P09 657-502 Bid Drawings Part 10 of 10 Electrical 3-19 pages.pdf

PDF 9 MB Posted

Attached to
Expand and Upgrade Building 42 for Laboratory
Solicitation number
36C25520R0073
Issued by

About this file

This solicitation is for expansion and upgrade work at the Marion VA Medical Center in Marion, Illinois. The scope of work includes expanding and upgrading Building 42 to accommodate new laboratory facilities. Construction will include a lower level addition as well as renovations to existing spaces. Bids are due by November 8, 2019. The estimated value of the contract is between $5-10 million. The solicitation is set aside for verified service-disabled veteran-owned small businesses. The Department of Veterans Affairs Veterans Health Administration is the contracting agency.

The document includes architectural and engineering drawings detailing the proposed construction. Plans cover site work, new foundations, structural elements, utilities infrastructure, and layouts for all floors and additions. Technical specifications are provided for general contracting as well as trades such as electrical, mechanical, plumbing and technology systems. Drawings and specifications are at 30-60% design development.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

OS

WP/GF

CR

S S

S F

F

C

B

A

54321

J

K

M

L

N

16 17 19

EX/R

EX/R

11 1212

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:55:14 PM

/7

/2

:5

:1

P

M

PARTIAL LOWER LEVEL -

DEMOLITION PLAN

Expand & Upgrade Building 42 for Laboratory

ED100

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

SCALE: 1/8" = 1'-0"

EXISTING LOWER LEVEL - DEMO

GENERAL NOTES

A. DISCONNECT AND REMOVE LIGHTING FIXTURES, DEVICES, EQUIPMENT, AND

CIRCUITRY IN EXISTING W ALLS AND CEILINGS BEING REMOVED. COORDINATE W ALLS

AND CEILINGS BEING REMOVED W ITH ARCHITECTURAL DEMOLITION PLANS.

B. REMOVE ABANDONED W IRING AND CABLING IN AREA OF DEMOLITION PER THE NEC.

C. RELOCATE AND RECONNECT ACTIVE PORTIONS OF THE ELECTRICAL SYSTEM

OUTSIDE OF THE SCOPE OF W ORK, AS REQUIRED, TO MAINTAIN A COMPLETE AND

OPERATIONAL SYSTEM THAT IS FUNCTIONALLY EQUIVALENT TO THE PRE-EXISTING

SYSTEMS PRIOR TO DEMOLITION.

D. REMOVE FIRE ALARM SYSTEM THROUGHOUT DEMOLITION AREA.

PLAN NOTES

1. NOTE OMITTED.

2. NOTE OMITTED.

3. NOTE OMITTED.

4. NOTE OMITTED.

5. NOTE OMITTED.

6. REMOVE SECURITY LIGHTING FIXTURE.

7. REMOVE AND RELOCATE SUMP ALARM & LIGHT.

8. REMOVE AND RELOCATE CARD READER.

9. REMOVE RECEPTACLE.

10. DEVICE LOCATED ABOVE GRADE AT FIRST FLOOR LEVEL.

11. DEVICES IN TUNNEL ARE EXISTING TO REMAIN UNLESS OTHERW ISE NOTED.

12. EXISTING CEILING TO BE TEMPORARILY REMOVED AND REINSTALLED. REMOVE AND

REINSTALL ALL DEVICES. SUPPORT ALL LIGHTING, CABLING AND CONDUIT IN THIS

AREA DURING CONSTRUCTION.

1 BULLETIN #1 05/24/2019

P OS OS

OS

OS

OS

D

C

B

A

54321

C1 C1 C1 C1 C1 C1

C1C1C1C1C1C1

C1 C1 C1 C1 C1 C1

C1

C1 C1 C1 C1

C1C1C1C1C1 D5

X1

D5

X1

EL100

D4

11 1 1 11 11 1

1111111

1 1 11 1 1 1

11 1 1 1 1

1 1 1 11 1

B2

B2

B2

B2

UP

42-EL-3 - 15

Elevator Machine Room

ESB004

Tunnel Access

ECSB002

C1

D4 16

X1

X2

X1

2 2

EX

X1

D4 16

X1

EL100

EX EX EX EX EX EX EX EX

X1

C1

C1

X1

C1

EX EX

EX

EX

EX

X1

MAINnd Floor

LEVEL

100' - 0"

2ND

Floor/InterstiEVEL

117' - 2 1/2"

Existing Lower Level 91' - 9"

Tunnel Level 87' - 9"

D

Lower Level 85' - 10"

Roof Level 135' - 10"

Stair Roof 150' - 8 1/2"

D4

D4

D4

D4

D4

D4

D4

8'

6" 8'

6"

8'

6"

8' -6

8' -6

6' -6

8'

0"

8' -0

X1

8'

0"

DC.2

D

K1

EL100

D4

D4

16X1

X1

9' - 0"

EX/R

EL100

SOUTH

NORTH

MAINnd Floor

LEVEL

100' - 0"

2ND

Floor/InterstiEVEL

117' - 2 1/2"

Existing Lower Level 91' - 9"

Tunnel Level 87' - 9"

Lower Level 85' - 10"

Roof Level 135' - 10"

Stair Roof 150' - 8 1/2"

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 1:09:47 PM

/7

/2

:0 :4

P

M

LOWER LEVEL FLOOR PLAN -

LIGHTING

Expand & Upgrade Building 42 for Laboratory

EL100

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/8" = 1'-0"1 LOWER LEVEL PLAN - LIGHTING

GENERAL NOTES

A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR

CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.

B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR

RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).

C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.

D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING

PLANS.

E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING

PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .

OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.

REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE

TIME OF DELIVERY.

F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO

INSTALLATION.

G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.

H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH

CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL

BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL

DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR

BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. LIFE SAFETY: PANEL "42-EL-3" LOCATED IN BUILDING 42 MAIN ELECTRIC ROOM. PROVIDE NEW

BREAKERS FOR CIRCUITS SHOW N.

b. NORMAL: PANEL "42-9"

1/8" = 1'-0"2 STAIR LIGHTING ELEVATION

1/8" = 1'-0"3 GRADE LEVEL - SOUTH

PLAN NOTES

1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED SO THAT IT

DOES NOT INTERFERE W ITH EQUIPMENT.

2. STEM MOUNT AT 10'-0".

3. RELOCATED SUMP ALARM AND LIGHT.

4. LIGHTING IN THIS AREA IS TEMPORARY. CONNECT LIGHTING IN THIS AREA TO EXISTING

TUNNEL LIGHTING CONTROL. REMOVE LIGHTING PRIOR TO DEMOLITION OF TEMPORARY

TUNNEL.

5. PROVIDE TEMPORARY EXIT SIGN FOR TUNNEL. REMOVE W HEN TEMPORARY TUNNEL IS

DEMOLISHED.

N

Not to Scale

KEYPLAN - AREA OF WORK

1/4" = 1'-0"4 ELEVATOR LIGHTS

OS

OS

D M

DMDMOS OSOS

DM

D M

OS

O S

OS

OS

D M

D M

D M

D M

D M

D M

D M

OS

D M

O S

O S

O S

OS

OS

DM

OS

OS

OS

OS

OS

OS OS

OS

OS

D M

D M

3 3

B

A

54321

2 2

B2b

B2 B2 B2 B2 B2

F1 F1 F1 F1

B2

B2

B2a

B2a

B2a B2a

B2a

B2a

B2a

B2a

X1

X1

B2b

X1

X1

X1 a b

X2

D2

D2 D2

D2 K1

K1

K1 K1

K1

B2

B2

B2

B2

18 18 18 18

B2

B2

B2

B2

B2

B2a

B2a

B2b

B2a

B2a

B2 B2b

14 14

B2

Waiting

E001

Station

E003 Station

E005

Station

E007

Station

E009

Station

E011

Office

E013

Shared Office

E015 Office

E017

Open Office

E010

Phlebotomy

E002

Alcove

E010A

Office

E012

PSA

E014

Pyxis Storage

E008

Corridor

E018C

P. Toilet

E006

Toilet

E020

ADA Toilet

E022

HAC

E024A

Break Room

E024

P. Toilet

E004

Shared Office

E016

Blood Bank

E021

B2

B2

B2

3 3 a b ba

B2a B2a

B2aB2a

Conf

E026

B2

2 2 2

2 2 2 2 2

X2

MATCHLINE

X1

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5 L5

L5

L5

L5

L5

L5

L5

L5a

L5

L5

L5a

L5a

L5

L5 L5

L5a

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5

L5a

L5

L5

L5

L5a

2B2 1B2 19B2 1B2

B2 1 B2 19 B2 2 B2 1 B2 19 B2 2

L5a

14' - 0"

14' - 0"

Cooler

E018A z xy z z r z rp p a b b b b a a a a a

14' - 0"

14' - 0"14' - 0" ab c sr

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:56:20 PM

/7

/2

:5

:2

P

M

PARTIAL MAIN LEVEL FLOOR

PLAN - LIGHTING

Expand & Upgrade Building 42 for Laboratory

EL101A

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/4" = 1'-0"1 MAIN LEVEL - NORTH

N

Not to Scale

KEYPLAN - NORTH

GENERAL NOTES

A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR

CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.

B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR

RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).

C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.

D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING

PLANS.

E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING

PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .

OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.

REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE

TIME OF DELIVERY.

F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO

INSTALLATION.

G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.

H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH

CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL

BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL

DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR

BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. LIFE SAFETY: PANEL "42-EL-3".

b. CRITICAL: PANEL "42-EC-3".

c. NORMAL: PANEL "42-9"

J

DSDS DS

O S

DS

DS

OS

D

C

654321

D4

B2

B2

X1

1D5

D5

D4

D4

D4

B2

B2

16 16

UP/DN

Stair/Elev Vestibule

EC027

Microbiology

E019A

Blood Bank

E021

Bio-Safety Level 3

E019B

Acid/Base

E023A

Histology

E023

IT

E025 dc d

D4

MATCHLINE

X1

Main Lab

E019

19B2

1B2

19B2

1B2

2B2

1B2

2B2

19B2

2B2

1B2

2B2

1B2

19B2

1B2

19B2

1B2

2B2

1B2

19B2

2B2

2B2

1B2

1B2

19B2

2B2

1B2

1B2

1B2 2B2 19B2 2B2

1B2

1B2

2B2

1B2

19B2

2B2

2B2

19B2

1B2

1B2a

1B2a

2B2a

1B2a

19B2a

1B2a

1B2a

19B2a

1B2

2B2 d e b/d b/d d d d d d d e e

K1

14' - 0"

K1 14' - 0"

K1 14' - 0"

F1

Cooler

E018A xy x x y z y x y v w z v z v w v w z w t u t z t z t u t t u s r r z s r r s z p

2B3a

2B3a ab c a c cb a c b b b/d a b c a a b b c c c b/d a c b

42-EC-10A - 22

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:56:47 PM

/7

/2

:5

:4

P

M

PARTIAL MAIN LEVEL FLOOR

PLAN - LIGHTING

Expand & Upgrade Building 42 for Laboratory

EL101B

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/4" = 1'-0"1 MAIN LEVEL - SOUTH

N

Not to Scale

KEYPLAN - SOUTH

PLAN NOTES

1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY

AND BE LOCATED SO THAT IT DOES NOT INTERFERE W ITH

EQUIPMENT.

2. CONNECT TO COOLER LIGHTING.

GENERAL NOTES

A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR

CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.

B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR

RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).

C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.

D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING

PLANS.

E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING

PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .

OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.

REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE

TIME OF DELIVERY.

F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO

INSTALLATION.

G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.

H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

I. PROVIDE PROGRAMMED RAPID START BALLASTS FOR ALL FLUORESCENT FIXTURES AND SUBMIT

BALLAST INFORMATION DURING SHOP DRAW ING REVIEW .

J. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH

CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

K. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL

BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

L. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL

DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

M. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

N. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR

BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

O. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

P. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. LIFE SAFETY: PANEL "42-EL-3"

b. CRITICAL: PANEL "42-EC-3"

c. NORMAL: PANEL "42-9"

P

T

D

C

B

A

54321

Mechanical Room

E102

Mechanical Room

E102

C1 C1 C1 C1

C1

C1

C1 C1 C1 C1

C1

C1

C1 C1 C1 C1 C1

C1 C1 C1 C1 C1 C1

C1 C1 C1 C1 C1

C1C1 C1 C1 C1C1

D4

D5

D5

D4

EL100

X1

4 4 4 4

44134

4 4 4 4 4

4413444

13 4 4 4 4

4134444

UP/DN

D4

D4 16

X1

X2

K1

AHU-1

AHU-2

C1 a a a a a a

C1

X2 8' - 0"

EL100

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:57:04 PM

/7

/2

:5

:0

P

M

INTERSTITIAL LEVEL FLOOR

PLAN - LIGHTING

Expand & Upgrade Building 42 for Laboratory

EL102

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/8" = 1'-0"1 INTERSTITIAL LEVEL - LIGHTING

PLAN NOTES

GENERAL NOTES

A. W HERE MULTIPLE OCCUPANCY SENSORS ARE SHOW N IN A COMMON ROOM OR

CORRIDOR, W IRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.

B. W HERE SW ITCHES ARE SHOW N IN SPACES CONTROLLED BY OCCUPANCY SENSORS, W IRE SENSOR

RELAY PACK AHEAD OF LOCAL SW ITCHING (EXCEPT LIFE SAFETY CIRCUITS).

C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.

D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS W ITH ARCHITECTURAL REFLECTED CEILING

PLANS.

E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN SHOW ING

PROPOSED LAYOUT W ITH DEVICES CLEARLY IDENTIFIED DURING SHOP DRAW ING REVIEW .

OCCUPANCY SENSOR SHOP DRAW ING SUBMITTAL MISSING THIS INFORMATION W ILL BE REJECTED.

REQUEST AutoCAD FLOOR PLANS W ELL IN ADVANCE OF SHOP DRAW INGS TO ENSURE REASONABLE

TIME OF DELIVERY.

F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT W ITH MANUFACTURER PRIOR TO

INSTALLATION.

G. W IRE ALL EXIT SIGNS AHEAD OF LOCAL SW ITCHING.

H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH

CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL

BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

K. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL

DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

L. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE OR

BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

O. UNLESS OTHERW ISE NOTED LIGHTING IS TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. LIFE SAFETY: PANEL "42-EL-3"

b. NORMAL: PANEL "42-9"

1. ELEVATOR PIT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED SO THAT IT DOES NOT

INTERFERE W ITH EQUIPMENT.

2. PROVIDE 4 HOUR SPRING W OUND TIMER.

N

Not to Scale

KEYPLAN - AREA OF WORK

WP/GF

S

AM

I

NO. 28 CLASS II COPPER LIGHTNING CONDUCTOR

DOWN IN EXTERIOR WALL CONSTRUCTION TO

LOWER ROOF OR GROUND

AIR TERMINAL DETAIL AIR TERMINAL DETAIL

AIR TERMINAL DETAILNTS

E

NTS

D

NTSC

NTS

A

NTS

NO. 28 CLASS II COPPER

LIGHTNING CONDUCTOR

(28 X 14 AWG)

CADWELD EXOTHERMIC WELD

CONNECTION TYPE "GR"

N0. 5810 5/8" X 10'-0"

COPPERCLAD GROUND ROD

NO. 230 THRU-ROOF

ASSEMBLY MOUNTED

ON CONCRETE ROOF

DECK EXTENDING

THROUGH INSULATION

& ROOFING MATERIALS

TO 6" ABOVE FINISHED

ROOF FLASHING BY

ROOFING

CONTRACTOR

NO. 28 CLASS II COPPER LIGHTNING

CONDUCTOR (28 X 14 AWG)

NO. 97 1/2" X 36" COPPER, LEAD

COATED CHIMNEY AIR TERMINAL

NO. 251L LEAD COATED

COPPER LOOP

FASTENER WITH

STAINLESS STEEL

SCREWS

NO. 28 COPPER LIGHTNING

CONDUCTOR (28 X 17 AWG)

NO. 28 COPPER

LIGHTNING

CONDUCTOR (28

X 14 AWG)

NO. A37 ALUMINUM

LIGHTNING

CONDUCTOR

NO. A150 ALUMINUM FLAT

SURFACE PLATE

NO. A81 5/8" X 12"

ALUMINUM AIR TERMINAL

NO. A251 ALUMINUM

LOOP CABLE CLIP

NO. A217 ALUMINUM

BONDING PLATE

NO. 211 BIMETAL

CONNECTOR

1/2" STAINLESS STEEL

OR BRASS THREAD

ROD

2" SCHEDULE 40 PVC

WITH CAP LENGTH AS

REQUIRED

NO. 251 COPPER LOOP CABLE CLIP WITH

STAINLESS STEEL SCREW (3'-0" O.C.)

NO. 28 COPPER

LIGHTNING

CONDUCTOR (28

X 14 AWG)

NO. 71, 1/2" X 12"

COPPER AIR TERMINAL

NO. 150 BRONZE

FLAT SURFACE

BASE

B

LIGHTNING PROTECTION

GROUNDING DETAIL

LIGHTNING PROTECTION

THRU-ROOF DETAIL

LIGHTNING PROTECTION

LIGHTNING PROTECTIONLIGHTNING PROTECTION

D

C

B

A

54321

TYP.

2TYP.

D5

D5

DOW N

D4 16D4 16

X1

X3

COOLER

CONDENSER

W P

CU-1

42-EMDP-EQ-1 - 2,4,6

W P

D D

C C

B B

A A

C.2 C.2

B.2 B.2

2.2

2.2

2.1

2.1

A.6 A.6

A.2 A.2

4.5

4.5

3.5

3.5

2.5

2.5

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:57:21 PM

/7

/2

:5

:2

P

M

ROOF PLAN Expand & Upgrade Building 42 for Laboratory

EL103

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/8" = 1'-0"1 ROOF PLAN

PLAN NOTES

1. PROVIDE AIR TERMINALS AS SHOW N.

2. LIGHTNING PROTECTION DOW N CONDUCTOR AND GROUND ROD.

3. LIGHTNING PROTECTION MAIN CONDUCTOR.

4. ELEVATOR SHAFT LIGHTING IS TO BE INSTALLED VERTICALLY AND BE LOCATED

SO THAT IT DOES NOT INTERFERE W ITH EQUIPMENT.

5. CONNECT TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM. PROVIDE

U.L. MASTER LABEL. IF EXISTING BUILDING SYSTEM DOES NOT HAVE A LABEL,

PROVIDE A U.L. LETTER OF FINDINGS FOR ADDITION ONLY.

6. BOND TO METAL STAIR BELOW .

7. BOND TO MECHANICAL EQUIPMENT TO LIGHTNING PROTECTION SYSTEM.

8. DISABLE POW ER TO ACCESS CONTROL UPON FIRE ALARM ACTIVATION.

N

Not to Scale

KEYPLAN - AREA OF WORK

GENERAL NOTES

A. REFER TO ARCHITECTURAL PHASING PLAN AND INCLUDE ALL

W ORK NECESSARY TO ACCOMMODATE PHASING.

B. REFER TO ARCHITECTURAL DRAW INGS FOR INFORMATION ON

SMOKE COMPARTMENTS, SMOKE PARTITIONS AND FIRE

BARRIERS.

C. REFER TO ARCHITECTURAL DRAW INGS FOR LOCATIONS OF FIRE RATED

W ALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE RATED

ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE STOPPED AS

REQUIRED TO MAINTAIN FIRE RATINGS AS INDICATED.

D. LIGHTNING PROTECTION PLAN SHOW N FOR REFERENCE ONLY.

SYSTEM SHALL BE DESIGNED PER NFPA 780 AND SUBMITTED

W ITH SHOP DRAW INGS.

E. COMPLETED SYSTEM SHALL MEET THE INSTALLATION REQUIREMENTS

FOR LIGHTNING PROTECTION SYSTEMS, "UL96A" OF UNDERW RITERS

LABORATORIES INC., NFPA 780 AND SHALL BEAR THE MASTER LABEL

OF UNDERW RITERS LABORATORIES INC.

F. LAYOUT IS FOR BIDDING PURPOSE AND REFERENCE ONLY.

SUCCESSFUL CONTRACTOR SHALL PREPARE FINAL LIGHTNING

PROTECTION DRAW INGS AND DETAIL AND SUBMIT DURING SHOP

DRAW ING PHASE FOR REVIEW .

G. REFER TO LIGHTNING PROTECTION SPECIFICATIONS.

H. INCLUDE BONDING OF ALL ROOF MOUNTED EQUIPMENT, VENTS, ETC

PER NFPA 780.

GF

J

G F

J

SP-1

26 26

42-EQ-11-A - 2

42-EL-4 - 11

42-EQ-11 - 14,16,18

42-EL-4 - 11

EX

D

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:57:38 PM

/7

/2

:5

:3

P

M

LOWER LEVEL FLOOR PLAN -

POWER

Expand & Upgrade Building 42 for Laboratory

EP100

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/8" = 1'-0"1 LOWER LEVEL PLAN - POWER

A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.

B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

C. EMT CONDUIT SHALL BE 0.75" M INIMUM.

D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING

EQUIPMENT.

E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.

I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE

OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. CRITICAL: PANEL "42-EC-10"

b. LIFE SAFETY "42-EL-4"

c. NORMAL: PANEL "42-10"

GENERAL NOTES

1/8" = 1'-0"2 GRADE LEVEL POWER - SOUTH

PLAN NOTE

1. PROVIDE NON-FUSIBLE DISCONNECT INSTALLED IN HOISTW AY. COORDINATE W ITH ELEVATOR

MANUFACTURER PRIOR TO INSTALLATION.

2. RUN 2-4"C, (2) 2" CONDUIT AND (4) 1" CONDUIT FROM THIS FLOOR TO THE INTERSTITIAL LEVEL FOR

FUTURE USE.

3. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE CEILING.

4. PROVIDE 120V-30A FUSIBLE DISCONNECT SW ITCH (FUSED AT 20 AMPS). FOR ELEVATOR CAB LIGHTS.

5. CIRCUIT TO LOCAL RECEPTACLE CIRCUIT.

N

Not to Scale

T R T R

TR

TR

T

RT

R

G F

G F

G F

G F

G F

G F

G F

G F

G F

G F

/C M

G F

/M W

PX

PX

PX

PX

ICE

G F

TV

84" MH

J

J

J

J

J

J

J

J T

V

M H

J

G F

R F

/G F

B

J J

J J J J

J

J

U C

/G F

B

TV

84" MH

B

A

54321

2 2

5 5 5 5

4 4 4 4 4

16 17 18

1 1 1 2 2

14 14

5 14

42-EC-10 - 18

42-EC-10 - 18

42-EC-10 - 18

42-EC-10 - 18

42-EC-10 - 18

42-EC-10 - 18

Conf

E026

Waiting

E001

Station

E003

Station

E005

Station

E007

Station

E009 Station

E011

Office

E013

Shared Office

E015

Office

E017

Open Office

E010

Phlebotomy

E002

Alcove

E010A

Office

E012

PSA

E014

Pyxis Storage

E008

Corridor

E018C

P. Toilet

E006

Toilet

E020

ADA Toilet

E022

HAC

E024A

Break Room

E024

P. Toilet

E004

Shared Office

E016

4 4 4

5 5 5

42-10A - 26,28

42-EC-10B - 9,11

42-10A - 25,27

42-EC-10B - 13,15

42-10A - 31,33

42-EC-10A - 5,7

42-10A - 30

42-EC-10B - 12

42-EC-10 - 18

42-EC-10 - 18

42-EC-10 - 18

42-10C - 9

15 15 15 23

42-10A - 21,23

42-EC-10B - 8,10

42-10B - 33

42-EC-10C - 20

42-EC-10 - 18

42-EC-10 - 18

7 7

MATCHLINE

42-EL-442-T-EC 42-T-EL42-EMDP-EC-2

1500 KVA

TRANSFORMER

HIGH

VOLTAGE

SW ITCH

600A

HIGH

VOLTAGE

SW ITCH

600A

DIG. MTR

MTR ANT

STOR.

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:58:03 PM

/7

/2

:5

:0

P

M

PARTIAL MAIN LEVEL FLOOR

PLAN - POWER

Expand & Upgrade Building 42 for Laboratory

EP101A

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/4" = 1'-0"1 MAIN LEVEL - NORTH

N

Not to Scale

KEYPLAN - NORTH

PLAN NOTES

1. LOW VOLTAGE TRANSFORMER ABOVE LAY-IN CEILING FOR SENSOR OPERATED

FAUCET/FLUSH VALVE PROVIDED BY DIVISION 22. PROVIDE RECESSED SINGLE GANG

J-BOX AT EACH LAV/W ATER CLOSET AND 0.75"C. TO ABOVE ACCESSIBLE CEILING FOR

LOW VOLTAGE W IRING BY DIVISION 22. PROVIDE GROMMETTED OPENING.

COORDINATE EXACT M.H. W ITH DIVISION 22 PRIOR TO ROUGH-IN.

2. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE

CEILING.

3. PROVIDE JUNCTION BOX FOR FURNITURE SYSTEM. COORDINATE EXACT LOCATION

AND QUANTITY OF NEUTRAL / GROUND W IRE REQUIRED W ITH FURNITURE SYSTEM

VENDOR.

4. PROVIDE 120V CONNECTION ABOVE CEILING FOR MOTORIZED W INDOW SHADES.

5. PROVIDE ROUGH-IN AND W IRING / CONDUIT FOR MOTORIZED W INDOW SHADE

SW ITCH.

6. PROVIDE 0.75" CONDUIT TO INTERSTITIAL ROOM FOR FUTURE POW ER CIRCUIT.

7. PROVIDE SURFACE MOUNTED MULTI-CHANNEL/SERVICE FINISHED ALUMINUM RACE

W AY (HEAVY 0.080" T5 EXTRUDED ALUMINUM CHANNEL, FOUR RIBS FOR SNAP-IN

DIVIDERS, SNAP -IN 0.075" T5 EXTRUDED ALUMINUM COVER, 0.050" DIVIDER) W ITH

HOSPITAL GRADE DUPLEX RECEPTACLES 24" O.C. (ALTERNATE BETW EEN THE (2)

BRANCH CIRCUITS FOR BOTH NORMAL AND CRITICAL. PROVIDE POW ER TO RACEW AY

CONCEALED THROUGH W ALL FROM ABOVE CEILING. PROVIDE GFCI CIRCUIT

BREAKER. COORDINATE MOUNTING HEIGHT W ITH ARCH.

A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.

B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

C. EMT CONDUIT SHALL BE 0.75" M INIMUM.

D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING

EQUIPMENT.

E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.

I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE

OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. CRITICAL: PANEL "42-EC-10"

b. NORMAL: PANEL "42-10"

M. PROVIDE GFCI BREAKER FOR ALL LAB RACEW AY CIRCUITS.

GENERAL NOTES

R F

RF

72" MH

G F

RF/GFB

J J J a

J b

J c

J

J

R F

FRZ

FRZ

G F

J

J

GF

72" MH

D

C

654321

3 3

42-10 - 29

27,29

26,28

Stair/Elev Vestibule

EC027

Microbiology

E019A

Blood Bank

E021

Bio-Safety Level 3

E019B

Acid/Base

E023A

Histology

E023

IT

E025 a b c

42-EC-10C - 18

42-EC-10C - 4

42-EC-10C - 2

42-EC-10C - 3

42-EC-10C - 5

42-10A - 5,7

42-EC-10A - 9,11

42-10A - 6,8

42-EC-10A - 6,8

42-EC-10C - 1

42-10A - 1,3

42-EC-10A - 1,3

42-EC-10A - 2,4

42-10A - 2,4

42-EC-10A - 13,15

42-10A - 9,11

42-10A - 13,15

42-EC-10A - 17,19

42-EC-10A - 18,20

42-10A - 10,12

42-EC-10B - 1,3,5

42-10A - 14,16,18

42-10A - 20,22,24

42-EC-10B - 2,4,6

42-10A - 31,33

42-EC-10A - 5,7

42-10A - 30

42-EC-10B - 12

42-EC-10B - 14,16

42-10A - 32,34

42-10A - 17,29

42-EC-10B - 17,19

42-10B - 14,16

42-10B - 13,15,17

42-EC-10B - 27,29,31

42-EC-10B - 28,30

42-10B - 10,12

42-10B - 35,37

42-EC-10B - 24,26

42-10B - 9,11

42-EC-10B - 32,34

42-10B - 6,8

42-EC-10B - 20,22

42-10B - 1,2,3

42-EC-10B - 18,21,35

42-10C - 5,7

9 9

Cooler

E018A

42-10B - 5,7

42-EC-10B - 23,25

42-10B - 19,21,23

42-10B - 25,27

42-10B - 32,34

42-EC-10A - 21,23,25

42-EC-10A - 30,32,34

42-10B - 26,28,30

42-EC-10A - 27,29

42-EQ-11-A - 6

42-10C - 4,6

42-EC-10C - 19,21

42-EC-10A - 14,16

42-EC-10A - 24,26

42-10B - 29,31

42-EC-10A - 10,12

42-10B - 36,38

42-EC-10A - 35,37

42-10B - 33

42-EC-10C - 20

42-10B - 22,24

42-EC-10C - 6,8

MATCHLINE

TYP.

TYP.

TYP.

GFCI

42-10C - 10,12

42-10B - 18,20

TYP.

HIGH

VOLTAGE

SW ITCH

600A

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:58:34 PM

/7

/2

:5

:3

P

M

PARTIAL MAIN LEVEL FLOOR

PLAN - POWER

Expand & Upgrade Building 42 for Laboratory

EP101B

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/4" = 1'-0"1 MAIN LEVEL - SOUTH

N

Not to Scale

KEYPLAN - SOUTH

PLAN NOTES

1. PROVIDE 120V CONNECTION FOR HOOD.

2. PROVIDE 208V-30A RECEPTACLE FOR DATA RACK. COORDINATE EXACT LOCATION

W ITH DIV. 27.

3. PROVIDE 120V CONNECTION ABOVE CEILING FOR MOTORIZED W INDOW SHADES.

4. PROVIDE SURFACE MOUNTED MULTI-CHANNEL/SERVICE FINISHED ALUMINUM RACE

W AY (HEAVY 0.080" T5 EXTRUDED ALUMINUM CHANNEL, FOUR RIBS FOR SNAP-IN

DIVIDERS, SNAP -IN 0.075" T5 EXTRUDED ALUMINUM COVER, 0.050" DIVIDER) W ITH

HOSPITAL GRADE DUPLEX RECEPTACLES 24" O.C. (ALTERNATE BETW EEN THE

BRANCH CIRCUITS FOR BOTH NORMAL AND CRITICAL. PROVIDE POW ER TO

CONCEALED THROUGH W ALL FROM ABOVE CEILING. PROVIDE GFCI CIRCUIT

BREAKER. COORDINATE MOUNTING HEIGHT W ITH ARCHITECT.

5. PROVIDE MULTI-CHANNEL ALUMINUM POW ER POLE. MOUNT TW O RECEPTACLES ON

POW ER POLE. MOUNT ONE STANDARD 20A-120V DUPLEX RECEPTACLE ON POW ER

POLE. MOUNT ONE 208V-30A RECEPTACLE ON POW ER POLE FOR UPS/EQUIPMENT.

VERIFY CIRCUIT / RECEPTACLE SIZE PRIOR TO ROUGH-IN / ORDERING. RUN 3-#8, #10

GRD., IN 1"C. FOR 208V/30A RECEPTACLE.

6. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY ABOVE

CEILING.

7. PROVIDE ELECTRICAL CONNECTION FOR W ALK IN COOLER EVAPORATOR.

8. PROVIDE ROUGH-IN AND W IRING / CONDUIT FOR MOTORIZED SHADE SW ITCH.

9. PROVIDE 0.75" CONDUIT TO INTERSTITIAL ROOM FOR FUTURE POW ER CIRCUIT. SPARE

STUBBED NEAR PANEL LOCATION.

A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.

B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

C. EMT CONDUIT SHALL BE 0.75" M INIMUM.

D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING

EQUIPMENT.

E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.

I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE

OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. CRITICAL: PANEL "42-EC-10C"

b. NORMAL: PANEL "42-10C"

DI

WP/GF

D

C

B

A

54321

Mechanical Room

E102

AHU-1

AHU-2

42-EC-10

42-EC-10A

42-EQ-11

42-EQ-11-A

42-9

T-EQ-11-A

42-10A

42-10

30 30

EF-1 EF-2 EF-3HWP-1HWP-2

42-EQ-11 - 8,10,12

42-EQ-11 - 13,15,17

DDC

42-EC-10B

42-10B

42-EQ-11-A - 3

42-EQ-11-A - 4

COOLER

CONDENSER

42-EQ-11-A - 5,7

42-EC-10C

42-10C

42-EQ-11 - 1,3,5

42-EQ-11 - 2,4,6

FACP

42-EQ-11-A - 8

42-EQ-11-A - 9

42-EQ-11 - 7,9,11

W P

Stair/ Elev Vestibule

EC101

Space

CB461

42-EL-4 - 9 2

SOUTH

NORTH

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:58:51 PM

/7

/2

:5

:5

P

M

INTERSTITIAL LEVEL FLOOR

PLAN - POWER

Expand & Upgrade Building 42 for Laboratory

EP102

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

N

1/8" = 1'-0"1 INTERSTITIAL LEVEL - POWER

A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.

B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SW ITCH COVERPLATES INDICATING PANEL

AND CIRCUIT NUMBER.

C. EMT CONDUIT SHALL BE 0.75" M INIMUM.

D. REFER TO DIVISION 22/ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL PLUMBING

EQUIPMENT.

E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW

FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.

F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH W IRING DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

H. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.

I. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

J. REFER TO ARCHITECTURAL DRAW INGS FOR RATED W ALL LOCATIONS.

K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE

OR BELOW CASEW ORK, FURNITURE, LAVATORIES, ETC.

L. UNLESS OTHERW ISE NOTED POW ER DEVICES ARE TO BE CIRCUITED TO THE FOLLOW ING PANELS:

a. CRITICAL: PANEL "42-EC-10"

b. NORMAL: PANEL "42-10"

GENERAL NOTES

PLAN NOTES

1. PROVIDE 120V/1PH CONNECTION TO ACCESS CONTROL POW ER SUPPLY

ABOVE CEILING.

2. PROVIDE NEW 20A/1P BREAKER IN PANEL "42-EL-4".

N

C100

DN

UP

DN

J PC

Main Hospital

Outpatient ClinicDental/S

PD &

Clinics

Dental/S

PD &

Clinics

Canteen/ Clinics P ro p o s e d

A d d it io n

Engineering / Safety

East Trailer

SNRF

Project Location

N

D

C

B

A

54321

EXISTING STEAM TUNNEL

PB

ABANDON SIGNAL MAN HOLE

MH #4BB

EX.

NEW

M.H.

EX

MH #4A

EXISTING

EM DUCTBANK

BUILDING 42

CRAW L SPACE

EX. MH #4B

EXISTING

EM DUCTBANK

EXISTING

TO MH #4AA (FEEDER #3)

TO MH EMH #4 (FEEDER #1, #2)

FEEDERS #1, #3 7

E604

EX. TO

BLDG #8

TO BLDG #43

NEW LAB ADDITION

E604

5 2

EXISTING BUILDING #42

PULLBOX

42-9 - 7

NEW

M.H.

G

A

B

C

E

J

K

M

L

N

P

15 16 17

H

PB

UNIT SUB "A"

ABOVE

EX EX

1 4-4" C.

4-4" C.

13 4-4" C.

1 2-4" C.

1 2-4" C.

UNIT SUB "B"

ABOVE

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:59:19 PM

/7

/2

:5

:1

P

M

PARTIAL SITE PLAN Expand & Upgrade Building 42 for Laboratory

ES100

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG CLM

Not to Scale

KEYPLAN - CAMPUS

SCALE: 1/16" = 1'-0"

SITE PLAN

NOTES

1. NEW 15 KV FEEDER IN CONCRETE ENCASED DUCTBANK.

2. UP TO UNIT SUB "A".

3. REMOVE 15 KV FEEDER AND CONCRETE DUCTBANK.

4. EXCAVATE EACH SIDE OF CONNECTOR AND DIRECTIONAL BORE NEW 4-4"C. UNDER

NEATH.

5. RUN NEW 15KV FEEDER IN CRAW LSPACE IN RIGID METALLIC CONDUIT PAINTED PER

SPECIFICATIONS W ITH PROPER SIGNAGE.

6. PRIMARY DUCTBANK MUST CROSS STEAM TUNNEL. REMOVE AND REPLACE 15KV

FEEDER IN EXISTING CONDUIT.

7. REMOVE AND REPLACE 15KV FEEDERS IN EXISTING CONDUIT.

8. EXCAVATE EACH SIDE OF THE STEAM TUNNEL AND DIRECTIONAL BORE UNDER NEATH.

9. APPROXIMATE LOCATION OF 002 PRIMARY GEAR B.

10. PROVIDE 277V/1PH CONNECTION FOR SITE LIGHTING. RUN THROUGH PHOTOCELL ON

ROOF.

11. EXISTING FEEDERS UP TO UNIT SUB "B".

12. PROVIDE SPECIFICATION GRADE 277V PHOTOCELL ON ROOF FOR SITE LIGHTING

CONTROL.

13. FORM AND POUR MANHOLE IN PLACE DUE TO VERY LIMITED SPACE AVAILABLE. MANHOLE

SHALL BE TIGHT TO STEAM TUNNEL W ALL. CONDUITS UNDER TUNNEL SHALL BE BORED

FIRST.

14. SIZE PER NEC.

15. PROTECT IN PLACE.

16. EXISTING 15KV FEEDERS.

A. REFER TO SEQUENCE OF CONSTRUCTION NOTES ON SHEET E001 FOR PHASING.

B. REFER TO DUCTBANK PROFILE ON SHEET ES102.

C. PROVIDE ALL SHORING, PLATE STEEL AND BARRICADES REQUIRED.

FEC

FEC

101 102

102B 102B

102C

102D

102A

104A

106A 106

107107A

108110

114A

114B

115A 116A

119A

119B

119C 119D 119E 120A

121A121B

C101-02

C102-02

C103-02

C104-02

C105-02

C106-02

P4

P3

SB1-02

105A

DN

DN

FEC

FEC

103104105105A

110109 111

115 116 117

118B

129130

102A

123A

FEC

FEC

FEC

102A

103A 103B 103C 104

106A

106B

106C

106D

107A

107B 107C 107D

107E

109A

110A

110B

110C

110D

113A

113B

113C

116A

117118

S102-01

118A

118B

119B

119A

119C 119

S101-01

S104-01

S105-01

S103-01

103D

P-2

P-1

P-7

UP UP

UP

CB2-38

006A005A

006B

CB3-38

CB1-38

SC

D

C

B

A

BLDG. 1

BLDG 38

BLDG 2

BLDG 37

TEL DATA

3 4

BLDG 42

G

A

D

B

C

E

F

J

K

M

L

N

P

3 4

65 78

10 11 13 15

16 17

QR

S

T

H

2.8

D

C

B

A

C.2 C.2

B.2 B.2

2.2

2.2

2.1

2.1

A.6 A.6

A.2 A.2

3.5

3.5

2.5

2.5

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

BBBB

AAAA

CCCC

DDDD

EEEE

FFFF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1111 2222 3333 4444 5555 6666 88887777 9999

FFFF

EEEE

DDDD

CCCC

BBBB

AAAA

99997777 8888666655554444333322221111

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 O ld West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel Fax

618.529.5262 618.457.8991

Geotechnical

Heapy Project No.: 2017-05045 Firm License No. 01528

11/7/2019 12:59:31 PM

/7

/2

:5

:3

P

M

PARTIAL SITE PLAN -

TECHNOLOGY

Expand & Upgrade Building 42 for Laboratory

ES101

657-502

MARION, ILLINOIS

11/08/2019

BID DOCUMENTS

MSG JC

SCALE: 1" = 20'-0"

COMPOSITE SITE TECHNOLOGY SITE PLAN

PLAN NOTES

1. NEW COPPER BACKBONE CABLING RUN ABOVE CEILING FROM EXISTING TELEPHONE ROOM.

2. NEW FIBER BACKBONE CABLING RUN ABOVE CEILING FROM EXISTING DATA ROOM.

3. UTILIZE EXISTING BUILDING MOUNTED PULLBOX.

4. UTILIZE EXISTING UNDERGROUND CONDUITS, PROVIDE NEW INNERDUCT FOR NEW FIBER.

5. CABLE TO BE ROUTED IN EXISTING CABLE TRAY IN EXISTING PIPE-BASEMENT. REFER TO SHEET ET300.

6. CABLE TO TRANSITION FROM STEAM TUNNEL TO PIPE BASEMENT IN NEW CONDUIT.

7. CABLE TO BE ROUTED IN EXISTING CABLE TRAY IN EXISTING STEAM TUNNEL.

8. CABLE TO BE ROUTED IN NEW CONUIT. PROVIDE INNERDUCT IN CONUIT FOR FIBER. REFER TO SHEET ET300.

9. RERER TO SHEET ET200

HORIZ: 1'=10' VERTICAL 1"=5'

NORTH ELECTRIC DUCT BANK PROFILE STA: 0+00N TO 2+58N1

HORIZ: 1'=10' VERTICAL 1"=5'

SOUTHWEST ELECTRIC DUCT BANK PROFILE STA: 0+00 TO 2+482

NOTE: CONTRACTOR SHALL TAKE EXTRA CARE TO PROTECT ALL TREES, BUSHES,

SURVEY MONUMENTS, R.O.W. MARKERS AND OTHER EXISTING SITE FEATURES THAT

ARE TO REMAIN. ANY DAMAGE TO EXISTING FEATURES TO REMAIN SHALL BE FIXED AT

THE CONTRACTORS OWN EXPENSE AND BE RESTORED TO IT'S ORIGINAL CONDITION.

A DETAILED UTILITY SURVEY WAS NOT CONDUCTED ON THIS PROPERTY OR AS A PART

OF THIS SURVEY. THE LOCATIONS OF ANY UNDERGROUND UTILITIES AS SHOWN HEREON

ARE BASED ON ABOVE GROUND STRUCTURES AND UTILITY MAPS AS PROVIDED BY

UTILITY OWNERS. LOCATIONS OF UNDERGROUND UTILITIES/STRUCTURES MAY VARY

FROM LOCATIONS SHOWN HEREON.

This is the start of the file's text. The full file is on GovTribe.