A 26 / 0 SPACE

SPACE 0 / 27 B 28 / 0 SPACE

SPACE 0 / 29 C 30 / 0 SPACE

SPACE 0 / 31 A 32 / 0 SPACE

SPACE 0 / 33 B 34 / 0 SPACE

SPACE 0 / 35 C 36 / 0 SPACE

SPACE 0 / 37 A 38 / 0 SPACE

SPACE 0 / 39 B 40 / 0 SPACE

SPACE 0 / 41 C 42 / 0 SPACE

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 0.0 0.0 0.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 100%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 17,268.0 17,268.0 17,268.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 17,268.0 17,268.0 17,268.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 143.8

NEC CALCULATED LARGEST 0.0 KVA x 125% = 0.0 KVA x 90% = 0.0 KW

PHASE AMPACITY 143.6 143.6 143.6 REMAINDER 0.0 KVA x 100% = 0.0 KVA x 90% = 0.0 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

225.0 GENERAL 51.8 KVA x 100% = 51.8 KVA x 100% = 51.8 KW 143.8

PHASE BALANCE A-B B-C C-A

0% 0% 0% TOTAL 51.8 KVA 51.8 KVA 51.8 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

PANELNEW " L3C-B5 " SERVES LAB #3337

Panel Notes:

225 A MAIN CIRCUIT BREAKER VOLTAGE 120 / 208 V 1. PANELBOARD SCHEDULE SHOWN FOR REQUIRED RATINGS, CIRCUIT BREAKER SIZES

225 A BUS PHASE 3 PH AND CIRCUIT BREAKER QUANTITIES ONLY.

WIRE 4 W 2. LOAD IS ESTIMATED.

MFR : 3. PROVIDE PANELBOARD WITH INTEGRAL SURGE PROTECTIVE DEVICE

MTG. : SURFACE 10,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 4. PROVIDE POWER MONITOR (SIEMENS #SENTROL PAC 3200) TO MATCH EXISTING POWER MONITORING DEVICES.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

LAB 3337 EQUIP 1,500 1500 20 / 1 1 A 2 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 3 B 4 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 5 C 6 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 7 A 8 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 9 B 10 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 11 C 12 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 13 A 14 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 15 B 16 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 17 C 18 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 19 A 20 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 1,500 1500 20 / 1 21 B 22 20 / 1 1500 1,500 LAB 3337 EQUIP

LAB 3337 EQUIP 2,500 2500 30 / 23 C 24 30 / 2500 2,500 LAB 3337 EQUIP

" 2,500 2500 / 2 25 A 26 / 2 2500 2,500 "

LAB 3337 EQUIP 2,500 2500 30 / 27 B 28 30 / 2500 2,500 LAB 3337 EQUIP

" 2,500 2500 / 2 29 C 30 / 2 2500 2,500 "

LAB 3337 EQUIP 2,500 2500 30 / 31 A 32 30 / 2500 2,500 LAB 3337 EQUIP

" 2,500 2500 / 2 33 B 34 / 2 2500 2,500 "

SPACE 0 / 35 C 36 / 0 SPACE

SPACE 0 / 37 A 38 / 0 SPACE

SPACE 0 / 39 B 40 / 0 SPACE

SPACE 0 / 41 C 42 / 0 SPACE

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 0.0 0.0 0.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 100%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 22,000.0 22,000.0 19,000.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 22,000.0 22,000.0 19,000.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 174.9

NEC CALCULATED LARGEST 0.0 KVA x 125% = 0.0 KVA x 90% = 0.0 KW

PHASE AMPACITY 183.0 183.0 158.0 REMAINDER 0.0 KVA x 100% = 0.0 KVA x 90% = 0.0 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

225.0 GENERAL 63.0 KVA x 100% = 63.0 KVA x 100% = 63.0 KW 174.9

PHASE BALANCE A-B B-C C-A

0% 16% 16% TOTAL 63.0 KVA 63.0 KVA 63.0 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

PANELNEW " L3C-B6 " SERVES LAB #3341/3349

Panel Notes:

225 A MAIN CIRCUIT BREAKER VOLTAGE 120 / 208 V 1. PANELBOARD SCHEDULE SHOWN FOR REQUIRED RATINGS, CIRCUIT BREAKER SIZES

225 A BUS PHASE 3 PH AND CIRCUIT BREAKER QUANTITIES ONLY.

WIRE 4 W 2. LOAD IS ESTIMATED.

MFR : 3. PROVIDE PANELBOARD WITH INTEGRAL SURGE PROTECTIVE DEVICE

MTG. : SURFACE 10,000 AMPERE SHORT CIRCUIT RATING (FULLY RATED) 4. PROVIDE POWER MONITOR (SIEMENS #SENTROL PAC 3200) TO MATCH EXISTING POWER MONITORING DEVICES.

BREAKER BREAKER

NOTE DESCRIPTION LTG RECEPT MOTORS OTHER GENERAL TOTAL AMP / P CCT PH CCT AMP / P TOTAL GENERAL OTHER MOTORS RECEPT LTG DESCRIPTION NOTE

LAB 3341 EQUIP 2,878 2878 30 / 1 A 2 30 / 2878 2,878 LAB 3341 EQUIP

" 2,878 2878 / 3 B 4 / 2878 2,878 "

" 2,878 2878 / 3 5 C 6 / 3 2878 2,878 "

LAB 3341 EQUIP 2,878 2878 30 / 7 A 8 30 / 2878 2,878 LAB 3341 EQUIP

" 2,878 2878 / 9 B 10 / 2878 2,878 "

" 2,878 2878 / 3 11 C 12 / 3 2878 2,878 "

LAB 3349 EQUIP 2,878 2878 30 / 13 A 14 30 / 2878 2,878 LAB 3349 EQUIP

" 2,878 2878 / 15 B 16 / 2878 2,878 "

" 2,878 2878 / 3 17 C 18 / 3 2878 2,878 "

SPACE 0 / 19 A 20 / 0 SPACE

SPACE 0 / 21 B 22 / 0 SPACE

SPACE 0 / 23 C 24 / 0 SPACE

SPACE 0 / 25 A 26 / 0 SPACE

SPACE 0 / 27 B 28 / 0 SPACE

SPACE 0 / 29 C 30 / 0 SPACE

SPACE 0 / 31 A 32 / 0 SPACE

SPACE 0 / 33 B 34 / 0 SPACE

SPACE 0 / 35 C 36 / 0 SPACE

SPACE 0 / 37 A 38 / 0 SPACE

SPACE 0 / 39 B 40 / 0 SPACE

SPACE 0 / 41 C 42 / 0 SPACE

PHASE LOADING SUMMARY PANEL LOADING SUMMARY

LOAD TYPE (VA) PH A PH B PH C LOAD TYPE CONNECTED NEC CALCULATED POWER DEMAND

LIGHTING 0.0 0.0 0.0 LOAD KVA DEMAND LOAD FACTOR LOAD KW PANEL

RECEPTACLES 0.0 0.0 0.0 CONNECTED PF=

MOTORS 0.0 0.0 0.0 LIGHTING 0.0 KVA x 125% = 0.0 KVA x 95% = 0.0 KW 100%

OTHER 0.0 0.0 0.0 RECEPTACLES

GENERAL 17,268.0 17,268.0 17,268.0 FIRST 10 KVA 0.0 KVA x 100% = 0.0 KVA x 100% = 0.0 KW CONNECTED

TOTAL (VA) 17,268.0 17,268.0 17,268.0 REMAINDER 0.0 KVA x 50% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

MOTORS 143.8

NEC CALCULATED LARGEST 0.0 KVA x 125% = 0.0 KVA x 90% = 0.0 KW

PHASE AMPACITY 143.6 143.6 143.6 REMAINDER 0.0 KVA x 100% = 0.0 KVA x 90% = 0.0 KW NEC DEMAND

OTHER 0.0 KVA x 125% = 0.0 KVA x 100% = 0.0 KW AMPACITY =

225.0 GENERAL 51.8 KVA x 100% = 51.8 KVA x 100% = 51.8 KW 143.8

PHASE BALANCE A-B B-C C-A

0% 0% 0% TOTAL 51.8 KVA 51.8 KVA 51.8 KW

GENERAL NOTES:

' PROVIDE NEW UPDATED PANEL DIRECTORIES FOR PANELS THAT ARE INCLUDED IN THIS PROJECT.

' PROVIDE TYPED DESCRIPTIONS OF NEW CIRCUITS BEING INSTALLED. INDICATE NEW SPARES IN PENCIL.

ISSUE / REVISION:

PROJECT NUMBER

DATE

DRAWN BY

CHECKED BY

NO. DESCRIPTION DATE

475 17th Street, Suite 720 Denver, Colorado 80202 Phone: 720-855-7572 www.iron-horse-architects.com

This document is an instrument of services and as such, remains the property of the Architect.

The use of this document is limited and can be extended only by written agreement with IRON

HORSE ARCHITECTS, INC.

COPYRIGHT 2015 ©

D R e v it L o c a l F ile s \2

\M

E P

-N

IS

T W in g

C u s to m iz a ti o n J H a fe r.

rv t

/3

/2

:3 :5

P

M

ELECTRICAL

PANELBOARD

SCHEDULES

W

IN

G

R E

-C U

S T

O M

IZ

A

T

IO

N

E0.2.1

201009.006

JAH

JAH

03/30/16

B ro a d w a y

B o u ld e r, C O

T TT

FBX

F

P P P P

J

T

TT

P

P P

P P

P P P

J

J

J J

J

J

J J

J

J

J

J

J J

J J

J J

J J

J

J J

J J

J

J

J

J

J

J

J

J

J J J

J

J

JJ

J

J

J

J

P P

F F

J

J J

J JJJ

J J

J

T75 T75

DN

T T T

FBX

J

J

P P

J

PP P P

P

P

PP P

P

J

J J

J

J J

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J J

J J

J

J

J

J

J

J J

J

JJ J

J

J

J

J

J

J

J

J

J J J

J

J

F

JJJJ

J

F

J J

J

J

J

J

T

J

T75 T75

M

M

H3LS-A1

H3EQ-B1

H3SB-A2

H3SB-B1

H3SB-A1

L3C-B1

L3LS-A1

L3SB-B1

L3C-A2 L3C-A1

L3-B2

L3C-B1- 41

L3-B2- 3 L3-B2- 3

L3-B2- 3

L3C-B1- 42 L3-B2- 5

L3-B2- 5

L3C-B1- 41

L3-B2- 5

L3-B2- 5

L3-B2- 5

L3-B2- 6

L3-B2- 6

L3-B2- 5

L3C-B1- 39

L3C-B1- 40

L3-B2- 6

L3-B2- 6

L3-B2- 6 L3-B2- 7

L3-B2- 7

L3C-B1- 37 L3C-B1- 37

L3C-B1- 35L3C-B1- 35

L3C-B1- 38 L3C-B1- 38

L3-B2- 7

L3-B2- 7

L3-B2- 8

L3-B2- 7

L3-B2- 7

L3-B2- 8

L3-B2- 8

L3-B2- 8

L3C-B1- 33

L3C-B1- 33

L3C-B1- 31

L3C-B1- 27

L3C-B1- 29

L3C-B1- 36

L3C-B1- 3L3C-B1- 3

L3C-B1- 16 L3C-B1- 16

L3C-B1- 2

L3-B2- 32L3-B2- 30L3-B2- 30

L3-B2- 12 L3-B2- 12

L3-B2- 12

L3-B2- 18 L3-B2- 18

L3-B2- 20

L3-B2- 20

L3-B2- 20

L3-B2- 18

L3-B2- 26

L3-B2- 30

L3-B2- 22

L3-B2- 22

L3-B2- 29L3-B2- 29L3-B2- 29

L3C-B1- 12 L3C-B1- 12

L3C-B1- 11

L3C-B1- 7

L3C-B1- 7

L3C-B1- 7

L3C-A2- 31…