This is a solicitation document, number 36C25520R0073, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15, for the expansion and upgrade of Building 42 to accommodate new laboratory facilities at the Marion VA Medical Center. The solicitation seeks general contractor services including construction of an approximately 15,000 square foot addition to the existing building, as well as renovations and upgrades to existing spaces. The work includes structural, interior demolition and construction, mechanical, electrical and low voltage systems. The period of performance is 420 calendar days from NTP. Responses are due by 2:00 PM Eastern on November 8, 2019 and the contract is to be awarded by January 15, 2020. Pricing is to be provided as a firm fixed price with unit prices for additional work. No set-asides or preferences are specified.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM SYMBOLS

FIRE ALARM BELL & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT

SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH BOTTOM OUTLET CONTROLLED BY W ALL SW ITCH. (18" MH UNLESS

NOTED OTHERW ISE).

20A-125V TAMPER RESISTANT DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).

20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH

STANDARD COVER, VERTICAL MOUNT.

20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH

UNLESS NOTED OTHERW ISE), W ITH STANDARD COVER, VERTICAL MOUNT.

20A-125V POW ERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERW ISE).

20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R. PROVIDE CARPET FLANGE W HERE REQUIRED.

20-125V DUPLEX RECEPTACLE, NEMA 5-20R, W ITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERW ISE).

20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERW ISE).

30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERW ISE).

50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERW ISE).

20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERW ISE).

30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERW ISE).

50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERW ISE).

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED

OTHERW ISE).

CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERW ISE).

SINGLE POLE SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

TW O POLE W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

MULTI-W AY W ALL SW ITCH, # INDICATES NUMBER OF W AYS (46" MH UNLESS NOTED OTHERW ISE).

SW ITCH W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERW ISE).

KEY OPERATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

LIGHTING DIMMER SW ITCH (46" MH UNLESS NOTED OTHERW ISE) 1000 W ATTS UNLESS OTHERW ISE INDICATED.

SW ITCH W ITH RECEPTACLE (46" MH UNLESS NOTED OTHERW ISE) STANDARD TW O-GANG ASSEMBLY OF SW ITCH AND

RECEPTACLE.

FLUSH FRACTIONAL HORSEPOW ER MOTOR STARTER W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS

NOTED OTHERW ISE).

HP RATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

DISCONNECT SW ITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.

PULL BOX.

LINE VOLTAGE THERMOSTAT.

UNIT HEATER.

FAN COIL.

ELECTRIC BASEBOARD HEATER.

AIR CONDITIONER.

CONDENSING UNIT.

UNIT VENTILATOR.

CORD REEL.

POW ER POLE.

PHOTOELECTRIC SENSOR.

LIGHTING CONTACTOR.

CEILING MOUNTED OCCUPANCY SENSOR.

W ALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POW ER PACK.

FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS

NOT SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.

FIRE ALARM CHIME & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS

NOT SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.

FIRE ALARM HORN & SIGNAL LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT

SHOW N, THE STROBE SHALL BE RATED 75 CANDELA.

FIRE ALARM SIGNALING LIGHT (80" AFF), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT

SHOW N, THE STROBE SHALL BE RATED 75.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERW ISE). SUBSCRIPT "K" INDICATES KEY OPERATED.

CEILING MOUNTED SMOKE DETECTOR.

CEILING MOUNTED HEAT DETECTOR.

DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

ELECTRIC RELEASE DOOR CLOSER.

ELECTRO-MAGNETIC DOOR HOLDER.

W ATER FLOW SW ITCH.

VALVE SUPERVISORY SW ITCH.

DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATOR LIGHT. SUBSCRIPT "W " INDICATES W ALL

MOUNTED.

SMOKE DAMPER.

FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERW ISE).

PUSHBUTTON (46" MH UNLESS NOTED OTHERW ISE).

BUZZER (90" MH UNLESS NOTED OTHERW ISE) EDW ARDS 340-A (120 VOLT).

4" DIAMETER (90" MH UNLESS NOTED OTHERW ISE).

TR

WP

WP/GF

T

IG

20A

30A

50A

20A

50A

30A

J

P

K

DM

R

H

UH

FC

AC

CU

UV

PP

OS

M

OS

M

DS

OP

PC

T

F

F

F

F

S F

CEILING MOUNTED FIRE ALARM SPEAKER.

KF

S M

H

C

D

FS

V

R W

SD

FT

B

PRESSURE SW ITCH.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

KNOX BOX.

PS

AM

C/I

PIV

K

FIRE ALARM CONTROL PANEL.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).

C

M

CR

LC

P/B

H

S S/R

S/R

ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERW ISE) W ITH RESET SW ITCH (46" MH UNLESS NOTED

OTHERW ISE).

INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W " INDICATES W ALL MOUNT (46" MH

UNLESS NOTED OTHERW ISE).

INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERW ISE).

INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERW ISE).

INTERCOM SPEAKER FLUSH MOUNT IN CEILING.

I

M

H

S

FACP

AV SYMBOLS WITH ELECTRICAL REQUIREMENTS

S H

SURFACE MOUNTED PAGING/INTERCOM SPEAKER (90" MH UNLESS NOTED OTHERW ISE). SUBSCRIPT "H" INDICATES HANGING CEILING SPEAKER. 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SPEAKER, INSTALLATION AND CABLING PER DIV 27.

MUSIC PLAY BACK SPEAKER (102" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION ADJACENT TO BOX AND W IRING PER

DIV 27.

S M

S HORN TYPE PAGING/INTERCOM SYSTEM SPEAKER (90" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION AND W IRING PER DIV 27.

DUCT HEATER.H

DH

H

EB

LOW -VOLTAGE MOMENTARY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

L

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

CC

CCTV SYSTEM W ALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE

ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.

PS

LOCAL LOW VOLTAGE POW ER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA. 120V POW ER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POW ER SUPPLY PER DIV 26. POW ER SUPPLY

MOUNTED ABOVE CEILING AND LOW VOLTAGE W IRING TO LOCAL CAMERA PER DIV 28.

IC

W ALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO

ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.

DM

DOOR POSITION SW ITCH W ITH W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR

OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.

EL

ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY

ROUGH-IN DETAILS.

EM

ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN

DETAILS.

ES

ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN

DETAILS.

LB

RX

REQUEST TO EXIT SW ITCH IN DOOR HARDW ARE BY OTHERS. LOW VOLTAGE W IRING PER DIV 28. CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY

ROUGH-IN DETAILS.

HD

HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POW ER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE W IRING AND INTERFACE W ITH SMS AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.

HA

W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER W ITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE W IRING AND INTERFACE W ITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY

ROUGH-IN DETAILS.

HO

FA

W ALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN W ITH POW ER SUPPLY INSTALLED BY OTHERS. 120V POW ER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE W IRING FROM POW ER SUPPLY TO HOLD OPEN AND INTERFACE W ITH SMS PER DIV 28. SUBSCRIPT "FA" INDICATES DEVICES POW ERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM REQUIRED FOR DOOR RELEASE PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.

CR EL

W ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER

TO SECURITY ROUGH-IN DETAILS.

CR EL

ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED W ITH ELEVATOR CONTRACTOR. W IRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE W ITH ELEVATOR CONTROLLER AND SMS PER DIV 28, COORDINATE W ITH ELEVATOR

CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.

KC

W ALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERW ISE). 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.

K W ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYPAD AND CABLING PER DIV 28.

MD

W ALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. MOTION DETECTOR, W ALL MOUNT HARDW ARE, AND CABLING PER DIV 28.

PP W

W ALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO

ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.

X W ALL MOUNTED SECURITY SYSTEM W IRING OUTLET MOUNTED BELOW COUNTER TOP. 2-GANG BOX W ITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE AND SECURITY

SYSTEM CABLING PER DIV 28.

CM

W ALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 1" CONDUIT TO ABOVE CORRIDOR CEILING PER DIV 26. JACK, FACEPLATE AND CABLING PER DIV 28.

MIC

CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. 1-GANG BOX MOUNTED IN CEILING PER DIV 26.

M ICROPHONE AND CABLING PER DIV 28.

BR

W ALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERW ISE). 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. READER AND CABLING PER DIV 28. REFER TO

SECURITY ROUGH-IN DETAILS.

X

X

MD

PB W

W ALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERW ISE). 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.

ELECTRONIC LATCH BOLT MONITORING. HARDW ARE AND INSTALLATION BY OTHERS. LOW VOLTAGE W IRING PER DIV 28.

CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SECURITY JUNCTION BOX ABOVE CEILING PER DIV 26. REFER TO

SECURITY ROUGH-IN DETAILS.

CEILING MOUNTED MOTION DETECTOR. 1-GANG BOX MOUNTED IN CEILING PER DIV 26. DETECTOR AND CABLING PER

DIV 28.

DC

LOCAL IP BASED 2-DOOR ACCESS CONTROL PANEL SERVING LOCAL CARD READER/SECURITY CONTROLLED DOORS.

LOCATE ABOVE ADJACENT ACCESSIBLE CEILING. PROVIDE DATA DROP IN 0.75" CONDUIT TO LOCAL DATA CLOSET.

EXTEND 1" CONDUIT W ITH DOOR SECURITY W IRING TO LOCAL SECURITY SYSTEM JUNCTION BOX. REFER TO SECURITY

ROUGH-IN DETAILS.

JB M

SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY W IRING CONDUITS/RACEW AYS TO JUNCTION BOX. EXTEND 1" CONDUIT W ITH DOOR SECURITY W IRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAW INGS. REFER TO SECURITY

ROUGH-IN DETAILS.

PL

SITE POLE FOR MOUNTING SECURITY CAMERAS (REFER TO SPECIFICATIONS FOR SIZE/TYPE). PROVIDE POLE W ITH CONCRETE BASE AS INDICATED ON PLANS. EXTEND AND CONNECT TO SITE CONDUIT SYSTEM AS INDICATED ON PLANS.

PROVIDE NEMA 3R JUNCTION BOX AT BASE OF POLE FOR CAMERA EQUIPMENT (120V POW ER SUPPLY, FIBER

CONVERTERS, ETC.). REFER TO SECURITY ROUGH-IN DETAILS.

TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS

P W ALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.

X R

W ALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.

X V

W ALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.

CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU W ALL (1-2" SLEEVE UNLESS NOTED OTHERW ISE) PER DIV 26.

J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.

D W ALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.

X I

W ALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUITS TO ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES

ALTERNATE CONFIGURATION.

AP

W ALL MOUNTED W IRELESS ACCESS POINT (96” MH UNLESS NOTED OTHERW ISE). BOX W ITH CONDUIT TO ABOVE

ACCESSIBLE CEILING PER DIV 26. W AP AND CABLE PER DIV 27.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SW ITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTW N - BETW EEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOW N

DW G - DRAW ING

EA - EACH

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

EX/R - EXISTING TO BE REMOVED AND RE-INTSALLED.

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)

FT - FEET

FTG - FOOTING

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFB - GROUND FAULT BREAKER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC CONTRACTOR (DIVISION 23)

HP - HORSE POW ER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OW NER FURNISHED CONTRACTOR INSTALLED

OFOI - OW NER FURNISHED OW NER INSTALLED

PC - PLUMBING CONTRACTOR (DIVISION 22)

PLBG - PLUMBING

PX - PYXIS

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY CONTRACTOR

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY CONTRACTOR

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TR - TAMPER RESISTANT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W / - W ITH

W /0 - W ITHOUT

W P - W EATHERPROOF

ZVC - ZONE VALVE CABINET

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET W HERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

W IRE & CONDUIT IN W ALL OR ABOVE CEILING.

W IRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES

CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.

CONDUIT FOR DATA CIRCUITRY.DAT

W IRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

W IRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING W IRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

W IRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

W IRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

W IRE RUN IN SURFACE W IREW AY.W

CABLE MANAGEMENT SYSTEM PATHW AY.CM

X - 1,2

W IRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

W IRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

W IRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

W IRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES

SW ITCHING ARRANGEMENT.

LIGHTING FIXTURE ON LIFE SAFETY CIRCUIT.

EXIT LIGHTING FIXTURE ON LIFE SAFETY CIRCUIT, ARROW S AS INDICATED.

A a

W IREMOLD RACEW AY, AS NOTED ON PLANS.

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.

4"

4"

4"

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERW ISE).

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

LIGHTING FIXTURE ON CRITICAL CIRCUIT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

FOUR 20A-125V RECEPTACLES, NEMA 5-20R AND FOUR DATA JACK KEYSTONE OPENINGS. FIRE RATED POKE-THRU W ITH

ROUND COVER PLATE. PROVIDE CARPET FLANGE W HERE REQUIRED.

MULTI-SERVICE POKE THRU PER DIV 26. PROVIDE APPROPRIATE CONNECTOR PLATE AND OVER. SUBSCRIPT "4D"

INDICATES # OF DATA. REFER TO FACEPLATE DETAILS.

4D

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERW ISE).

GF

1. ALL EXISTING UNDERGROUND UTILITIES ARE TO BE MARKED AND DEPTH LOCATED IN AREAS W HERE NEW DUCTBANKS, UTILITIES, FOOTERS, ETC. ARE TO CROSS BY A THIRD PARTY LOCATING SERVICE.

2. INSTALL NEW DUCTBANKS AND MANHOLES, ASSOCIATED W ITH THE NEW 12KV FEEDERS.

3. SCHEDULE OUTAGE FOR NEW DUCTBANK TIE-INS TO EXISTING MANHOLES.

4. START ALL CAMPUS EMERGENCY GENERATORS AND TRANSFER BUILDING LOAD TO PREPARE FOR OUTAGE.

5. DE-ENERGIZE MAIN CAMPUS 12KV BREAKER. DISCONNECT FEEDER SPLICES SERVING M.H. #4A AND RE-ENERGIZE

CAMPUS POW ER. THIS W ORK SHALL BE PERFORMS IN NO MORE THAN 4 HOURS. SHUT DOW N ALL EM GENERATORS EXCEPT BUILDINGS 8, 42, 43, 81, 82 AND 83. PERFORM THIS W ORK DURING NONPEAK HEATING OR COOLING SEASON.

6. BUILDINGS 8, 42, 43, 81, 82 AND 83 (US-A, US-B) ARE NOW DE-ENERGIZED. COMPLETE NEW DUCTBANK IN MH #4A, 4B, MH #4B AND CONDUITS INTO UNIT SUBS A & B. PULL M.V. CABLE TERMINATE AND TEST. REMOVE ABANDON CABLE.

THIS W ORK SHALL BE PERFORMED IN NO MORE THAN 24 HOURS.

7. START ALL CAMPUS EMERGENCY GENERATORS AND TRANSFER BUILDING LOAD TO PREPARE FOR OUTAGE.

8. DE-ENERGIZE MAIN CAMPUS 12KV BREAKER. RE-CONNECT FEEDER SPLICES SERVING M.H. #4A AND RE-ENERGIZE

CAMPUS POW ER. THIS W ORK SHALL BE PERFORMS IN NO MORE THAN 4 HOURS. SHUT DOW N ALL EM GENERATORS.

PERFORM THIS W ORK DURING NONPEAK HEATING OR COOLING SEASON.

9. VERIFY ALL BUILDINGS HAVE RETURNED TO UTILITY POW ER.

A. SEQUENCE OF CONSTRUCTION INDICATED ON THIS SHEET IS ONE POSSIBLE SOLUTION TO MINIMIZE DOW NTIME OF THE BUILDING ELECTRICAL SYSTEM. CONTRACTOR IS REQUIRED TO SUBMIT FOR APPROVAL A DETAILED SEQUENCE OF CONSTRUCTION NARRATIVE THAT INCLUDES ALL ANTICIPATED OUTAGES AND DURATIONS TO THE COR/ENGINEER W ITHIN 60 DAYS FROM NOTICE TO PROCEED. DEVIATIONS FROM THE FOLLOW ING PROPOSED SEQUENCE OF CONSTRUCTION W ILL BE REVIEW ED, BUT W ILL NOT BE GROUNDS FOR ADDITIONAL COST TO THE GOVERNMENT.

CONTRACTOR SHALL SCHEDULE REVIEW MEETINGS W ITH THE COR/ENGINEER PRIOR TO ANY OUTAGE. CONTRACTOR

SHALL OBTAIN W RITTEN APPROVAL FROM THE COR PRIOR TO ANY OUTAGE.

B. ALL CUTOVER W ORK REQUIRING BUILDING ELECTRICAL SYSTEM OUTAGES AND/OR EMERGENCY SYSTEM DOW NTIME SHALL BE DONE OUTSIDE OF NORMAL W ORKING HOURS (NIGHTS/W EEKENDS) AND OUTSIDE OF PEAK HEATING/COOLING SEASON AND SHALL BE COORDINATED W ITH COR A MINIMUM OF 4 W EEKS PRIOR TO OUTAGE.

OUTAGES OF ALL TYPES SHALL BE AS MINIMAL AS POSSIBLE.

C. W ORK PERFORMED INSIDE OF MANHOLES REQUIRE ALL FEEDERS INSIDE THE MANHOLE TO BE DE-ENERGIZED. FIELD VERIFY ALL CIRCUIT NUMBERS AND SOURCES INSIDE OF MANHOLES PRIOR TO SCHEDULING OUTAGES. VERIFY ALL CIRCUITS ARE DE-ENERGIZED INSIDE OF THE MANHOLE PRIOR TO PERFORMING W ORK. ROUTING OF ALL EXISTING 12KV

FEEDERS SHALL BE VERIFIED.

D. AT THE CONCLUSION OF EACH OUTAGE THE NEW 12KV FEEDER CABLES SHALL BE COILED INSIDE OF THE NEAREST MANHOLE AND ALL MANHOLE COVERS SHALL BE RE-INSTALLED. UNDER SPECIAL CIRCUMSTANCES W HERE CABLES CANNOT BE COILED INTO THE MANHOLE THE AREA SHALL BE TEMPORARILY BARRICADED TO PREVENT PEDESTRIAN ACCESS AND MARKED W ITH BARRICADE TAPE READING “DANGER HIGH VOLTAGE”. CABLE SPOOLS AND ASSOCIATED MANHOLES SHALL ALSO BE BARRICADED TO PREVENT PEDESTRIAN ACCESS AND MARKED W ITH THE AFOREMENTIONED

BARRICADE TAPE. NO MORE THAN 2 MANHOLES SHALL BE OPENED AT ONE TIME.

E. PHASES BELOW DO NOT CORRESPOND W ITH PROJECT PHASES AND ARE USED FOR REFERENCE ONLY.

F. CONTRACTOR SHALL VERIFY SUFFICIENT FUEL (PROVIDED BY VA) IS PRESENT IN GENERATORS PRIOR TO ALL

OUTAGES. VA W ILL SUPPLY FUEL FOR RUNNING EXISTING EMERGENCY GENERATORS, CONTRACTOR SHALL SUPPLY

FUEL FOR RUNNING TEMPORARY GENERATORS.

G. PROVIDE A STAND-BY TEMPORARY EMERGENCY GENERATOR ONSITE DURING ALL NORMAL POW ER OUTAGES W HERE THE BUILDING IS RUNNING SOLELY ON AN EMERGENCY GENERATOR INCASE THE PRIMARY GENERATOR FAILS.

TEMPORARILY CABLE THE STAND-BY GENERATOR TO REPLACE THE FAILED GENERATOR UNTIL REPAIRS CAN BE MADE.

H. W HERE INCLUDED IN THE SEQUENCE OF CONSTRUCTION, BARRICADES SHALL CONSIST OF AT A MINIMUM A 6' HIGH TEMPORARY CONSTRUCTION CHAIN-LINK FENCE SURROUNDING THE BARRICADED AREA AND SHALL DISPLAY

APPROPRIATE CONSTRUCTION SIGNAGE.

I. ALL OPEN MANHOLES SHALL BE MANNED BY A QUALIFIED INDIVIDUAL.

J. ALL LABELS FOR FEEDERS IN MANHOLES SHALL BE INSTALLED DURING SCHEDULED OUTAGES AND SHALL NOT

REQUIRE AN ADDITIONAL OUTAGE FOR THEIR INSTALLATION.

K. TRAFFIC CONTROL W HERE REQUIRED SHALL BE PROVIDED.

L. TERMINATION KITS SHALL BE INSTALLED PRIOR TO SHUT-DOW NS W HERE FEASIBLE.

M. LOCK OUT TAG OUT PROCEDURES SHALL BE FOLLOW ED PER CAMPUS STANDARDS. CONTRACTOR SHALL INCLUDE 24

HOURS A DAY / 7 DAYS A W EEK CONTACT INFORMATION W ITH AN ON-SITE RESPONSE TIME OF 30 MINUTES OR LESS.

12 KV FEEDER WORK PHASING

SEQUENCE OF CONSTRUCTION

GENERAL NOTES

SC RECESSED CEILING PAGING SPEAKER W ITH W IRING.

AR EMERGENCY 2-W AY COMMUNICATION SYSTEM ELEVATOR CALL STATION. PROVIDE STATION, W ITH OUTLET BOX AND

CONDUIT TO ABOVE CEILING AND CABLING TO MASTER STATION AS REQUIRED.

AM EMERGENCY 2-W AY COMMUNICATION SYSTEM MASTER STATION, DESK MOUNTED. PROVIDE STATION, W ITH BOX AND

CONDUIT TO ABOVE CEILING AND CABLING TO MAIN CONTROLLER AS REQUIRED.

AE EMERGENCY 2-W AY COMMUNICATION SYSTEM MAIN CONTROLLER W ITH POW ER SUPPLY, W ALL MOUNTED. PROVIDE

CABLING TO MASTER STATION AND REMOTE STATIONS AS REQUIRED.

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:51:37 PM

/7

/2

:5

:3

P

M

LEGEND, SYMBOLS & INDEX OF

DRAWINGS

Expand & Upgrade Building 42 for Laboratory

E001

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

INDEX OF DRAWINGS

Sheet Number Sheet Name

E001 LEGEND, SYMBOLS & INDEX OF DRAWINGS

E401 ENLARGED TR ROOM PLAN

E501 DETAILS

E502 DETAILS

E503 DETAILS

E601 SCHEDULES

E601a LIGHTING SCHEDULE

E601b LIGHTING SCHEDULE

E602 BLDG 42 - DISTRIBUTION DIAGRAM

E603 PRIMARY SINGLE LINE DIAGRAM

E604 SITE PHOTOGRAPHS

E605 MAIN LEVEL PLAN - ELECTRIC ROOM

E606 PANEL SCHEDULES

ED100 PARTIAL LOWER LEVEL - DEMOLITION PLAN

EL100 LOWER LEVEL FLOOR PLAN - LIGHTING

EL101A PARTIAL MAIN LEVEL FLOOR PLAN - LIGHTING

EL101B PARTIAL MAIN LEVEL FLOOR PLAN - LIGHTING

EL102 INTERSTITIAL LEVEL FLOOR PLAN - LIGHTING

EL103 ROOF PLAN

EP100 LOWER LEVEL FLOOR PLAN - POWER

EP101A PARTIAL MAIN LEVEL FLOOR PLAN - POWER

EP101B PARTIAL MAIN LEVEL FLOOR PLAN - POWER

EP102 INTERSTITIAL LEVEL FLOOR PLAN - POWER

ES100 PARTIAL SITE PLAN

ES101 PARTIAL SITE PLAN - TECHNOLOGY

ES102 PRIMARY DUCTBANK PROFILES

ET100 LOWER LEVEL FLOOR PLAN - TECHNOLOGY

ET101A PARTIAL MAIN LEVEL FLOOR PLAN - TECHNOLOGY

ET101B PARTIAL MAIN LEVEL FLOOR PLAN - TECHNOLOGY

ET102 INTERSTITIAL LEVEL FLOOR PLAN - TECHNOLOGY

ET200 BUILDING PLANS - BLDG 1, BLDG 2, BLDG 37, BLDG, 38

ET300 TUNNEL LEVEL BUILDING 42 - TECHNOLOGY

72" MH

D

D

J

72" MH

E4014

E401

4" FIRE RATED

SLEEVE ASSEMBLY

D D

AE

AP

1 265 12 26 6

212 6 2

13CCTV 13W AP

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:52:06 PM

/7

/2

:5

:0

P

M

ENLARGED TR ROOM PLAN Expand & Upgrade Building 42 for Laboratory

E401

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG JC

SCALE: 1/2" = 1'-0"

ENLARGED TELECOMMUNICATION ROOM - NEW TR

SCALE: 1/2" = 1'-0"

TELECOMMUNICATION ROOM - EAST ELEVATION

SCALE: 1/2" = 1'-0"

TELECOMMUNICATION ROOM - NORTH ELEVATION

SCALE: 1/2" = 1'-0"

TELECOMMUNICATION ROOM - WEST ELEVATION

4 SCALE: 1/2" = 1'-0"

TELECOMMUNICATION ROOM - SOUTH ELEVATION

SCALE: 1 1/2" = 1'-0"

TELECOMMUNICATION ROOM NEW TR - RACK ELEVATION

SHEET NOTES

1. FULL HEIGHT RELAY RACK

2. FULL HEIGHT, FRONT/REAR VERTICAL W IRE MANAGER

3. TELECOMMUNICATIONS GROUND BAR (TGB) W ITH TELECOMMUNCIATIONS BONDING BACKBONE (TBB)

TO EXISTING ELECTRICAL SERVICE GROUNDING ELECTRODE CONDUCTOR SYSTEM.

4. 3/4" X 8' HIGH TYPE A/C FIRE RATED PLYW OOD, PAINTED LIGHT GRAY.

5. 12" W IDE OVERHEAD LADDER RACK

6. PROVIDE CABLE DROP-OUTS OVER RACKS

7. 12" W IDE VERTICAL W ALL MOUNTED LADDER RACK W ITH "HOOK AND LOOP" CABLE TIES TO MANAGE

CABLE RISERS.

8. W ALL FIELD FOR DOOR CONTROL PANELS AND POW ER SUPPLIES.

9. W ALL FIELD FOR PAGING SYSTEM COMPONENTS.

10. 1RU HORIZONTAL, FRONT/REAR W IRE MANAGER PANEL.

11. 2RU HORIZONTAL, FRONT/REAR W IRE MANAGER PANEL.

12. 24 PORT DATA STATION CABLE PATCH PANEL.

13. 48 PORT DATA STATION CABLE PATCH PANEL.

14. 2RU FIBER TERMINATION CABINET W ITH "ST" BULKHEADS AND FIBER SPLICE TRAYS INTEGRAL TO

HOUSING.

15. NETW ORK ELECTRONICS BY VA.

16. RACK MOUNTED UPS BY VA.

17. CONDUIT EXTENSIONS W ITH NEW FIBER/COPPER/GROUNDING BACKBONE CABLING.

18. FIRE RATED, RE-ETERABLE SLEEVE ASSEMBLY (4" CONDUIT CAPACITY EQUIVALENT), REFER TO

DRAW INGS FOR QUANTITY.

19. W ALL MOUNTED EMERGENCY 2-W AY ELEVATOR COMMUNICATIONS SYSTEM MAIN CONTROLLER W ITH

POW ER SUPPLY. PROVIDE CONNECTION TO PHONE SYSTEM FOR REMOTE COMMUNICATIONS.

1. BALANCED MAGNETIC DOOR POSITION SW ITCH, DPDT. PROVIDE

2PR-#22AW G SHIELDED FROM DOOR FRAME TO LOCAL SECURITY

JUNCTION BOX ON SECURE SIDE OF DOOR.

2. PROVIDE 0.5" CONDUIT FROM DOOR FRAME TO COMMON SECURITY

JUNCTION BOX ON SECURE SIDE OF DOOR.

3. COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.

(12"X12"X4" W ITH SECURITY SCREW COVER).

4. PROVIDE PLENUM COMPOSITE DOOR SECURITY W IRING (EQUAL TO

BELDEN B658AFJ) FROM COMMON SECURITY JUNCTION BOX TO

BACKBOARD IN LOCAL SIGNALS CLOSET. ROVIDE 24" TAIL IN

JUNCTION BOX AND 5' SLACK AT BACKBOARD PRIOR TO

TERMINATION. CABLE TO BE PROPERLY SUPPORTED UTILIZING J-

HOOKS.

5. ELECTRONIC DOOR LOCK.

6. PROVIDE 0.75" CONDUIT FROM DOOR FRAME TO COMMON

SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.

7. REQUEST TO EXIT SENSOR IN THE HARDW ARE.

8. W ALL MOUNTED REQUEST TO EXIT MOTION SENSOR . PROVIDE 1-

GANG BOX W ITH 0.5" CONDUIT TO COMMON SECURITY JUNCTION

BOX ON SECURE SIDE OF DOOR. SENSOR BOX TO BE LOCATED ON

SECURE SIDE OF DOOR, DIRECTLY ABOVE THE DOOR FRAME.

9. W ALL MOUNTED CREDENTIAL READER. PROVIDE 1-GANG BOX AT 46"

MH (UNLESS OTHERW ISE NOTED) AND EXTEND 0.75" CONDUIT FROM

BOX TO COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF

DOOR.

10. LOCAL DOOR LOCK POW ER SUPPLY, MOUNT ABOVE CEILING,

EXTEND POW ER AND LOW VOLTAGE W IRING AS REQUIRED.

FINISH FLOOR

CEILING

NON-SECURE SIDESECURE SIDE

5 7

CR

SINGLE DOOR W ITH CARD READER ACCESS

ON ENTRY SIDE

JB

FINISH FLOOR

CEILING

NON-SECURE SIDESECURE SIDE

SINGLE DOOR W ITH DOOR MONITOR

FINISH FLOOR

CEILING

NON-SECURE SIDESECURE SIDE

2 2

DOUBLE DOOR W ITH CARD READER ACCESS

AND AUTO OPEN

CR

HA

FINISH FLOOR

CEILING

NON-SECURE SIDESECURE SIDE

2 2

DOUBLE DOOR W ITH CARD READER ACCESS

ENTRY

CR

7 7

JB

JB

JB

DETAIL NOTES

9/16" D

6/32" D (TYP. OF 6)

1-1/8" O.C.

9/32" D (TYP. OF 12)

1-1/8" O.C.

DETAIL NOTES

1. 4"x1/4"x10" MIN. LENGTH GROUNDING BAR.

ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND

CONNECTIONS.

2. W ALL MOUNTING BRACKET.

3. INSULATORS.

4. 5/8-11X1 H.H.C.S.

5. 5/8" LOCKW ASHER.

CAMERA MOUNTING DETAIL NOTES

INTERIOR - WALL MOUNTED EXTERIOR - WALL MOUNTED

INTERIOR - CEILING RECESSED INTERIOR - CEILING SURFACE

N O

M

INTERIOR CEILING

INTERIOR CEILING

1. CAMERA AS SHOW N ON THE PLANS, REFER TO CAMERA

SCHEDULE FOR SPECIFICATIONS.

2. W ALL MOUNTED PENDANT ARM FOR CAMERA.

3. 1-GANG BOX, SEALED FOR MOUNTING OF CAMERA.

4. 0.75" CONDUIT TO BE ROUTED TO ACCESSIBLE INTERIOR

JUNCTION BOX.

5. W IRING TO BE FOR CONNECTION TO CAMERA.

6. PROVIDE JUNCTION BOX ABOVE ACCESSIBLE CEILING.

7. PROVIDE 1-DATA OUTLET UTILIZING SURFACE MOUNT

"BISCUIT" FOR TERMINATION OF DATA DROP INTO RJ-45

OUTLET.

8. PATCH CABLE.

9. PROVIDE 20' COIL OF CABLE MANAGED ABOVE CEILING.

10. SURFACE CEILING MOUNTED JUNCTION BOX FOR CAMERA.

8 7 9

8 7

BLDG 37

TELEPHONE

ROOM

DATA

ROOM

BLDG 1

SUB-BASEMENT

BLDG 38

SUB-BASEMENT

BLDG 2

SUB-BASEMENT

GROUND FLOOR

BLDG 42

EXISTING

NEW LAB

ADDITION

STEAM TUNNEL

NEW SIGNALS

CLOSET

3 6

DETAIL NOTES

1. PROVIDE NEW 66 BLOCKS IN EXISTING RACK FRAME AND TERMINATE

NEW VOICE BACKBONE CABLING.

2. EXISTING VOICE BACKBONE RACK FRAME.

3. NEW 100 PAIR PLENUM RATED VOICE BACKBONE CABLE.

4. PROVIDE NEW FIBER TERMINATION CABINET IN EXISTING RACK AND

TERMINATE NEW FIBER BACKBONE CABLE.

5. EXISTING FIBER TERMINATION RACKS.

6. NEW 12 STRAND OM3 INDOOR/OUTDOOR, PLENUM RATED FIBER

BACKBONE CABLE. INSTALL IN INEW NNERDUCT.

7. EXISTING W ALL MOUNTED PULL BOX.

8. EXISTING EXTERIOR/UNDERGREOUND CONDUIT PATHW AY.

9. INSTALL CABLE IN EXISTING CABLE TRAY

10. PROVIDE NEW CONDUIT RISER FROM EXISTING TUNNEL UP INTO

EXISTING SUB-BASEMENT. REFER TO PLANS FOR QUANTITY/SIZES.

11. PROVIDE NEW CONDUIT PATHW AY FOR BACKBONE CABLING TO NEW

SIGNALS CLOSET. REFER TO PLANS FOR QUANTITY/SIZES.

12. NEW TELECOMMUNICATIONS GROUND BAR (TGB).

13. #3/0 AW G TELECOMMUNCIATIONS BONDING BACKBONE TO EXISTING

MAIN ELECTRICAL SERVICE GROUNDING ELECTRODE CONDUCTOR

SYSTEM.

AP

V

CATV

D

TYP.

DATA

P

DETAIL NOTES

1. SURFACE MOUNT UTP DATA JACK ABOVE ACCESSIBLE CEILING.

2. 1-GANG DEVICE BOX W ITH .75"C. TO CORRIDOR CABLETRAY.

3. 2-GANG DEEP DEVICE BOX W /SINGLE-GANG PLATE, 1.25"C TO CORRIDOR

CABLETRAY.

4. CONNECT TO LOCAL CATV DISTRIBUTION EQUIPMENT.

5. UTP DATA/VOICE JACK.

6. DEFAULT OUTLET IS 4-DATA.

7. RUN TO LOCAL DATA STATION CABLE TERMINATION EQUIPMENT.

8. DOUBLE DUPLEX RECEPTACLE.

9. CATV COAXIAL TYPE "F" CONNECTOR.

10. PROVIDE W ALL PLATE FOR MOUNTING OF W ALL PHONE.

11. ELECTRICAL OUTLETS.

12. MULTI-SERVICE, FIRE RATED POKE THRU.

13. BLANK INSERT.

DATA

DATA

DATA

A

B

A

A

B

B

5 5

4D

DATA DATA

7 7

BLANK

D

BLANK

DATA DATA

2D

DETAIL NOTES

1. EXISTING PAGING SYSTEM HEADEND.

2. EXTEND NEW PAGING SYSTEM LINE LEVEL SIGNAL

3. NEW PAGING SYSTEM LOCAL AMPLIFIER.

4. NEW PAGING SPEAKERS, REFER TO PLANS FOR QUANTITIES AND LOCAITONS.

5. PROVIDE REQUIRED 70V SPEAKER LEVEL CABLING

3 SC

S H

SC

S H

SC

NEW TR

EXIST HEADEND

AR

AR

AR

AR

AEAP

LOW ER LEVEL

1ST FLOOR

2ND FLOOR

ROOF

DIAGRAM NOTES

1. VERIFY SYSTEM ROUGH-IN REQUIREMENTS W ITH VENDOR PRIOR TO INSTALLATION

2. DEDICATED 20A-120V EMERGENCY CIRCUIT.

3. MAIN CONTROL PANEL INCLUDING CONNECTION TO PHONE SYSTEM.

4. POW ER SUPPLY

5. EMERGENCY 2-W AY COMMUNICATION SYSTEM ELEVATOR CALL STATION IN

ELEVATOR LOBBY W ITH BACKBOX, CONDUIT, AND W IRING.

6. NEW SIGNAL CLOSET.

1 5

1 5

1 5

1 5

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:52:26 PM

/7

/2

:5

:2

P

M

DETAILS Expand & Upgrade Building 42 for Laboratory

E501

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG JC

SCALE: NONE

SECURITY DOOR DETAILS

SCALE: NONE

GROUND BAR DETAIL

SCALE: NONE

IP CCTV MOUNTING DETAILS

SCALE: NONE

BACKBONE CABLING DIAGRAM

SCALE: NONE

TECHNOLOGY OUTLET FACEPLATE DETAILS

SCALE: NONE

PAGING SYSTEM EXPANSION

SCALE: NONE

EMERGENCY 2-WAY COMMUNICATION SYSTEM DIAGRAM

GROUNDING BAR DETAIL

NTS

(2 m m

(4 m m

(1")

25mm

(1")

25mm

(1")

25mm

(2")

51mm

(1 1/2") TYP

38mm

(1 m m

(5 8" m m

6.35mm (1/4") DIA.

MOUNTING HOLES

TYP. OF (4)

BASE CLAMP/

BRACKET

9.52mm (3/8") DIA.

HOLE TYP. OF (6)

9.52mm (3/8") x 16mm

(5/8") HEX HEAD BOLT

9.52mm (3/8") LOCK WASHER

9.52mm (3/8") FLAT WASHER & 9.52mm (3/8") LOCK WASHER

6.35mm (1/4")

THICK CU BAR

(2'-0") MIN

610mm

6.35mm (1/4") DIA.

HOLE TYP OF (8)

GENERAL NOTES:

1. ALL HARDWARE SHALL BE STAINLESS STEEL.

2. PROVIDE 1 MOUNTING POINT PER 305mm (12") OF BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

SECTION

STEEL EXPANSION

ANCHOR

INSULATOR

9.52mm (3/8") FLAT WASHER

(3'-0") MAX

CONDUIT EXPANSION JOINT CROSSING DETAIL-

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.FLOOR OR ROOF STRUCTURE.

FIELD VERIFY ACTUAL

CONDITIONS, TYP.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

CONDUIT

TRAPEZE PER

SD260533-03, TYP.

914mm

BEAM

CLAMP, TYP.

CONDUIT,

TYP.

PROVIDE 127mm (5") OF SLACK AT

MIDPOINT BETWEEN TWO END OF

FLEXIBLE GALVANIZED STEEL CONDUIT.

PROVIDE GREEN INSULATED COPPER

EQUIPMENT GROUNDING CONDUCTOR

WITH FLEXIBLE CONDUIT.

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

STEEL

EXPANSION

ANCHOR

JUNCTION BOX (SIZE

AS REQUIRED)

CONDUIT FITTING

SPRING NUT

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

FLEXIBLE CONDUIT

NTS

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").

(3'-0") MAX

CONDUIT EXPANSION JOINT CROSSING DETAIL-

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.FLOOR OR ROOF STRUCTURE.

FIELD VERIFY ACTUAL

CONDITIONS, TYP.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

CONDUIT

TRAPEZE PER

SD260533-03, TYP.

914mm

BEAM

CLAMP, TYP.

CONDUIT,

TYP.

EXPANSION FITTING

WITH BONDING JUMPER

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

STEEL

EXPANSION

ANCHOR

JUNCTION BOX (SIZE

AS REQUIRED)

CONDUIT FITTING

SPRING NUT

HEAD

INSULATING

BUSHING

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

EXPANSION FITTING

NTS

GENERAL NOTES:

1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL SD260533-01.

2. INSTALLATION IS REQUIRED FOR CONDUIT 76mm (3") AND LARGER.

LENGTH AS REQUIRED

CONDUIT TRAPEZE MOUNTING DETAIL

NTS

CONDUIT CLAMP. SIZE

AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A

CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES

FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO

SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

FLOOR SLAB PENETRATION DETAIL

NTS

CONDUIT, TYP MINERAL WOOL

(FIRMLY PACKED)

FIRESTOP SEALANT

PER SECTION 07 84 00,

FIRESTOPPING

9.52mm

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

SPRING

NUT, TYP

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL, TYP.

FLOOR SLAB,

TYP.

STEEL EXPANSION

ANCHOR, TYP

(3/8") MAX

PLASTIC

SPACER

INNERDUCT, SEE

NOTE 5

DUCT [SIZE AS

INDICATED ON

DWGS.]

6-WAY DUCT LINE 4-WAY DUCT LINE

2-WAY DUCT LINE

GENERAL NOTES:

1. CONCRETE SHALL BE 3000 P.S.I. @ 28 DAYS, OR AS SPECIFIED, DYED

RED.

2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN

CROSSING OR PLACED IN ROADWAYS.

3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS

OTHERWISE SPECIFIED IN SECTION 26 05 41. REFER TO DUCT BANK

PROFILES FOR APPROXIMATE DEPTH.

4. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

5. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS. 4" SCHEDULE

40 PVC U.N.O.

DUCT BANK DETAILS

NTS

TIE WIRE

(3")

(3")

76mm

3" m m

3" m m

76mm

(3")

76mm

(3 m m m

(3 m m

(3") (3")

76mm (3")

76mm 76mm m m m m

76mm

(3")

76mm

(3") (3")

76mm

152mm

(6")(SEE NOTE 4)

(T Y

P

1' -6

FINISH GRADEMARKER TAPEMARKER TAPE

1' -6

FINISH GRADE

1' -6

FINISH GRADEMARKER TAPE

2' -3

C

O V

E R

2' -3

C

O V

E R

2' -3

C

O V

E R

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:52:37 PM

/7

/2

:5

:3

P

M

DETAILS Expand & Upgrade Building 42 for Laboratory

E502

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

POWER MANHOLE DETAILS

NTS

TOP VIEW

SECTION "A-A"

POWER

SECTION "B-B"

S

LO

P E

SL

O

PE

SLOPE

305x305mm (12"x12") SUMP

A

A

B B

PULLING

IRON

CONC.

ENVELOPE

GROUND ROD

SLEEVE

PULLING IRON CABLE STANCHION PER

SECTION 26 05 41.

305mm (12") SUMP

SUMP FRAME &

COVER

GRADE RINGS AS REQ'D TO MATCH CIVIL

FINISHED GRADE ELEVATION.

CABLE STANCHION

GENERAL NOTE:

1. INCLUDE ALUMINUM LADDER (NOT

SHOWN FOR CLARITY).

2. REFER TO DUCT BANK PROFILES FOR

COLLAR DEPTH. MANHOLE DEPTH MAY

NEED TO BE DEEPER BASED ON

PROFILES. ADJUST ACCORDINGLY.

REFER TO DUCTBANK

PROFILES

FINISHED

GRADE

GROUND ROD PER

SECTION 26 05 26.

0.764 CUBIC METERS

(1 CUBIC YARD) 19mm

(3/4") GRAVEL SUMP

V A

R

IE

S

(5'-0")

1930mm

(6'-4")

(8")

1524mm 203mm

8"

3m m

(6

2m m

5m m

(1 2"

M

IN

3m m

(8

1524mm

(5'-0")

3m m

(8

(1 0'

-0

965mm965mm

(3'-2")

1930mm

(6'-4")

(3'-2")

(5 '-6

(3

'-1 0"

(9 '-4 m m m m m m

(3")

76mm

(8 '-0

8"

3m m (9

'-4

(8

3m m m m m m

3'

-0

5m m915mm

(3'-0")

(4) CONCRETE BRICKS

51mmx203mmx406mm (2"x8"x16")

CONDUIT(S) WITH BELL ENDS

(TYP). SIZE, QUANTITY AND

WIRING AS INDICATED ON

PLANS

CLEAN 19mm (3/4")

CRUSHED ROCK

GRADE. FEATHER & TAMP BACKFILL

TO CREATE FLUSH INSTALLATION

AND POSITIVE DRAINAGE AWAY

FROM BOX

VA

R

IE

S

(1 2"

PULLBOX (SEE SPECIFICATIONS)

LINE SIDES OF EXCAVATION

WITH 13.6 KG (30 LBS.) FELT

PAPER

(12")

5m m

305mm

UNDERGROUND CONCRETE PULLBOX -

TURF AREAS

NTS

LUMINAIRE MOUNTING - LAY-IN CEILING

NTS

LUMINAIRE

SUSPENSION WIRES

REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

LUMINAIRE. REFER TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION SECTION

26 51 00

ACOUSTICAL CEILING

TILE (TYP)

ARCHITECTURAL

CEILING GRID

LUMINAIRE. REFER TO SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

EXIT SIGN MOUNTING - LAY-IN CEILING

NTS

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

ARCHITECTURAL

CEILING GRID

ACOUSTICAL CEILING TILE (TYP)

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO STRUCTURE

REFER TO SPECIFICATION SECTION 26

51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

JUNCTION BOX

LOCKING SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

ARCHITECTURAL

CEILING GRID

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

FIXTURE WHIP FROM JUNCTION BOX

(1829mm (6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

CONDUIT ROOF PENETRATION DETAIL

NTS

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF

PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE

PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE

PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

PREFABRICATED RUBBER

BOOT CAP WITH GRADUATED

STEPS & WEATHER-PROOF

PRESSURE SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE BY

ROOFING CONTRACTOR MULTIPLE MEMBRANE STRIPPING

PLIES FEATHERED AT FIELD OF ROOF

BY ROOFING CONTRACTOR. PRIME

FLANGE BEFORE STRIPPING.

PREFABRICATED FORMED 1.52mm

(0.06") THICK ALUMINUM FLASHING

ROUND COLLAR WITH MIN. 76mm

(3") WIDE FLANGE. ATTACH TO

ROOF PER MANUFACTURER'S

INSTRUCTIONS

CONDUIT CLAMP. SIZE AS

REQUIRED

BATT INSULATION

ROOF MEMBRANE

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

STAINLESS CLAMP, TYP.

9.52mm (3/8")

MIN

GALVANIZED

THREADED ROD,

TYP.

SEAL-OFF

FITTING,

TYP.

ROOF

STEEL

EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

CONDUIT,

TYP.

CONDUIT

CLAMP. SIZE AS

REQUIRED

LOCKING

SQUARE

WASHER &

LOCKNUT

EQUIPMENT GROUND CONDUCTOR

MANHOLE COVER FRAME

GROUND CONNECTION

#6 STRANDED BARE CU

CABLE (TYP)

DUCT BANK

CABLE PULLING

IRONS

#3/0 STRANDED

BARE CU COMPLETE

RING.

EXOTHERMIC

WELD CONNECTION

GROUND ROD PER SECTION

26 05 26

SUMP

FRAME

BRAIDED SHIELD

DRAIN WIRES (TYP)

EMBED CHANNEL

OR CABLE RACK

(TYP)

EXOTHERMIC

WELD

CONNECTION

(TYP)

CABLE CLIP

(TYP)

DRILL AND

TAP GROUND

CONNECTION

MANHOLE GROUNDING DETAILS

NTS

CABLE SPLICES

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:52:51 PM

/7

/2

:5

:5

P

M

DETAILS Expand & Upgrade Building 42 for Laboratory

E503

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM