P09 657-502 Bid Drawings Part 6 of 10 Mechanical-21 pages.pdf
PDF 6 MB Posted
- Attached to
- Expand and Upgrade Building 42 for Laboratory
- Solicitation number
- 36C25520R0073
About this file
This solicitation document is for the expansion and upgrade of Building 42 for laboratory use at the Marion VA Medical Center. The solicitation requests proposals for mechanical, electrical, and plumbing construction services. Proposals are due by January 15, 2020, with award anticipated by March 1, 2020. The work includes upgrading existing mechanical, electrical, and plumbing systems as well as installing new systems to support laboratory functions. The contract will have a one-year base period of performance with four one-year options. The solicitation is designated as a VA small business set-aside. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is the contracting agency.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet List
Sheet Number Sheet Name Sheet Order
MQ001
MQ002
MQ003
MQ005 MECHANICAL DETAILS
MQ004
MQ006
MQ007
MQ008
MQ009
MQ010
MH101 LOWER LEVEL - HVAC DUCT PLAN
MH102 FIRST FLOOR - SUPPLY DUCT PLAN
MP101
MP102
SECOND FLOOR MEZZANINE - SUPPLY DUCT PLAN
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MH103
LOWER LEVEL - HVAC PIPING PLAN
FIRST FLOOR - HVAC PIPING PLAN
MECHANICAL ROOF PLANMP201
MQ011 MECHANICAL DETAILS
MP103 SECOND FLOOR - HVAC PIPING PLAN
LOWER LEVEL - RETURN AND EXHAUST PLANMH104
MH105 SECOND FLOOR MEZZANINE - SUPPLY DUCT PLAN
MH106 HVAC ISOMETRICS
FEEDWATER SAMPLE (FROM DEAERATOR)
BOILER WATER SAMPLE
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF
TUBE CLEANER WATER SUPPLY
COMPRESSED AIR
OVERFLOW
COLD WATER (CITY WATER)
LIQUEFIED PETROLEUM GAS IGNITER FUEL
NATURAL GAS IGNITER FUEL
NATURAL GAS MAIN FUEL
HOT WATER
SOFTENED WATER
FUEL OIL RETURN
FUEL OIL SUPPLY
RISER CLAMP (TYPE 42)*
FLOOR-SUPPORTED PIPE STAND
CLEVIS-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
ROLLER-TYPE HANGER
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
STANDARD PRACTICE SP-58
SLIDING SUPPORTS (TYPE 35)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
WALL BRACKET (TYPE 31, 32, 33)*
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY
QUICK-COUPLE HOSE CONNECTOR
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
WATER LEVEL CONTROLLER
FLOW METER
ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.
THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.
TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL
UNITS, FILTERS, COILS, ETC.
FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD
EQUIPMENT DETAILS.
DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING
DIFFUSERS, REGISTERS, AND GRILLES.
DRAWING SYMBOLS
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
DRAWING NUMBER WHERE DRAWN
DUCTWORK SYMBOLS
BACK DRAFT DAMPER
SECTION.)
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
FIRE DAMPER
DUCT WITH SOUND LINING
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
DUCTWORK SYMBOLS
(WALL TYPE)
(WALL TYPE)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT ON LIMIT OF
DEMOLITION
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SQUARE 1-WAY CEILING DIFFUSERS
DUCTWORK SYMBOLS
DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)
RETURN, NO SPLITTER (45° TAP)
STANDARD BRANCH SUPPLY OR
MANUAL SPLITTER DAMPER
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
COMBINATION FIRE/SMOKE DAMPER
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
AIR TERMINAL SYMBOLS
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
DOUBLE DUCT MIXING BOX.
TERMINAL UNIT WITH REHEAT COIL
PIPING SYMBOLS
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HOT WATER HEATING SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
VENT LINE
SOLAR WATER RETURN
SOLAR WATER SUPPLY
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN LINE
MAKE-UP WATER
CONDENSER WATER RETURN (TO TOWER)
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
CONDENSER WATER SUPPLY (FROM TOWER)
HOT WATER HEATING RETURN
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURN
EXISTING PIPE TO BE REMOVED
PIPING SYMBOLS
VACUUM CONDENSATE RETURN
CONDENSATE TRANSFER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
GENERAL PIPING SYMBOLS
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENT
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
MANUAL AIR VENT
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
VALVE SYMBOLS
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
WATER BALANCE DEVICE
CIRCUIT SETTER VALVE
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN
(STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY
(STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING)
PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE
DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT
EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
C CENTIGRADE (CELCIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE
DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS
(SUBMISSION1)
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL
DAMPER,MODULATING
ACD-TP AUTOMATIC CONTROL
DAMPER,TWO POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
CD-2 CONSTRUCTION DOCUMENTS
(SUBMISSION2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
(TO COOLING TOWER)
CWS CONDENSER WATER SUPPLY
(FROM COOLING TOWER)
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DD-1 DESIGN DEVELOPMENT
(SUBMISSION1)
DD-2 DESIGN DEVELOPMENT
(SUBMISSION2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
ABBREVIATIONS
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J INTENTIALLY LEFT BLANK
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN
(STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR
INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
WAG WASTE ANETHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
1.
2.
3.
4.
5.
6.
7.
8.
GENERAL NOTES
LOCATION OF EXISTING TO REMAIN
CROSS HATCHED AREAS ARE NOT IN
CONTRACT AND ARE EXISTING TO REMAIN,
UNLESS SPECIFICALLY NOTED OR SHOWN
OTHERWISE.
MECHANICAL GENERAL PROJECT NOTES:
FOR GENERAL DUCT CONSTRUCTION SEE DETAILS ON MECHANICAL DETAILS SHEETS.
ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE
TRADE, AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND
STANDARDS.
CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE,
HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES,
ENLARGED FOR CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR
APPURTENANCES REQUIRED TO PROVIDE A COMPLETE AND COORDINATED SYSTEM
SHALL BE BORNE BY THE CONTRACTOR.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF
CEILING MOUNTED MATERIALS INCLUDING ALL DIFFUSERS, GRILLES, AND REGISTERS.
THE H.C. SHALL COORDINATE DUCTWORK INSTALLATIONS WITH OTHER TRADES.
LIGHTING AND DUCTWORK DESIGNS INDICATED ON CONTRACT DRAWINGS WERE
COORDINATED, HOWEVER CONFLICTS WITH DUCTWORK AND LIGHTS MAY ARISE DUE TO
GRID INSTALLATION. MECHANICAL CONTRACTOR. SHALL BE RESPONSIBLE FOR ALL
DUCTWORK MODIFICATIONS AND OFFSETS REQUIRED TO AVOID FIELD CONDITIONS.
BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE MAIN.
FLEXIBLE DUCTWORK IS LIMITED TO A MAXIMUM LENGTH OF 3 FEET, WITH NO DIPS,
SAGS, OR TIGHT ELBOWS; AND ON SUPPLY DUCTWORK ONLY. FLEXIBLE DUCTWORK
SHALL BE AN INSULATED, SEMI-RIGID AND LIGHT WEIGHT AIR DUCT, MANUFACTURED
BY USING DEAD SOFT ALUMINUM STRIP WHICH IS SPIRALLY WOUND AND
MECHANICALLY JOINED TOGETHER FORMING AN AIR TIGHT-LEAKPROOF TRIPLE LOCK
SEAM. DUCT TO BE SELF-SUPPORTING AND CORROSIVE RESISTANT UL-181 CLASS I
PRODUCT, WITH A POLYETHYLENE VAPOR BARRIER. FLEXIBLE DUCTWORK TO BE LIKE
MASTERFIT UPC-018 (ACOUSTICAL) OR AN APPROVED EQUAL.
PROVIDE NECK PLENUMS ON RETURN AND EXHAUST GRILLES AS REQUIRED. SEE
DETAILS.
PROVIDE TURNING VANES IN ALL SQUARE ELBOWS. SEE DETAILS.
ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, UNIT HEATERS,
ETC. SHALL BE HUNG FROM THE TOP CHORD OF THE STRUCTURAL STEEL.
EACH MAIN DUCT PASSING THROUGH FLOOR SPACES OR FIRE BARRIERS SHALL BE FIRE
ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.
CONTRACTORS ARE TO REVIEW EXISTING STRUCTURAL AND PLANS, WITH ACTUAL
LAYOUT OF BEAMS, JOISTS, ETC. TO AVOID CONFLICT BETWEEN DUCT. ADJUST DUCT
ROUTING TO ACCEPT STRUCTURAL CONDITIONS.
ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A
MINIMUM OF 25'-0" AWAY FROM OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL
AND STATE CODES MANDATE ADDITIONAL DISTANCE.
CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL
EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON
ORDER
WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL
WATER-TIGHT ALL AROUND LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL
COORDINATE PAINTING REQUIREMENTS FOR LOUVERS WITH GENERAL CONTRACTOR
PRIOR TO SUBMITTING BID.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
L.
M.
N.
O.
THIS SYMBOL SHOWS THE APPROXIMATE POINT WHERE
NEW WORK STARTS AND EXISTING IS TO REMAIN. FOR
DEMOLITION THIS SYMBOL SHOW THE APPROXIMATE POINT
WHERE DEMOLITION STOPS AND EXISTING IS TO REMAIN
FOR REVISED WORK.
K.
DAMPERED. SEE ARCHITECTURAL PLANS.
RH
SCH
SH
TH
PS
RC
WB
CSH
SS
LC
M
H4
H7
A
BDD
FC
10x8
FD
VD
DN
DN
UP
UP
D
R
DNUP
SUPPLY
RETURN45°
45°
N
2 1
1/24
F/S DPR
MB
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CHWR
CHR
GCR
RL
RS
RHG
CHWS
CHS
GCS
MW
D
GRR
GRS
X
VR
CTPS
CTPD
FWPS
FWPD
CF
FWS
BWS
CBD
BO
TC
A
OFL
HW
SW
CW
FOR
FOS
LPG(I)
G(I)
G
AV
MV
FE
E.T.R.
ENGINEERS
T A
TE
OF I L L
NO
I S
ER
AW
LUOBEDAW
LRAE
I
062-044274
REGISTERED
PROFESSIONAL
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel
Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel
Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel
Fax
618.529.5262 618.457.8991
Geotechnical
11/8/2019 10:53:22 AM
MECHANICAL NOTES &
ABBEVIATIONS
Expand & Upgrade Building 42 for Laboratory
MQ-001
657-502
Marion, IL
11-07-2019
Bid Document
DH BZ
SUPPLY
RETURN 1
1 4 CFM/ SQ. FT.
4 CFM/ SQ. FT. 8 CFM/ SQ. FT.
8 CFM/ SQ. FT. 350°F.
350°F. 0.05 @ 1,200 FPM
0.11 @ 2,500 FPM
AIRFOIL BLADES
ALL SUPPLY FSD'S * SEE PLANS FOR SIZE
ALL RETURN FSD'S * SEE PLANS FOR SIZE
NOTE:
50704.97.096 77 5075LAB AREAS
* INCREASE DAMPER SIZE IF REQUIRED TO MAINTAIN INDICATED STATIC PRESSURE LOSS.
REMARKS
40.0ORIFICECHILLED WATER 2"WFMD-1
GPM
SIZECAPACITYTYPESYSTEM
WATER FLOW MEASURING DEVICES
UNIT NO. LOCATION
REMARKSMIN. STATIC DEFL.TYPE
ISOLATOR
RAILAHU-1
UNIT. NO. TYPE BASE
VIBRATION ISOLATION FOR EQUIPMENT
D ---
DUCT LEAKAGE CLASSIFICATION AND ALLOWABLE LEAKAGE
SEAL CLASSDUCT PRESSURE
C
APPLICABLE SEALINGS SMACNA LEAKAGE CLASS
CLASS, W.G.
3" B TRAVERSE JOINTS AND SEAMS 12
4", 6", 10" A JOINTS, SEAMS AND ALL WALL PENETRATIONS 6 3
12TRAVERSE JOINTS ONLY
RECTANGULAR
DUCT DUCT
ROUND
.06 AHU-1
.065000SUPPLY
RETURN--
-- AHU-1MEZZANINEAFM-S1
AFM-R1
AFM-OA1 O.A. 1300 .06 AHU-1
11,500
1/2", 1", 2"
REFER TO "MOTORS" SECTION OF THE SPECIFICATIONS.
ALL MOTORS 1HP AND LARGER SHALL BE ENERGY
EFFICIENT TYPE.
AFM-S2
AFM-E2
AFM-OA2
MEZZANINE
MEZZANINE
MEZZANINE
MEZZANINE
MEZZANINE
SUPPLY
EXHAUST
O.A.
11,500
.06
.06
.06
AHU-2
AHU-2
AHU-2
MEZZANINE
96.0 3"ORIFICECHILLED WATERWFMD-2 MEZZANINE
RAILAHU-2 D ---
OFFICE AREAS 40704.97.096 77 5075
11,50011,500 11,50011,500
AFM-R2 MEZZANINE -- EXHAUST .06 AHU-2 111,50011,500
FMB,SAH
85% 30%5,000
AHU-1
AHU-1
FF-1
PF-1 PLEATED
5,000 CARTRIDGE
O.1 0.3
0.65O.3 SAH
NOTE:
13"352,076238STEAM
SIZE REMARKS
PSIG
SET PRESS.MIN. CAP.
LBS/HRF
TEMP.FLUID
PRV STATIONSV-1
SAFETY VALVES & RELIEF VALVES
UNIT. NO. SYSTEM
2"1-1/2"2,07625110
D2D1
SIZES
PIPE
SIZE
VALVE
BYPASS
OUTLETINLET
PSIG
STEAM PRESSURE
LOCATIONPRV. NO.
PRESSURE REDUCING VALVES
PRV-1
CAPACITY
LBS/HR
REQUIRED
REMARKS
3"
INLET OUTLET
2"
PRV STATION LOCATED IN MECHANICAL ROOM BM-1081
11,500
FF-2
PF-2 AHU-2
11,500 AHU-2
MEZZANINE
MEZZANINE
MEZZANINE
MEZZANINE
PLEATED
CARTRIDGE
FMB,SAH
85% 30% O.1 0.3
0.65O.3 SAH
1. SEE PLAN FOR LOCATION OF PIPE SIZES.
NOTE:
FMB - FILTER MIXING BOX
SAH - SIDE ACCESS HOUSING
AIR FILTERS
ROOM
ROOM OR
EQUIPMENT
SERVED
C.F.M.
RATED
EFFICIENCY
CARTRIDGE
REMARKS
H x W x D OF CART. TYPE
FILTER
NO.
LOCATION
NO.
FACE
FILTER MAX.
VELOCITY
CART. SIZE NUMBER HOUSINGTYPE
INITIAL FINAL
MAXIMUM S.P. DROP
NUMBER AND SIZE TO FIT AIR HANDLING UNIT MANUFACTURERS STANDARD FILTER MIXING BOX, VERIFY WITH AIR HANDLING UNIT MANUFACTURER.
DESIGN ALTITUDE 200 FT.
AIR CONDITIONING DESIGN DATA-
ENERGY EFFICIENT MOTORS
(FD) FIRE DAMPER SCHEDULE
2 ALL WATER FLOW MEASURING DEVICES SHALL SEND SIGNAL TO EMCS.
1 DEVICE RANGE GPM SHALL EXCEED DESIGN CAPACITY BY 20%.
1,2
N 1"
P 3"
AIR
HANDLERS
FROM ROOM OUTLETS TO EXHAUST FAN.
FROM TERMINAL BOXES TO ROOM OUTLETS.
1"NPREHEAT COIL.
FROM OUTSIDE AIR LOUVER OR RETURN SMOKE DAMPER TO
CLASS W.G.
PRESSURE
MINUMUM
PRESSURE
OR NEGATIVE (N)
POSITIVE (P)
DUCT INVOLVEDEQUIPMENT
DUCT PRESSURE CLASSES
FROM FAN DISCHARGE TO TERMINAL BOXES.
1. MOUNT AIR FLOW STATIONS AT INLETS TO FAN USING PROBE ARRAY DESIGNED FOR THE PURPOSE.
P 1"
NOTE:
1,2
EXHAUST
FANS
%RH.
INSIDE
D.B.W.B.D.B.
OUTSIDE
SUMMER
D.B. W.B.
DESIGN
AREA OUTSIDE
D.B.
INSIDE
WINTER
%RH.
HP
SCHEDULED
NEMA EFF.
NOMINAL
1.0 82.5
1.5 84.0
2.0 84.0
3.0 86.5
5.0 88.5
7.5 89.5
10 89.5
REMARKSLOCATION CLASS
MAX. LEAKAGE
@ 1" W.C. @ 4" W.C.
MAX. LEAKAGE
CLASSIFICATION
TEMPERATURE * MAX. LOSS IN
INCHES WG TEMP °F.
FUSIBLE LINK
TYPE
DAMPER
FAN
SYSTEM
REMARKSS.P.
DROP
MAX.MIN.
CFM
HW
LOCATION
AIR FLOW MEASURING DEVICES
UNIT
NO.
DUCT SIZE
TYPE
DUCT
ENGINEERS
T A
TE
OF I L L
NO
I S
ER
AW
LUOBEDAW
LRAE
I
062-044274
REGISTERED
PROFESSIONAL
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel
Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel
Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel
Fax
618.529.5262 618.457.8991
Geotechnical
11/8/2019 10:53:24 AM
MECHANICAL SCHEDULES Expand & Upgrade Building 42 for Laboratory
MQ-002
657-502
Marion, IL
11-07-2019
NOTES:
EF-1
EF-2 800 0.75"
CFM
0.25"
E.S.P. SPEED
TIP
89 2241
RPM
FAN DATA
MANUFACTURER/ MODEL NO.
COOK 135TMX460/3�
VOLTAGE
SONES
2.0
HP
3.4
FLA
MOTOR DATA
1,3
NOTES
TAG
1. Square inline, direct drive, unit mounted disconnect, speed control, backdraft damper, (4) rc-75 isolators.
2. Mixed flow horizontal inline fan, belt drive, arrangement 9, prem. eff. drive motor, disconnect, motor cover, isolation rails, (4) rc-125 isolators, invertek 2.0 hp vfd.
3. Electronically commutated vari-flow motor.
EF-3 400 0.75"
COOK 120SQN17DEC115/1�1725 1/2--- --- ---
1COOK 100SQN15D115/1�1/61550--- --- ---
LWT
COLD SIDE DATA
OF PLATESMANUFACTURER
MODEL NO.
MARK CONN.
SIZEMBTU
HOT SIDE DATA
LWT
°F
FOULING
FACTOR
NUMBER
EWTLB/HR °F°FPSI°F
WPD EWT
PSI WWPD HL
DIMENSIONS
NOTES
NOTES:
HE-1 TACO PF 10-23-1-EH 1212.97 232" 16.4 29.812.243.59 1129.38 .75239.4 120.6 ---120.0 140.0
GPM
123.5
TAG
AHU-1
CFM
5,000 1.5 4.01 8
HP
5.34
BHP
RPM
SUPPLY FAN EXHAUST FAN
CFM
HP
BHP
CONDITIONS
SUMMER AMBIENT
DB WB
96.0 77.0
SUMMER RETURN
DB WB
81.0 65.7
WINTER AMBIENT
DB WB
7.0 5.0
WINTER RETURN
DB WB
70.0 58.0
HEAT WHEEL
COOLING PERFORMANCE
EDB/EWB
LDB/LWB
HEATING PERFORMANCE
EDB/EWB
LDB/LWB
HP
MODEL
COOLING
PERFORMANCE
134.7 151.8
EDB/EWB
96.0/77.0
LDB/LWB
52.4/52.1
GPM
40.0 5.7
EWT
45.0
LWT ROWS FPI
54.8 6.0 10 11.8
HEATING
PERFORMANCE
EDB/EWB
77.0/40
LDB/LWB
60/47
GPM
12.0 1.5
EWT
LWT ROWS FPI
120 1.0 6 11.8
UNIT POWER
VOLTAGE MCA MOP
10.0 15 2,554
AHU-2 11,500 1.25 5.29 20 14.6 1760 11,500 2.07 2.07 7.5 5.91 96.0 77.0 80.3 66.4 7.0 5.0 70.0 58.0 271.4 115.9 96.0/77.0 86.9/71.4 667.8 455.1 96.0/77.0 86.9/71.4 1/4 594.8 384.9 86.9/71.4 54.8/54.5 96.0 12.8 45.0 57.4 6.0 10 21.9 43.6/40.0 62.7/49.1 27.0 2.5 140 120 1.0 8 21.9 46.0 70 6,957
NOTES:
Variable Air Volume unit.
SS Drain pan, phase and brown out protection, direct drive premium VFD motor(s), VFD.
Combination filter -2" 30% pleated, cartridge 90-95%, magnehelic gauge.
Heat Recovery Wheel with 2" 30% pleated filter.
1.
2.
3.
4.
MANUFACTURER
AND
MODEL
NUMBER
FLUID
PD FT
FACE
AREA
SQFT
FACE
AREA
SQFT
FLUID
PD FT
SENSIBLE
MBH
TOTAL
MBH
T.S.P.
IN
W.C.
E.S.P.
IN
W.C.
T.S.P.
IN
W.C.
E.S.P.
IN
W.C.
ERC-
68100C
AAON
M2-H-011-R-3-
A-B-B-D-O
AAON
M2-H-022-R-3-B- B-E-D-X
460/60
/3PH
460/60
/3PH
APPROX
WEIGHT
Double walled insulated unit.5.
TOTAL
MBH
SENSIBLE
MBH
TOTAL
MBH
SENSIBLE
MBH
NOTES
1,2,3,5
1,2,3,4,5
1. 1 PASS IN SERIES, WEIGHT IS 201LBS.
ALL
A. Maximum N.C. values are based on Octave Band 1 through 8 sound power levels minus a room absorption of 10dB, C. All grilles, registers, and diffusers shall have visible sheet metal and ductwork painted flat black behind face.
B. Verify border requirements with all applicable architectural sheets, reflected ceiling plans, and room finish schedules.
D. All parts of diffuser behind perforated face will be painted flat black by manufacturer.
E. Provide square to round transitions, by manufacturer, as required. Also see plans.
GENERAL NOTES:
J
K
L
2. All diffusers shall be aluminum.
1. Provide white baked enamel finish, color as selected by architect.
NOTES:
re 10 to the -12 Watts.
22"x 10"
22"x 22"
6"�
N
N
N
SCHED3
RETURN, LAY-IN
RETURN, SURFACE
GRILLE AND DIFFUSER SCHEDULE
TAG
C
A
B
D
DAMPER
Y / N
MAX.
N.C.
CFM
MAXIMUM
6"�
8"�
12"�
NECK SIZE MANUFACTURER/ MODEL NO.
PRICE ASCDAY
SYMBOL:
PLAN A
300 CFM Value of Diffuser/Register
SUPPLY, LAY-IN
SUPPLY, LAY-IN
SUPPLY, LAY-IN
REMARKS
TAG
NOTES
PRICE 10A
1,2,4
RETURN, LAY-IN
PRICE AFRFDA
1,2,4
1,2,4
1,2,5,6
1,2,5,6
1,2,5,6
1,2,3
3. Flush face radial diffuser.
4. 4 cone fully adjustable air pattern diffuser.
5. Perforated face grille.
E 27650 SUPPLY, LAY-IN 1,2,3
F 25350 SUPPLY, LAY-IN 1,2,3
SCHD58A
24"x 12"
24"x 24"
12"x 12"
24"x 24"
FACE SIZE
6. Provide neck plenum on all grilles.
10"�
12"�
10"�
24"x 24"
24"x 24"
24"x 24"
24"x 48"
24"x 24"
Y
Y
Y
Y
Y
PRICE AFRFDA
PRICE AFRFDA
PRICE ASCDA
PRICE ASCDA
PRICE 10A
PRICE 10A
SUPPLY, LAY-IN
VAV SCHEDULE
Q ty
M o d e l
T a g
U n it S iz e
M a x P ri m a ry
C
F M
M in
P ri m a ry
C F
M
R e h e a t
(C F
M
LA
T
°F
In le t S
P in w g
W C
C a p a ci ty
M
B H
R o w s
D o w n st re a m
S P in w g
T e rm in a l
Li n e r
M a x D is N
C
M a x R a d
N C
E A
T
°F
F lu id F lo w
G
P M
F P
D ft w g
M a x A ir P
D in w g
C o il T y p e
E W
T
°F
LW
T
°F
C ir cu it s
C o il
W e ig h t (l b s)
1 SDV5 V114 8 480 310 310 68.90 1.00 4.80 1L 0.25 FF 22 (2) -- 55.00 1.2 0.10 0.14 140.00 107.70 1 Water 22
1 SDV5 V26 5 150 70 70 78.60 1.00 3.2 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19
1 SDV5 V13 4 150 87 87 82.20 1.00 2.60 1L 0.25 FF 25 (2) -- 55.00 0.6 0.07 0.02 140.00 122.10 1 Water 19
1 SDV5 V22 14 2900 1377 1377 68.10 1.00 20.10 1L 0.25 FF -- -- 55.00 12.0 0.46 0.31 140.00 108.90 2 Water 43
1 SDV5 V112 9 700 439 439 74.80 1.00 9.70 1L 0.25 FF 21 (2) -- 55.00 2.5 0.31 0.14 140.00 125.30 2 Water 28
1 SDV5 V28 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.31 0.07 0.09 140.00 116.30 1 Water 18
1 SDV5 V19 5 100 62 62 87.30 1.00 2.20 1L 0.25 FF -- -- 55.00 0.4 0.07 0.01 140.00 124.90 1 Water 19
1 SDV5 V111 5 250 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 1.0 0.07 0.06 140.00 118.20 1 Water 19
1 SDV5 V27 16 2150 1204 1204 95.00 1.00 53.70 2L 0.25 FF -- -- 55.00 5.5 2.78 0.42 HC 140.00 114.80 3 Water 56
1 SDV5 V20 12 1750 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 8.0 1.17 0.70 140.00 107.40 2 Water 37
1 SDV5 V24 7 500 312 312 68.80 1.00 4.80 1L 0.25 FF 25 (2) -- 55.00 2.2 0.10 0.15 140.00 107.50 1 Water 22
1. Dashes (--) indicate NC values less than 20.
2. NC values are calculated based on procedures outlined in AHRI Standard 885-2008, “A Procedure for Estimating Occupied Space Sound Levels in the Application of Air Terminals and Air Outlets.”
3. Sound power levels are given in decibels (dB).
4. "** Discharge sound power levels 2008" do not include duct end reflection. For the most current data based on ASHRAE Standard 130-2008 and AHRI Standard 880-2011 reference "Discharge sound power levels."
5. Dashes (--) indicate sound power levels below 36-29-26-22-19-17 for each octave band; values below these sound power levels are considered below significance per AHRI 880.
6. Minimum operating pressure is the minimum static pressure required to operate the terminal unit assembly at maximum primary flow with a wide open damper.
7. Airflow is given in cubic feet per minute (cfm).
8. Air pressure drop is given in inches water gauge (in. w.g.), and water pressure drop is given in feet of water gauge (ft. w.g.).
9. NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI Standard 880-2011, which include duct end reflection corrections.
10. * NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI Standard 880-2008.
These values are NOT the most current method for estimating NC values because AHRI 880-2008 does not include duct end reflection corrections.
11. Water coil performance is rated and certified in accordance with the latest edition of AHRI Standard 410.
1 SDV5 V18 4 75 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19
1 SDV5 V16 4 80 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19
1 SDV5 V15 4 80 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19
1 SDV5 V14 4 87 87 82.20 1.00 2.60 1L 0.25 FF 25 (2) -- 55.00 0.6 0.07 0.02 140.00 122.10 1 Water 19150
1 SDV5 V25 14 2150 1377 1377 68.10 1.00 20.10 1L 0.25 FF -- -- 55.00 3.5 0.46 0.31 140.00 108.90 2 Water 43
1 SDV5 V12 9 600 439 439 74.80 1.00 9.70 1L 0.25 FF 21 (2) -- 55.00 2.4 0.31 0.14 140.00 125.30 2 Water 28
1 SDV5 V113 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 2.0 0.07 0.09 140.00 116.30 1 Water 18
1 SDV5 V11 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.2 0.07 0.09 140.00 116.30 1 Water 18
1 SDV5 V10 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.2 0.07 0.09 140.00 116.30 1 Water 18
1 SDV5 V110 5 200 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 0.8 0.07 0.06 140.00 118.20 1 Water 19
1 SDV5 V17 5 240 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 1.0 0.07 0.06 140.00 118.20 1 Water 19
1 SDV5 V21 12 1750 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 8.0 1.17 0.70 140.00 107.40 2 Water 37
1 SDV5 V23 12 1700 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 7.9 1.17 0.70 140.00 107.40 2 Water 37
EXHAUST FAN SCHEDULE
1 SDV5 V115 12 1500 1000 1000 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 5.9 1.17 0.70 140.00 107.40 1 Water 37
McQuay FCHF-1BSO2AA
MANUFACTURER/ MODEL NO.
CABINET HEATER SCHEDULE - Hot Water
13.7
MBHTAG
CH-1 200
CFM GPM
.5 .75
EWT
140 120
LWT
EAT
1/12
HP
120/1�
VOLTAGE
ALL
NOTES
DROP
FT
NOTES:
1. UNIT TO BE SEMI-RECESSED. PROVIDE TRIM KIT AND FILTERS, AND INTEGRAL/UNIT MOUNTED THERMOSTAT.
3500460-33.0VFD------ 4814045123.5WATERHWHMEZZANINEHWP-1
CIRCULATING PUMPS
PUMP NO. LOCATION SYSTEM CIRCULATING FLUID
FLUID GPM PUMP HEAD
FT. FLUID
TEMP
F
SP.
GR.
EFF.
(MIN) SERVED
CIRCUIT
PIPING TYPE MOTOR
VOLTSNOM.
HP. PHASE
RPM
NOTES MANUFACTURER/MODEL
TACO 1935
NOTES: VFD RATED MOTOR AND VFD CONTROLLER MOUNTED TO PUMP.
PLATE AND FRAME HEAT EXCHANGER SCHEDULE
MS-30
3500460-33.0VFD------ 4814045WATERHWHMEZZANINEHWP-2 TACO 1935
CONDENSING UNIT SCHEDULE
TAG
CU-1
NOTES:
WITH HOT GAS REHEAT, NON FUSED DISCONNECT, 5 MINTUE COMPRESSOR OFF TIME AND 20 SECOND COMPRESSOR STAGE
DELAY, SINGLE POWER POINT CONNECTION.
VARIABLE CAPACITY COMPRESSORS, PHASE AND BROWN OUT PROTECTION, SIGHT GLASS AND COMPRESSOR ISOLATION VALVES.
CONVENIENCE RECEPTACLE FACTORY WIRED, CONDENSER COIL GUARDS, VFD CONTROLLED CONDENSER FANS.
EER
CU-1
AMB. AIR
TEMP.
95 603.8
COMPRESSOR
QTY
REFRIGERANT
410A
ELECTRICAL
VOLTAGE MCA MOP
WEIGHT
LBS
2541460/3PH 113 125
MANUFACTURER AND
MODEL NUMBER
AAON CFA-060-DA3EC001
NOTES
ALL
AIR HANDLING UNIT SCHEDULE WITH HEAT RECLAIM
Provide a SCCR per the Div 26 OCPD study.
COOLING
MBH @
95 F
123.5
ALL
ALL
CONDENSATE PUMPS
PUMP NO. LOCATION TYPE UNIT GPM MOTIVE
PRESSURE
MOTOR
NOM. HP. VOLT-PHASE
RECEIVER
CRU-1 MEZZANINE 6 5 - 15
MANUFACTURER / MODEL
SIZE
GALLONS
REMARKS
PSI
WATSON MCDANIEL WPT3 ALL
NOTES:
PRESSURE MOTIVE
PUMP
1. PUMP-TRAP COMBINATION, S.S. BALL FLOAT AND CHECK VALVES.
ENGINEERS
T A
TE
OF I L L
NO
I S
ER
AW
LUOBEDAW
LRAE
I
062-044274
REGISTERED
PROFESSIONAL
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel
Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel
Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel
Fax
618.529.5262 618.457.8991
Geotechnical
11/8/2019 10:53:25 AM
MECHANICAL SCHEDULES Expand & Upgrade Building 42 for Laboratory
MQ-003
657-502
Marion, IL
11-07-2019
SUPPLY DUCTWORK TAKE-OFFS
SUPPLY DUCT TAKEOFF - AIR
TERMINAL UNIT
AIR TERMINAL UNITS
VOLUME DAMPER DETAIL
FLEXIBLE DUCT CONNECTIONS
EXHAUST OR RETURN BRANCH
DUCTWORK ACCESS PANEL AND DOOR DETAIL
DUCTWORK RADIUS ELBOWS
DUCTWORK SQUARE VANE ELBOWS
FIRE DAMPER INSTALLATION
DUCT CONNECTIONS - AIR TERMINAL
UNITS
SEE NOTE 1
SEE NOTE 2
SEE NOTE 3
NTS
NTS
NTS
ALTERNATE SUPPLY DUCT TAKEOFF -
NTS
NTS
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
J
NTS
MAIN EXHAUST OR RETURN
PLAN VIEW
SECTION "A-A"
"B" "B"
NTS
NTS
VANE
VANE
NTS
NTS
SECTION THRU
NTS
SEE NOTE 5
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
DIFFUSER (TYP.)
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
SOUND ATTENUATOR
SEE EQUIPMENT
SCHEDULE
REHEAT COIL
AIR TERMINAL UNIT
(CV OR VAV)
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO
THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM
LENGTH 3'-0" [900mm].
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE
AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE
BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS).
FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A
DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT
OR BELOW 0.2"/100' [1.64Pa/m].
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT
SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 3'-0"
[1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER
THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
NOTE:
1.
2.
3.
4.
5.
6.
[25mm]
ACCESS
PANEL
NOTE 5
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
TYPICAL DUCT
INSULATION
FIRE BARRIER
PARTITION OR CHASE
NOTE 6
SLEEVE, NOTE 2
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
DAMPER,
NOTE 1
DUCT
CONNECTION
NOTE 4
SLEEVE, NOTE 2
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR.
FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND
GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN
THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR
LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH.
FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH
CONCRETE CURB AROUND OPENING FOR DUCT.
NOTE:
1.
2.
3.
4.
5.
6.
7.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE
DOUBLE VANE TYPE.
NOTE:
1.
2.
3.
4.
SHORT RADIUS ELBOW
WITH TWO VANES
SHORT RADIUS ELBOW
WITH ONE VANE
STANDARD RADIUS OR
LONG RADIUS ELBOW
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
NOTE:
1.
2.
"A"
"A"
INSULATION
INSULATION
GASKET
DUCT
INSULATION
SECTION "B-B" FACTORY
FABRICATED
LATCH
FLEXIBLE
WASHER
HANDLE INSIDE
GASKET
CASING
ACCESS DOOR
ACCESS PANEL
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS
TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE
PINS.
3. SEE SMACNA 2005, FIGURE 9-15
VD
BRANCH DUCT
1/4W OR 4"
[100mm] MIN.
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
AIR
FLOW
AIR
FLOW
FLEXIBLE MATERIAL
AS SPECIFIED
WASHER
FLANGED
CONNECTION
ON FAN SIDE
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]
NOMINAL WITH MATERIAL TAUT
[40mm][15mm][15mm]
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
DUCT
1 1/2" [40mm]
POCKET SLIP
ALTERNATE
POSITION
OF BOLT
1" [25mm] FLANGE & HEM
BOLT ON 4" [100mm] CENTERS
1"x1/8" [25x3mm] BAND IRON
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
RIVET ON 4"
[100mm]
CENTERS
SHEET METAL SCREWS ON
12" [300mm] CENTERS
DUCT
5/16" [8mm] FLANGE
BOLT ON 4" [100mm] CENTERS
1"x1/8" [25x3mm] BAND IRON
1"x1/8" [25x3mm] DRAW BAND
FLEXIBLE
MATERIAL AS
SPECIFIED
1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]
NOMINAL WITH MATERIAL TAUT
WASHER
FLANGED CONNECTION
ON FAN SIDE
SECTIONSIDE ELEVATION
STIFFEN BLADE
AS REQUIRED
DUCT
1/2" [15mm]
ROUND ROD PIN
INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
1/8" [6mm]
CLEARANCE
ALL AROUND
DAMPER BLADE
INSULATION SEE
SPECIFICATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTE:
1.
2.
FLOW
FLOW
PLAN VIEW
MAIN SUPPLY
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR TERMINAL
UNIT.
PLAN VIEW
MAIN SUPPLY
ROUND SHEET METAL
DUCT.
RIGID DUCT TO AIR TERMINAL
UNIT.
AIR
FLOW
MAIN SUPPLY
DUCT
AIR
FLOW
1/4 W OR 4"
[100mm] MIN.
AIR
FLOW
AIR
FLOW
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
MAIN
SUPPLY
DUCT
TOP REGISTER
ADJUSTABLE
METAL ROD
OR LINKAGE
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN
SUPPLY
DUCT
TURNING VANES
SUPPLY REGISTER
OR BRANCH DUCT
AIR
FLOW
AIR
FLOW
AIR
FLOW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
K
MQ004
I
H
G
A
B
C
D
E
F
MQ004
MQ004
MQ004
MQ004
MQ004
MQ004
MQ004
MQ004
MQ004
MQ004
S E E
N O T E
W1
W
R
1/6W
W
1/2W
WW
W
2/3WR
R
W
W
1/2"
1/2" 1/2"
°M A X
"D"
W
ENGINEERS
T A
TE
OF I L L
NO
I S
ER
AW
LUOBEDAW
LRAE
I
062-044274
REGISTERED
PROFESSIONAL
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel
Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel
Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel
Fax
618.529.5262 618.457.8991
Geotechnical
11/8/2019 10:53:27 AM
MECHANICAL DETAILS Expand & Upgrade Building 42 for Laboratory
MQ-004
657-502
Marion, IL
11-07-2019
A
W
R
"B""B"
A
W
NO SCALE
SUPPLY DUCT
FLEX
SPIN-IN EXTRACTOR
BUTTERFLY DAMPER
MANUAL VOLUME
A
IR
F L O W
ROUND METAL
DUCT
ROUND AND/OR SQUARE NECK CEILING DIFFUSER TAKE-OFFS
SIDE VIEW
FOR SQUARE NECK DIFFUSER
DIFFUSER & OPPOSED BLADE DAMPER
MULTI-BLADE DAMPER FOR ROUND NECK
CONTROL GRID
SUPPLY DUCT
CEILING
QUADRANT
SIDE ELEVATION
SECTION
OUTSIDE END BEARING
DUCT
DAMPER BLADE
INSIDE END BEARING
INSULATION STAND-OFF
LOCKING QUADRANT
HANDLE WITH
INSULATION
DUCT
HANDLE WITH LOCKING
DAMPER BLADE
STIFFEN BLADE AS REQ'D.INSULATION
Ê" CLEARANCE ALL AROUND
1/2" ROUND ROD PIN
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
BRANCH DUCT TAKE-OFF
WITH EQUIPMENT IN DUCT
DUCT TRANSFORMATION
RADIUS ELBOWS
EXHAUST AND/OR RETURN BRANCH DUCT
ACCESS SECTION FOR ROUND/OVAL DUCT
SQUARE VANED ELBOWS
ACCESS DOOR
SPIN-IN AIR EXTRACTOR
DETAIL
HOUSING WELDED
TO DUCT SECTIONCEILING DIFFUSER TAKE-OFFS
VOLUME DAMPER DETAIL
FACTORY FABRICATED LATCH
2.
1.
ROUND OR FLAT OVAL
DUCT SECTION
INSULATION
DUCT
GASKET
PLAN OR SIDE VIEW
MAXIMUM ANGLES SHOWN SHALL APPLY.
NOTE: UNLESS OTHERWISE INDICATED ON PLANS,
AIR FLOW
20° MAX 30° MAX
20° MAX
EQUIPMENT
DUCT TRANSITION
PLAN OR SIDE VIEW
15° MAX
15° MAX
PLAN VIEW
MAIN SUPPLY DUCT
BRANCH DUCT
1/4W 4" MIN.
PLAN VIEW
BRANCH DUCT
DAMPER AS REQ'D.
PROVIDE VOLUME
1/4W 4" MIN.
45°
MAIN EXHAUST OR RETURN
NOTES:
STANDARD RADIUS ELBOW
GREATER THAN W
R SHALL EQUAL OR BE
R SHALL EQUAL OR BE
GREATER THAN 1/3 W.
2/3 W
1/3 W
VANE
W
SHORT RADIUS ELBOW WITH
ONE VANE
SHORT RADIUS ELBOW WITH TWO VANES
W
VANE
1/6 W 1/3 W
1/2 W
GREATER THAN 1/16 W.
R SHALL EQUAL OR BE
INCHES VANES SHALL BE DOUBLE VANE TYPE.
4. WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 20
3/4 INCH TRAILING EDGE.
1-1/2 INCH MAXIMUM SPACE BETWEEN VANES AND A
3. ALL SINGLE VANES SHALL HAVE A 2 INCH RADIUS,
VANE TYPE REGARDLESS OF W DIMENSION.
2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE
INSTALLED AS DETAILED BY SMACNA
1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND
W1
W2
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
NOTES: SECTION "B-B"
FLEXIBLE WASHER
INSULATION
CASING GASKET
HANDLE INSIDE
ACCESS PANEL
SECTION "A-A"
NOTE
NEGATIVE PRESSURE RELIEF
VENT IS SIMILAR
W
PROVIDE VOLUME
DAMPER WHEN
SHOWN ON PLANS
THE INTERIOR SURFACE OF ALL RADIUS
ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS SHOWN
ON PLANS MAY BE MADE SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS
SHALL HAVE VANES.VANES SHALL BE
CONSTRUCTED, SUPPORTED AND
FASTENED AS RECOMMENDED BY SMACNA.
COVER WITH HANDLE
AND CHAIN
RETAINER GASKETED
AND PRESSURE
SEALED.
20° MAX
L
MQ005
A
MQ005
B
MQ005
C
MQ005
E
MQ005
F
MQ005
J
MQ005
K
MQ005
I
MQ005
H
MQ005
G
MQ005
D
MQ005
ENGINEERS
T A
TE
OF I L L
NO
I S
ER
AW
LUOBEDAW
LRAE
I
062-044274
REGISTERED
PROFESSIONAL
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032
Tel
Fax
317.580.0402 317.582.0766
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel
Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel
Fax
618.529.5262 618.457.8991
Geotechnical
11/8/2019 10:53:29 AM
MECHANICAL DETAILS Expand & Upgrade Building 42 for Laboratory
MQ-005
657-502
Marion, IL
11-07-2019
D
D
NTS
AV
1. SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.
2. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS
SHOWN ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY FOR HOT WATER HEATING.
3. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN EXPANSION TANK SCHEDULE.
4. FOR HOT WATER SYSTEMS 2" [50mm] AND SMALLER AND CHILLED WATER SYSTEMS USE
IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.
5 SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM HAS A
MINIMUM OF 4 PSIG. [28kPa]
DIAPHRAGM
EXPANSION
TANK
TANK SADDLE
TO PUMP SUCTION
PITCH UP 1.6%
SLOPE (MIN.)
HANGER ROD SUPPORTS
(TYPICAL)
CONNECTOR PIPE
NORMALLY OPEN GATE VALVE
IN VERTICAL (REMOVE
HANDLE)
RUN DRAIN LINE TO
NEAREST F.D.
UNLESS INDICATED
OTHERWISE
FROM SYSTEM
AIR SEPARATOR
SEE NOTES NO. 3
& 4
DRAIN
HORIZONTAL EXPANSION TANK -
PIPING CONNECTIONS
COLD WATER FILL LINE. SEE
EXPANSION TANK SCHEDULE
FOR SIZE
NC
RUN DRAIN LINE
TO NEAREST FD
REDUCED PRESSURE BACKFLOW
PREVENTER
BUTTERFLY
OR BALL
ISOLATION
VALVE
HANGER RODS
(TYP)
AUTOMATIC AIR VENT
PI
1" GREATER THAN
1/2 OF FAN STATIC
PRESSURE
PIPING CONNECTIONS
NTS
TERMINAL UNIT WATER COILS -
MV
MODULATION CONTROL VALVE
DRAIN WITH HOSE
CONNECTION
SHUT OFF VALVE
WATER SUPPLY
UNION CONNECTIONS
(TYP.)
MANUAL AIR VENT
WATER RETURN
REDUCER, IF REQUIRED
TEST PLUG (TYP.)
COIL
H
MQ006
NOT TO SCALE
COOLING COIL CONDENSATE DRAIN
F
MQ006
A
MQ006
B
MQ006
C
MQ006
E
MQ006
G
MQ006
I
MQ006
D
MQ006
STEAM MAIN DRIP CONNECTION
END OF H.P. OR M.P.
VALVE CONNECTION
TYPICAL DRAIN
TYPICAL AIR VENT
ELEVATION
HEATING CONVERTOR DETAIL
TYPICAL STEAM CONNECTIONS TO H.W.
TYPICAL WATER CONNECTIONS TO
H.W. HEATING CONVERTOR DETAIL
CONVERTOR
CONTROL VALVE
SIZE AS
BUCKET TRAP
VACUUM BREAKER
AUTO AIR VENT
STRAINER (TYP); WITH HOSE END BLOW DOWN VALVE; TYPICAL
ECCENTRIC REDUCER (TYP)GLOBE VALVE BYPASS SAME
STEAM MAIN
CONDENSATE
RETURN
(TYPICAL)
UNION
CONTROL VALVE
(TYPICAL)
GATE VALVE
1/3 CAPACITY
2/3 CAPACITY
2/3 CAPACITY
PIPE SIZE PER
MANUFACTURER. PITCH
DOWN 1/8" PER FOOT TO
FLOOR DRAIN.
RUN FULL SIZE
OF DRAIN PAN
OUTLET TO AND
INCLUDING TEE
1" GREATER THAN
FAN STATIC
PRESSURE
PIPE RUN FOR
BOTTOM DRAIN
CONFIGURATION
CLEAN OUT
PLUG
COOLING COIL
DRAIN PAN
SEE DETAIL
K/MQ006
FOR WATER PIPING
LAST CONNECTION
NOTE:
(FULL SIZE)
DIRT POCKET
6" MIN.
STEAM MAIN
ON LINE
BASE OF RISER DRIPS SIMILAR TO ABOVE
OF TRAP
FULL SIZE
5LB. DROP UNLESS OTHERWISE
BUCKET TRAP CAP 200LBS/HR @
INDICATED
DRIP RETURN MAIN
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
PROVIDE HOSE CAP NUT ELEVATION
WELDED PIPING
ELEVATION
THREADED PIPING
NOTES:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.
2.
IF AUTOMATIC AIR VENTS ARE USED,
PIPE DISCHARGE TO DRAIN.
VENT ALL…