This is a solicitation document, number 36C25520R0073, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15, for the expansion and upgrade of Building 42 to accommodate new laboratory facilities at the Marion VA Medical Center. The solicitation seeks general contractor services including construction of an approximately 15,000 square foot addition to the existing building, as well as renovations and upgrades to existing spaces. The work includes structural, interior demolition and construction, mechanical, electrical and low voltage systems. The period of performance is 420 calendar days from NTP. Responses are due by 2:00 PM Eastern on November 8, 2019 and the contract is to be awarded by January 15, 2020. Pricing is to be provided as a firm fixed price with unit prices for additional work. No set-asides or preferences are specified.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT
SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE
REQUIRED.
ELECTRICAL CONNECTION.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH BOTTOM OUTLET CONTROLLED BY W ALL SW ITCH. (18" MH UNLESS
NOTED OTHERW ISE).
20A-125V TAMPER RESISTANT DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH
STANDARD COVER, VERTICAL MOUNT.
20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH
UNLESS NOTED OTHERW ISE), W ITH STANDARD COVER, VERTICAL MOUNT.
20A-125V POW ERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERW ISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R. PROVIDE CARPET FLANGE W HERE REQUIRED.
20-125V DUPLEX RECEPTACLE, NEMA 5-20R, W ITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERW ISE).
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERW ISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERW ISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERW ISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERW ISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERW ISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERW ISE).
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERW ISE).
CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERW ISE).
SINGLE POLE SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
TW O POLE W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
MULTI-W AY W ALL SW ITCH, # INDICATES NUMBER OF W AYS (46" MH UNLESS NOTED OTHERW ISE).
SW ITCH W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERW ISE).
KEY OPERATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
LIGHTING DIMMER SW ITCH (46" MH UNLESS NOTED OTHERW ISE) 1000 W ATTS UNLESS OTHERW ISE INDICATED.
SW ITCH W ITH RECEPTACLE (46" MH UNLESS NOTED OTHERW ISE) STANDARD TW O-GANG ASSEMBLY OF SW ITCH AND
RECEPTACLE.
FLUSH FRACTIONAL HORSEPOW ER MOTOR STARTER W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS
NOTED OTHERW ISE).
HP RATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
DISCONNECT SW ITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
CORD REEL.
POW ER POLE.
PHOTOELECTRIC SENSOR.
LIGHTING CONTACTOR.
CEILING MOUNTED OCCUPANCY SENSOR.
W ALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POW ER PACK.
FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS
NOT SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM CHIME & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS
NOT SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM HORN & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT
SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM SIGNALING LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT
SHOW N, THE STROBE SHALL BE RATED 75.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERW ISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
W ATER FLOW SW ITCH.
VALVE SUPERVISORY SW ITCH.
DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATOR LIGHT. SUBSCRIPT "W " INDICATES W ALL
MOUNTED.
SMOKE DAMPER.
FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERW ISE).
PUSHBUTTON (46" MH UNLESS NOTED OTHERW ISE).
BUZZER (90" MH UNLESS NOTED OTHERW ISE) EDW ARDS 340-A (120 VOLT).
4" DIAMETER (90" MH UNLESS NOTED OTHERW ISE).
TR
WP
WP/GF
T
IG
20A
30A
50A
20A
50A
30A
J
P
K
DM
R
H
UH
FC
AC
CU
UV
PP
OS
M
OS
M
DS
OP
PC
T
F
F
F
F
S F
CEILING MOUNTED FIRE ALARM SPEAKER.
KF
S M
H
C
D
FS
V
R W
SD
FT
B
PRESSURE SW ITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
KNOX BOX.
PS
AM
C/I
PIV
K
FIRE ALARM CONTROL PANEL.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).
C
M
CR
LC
P/B
H
S S/R
S/R
ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERW ISE) W ITH RESET SW ITCH (46" MH UNLESS NOTED
OTHERW ISE).
INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W " INDICATES W ALL MOUNT (46" MH
UNLESS NOTED OTHERW ISE).
INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERW ISE).
INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERW ISE).
INTERCOM SPEAKER FLUSH MOUNT IN CEILING.
I
M
H
S
FACP
AV SYMBOLS WITH ELECTRICAL REQUIREMENTS
S H
SURFACE MOUNTED PAGING/INTERCOM SPEAKER (90" MH UNLESS NOTED OTHERW ISE). SUBSCRIPT "H" INDICATES HANGING CEILING SPEAKER. 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SPEAKER, INSTALLATION AND CABLING PER DIV 27.
MUSIC PLAY BACK SPEAKER (102" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION ADJACENT TO BOX AND W IRING PER
DIV 27.
S M
S HORN TYPE PAGING/INTERCOM SYSTEM SPEAKER (90" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION AND W IRING PER DIV 27.
DUCT HEATER.H
DH
H
EB
LOW -VOLTAGE MOMENTARY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
L
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
CC
CCTV SYSTEM W ALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.
PS
LOCAL LOW VOLTAGE POW ER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA. 120V POW ER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POW ER SUPPLY PER DIV 26. POW ER SUPPLY
MOUNTED ABOVE CEILING AND LOW VOLTAGE W IRING TO LOCAL CAMERA PER DIV 28.
IC
W ALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.
DM
DOOR POSITION SW ITCH W ITH W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR
OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.
EL
ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
EM
ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
ES
ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
LB
RX
REQUEST TO EXIT SW ITCH IN DOOR HARDW ARE BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
HD
HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POW ER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE W IRING AND INTERFACE W ITH SMS AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
HA
W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER W ITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE W IRING AND INTERFACE W ITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY
ROUGH-IN DETAILS.
HO
FA
W ALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN W ITH POW ER SUPPLY INSTALLED BY OTHERS. 120V POW ER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE W IRING FROM POW ER SUPPLY TO HOLD OPEN AND INTERFACE W ITH SMS PER DIV 28. SUBSCRIPT "FA" INDICATES DEVICES POW ERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM REQUIRED FOR DOOR RELEASE PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
CR EL
W ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER
TO SECURITY ROUGH-IN DETAILS.
CR EL
ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED W ITH ELEVATOR CONTRACTOR. W IRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE W ITH ELEVATOR CONTROLLER AND SMS PER DIV 28, COORDINATE W ITH ELEVATOR
CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.
KC
W ALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERW ISE). 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.
K W ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYPAD AND CABLING PER DIV 28.
MD
W ALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. MOTION DETECTOR, W ALL MOUNT HARDW ARE, AND CABLING PER DIV 28.
PP W
W ALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.
X W ALL MOUNTED SECURITY SYSTEM W IRING OUTLET MOUNTED BELOW COUNTER TOP. 2-GANG BOX W ITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE AND SECURITY
SYSTEM CABLING PER DIV 28.
CM
W ALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 1" CONDUIT TO ABOVE CORRIDOR CEILING PER DIV 26. JACK, FACEPLATE AND CABLING PER DIV 28.
MIC
CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. 1-GANG BOX MOUNTED IN CEILING PER DIV 26.
M ICROPHONE AND CABLING PER DIV 28.
BR
W ALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERW ISE). 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. READER AND CABLING PER DIV 28. REFER TO
SECURITY ROUGH-IN DETAILS.
X
X
MD
PB W
W ALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.
ELECTRONIC LATCH BOLT MONITORING. HARDW ARE AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28.
CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SECURITY JUNCTION BOX ABOVE CEILING PER DIV 26. REFER TO
SECURITY ROUGH-IN DETAILS.
CEILING MOUNTED MOTION DETECTOR. 1-GANG BOX MOUNTED IN CEILING PER DIV 26. DETECTOR AND CABLING PER
DIV 28.
DC
LOCAL IP BASED 2-DOOR ACCESS CONTROL PANEL SERVING LOCAL CARD READER/SECURITY CONTROLLED DOORS.
LOCATE ABOVE ADJACENT ACCESSIBLE CEILING. PROVIDE DATA DROP IN 0.75" CONDUIT TO LOCAL DATA CLOSET.
EXTEND 1" CONDUIT W ITH DOOR SECURITY W IRING TO LOCAL SECURITY SYSTEM JUNCTION BOX. REFER TO SECURITY
ROUGH-IN DETAILS.
JB M
SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY W IRING CONDUITS/RACEW AYS TO JUNCTION BOX. EXTEND 1" CONDUIT W ITH DOOR SECURITY W IRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAW INGS. REFER TO SECURITY
ROUGH-IN DETAILS.
PL
SITE POLE FOR MOUNTING SECURITY CAMERAS (REFER TO SPECIFICATIONS FOR SIZE/TYPE). PROVIDE POLE W ITH CONCRETE BASE AS INDICATED ON PLANS. EXTEND AND CONNECT TO SITE CONDUIT SYSTEM AS INDICATED ON PLANS.
PROVIDE NEMA 3R JUNCTION BOX AT BASE OF POLE FOR CAMERA EQUIPMENT (120V POW ER SUPPLY, FIBER
CONVERTERS, ETC.). REFER TO SECURITY ROUGH-IN DETAILS.
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P W ALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X R
W ALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
X V
W ALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU W ALL (1-2" SLEEVE UNLESS NOTED OTHERW ISE) PER DIV 26.
J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.
D W ALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X I
W ALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUITS TO ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES
ALTERNATE CONFIGURATION.
AP
W ALL MOUNTED W IRELESS ACCESS POINT (96” MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. W AP AND CABLE PER DIV 27.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SW ITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTW N - BETW EEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOW N
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
EX/R - EXISTING TO BE REMOVED AND RE-INTSALLED.
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFB - GROUND FAULT BREAKER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC CONTRACTOR (DIVISION 23)
HP - HORSE POW ER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OW NER FURNISHED CONTRACTOR INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
PC - PLUMBING CONTRACTOR (DIVISION 22)
PLBG - PLUMBING
PX - PYXIS
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY CONTRACTOR
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TR - TAMPER RESISTANT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W / - W ITH
W /0 - W ITHOUT
W P - W EATHERPROOF
ZVC - ZONE VALVE CABINET
E2
B
E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET W HERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
W IRE & CONDUIT IN W ALL OR ABOVE CEILING.
W IRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES
CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.
CONDUIT FOR DATA CIRCUITRY.DAT
W IRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
W IRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC
EXISTING W IRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
W IRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL
CONDUIT FOR PHONE CIRCUITRY.PHO
W IRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC
W IRE RUN IN SURFACE W IREW AY.W
CABLE MANAGEMENT SYSTEM PATHW AY.CM
X - 1,2
W IRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
W IRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S
W IRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I
W IRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES
SW ITCHING ARRANGEMENT.
LIGHTING FIXTURE ON LIFE SAFETY CIRCUIT.
EXIT LIGHTING FIXTURE ON LIFE SAFETY CIRCUIT, ARROW S AS INDICATED.
A a
W IREMOLD RACEW AY, AS NOTED ON PLANS.
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.
4"
4"
4"
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERW ISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
LIGHTING FIXTURE ON CRITICAL CIRCUIT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
FOUR 20A-125V RECEPTACLES, NEMA 5-20R AND FOUR DATA JACK KEYSTONE OPENINGS. FIRE RATED POKE-THRU W ITH
ROUND COVER PLATE. PROVIDE CARPET FLANGE W HERE REQUIRED.
MULTI-SERVICE POKE THRU PER DIV 26. PROVIDE APPROPRIATE CONNECTOR PLATE AND OVER. SUBSCRIPT "4D"
INDICATES # OF DATA. REFER TO FACEPLATE DETAILS.
4D
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERW ISE).
GF
1. ALL EXISTING UNDERGROUND UTILITIES ARE TO BE MARKED AND DEPTH LOCATED IN AREAS W HERE NEW DUCTBANKS, UTILITIES, FOOTERS, ETC. ARE TO CROSS BY A THIRD PARTY LOCATING SERVICE.
2. INSTALL NEW DUCTBANKS AND MANHOLES, ASSOCIATED W ITH THE NEW 12KV FEEDERS.
3. SCHEDULE OUTAGE FOR NEW DUCTBANK TIE-INS TO EXISTING MANHOLES.
4. START ALL CAMPUS EMERGENCY GENERATORS AND TRANSFER BUILDING LOAD TO PREPARE FOR OUTAGE.
5. DE-ENERGIZE MAIN CAMPUS 12KV BREAKER. DISCONNECT FEEDER SPLICES SERVING M.H. #4A AND RE-ENERGIZE
CAMPUS POW ER. THIS W ORK SHALL BE PERFORMS IN NO MORE THAN 4 HOURS. SHUT DOW N ALL EM GENERATORS EXCEPT BUILDINGS 8, 42, 43, 81, 82 AND 83. PERFORM THIS W ORK DURING NONPEAK HEATING OR COOLING SEASON.
6. BUILDINGS 8, 42, 43, 81, 82 AND 83 (US-A, US-B) ARE NOW DE-ENERGIZED. COMPLETE NEW DUCTBANK IN MH #4A, 4B, MH #4B AND CONDUITS INTO UNIT SUBS A & B. PULL M.V. CABLE TERMINATE AND TEST. REMOVE ABANDON CABLE.
THIS W ORK SHALL BE PERFORMED IN NO MORE THAN 24 HOURS.
7. START ALL CAMPUS EMERGENCY GENERATORS AND TRANSFER BUILDING LOAD TO PREPARE FOR OUTAGE.
8. DE-ENERGIZE MAIN CAMPUS 12KV BREAKER. RE-CONNECT FEEDER SPLICES SERVING M.H. #4A AND RE-ENERGIZE
CAMPUS POW ER. THIS W ORK SHALL BE PERFORMS IN NO MORE THAN 4 HOURS. SHUT DOW N ALL EM GENERATORS.
PERFORM THIS W ORK DURING NONPEAK HEATING OR COOLING SEASON.
9. VERIFY ALL BUILDINGS HAVE RETURNED TO UTILITY POW ER.
A. SEQUENCE OF CONSTRUCTION INDICATED ON THIS SHEET IS ONE POSSIBLE SOLUTION TO MINIMIZE DOW NTIME OF THE BUILDING ELECTRICAL SYSTEM. CONTRACTOR IS REQUIRED TO SUBMIT FOR APPROVAL A DETAILED SEQUENCE OF CONSTRUCTION NARRATIVE THAT INCLUDES ALL ANTICIPATED OUTAGES AND DURATIONS TO THE COR/ENGINEER W ITHIN 60 DAYS FROM NOTICE TO PROCEED. DEVIATIONS FROM THE FOLLOW ING PROPOSED SEQUENCE OF CONSTRUCTION W ILL BE REVIEW ED, BUT W ILL NOT BE GROUNDS FOR ADDITIONAL COST TO THE GOVERNMENT.
CONTRACTOR SHALL SCHEDULE REVIEW MEETINGS W ITH THE COR/ENGINEER PRIOR TO ANY OUTAGE. CONTRACTOR
SHALL OBTAIN W RITTEN APPROVAL FROM THE COR PRIOR TO ANY OUTAGE.
B. ALL CUTOVER W ORK REQUIRING BUILDING ELECTRICAL SYSTEM OUTAGES AND/OR EMERGENCY SYSTEM DOW NTIME SHALL BE DONE OUTSIDE OF NORMAL W ORKING HOURS (NIGHTS/W EEKENDS) AND OUTSIDE OF PEAK HEATING/COOLING SEASON AND SHALL BE COORDINATED W ITH COR A MINIMUM OF 4 W EEKS PRIOR TO OUTAGE.
OUTAGES OF ALL TYPES SHALL BE AS MINIMAL AS POSSIBLE.
C. W ORK PERFORMED INSIDE OF MANHOLES REQUIRE ALL FEEDERS INSIDE THE MANHOLE TO BE DE-ENERGIZED. FIELD VERIFY ALL CIRCUIT NUMBERS AND SOURCES INSIDE OF MANHOLES PRIOR TO SCHEDULING OUTAGES. VERIFY ALL CIRCUITS ARE DE-ENERGIZED INSIDE OF THE MANHOLE PRIOR TO PERFORMING W ORK. ROUTING OF ALL EXISTING 12KV
FEEDERS SHALL BE VERIFIED.
D. AT THE CONCLUSION OF EACH OUTAGE THE NEW 12KV FEEDER CABLES SHALL BE COILED INSIDE OF THE NEAREST MANHOLE AND ALL MANHOLE COVERS SHALL BE RE-INSTALLED. UNDER SPECIAL CIRCUMSTANCES W HERE CABLES CANNOT BE COILED INTO THE MANHOLE THE AREA SHALL BE TEMPORARILY BARRICADED TO PREVENT PEDESTRIAN ACCESS AND MARKED W ITH BARRICADE TAPE READING “DANGER HIGH VOLTAGE”. CABLE SPOOLS AND ASSOCIATED MANHOLES SHALL ALSO BE BARRICADED TO PREVENT PEDESTRIAN ACCESS AND MARKED W ITH THE AFOREMENTIONED
BARRICADE TAPE. NO MORE THAN 2 MANHOLES SHALL BE OPENED AT ONE TIME.
E. PHASES BELOW DO NOT CORRESPOND W ITH PROJECT PHASES AND ARE USED FOR REFERENCE ONLY.
F. CONTRACTOR SHALL VERIFY SUFFICIENT FUEL (PROVIDED BY VA) IS PRESENT IN GENERATORS PRIOR TO ALL
OUTAGES. VA W ILL SUPPLY FUEL FOR RUNNING EXISTING EMERGENCY GENERATORS, CONTRACTOR SHALL SUPPLY
FUEL FOR RUNNING TEMPORARY GENERATORS.
G. PROVIDE A STAND-BY TEMPORARY EMERGENCY GENERATOR ONSITE DURING ALL NORMAL POW ER OUTAGES W HERE THE BUILDING IS RUNNING SOLELY ON AN EMERGENCY GENERATOR INCASE THE PRIMARY GENERATOR FAILS.
TEMPORARILY CABLE THE STAND-BY GENERATOR TO REPLACE THE FAILED GENERATOR UNTIL REPAIRS CAN BE MADE.
H. W HERE INCLUDED IN THE SEQUENCE OF CONSTRUCTION, BARRICADES SHALL CONSIST OF AT A MINIMUM A 6' HIGH TEMPORARY CONSTRUCTION CHAIN-LINK FENCE SURROUNDING THE BARRICADED AREA AND SHALL DISPLAY
APPROPRIATE CONSTRUCTION SIGNAGE.
I. ALL OPEN MANHOLES SHALL BE MANNED BY A QUALIFIED INDIVIDUAL.
J. ALL LABELS FOR FEEDERS IN MANHOLES SHALL BE INSTALLED DURING SCHEDULED OUTAGES AND SHALL NOT
REQUIRE AN ADDITIONAL OUTAGE FOR THEIR INSTALLATION.
K. TRAFFIC CONTROL W HERE REQUIRED SHALL BE PROVIDED.
L. TERMINATION KITS SHALL BE INSTALLED PRIOR TO SHUT-DOW NS W HERE FEASIBLE.
M. LOCK OUT TAG OUT PROCEDURES SHALL BE FOLLOW ED PER CAMPUS STANDARDS. CONTRACTOR SHALL INCLUDE 24
HOURS A DAY / 7 DAYS A W EEK CONTACT INFORMATION W ITH AN ON-SITE RESPONSE TIME OF 30 MINUTES OR LESS.
12 KV FEEDER WORK PHASING
SEQUENCE OF CONSTRUCTION
GENERAL NOTES
SC RECESSED CEILING PAGING SPEAKER W ITH W IRING.
AR EMERGENCY 2-W AY COMMUNICATION SYSTEM ELEVATOR CALL STATION. PROVIDE STATION, W ITH OUTLET BOX AND
CONDUIT TO ABOVE CEILING AND CABLING TO MASTER STATION AS REQUIRED.
AM EMERGENCY 2-W AY COMMUNICATION SYSTEM MASTER STATION, DESK MOUNTED. PROVIDE STATION, W ITH BOX AND
CONDUIT TO ABOVE CEILING AND CABLING TO MAIN CONTROLLER AS REQUIRED.
AE EMERGENCY 2-W AY COMMUNICATION SYSTEM MAIN CONTROLLER W ITH POW ER SUPPLY, W ALL MOUNTED. PROVIDE
CABLING TO MASTER STATION AND REMOTE STATIONS AS REQUIRED.
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:51:37 PM
/7
/2
:5
:3
P
M
LEGEND, SYMBOLS & INDEX OF
DRAWINGS
Expand & Upgrade Building 42 for Laboratory
E001
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
INDEX OF DRAWINGS
Sheet Number Sheet Name
E001 LEGEND, SYMBOLS & INDEX OF DRAWINGS
E401 ENLARGED TR ROOM PLAN
E501 DETAILS
E502 DETAILS
E503 DETAILS
E601 SCHEDULES
E601a LIGHTING SCHEDULE
E601b LIGHTING SCHEDULE
E602 BLDG 42 - DISTRIBUTION DIAGRAM
E603 PRIMARY SINGLE LINE DIAGRAM
E604 SITE PHOTOGRAPHS
E605 MAIN LEVEL PLAN - ELECTRIC ROOM
E606 PANEL SCHEDULES
ED100 PARTIAL LOWER LEVEL - DEMOLITION PLAN
EL100 LOWER LEVEL FLOOR PLAN - LIGHTING
EL101A PARTIAL MAIN LEVEL FLOOR PLAN - LIGHTING
EL101B PARTIAL MAIN LEVEL FLOOR PLAN - LIGHTING
EL102 INTERSTITIAL LEVEL FLOOR PLAN - LIGHTING
EL103 ROOF PLAN
EP100 LOWER LEVEL FLOOR PLAN - POWER
EP101A PARTIAL MAIN LEVEL FLOOR PLAN - POWER
EP101B PARTIAL MAIN LEVEL FLOOR PLAN - POWER
EP102 INTERSTITIAL LEVEL FLOOR PLAN - POWER
ES100 PARTIAL SITE PLAN
ES101 PARTIAL SITE PLAN - TECHNOLOGY
ES102 PRIMARY DUCTBANK PROFILES
ET100 LOWER LEVEL FLOOR PLAN - TECHNOLOGY
ET101A PARTIAL MAIN LEVEL FLOOR PLAN - TECHNOLOGY
ET101B PARTIAL MAIN LEVEL FLOOR PLAN - TECHNOLOGY
ET102 INTERSTITIAL LEVEL FLOOR PLAN - TECHNOLOGY
ET200 BUILDING PLANS - BLDG 1, BLDG 2, BLDG 37, BLDG, 38
ET300 TUNNEL LEVEL BUILDING 42 - TECHNOLOGY
72" MH
D
D
J
72" MH
E4014
E401
4" FIRE RATED
SLEEVE ASSEMBLY
D D
AE
AP
1 265 12 26 6
212 6 2
13CCTV 13W AP
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:52:06 PM
/7
/2
:5
:0
P
M
ENLARGED TR ROOM PLAN Expand & Upgrade Building 42 for Laboratory
E401
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG JC
SCALE: 1/2" = 1'-0"
ENLARGED TELECOMMUNICATION ROOM - NEW TR
SCALE: 1/2" = 1'-0"
TELECOMMUNICATION ROOM - EAST ELEVATION
SCALE: 1/2" = 1'-0"
TELECOMMUNICATION ROOM - NORTH ELEVATION
SCALE: 1/2" = 1'-0"
TELECOMMUNICATION ROOM - WEST ELEVATION
4 SCALE: 1/2" = 1'-0"
TELECOMMUNICATION ROOM - SOUTH ELEVATION
SCALE: 1 1/2" = 1'-0"
TELECOMMUNICATION ROOM NEW TR - RACK ELEVATION
SHEET NOTES
1. FULL HEIGHT RELAY RACK
2. FULL HEIGHT, FRONT/REAR VERTICAL W IRE MANAGER
3. TELECOMMUNICATIONS GROUND BAR (TGB) W ITH TELECOMMUNCIATIONS BONDING BACKBONE (TBB)
TO EXISTING ELECTRICAL SERVICE GROUNDING ELECTRODE CONDUCTOR SYSTEM.
4. 3/4" X 8' HIGH TYPE A/C FIRE RATED PLYW OOD, PAINTED LIGHT GRAY.
5. 12" W IDE OVERHEAD LADDER RACK
6. PROVIDE CABLE DROP-OUTS OVER RACKS
7. 12" W IDE VERTICAL W ALL MOUNTED LADDER RACK W ITH "HOOK AND LOOP" CABLE TIES TO MANAGE
CABLE RISERS.
8. W ALL FIELD FOR DOOR CONTROL PANELS AND POW ER SUPPLIES.
9. W ALL FIELD FOR PAGING SYSTEM COMPONENTS.
10. 1RU HORIZONTAL, FRONT/REAR W IRE MANAGER PANEL.
11. 2RU HORIZONTAL, FRONT/REAR W IRE MANAGER PANEL.
12. 24 PORT DATA STATION CABLE PATCH PANEL.
13. 48 PORT DATA STATION CABLE PATCH PANEL.
14. 2RU FIBER TERMINATION CABINET W ITH "ST" BULKHEADS AND FIBER SPLICE TRAYS INTEGRAL TO
HOUSING.
15. NETW ORK ELECTRONICS BY VA.
16. RACK MOUNTED UPS BY VA.
17. CONDUIT EXTENSIONS W ITH NEW FIBER/COPPER/GROUNDING BACKBONE CABLING.
18. FIRE RATED, RE-ETERABLE SLEEVE ASSEMBLY (4" CONDUIT CAPACITY EQUIVALENT), REFER TO
DRAW INGS FOR QUANTITY.
19. W ALL MOUNTED EMERGENCY 2-W AY ELEVATOR COMMUNICATIONS SYSTEM MAIN CONTROLLER W ITH
POW ER SUPPLY. PROVIDE CONNECTION TO PHONE SYSTEM FOR REMOTE COMMUNICATIONS.
1. BALANCED MAGNETIC DOOR POSITION SW ITCH, DPDT. PROVIDE
2PR-#22AW G SHIELDED FROM DOOR FRAME TO LOCAL SECURITY
JUNCTION BOX ON SECURE SIDE OF DOOR.
2. PROVIDE 0.5" CONDUIT FROM DOOR FRAME TO COMMON SECURITY
JUNCTION BOX ON SECURE SIDE OF DOOR.
3. COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.
(12"X12"X4" W ITH SECURITY SCREW COVER).
4. PROVIDE PLENUM COMPOSITE DOOR SECURITY W IRING (EQUAL TO
BELDEN B658AFJ) FROM COMMON SECURITY JUNCTION BOX TO
BACKBOARD IN LOCAL SIGNALS CLOSET. ROVIDE 24" TAIL IN
JUNCTION BOX AND 5' SLACK AT BACKBOARD PRIOR TO
TERMINATION. CABLE TO BE PROPERLY SUPPORTED UTILIZING J-
HOOKS.
5. ELECTRONIC DOOR LOCK.
6. PROVIDE 0.75" CONDUIT FROM DOOR FRAME TO COMMON
SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.
7. REQUEST TO EXIT SENSOR IN THE HARDW ARE.
8. W ALL MOUNTED REQUEST TO EXIT MOTION SENSOR . PROVIDE 1-
GANG BOX W ITH 0.5" CONDUIT TO COMMON SECURITY JUNCTION
BOX ON SECURE SIDE OF DOOR. SENSOR BOX TO BE LOCATED ON
SECURE SIDE OF DOOR, DIRECTLY ABOVE THE DOOR FRAME.
9. W ALL MOUNTED CREDENTIAL READER. PROVIDE 1-GANG BOX AT 46"
MH (UNLESS OTHERW ISE NOTED) AND EXTEND 0.75" CONDUIT FROM
BOX TO COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF
DOOR.
10. LOCAL DOOR LOCK POW ER SUPPLY, MOUNT ABOVE CEILING,
EXTEND POW ER AND LOW VOLTAGE W IRING AS REQUIRED.
FINISH FLOOR
CEILING
NON-SECURE SIDESECURE SIDE
5 7
CR
SINGLE DOOR W ITH CARD READER ACCESS
ON ENTRY SIDE
JB
FINISH FLOOR
CEILING
NON-SECURE SIDESECURE SIDE
SINGLE DOOR W ITH DOOR MONITOR
FINISH FLOOR
CEILING
NON-SECURE SIDESECURE SIDE
2 2
DOUBLE DOOR W ITH CARD READER ACCESS
AND AUTO OPEN
CR
HA
FINISH FLOOR
CEILING
NON-SECURE SIDESECURE SIDE
2 2
DOUBLE DOOR W ITH CARD READER ACCESS
ENTRY
CR
7 7
JB
JB
JB
DETAIL NOTES
9/16" D
6/32" D (TYP. OF 6)
1-1/8" O.C.
9/32" D (TYP. OF 12)
1-1/8" O.C.
DETAIL NOTES
1. 4"x1/4"x10" MIN. LENGTH GROUNDING BAR.
ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND
CONNECTIONS.
2. W ALL MOUNTING BRACKET.
3. INSULATORS.
4. 5/8-11X1 H.H.C.S.
5. 5/8" LOCKW ASHER.
CAMERA MOUNTING DETAIL NOTES
INTERIOR - WALL MOUNTED EXTERIOR - WALL MOUNTED
INTERIOR - CEILING RECESSED INTERIOR - CEILING SURFACE
N O
M
INTERIOR CEILING
INTERIOR CEILING
1. CAMERA AS SHOW N ON THE PLANS, REFER TO CAMERA
SCHEDULE FOR SPECIFICATIONS.
2. W ALL MOUNTED PENDANT ARM FOR CAMERA.
3. 1-GANG BOX, SEALED FOR MOUNTING OF CAMERA.
4. 0.75" CONDUIT TO BE ROUTED TO ACCESSIBLE INTERIOR
JUNCTION BOX.
5. W IRING TO BE FOR CONNECTION TO CAMERA.
6. PROVIDE JUNCTION BOX ABOVE ACCESSIBLE CEILING.
7. PROVIDE 1-DATA OUTLET UTILIZING SURFACE MOUNT
"BISCUIT" FOR TERMINATION OF DATA DROP INTO RJ-45
OUTLET.
8. PATCH CABLE.
9. PROVIDE 20' COIL OF CABLE MANAGED ABOVE CEILING.
10. SURFACE CEILING MOUNTED JUNCTION BOX FOR CAMERA.
8 7 9
8 7
BLDG 37
TELEPHONE
ROOM
DATA
ROOM
BLDG 1
SUB-BASEMENT
BLDG 38
SUB-BASEMENT
BLDG 2
SUB-BASEMENT
GROUND FLOOR
BLDG 42
EXISTING
NEW LAB
ADDITION
STEAM TUNNEL
NEW SIGNALS
CLOSET
3 6
DETAIL NOTES
1. PROVIDE NEW 66 BLOCKS IN EXISTING RACK FRAME AND TERMINATE
NEW VOICE BACKBONE CABLING.
2. EXISTING VOICE BACKBONE RACK FRAME.
3. NEW 100 PAIR PLENUM RATED VOICE BACKBONE CABLE.
4. PROVIDE NEW FIBER TERMINATION CABINET IN EXISTING RACK AND
TERMINATE NEW FIBER BACKBONE CABLE.
5. EXISTING FIBER TERMINATION RACKS.
6. NEW 12 STRAND OM3 INDOOR/OUTDOOR, PLENUM RATED FIBER
BACKBONE CABLE. INSTALL IN INEW NNERDUCT.
7. EXISTING W ALL MOUNTED PULL BOX.
8. EXISTING EXTERIOR/UNDERGREOUND CONDUIT PATHW AY.
9. INSTALL CABLE IN EXISTING CABLE TRAY
10. PROVIDE NEW CONDUIT RISER FROM EXISTING TUNNEL UP INTO
EXISTING SUB-BASEMENT. REFER TO PLANS FOR QUANTITY/SIZES.
11. PROVIDE NEW CONDUIT PATHW AY FOR BACKBONE CABLING TO NEW
SIGNALS CLOSET. REFER TO PLANS FOR QUANTITY/SIZES.
12. NEW TELECOMMUNICATIONS GROUND BAR (TGB).
13. #3/0 AW G TELECOMMUNCIATIONS BONDING BACKBONE TO EXISTING
MAIN ELECTRICAL SERVICE GROUNDING ELECTRODE CONDUCTOR
SYSTEM.
AP
V
CATV
D
TYP.
DATA
P
DETAIL NOTES
1. SURFACE MOUNT UTP DATA JACK ABOVE ACCESSIBLE CEILING.
2. 1-GANG DEVICE BOX W ITH .75"C. TO CORRIDOR CABLETRAY.
3. 2-GANG DEEP DEVICE BOX W /SINGLE-GANG PLATE, 1.25"C TO CORRIDOR
CABLETRAY.
4. CONNECT TO LOCAL CATV DISTRIBUTION EQUIPMENT.
5. UTP DATA/VOICE JACK.
6. DEFAULT OUTLET IS 4-DATA.
7. RUN TO LOCAL DATA STATION CABLE TERMINATION EQUIPMENT.
8. DOUBLE DUPLEX RECEPTACLE.
9. CATV COAXIAL TYPE "F" CONNECTOR.
10. PROVIDE W ALL PLATE FOR MOUNTING OF W ALL PHONE.
11. ELECTRICAL OUTLETS.
12. MULTI-SERVICE, FIRE RATED POKE THRU.
13. BLANK INSERT.
DATA
DATA
DATA
A
B
A
A
B
B
5 5
4D
DATA DATA
7 7
BLANK
D
BLANK
DATA DATA
2D
DETAIL NOTES
1. EXISTING PAGING SYSTEM HEADEND.
2. EXTEND NEW PAGING SYSTEM LINE LEVEL SIGNAL
3. NEW PAGING SYSTEM LOCAL AMPLIFIER.
4. NEW PAGING SPEAKERS, REFER TO PLANS FOR QUANTITIES AND LOCAITONS.
5. PROVIDE REQUIRED 70V SPEAKER LEVEL CABLING
3 SC
S H
SC
S H
SC
NEW TR
EXIST HEADEND
AR
AR
AR
AR
AEAP
LOW ER LEVEL
1ST FLOOR
2ND FLOOR
ROOF
DIAGRAM NOTES
1. VERIFY SYSTEM ROUGH-IN REQUIREMENTS W ITH VENDOR PRIOR TO INSTALLATION
2. DEDICATED 20A-120V EMERGENCY CIRCUIT.
3. MAIN CONTROL PANEL INCLUDING CONNECTION TO PHONE SYSTEM.
4. POW ER SUPPLY
5. EMERGENCY 2-W AY COMMUNICATION SYSTEM ELEVATOR CALL STATION IN
ELEVATOR LOBBY W ITH BACKBOX, CONDUIT, AND W IRING.
6. NEW SIGNAL CLOSET.
1 5
1 5
1 5
1 5
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:52:26 PM
/7
/2
:5
:2
P
M
DETAILS Expand & Upgrade Building 42 for Laboratory
E501
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG JC
SCALE: NONE
SECURITY DOOR DETAILS
SCALE: NONE
GROUND BAR DETAIL
SCALE: NONE
IP CCTV MOUNTING DETAILS
SCALE: NONE
BACKBONE CABLING DIAGRAM
SCALE: NONE
TECHNOLOGY OUTLET FACEPLATE DETAILS
SCALE: NONE
PAGING SYSTEM EXPANSION
SCALE: NONE
EMERGENCY 2-WAY COMMUNICATION SYSTEM DIAGRAM
GROUNDING BAR DETAIL
NTS
(2 m m
(4 m m
(1")
25mm
(1")
25mm
(1")
25mm
(2")
51mm
(1 1/2") TYP
38mm
(1 m m
(5 8" m m
6.35mm (1/4") DIA.
MOUNTING HOLES
TYP. OF (4)
BASE CLAMP/
BRACKET
9.52mm (3/8") DIA.
HOLE TYP. OF (6)
9.52mm (3/8") x 16mm
(5/8") HEX HEAD BOLT
9.52mm (3/8") LOCK WASHER
9.52mm (3/8") FLAT WASHER & 9.52mm (3/8") LOCK WASHER
6.35mm (1/4")
THICK CU BAR
(2'-0") MIN
610mm
6.35mm (1/4") DIA.
HOLE TYP OF (8)
GENERAL NOTES:
1. ALL HARDWARE SHALL BE STAINLESS STEEL.
2. PROVIDE 1 MOUNTING POINT PER 305mm (12") OF BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
SECTION
STEEL EXPANSION
ANCHOR
INSULATOR
9.52mm (3/8") FLAT WASHER
(3'-0") MAX
CONDUIT EXPANSION JOINT CROSSING DETAIL-
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY
ACTUAL CONDITIONS &
LOCATIONS.FLOOR OR ROOF STRUCTURE.
FIELD VERIFY ACTUAL
CONDITIONS, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
SD260533-03, TYP.
914mm
BEAM
CLAMP, TYP.
CONDUIT,
TYP.
PROVIDE 127mm (5") OF SLACK AT
MIDPOINT BETWEEN TWO END OF
FLEXIBLE GALVANIZED STEEL CONDUIT.
PROVIDE GREEN INSULATED COPPER
EQUIPMENT GROUNDING CONDUCTOR
WITH FLEXIBLE CONDUIT.
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
STEEL
EXPANSION
ANCHOR
JUNCTION BOX (SIZE
AS REQUIRED)
CONDUIT FITTING
SPRING NUT
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
FLEXIBLE CONDUIT
NTS
GENERAL NOTE:
1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").
(3'-0") MAX
CONDUIT EXPANSION JOINT CROSSING DETAIL-
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY
ACTUAL CONDITIONS &
LOCATIONS.FLOOR OR ROOF STRUCTURE.
FIELD VERIFY ACTUAL
CONDITIONS, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
SD260533-03, TYP.
914mm
BEAM
CLAMP, TYP.
CONDUIT,
TYP.
EXPANSION FITTING
WITH BONDING JUMPER
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
STEEL
EXPANSION
ANCHOR
JUNCTION BOX (SIZE
AS REQUIRED)
CONDUIT FITTING
SPRING NUT
HEAD
INSULATING
BUSHING
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
EXPANSION FITTING
NTS
GENERAL NOTES:
1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL SD260533-01.
2. INSTALLATION IS REQUIRED FOR CONDUIT 76mm (3") AND LARGER.
LENGTH AS REQUIRED
CONDUIT TRAPEZE MOUNTING DETAIL
NTS
CONDUIT CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
FLOOR SLAB PENETRATION DETAIL
NTS
CONDUIT, TYP MINERAL WOOL
(FIRMLY PACKED)
FIRESTOP SEALANT
PER SECTION 07 84 00,
FIRESTOPPING
9.52mm
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT, TYP
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, TYP.
FLOOR SLAB,
TYP.
STEEL EXPANSION
ANCHOR, TYP
(3/8") MAX
PLASTIC
SPACER
INNERDUCT, SEE
NOTE 5
DUCT [SIZE AS
INDICATED ON
DWGS.]
6-WAY DUCT LINE 4-WAY DUCT LINE
2-WAY DUCT LINE
GENERAL NOTES:
1. CONCRETE SHALL BE 3000 P.S.I. @ 28 DAYS, OR AS SPECIFIED, DYED
RED.
2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41. REFER TO DUCT BANK
PROFILES FOR APPROXIMATE DEPTH.
4. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
5. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS. 4" SCHEDULE
40 PVC U.N.O.
DUCT BANK DETAILS
NTS
TIE WIRE
(3")
(3")
76mm
3" m m
3" m m
76mm
(3")
76mm
(3 m m m
(3 m m
(3") (3")
76mm (3")
76mm 76mm m m m m
76mm
(3")
76mm
(3") (3")
76mm
152mm
(6")(SEE NOTE 4)
(T Y
P
1' -6
FINISH GRADEMARKER TAPEMARKER TAPE
1' -6
FINISH GRADE
1' -6
FINISH GRADEMARKER TAPE
2' -3
C
O V
E R
2' -3
C
O V
E R
2' -3
C
O V
E R
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:52:37 PM
/7
/2
:5
:3
P
M
DETAILS Expand & Upgrade Building 42 for Laboratory
E502
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
POWER MANHOLE DETAILS
NTS
TOP VIEW
SECTION "A-A"
POWER
SECTION "B-B"
S
LO
P E
SL
O
PE
SLOPE
305x305mm (12"x12") SUMP
A
A
B B
PULLING
IRON
CONC.
ENVELOPE
GROUND ROD
SLEEVE
PULLING IRON CABLE STANCHION PER
SECTION 26 05 41.
305mm (12") SUMP
SUMP FRAME &
COVER
GRADE RINGS AS REQ'D TO MATCH CIVIL
FINISHED GRADE ELEVATION.
CABLE STANCHION
GENERAL NOTE:
1. INCLUDE ALUMINUM LADDER (NOT
SHOWN FOR CLARITY).
2. REFER TO DUCT BANK PROFILES FOR
COLLAR DEPTH. MANHOLE DEPTH MAY
NEED TO BE DEEPER BASED ON
PROFILES. ADJUST ACCORDINGLY.
REFER TO DUCTBANK
PROFILES
FINISHED
GRADE
GROUND ROD PER
SECTION 26 05 26.
0.764 CUBIC METERS
(1 CUBIC YARD) 19mm
(3/4") GRAVEL SUMP
V A
R
IE
S
(5'-0")
1930mm
(6'-4")
(8")
1524mm 203mm
8"
3m m
(6
2m m
5m m
(1 2"
M
IN
3m m
(8
1524mm
(5'-0")
3m m
(8
(1 0'
-0
965mm965mm
(3'-2")
1930mm
(6'-4")
(3'-2")
(5 '-6
(3
'-1 0"
(9 '-4 m m m m m m
(3")
76mm
(8 '-0
8"
3m m (9
'-4
(8
3m m m m m m
3'
-0
5m m915mm
(3'-0")
(4) CONCRETE BRICKS
51mmx203mmx406mm (2"x8"x16")
CONDUIT(S) WITH BELL ENDS
(TYP). SIZE, QUANTITY AND
WIRING AS INDICATED ON
PLANS
CLEAN 19mm (3/4")
CRUSHED ROCK
GRADE. FEATHER & TAMP BACKFILL
TO CREATE FLUSH INSTALLATION
AND POSITIVE DRAINAGE AWAY
FROM BOX
VA
R
IE
S
(1 2"
PULLBOX (SEE SPECIFICATIONS)
LINE SIDES OF EXCAVATION
WITH 13.6 KG (30 LBS.) FELT
PAPER
(12")
5m m
305mm
UNDERGROUND CONCRETE PULLBOX -
TURF AREAS
NTS
LUMINAIRE MOUNTING - LAY-IN CEILING
NTS
LUMINAIRE
SUSPENSION WIRES
REFER TO
SPECIFICATION
SECTION 26 51 00
3 TWIST MINIMUM
(TYP)
FIXTURE WHIP FROM
JUNCTION BOX
(1829mm (6') LONG
MAX.)
LUMINAIRE. REFER TO SCHEDULE
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
REFER TO SPECIFICATION SECTION
26 51 00
ACOUSTICAL CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER TO SCHEDULE
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
EXIT SIGN MOUNTING - LAY-IN CEILING
NTS
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING TILE (TYP)
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION 26
51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
ARCHITECTURAL
CEILING GRID
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
FIXTURE WHIP FROM JUNCTION BOX
(1829mm (6') LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
CONDUIT ROOF PENETRATION DETAIL
NTS
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE
PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
PREFABRICATED RUBBER
BOOT CAP WITH GRADUATED
STEPS & WEATHER-PROOF
PRESSURE SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE BY
ROOFING CONTRACTOR MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF ROOF
BY ROOFING CONTRACTOR. PRIME
FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED 1.52mm
(0.06") THICK ALUMINUM FLASHING
ROUND COLLAR WITH MIN. 76mm
(3") WIDE FLANGE. ATTACH TO
ROOF PER MANUFACTURER'S
INSTRUCTIONS
CONDUIT CLAMP. SIZE AS
REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
STAINLESS CLAMP, TYP.
9.52mm (3/8")
MIN
GALVANIZED
THREADED ROD,
TYP.
SEAL-OFF
FITTING,
TYP.
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
CONDUIT,
TYP.
CONDUIT
CLAMP. SIZE AS
REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT
EQUIPMENT GROUND CONDUCTOR
MANHOLE COVER FRAME
GROUND CONNECTION
#6 STRANDED BARE CU
CABLE (TYP)
DUCT BANK
CABLE PULLING
IRONS
#3/0 STRANDED
BARE CU COMPLETE
RING.
EXOTHERMIC
WELD CONNECTION
GROUND ROD PER SECTION
26 05 26
SUMP
FRAME
BRAIDED SHIELD
DRAIN WIRES (TYP)
EMBED CHANNEL
OR CABLE RACK
(TYP)
EXOTHERMIC
WELD
CONNECTION
(TYP)
CABLE CLIP
(TYP)
DRILL AND
TAP GROUND
CONNECTION
MANHOLE GROUNDING DETAILS
NTS
CABLE SPLICES
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:52:51 PM
/7
/2
:5
:5
P
M
DETAILS Expand & Upgrade Building 42 for Laboratory
E503
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS