S02 - 03 - VA Hospital Phase 2B - ATC As-Built Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- 36C24426Q0675
About this file
This document is a set of construction control drawings for Phase 2B of a VA HVAC Controls Upgrade project at VA Medical Center in Wilmington, Delaware, covering the 7th, 8th, and 9th floor HVAC equipment.
The drawings specify control systems for five air handling units (AHU-1 through AHU-7) and associated equipment. AHU-1 (MER 7003) is a variable volume unit with temperature control via modulating valves V-1 and V-2, humidity control through steam injection valve V-3 and condensate return valve V-4, and airflow control maintaining 1.5" duct static pressure. AHU-2 and AHU-3 (MER 7060A and 7074) are constant volume units with similar temperature and humidity control sequences. A/C-1 (8th Floor West) provides both heating and cooling mode control with temperature sensors T-1 and T-2 modulating four control valves in sequence. AHU-7 (8th Floor East) includes dual supply and return fans with variable speed controllers, operates with outside air economizer dampers (D-1, D-2, D-3), and incorporates freeze protection at 45°F with shutdown at 40°F. The 9th floor elevator AHU includes relief dampers and similar temperature control logic. All units feature emergency shutdown protocols activated by smoke detection, with dampers closing and fans stopping until fire alarm circuits are manually reset. Control is managed through Johnson DDC controllers (FEC2611 and IOM4711 modules) with point identification tables, wiring details, and SAPC/FC bus communication. VAV boxes for 7th Floor East include velocity probes and modulating dampers controlled by space temperature sensors. Heat exchanger controls (C5-C8) for the main building include pump staging based on hot water demand and sensor-modulated valve control maintaining 180°F supply temperature. All pneumatic devices have been replaced with electronic controls, and new valve schedules and network architecture documentation are referenced in the ATC O&M manual binder. The document specifies that panel labels will be provided for all new and existing control panels, with approval required from the VA Hospital.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL AND CONTROL SYSTEMS
Environmental Control System
Building Automation System
VA MEDICAL CENTER
HVAC CONTROLS UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
PROJECT
OWNER
ENGINEER
CONTRACTOR
211-1009IW/BM 7/19/11IW/JAIW
REFERENCE DRAWING
SUB. REVISION TITLE DATES1 12/13/11 VD
NO. REVISION-LOCATION ECN DATE BY
Automatic Temperature Controls
Heating
Air Conditioning
Air Filters
Water Treatment
Coil Cleaning
Contract Operations
Time-Shared Automated Building Service
Refrigeration
Industrial Controls / Recording / Indication Equipment
Air and Water Systems Balancing
Instrumentation System Installation
Building Operations Management
Energy Conservation Control
Custom Programmed Maintenance
HATCH MOTT MACDONALD
27 BLEEKER ST.
MILLBURN, NJ 07041
BOB SMITH CONTRACTORS
281 EAST EVERGREEN ST.
WEST GROVE, PA 19390
DEPT. OF VETERANS AFFAIRS
1601 KIRKWOOD HIGHWAY
WILMINGTON, DE 19805
VA HVAC CONTROLS UPGRADE - PHASE 2B
(PARTIAL SUBMITTAL - INCLUDES 7TH 8TH & 9TH FLOOR HVAC EQUIPMENT)
PAGE # DRAWING TITLE LAST REVISION
TP-1 TITLE PAGE 01/28/14
C-1A AIR HANDLING UNIT CONTROL – AHU-1 (MER 7003) 12/03/14
C-1B CONTROLLER WIRING DETAIL – AHU-1 (MER 7003) 12/03/14
C-1C SEQUENCE OF OPERATIONS – AHU-1 (MER 7003) 12/03/14
C-2A AIR HANDLING UNIT CONTROL – AHU-2 (MER 7060A) 12/03/14
C-2B CONTROLLER WIRING DETAIL – AHU-2 (MER 7060A) 12/03/14
C-2C AIR HANDLING UNIT CONTROL – AHU-3 (MER 7074) 12/03/14
C-2D CONTROLLER WIRING DETAIL – AHU-3 (MER 7074) 12/03/14
C-2E SEQUENCE OF OPERATIONS – TYPICAL FOR AHU-2 & AHU-3 (MER 7060A & 7074) 12/03/14
C-3A AIR HANDLING UNIT CONTROL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14
C-3B CONTROLLER WIRING DETAIL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14
C-3C SEQUENCE OF OPERATIONS – AC-1 (MER 8TH FLOOR WEST) 12/03/14
C-4A AIR HANDLING UNIT CONTROLS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-4B CONTROLLER WIRING DETAIL – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-4C VAV BOX CONTROLS FOR 7TH FLOOR EAST (SERVED BY AHU-7) 12/03/14
C-4D SEQUENCE OF OPERATIONS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-5A AIR HANDLING UNIT CONTROL – ELEVATOR AHU 9TH FLOOR 12/03/14
C-5B CONTROLLER WIRING DETAIL – ELEVATOR AHU 9TH FLOOR 12/03/14
C-6A TYPICAL HEAT EXCHANGER CONTROL – MAIN BUILDING 01/28/14
C-6B CONTROLLER WIRING DETAIL – TYPICAL HEAT EXCHANGER (MAIN BUILDING) 01/28/14
AS-BUILT REV. NEW DWG. TITLES/DATES2 12/03/13 BM
2 3
AS-BUILT REV. ADD ‘MASTER’ NOTE3 1/28/14 DB
NOTE(S): REFER TO ‘MASTER BUILDING NETWORK ARCHITECTURE DRAWING’
PROVIDED IN OUR ATC AS-BUILT / O&M MANUAL BINDER FOR ALL
SUPERVISORY CONTROLLER INFORMATION AND ASSOCIATED IP
ADDRESSES USED BY MODERN CONTROLS.
REFER TO ‘MASTER BUILDING VALVE SCHEDULE’ PROVIDED IN OUR
ATC AS-BUILT / O&M MANUAL BINDER FOR A COMPLETE LIST OF ALL
CONTROL VALVES PROVIDED FOR AIR HANDLING UNITS AND
ASSOCIATED VAV BOXES.
211-1009
IW/BMIW/JAIW BM 7/20/11
REFERENCE DRAWING
SUB. REVISION ADD NOTE1 12/12/11 VD
C-1C
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
ONTRACT NUMBER
RAWING NUMBER
VA HVAC CONTROLS
UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
AHU-1 (MER 7003)
Project Title
SEQUENCE OF OPERATIONS - AHU-1 (MER 7003)
AHU-1 (MER #7003)
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND”
AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE
FULLY OPENED.
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE.
3. AIF FLOW CONTROL
THE SUPPLY AIRFLOW SHALL BE CONTROLLED BY THE DCP MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO
MAINTAIN 1.5” OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE) SENSED BY SPS-1.
THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM
DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY FAN SHALL STOP.
4. HUMIDITY CONTROL
WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY SPACE AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN
CLOSED. WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED
HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE
VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH; (FIELD VERIFY INTERLOCK) TO
KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS
BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
6. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN STOPS AND THE ALARM SIGNAL IS TRANSMITTED TO THE
FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL OPEN WHEN THE
FIRE ALARM CIRCUIT IS MANUALLY RESET.
1 2
AS-BUILT REV. NEW DRAWING2 12/3/13 BM
211-1009
IW/BMIW/JAIW BM 7/19/11
REFERENCE DRAWING
SUB. REVISION EDIT SEQUENCE1 12/13/11 VD
C-4D
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
ONTRACT NUMBER
RAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
AHU-7 (MER 8TH FLOOR EAST)
Project Title
SEQUENCE OF OPERATIONS - AHU-7 (MER 8TH FLOOR EAST)
AHU-7 (MER 8TH FL EAST)
1. GENERAL
SUPPLY AND RETURN FANS ARE NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1, D-2 AND D-3 SHALL BE CLOSED. WHEN THE UNIT IS
“ON” D-1, D-2 AND D-3 SHALL BE OPENED.
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING EITHER V-1 AND V02 OR D-1, D-2 AND D-3 IN SEQUENCE.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS ABOVE 65°F DCP PREVENTS MODULATION OF D-1 AND D-2; D-1 ASSUMES MINIMUM OUTSIDE AIR POSITION AND D-2 IS OPENED. V-1 MODULATES TO MAINTAIN SUPPLY AIR TEMPERATURE SENSED BY T-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS BETWEEN 65°F AND THE SUPPLY AIR TEMPERATURE SENSED BY T-1, DAMPER D-2 IS CLOSED AND DAMPER D-1 IS OPENED TO MAXIMUM OUTSIDE AIR POSITION. V-1 MODULATES OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE.
3. AIR FLOW CONTROL
THE SUPPLY AIR FLOW IS CONTROLLED BY THE DCP MODULATING SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN THE DUCT STATIC
PRESSURE SETPOINT AS SENSED BY SPS-1.
THE DCP BY USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS SHALL RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT CFM DIFFERENCE
BETWEEN THE SUPPLY AIR FAN CFM AND THE RETURN AIR FAN CFM.
THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL
SHALL INDICATE ON DCP AND BMS.
4. HUMIDITY CONTROL
WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY RETURN AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN CLOSED.
WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2.
DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPY FAN IS OFF.
VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH (FIELD VERIFY INTERLOCK) TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE
APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-3 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40°F THE SUPPLY AND RETURN FANS SHALL SHUT DOWN, DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
6. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. DAMPERS D-1, D-2 AND D-3 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL
OPEN WHEN THE FIRE ALARM CIRCUIT IS MANUALLY RESET.
7. EMERGENCY CONSTANT SPEED OPERATION
UPON FAILURE OF VSMC THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE BMS THROUGH THE BYPASS STARTER.
FANS SHALL THEN OPERATE AT CONSTANT SPEED.
AS-BUILT REV. NEW DWG. / ADD NOTE2 12/3/13 BM
NOTE(S): REFER TO DRAWING C-4C FOR ASSOCIATED VAV BOX
SEQUENCE OF OPERATIONS AND AIR FLOW SCHEDULE.