P09 657-502 Bid Drawings Part 10 of 10 Electrical 3-19 pages.pdf
PDF 9 MB Posted
- Attached to
- Expand and Upgrade Building 42 for Laboratory
- Solicitation number
- 36C25520R0073
About this file
This solicitation is for expansion and upgrade work at the Marion VA Medical Center in Marion, Illinois. The scope of work includes expanding and upgrading Building 42 to accommodate new laboratory facilities. Construction will include a lower level addition as well as renovations to existing spaces. Bids are due by November 8, 2019. The estimated value of the contract is between $5-10 million. The solicitation is set aside for verified service-disabled veteran-owned small businesses. The Department of Veterans Affairs Veterans Health Administration is the contracting agency.
The document includes architectural and engineering drawings detailing the proposed construction. Plans cover site work, new foundations, structural elements, utilities infrastructure, and layouts for all floors and additions. Technical specifications are provided for general contracting as well as trades such as electrical, mechanical, plumbing and technology systems. Drawings and specifications are at 30-60% design development.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
OS
WP/GF
CR
S S
S F
F
C
B
A
54321
J
K
M
L
N
16 17 19
EX/R
EX/R
11 1212
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:55:14 PM
/7
/2
:5
:1
P
M
PARTIAL LOWER LEVEL -
DEMOLITION PLAN
Expand & Upgrade Building 42 for Laboratory
ED100
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
SCALE: 1/8" = 1'-0"
EXISTING LOWER LEVEL - DEMO
GENERAL NOTES
A. DISCONNECT AND REMOVE LIGHTING FIXTURES, DEVICES, EQUIPMENT, AND
CIRCUITRY IN EXISTING W ALLS AND CEILINGS BEING REMOVED. COORDINATE W ALLS
AND CEILINGS BEING REMOVED W ITH ARCHITECTURAL DEMOLITION PLANS.
B. REMOVE ABANDONED W IRING AND CABLING IN AREA OF DEMOLITION PER THE NEC.
C. RELOCATE AND RECONNECT ACTIVE PORTIONS OF THE ELECTRICAL SYSTEM
OUTSIDE OF THE SCOPE OF W ORK, AS REQUIRED, TO MAINTAIN A COMPLETE AND
OPERATIONAL SYSTEM THAT IS FUNCTIONALLY EQUIVALENT TO THE PRE-EXISTING
SYSTEMS PRIOR TO DEMOLITION.
D. REMOVE FIRE ALARM SYSTEM THROUGHOUT DEMOLITION AREA.
PLAN NOTES
1. NOTE OMITTED.
2. NOTE OMITTED.
3. NOTE OMITTED.
4. NOTE OMITTED.
5. NOTE OMITTED.
6. REMOVE SECURITY LIGHTING FIXTURE.
7. REMOVE AND RELOCATE SUMP ALARM & LIGHT.
8. REMOVE AND RELOCATE CARD READER.
9. REMOVE RECEPTACLE.
10. DEVICE LOCATED ABOVE GRADE AT FIRST FLOOR LEVEL.
11. DEVICES IN TUNNEL ARE EXISTING TO REMAIN UNLESS OTHERW ISE NOTED.
12. EXISTING CEILING TO BE TEMPORARILY REMOVED AND REINSTALLED. REMOVE AND
REINSTALL ALL DEVICES. SUPPORT ALL LIGHTING, CABLING AND CONDUIT IN THIS
AREA DURING CONSTRUCTION.
1 BULLETIN #1 05/24/2019
P OS OS
OS
OS
OS
D
C
B
A
54321
C1 C1 C1 C1 C1 C1
C1C1C1C1C1C1
C1 C1 C1 C1 C1 C1
C1
C1 C1 C1 C1
C1C1C1C1C1 D5
X1
D5
X1
EL100
D4
11 1 1 11 11 1
1111111
1 1 11 1 1 1
11 1 1 1 1
1 1 1 11 1
B2
B2
B2
B2
UP
42-EL-3 - 15
Elevator Machine Room
ESB004
Tunnel Access
ECSB002
C1
D4 16
X1
X2
X1
2 2
EX
X1
D4 16
X1
EL100
EX EX EX EX EX EX EX EX
X1
C1
C1
X1
C1
EX EX
EX
EX
EX
X1
MAINnd Floor
LEVEL
100' - 0"
2ND
Floor/InterstiEVEL
117' - 2 1/2"
Existing Lower Level 91' - 9"
Tunnel Level 87' - 9"
D
Lower Level 85' - 10"
Roof Level 135' - 10"
Stair Roof 150' - 8 1/2"
D4
D4
D4
D4
D4
D4
D4
8'
6" 8'
6"
8'
6"
8' -6
8' -6
6' -6
8'
0"
8' -0
X1
8'
0"
DC.2
D
K1
EL100
D4
D4
16X1
X1
9' - 0"
EX/R
EL100
SOUTH
NORTH
MAINnd Floor
LEVEL
100' - 0"
2ND
Floor/InterstiEVEL
117' - 2 1/2"
Existing Lower Level 91' - 9"
Tunnel Level 87' - 9"
Lower Level 85' - 10"
Roof Level 135' - 10"
Stair Roof 150' - 8 1/2"
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 1:09:47 PM
/7
/2
:0 :4
P
M
LOWER LEVEL FLOOR PLAN -
LIGHTING
Expand & Upgrade Building 42 for Laboratory
EL100
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/8" = 1'-0"1 LOWER LEVEL PLAN - LIGHTING
GENERAL NOTES
A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR
CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.
B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR
RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).
C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.
D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING
PLANS.
E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING
PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .
OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.
REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE
TIME OF DELIVERY.
F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO
INSTALLATION.
G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.
H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH
CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL
BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR
BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. LIFE SAFETY: PANEL "42-EL-3" LOCATED IN BUILDING 42 MAIN ELECTRIC ROOM. PROVIDE NEW
BREAKERS FOR CIRCUITS SHOW N.
b. NORMAL: PANEL "42-9"
1/8" = 1'-0"2 STAIR LIGHTING ELEVATION
1/8" = 1'-0"3 GRADE LEVEL - SOUTH
PLAN NOTES
1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED SO THAT IT
DOES NOT INTERFERE W ITH EQUIPMENT.
2. STEM MOUNT AT 10'-0".
3. RELOCATED SUMP ALARM AND LIGHT.
4. LIGHTING IN THIS AREA IS TEMPORARY. CONNECT LIGHTING IN THIS AREA TO EXISTING
TUNNEL LIGHTING CONTROL. REMOVE LIGHTING PRIOR TO DEMOLITION OF TEMPORARY
TUNNEL.
5. PROVIDE TEMPORARY EXIT SIGN FOR TUNNEL. REMOVE W HEN TEMPORARY TUNNEL IS
DEMOLISHED.
N
Not to Scale
KEYPLAN - AREA OF WORK
1/4" = 1'-0"4 ELEVATOR LIGHTS
OS
OS
D M
DMDMOS OSOS
DM
D M
OS
O S
OS
OS
D M
D M
D M
D M
D M
D M
D M
OS
D M
O S
O S
O S
OS
OS
DM
OS
OS
OS
OS
OS
OS OS
OS
OS
D M
D M
3 3
B
A
54321
2 2
B2b
B2 B2 B2 B2 B2
F1 F1 F1 F1
B2
B2
B2a
B2a
B2a B2a
B2a
B2a
B2a
B2a
X1
X1
B2b
X1
X1
X1 a b
X2
D2
D2 D2
D2 K1
K1
K1 K1
K1
B2
B2
B2
B2
18 18 18 18
B2
B2
B2
B2
B2
B2a
B2a
B2b
B2a
B2a
B2 B2b
14 14
B2
Waiting
E001
Station
E003 Station
E005
Station
E007
Station
E009
Station
E011
Office
E013
Shared Office
E015 Office
E017
Open Office
E010
Phlebotomy
E002
Alcove
E010A
Office
E012
PSA
E014
Pyxis Storage
E008
Corridor
E018C
P. Toilet
E006
Toilet
E020
ADA Toilet
E022
HAC
E024A
Break Room
E024
P. Toilet
E004
Shared Office
E016
Blood Bank
E021
B2
B2
B2
3 3 a b ba
B2a B2a
B2aB2a
Conf
E026
B2
2 2 2
2 2 2 2 2
X2
MATCHLINE
X1
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5 L5
L5
L5
L5
L5
L5
L5
L5a
L5
L5
L5a
L5a
L5
L5 L5
L5a
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5
L5a
L5
L5
L5
L5a
2B2 1B2 19B2 1B2
B2 1 B2 19 B2 2 B2 1 B2 19 B2 2
L5a
14' - 0"
14' - 0"
Cooler
E018A z xy z z r z rp p a b b b b a a a a a
14' - 0"
14' - 0"14' - 0" ab c sr
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:56:20 PM
/7
/2
:5
:2
P
M
PARTIAL MAIN LEVEL FLOOR
PLAN - LIGHTING
Expand & Upgrade Building 42 for Laboratory
EL101A
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/4" = 1'-0"1 MAIN LEVEL - NORTH
N
Not to Scale
KEYPLAN - NORTH
GENERAL NOTES
A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR
CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.
B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR
RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).
C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.
D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING
PLANS.
E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING
PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .
OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.
REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE
TIME OF DELIVERY.
F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO
INSTALLATION.
G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.
H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH
CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL
BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR
BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. LIFE SAFETY: PANEL "42-EL-3".
b. CRITICAL: PANEL "42-EC-3".
c. NORMAL: PANEL "42-9"
J
DSDS DS
O S
DS
DS
OS
D
C
654321
D4
B2
B2
X1
1D5
D5
D4
D4
D4
B2
B2
16 16
UP/DN
Stair/Elev Vestibule
EC027
Microbiology
E019A
Blood Bank
E021
Bio-Safety Level 3
E019B
Acid/Base
E023A
Histology
E023
IT
E025 dc d
D4
MATCHLINE
X1
Main Lab
E019
19B2
1B2
19B2
1B2
2B2
1B2
2B2
19B2
2B2
1B2
2B2
1B2
19B2
1B2
19B2
1B2
2B2
1B2
19B2
2B2
2B2
1B2
1B2
19B2
2B2
1B2
1B2
1B2 2B2 19B2 2B2
1B2
1B2
2B2
1B2
19B2
2B2
2B2
19B2
1B2
1B2a
1B2a
2B2a
1B2a
19B2a
1B2a
1B2a
19B2a
1B2
2B2 d e b/d b/d d d d d d d e e
K1
14' - 0"
K1 14' - 0"
K1 14' - 0"
F1
Cooler
E018A xy x x y z y x y v w z v z v w v w z w t u t z t z t u t t u s r r z s r r s z p
2B3a
2B3a ab c a c cb a c b b b/d a b c a a b b c c c b/d a c b
42-EC-10A - 22
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:56:47 PM
/7
/2
:5
:4
P
M
PARTIAL MAIN LEVEL FLOOR
PLAN - LIGHTING
Expand & Upgrade Building 42 for Laboratory
EL101B
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/4" = 1'-0"1 MAIN LEVEL - SOUTH
N
Not to Scale
KEYPLAN - SOUTH
PLAN NOTES
1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY
AND BE LOCATED SO THAT IT DOES NOT INTERFERE W ITH
EQUIPMENT.
2. CONNECT TO COOLER LIGHTING.
GENERAL NOTES
A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR
CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.
B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR
RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).
C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.
D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING
PLANS.
E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING
PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .
OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.
REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE
TIME OF DELIVERY.
F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO
INSTALLATION.
G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.
H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
I. PROVIDE PROGRAMMED RAPID START BALLASTS FOR ALL FLUORESCENT FIXTURES AND SUBMIT
BALLAST INFORMATION DURING SHOP DRAW ING REVIEW .
J. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH
CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
K. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL
BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
L. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
M. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
N. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR
BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
O. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
P. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. LIFE SAFETY: PANEL "42-EL-3"
b. CRITICAL: PANEL "42-EC-3"
c. NORMAL: PANEL "42-9"
P
T
D
C
B
A
54321
Mechanical Room
E102
Mechanical Room
E102
C1 C1 C1 C1
C1
C1
C1 C1 C1 C1
C1
C1
C1 C1 C1 C1 C1
C1 C1 C1 C1 C1 C1
C1 C1 C1 C1 C1
C1C1 C1 C1 C1C1
D4
D5
D5
D4
EL100
X1
4 4 4 4
44134
4 4 4 4 4
4413444
13 4 4 4 4
4134444
UP/DN
D4
D4 16
X1
X2
K1
AHU-1
AHU-2
C1 a a a a a a
C1
X2 8' - 0"
EL100
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:57:04 PM
/7
/2
:5
:0
P
M
INTERSTITIAL LEVEL FLOOR
PLAN - LIGHTING
Expand & Upgrade Building 42 for Laboratory
EL102
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/8" = 1'-0"1 INTERSTITIAL LEVEL - LIGHTING
PLAN NOTES
GENERAL NOTES
A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR
CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.
B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR
RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).
C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.
D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING
PLANS.
E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING
PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .
OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.
REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE
TIME OF DELIVERY.
F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO
INSTALLATION.
G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.
H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH
CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL
BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR
BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. LIFE SAFETY: PANEL "42-EL-3"
b. NORMAL: PANEL "42-9"
1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED SO THAT IT DOES NOT
INTERFERE W ITH EQUIPMENT.
2. PROVIDE 4 HOUR SPRING W OUND TIMER.
N
Not to Scale
KEYPLAN - AREA OF WORK
WP/GF
S
AM
I
NO. 28 CLASS II COPPER LIGHTNING CONDUCTOR
DOWN IN EXTERIOR WALL CONSTRUCTION TO
LOWER ROOF OR GROUND
AIR TERMINAL DETAIL AIR TERMINAL DETAIL
AIR TERMINAL DETAILNTS
E
NTS
D
NTSC
NTS
A
NTS
NO. 28 CLASS II COPPER
LIGHTNING CONDUCTOR
(28 X 14 AWG)
CADWELD EXOTHERMIC WELD
CONNECTION TYPE "GR"
N0. 5810 5/8" X 10'-0"
COPPERCLAD GROUND ROD
NO. 230 THRU-ROOF
ASSEMBLY MOUNTED
ON CONCRETE ROOF
DECK EXTENDING
THROUGH INSULATION
& ROOFING MATERIALS
TO 6" ABOVE FINISHED
ROOF FLASHING BY
ROOFING
CONTRACTOR
NO. 28 CLASS II COPPER LIGHTNING
CONDUCTOR (28 X 14 AWG)
NO. 97 1/2" X 36" COPPER, LEAD
COATED CHIMNEY AIR TERMINAL
NO. 251L LEAD COATED
COPPER LOOP
FASTENER WITH
STAINLESS STEEL
SCREWS
NO. 28 COPPER LIGHTNING
CONDUCTOR (28 X 17 AWG)
NO. 28 COPPER
LIGHTNING
CONDUCTOR (28
X 14 AWG)
NO. A37 ALUMINUM
LIGHTNING
CONDUCTOR
NO. A150 ALUMINUM FLAT
SURFACE PLATE
NO. A81 5/8" X 12"
ALUMINUM AIR TERMINAL
NO. A251 ALUMINUM
LOOP CABLE CLIP
NO. A217 ALUMINUM
BONDING PLATE
NO. 211 BIMETAL
CONNECTOR
1/2" STAINLESS STEEL
OR BRASS THREAD
ROD
2" SCHEDULE 40 PVC
WITH CAP LENGTH AS
REQUIRED
NO. 251 COPPER LOOP CABLE CLIP WITH
STAINLESS STEEL SCREW (3'-0" O.C.)
NO. 28 COPPER
LIGHTNING
CONDUCTOR (28
X 14 AWG)
NO. 71, 1/2" X 12"
COPPER AIR TERMINAL
NO. 150 BRONZE
FLAT SURFACE
BASE
B
LIGHTNING PROTECTION
GROUNDING DETAIL
LIGHTNING PROTECTION
THRU-ROOF DETAIL
LIGHTNING PROTECTION
LIGHTNING PROTECTIONLIGHTNING PROTECTION
D
C
B
A
54321
TYP.
2TYP.
D5
D5
DOW N
D4 16D4 16
X1
X3
COOLER
CONDENSER
W P
CU-1
42-EMDP-EQ-1 - 2,4,6
W P
D D
C C
B B
A A
C.2 C.2
B.2 B.2
2.2
2.2
2.1
2.1
A.6 A.6
A.2 A.2
4.5
4.5
3.5
3.5
2.5
2.5
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:57:21 PM
/7
/2
:5
:2
P
M
ROOF PLAN Expand & Upgrade Building 42 for Laboratory
EL103
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/8" = 1'-0"1 ROOF PLAN
PLAN NOTES
1. PROVIDE AIR TERMINALS AS SHOW N.
2. LIGHTNING PROTECTION DOW N CONDUCTOR AND GROUND ROD.
3. LIGHTNING PROTECTION MAIN CONDUCTOR.
4. ELEVATOR SHAFT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED
SO THAT IT DOES NOT INTERFERE W ITH EQUIPMENT.
5. CONNECT TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM. PROVIDE
U.L. MASTER LABEL. IF EXISTING BUILDING SYSTEM DOES NOT HAVE A LABEL,
PROVIDE A U.L. LETTER OF FINDINGS FOR ADDITION ONLY.
6. BOND TO METAL STAIR BELOW .
7. BOND TO MECHANICAL EQUIPMENT TO LIGHTNING PROTECTION SYSTEM.
8. DISABLE POW ER TO ACCESS CONTROL UPON FIRE ALARM ACTIVATION.
N
Not to Scale
KEYPLAN - AREA OF WORK
GENERAL NOTES
A. REFER TO ARCHITECTURAL PHASING PLAN AND INCLUDE ALL
W ORK NECESSARY TO ACCOMMODATE PHASING.
B. REFER TO ARCHITECTURAL DRAW INGS FOR INFORMATION ON
SMOKE COMPARTMENTS, SMOKE PARTITIONS AND FIRE
BARRIERS.
C. REFER TO ARCHITECTURAL DRAW INGS FOR LOCATIONS OF FIRE RATED
W ALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE RATED
ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE STOPPED AS
REQUIRED TO MAINTAIN FIRE RATINGS AS INDICATED.
D. LIGHTNING PROTECTION PLAN SHOW N FOR REFERENCE ONLY.
SYSTEM SHALL BE DESIGNED PER NFPA 780 AND SUBMITTED
W ITH SHOP DRAW INGS.
E. COMPLETED SYSTEM SHALL MEET THE INSTALLATION REQUIREMENTS
FOR LIGHTNING PROTECTION SYSTEMS, "UL96A" OF UNDERW RITERS
LABORATORIES INC., NFPA 780 AND SHALL BEAR THE MASTER LABEL
OF UNDERW RITERS LABORATORIES INC.
F. LAYOUT IS FOR BIDDING PURPOSE AND REFERENCE ONLY.
SUCCESSFUL CONTRACTOR SHALL PREPARE FINAL LIGHTNING
PROTECTION DRAW INGS AND DETAIL AND SUBMIT DURING SHOP
DRAW ING PHASE FOR REVIEW .
G. REFER TO LIGHTNING PROTECTION SPECIFICATIONS.
H. INCLUDE BONDING OF ALL ROOF MOUNTED EQUIPMENT, VENTS, ETC
PER NFPA 780.
GF
J
G F
J
SP-1
26 26
42-EQ-11-A - 2
42-EL-4 - 11
42-EQ-11 - 14,16,18
42-EL-4 - 11
EX
D
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:57:38 PM
/7
/2
:5
:3
P
M
LOWER LEVEL FLOOR PLAN -
POWER
Expand & Upgrade Building 42 for Laboratory
EP100
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/8" = 1'-0"1 LOWER LEVEL PLAN - POWER
A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.
B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
C. EMT CONDUIT SHALL BE 0.75" M INIMUM.
D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.
E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.
I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE
OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. CRITICAL: PANEL "42-EC-10"
b. LIFE SAFETY "42-EL-4"
c. NORMAL: PANEL "42-10"
GENERAL NOTES
1/8" = 1'-0"2 GRADE LEVEL POWER - SOUTH
PLAN NOTE
1. PROVIDE NON-FUSIBLE DISCONNECT INSTALLED IN HOISTW AY. COORDINATE W ITH ELEVATOR
MANUFACTURER PRIOR TO INSTALLATION.
2. RUN 2-4"C, (2) 2" CONDUIT AND (4) 1" CONDUIT FROM THIS FLOOR TO THE INTERSTITIAL LEVEL FOR
FUTURE USE.
3. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE CEILING.
4. PROVIDE 120V-30A FUSIBLE DISCONNECT SW ITCH (FUSED AT 20 AMPS). FOR ELEVATOR CAB LIGHTS.
5. CIRCUIT TO LOCAL RECEPTACLE CIRCUIT.
N
Not to Scale
T R T R
TR
TR
T
RT
R
G F
G F
G F
G F
G F
G F
G F
G F
G F
G F
/C M
G F
/M W
PX
PX
PX
PX
ICE
G F
TV
84" MH
J
J
J
J
J
J
J
J T
V
M H
J
G F
R F
/G F
B
J J
J J J J
J
J
U C
/G F
B
TV
84" MH
B
A
54321
2 2
5 5 5 5
4 4 4 4 4
16 17 18
1 1 1 2 2
14 14
5 14
42-EC-10 - 18
42-EC-10 - 18
42-EC-10 - 18
42-EC-10 - 18
42-EC-10 - 18
42-EC-10 - 18
Conf
E026
Waiting
E001
Station
E003
Station
E005
Station
E007
Station
E009 Station
E011
Office
E013
Shared Office
E015
Office
E017
Open Office
E010
Phlebotomy
E002
Alcove
E010A
Office
E012
PSA
E014
Pyxis Storage
E008
Corridor
E018C
P. Toilet
E006
Toilet
E020
ADA Toilet
E022
HAC
E024A
Break Room
E024
P. Toilet
E004
Shared Office
E016
4 4 4
5 5 5
42-10A - 26,28
42-EC-10B - 9,11
42-10A - 25,27
42-EC-10B - 13,15
42-10A - 31,33
42-EC-10A - 5,7
42-10A - 30
42-EC-10B - 12
42-EC-10 - 18
42-EC-10 - 18
42-EC-10 - 18
42-10C - 9
15 15 15 23
42-10A - 21,23
42-EC-10B - 8,10
42-10B - 33
42-EC-10C - 20
42-EC-10 - 18
42-EC-10 - 18
7 7
MATCHLINE
42-EL-442-T-EC 42-T-EL42-EMDP-EC-2
1500 KVA
TRANSFORMER
HIGH
VOLTAGE
SW ITCH
600A
HIGH
VOLTAGE
SW ITCH
600A
DIG. MTR
MTR ANT
STOR.
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:58:03 PM
/7
/2
:5
:0
P
M
PARTIAL MAIN LEVEL FLOOR
PLAN - POWER
Expand & Upgrade Building 42 for Laboratory
EP101A
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/4" = 1'-0"1 MAIN LEVEL - NORTH
N
Not to Scale
KEYPLAN - NORTH
PLAN NOTES
1. LOW VOLTAGE TRANSFORMER ABOVE LAY-IN CEILING FOR SENSOR OPERATED
FAUCET/FLUSH VALVE PROVIDED BY DIVISION 22. PROVIDE RECESSED SINGLE GANG
J-BOX AT EACH LAV/W ATER CLOSET AND 0.75"C. TO ABOVE ACCESSIBLE CEILING FOR
LOW VOLTAGE W IRING BY DIVISION 22. PROVIDE GROMMETTED OPENING.
COORDINATE EXACT M.H. W ITH DIVISION 22 PRIOR TO ROUGH-IN.
2. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE
CEILING.
3. PROVIDE JUNCTION BOX FOR FURNITURE SYSTEM. COORDINATE EXACT LOCATION
AND QUANTITY OF NEUTRAL / GROUND W IRE REQUIRED W ITH FURNITURE SYSTEM
VENDOR.
4. PROVIDE 120V CONNECTION ABOVE CEILING FOR MOTORIZED W INDOW SHADES.
5. PROVIDE ROUGH-IN AND W IRING / CONDUIT FOR MOTORIZED W INDOW SHADE
SW ITCH.
6. PROVIDE 0.75" CONDUIT TO INTERSTITIAL ROOM FOR FUTURE POW ER CIRCUIT.
7. PROVIDE SURFACE MOUNTED MULTI-CHANNEL/SERVICE FINISHED ALUMINUM RACE
W AY (HEAVY 0.080" T5 EXTRUDED ALUMINUM CHANNEL, FOUR RIBS FOR SNAP-IN
DIVIDERS, SNAP -IN 0.075" T5 EXTRUDED ALUMINUM COVER, 0.050" DIVIDER) W ITH
HOSPITAL GRADE DUPLEX RECEPTACLES 24" O.C. (ALTERNATE BETW EEN THE (2)
BRANCH CIRCUITS FOR BOTH NORMAL AND CRITICAL. PROVIDE POW ER TO RACEW AY
CONCEALED THROUGH W ALL FROM ABOVE CEILING. PROVIDE GFCI CIRCUIT
BREAKER. COORDINATE MOUNTING HEIGHT W ITH ARCH.
A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.
B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
C. EMT CONDUIT SHALL BE 0.75" M INIMUM.
D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.
E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.
I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE
OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. CRITICAL: PANEL "42-EC-10"
b. NORMAL: PANEL "42-10"
M. PROVIDE GFCI BREAKER FOR ALL LAB RACEW AY CIRCUITS.
GENERAL NOTES
R F
RF
72" MH
G F
RF/GFB
J J J a
J b
J c
J
J
R F
FRZ
FRZ
G F
J
J
GF
72" MH
D
C
654321
3 3
42-10 - 29
27,29
26,28
Stair/Elev Vestibule
EC027
Microbiology
E019A
Blood Bank
E021
Bio-Safety Level 3
E019B
Acid/Base
E023A
Histology
E023
IT
E025 a b c
42-EC-10C - 18
42-EC-10C - 4
42-EC-10C - 2
42-EC-10C - 3
42-EC-10C - 5
42-10A - 5,7
42-EC-10A - 9,11
42-10A - 6,8
42-EC-10A - 6,8
42-EC-10C - 1
42-10A - 1,3
42-EC-10A - 1,3
42-EC-10A - 2,4
42-10A - 2,4
42-EC-10A - 13,15
42-10A - 9,11
42-10A - 13,15
42-EC-10A - 17,19
42-EC-10A - 18,20
42-10A - 10,12
42-EC-10B - 1,3,5
42-10A - 14,16,18
42-10A - 20,22,24
42-EC-10B - 2,4,6
42-10A - 31,33
42-EC-10A - 5,7
42-10A - 30
42-EC-10B - 12
42-EC-10B - 14,16
42-10A - 32,34
42-10A - 17,29
42-EC-10B - 17,19
42-10B - 14,16
42-10B - 13,15,17
42-EC-10B - 27,29,31
42-EC-10B - 28,30
42-10B - 10,12
42-10B - 35,37
42-EC-10B - 24,26
42-10B - 9,11
42-EC-10B - 32,34
42-10B - 6,8
42-EC-10B - 20,22
42-10B - 1,2,3
42-EC-10B - 18,21,35
42-10C - 5,7
9 9
Cooler
E018A
42-10B - 5,7
42-EC-10B - 23,25
42-10B - 19,21,23
42-10B - 25,27
42-10B - 32,34
42-EC-10A - 21,23,25
42-EC-10A - 30,32,34
42-10B - 26,28,30
42-EC-10A - 27,29
42-EQ-11-A - 6
42-10C - 4,6
42-EC-10C - 19,21
42-EC-10A - 14,16
42-EC-10A - 24,26
42-10B - 29,31
42-EC-10A - 10,12
42-10B - 36,38
42-EC-10A - 35,37
42-10B - 33
42-EC-10C - 20
42-10B - 22,24
42-EC-10C - 6,8
MATCHLINE
TYP.
TYP.
TYP.
GFCI
42-10C - 10,12
42-10B - 18,20
TYP.
HIGH
VOLTAGE
SW ITCH
600A
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:58:34 PM
/7
/2
:5
:3
P
M
PARTIAL MAIN LEVEL FLOOR
PLAN - POWER
Expand & Upgrade Building 42 for Laboratory
EP101B
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/4" = 1'-0"1 MAIN LEVEL - SOUTH
N
Not to Scale
KEYPLAN - SOUTH
PLAN NOTES
1. PROVIDE 120V CONNECTION FOR HOOD.
2. PROVIDE 208V-30A RECEPTACLE FOR DATA RACK. COORDINATE EXACT LOCATION
W ITH DIV. 27.
3. PROVIDE 120V CONNECTION ABOVE CEILING FOR MOTORIZED W INDOW SHADES.
4. PROVIDE SURFACE MOUNTED MULTI-CHANNEL/SERVICE FINISHED ALUMINUM RACE
W AY (HEAVY 0.080" T5 EXTRUDED ALUMINUM CHANNEL, FOUR RIBS FOR SNAP-IN
DIVIDERS, SNAP -IN 0.075" T5 EXTRUDED ALUMINUM COVER, 0.050" DIVIDER) W ITH
HOSPITAL GRADE DUPLEX RECEPTACLES 24" O.C. (ALTERNATE BETW EEN THE
BRANCH CIRCUITS FOR BOTH NORMAL AND CRITICAL. PROVIDE POW ER TO
CONCEALED THROUGH W ALL FROM ABOVE CEILING. PROVIDE GFCI CIRCUIT
BREAKER. COORDINATE MOUNTING HEIGHT W ITH ARCHITECT.
5. PROVIDE MULTI-CHANNEL ALUMINUM POW ER POLE. MOUNT TW O RECEPTACLES ON
POW ER POLE. MOUNT ONE STANDARD 20A-120V DUPLEX RECEPTACLE ON POW ER
POLE. MOUNT ONE 208V-30A RECEPTACLE ON POW ER POLE FOR UPS/EQUIPMENT.
VERIFY CIRCUIT / RECEPTACLE SIZE PRIOR TO ROUGH-IN / ORDERING. RUN 3-#8, #10
GRD., IN 1"C. FOR 208V/30A RECEPTACLE.
6. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE
CEILING.
7. PROVIDE ELECTRICAL CONNECTION FOR W ALK IN COOLER EVAPORATOR.
8. PROVIDE ROUGH-IN AND W IRING / CONDUIT FOR MOTORIZED SHADE SW ITCH.
9. PROVIDE 0.75" CONDUIT TO INTERSTITIAL ROOM FOR FUTURE POW ER CIRCUIT. SPARE
STUBBED NEAR PANEL LOCATION.
A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.
B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
C. EMT CONDUIT SHALL BE 0.75" M INIMUM.
D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.
E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.
I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE
OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. CRITICAL: PANEL "42-EC-10C"
b. NORMAL: PANEL "42-10C"
DI
WP/GF
D
C
B
A
54321
Mechanical Room
E102
AHU-1
AHU-2
42-EC-10
42-EC-10A
42-EQ-11
42-EQ-11-A
42-9
T-EQ-11-A
42-10A
42-10
30 30
EF-1 EF-2 EF-3HWP-1HWP-2
42-EQ-11 - 8,10,12
42-EQ-11 - 13,15,17
DDC
42-EC-10B
42-10B
42-EQ-11-A - 3
42-EQ-11-A - 4
COOLER
CONDENSER
42-EQ-11-A - 5,7
42-EC-10C
42-10C
42-EQ-11 - 1,3,5
42-EQ-11 - 2,4,6
FACP
42-EQ-11-A - 8
42-EQ-11-A - 9
42-EQ-11 - 7,9,11
W P
Stair/ Elev Vestibule
EC101
Space
CB461
42-EL-4 - 9 2
SOUTH
NORTH
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:58:51 PM
/7
/2
:5
:5
P
M
INTERSTITIAL LEVEL FLOOR
PLAN - POWER
Expand & Upgrade Building 42 for Laboratory
EP102
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
N
1/8" = 1'-0"1 INTERSTITIAL LEVEL - POWER
A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.
B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER.
C. EMT CONDUIT SHALL BE 0.75" M INIMUM.
D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.
E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.
I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.
K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE
OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.
L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:
a. CRITICAL: PANEL "42-EC-10"
b. NORMAL: PANEL "42-10"
GENERAL NOTES
PLAN NOTES
1. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY
ABOVE CEILING.
2. PROVIDE NEW 20A/1P BREAKER IN PANEL "42-EL-4".
N
C100
DN
UP
DN
J PC
Main Hospital
Outpatient ClinicDental/S
PD &
Clinics
Dental/S
PD &
Clinics
Canteen/ Clinics P ro p o s e d
A d d it io n
Engineering / Safety
East Trailer
SNRF
Project Location
N
D
C
B
A
54321
EXISTING STEAM TUNNEL
PB
ABANDON SIGNAL MAN HOLE
MH #4BB
EX.
NEW
M.H.
EX
MH #4A
EXISTING
EM DUCTBANK
BUILDING 42
CRAW L SPACE
EX. MH #4B
EXISTING
EM DUCTBANK
EXISTING
TO MH #4AA (FEEDER #3)
TO MH EMH #4 (FEEDER #1, #2)
FEEDERS #1, #3 7
E604
EX. TO
BLDG #8
TO BLDG #43
NEW LAB ADDITION
E604
5 2
EXISTING BUILDING #42
PULLBOX
42-9 - 7
NEW
M.H.
G
A
B
C
E
J
K
M
L
N
P
15 16 17
H
PB
UNIT SUB "A"
ABOVE
EX EX
1 4-4" C.
4-4" C.
13 4-4" C.
1 2-4" C.
1 2-4" C.
UNIT SUB "B"
ABOVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:59:19 PM
/7
/2
:5
:1
P
M
PARTIAL SITE PLAN Expand & Upgrade Building 42 for Laboratory
ES100
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG CLM
Not to Scale
KEYPLAN - CAMPUS
SCALE: 1/16" = 1'-0"
SITE PLAN
NOTES
1. NEW 15 KV FEEDER IN CONCRETE ENCASED DUCTBANK.
2. UP TO UNIT SUB "A".
3. REMOVE 15 KV FEEDER AND CONCRETE DUCTBANK.
4. EXCAVATE EACH SIDE OF CONNECTOR AND DIRECTIONAL BORE NEW 4-4"C. UNDER
NEATH.
5. RUN NEW 15KV FEEDER IN CRAW LSPACE IN RIGID METALLIC CONDUIT PAINTED PER
SPECIFICATIONS W ITH PROPER SIGNAGE.
6. PRIMARY DUCTBANK MUST CROSS STEAM TUNNEL. REMOVE AND REPLACE 15KV
FEEDER IN EXISTING CONDUIT.
7. REMOVE AND REPLACE 15KV FEEDERS IN EXISTING CONDUIT.
8. EXCAVATE EACH SIDE OF THE STEAM TUNNEL AND DIRECTIONAL BORE UNDER NEATH.
9. APPROXIMATE LOCATION OF 002 PRIMARY GEAR B.
10. PROVIDE 277V/1PH CONNECTION FOR SITE LIGHTING. RUN THROUGH PHOTOCELL ON
ROOF.
11. EXISTING FEEDERS UP TO UNIT SUB "B".
12. PROVIDE SPECIFICATION GRADE 277V PHOTOCELL ON ROOF FOR SITE LIGHTING
CONTROL.
13. FORM AND POUR MANHOLE IN PLACE DUE TO VERY LIMITED SPACE AVAILABLE. MANHOLE
SHALL BE TIGHT TO STEAM TUNNEL W ALL. CONDUITS UNDER TUNNEL SHALL BE BORED
FIRST.
14. SIZE PER NEC.
15. PROTECT IN PLACE.
16. EXISTING 15KV FEEDERS.
A. REFER TO SEQUENCE OF CONSTRUCTION NOTES ON SHEET E001 FOR PHASING.
B. REFER TO DUCTBANK PROFILE ON SHEET ES102.
C. PROVIDE ALL SHORING, PLATE STEEL AND BARRICADES REQUIRED.
FEC
FEC
101 102
102B 102B
102C
102D
102A
104A
106A 106
107107A
108110
114A
114B
115A 116A
119A
119B
119C 119D 119E 120A
121A121B
C101-02
C102-02
C103-02
C104-02
C105-02
C106-02
P4
P3
SB1-02
105A
DN
DN
FEC
FEC
103104105105A
110109 111
115 116 117
118B
129130
102A
123A
FEC
FEC
FEC
102A
103A 103B 103C 104
106A
106B
106C
106D
107A
107B 107C 107D
107E
109A
110A
110B
110C
110D
113A
113B
113C
116A
117118
S102-01
118A
118B
119B
119A
119C 119
S101-01
S104-01
S105-01
S103-01
103D
P-2
P-1
P-7
UP UP
UP
CB2-38
006A005A
006B
CB3-38
CB1-38
SC
D
C
B
A
BLDG. 1
BLDG 38
BLDG 2
BLDG 37
TEL DATA
3 4
BLDG 42
G
A
D
B
C
E
F
J
K
M
L
N
P
3 4
65 78
10 11 13 15
16 17
QR
S
T
H
2.8
D
C
B
A
C.2 C.2
B.2 B.2
2.2
2.2
2.1
2.1
A.6 A.6
A.2 A.2
3.5
3.5
2.5
2.5
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 O ld West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Heapy Project No.: 2017-05045 Firm License No. 01528
11/7/2019 12:59:31 PM
/7
/2
:5
:3
P
M
PARTIAL SITE PLAN -
TECHNOLOGY
Expand & Upgrade Building 42 for Laboratory
ES101
657-502
MARION, ILLINOIS
11/08/2019
BID DOCUMENTS
MSG JC
SCALE: 1" = 20'-0"
COMPOSITE SITE TECHNOLOGY SITE PLAN
PLAN NOTES
1. NEW COPPER BACKBONE CABLING RUN ABOVE CEILING FROM EXISTING TELEPHONE ROOM.
2. NEW FIBER BACKBONE CABLING RUN ABOVE CEILING FROM EXISTING DATA ROOM.
3. UTILIZE EXISTING BUILDING MOUNTED PULLBOX.
4. UTILIZE EXISTING UNDERGROUND CONDUITS, PROVIDE NEW INNERDUCT FOR NEW FIBER.
5. CABLE TO BE ROUTED IN EXISTING CABLE TRAY IN EXISTING PIPE-BASEMENT. REFER TO SHEET ET300.
6. CABLE TO TRANSITION FROM STEAM TUNNEL TO PIPE BASEMENT IN NEW CONDUIT.
7. CABLE TO BE ROUTED IN EXISTING CABLE TRAY IN EXISTING STEAM TUNNEL.
8. CABLE TO BE ROUTED IN NEW CONUIT. PROVIDE INNERDUCT IN CONUIT FOR FIBER. REFER TO SHEET ET300.
9. RERER TO SHEET ET200
HORIZ: 1'=10' VERTICAL 1"=5'
NORTH ELECTRIC DUCT BANK PROFILE STA: 0+00N TO 2+58N1
HORIZ: 1'=10' VERTICAL 1"=5'
SOUTHWEST ELECTRIC DUCT BANK PROFILE STA: 0+00 TO 2+482
NOTE: CONTRACTOR SHALL TAKE EXTRA CARE TO PROTECT ALL TREES, BUSHES,
SURVEY MONUMENTS, R.O.W. MARKERS AND OTHER EXISTING SITE FEATURES THAT
ARE TO REMAIN. ANY DAMAGE TO EXISTING FEATURES TO REMAIN SHALL BE FIXED AT
THE CONTRACTORS OWN EXPENSE AND BE RESTORED TO IT'S ORIGINAL CONDITION.
A DETAILED UTILITY SURVEY WAS NOT CONDUCTED ON THIS PROPERTY OR AS A PART
OF THIS SURVEY. THE LOCATIONS OF ANY UNDERGROUND UTILITIES AS SHOWN HEREON
ARE BASED ON ABOVE GROUND STRUCTURES AND UTILITY MAPS AS PROVIDED BY
UTILITY OWNERS. LOCATIONS OF UNDERGROUND UTILITIES/STRUCTURES MAY VARY
FROM LOCATIONS SHOWN HEREON.