S02 DRAWINGS - ARCHITECTUAL.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24221B0061_1
About this file
This federal solicitation requests proposals for the installation of a new 1000 kW diesel generator, Tier 4 emissions compliant, in a weatherproof housing with associated electrical equipment at a Department of Veterans Affairs medical center. Key requirements include a 96-hour run time dual fuel tank, remote monitoring panels located in an existing vault and tied to the facility's building management system, and load capabilities to serve future needs. The generator must meet EPA Tier 4 engine standards. Additional scope components comprise improvements to an adjacent switchgear building including a new roof and conduit routing, as well as lead paint abatement, structural work for a generator pad and exhaust system, and temporary power provisions. The solicitation is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. A site visit is scheduled and submittals must allow for timely equipment procurement to minimize downtime given the critical nature of the work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24221B0061 0002.docx | DOCX document | |
| 36C24221B0061 0001.docx | DOCX document | |
| COVID-19 FORM.pdf | ||
| COVID-19 DIRECTIVE.pdf | ||
| RFI ANSWERS.xlsx | XLSX spreadsheet | |
| COVID-19 POLICY.pdf | ||
| S02 DRAWINGS - CIVIL.pdf | ||
| S02 VA ID PACKAGE 06-18-2019.pdf | ||
| S02 DRAWINGS - GENERAL.pdf | ||
| 36C24221B0061_1.docx | DOCX document | |
| S02 SPECS - FINAL.pdf | ||
| S02 Safety or Environmental Violations and Experience Modification Rate.pdf | ||
| S02 Participation Goals for Minorities and Females.pdf | ||
| S02 ALL POSTERS.pdf | ||
| S02 DRAWINGS - ELECTRICAL.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CR CARD READER
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA, Ø DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
LVT LUXURY VINYL TILE
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PP PUSH PAD
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SJ SEAL JOINT
SJS SEAL JOINT @ SLOPE EDGE
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
DEMOLITION KEYNOTE
DOOR NUMBER
TYPICAL KEYNOTE
1-
# FIRE EXTINGUISHER
CABINETFEC
ROOF SLOPE
DIRECTION OF SPAN
1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT GENERAL WORK AND DO NOT PORTRAY FULL SCOPE OF THE PROJECT. SEE
SPECIFICATIONS FOR DETAILED REQUIREMENTS.
2. REMOVE EXISTING CONSTRUCTION AS DESIGNATED HEREIN AND CLEAR AREA OF DEBRIS PRIOR TO PROCEEDING WITH NEW CONSTRUCTION.
3. EXISTING EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OFF MEDICAL CENTER GROUNDS. COORDINATE WITH VA COR.
4. PATCHED WALL OPENING SHALL MATCH THE INTEGRITY OF ADJACENT CONSTRUCTION UNLESS INDICATED OTHERWISE.
5. COORDINATE WORKING HOURS ALLOWED FOR DEMOLITION AND WASTE REMOVAL WITH VA COR.
6. CONTRACTOR PROTECT AREA ADJACENT TO THE DEMOTION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES, (IF DAMAGED REPAIR, PATCH AND REFINISH TO MATCH EXISTING.) REPAIR OR REPLACE ITEMS DAMAGED DURING CONSTRUCTION ACTIVITIES AT NO ADDITIONAL COST.
7. THE INFORMATION CONTAINED IN THE CONSTRUCTION DOCUMENTS DEFINES GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING ALL DEMOLITION REQUIRED FOR THE COMPLETION OF THE PROJECT.
8. DO NOT ENCROACH ON ADJACENT OCCUPIED AREAS NOT INDENTIFIED WITHIN THE SCOPE OF WORK.
9. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION REGARDING DEMOLITION OF ELECTRICAL SYSTEMS.
10. BEFORE THE START OF WORK, IDENTIFY ANY REQUIRED DEMOLITION BEYOND THE IDENTIFIED PROJECT SCOPE WHETHER ABOVE, BELOW OR OUTSIDE PROJECT AREA. NOTIFY AND COORDINATE WITH THE COR, PROVIDE DEMOLITION OF THESE AREAS AND PATCH THE SAME AS A PART OF THE SCOPE OF THE PROJECT.
11. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND DILIGENCE IN ORDER TO PREVENT ARBITRARY DAMAGE OR INTERRUPTION OF SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE. DISCOVERY OF UTILITIES OR CONDITIONS LOCATED DIFFERENTLY FROM THAT INDICATED OR THAT ARE
NOT IDENTIFIED. SHALL BE REPORTED TO THE CONTRACTING OFFICER.
12. AFTER REMOVAL OF EXISTING CMU CURB WALL, FILL FLOOR VOIDS UP TO FINISH CONCRETE LEVEL AND PERFORM FLOOR LEVELING FOR ENTIRE AREA OF
RENOVATION.
13. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY VA COR AND ARCHITECT OF ANY CONFLICTS PRIOR TO PROCEEDING WITH DEMOLITION.
14. ALL ITEMS BEING REMOVED SHALL REMAIN THE PROPERTY OF THE VA MEDICAL CENTER UNTIL CONFIRMATION HAS BEEN MADE BY THE VA COR AS TO WHETHER THE VA WILL RETAIN SUCH ITEMS. ALL ITEMS NOT BEING RETAINED BY THE VA COR OR DESIGNATED ON THE DRAWINGS TO BE RELOCATED OR REMOVED FROM
THE SITE BY CONTRACTOR.
15. VA SHALL HAVE FIRST OPPORTUNITY FOR SALVAGE. ALL ITEMS NOTE SALVAGED BY THE VA TO BE REMOVED AND DISPOSED OF BY THE CONTRACTOR IN
APPROVED MANNER.
16. CONTRACTOR SHOULD NOTIFY VA COR OF ANY AREA REQUIRING DEMOLITION OTHER THAN SHOWN IN THESE DRAWINGS DUE TO UNFORSEEN CONDITIONS TO ACCOMMODATE INSTALLATION OF MECHANICAL, PLUMBING, STRUCTURAL, ELECTRICAL, OR DATA ITEMS (INCLUDING ROOF PENETRATIONS). AFTER SUCH DEMOLITION AND INSTALLATION, PATCH OR REPLACE MATERIALS AND FINISHES TO MATCH EXISTING.
17. COORDINATE WITH VA COR FOR CONSTRUCTION ACCESS ROUTE AND LOCATION OF DUMPSTER. COORDINATE WITH COR FOR SCHEDULE OF USE OF ACCESS
ROUTE FOR WASTE REMOVAL.
1. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE DESIGNER AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND CONTRACTOR
BEFORE THE START OF THE WORK.
2. DRAWINGS ARE PREPARED USING DIMENSIONS AND PRODUCT DRAWINGS FOR SPECIFIC PRODUCTS. DETAILS FOR SPECIFIC PRODUCTS MAY CHANGE BEFORE THEY ARE ACTUALLY INCORPORATED INTO THE WORK, AND PRODUCTS BY OTHER MANUFACTURERS ARE ALSO ACCEPTABLE. THEREFORE, ACTUAL INSTALLATION DETAILS AND DIMENSIONS MAY DIFFER FROM THOSE SHOWN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE INCORPORATED IN THE WORK (INCLUDING THICKNESS FOR RECESSED OR SEMI-RECESSED PRODUCT(S) AND IS RESPONSIBLE FOR ACCOMMODATING AND COORDINATING CHANGES TO
OTHER MATERIALS OR PRODUCTS THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
3. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT THE WORK IS NOT TO BE CONSTRUCTED AS A
COMPLETE, INTEGRATED AND UNIFIED WHOLE.
4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR
SHALL PROVIDE THE BETTER QUALITY OR GREATER QUANTITY OF WORK.
5. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE DRAWINGS
AND SPECIFICATIONS.
6. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND ACTUAL FIELD CONDITIONS
NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL GOVERN.
8. PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN DIFFERENT MATERIALS.
9. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.
10. REFER TO ELECTRICAL AND CIVIL DRAWINGS FOR ADDITIONAL INFORMATION.
11. PROVIDE BLOCKING AT PARTITIONS AS REQUIRED FOR MOUNTING OF WALL-MOUNTED ITEMS.
12. COORDINATE THE WORK OF TRADES PRIOR TO THE START OF CONSTRUCTION.
13. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF WORK FOR EACH PHASE.
14. DIMENSIONS SHOWN ARE TO FACE OF STUD FRAMING, FACE OF CONCRETE/MASONRY WALLS, OR FINISHED FACE
OF EXISTING WALL SURFACE.
15. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED.
16. INSTALL ALL WORK IN ACCORDANCE WITH CURRENT APPLICABLE CODES AND PUBLISHED STANDARDS.
17. AT AREAS INDICATED TO BE PATCHED AND REPAIRED, FOR ADDTION AND RENOVATION PROJECTS. THE CONSTRUCTION AND ASSEMBLY OF THE PATCH OR REPAIR SHALL MATCH THE ASSEMBLY AND INTEGRITY OF THE ADJACENT EXISTING CONSTRUCTION, FOR FIRE RATING, MATERIALS, FINISH, THICKNESS, AND QUALITY.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects JULY 20, 2021
INSTALL GENERATOR FOR
BUILDINGS 85, 86 AND 87 (SA)
630A4-18-415
VA NEW YORK HARBOR HEALTHCARE
SYSTEM, ST. ALBANS CAMPUS
179-00 LINDEN BLVD,
JAMAICA, NY 1134-1468
19-227
BID DOCUMENTS
FULLY SPRINKLERED
20-1-SA
7/
/2
:0 2:
P
M
B85, B86, B87
A-001
DGC, NPMWVS
ARCHITECTURAL SYMBOLS,
ABBREVIATIONS AND NOTES
1 6
ABBREVIATIONS
ARCHITECTURAL SYMBOL LEGENDDEMOLITION NOTES GENERAL NOTES
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
101A
101B
101C
MECHANICAL
ROOM
ELECTRICAL
ROOM
101A
101B
101C
MECHANICAL
ROOM
8'- 0"
17'-6 1/2"
FV
2'-1"
2"
3'-5"
FV
FEC
A-101
FEC
DS DS
3'- 3 1
/2"
FV
5'-
2" FV
ELECTRICAL
ROOM
NEW TREATED CONTINUOUS
WOOD BLOCKING ANCHOR
TO EXTERIOR BRICK VENEER
2" TOP LAYER TAPERED
POLY ISO INSULATION
8"
FULLY ADHERED 60MIL
TPO MEMBRANE
1"
STANDARD DETAIL
AS PER MANUFACTURER'S
STANDARD DETAILS
NEW PREFABRICATED METAL
ROOF EDGE SYSTEM
EXISTING BRICK VENEER
EXISTING CMU MASONRY
EXISTING METAL DECK
EXISTING STEEL JOIST
12" 1/4"
(2) 1 1/2" LAYER OF POLY
ISO INSULATION
(2) 1 1/2" LAYER OF POLY
ISO INSULATION
6X6- W1.4X W1.4 WWF
WIRE TO #3 DOWELS
TYPICAL EQUIPMENT
ANCHORAGE - SEE
EQUIPMENT CUT
SHEETS
PROVIDE #3 DOWEL
BARS 24" O.C. EACH WAY.
EPOXY DOWELS INTO
EXISTING SLAB
NOTE: L & W DIMENSIONS SHALL BE 2" GREATER THAN THE EQUIPMENT MOUNTING LOCATIONS. SEE
ELECTRICAL DRAWINGS FOR EQUIPMENT INFORMATION.
CONCRETE TO PAINTED YELLOW. PRIMER, 1 EPOXY FINISH COAT ALL EXPOSE SURFACES.
EXISTING CONCRETE
SLAB
5" MI
N.
2"
1/4 " M
AX
2"
TAPERED TOP LAYER
(2) 1 1/2" FLAT LAYERS
1/2"
12" 1/4"
15'-0"
5'-
0" FV
1/4
10'-10 1/2"
FV
A-101
A-101
1/4
1/4
19'-4 1/2"
FV
2'-
'-2 1/
2"
FV
DSDS
1'-10" 3'-8" 1'-10"
NOTE: FLOOR TO BE FLUSH AND FLAT AFTER DEMO & PATCHING WORK COMPLETE
EXISTING CONCRETE SLAB
CUT ANY VERTICAL
REINFORCEMENT AND
GRIND FLUSH W/ FLOOR
REMOVE EXISTING CMU WALL
GROUT SMOOTH ALL
AREAS DISRUPTED BY
BLOCK DEMOLITION
NEW TREATED CONTINUOUS
WOOD BLOCKING ANCHOR
TO EXTERIOR BRICK VENEER
2" TOP LAYER TAPERED
POLY ISO INSULATION
FULLY ADHERED 60MIL
TPO MEMBRANE
EXISTING BRICK VENEER
EXISTING CMU MASONRY
EXISTING METAL DECK
EXISTING STEEL JOIST
12"
1/4"
NEW GUTTER TO BE INSTALLED
PER TPO MANUFACTURER'S
STANDARD ROOF EDGE TO
GUTTER DETAIL FOR WATER
TIGHTNESS
4"
ALL SHEET METAL ROOF EDGE
FABRICATIONS TO BE PAINTED
PER MANUFACTURER'S
STANDARD COLOR RANGE,
COLOR TO BE SELECTED BY VA
OR ARCHITECT
4"
NEW 3"X3" SQUARE
DOWNSPOUT BEYOND
(2) 1 1/2" LAYER OF POLY
ISO INSULATION
(2) 1 1/2" LAYER OF POLY
ISO INSULATION
1" 4'-
0"
FINISH FLOOR
FIRE EXTINGUISHER CABINET
CABINET TO HAVE 8X8X26
CLEAR SPACE
- SEE SPECFICATIONS
1. DEMOLISH EXISTING 2 COURSE HIGH 8" W CMU CURB. SEE
DETAIL 5/A1-01 THIS SHEET.
2. DEMOLISH EXISTING 2" HIGH CONCRETE HOUSEKEEPING
PAD.
3. FOR EXISTING ELECTRICAL EQUIPMENT TO REMAIN PROVIDE
PLASTIC ENCLOSURES/TENTING TO PROTECT ELECTRICAL
EQUIPMENT DURING DEMOLITION PHASE - SEE ELECTRICAL
DRAWINGS.
CONTRACTOR TO VERIFY ANY ADDITIONAL EQUIPMENT TO
BE PROTECTED.
4. EXISTING DOOR TO REMAIN
5. EXISTING LOUVER TO REMAIN
6. REMOVE EXISTING ROOFING INSULATION DOWN TO EXISTING
METAL DECK. REMOVE EXISTING ROOF EDGE AND ALL
ASSOCIATED NAILERS.
7. REMOVE EXHAUST FAN AND CURB, PATCH HOLE IN METAL
DECK WITH NEW METAL DECK PATCH.
8. REMOVE EXISTING VENT STACK, PATCH HOLE IN METAL
DECK WITH NEW METAL DECK PATCH.
9. REMOVE EXISTING ROOF DRAIN.
10. PROVIDE PLASTIC ZIPPER BARRIER AT DOOR OPENING
DURING DEMOLITION PHASE.
11. ELECTRICAL ROOM 101, MECHANICAL ROOM 102 CONTAINS
HAZARDOUS MATERIALS SEE SPECIFICATIONS 02 83 13.13
LEAD-PAINT REMOVAL. VETERANS ADMINISTRATION REPORT
"ASBESTOS AND LEAD PAINT REPORT SURVEY US DEPT OF
VETERANS AFFAIRS INSTALL GENERATOR FOR BLDG 85, 86,
AND 87 PROJECT" JUNE 2020
12. DEMOLISH EXISTING EXHAUST FAN SEE ELECTRICAL
SHEETS.
X
DEMOLITION
NEW WORK
1. NEW 5" H CONCRETE EQUIPMENT BASE. SEE DETAIL 6 THIS
SHEET. VERIFY SIZE AND LOCATION WITH ELECTRICAL
EQUIPMENT.
2. NEW ELECTRICAL EQUIPMENT - SEE ELECTRICAL DRAWINGS
3. THOROUGHLY CLEAN AND PAINT EXISTING LOUVER AND
DAMPER. PROVIDE PRIMER AND HEAVY DUTY URETHANE
TOPCOAT. COLOR TO BE SELECTED BY VA.
4. NEW OVERHEAD METAL FABRICATION FOR CONDUITS. SEE
A-502.
5. POLY ISO TAMPERED INSULATION CRICKET.
6. LOWER CONDUIT BANK TURN DOWN.
7. UPPER CONDUIT BANK TURN DOWN.
8. NEW FIRE EXTINGUISHER CABINET
- SEE SPECIFICATIONS.
9. NEW ROOFING SYSTEM - SEE DETAILS 8 AND 9 THIS SHEET.
1 DEMOLITION FLOOR PLAN
SCALE: 1/4" = 1'-0"
7/
/2
:0 2:
P
M
B85, B86, B87
A-101
NPM, DGCWVS
ENLARGED PLANS AND DETAILS
2 6
AREA OF WORK
6 6
A. SEE SPECIFICATIONS FOR FIRE EXTINGUISHER CABINETS
EXTINGUISHERS PROVIDED BY VA.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
KEY PLAN:
JULY 20, 2021
INSTALL GENERATOR FOR
BUILDINGS 85, 86 AND 87 (SA)
630A4-18-415
VA NEW YORK HARBOR HEALTHCARE
SYSTEM, ST. ALBANS CAMPUS
179-00 LINDEN BLVD,
JAMAICA, NY 1134-1468
19-227
BID DOCUMENTS
NORTH
FULLY SPRINKLERED
20-1-SA
7 ROOF INSULATION DIAGRAM
1/2" = 1'-0"
6 CONCRETE EQUIPMENT BASE
SCALE: 1" = 1'-0"
8 ROOF DETAIL
SCALE: 3" = 1'-0"
3 DEMOLITION ROOF PLAN
SCALE: 1/4" = 1'-0"
2 NEW WORK FLOOR PLAN
SCALE: 1/4" = 1'-0"
4 NEW ROOF PLAN
SCALE: 1/4" = 1'-0"
5 CURB DEMO DETAIL
NTS
9 ROOF DETAIL
SCALE: 3" = 1'-0"
10 MOUNTING HEIGHT
SCALE: 1/2" = 1'-0"
11 11
AREA OF WORK
00 4 8 16
0 2 4 8
0 2 4 80 1 2 4
00 4 8 16
SHEET NOTES
SHEET KEY NOTES
SHEET KEY NOTES
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text x
AutoCAD SHX Text
LINDEN BLVD.
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text
AutoCAD SHX Text 30'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
GRASS INFIELD
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP
UP
UP
UP
25'-5 1/2"
'-0
EDGE OF EXISTING
BUILDING
3'- 0"
MI
NI
MU
M
11'-5 1/2"
'-1
1'-0"
8'-0" 8'-4 1/2" 1'-0" 1'-4 1/2"
1'-0"
1'-0" 1'-4 1/2"
'-3
DSDS
DN
DN
3'- 0"
MI
NI
MU
M
101A
101C
102MECHANICAL
ROOM
FEC
DS DS
NEW WORK
1. EDGE OF NEW CONCRETE SLAB.
2. LOCATION OF EXISTING CONDUITS THROUGH ROOF.
3. APPROXIMATE LOCATION OF EXHAUST.
4. COLUMNS TO BE LAND IN CONCRETE SLAB NOT TO
INTERFERE WITH LOWER ACCESS PLATFORM OR OPEN
YARD.
5. PROPOSED UPPER PLATFORM ACCESS - BY GENERATOR
ENCLOSURE VENDOR.
6. STRUCTURAL SUPPORT POINTS FOR CONDUIT BANK - BY
GENERATOR ENCLOSURE VENDOR.
7/
/2
:0 2:
P
M
B85, B86, B87
A-102
DGC, NPMWVS
CONC SLAB AND PLATFORM LAYOUT
3 6
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
KEY PLAN:
JULY 20, 2021
INSTALL GENERATOR FOR
BUILDINGS 85, 86 AND 87 (SA)
630A4-18-415
VA NEW YORK HARBOR HEALTHCARE
SYSTEM, ST. ALBANS CAMPUS
179-00 LINDEN BLVD,
JAMAICA, NY 1134-1468
19-227
BID DOCUMENTS
NORTH
FULLY SPRINKLERED
20-1-SA
1 CONCRETE SLAB PLAN
1/4" = 1'-0"2 PLATFORM PLAN
1/4" = 1'-0"
AREA OF WORK
SHEET KEY NOTES
0 2 4 8 0 2 4 8
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text x
AutoCAD SHX Text
LINDEN BLVD.
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text
AutoCAD SHX Text 30'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
GRASS INFIELD
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text x
AutoCAD SHX Text
LINDEN BLVD.
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text 30'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
3'-5"3'-6 1/2"3'-4 1/2"3'-8"3'-7 1/2"3'-8"
A-501
35.13
A-501
3'-4 1/2" 3'-8" 3'-7 1/2" 3'-8"
A-501
36.20
TOP OF GEN. ENCLOSURE SLAB
TYP.
2'-10 1/2"2'-10 1/2"2'-10 1/2"
34.28 +/-
40.20
ASSUMED
FLOOR HEIGHT
GENERATOR ENCLOSURE
36.20
TOP OF GEN. ENCLOSURE SLAB
35.13
35.06
5'-0" 34.28
4'- 0"
7/
/2
:0 3:
P
M
B85, B86, B87
A-502
DGC, NPMWVS
PARTIAL PLAN, SECTIONS AND
ELEVATIONS
5 6
AREA OF WORK
3 FRONT ELEVATION
SCALE: 1/2" = 1'-0"
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
KEY PLAN:
JULY 20, 2021
INSTALL GENERATOR FOR
BUILDINGS 85, 86 AND 87 (SA)
630A4-18-415
VA NEW YORK HARBOR HEALTHCARE
SYSTEM, ST. ALBANS CAMPUS
179-00 LINDEN BLVD,
JAMAICA, NY 1134-1468
19-227
BID DOCUMENTS
NORTH
FULLY SPRINKLERED
20-1-SA
1 ELEVATION STAIR A
SCALE: 1/2" = 1'-0"
0 1 2 4
2 ELEVATION STAIR B
SCALE: 1/2" = 1'-0"
0 1 2 4
4 BACK ELEVATION
SCALE: 1/2" = 1'-0"
0 1 2 4
1. PREFABRICATED GALVANIZED GRATED TREADS
1"D X 11"W, WITH INTEGRAL SAFETY NOSING.
BOLT OR WELD TO STRINGERS.
2. DOOR BY GENERATOR ENCLOSURE MANUFACTURER.
3. SELF CONTAINED GENERATOR ENCLOSURE BY
CONTRACTOR.
4. FLOOR LEVEL OF GENERATOR ENCLOSURE BEYOND, ALIGN
WITH METAL STAIR PLATFORM AND TOP TREAD.
5. STRUCTURAL CONCRETE PAD FOR GENERATOR ENCLOSURE
- SEE CIVIL DRAWINGS.
6. 1 1/4" GALVANIZED STEEL SQUARE NEWELS
7. 3/4" GALVANIZED STEEL SQUARE BALUSTERS
8. C12x10.6 STEEL CHANNEL
9. C12x10.6 STEEL CHANNEL STRINGER
10. STEEL ANGLE - L3x3x.25
11. STEEL TUBE - TS6xX.25
12. CONCRETE LANDINGS - SEE CIVIL DRAWINGS.
13. CONCRETE FOUNDATIONS / PEDESTAL TO 3'-6" BELOW GRAD.
14. INTERIOR PLATFORM COLUMNS TO BEAR ON STRUCTURAL
CONCRETE PAD.
15. LINE OF APPROXIMATE GRADE.
SHEET KEY NOTES
0 1 2 4
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text
SAN
AutoCAD SHX Text 6"
AutoCAD SHX Text 4"
AutoCAD SHX Text 6"
AutoCAD SHX Text
8" WATER MAIN
AutoCAD SHX Text
8" WATER MAIN
AutoCAD SHX Text
8" WATER MAIN
AutoCAD SHX Text
LINDEN BLVD.
AutoCAD SHX Text 30'
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
GRASS INFIELD
AutoCAD SHX Text
PARKING
AutoCAD SHX Text H-12
AutoCAD SHX Text H-13
AutoCAD SHX Text M
AutoCAD SHX Text I-5
AutoCAD SHX Text I-6
AutoCAD SHX Text I-2
AutoCAD SHX Text I-1
AutoCAD SHX Text I-3
AutoCAD SHX Text I-4
AutoCAD SHX Text I-14
AutoCAD SHX Text I-13
AutoCAD SHX Text I-12
AutoCAD SHX Text I-11
AutoCAD SHX Text I-9
AutoCAD SHX Text I-8
AutoCAD SHX Text I-7
AutoCAD SHX Text I-10
AutoCAD SHX Text A-6
AutoCAD SHX Text I-18
AutoCAD SHX Text I-15
AutoCAD SHX Text I-17
AutoCAD SHX Text H-2
AutoCAD SHX Text B-6
AutoCAD SHX Text B-5
AutoCAD SHX Text B-7
AutoCAD SHX Text B-8
AutoCAD SHX Text B-13
AutoCAD SHX Text B-12
AutoCAD SHX Text B-14
AutoCAD SHX Text B-15
AutoCAD SHX Text A-5
AutoCAD SHX Text B-16
AutoCAD SHX Text I-16
AutoCAD SHX Text H-1
AutoCAD SHX Text A-2
AutoCAD SHX Text
FM
AutoCAD SHX Text B-11
AutoCAD SHX Text
MATCHLINE B
AutoCAD SHX Text
(SEE SHEET E-6)
AutoCAD SHX Text
(SEE SHEET E-3)
AutoCAD SHX Text
MATCHLINE B
AutoCAD SHX Text
MATCHLINE D
AutoCAD SHX Text
MATCHLINE D
AutoCAD SHX Text
(SEE SHEET E-6)
AutoCAD SHX Text
(SEE SHEET E-5)
AutoCAD SHX Text B-10
AutoCAD SHX Text 2#6
AutoCAD SHX Text 3#6
AutoCAD SHX Text 9#6
AutoCAD SHX Text 3#6
AutoCAD SHX Text 3#6
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text 2#6
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text 3#6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
STEEL FABRICATION TO BE DESIGNED
BY LICENSE STRUCT ENGINEER. SHOP
DRAWINGS REQUIRED.
EXISTING CONC
SIDEWALK
STL TUBE 2 X 2
BRACING TO EXISTING
BAR JOISTS. CONNECT
4 JOISTS MIN.
NEW ELECTRICAL
EQUIPMENT
A-503
'-0
" M
IN
A-502
NEW CONCRETE
PEDESTAL AND
FOUNDATIONS AS
PER STRUCT. ENG.
NEW GENERATOR
ENCLOSURE
STRUCTURAL SUPPORT POINTS FOR
CONDUIT BANK - BY GENERATOR
ENCLOSURE VENDOR.
8" MI
N.
FLASH AS PER MANUFACTURER'S
STANDARD DETAILS
LINE OF NEW DUCT BANK
NEW TREATED CONTINOUS WOOD
BLOCKING
EXISTING ELECTRICAL
BUILDING VAULT 164
NEW GUTTER AND
DOWNSPOUT
STEEL FABRICATION TO BE DESIGNED
BY LICENSED STRUCT ENGINEER. SHOP
DRAWINGS REQUIRED.
PRECAST CONCRETE SPLASH
BLOCK 12" W X 18" L X 24" H
A-503
18 GA. STAINLESS STEEL COVER.
ALL SEAMS TO CONFORM TO
SMACNA ARCH. SHEET METAL
MANUAL, 7TH ED.
EXISTING CONCRETE
WALK - SEE CIVIL
NEW ROOFING SYSTEM
SEE DETAILS A-101
LINE OF APPROX.
GRADE AT BLDG.
THOROUGHLY CLEAN AND PAINT
EXISTING LOUVER AND DAMPER.
PROVIDE PRIMER AND HEAVY DUTY
URETHANE TOPCOAT.
THOROUGHLY CLEAN AND PAINT
EXISTING LOUVER AND DAMPER.
PROVIDE PRIMER AND HEAVY DUTY
URETHANE TOPCOAT.
NEW METAL COPING
18 GA. STAINLESS STEEL COVER.
ALL SEAMS TO CONFORM TO
SMACNA ARCH. SHEET METAL
MANUAL, 7TH ED.
EXISTING ELECTRICAL
BUILDING VAULT 164
A-503
STANDING SEAMS
TYPICAL
COORDINATE CURB AND
CONDUIT COVER WATER
TIGHTNESS WITH
GENERATOR ENCLOSURE
SUPPLIER
A-501
A-101
A-101
A-503
3'- 8"
TY
P.
S
PA
CI
NG
2'-0"
2'- 1"
EXISTING ELECTRICAL
BUILDING VAULT 164
A-503
A-101
A-101
A-503
EXISTING ELECTRICAL
BUILDING VAULT 164
CONDUIT BANK -
SEE ELECTRICAL DWGS
STEEL FABRICATION TO BE
DESIGN BY LICENSE STRUCT
ENGINEER. SHOP DRAWINGS
REQUIRED.
BACK TO BACK STEEL UNISTRUT
8'-0" O.C. MAX
1/2" TREATED PLYWOOD, ALL 4
SIDES. ATTACH TO STEEL FRAME
SINGLE CORNER SEAM - SLOPE
DOWN SLIGHTLY FOR WATER
RUN OFF
SINGLE CORNER SEAM
18 GA. STAINLESS STEEL COVER.
ALL SEAMS TO CONFORM TO
SMACNA ARCH. SHEET METAL
MANUAL, 7TH ED.
STAINLESS STEEL COVER NOTES
SURROUND FABRICATED IN 2 PIECES
SHAPE OF FIRST PIECE FROM 4'X 10' SHEET
FORMING 3 SIDES.
SHAPE OF SECOND PIECE - FLAT SIDE,
ATTACHED VIA CLIPS TO PLYWOOD
STAINLESS STEEL COVER NOTES
SINGLE CORNER SEAM
REFER TO SMACNA ARCH. SHEET METAL MANUAL, 7TH ED.
STANDING SEAM
NEW GENERATOR
ENCLOSURE
NEW GENERATOR
ENCLOSURE
1 METAL FABRICATION PLANS
SCALE: 1/4" = 1'-0"
7/
/2
:0 4:
P
M
B85, B86, B87
A-503
DGCWVS
ENLARGED ROOF PLAN, SECTION,
DETAILS
6 6
5 SECTION
SCALE: 1/4" = 1'-0"
2 DUCT BANK COVER PLAN
SCALE: 1/4" = 1'-0"
STRUCTURAL
ELECTRICAL
LEGEND
AREA OF WORK
7 SECTION DETAIL
SCALE: 1-1/2" = 1'-0"
3 ELEVATION
SCALE: 1/4" = 1'-0"
4 ELEVATION
SCALE: 1/4" = 1'-0"
6 SECTION DETAIL
SCALE: 1-1/2" = 1'-0"
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
KEY PLAN:
JULY 20, 2021
INSTALL GENERATOR FOR
BUILDINGS 85, 86 AND 87 (SA)
630A4-18-415
VA NEW YORK HARBOR HEALTHCARE
SYSTEM, ST. ALBANS CAMPUS
179-00 LINDEN BLVD,
JAMAICA, NY 1134-1468
19-227
BID DOCUMENTS
NORTH
FULLY SPRINKLERED
20-1-SA
0 2 4 8
0 2 4 8
0 2 4 8
0 2 4 8
0 2 4 8
DocuSign Envelope ID: E26C3B4A-3E59-4539-B825-8DACFEE00F57
7/21/2021
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LINDEN BLVD.
AutoCAD SHX Text
AutoCAD SHX Text 30'
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CIVIL ENGINEER: Brett Basquin, PE 2128 Moores Mill Road Suite C Auburn, AL 36830 (O) 334.887.6064 ext. 302 (F) 334.887.6024 BRETT BASQUIN, SOLE PROPRIETOR
| 2021-07-21T08:48:31-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it. Updated .