P09 657-502 Bid Drawings Part 6 of 10 Mechanical-21 pages.pdf

PDF 6 MB Posted

Attached to
Expand and Upgrade Building 42 for Laboratory
Solicitation number
36C25520R0073
Issued by

About this file

This solicitation document is for the expansion and upgrade of Building 42 for laboratory use at the Marion VA Medical Center. The solicitation requests proposals for mechanical, electrical, and plumbing construction services. Proposals are due by January 15, 2020, with award anticipated by March 1, 2020. The work includes upgrading existing mechanical, electrical, and plumbing systems as well as installing new systems to support laboratory functions. The contract will have a one-year base period of performance with four one-year options. The solicitation is designated as a VA small business set-aside. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is the contracting agency.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet List

Sheet Number Sheet Name Sheet Order

MQ001

MQ002

MQ003

MQ005 MECHANICAL DETAILS

MQ004

MQ006

MQ007

MQ008

MQ009

MQ010

MH101 LOWER LEVEL - HVAC DUCT PLAN

MH102 FIRST FLOOR - SUPPLY DUCT PLAN

MP101

MP102

SECOND FLOOR MEZZANINE - SUPPLY DUCT PLAN

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MH103

LOWER LEVEL - HVAC PIPING PLAN

FIRST FLOOR - HVAC PIPING PLAN

MECHANICAL ROOF PLANMP201

MQ011 MECHANICAL DETAILS

MP103 SECOND FLOOR - HVAC PIPING PLAN

LOWER LEVEL - RETURN AND EXHAUST PLANMH104

MH105 SECOND FLOOR MEZZANINE - SUPPLY DUCT PLAN

MH106 HVAC ISOMETRICS

FEEDWATER SAMPLE (FROM DEAERATOR)

BOILER WATER SAMPLE

CONTINUOUS BLOWDOWN

CHEMICAL FEED

BOILER BLOWOFF

TUBE CLEANER WATER SUPPLY

COMPRESSED AIR

OVERFLOW

COLD WATER (CITY WATER)

LIQUEFIED PETROLEUM GAS IGNITER FUEL

NATURAL GAS IGNITER FUEL

NATURAL GAS MAIN FUEL

HOT WATER

SOFTENED WATER

FUEL OIL RETURN

FUEL OIL SUPPLY

RISER CLAMP (TYPE 42)*

FLOOR-SUPPORTED PIPE STAND

CLEVIS-TYPE HANGER

VARIABLE SPRING-TYPE HANGER (TYPE 51)*

ROLLER-TYPE HANGER

TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)

TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT

SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*

STANDARD PRACTICE SP-58

SLIDING SUPPORTS (TYPE 35)*

CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*

WALL BRACKET (TYPE 31, 32, 33)*

* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY

QUICK-COUPLE HOSE CONNECTOR

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

HOSE CONNECTOR

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

WATER LEVEL CONTROLLER

FLOW METER

ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.

THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,

DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND

INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.

TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL

UNITS, FILTERS, COILS, ETC.

FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD

EQUIPMENT DETAILS.

DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING

DIFFUSERS, REGISTERS, AND GRILLES.

DRAWING SYMBOLS

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

DRAWING NUMBER WHERE DRAWN

DUCTWORK SYMBOLS

BACK DRAFT DAMPER

SECTION.)

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

FIRE DAMPER

DUCT WITH SOUND LINING

FLEXIBLE DUCTWORK (INSULATED)

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

VIBRATION, OR SEISMIC

DUCTWORK SYMBOLS

(WALL TYPE)

(WALL TYPE)

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER OR TOP GRILLE

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT ON LIMIT OF

DEMOLITION

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

RETURN DUCT (UP & DOWN)

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

SQUARE 1-WAY CEILING DIFFUSERS

DUCTWORK SYMBOLS

DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

MANUAL SPLITTER DAMPER

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE

COMBINATION FIRE/SMOKE DAMPER

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

AIR TERMINAL SYMBOLS

FAN POWERED VARIABLE VOLUME

TERMINAL UNIT WITH HEATING COIL.

DOUBLE DUCT MIXING BOX.

TERMINAL UNIT WITH REHEAT COIL

PIPING SYMBOLS

HIGH PRESSURE STEAM CONDENSATE RETURN

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HOT WATER HEATING SUPPLY

CONDENSATE PUMP DISCHARGE

LOW PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

VENT LINE

SOLAR WATER RETURN

SOLAR WATER SUPPLY

GLYCOL-WATER HEATING RETURN

GLYCOL-WATER HEATING SUPPLY

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

REFRIGERANT LIQUID

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRAIN LINE

MAKE-UP WATER

CONDENSER WATER RETURN (TO TOWER)

CHILLED GLYCOL-WATER RETURN

CHILLED GLYCOL-WATER SUPPLY

CONDENSER WATER SUPPLY (FROM TOWER)

HOT WATER HEATING RETURN

GLYCOL-WATER RUN AROUND SUPPLY

GLYCOL-WATER RUN AROUND RETURN

EXISTING PIPE TO BE REMOVED

PIPING SYMBOLS

VACUUM CONDENSATE RETURN

CONDENSATE TRANSFER PUMP SUCTION

CONDENSATE TRANSFER PUMP DISCHARGE

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

GENERAL PIPING SYMBOLS

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

FLOW ELEMENT

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

PIPING ACCESSORIES SEE DETAIL

INVERTED BUCKET TRAP SET INCLUDING

PIPE UP

PIPE DOWN

REFRIGERANT SIGHT GLASS

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

VALVE SYMBOLS

BALL VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC BALANCING CONTROL VALVE

PRESSURE SAFETY VALVE

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

FLEXIBLE CONNECTION

WATER BALANCE DEVICE

CIRCUIT SETTER VALVE

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

H HUMIDIFER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN

(STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY

(STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING)

PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HVD HOISTWAY VENT DAMPER

HX HEAT EXCHANGER

HZ HERTZ

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE

DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT

EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

C CENTIGRADE (CELCIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE

DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS

(SUBMISSION1)

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACU AIR CONDITIONING UNIT

ACD AUTOMATIC CONTROL

DAMPER,MODULATING

ACD-TP AUTOMATIC CONTROL

DAMPER,TWO POSITION

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND

REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BMT BONE MARROW TRANSPLANT

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

CD-2 CONSTRUCTION DOCUMENTS

(SUBMISSION2)

CENT CENTRIFICAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXODE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

(TO COOLING TOWER)

CWS CONDENSER WATER SUPPLY

(FROM COOLING TOWER)

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

DB DECIBELS

Db DRY-BULB TEMPERATURE

DD-1 DESIGN DEVELOPMENT

(SUBMISSION1)

DD-2 DESIGN DEVELOPMENT

(SUBMISSION2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

ABBREVIATIONS

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PEF PROPELLER (TYPE) EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCI SPINAL CODE INJURY

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN (SUBMISSION1)

SD-2 SCHEMATIC DESIGN (SUBMISSION2)

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING VALVE

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

T & PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTERGRATED PART LOAD VALUE

IRH INTRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

J INTENTIALLY LEFT BLANK

kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN

(STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR

INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OR OPERATING ROOM

UC UNDER CUT

UC UNIT COOLER

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WATTS

WAG WASTE ANETHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WEF WALL EXHAUST FAN

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

1.

2.

3.

4.

5.

6.

7.

8.

GENERAL NOTES

LOCATION OF EXISTING TO REMAIN

CROSS HATCHED AREAS ARE NOT IN

CONTRACT AND ARE EXISTING TO REMAIN,

UNLESS SPECIFICALLY NOTED OR SHOWN

OTHERWISE.

MECHANICAL GENERAL PROJECT NOTES:

FOR GENERAL DUCT CONSTRUCTION SEE DETAILS ON MECHANICAL DETAILS SHEETS.

ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE

TRADE, AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND

STANDARDS.

CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE,

HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES,

ENLARGED FOR CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR

APPURTENANCES REQUIRED TO PROVIDE A COMPLETE AND COORDINATED SYSTEM

SHALL BE BORNE BY THE CONTRACTOR.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF

CEILING MOUNTED MATERIALS INCLUDING ALL DIFFUSERS, GRILLES, AND REGISTERS.

THE H.C. SHALL COORDINATE DUCTWORK INSTALLATIONS WITH OTHER TRADES.

LIGHTING AND DUCTWORK DESIGNS INDICATED ON CONTRACT DRAWINGS WERE

COORDINATED, HOWEVER CONFLICTS WITH DUCTWORK AND LIGHTS MAY ARISE DUE TO

GRID INSTALLATION. MECHANICAL CONTRACTOR. SHALL BE RESPONSIBLE FOR ALL

DUCTWORK MODIFICATIONS AND OFFSETS REQUIRED TO AVOID FIELD CONDITIONS.

BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE MAIN.

FLEXIBLE DUCTWORK IS LIMITED TO A MAXIMUM LENGTH OF 3 FEET, WITH NO DIPS,

SAGS, OR TIGHT ELBOWS; AND ON SUPPLY DUCTWORK ONLY. FLEXIBLE DUCTWORK

SHALL BE AN INSULATED, SEMI-RIGID AND LIGHT WEIGHT AIR DUCT, MANUFACTURED

BY USING DEAD SOFT ALUMINUM STRIP WHICH IS SPIRALLY WOUND AND

MECHANICALLY JOINED TOGETHER FORMING AN AIR TIGHT-LEAKPROOF TRIPLE LOCK

SEAM. DUCT TO BE SELF-SUPPORTING AND CORROSIVE RESISTANT UL-181 CLASS I

PRODUCT, WITH A POLYETHYLENE VAPOR BARRIER. FLEXIBLE DUCTWORK TO BE LIKE

MASTERFIT UPC-018 (ACOUSTICAL) OR AN APPROVED EQUAL.

PROVIDE NECK PLENUMS ON RETURN AND EXHAUST GRILLES AS REQUIRED. SEE

DETAILS.

PROVIDE TURNING VANES IN ALL SQUARE ELBOWS. SEE DETAILS.

ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, UNIT HEATERS,

ETC. SHALL BE HUNG FROM THE TOP CHORD OF THE STRUCTURAL STEEL.

EACH MAIN DUCT PASSING THROUGH FLOOR SPACES OR FIRE BARRIERS SHALL BE FIRE

ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.

CONTRACTORS ARE TO REVIEW EXISTING STRUCTURAL AND PLANS, WITH ACTUAL

LAYOUT OF BEAMS, JOISTS, ETC. TO AVOID CONFLICT BETWEEN DUCT. ADJUST DUCT

ROUTING TO ACCEPT STRUCTURAL CONDITIONS.

ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A

MINIMUM OF 25'-0" AWAY FROM OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL

AND STATE CODES MANDATE ADDITIONAL DISTANCE.

CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL

EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON

ORDER

WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL

WATER-TIGHT ALL AROUND LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL

COORDINATE PAINTING REQUIREMENTS FOR LOUVERS WITH GENERAL CONTRACTOR

PRIOR TO SUBMITTING BID.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

L.

M.

N.

O.

THIS SYMBOL SHOWS THE APPROXIMATE POINT WHERE

NEW WORK STARTS AND EXISTING IS TO REMAIN. FOR

DEMOLITION THIS SYMBOL SHOW THE APPROXIMATE POINT

WHERE DEMOLITION STOPS AND EXISTING IS TO REMAIN

FOR REVISED WORK.

K.

DAMPERED. SEE ARCHITECTURAL PLANS.

RH

SCH

SH

TH

PS

RC

WB

CSH

SS

LC

M

H4

H7

A

BDD

FC

10x8

FD

VD

DN

DN

UP

UP

D

R

DNUP

SUPPLY

RETURN45°

45°

N

2 1

1/24

F/S DPR

MB

HPS

HPR

MPS

MPR

LPS

LPR

PC

HWS

HWR

GHS

GHR

V

SWS

SWR

CHWR

CHR

GCR

RL

RS

RHG

CHWS

CHS

GCS

MW

D

GRR

GRS

X

VR

CTPS

CTPD

FWPS

FWPD

CF

FWS

BWS

CBD

BO

TC

A

OFL

HW

SW

CW

FOR

FOS

LPG(I)

G(I)

G

AV

MV

FE

E.T.R.

ENGINEERS

T A

TE

OF I L L

NO

I S

ER

AW

LUOBEDAW

LRAE

I

062-044274

REGISTERED

PROFESSIONAL

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel

Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel

Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel

Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel

Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel

Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel

Fax

618.529.5262 618.457.8991

Geotechnical

11/8/2019 10:53:22 AM

MECHANICAL NOTES &

ABBEVIATIONS

Expand & Upgrade Building 42 for Laboratory

MQ-001

657-502

Marion, IL

11-07-2019

Bid Document

DH BZ

SUPPLY

RETURN 1

1 4 CFM/ SQ. FT.

4 CFM/ SQ. FT. 8 CFM/ SQ. FT.

8 CFM/ SQ. FT. 350°F.

350°F. 0.05 @ 1,200 FPM

0.11 @ 2,500 FPM

AIRFOIL BLADES

ALL SUPPLY FSD'S * SEE PLANS FOR SIZE

ALL RETURN FSD'S * SEE PLANS FOR SIZE

NOTE:

50704.97.096 77 5075LAB AREAS

* INCREASE DAMPER SIZE IF REQUIRED TO MAINTAIN INDICATED STATIC PRESSURE LOSS.

REMARKS

40.0ORIFICECHILLED WATER 2"WFMD-1

GPM

SIZECAPACITYTYPESYSTEM

WATER FLOW MEASURING DEVICES

UNIT NO. LOCATION

REMARKSMIN. STATIC DEFL.TYPE

ISOLATOR

RAILAHU-1

UNIT. NO. TYPE BASE

VIBRATION ISOLATION FOR EQUIPMENT

D ---

DUCT LEAKAGE CLASSIFICATION AND ALLOWABLE LEAKAGE

SEAL CLASSDUCT PRESSURE

C

APPLICABLE SEALINGS SMACNA LEAKAGE CLASS

CLASS, W.G.

3" B TRAVERSE JOINTS AND SEAMS 12

4", 6", 10" A JOINTS, SEAMS AND ALL WALL PENETRATIONS 6 3

12TRAVERSE JOINTS ONLY

RECTANGULAR

DUCT DUCT

ROUND

.06 AHU-1

.065000SUPPLY

RETURN--

-- AHU-1MEZZANINEAFM-S1

AFM-R1

AFM-OA1 O.A. 1300 .06 AHU-1

11,500

1/2", 1", 2"

REFER TO "MOTORS" SECTION OF THE SPECIFICATIONS.

ALL MOTORS 1HP AND LARGER SHALL BE ENERGY

EFFICIENT TYPE.

AFM-S2

AFM-E2

AFM-OA2

MEZZANINE

MEZZANINE

MEZZANINE

MEZZANINE

MEZZANINE

SUPPLY

EXHAUST

O.A.

11,500

.06

.06

.06

AHU-2

AHU-2

AHU-2

MEZZANINE

96.0 3"ORIFICECHILLED WATERWFMD-2 MEZZANINE

RAILAHU-2 D ---

OFFICE AREAS 40704.97.096 77 5075

11,50011,500 11,50011,500

AFM-R2 MEZZANINE -- EXHAUST .06 AHU-2 111,50011,500

FMB,SAH

85% 30%5,000

AHU-1

AHU-1

FF-1

PF-1 PLEATED

5,000 CARTRIDGE

O.1 0.3

0.65O.3 SAH

NOTE:

13"352,076238STEAM

SIZE REMARKS

PSIG

SET PRESS.MIN. CAP.

LBS/HRF

TEMP.FLUID

PRV STATIONSV-1

SAFETY VALVES & RELIEF VALVES

UNIT. NO. SYSTEM

2"1-1/2"2,07625110

D2D1

SIZES

PIPE

SIZE

VALVE

BYPASS

OUTLETINLET

PSIG

STEAM PRESSURE

LOCATIONPRV. NO.

PRESSURE REDUCING VALVES

PRV-1

CAPACITY

LBS/HR

REQUIRED

REMARKS

3"

INLET OUTLET

2"

PRV STATION LOCATED IN MECHANICAL ROOM BM-1081

11,500

FF-2

PF-2 AHU-2

11,500 AHU-2

MEZZANINE

MEZZANINE

MEZZANINE

MEZZANINE

PLEATED

CARTRIDGE

FMB,SAH

85% 30% O.1 0.3

0.65O.3 SAH

1. SEE PLAN FOR LOCATION OF PIPE SIZES.

NOTE:

FMB - FILTER MIXING BOX

SAH - SIDE ACCESS HOUSING

AIR FILTERS

ROOM

ROOM OR

EQUIPMENT

SERVED

C.F.M.

RATED

EFFICIENCY

CARTRIDGE

REMARKS

H x W x D OF CART. TYPE

FILTER

NO.

LOCATION

NO.

FACE

FILTER MAX.

VELOCITY

CART. SIZE NUMBER HOUSINGTYPE

INITIAL FINAL

MAXIMUM S.P. DROP

NUMBER AND SIZE TO FIT AIR HANDLING UNIT MANUFACTURERS STANDARD FILTER MIXING BOX, VERIFY WITH AIR HANDLING UNIT MANUFACTURER.

DESIGN ALTITUDE 200 FT.

AIR CONDITIONING DESIGN DATA-

ENERGY EFFICIENT MOTORS

(FD) FIRE DAMPER SCHEDULE

2 ALL WATER FLOW MEASURING DEVICES SHALL SEND SIGNAL TO EMCS.

1 DEVICE RANGE GPM SHALL EXCEED DESIGN CAPACITY BY 20%.

1,2

N 1"

P 3"

AIR

HANDLERS

FROM ROOM OUTLETS TO EXHAUST FAN.

FROM TERMINAL BOXES TO ROOM OUTLETS.

1"NPREHEAT COIL.

FROM OUTSIDE AIR LOUVER OR RETURN SMOKE DAMPER TO

CLASS W.G.

PRESSURE

MINUMUM

PRESSURE

OR NEGATIVE (N)

POSITIVE (P)

DUCT INVOLVEDEQUIPMENT

DUCT PRESSURE CLASSES

FROM FAN DISCHARGE TO TERMINAL BOXES.

1. MOUNT AIR FLOW STATIONS AT INLETS TO FAN USING PROBE ARRAY DESIGNED FOR THE PURPOSE.

P 1"

NOTE:

1,2

EXHAUST

FANS

%RH.

INSIDE

D.B.W.B.D.B.

OUTSIDE

SUMMER

D.B. W.B.

DESIGN

AREA OUTSIDE

D.B.

INSIDE

WINTER

%RH.

HP

SCHEDULED

NEMA EFF.

NOMINAL

1.0 82.5

1.5 84.0

2.0 84.0

3.0 86.5

5.0 88.5

7.5 89.5

10 89.5

REMARKSLOCATION CLASS

MAX. LEAKAGE

@ 1" W.C. @ 4" W.C.

MAX. LEAKAGE

CLASSIFICATION

TEMPERATURE * MAX. LOSS IN

INCHES WG TEMP °F.

FUSIBLE LINK

TYPE

DAMPER

FAN

SYSTEM

REMARKSS.P.

DROP

MAX.MIN.

CFM

HW

LOCATION

AIR FLOW MEASURING DEVICES

UNIT

NO.

DUCT SIZE

TYPE

DUCT

ENGINEERS

T A

TE

OF I L L

NO

I S

ER

AW

LUOBEDAW

LRAE

I

062-044274

REGISTERED

PROFESSIONAL

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel

Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel

Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel

Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel

Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel

Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel

Fax

618.529.5262 618.457.8991

Geotechnical

11/8/2019 10:53:24 AM

MECHANICAL SCHEDULES Expand & Upgrade Building 42 for Laboratory

MQ-002

657-502

Marion, IL

11-07-2019

NOTES:

EF-1

EF-2 800 0.75"

CFM

0.25"

E.S.P. SPEED

TIP

89 2241

RPM

FAN DATA

MANUFACTURER/ MODEL NO.

COOK 135TMX460/3�

VOLTAGE

SONES

2.0

HP

3.4

FLA

MOTOR DATA

1,3

NOTES

TAG

1. Square inline, direct drive, unit mounted disconnect, speed control, backdraft damper, (4) rc-75 isolators.

2. Mixed flow horizontal inline fan, belt drive, arrangement 9, prem. eff. drive motor, disconnect, motor cover, isolation rails, (4) rc-125 isolators, invertek 2.0 hp vfd.

3. Electronically commutated vari-flow motor.

EF-3 400 0.75"

COOK 120SQN17DEC115/1�1725 1/2--- --- ---

1COOK 100SQN15D115/1�1/61550--- --- ---

LWT

COLD SIDE DATA

OF PLATESMANUFACTURER

MODEL NO.

MARK CONN.

SIZEMBTU

HOT SIDE DATA

LWT

°F

FOULING

FACTOR

NUMBER

EWTLB/HR °F°FPSI°F

WPD EWT

PSI WWPD HL

DIMENSIONS

NOTES

NOTES:

HE-1 TACO PF 10-23-1-EH 1212.97 232" 16.4 29.812.243.59 1129.38 .75239.4 120.6 ---120.0 140.0

GPM

123.5

TAG

AHU-1

CFM

5,000 1.5 4.01 8

HP

5.34

BHP

RPM

SUPPLY FAN EXHAUST FAN

CFM

HP

BHP

CONDITIONS

SUMMER AMBIENT

DB WB

96.0 77.0

SUMMER RETURN

DB WB

81.0 65.7

WINTER AMBIENT

DB WB

7.0 5.0

WINTER RETURN

DB WB

70.0 58.0

HEAT WHEEL

COOLING PERFORMANCE

EDB/EWB

LDB/LWB

HEATING PERFORMANCE

EDB/EWB

LDB/LWB

HP

MODEL

COOLING

PERFORMANCE

134.7 151.8

EDB/EWB

96.0/77.0

LDB/LWB

52.4/52.1

GPM

40.0 5.7

EWT

45.0

LWT ROWS FPI

54.8 6.0 10 11.8

HEATING

PERFORMANCE

EDB/EWB

77.0/40

LDB/LWB

60/47

GPM

12.0 1.5

EWT

LWT ROWS FPI

120 1.0 6 11.8

UNIT POWER

VOLTAGE MCA MOP

10.0 15 2,554

AHU-2 11,500 1.25 5.29 20 14.6 1760 11,500 2.07 2.07 7.5 5.91 96.0 77.0 80.3 66.4 7.0 5.0 70.0 58.0 271.4 115.9 96.0/77.0 86.9/71.4 667.8 455.1 96.0/77.0 86.9/71.4 1/4 594.8 384.9 86.9/71.4 54.8/54.5 96.0 12.8 45.0 57.4 6.0 10 21.9 43.6/40.0 62.7/49.1 27.0 2.5 140 120 1.0 8 21.9 46.0 70 6,957

NOTES:

Variable Air Volume unit.

SS Drain pan, phase and brown out protection, direct drive premium VFD motor(s), VFD.

Combination filter -2" 30% pleated, cartridge 90-95%, magnehelic gauge.

Heat Recovery Wheel with 2" 30% pleated filter.

1.

2.

3.

4.

MANUFACTURER

AND

MODEL

NUMBER

FLUID

PD FT

FACE

AREA

SQFT

FACE

AREA

SQFT

FLUID

PD FT

SENSIBLE

MBH

TOTAL

MBH

T.S.P.

IN

W.C.

E.S.P.

IN

W.C.

T.S.P.

IN

W.C.

E.S.P.

IN

W.C.

ERC-

68100C

AAON

M2-H-011-R-3-

A-B-B-D-O

AAON

M2-H-022-R-3-B- B-E-D-X

460/60

/3PH

460/60

/3PH

APPROX

WEIGHT

Double walled insulated unit.5.

TOTAL

MBH

SENSIBLE

MBH

TOTAL

MBH

SENSIBLE

MBH

NOTES

1,2,3,5

1,2,3,4,5

1. 1 PASS IN SERIES, WEIGHT IS 201LBS.

ALL

A. Maximum N.C. values are based on Octave Band 1 through 8 sound power levels minus a room absorption of 10dB, C. All grilles, registers, and diffusers shall have visible sheet metal and ductwork painted flat black behind face.

B. Verify border requirements with all applicable architectural sheets, reflected ceiling plans, and room finish schedules.

D. All parts of diffuser behind perforated face will be painted flat black by manufacturer.

E. Provide square to round transitions, by manufacturer, as required. Also see plans.

GENERAL NOTES:

J

K

L

2. All diffusers shall be aluminum.

1. Provide white baked enamel finish, color as selected by architect.

NOTES:

re 10 to the -12 Watts.

22"x 10"

22"x 22"

6"�

N

N

N

SCHED3

RETURN, LAY-IN

RETURN, SURFACE

GRILLE AND DIFFUSER SCHEDULE

TAG

C

A

B

D

DAMPER

Y / N

MAX.

N.C.

CFM

MAXIMUM

6"�

8"�

12"�

NECK SIZE MANUFACTURER/ MODEL NO.

PRICE ASCDAY

SYMBOL:

PLAN A

300 CFM Value of Diffuser/Register

SUPPLY, LAY-IN

SUPPLY, LAY-IN

SUPPLY, LAY-IN

REMARKS

TAG

NOTES

PRICE 10A

1,2,4

RETURN, LAY-IN

PRICE AFRFDA

1,2,4

1,2,4

1,2,5,6

1,2,5,6

1,2,5,6

1,2,3

3. Flush face radial diffuser.

4. 4 cone fully adjustable air pattern diffuser.

5. Perforated face grille.

E 27650 SUPPLY, LAY-IN 1,2,3

F 25350 SUPPLY, LAY-IN 1,2,3

SCHD58A

24"x 12"

24"x 24"

12"x 12"

24"x 24"

FACE SIZE

6. Provide neck plenum on all grilles.

10"�

12"�

10"�

24"x 24"

24"x 24"

24"x 24"

24"x 48"

24"x 24"

Y

Y

Y

Y

Y

PRICE AFRFDA

PRICE AFRFDA

PRICE ASCDA

PRICE ASCDA

PRICE 10A

PRICE 10A

SUPPLY, LAY-IN

VAV SCHEDULE

Q ty

M o d e l

T a g

U n it S iz e

M a x P ri m a ry

C

F M

M in

P ri m a ry

C F

M

R e h e a t

(C F

M

LA

T

°F

In le t S

P in w g

W C

C a p a ci ty

M

B H

R o w s

D o w n st re a m

S P in w g

T e rm in a l

Li n e r

M a x D is N

C

M a x R a d

N C

E A

T

°F

F lu id F lo w

G

P M

F P

D ft w g

M a x A ir P

D in w g

C o il T y p e

E W

T

°F

LW

T

°F

C ir cu it s

C o il

W e ig h t (l b s)

1 SDV5 V114 8 480 310 310 68.90 1.00 4.80 1L 0.25 FF 22 (2) -- 55.00 1.2 0.10 0.14 140.00 107.70 1 Water 22

1 SDV5 V26 5 150 70 70 78.60 1.00 3.2 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19

1 SDV5 V13 4 150 87 87 82.20 1.00 2.60 1L 0.25 FF 25 (2) -- 55.00 0.6 0.07 0.02 140.00 122.10 1 Water 19

1 SDV5 V22 14 2900 1377 1377 68.10 1.00 20.10 1L 0.25 FF -- -- 55.00 12.0 0.46 0.31 140.00 108.90 2 Water 43

1 SDV5 V112 9 700 439 439 74.80 1.00 9.70 1L 0.25 FF 21 (2) -- 55.00 2.5 0.31 0.14 140.00 125.30 2 Water 28

1 SDV5 V28 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.31 0.07 0.09 140.00 116.30 1 Water 18

1 SDV5 V19 5 100 62 62 87.30 1.00 2.20 1L 0.25 FF -- -- 55.00 0.4 0.07 0.01 140.00 124.90 1 Water 19

1 SDV5 V111 5 250 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 1.0 0.07 0.06 140.00 118.20 1 Water 19

1 SDV5 V27 16 2150 1204 1204 95.00 1.00 53.70 2L 0.25 FF -- -- 55.00 5.5 2.78 0.42 HC 140.00 114.80 3 Water 56

1 SDV5 V20 12 1750 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 8.0 1.17 0.70 140.00 107.40 2 Water 37

1 SDV5 V24 7 500 312 312 68.80 1.00 4.80 1L 0.25 FF 25 (2) -- 55.00 2.2 0.10 0.15 140.00 107.50 1 Water 22

1. Dashes (--) indicate NC values less than 20.

2. NC values are calculated based on procedures outlined in AHRI Standard 885-2008, “A Procedure for Estimating Occupied Space Sound Levels in the Application of Air Terminals and Air Outlets.”

3. Sound power levels are given in decibels (dB).

4. "** Discharge sound power levels 2008" do not include duct end reflection. For the most current data based on ASHRAE Standard 130-2008 and AHRI Standard 880-2011 reference "Discharge sound power levels."

5. Dashes (--) indicate sound power levels below 36-29-26-22-19-17 for each octave band; values below these sound power levels are considered below significance per AHRI 880.

6. Minimum operating pressure is the minimum static pressure required to operate the terminal unit assembly at maximum primary flow with a wide open damper.

7. Airflow is given in cubic feet per minute (cfm).

8. Air pressure drop is given in inches water gauge (in. w.g.), and water pressure drop is given in feet of water gauge (ft. w.g.).

9. NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI Standard 880-2011, which include duct end reflection corrections.

10. * NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI Standard 880-2008.

These values are NOT the most current method for estimating NC values because AHRI 880-2008 does not include duct end reflection corrections.

11. Water coil performance is rated and certified in accordance with the latest edition of AHRI Standard 410.

1 SDV5 V18 4 75 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19

1 SDV5 V16 4 80 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19

1 SDV5 V15 4 80 49 49 91.60 1.00 2.00 1L 0.25 FF -- -- 55.00 0.4 0.08 0.01 140.00 127.70 1 Water 19

1 SDV5 V14 4 87 87 82.20 1.00 2.60 1L 0.25 FF 25 (2) -- 55.00 0.6 0.07 0.02 140.00 122.10 1 Water 19150

1 SDV5 V25 14 2150 1377 1377 68.10 1.00 20.10 1L 0.25 FF -- -- 55.00 3.5 0.46 0.31 140.00 108.90 2 Water 43

1 SDV5 V12 9 600 439 439 74.80 1.00 9.70 1L 0.25 FF 21 (2) -- 55.00 2.4 0.31 0.14 140.00 125.30 2 Water 28

1 SDV5 V113 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 2.0 0.07 0.09 140.00 116.30 1 Water 18

1 SDV5 V11 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.2 0.07 0.09 140.00 116.30 1 Water 18

1 SDV5 V10 6 300 183 183 72.60 1.00 3.60 1L 0.25 FF 22 (2) -- 55.00 1.2 0.07 0.09 140.00 116.30 1 Water 18

1 SDV5 V110 5 200 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 0.8 0.07 0.06 140.00 118.20 1 Water 19

1 SDV5 V17 5 240 139 139 75.80 1.00 3.20 1L 0.25 FF 29 (2) -- 55.00 1.0 0.07 0.06 140.00 118.20 1 Water 19

1 SDV5 V21 12 1750 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 8.0 1.17 0.70 140.00 107.40 2 Water 37

1 SDV5 V23 12 1700 986 986 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 7.9 1.17 0.70 140.00 107.40 2 Water 37

EXHAUST FAN SCHEDULE

1 SDV5 V115 12 1500 1000 1000 82.60 1.00 30.40 2L 0.25 FF -- -- 55.00 5.9 1.17 0.70 140.00 107.40 1 Water 37

McQuay FCHF-1BSO2AA

MANUFACTURER/ MODEL NO.

CABINET HEATER SCHEDULE - Hot Water

13.7

MBHTAG

CH-1 200

CFM GPM

.5 .75

EWT

140 120

LWT

EAT

1/12

HP

120/1�

VOLTAGE

ALL

NOTES

DROP

FT

NOTES:

1. UNIT TO BE SEMI-RECESSED. PROVIDE TRIM KIT AND FILTERS, AND INTEGRAL/UNIT MOUNTED THERMOSTAT.

3500460-33.0VFD------ 4814045123.5WATERHWHMEZZANINEHWP-1

CIRCULATING PUMPS

PUMP NO. LOCATION SYSTEM CIRCULATING FLUID

FLUID GPM PUMP HEAD

FT. FLUID

TEMP

F

SP.

GR.

EFF.

(MIN) SERVED

CIRCUIT

PIPING TYPE MOTOR

VOLTSNOM.

HP. PHASE

RPM

NOTES MANUFACTURER/MODEL

TACO 1935

NOTES: VFD RATED MOTOR AND VFD CONTROLLER MOUNTED TO PUMP.

PLATE AND FRAME HEAT EXCHANGER SCHEDULE

MS-30

3500460-33.0VFD------ 4814045WATERHWHMEZZANINEHWP-2 TACO 1935

CONDENSING UNIT SCHEDULE

TAG

CU-1

NOTES:

WITH HOT GAS REHEAT, NON FUSED DISCONNECT, 5 MINTUE COMPRESSOR OFF TIME AND 20 SECOND COMPRESSOR STAGE

DELAY, SINGLE POWER POINT CONNECTION.

VARIABLE CAPACITY COMPRESSORS, PHASE AND BROWN OUT PROTECTION, SIGHT GLASS AND COMPRESSOR ISOLATION VALVES.

CONVENIENCE RECEPTACLE FACTORY WIRED, CONDENSER COIL GUARDS, VFD CONTROLLED CONDENSER FANS.

EER

CU-1

AMB. AIR

TEMP.

95 603.8

COMPRESSOR

QTY

REFRIGERANT

410A

ELECTRICAL

VOLTAGE MCA MOP

WEIGHT

LBS

2541460/3PH 113 125

MANUFACTURER AND

MODEL NUMBER

AAON CFA-060-DA3EC001

NOTES

ALL

AIR HANDLING UNIT SCHEDULE WITH HEAT RECLAIM

Provide a SCCR per the Div 26 OCPD study.

COOLING

MBH @

95 F

123.5

ALL

ALL

CONDENSATE PUMPS

PUMP NO. LOCATION TYPE UNIT GPM MOTIVE

PRESSURE

MOTOR

NOM. HP. VOLT-PHASE

RECEIVER

CRU-1 MEZZANINE 6 5 - 15

MANUFACTURER / MODEL

SIZE

GALLONS

REMARKS

PSI

WATSON MCDANIEL WPT3 ALL

NOTES:

PRESSURE MOTIVE

PUMP

1. PUMP-TRAP COMBINATION, S.S. BALL FLOAT AND CHECK VALVES.

ENGINEERS

T A

TE

OF I L L

NO

I S

ER

AW

LUOBEDAW

LRAE

I

062-044274

REGISTERED

PROFESSIONAL

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel

Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel

Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel

Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel

Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel

Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel

Fax

618.529.5262 618.457.8991

Geotechnical

11/8/2019 10:53:25 AM

MECHANICAL SCHEDULES Expand & Upgrade Building 42 for Laboratory

MQ-003

657-502

Marion, IL

11-07-2019

SUPPLY DUCTWORK TAKE-OFFS

SUPPLY DUCT TAKEOFF - AIR

TERMINAL UNIT

AIR TERMINAL UNITS

VOLUME DAMPER DETAIL

FLEXIBLE DUCT CONNECTIONS

EXHAUST OR RETURN BRANCH

DUCTWORK ACCESS PANEL AND DOOR DETAIL

DUCTWORK RADIUS ELBOWS

DUCTWORK SQUARE VANE ELBOWS

FIRE DAMPER INSTALLATION

DUCT CONNECTIONS - AIR TERMINAL

UNITS

SEE NOTE 1

SEE NOTE 2

SEE NOTE 3

NTS

NTS

NTS

ALTERNATE SUPPLY DUCT TAKEOFF -

NTS

NTS

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

J

NTS

MAIN EXHAUST OR RETURN

PLAN VIEW

SECTION "A-A"

"B" "B"

NTS

NTS

VANE

VANE

NTS

NTS

SECTION THRU

NTS

SEE NOTE 5

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

DIFFUSER (TYP.)

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

SOUND ATTENUATOR

SEE EQUIPMENT

SCHEDULE

REHEAT COIL

AIR TERMINAL UNIT

(CV OR VAV)

RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A

MINIMUM OF 3 TIMES THE DIAMETER OF INLET

A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO

THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM

LENGTH 3'-0" [900mm].

A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE

AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE

BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS).

FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A

DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT

OR BELOW 0.2"/100' [1.64Pa/m].

FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT

SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 3'-0"

[1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER

THAN 45°.

COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE

INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.

USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED

FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.

NOTE:

1.

2.

3.

4.

5.

6.

[25mm]

ACCESS

PANEL

NOTE 5

PERIMETER ANGLE, NOTE 3

(NOTE FASTENED TO PARTITION)

TYPICAL DUCT

INSULATION

FIRE BARRIER

PARTITION OR CHASE

NOTE 6

SLEEVE, NOTE 2

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

DAMPER,

NOTE 1

DUCT

CONNECTION

NOTE 4

SLEEVE, NOTE 2

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR.

FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND

GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN

THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO

DAMPER FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR

LINKS.

PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH.

FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH

CONCRETE CURB AROUND OPENING FOR DUCT.

NOTE:

1.

2.

3.

4.

5.

6.

7.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE

DOUBLE VANE TYPE.

NOTE:

1.

2.

3.

4.

SHORT RADIUS ELBOW

WITH TWO VANES

SHORT RADIUS ELBOW

WITH ONE VANE

STANDARD RADIUS OR

LONG RADIUS ELBOW

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

NOTE:

1.

2.

"A"

"A"

INSULATION

INSULATION

GASKET

DUCT

INSULATION

SECTION "B-B" FACTORY

FABRICATED

LATCH

FLEXIBLE

WASHER

HANDLE INSIDE

GASKET

CASING

ACCESS DOOR

ACCESS PANEL

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS

TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE

PINS.

3. SEE SMACNA 2005, FIGURE 9-15

VD

BRANCH DUCT

1/4W OR 4"

[100mm] MIN.

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

AIR

FLOW

AIR

FLOW

FLEXIBLE MATERIAL

AS SPECIFIED

WASHER

FLANGED

CONNECTION

ON FAN SIDE

1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]

NOMINAL WITH MATERIAL TAUT

[40mm][15mm][15mm]

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

DUCT

1 1/2" [40mm]

POCKET SLIP

ALTERNATE

POSITION

OF BOLT

1" [25mm] FLANGE & HEM

BOLT ON 4" [100mm] CENTERS

1"x1/8" [25x3mm] BAND IRON

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

RIVET ON 4"

[100mm]

CENTERS

SHEET METAL SCREWS ON

12" [300mm] CENTERS

DUCT

5/16" [8mm] FLANGE

BOLT ON 4" [100mm] CENTERS

1"x1/8" [25x3mm] BAND IRON

1"x1/8" [25x3mm] DRAW BAND

FLEXIBLE

MATERIAL AS

SPECIFIED

1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]

NOMINAL WITH MATERIAL TAUT

WASHER

FLANGED CONNECTION

ON FAN SIDE

SECTIONSIDE ELEVATION

STIFFEN BLADE

AS REQUIRED

DUCT

1/2" [15mm]

ROUND ROD PIN

INSULATION

STAND-OFF

HANDLE WITH

LOCKING

QUADRANT

INSIDE END BEARING

OUTSIDE END BEARING

1/8" [6mm]

CLEARANCE

ALL AROUND

DAMPER BLADE

INSULATION SEE

SPECIFICATION

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR

FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

NOTE:

1.

2.

FLOW

FLOW

PLAN VIEW

MAIN SUPPLY

SMACNA FIGURE 4-6

45° LEED IN

RIGID DUCT TO AIR TERMINAL

UNIT.

PLAN VIEW

MAIN SUPPLY

ROUND SHEET METAL

DUCT.

RIGID DUCT TO AIR TERMINAL

UNIT.

AIR

FLOW

MAIN SUPPLY

DUCT

AIR

FLOW

1/4 W OR 4"

[100mm] MIN.

AIR

FLOW

AIR

FLOW

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

MAIN

SUPPLY

DUCT

TOP REGISTER

ADJUSTABLE

METAL ROD

OR LINKAGE

PROVIDE VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

SEE FLOOR PLAN FOR

SPLIT DIMENSION

MAIN

SUPPLY

DUCT

TURNING VANES

SUPPLY REGISTER

OR BRANCH DUCT

AIR

FLOW

AIR

FLOW

AIR

FLOW

SUPPLY REGISTER TAKE-OFF

PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

K

MQ004

I

H

G

A

B

C

D

E

F

MQ004

MQ004

MQ004

MQ004

MQ004

MQ004

MQ004

MQ004

MQ004

MQ004

S E E

N O T E

W1

W

R

1/6W

W

1/2W

WW

W

2/3WR

R

W

W

1/2"

1/2" 1/2"

°M A X

"D"

W

ENGINEERS

T A

TE

OF I L L

NO

I S

ER

AW

LUOBEDAW

LRAE

I

062-044274

REGISTERED

PROFESSIONAL

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel

Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel

Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel

Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel

Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel

Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel

Fax

618.529.5262 618.457.8991

Geotechnical

11/8/2019 10:53:27 AM

MECHANICAL DETAILS Expand & Upgrade Building 42 for Laboratory

MQ-004

657-502

Marion, IL

11-07-2019

A

W

R

"B""B"

A

W

NO SCALE

SUPPLY DUCT

FLEX

SPIN-IN EXTRACTOR

BUTTERFLY DAMPER

MANUAL VOLUME

A

IR

F L O W

ROUND METAL

DUCT

ROUND AND/OR SQUARE NECK CEILING DIFFUSER TAKE-OFFS

SIDE VIEW

FOR SQUARE NECK DIFFUSER

DIFFUSER & OPPOSED BLADE DAMPER

MULTI-BLADE DAMPER FOR ROUND NECK

CONTROL GRID

SUPPLY DUCT

CEILING

QUADRANT

SIDE ELEVATION

SECTION

OUTSIDE END BEARING

DUCT

DAMPER BLADE

INSIDE END BEARING

INSULATION STAND-OFF

LOCKING QUADRANT

HANDLE WITH

INSULATION

DUCT

HANDLE WITH LOCKING

DAMPER BLADE

STIFFEN BLADE AS REQ'D.INSULATION

Ê" CLEARANCE ALL AROUND

1/2" ROUND ROD PIN

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

BRANCH DUCT TAKE-OFF

WITH EQUIPMENT IN DUCT

DUCT TRANSFORMATION

RADIUS ELBOWS

EXHAUST AND/OR RETURN BRANCH DUCT

ACCESS SECTION FOR ROUND/OVAL DUCT

SQUARE VANED ELBOWS

ACCESS DOOR

SPIN-IN AIR EXTRACTOR

DETAIL

HOUSING WELDED

TO DUCT SECTIONCEILING DIFFUSER TAKE-OFFS

VOLUME DAMPER DETAIL

FACTORY FABRICATED LATCH

2.

1.

ROUND OR FLAT OVAL

DUCT SECTION

INSULATION

DUCT

GASKET

PLAN OR SIDE VIEW

MAXIMUM ANGLES SHOWN SHALL APPLY.

NOTE: UNLESS OTHERWISE INDICATED ON PLANS,

AIR FLOW

20° MAX 30° MAX

20° MAX

EQUIPMENT

DUCT TRANSITION

PLAN OR SIDE VIEW

15° MAX

15° MAX

PLAN VIEW

MAIN SUPPLY DUCT

BRANCH DUCT

1/4W 4" MIN.

PLAN VIEW

BRANCH DUCT

DAMPER AS REQ'D.

PROVIDE VOLUME

1/4W 4" MIN.

45°

MAIN EXHAUST OR RETURN

NOTES:

STANDARD RADIUS ELBOW

GREATER THAN W

R SHALL EQUAL OR BE

R SHALL EQUAL OR BE

GREATER THAN 1/3 W.

2/3 W

1/3 W

VANE

W

SHORT RADIUS ELBOW WITH

ONE VANE

SHORT RADIUS ELBOW WITH TWO VANES

W

VANE

1/6 W 1/3 W

1/2 W

GREATER THAN 1/16 W.

R SHALL EQUAL OR BE

INCHES VANES SHALL BE DOUBLE VANE TYPE.

4. WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 20

3/4 INCH TRAILING EDGE.

1-1/2 INCH MAXIMUM SPACE BETWEEN VANES AND A

3. ALL SINGLE VANES SHALL HAVE A 2 INCH RADIUS,

VANE TYPE REGARDLESS OF W DIMENSION.

2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE

INSTALLED AS DETAILED BY SMACNA

1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND

W1

W2

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

NOTES: SECTION "B-B"

FLEXIBLE WASHER

INSULATION

CASING GASKET

HANDLE INSIDE

ACCESS PANEL

SECTION "A-A"

NOTE

NEGATIVE PRESSURE RELIEF

VENT IS SIMILAR

W

PROVIDE VOLUME

DAMPER WHEN

SHOWN ON PLANS

THE INTERIOR SURFACE OF ALL RADIUS

ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS SHOWN

ON PLANS MAY BE MADE SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS

SHALL HAVE VANES.VANES SHALL BE

CONSTRUCTED, SUPPORTED AND

FASTENED AS RECOMMENDED BY SMACNA.

COVER WITH HANDLE

AND CHAIN

RETAINER GASKETED

AND PRESSURE

SEALED.

20° MAX

L

MQ005

A

MQ005

B

MQ005

C

MQ005

E

MQ005

F

MQ005

J

MQ005

K

MQ005

I

MQ005

H

MQ005

G

MQ005

D

MQ005

ENGINEERS

T A

TE

OF I L L

NO

I S

ER

AW

LUOBEDAW

LRAE

I

062-044274

REGISTERED

PROFESSIONAL

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel

Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel

Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel

Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel

Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel

Fax

636.757.3060 636.757.3064

Industrial Hygenist

Holcomb Foundation 393 Wood Road Carbondale, IL 62901

Tel

Fax

618.529.5262 618.457.8991

Geotechnical

11/8/2019 10:53:29 AM

MECHANICAL DETAILS Expand & Upgrade Building 42 for Laboratory

MQ-005

657-502

Marion, IL

11-07-2019

D

D

NTS

AV

1. SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.

2. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS

SHOWN ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY FOR HOT WATER HEATING.

3. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN EXPANSION TANK SCHEDULE.

4. FOR HOT WATER SYSTEMS 2" [50mm] AND SMALLER AND CHILLED WATER SYSTEMS USE

IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.

5 SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM HAS A

MINIMUM OF 4 PSIG. [28kPa]

DIAPHRAGM

EXPANSION

TANK

TANK SADDLE

TO PUMP SUCTION

PITCH UP 1.6%

SLOPE (MIN.)

HANGER ROD SUPPORTS

(TYPICAL)

CONNECTOR PIPE

NORMALLY OPEN GATE VALVE

IN VERTICAL (REMOVE

HANDLE)

RUN DRAIN LINE TO

NEAREST F.D.

UNLESS INDICATED

OTHERWISE

FROM SYSTEM

AIR SEPARATOR

SEE NOTES NO. 3

& 4

DRAIN

HORIZONTAL EXPANSION TANK -

PIPING CONNECTIONS

COLD WATER FILL LINE. SEE

EXPANSION TANK SCHEDULE

FOR SIZE

NC

RUN DRAIN LINE

TO NEAREST FD

REDUCED PRESSURE BACKFLOW

PREVENTER

BUTTERFLY

OR BALL

ISOLATION

VALVE

HANGER RODS

(TYP)

AUTOMATIC AIR VENT

PI

1" GREATER THAN

1/2 OF FAN STATIC

PRESSURE

PIPING CONNECTIONS

NTS

TERMINAL UNIT WATER COILS -

MV

MODULATION CONTROL VALVE

DRAIN WITH HOSE

CONNECTION

SHUT OFF VALVE

WATER SUPPLY

UNION CONNECTIONS

(TYP.)

MANUAL AIR VENT

WATER RETURN

REDUCER, IF REQUIRED

TEST PLUG (TYP.)

COIL

H

MQ006

NOT TO SCALE

COOLING COIL CONDENSATE DRAIN

F

MQ006

A

MQ006

B

MQ006

C

MQ006

E

MQ006

G

MQ006

I

MQ006

D

MQ006

STEAM MAIN DRIP CONNECTION

END OF H.P. OR M.P.

VALVE CONNECTION

TYPICAL DRAIN

TYPICAL AIR VENT

ELEVATION

HEATING CONVERTOR DETAIL

TYPICAL STEAM CONNECTIONS TO H.W.

TYPICAL WATER CONNECTIONS TO

H.W. HEATING CONVERTOR DETAIL

CONVERTOR

CONTROL VALVE

SIZE AS

BUCKET TRAP

VACUUM BREAKER

AUTO AIR VENT

STRAINER (TYP); WITH HOSE END BLOW DOWN VALVE; TYPICAL

ECCENTRIC REDUCER (TYP)GLOBE VALVE BYPASS SAME

STEAM MAIN

CONDENSATE

RETURN

(TYPICAL)

UNION

CONTROL VALVE

(TYPICAL)

GATE VALVE

1/3 CAPACITY

2/3 CAPACITY

2/3 CAPACITY

PIPE SIZE PER

MANUFACTURER. PITCH

DOWN 1/8" PER FOOT TO

FLOOR DRAIN.

RUN FULL SIZE

OF DRAIN PAN

OUTLET TO AND

INCLUDING TEE

1" GREATER THAN

FAN STATIC

PRESSURE

PIPE RUN FOR

BOTTOM DRAIN

CONFIGURATION

CLEAN OUT

PLUG

COOLING COIL

DRAIN PAN

SEE DETAIL

K/MQ006

FOR WATER PIPING

LAST CONNECTION

NOTE:

(FULL SIZE)

DIRT POCKET

6" MIN.

STEAM MAIN

ON LINE

BASE OF RISER DRIPS SIMILAR TO ABOVE

OF TRAP

FULL SIZE

5LB. DROP UNLESS OTHERWISE

BUCKET TRAP CAP 200LBS/HR @

INDICATED

DRIP RETURN MAIN

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

PROVIDE HOSE CAP NUT ELEVATION

WELDED PIPING

ELEVATION

THREADED PIPING

NOTES:

DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.

2.

IF AUTOMATIC AIR VENTS ARE USED,

PIPE DISCHARGE TO DRAIN.

VENT ALL…