P09 657-502 Bid Drawings Part 5 of 10 Architectural 2-15 pages.pdf

PDF 13 MB Posted

Attached to
Expand and Upgrade Building 42 for Laboratory
Solicitation number
36C25520R0073
Issued by

About this file

This solicitation is for the expansion and upgrade of Building 42 at the Marion VA Medical Center to provide additional laboratory space. The solicitation seeks proposals for construction services including architectural, structural, MEP, and general contracting work. Key requirements include expanding the building footprint, upgrading interior finishes, and installing new casework, equipment, and HVAC systems. Proposals are due by November 8, 2019. The award date is unspecified but work shall be completed within 18 months of the award. Pricing shall be fixed for the base period of performance. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ground Floor Level 100'-0"

Lower Level 85'-10"

1st Floor/Interstitial 117'-2 1/2"

D

T.O. Parapet 137'-6"

Roof Level 135'-10"

Aluminum Composite Panel System

2" Exterior Insulation Finish System (EIFS)

Structural Steel (See Struct.)

Concrete and Metal Deck Floor System (Re: Struct)

Wall Base (Re: Finish Plans)

Sheet Membrane Waterproofing (continuous vertical strip)

Protection Drainage Board and Filter Fabric

Crushed Stone - 4" Min.

all sides of drain tile

Drain Tile wrapped w/ filter fabric (Re:

Plumbing)

Concrete Footing and Foundation (Re: Struct)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Grade Re: Civil

Finish Floor (Re: Finish Plans)

3/4" Exterior Grade Gypsum Board Sheathing on 6"

Metal Mechanical Louver

Prefinished Metal Flashing

2 1/2" x 7 1/2" clear anodized aluminum Curtainwall system - thermally broken with 1 1/4" laminated insulating glass. System to meet level 3 blast requirements

2" Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Exterior Insulation Finish System (EIFS) 5/8" Exterior Grade Gypsum Board Sheathing

6" Metal Studs @ 16" o.c. w/ thermal batt insulation (R-13) Minimum

Aluminum Composite Material - sloped 1/4" per foot

2" Exterior Insulation Finish System (EIFS)

Paint Exposed Concrete Foundation Wall to Match EIFS

Suspended Acoustical Lay-in Celing System (RE: RCP & Specs)

2'-5"

Flashing @ Bottom of EIFS; Hold EIFS 8" From Grade (Grade Varies along Building - See Civil)

Backer Rod & Sealant @ Mullion / Sill

Prefinished Sheet Metal Coping

2'-5"

Epoxy Resin Counter/Base Cabinet

2'-4 5/8"5/8" Exterior Grade Gypsum Board Sheathing

3 5/8"Structural Metal Studs Frame (See Structural dwgs)

/2

1" Insulated Spandrel Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized (See elevation sfor locations and specs)

2'-4 5/8"

/2

5/8" Gyp. Bd. on 3 5/8" Metal Stud @ 16" o.c.

2'-4 5/8"

Louver Filler Panel

5/8" Gypsum Board on Metal Studs

Aluminum Composite Material - sloped 1/4" per foot

3 5/8"Structural Metal Studs Frame (See Structural dwgs)

5/8" Gypsum Board on Metal Studs

Structural Steel (See Struct.)

Fireproofing on Structure (See Struct.)

Curtainwall Insulation Panel (3" Min) Clipped between mullions

Thermal Batt insulation to complete thermal enclosure

3/4" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

5/8" Exterior Grade Gypsum Board Sheathing

A510

Roof Membrane - extend membrane up parapet & under coping.

1/4" / Foot Max slope

2" Rigid Insulation on washer clips attached to concrete wall

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Air / Vapor Barrier 3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

Prefinished Metal Flashing

"1

A510

A510

A510

1/2" Compressible Isolation Joint

Vapor Retarder Below Concrete Mud Slab

4" Concrete Mud Slab at 4" below future finish floor - Unfinished Basement Floor

Motorized Shade 6

8" 5"

Ground Floor Level 100'-0"

1st Floor/Interstitial 117'-2 1/2"

Tunnel Level 87'-9"

T.O. Parapet 137'-6"

Roof Level 135'-10"

Crushed Stone - 4" Min. all sides of drain tile

Drain Tile wrapped w/ filter fabric (Re: Plumbing)

Concrete Footing and Foundation (Re: Struct)

Metal Mechanical Louver

2" Exterior Insulation Finish System (EIFS) on 5/8" Exterior Grade Gypsum Board Sheathing

2" Exterior Insulation Finish System (EIFS) adhered to concrete wall

Fireproofing on Structural Steel (Re: Struct.)

Concrete and Metal Deck Floor System (Re: Struct)

Wall Base (Re: Finish Plans)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Finish Floor (Re: Finish Plans)

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Suspended Acoustical Lay-in Celing System (RE: RCP & Specs)

Protection Drainage Board and Filter Fabric

2'-5"

2" Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Fireproofing on Structural Steel (See Struct.)

Thermal Batt insulation

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Louver Filler Panel

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

2" Exterior Insulation Finish System (EIFS)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1" Low-E Insulated Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized

Sheet Membrane Waterproofing (continuous vertical strip)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Prefinished Sheet Metal Coping 5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Roof Membrane - extend membrane up parapet & under coping.

1/4" / Foot Max slope

Cont. Vapor Retarder

Air / Vapor Barrier 3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

Prefinished Metal Flashing

Prefinished Metal Flashing

Prefinished Metal Flashing

Prefinished Metal Flashing

A510

A510

A500

1/2" Compressible Isolation Joint

Flashing @ Bottom of EIFS; Hold EIFS 8" From Grade (Grade Varies along Building - See Civil)

Cont Vapor Retarder

Open Office

E010

Mechanical Room

E102

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Solid Surface window sill (SS2)

Steel tube RE: Struct.

Steel tube RE: Struct.

Fireproofing on structure RE: Struct

Ground Floor Level 100'-0"

T.O. Existing Parapet 119'-0"

Lower Level 85'-10"

1st Floor/Interstitial 117'-2 1/2"

Existing Lower Level 91'-9"

T.O. Parapet 137'-6"

Roof Level 135'-10"

Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Exisitng EIFS to be removed

Remove existing parapet cap

2x FRT blocking

Metal Flashing

Expansion joint and joint cover Re: spec.

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Thermal Batt insulation RE

SPEC

Fireproofing on Structural Steel (Re:

Struct.)

5/8" Gypsum Board on 7/8" Hat Channels Metal Studs

Finish Floor (Re: Finish Plans)

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Suspended Acoustical Lay-in Celing System (RE:

RCP & Specs)

Structural Steel (Re:

Struct.)

9'-0"

Tunnel Access

ECSB002

Exisitng Foundation Wall

Concrete and Metal Deck Floor System (Re: Struct)

Wall Base (Re: Finish Plans)

Finish Floor (Re: Finish Plans)

A350

Prefinished Sheet Metal Coping 5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Roof Membrane - extend up parapet & under coping.

1/4" / Foot Max slope Air / Vapor Barrier

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

Fireproofing on Structural Steel (See Struct.)

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Prefinished Metal Flashing

Cont. Vapor Retarder

Sheet Membrane Waterproofing (continuous vertical strip)

Concrete Footing and Foundation (Re: Struct)

Concrete Slab (Re: Struct) - Sloped at 1:20 Max

New Foundation Wall (Re: Struct)

Cast in Place WaterStop

Approx. location of existing footin verify in filed.

A510

3"

Existing parapet to remain

Existing roof

Thermal Batt insulation to complete thermal enclosure

Fireproofing on Lateral Bracing RE STRUCT

1 1/2" dia. handrail

Fireproofing on Lateral Bracing RE STRUCT

Corridor

EC028

IT

E025

Unfinished Basement

ESB005

Mechanical Room

E102

7 3/4"

Ground Floor Level 100'-0"

T.O. Existing Parapet 119'-0"

1st Floor/Interstitial 117'-2 1/2"

Tunnel Level 87'-9"

T.O. Parapet 137'-6"

Roof Level 135'-10"

A510

Exterior Insulation Finish System (EIFS) on 5/8" Exterior Grade Gypsum Board Sheathing

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Thermal Batt insulation RE SPEC

Prefinished Sheet Metal Coping on 5/8" Fire Treated Plywood

5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Roof Membrane - extend up parapet & under coping.

1/4" / Foot Max slope

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

Spray on fireproofing on Structural Steel (See Struct.)

Thermal Batt insulation to complete thermal enclosure

Expansion joint and joint cover Re: spec

2x Weather Resistant WD blocking

Exterior Exit door See door schedule

Metal Guardrail beyond - RE Spec

Existing roof

Existing parapet to be removed as required to accomodate new door and roof access

FRT WD blocking as req'd at BO stringers

Metal Stair, Landing and Supports by metal stair fabricator. RE SPEC

E102B

Cont. Vapor Retarder

Prefinished Metal Flashing

Existing ceiling

Suspended Acoustical Lay-in Celing System (RE: RCP & Specs)

Remove existing EIFS

Existing wall to remain

Modify/Extend existing ceiling as required

Corridor

EC028

Existing Tunnel

ECSB003

Mechanical Room

E102

5/8" Gyp. Bd. on 3 5/8" Metal Stud @ 16" o.c.

/8

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:05

Wall Sections Expand & Upgrade Building 42 for Laboratory

A500

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1/2" = 1'-0"1 Wall Section @ Column Line D 1/2" = 1'-0"2 Wall Section - East 1/2" = 1'-0"3 Wall Section - Existing/New Connection

1/2" = 1'-0"4 Wall Section - Interstitial Roof Access

Ground Floor Level 100'-0"

Lower Level 85'-10"

1st Floor/Interstitial 117'-2 1/2"

Tunnel Level 87'-9"

A

T.O. Parapet 137'-6"

Roof Level 135'-10"

Sheet Membrane Waterproofing (continuous vertical strip)

Protection Drainage Board and Filter Fabric

Crushed Stone - 4" Min.

all sides of drain tile

Drain Tile wrapped w/ filter fabric (Re:

Plumbing)

Concrete Footing and Foundation (Re: Struct)

Grade Re: Civil

Paint Exposed Concrete Foundation Wall to Match EIFS

Flashing @ Bottom of EIFS; Hold EIFS 8" From Grade (Grade Varies along Building - See Civil)

Wall Base (Re: Finish Plans)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Finish Floor (Re: Finish Plans)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Prefinished Metal Flashing

Solid Surface Window Sill

Backer Rod & Sealant @ Mullion / Sill

Epoxy Resin Counter/Base Cabinet

Suspended Acoustical Lay-in Celing System (RE: RCP & Specs)

2" Exterior Insulation Finish System (EIFS)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1" Low-E Insulated Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized

Cont. Vapor Retarder Prefinished Metal Flashing

Structural Steel (Re: Struct.)

Cont. Vapor Retarder

Thermal Batt Insulation (R-19) Minimum

2" Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Thermal Batt insulation

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Cont. Vapor Retarder

Prefinished Sheet Metal Coping

5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Roof Membrane -extend membrane up parapet & under coping.

1/4" / Foot Max slope

Air / Vapor Barrier 3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

1/2" Compressible Isolation Joint

Office

E013

Existing Tunnel

ECSB003

Mechanical Room

E102

Fireproofing on Structural Steel (Re: Struct.)

Fireproofing on Structural Steel (Re: Struct.)

A300

A.2

Ground Floor Level 100'-0"

Lower Level 85'-10"

1st Floor/Interstitial 117'-2 1/2"

Tunnel Level 87'-9"

T.O. Parapet 137'-6"

Roof Level 135'-10"

Metal Mechanical Louver

2" Exterior Insulation Finish System (EIFS)

Existing Tunnel Roof

Structural Steel (Re: Struct.)

Wall Base (Re: Finish Plans)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Finish Floor (Re: Finish Plans)

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Suspended Acoustical Lay-in Celing System (RE: RCP & Specs)

2'-5"

2" Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Structural Steel (See Struct.)

Thermal Batt insulation to complete thermal enclosure

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

2" Exterior Insulation Finish System (EIFS)

5/8" Exterior Grade Gypsum Board Sheathing

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1" Low-E Insulated Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Cont. Vapor Retarder

Prefinished Sheet Metal Coping

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1/4" / Foot Max slope

Air / Vapor Barrier 3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Prefinished Metal Flashing

Prefinished Metal Flashing

Prefinished Metal Flashing

Prefinished Metal Flashing

A500

5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Roof Membrane over 1/2" recovery board extend to termination bar

Structural Steel (See Struct.)

T.O. Existing Tunnel F.V.

Line of existing parapet (beyond)

Fireproofing on Structural Steel (Re: Struct.)

Fireproofing on Steel Lateral Bracing (Re: Struct.)

Fireproofing on Structural Steel (Re: Struct.)

Existing Tunnel

ECSB003

Open Office

E010 bentonite blankets where waterproofing is not accessible

Concrete Footing and Foundation (Re: Struct)

Existing Slab

New wall set to elevation above Existing Tunnel ceiling

Ground Floor Level 100'-0"

Lower Level 85'-10"

1st Floor/Interstitial 117'-2 1/2"

Existing Lower Level 91'-9"

Roof Level 135'-10"

Stair Roof 150'-8 1/2"

T.O. Stair Tower Parapet 152'-0"

South Entry Ground Level 94'-0"

Vapor Retarder

4" CONC slab on 6" Compacted Gravel

Crushed Stone - 4" Min. all sides of drain tile

Drain Tile wrapped w/ filter fabric (Re: Plumbing)

Concrete Footing and Foundation (Re: Struct)

Protection Drainage Board and Filter Fabric

Sheet Membrane Waterproofing (continuous vertical strip)

1/2" Compressible Isolation Joint

Compacted Gravel; RE: Civil

Exterior Walk; RE: Civil

2" Exterior Insulation Finish System (EIFS) RE: Elevations & Details for Additional Information

12" CMU RE: STRUCT

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Prefinished Sheet Metal Coping

5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Prefinished Metal Flashing

Rigid Insulation (min. 5" thick / R30) tapered to roof drain on vapor barrier

MTL Decking (RE: Struct)

Roof Membrane over Rigid Insulation, extend membrane up parapet & under coping

1/2" Cover Board

Fireproofing on Structural Steel - See Struct.

Steel Lintel RE: STRUCT for opening support

Stair Landing @ 108'-7 1/2"

Stair Landing @ 126'-6 1/2"

Suspended Acoustical Lay-in Ceilng System (RE: RCP & Specs

Slope

Bond beam @ 8'-0" O.C Typ. RE:

STRUCT

Bond beam @ 8'-0" O.C Typ. RE:

STRUCT

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:14

Wall Sections Expand & Upgrade Building 42 for Laboratory

A501

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1/2" = 1'-0"1 Wall Section - North 1/2" = 1'-0"2 Wall Section -East at Tunnel Intersection

1/2" = 1'-0"3 Wall Section - Stair Tower

1st Floor/Interstitial 117'-2 1/2"

D

Ground Floor Lab Parapet 117'-11 1/2"

Aluminum Composite Panel System

5/8" Exterior Grade Gypsum Board Sheathing

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

1" Insulated Spandrel Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized (See elevation sfor locations and specs)

5/8" Gypsum Board on Metal Studs

Aluminum Composite Material - sloped 1/4" per foot; Wet seal all joints at horizontal portion

3 5/8"Structural Metal Studs Frame (See Structural dwgs)

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

5/8" Exterior Grade Gypsum Board Sheathing

Extend MTL flashing with drip edge over ACM panels

Reinforcing Mesh Per Manufacturers' Instructions

EIFS Base Coat & Finish Coat REF: Elevations and Specs

2" Insulation Board

Provide Vertical Drainage

MTI Sure Cavity (SC5016 or SC 5032) or Gravity Cavity ( GC 1816 or GC 1832) Strip for Drainage;

Back - Wrap Fabric at Both Ends for Bug Screen

MTL Stop Bead Per Manufacturers' Instructions

Peel & Stick Flashing

Back-Wrap Fabric on Top & Tottom for Bug Screen

Motorized Shade

Suspended Acoustical Lay-in Ceiling System (RE: RCP & Specs

Shade Pocket @ 112'-5" a.f.f.

Fireproofing on Structural Steel (See struct.)

D

T.O. Parapet 137'-6"

Roof Level 135'-10"

2" Exterior Insulation Finish System (EIFS)

3/4" Exterior Grade Gypsum Board Sheathing on 6" Mtl. Studs

Prefinished Sheet Metal Coping

2'-5"

Structural Steel (See Struct.)

5/8" Fire Treated Plywood on 6" structural metal studs @16" o.c.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Roof Membrane over 1/2" recovery board exted membrane up parapet & under coping.

1/4" / Foot Max slope

5/8" Cont.

Vapor Retarder

3 1/2" Concrete on 1 1/2" MTL Decking (Re: Struct.)

Rigid insulation (min. 5" thick / R-30) tapered to roof drain on vapor barrier concrete slab.

5/8" Gypsum Board on 3-5/8" Mtl. Studs

Mtl. Stop Bead per manufacuturer's instructions

Reinforcing Mesh per manufacturer's instructions

Aluminum Composite Panel System

5/8" Exterior Grade Gypsum Board Sheathing

Aluminum Composite Material - sloped 1/4" per foot; Wet seal all joints at horizontal portion

3 5/8"Structural Metal Studs Frame (See Structural dwgs)

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Air/Moisture Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

5/8" Exterior Grade Gypsum Board Sheathing

Pre-finished Mtl. Flashing with Drip Edge

2" Exterior Insulation Finish System (EIFS)

Alum. Curtainwall System

T.O. Existing Parapet 119'-0"

Remove existing parapet cap

2x FRT blocking

Metal Flashing

Expansion joint and joint cover Re: spec.

Prefinished Metal Flashing

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Thermal Batt insulation to complete thermal enclosure

Cont. Vapor Retarder

Existing Parapet

Reinforcing Mesh Per Manufacturers' Instructions

EIFS Base Coat & Finish Coat REF: Elevations and Specs

2" Insulation Board

Provide Vertical Drainage

MTI Sure Cavity (SC5016 or SC 5032) or Gravity Cavity ( GC 1816 or GC 1832)

Strip for Drainage; Back - Wrap Fabric at Both Ends for Bug Screen

MTL Stop Bead Per Manufacturers' Instructions

Peel & Stick Flashing

Back-Wrap Fabric on Top & Tottom for Bug Screen

3/4" Exterior Grade Gypsum Board on 6" Mtl Studs

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

2" Exterior Insulation Finish System (EIFS)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1" Low-E Insulated Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized

Cont. Vapor RetarderPrefinished Metal Flashing

2" Exterior Insulation Finish System (EIFS) adhered to concrete wall

5/8" Gypsum Board on 6" Metal Studs @ 16" O.C.

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

1" Low-E Insulated Glass in Thermally broken Exterior Aluminum Framing System - Clear Annodized

Cont. Vapor Retarder

Prefinished Metal Flashing

Solid Surface window sill (SS2)

1/2"

Exterior Insulation Finish System (EIFS)

3/4" Exterior Grade Gypsum Board Sheathing

Metal Mechanical Louver

Prefinished Metal Flashing at Louver Head

Exterior Insulation Finish System

(EIFS)

3/4" Exterior Grade Gypsum Board Sheathing

Louver Filler Panel

5/8" Gypsum Board on Metal Studs

5/8" Gypsum Board on Metal Studs

See Structural drawings for header information

B.O. Louver

120'-2 1/2"

2" Exterior Insulation Finish System (EIFS)

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

Cont. Vapor Retarder

128'-2 1/2"

T.O. Louver

9 1/4"

9 1/4"

/2

12" Typ.

11"1" Typ.

M a x

M a x

/4

/4

2"x2" Painted Steel Top Rail - Weld to Post. All welds to be cleaned and ground smooth for seamless appearance.

1 1/2" Metal Handrail Installed @ 2'-10" MAX above Stair Nosing - TYP.

Metal Pickets Installed @ 4" OC MAX. REF: Specifications for Additional Information

Painted Steel Stringer Beyond - REF: Structural Drawings for Additional Information

Concrete Filled Steel Tread and Risers. Paint All Exposed Steel - TYP. REF: Material Legend for Additional Information

Rubber Tread/Riser. See Finish Sheet.

Metal Pan Support - REF:

Structural Drawings

Expansion joint and joint cover Re: spec

Existing Roof Membrane

2x Weather Resistant WD blocking

2x Weather Resistant WD blocking

Exterior Exit door See door schedule

E102B

Metal Guardrail beyond - RE Spec

Mtl Stringer beyond

Existing roof

Existing parapet to be removed as require to accomodate new door and roof access

FRT WD blocking as req'd at BO stringers

Metal Tread

6'-3 3/4" 3 T @ 11" = 2'-9" 1'-0"

117'-2 1/2"

1st Floor

115'-0"

Existing Roof

1 1/2" Dia. Mtl Handrail

RE SPEC

1 1/2" Dia. Mtl Post

R

/8

/2

Metal Stair, Landing and Supports by metal stair fabricator. RE SPEC

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:26

Enlarged Sections Expand & Upgrade Building 42 for Laboratory

A510

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1 1/2" = 1'-0"2 Detail - @ Canopy

1 1/2" = 1'-0"1 Detail - Parapet @ EIFS

1 1/2" = 1'-0"3 Detail - @ Canopy & Curtain Wall

1 1/2" = 1'-0"4 Detail - Exp. Joint @ Extg. Parapet

1 1/2" = 1'-0"5 Head Detail @ Exterior Window

1 1/2" = 1'-0"6 Sill Detail @ Exterior Window

1 1/2" = 1'-0"7 Detail - @ Louver

1" = 1'-0"8 Detail - Typ. Stair Section

9 3D - Roof Access Stairs

10 3D - Roof Access Stairs - Exp Joint

1 1/2" = 1'-0"11 Detail - Exp. Joint @ Roof Access

A500

A500

A500

A500

A500

D

G G

G2

Structural Steel (See Struct.)

2 1/2" x 7 1/2" clear anodized aluminum Curtainwall system - thermally broken with 1 1/4" laminated insulating glass. System to meet level 3 blast requirements

5/8"

3 5/8" 1'-6 3/8"

3 5/8" 5/8"

B

5/8" Gyp. Bd. on 3 5/8" Metal Stud @ 16" o.c. to 4" above ceiling

3 1/2" Acoustic Batt; Full Height

Sound Batt Insulation

Vision Glass

/8

/8

/4

/8

/8

Compressable Seal.

DD

2.1

12" CMU RE: STRUCT

2" Exterior Insulation Finish System (EIFS)

E

/8

/4

7 5/8"

/8

Cont. Air/Water Barrier applied to CMU. Seal all penetrations and flash all openings in wall (See specs)

2.2

Cont. Air/Water Barrier applied to exterior gyp. bd. Seal all penetrations and flash all openings in wall (See specs)

8" CMU RE: STRUCT

G

Cont. vapor retarder

5/8" Gyp. Bd. on 3 5/8" Metal Studs @ 16" o.c.

Fireproofing on Structural Steel (See Struct.)

5/8" Gyp. Bd. on 6" Metal Studs @ 16" o.c. w/ thermal batt insulation

Stair/Elev Vestibule

EC027

Existing Wall to remain

Line of exisitng EIFS to be removed.

2 hour rated shaft wall. 2 layers 5/8" gyp. bd on 2 1/2" C-H Studs at 24" O.C. to deck above with 1" liner panel. See partition details

Shaft - Open to below

J

2'-4 3/4" 1" 1 1/2"1 1/4"

2 hour rated wall. 2 layers 5/8" gyp. bd on 3 5/8" Studs at 16" O.C. to deck above with 1" liner panel. See partition details

D

C.2C.2

JJ

D

Structural Steel (See Struct.)

2 1/2" x 7 1/2" clear anodized aluminum Curtainwall system - thermally broken with 1

1/4" laminated insulating glass. System to meet level 3 blast requirements

5/8" Gyp. Bd. on 3 5/8" Metal Stud @ 16" o.c. to 4" above ceiling

Corner mullion; Anchor and Shear Block as required by Curtainwall Mfgr.

Composite Metal Panel System

4 1/4" 7" 7 3/4" 2 1/4" 4"

/4

/8

/4

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:30

Plan Details Expand & Upgrade Building 42 for Laboratory

A520

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1 1/2" = 1'-0"3 Plan Detail @ Column Furring at Exterior Glazing

1 1/2" = 1'-0"2 Plan Detail @ Exterior Stair Exterior

1 1/2" = 1'-0"1 Plan Detail @ Rated Connection between Exisitng and New Stair/Shaft

1 1/2" = 1'-0"4 Plan Detail - Corner Mullion

2.1

Fire caulk

CONTINUOUS BACKER

ROD AND SEALANT

EACH SIDE (TYPICAL)

DOOR (RE: SCHEDULE)

/4

D

Infill with rockwook

BB

A301

New Tunnel Slab

Existing Tunnel Walls

Existing Tunnel Slab

Double Stud at door frames and corners

C

1 1/2" dia. mtl. guardrail @ 42" a.f.f.

1 1/2" dia. mtl. guardrail @ 42" a.f.f.

C

C

GWB Expansion Joint

Corridor

ECSB004

Existing Tunnel

ECSB003

ECSB004

G

G

A.6A.6

1'-6"

1'-0"

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:32

Plan Details Expand & Upgrade Building 42 for Laboratory

A521

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

N

1 1/2" = 1'-0"2 Plan Detail @ ELevator Shaft - Lower Level

N

1" = 1'-0"1 Plan Detail @ Expansion Joint Copy 1

OVAL HARD WOOD MAPLE

HANDRAIL, 1 1/2" X 1 1/4"

REF: SPEC FOR MORE

INFORMATION

2X FTWD BLOCKING

BEHIND GWB.

/4

1 1/2"

2 1/2"

/4

R e D o o r s c h e d u le

Notes:

1. Head Similar

2. Provide (3) Anchors MIN per Jamb; (4) at Rated Partitions

3. Refer to Door Schedule for Ratings Required

4. HM Jamb Throat 1/8" Larger than Partition, Caulk and Paint , TYP

Double Stud @ Jamb

Welded HM Frame

X

P-Type;

REF: Plan

Line Of Adjacent Partition (Where

Occurs)

1/2"

/2

1 3/4" ± Varies

REF:

Schedule

A.-B. Jamb (Head SIM)

Double 3-5/8" MTL Stud @ Jamb, TYP

Sidelight

ALUM Frame

/2

/4

ALUM Frame

Clear TGL (1/4" TYP) w/ Frosted Film; See SPEC

Blocking as REQD

C. Sill

Finished Floor

5/8" GWB, TYP

1 5/8" MTL. STUDS

3 5/8" MTL. STUDS

5/8" TYPE

"X" GYP. BD.

/8

/2

1'-6 3/4"

W A

L L

D E

P T

H

/2

WALL OPENING

1'-1"

/2

HOLLOW METAL FRAME -

PAINT (RE: FINISH SCHEDULE)

JAMB ANCHORS PER MNFR

RECOMMENDATIONS

APPLIED STOP ON

HOLLOW METAL FRAME

(PAINT)(TYP.)(RE: FINISH

SCHEDULE)

1/4" GLASS (RE: FRAME

TYPE FOR GLAZING TYPE)SEALANT AT FRAME

PERIMETER (BOTH SIDES)

(R E

P

A R

T

IT

IO

N

T Y

P E

V A

R

IE

S

/8

E Q

E

Q

2" 5/8"

2 5/8"

SEE ROOM

SCHEDULE FOR

FINISHES TYP.

5/8" GYPSUM BOARD

GALV. HOLLOW METAL

FRAME (PAINT) FILL WITH

BATT INSULATION

CONTINUOUS BACKER

ROD AND SEALANT

EACH SIDE (TYPICAL)

DOOR (RE: SCHEDULE)

EXTERIOR INSULATION

FINISH SYSTEM (EIFS) ON

1/2" FIBER REINFORCED

GYP SHEATHING ON STL.

STUDS (RE: STRUCT.

DWGS.)

/4

/8

5 7/8"

/8

1/4" TEMPERED

GLASS

HOLLOW METAL

FRAME (PAINT)(TYP.)

(RE: FINISH

SCHEDULE)

APPLIED STOP ON

HOLLOW METAL FRAME

(PAINT)(TYP.)(RE:

FINISH SCHEDULE)

MTL. DECK WITH CONCRETE FILL (RE:

STRUCTURAL)

FILL VOIDS WITH FIRESAFING INSULATION

AS REQ'D

SEALANT

CUT GYPSUM BOARD TO DECK

CONFIGURATION (1/2" CONT. GAP)

20 GA. SLIP TRACK FASTENED TO

STRUCTURE ABOVE

25 GA. LONG LEG RUNNER - NEST STUDS IN

RUNNER AND PROVIDE 1/2" SPACE BETWEEN

TRACK AND RUNNER FOR DEFLECTION

2 LAYERS 5/8" TYPE "X" GYPSUM BOARD (DO

NOT FASTEN GYPSUM BOARD TO UPPER

TRACK OF SLIP JOINT) ON MTL. STUDS PER

PARTITION SCHEDULE

/2

MTL. DECK WITH CONCRETE FILL (RE:

STRUCTURAL)

FILL VOIDS WITH FIRESAFING

INSULATION AS REQ'D

SEALANT

CUT GYPSUM BOARD TO DECK

CONFIGURATION (1/2" CONT. GAP)

20 GA. SLIP TRACK FASTENED TO

STRUCTURE ABOVE

25 GA. LONG LEG RUNNER - NEST

STUDS IN RUNNER AND PROVIDE 1/2"

SPACE BETWEEN TRACK AND

RUNNER FOR DEFLECTION

2 LAYERS 5/8" TYPE "X" GYPSUM BOARD

(DO NOT FASTEN GYPSUM BOARD TO

UPPER TRACK OF SLIP JOINT) ON MTL.

STUDS PER PARTITION SCHEDULE

/2

Painted 3/4" X 3/4" Hollow Galvanized Steel Tube Balluster or Post

1 1/2" OS DIA Painted Steel Handrail

3/4" Dia Steel Rod

1 1/2" OS DIA Painted Steel Handrail

3/4" Painted Steel Bracket; Weld to Center of Vertical Baluster or Post (See Elevations)

/4

Painted 1" X 1" Hollow Galvanized Steel Tube Balluster or 2" DIA Tube Post

HOLD

1 1/2"

Section

Plan

/8

1 1/2" OS DIA Painted Steel Handrail

3/4" Painted Steel Bracket Welded to Steel Plate

/4

3/16" Thick STL Plate 2" DIA

(4) 1/4" DIA Holes

3/8" 5/8" 5/8" 3/8"

2"

3/4"x3/4" STL Bracket Welded to STL Plate

EQ EQ

1/4" Thick STL Plate 2" DIA

Steel Cover Plate

1/4" DIA Expansion Bolts into Brick/Stone Wall Beyond

Elevation

Plan

NOTE:

USE "SMACNA" GUIDELINES FOR GAUGES

& SCUPPER CONFIGURATION.

METAL DECK.

RIGID INSULATION.

SINGLE-PLY ROOFING

MEMBRANE.

SHEET MTL SCUPPER LINING.

TYPICAL OPENING

VARIES

ALUM PRESSURE

BARS - ANCHOR

TO WALL.

EXTERIOR WALL

CONSTRUCTION

Sealant both sides

1/4" Glass (RE: SPEC and window types for additional information

ALUM Frame

'J' Molding (TYP)

(RE: PARTITION TYPE)

2x Fire Retardant Treated WD Blocking in Walls as required

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:34

Details Expand & Upgrade Building 42 for Laboratory

A550

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

6" = 1'-0"5 DETAIL - HANDRAIL

3" = 1'-0"6 Detail - HM Door Jamb

3" = 1'-0"9 Details - TYP ALUM Sidelight Frame @ Offices / Conference Rooms

1 1/2" = 1'-0"15 FEC RECESSED 1 HR PLAN SECTION

3" = 1'-0"17 HEAD/JAMB - HM

3" = 1'-0"18 HEAD/JAMB - HM - EIFS

3" = 1'-0"19 HM SILL - SINGLE PANE GLASS

3" = 1'-0"30

SLIP TRACK PARALLEL TO FLUTES AT

2-HOUR FIRE PARTITION

3" = 1'-0"34

SLIP TRACK PERPENDICULAR TO

FLUTES AT 2-HOUR FIRE PARTITION

6" = 1'-0"2 Detail - Handrail Support @ Guardrail 6" = 1'-0"10 Detail - Handrail Support @ Stair

3/4" = 1'-0"4 Scupper Detail

3" = 1'-0"1 HEAD/JAMB - ALUM - INTERIOR

45°

(2) 12 GAGE

HANGAR

WIRES @ OPPOSITE

CORNERS TO

STRUCTURE

ACT & GRID

12 GAGE HANGAR WIRE

ELECTRICAL FIXTURE-

MECHANICALLY

FASTENED TO

SUSPENSION SYSTEM

ELECTRICAL/HVAC

FIXTURE

-MECHANICALLY FASTEN

TO SUSPENSION

SYSTEM

LFB

LATERAL FORCE BRACE

EC

EXPANSION CLIP

SJCG CLIP

MAIN GRID RUN

AT LAY-IN FIXTURE

AT RECESSED DOWNLIGHT

REQUIREMENTS:

-ATTACHED ON (2) ADJACENT WALLS WITH THE BERC2.

NOTE-ATTACHING BERC2 CLIP TO THE WALL SECURES

THE GRID AND ELIMINATES THE NEED FOR POP RIVITS

THROUGH THE VISIBLE PART OF THE WALL MOLDING.

-BERC2 CLIP WITH 3/4" CLEARANCE ON UNATTACHED ENDS.

-BERC2 CLIP ON ALL (4) WALLS

-HEAVY-DUTY GRID

-LATERAL BRACING

-PERIMETER SUPPORT WIRE

-EXPANSION CLIP EVERY X S.F.

BERC2 CLIP

ATTACHED WALL

NOTE: POP RIVITS ARE ACCEPTABLE

UNATTACHED WALL

7/8"

1/2"

7/8"

8" MAX.

8" MAX.

4"

6" Fascia Molding

Pop-Rivet - This Side Only

Channel Molding

2"

BOTTOM OF DECK /

STRUCTURE

3 5/8" STEEL STUD

KICKERS @ 4'-0" 0C

5/8" GYP BD CONT.

RUN 4" ABOVE

CEILING

3 5/8" STEEL STUDS

AT 16" OC

ACT Ceiling

RE: RCP

ACT Ceiling

RE: RCP

GWB Bulkhead

RE: RCP

A F

F

M in

Bottom of Decking

3 5/8" MTL Stud Kicker

@ 32" OC

5/8" GYP BD CONT.

RUN 6" ABOVE

CEILING

3 5/8" MTL Studs @

16" OC MIN

H O

L D

HOLD

8" 4 7/8"

ACT Ceiling

AFF: See RCP

3 5/8" MTL Studs @

16" OC MIN

GWB Soffit

Align w/ Hor. Mullion

J-Mold @ Mullion Face

Align GWB with top of Horizontal Mullion

V .I

.F

Manual Roller Shade Secured with Bracket to

Every Veritcal Mullion

BOTTOM OF DECK /

STRUCTURE

3 5/8" STEEL STUD

KICKERS @ 4'-0" 0C

5/8" GYP BD CONT.

RUN 6" ABOVE

CEILING

3 5/8" STEEL STUDS

AT 16" OC

See RCP

Varies

GWB

RE: RCP @ Elevations

ACT Ceiling

RE: RCP

ACT Ceiling

RE: RCP

1/2" Tempered Glazing

1 1/2" x 3" Extruded Aluminum Channel with Cont. gasket attached to MTL Stud @ 16" OC.

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:37

RCP Details Expand & Upgrade Building 42 for Laboratory

A551

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1 1/2" = 1'-0"1 Detail - Seismic Light Fixture 1" = 1'-0"2 Detail - Seismic Restraints @

Suspended Ceilings 3" = 1'-0"3 Detail - Seismic Separation Joint

3" = 1'-0"4 Detail - Bulkhead

1 1/2" = 1'-0"5 Detail - Window Pocket @ Lab

1 1/2" = 1'-0"6 Detail - Interior Glass Partition @ Head

E013

P2

P4

WSF5 (typ) 1/2" Clear TGL Sliding Panel

R

CL

QPON

9 5/8"

/8

/4

Applied Vinyl Numbers (typ) Font: Helvetica Bold Color: Pantone 611 C

E003 E005 E007 E009 E011

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:46:56

Sign Schedule & Details Expand & Upgrade Building 42 for Laboratory

A552

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1/8" = 1'-0"1 Department Sign - Type "A"

1/8" = 1'-0"2 Room Sign - Type "C"

1/8" = 1'-0"3 Unisex Restroom Sign - Type "B"

Pantone 402 C

Pantone 2945 C

GENERAL NOTES - Interior SignsPantone 402 C

Pantone 402 C

A. All signs should be in accordance with with VA Signage Design Guide.

B. Verify all room names & numbers with owner prior to sign production.

C. Signs should be level when attached over two diferent wall materials (ie.

drywall & ceramic wall tile), where applicapable.

D. All signage to be in compliance with ADA Accessibility Standards for

Fereral Facilities.

E. Verify in field all dimensions before all signage and graphic fabrication & installation.

F. All sign backing to be Environmentally Preffered Product EPP

Downstream Certified.

G. All signs with frames to be mechanically fastenet to wall.

H. All signs to be mounted at 5'-0" O.C. U.O.N. to the latch side of the room entry door.

NOTES - Department Sign

ADA MODULE:

Material: .125" non-glare acrylic, backpainted silver to match Matthew's Paint MP-1810 (metallic silver) with vinyl graphic applied to back

Image: Request from Architect Tactile Text: Helvetica Bold, raised 1/32" Text Color: Black Grade 2 Braille: Clear Frame: 1/8" face, 1/2" profile, anodized aluminum finished, 75% recycled content

CHANGABLE MODULE:

Base: .125" thick non-glare acrylic, back-painted silver to match Matthew's Paint MP-1810 Filler: .025" thick acrylic Text: Black ink on transparent acetate Face: .125" thick non-glare acrylic Typeface: Helvetica Medium

TRIM:

Material: .125" non-glare acrylic, back-painted

Pantone 402C

NOTES - Unisex restroom Sign

ADA MODULE:

Material: .125" non-glare acrylic, backpainted

Pantone 2945 C Tactile Text: Helvetica Bold, raised 1/32" Text/Symbol Color: To match Matthew's Paint

MP-1810 (metallic silver) Frame: 1/8" face, 1/2" profile, anodized aluminum finished, 75% recycled content

TRIM:

Material: .125" non-glare acrylic, back-painted

Pantone 402C

NOTES - Room Sign

ADA MODULE:

Material: .125" non-glare acrylic, backpainted silver to match Matthew's Paint MP-1810 (metallic silver)

Tactile Text: Helvetica Bold, raised 1/32" Text Color: Black Grade 2 Braille: Clear Frame: 1/8" face, 1/2" profile, anodized aluminum finished, 75% recycled content

TRIM:

Material: .125" non-glare acrylic, back-painted

Pantone 402C

Vinyl graphic Image

ROOM NUMBER ROOM NAME REMARKSSIGN TYPE

ECSB002 Tunnel Access 1C

ESB004 Elevator Machine Room 1C

ESB005 Unfinished Basement 1, 2C

EL1 Elevator 1, 3A

E002 Phlebotomy 1A

E003 Station 4---

E012 Office 1C

E013 Office 1C

INTERIOR SIGN SCHEDULE

REMARKS - Interior Sign Schedule

1. Coordinate with C.O.R. exact location and name (if applicapable) of sign

2. Two signs this room

3. Sign at each floor stop (4 total)

4. Custom Vinyl Graphic, See elevation on 4/A552

1/4" = 1'-0"4 Vinyl Room Numbers - Phebotomy 101

- North

E004 Patient Toilet 1B

E005 Station 4---

E006 Patient Toilet 1B

E007 Station 4---

E008 Pyxis Storage 1, 2B

E009 Station 4---

E011 Station 4---

E014 PSA 1C

E015 Shared Office 1C

E016 Shared Office 1C

E017 Office 1C

E018 Core/Specimin 1C

E018C Corridor 1C

E020 Toilet 1B

E021 Blood Bank 1C

E022 Toilet 1B

E023 Histology 1C

E023A Acid/Base 1C

E019A Microbiology 1C

E019B Bio-Safety Level 3 1C

E023A Acid/Base 1C

E024 Break Room 1C

E025 IT 1C

E026 Conference Room 1C

EC027 Stair/Elev/Vestibule 1C

E102 Mechanical Room 1C

P4 P2

RB1

P2 P2 P2

Ch5 G2

Co1 Co1

G1

U1

P2 P4

4" Backsplash (typ)

8" Wiremold (typ)

WSF2 (typ)

2'-4 1/4"

2 1/2"

1'-9" 5'-0" 2'-0" 2'-6" 6'-1 3/8" 2'-6" 2'-0" 2'-4 1/2" 2'-0" 3'-7" 5'-0" 3'-0" 2'-6" 2'-0" 2'-0"

3 7/8" typ.

2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6"

Co1

G1

G1 Ch1a

WSF2 (typ)

P4

Ch1a

Open

4" Backsplash

4'-0"4'-0"4'-0"4'-0"4'-0"

2'-6" 3'-0" 3'-1" 1'-3" 3'-7 3/8" 3'-0" 3'-7 3/8" 1'-3" 2'-2 1/8" 1'-3" 2'-1 3/4"

1 7/8"

(typ)

2'-0" 3'-0" 5'-1 3/4" 2'-0" 3'-1" 3'-0"

G5

C7

P2

4" Backsplash

WSF2 (typ)

E019A

3'-0" 3'-0" 3'-0" 3'-0" 3'-0"

" He3

G2 He1

He4 C2 He2

WSF2 (typ)

P4

4" BACKSPLASH

(typ)1

Open

2'-1 3/4" 1'-3" 2'-2 1/8" 1'-3" 3'-9 3/8" 3'-0" 3'-5 3/8" 1'-3" 3'-1" 3'-0"

1 7/8"

4'-0"4'-0"4'-0"4'-0"4'-0"

1'-0" 20'-0 3/8" 1'-0"

U2 G1

U3

G2 G2

WSF2 (typ)

4" Backsplash (typ)

8" Wiremold (typ)

P4

P41 typ.

1'-9"2'-6"4'-7 5/8"1'-9"2'-6"1'-9"2'-6"5'-0"9 3/8"2'-4 1/4" 3'-0" 2'-10 7/8" 2'-0" 2'-10 7/8" 2'-6" 4'-0" 5'-5 3/4" 1'-10" 7"

He2 He2 He4

C2

He1 He3

WSF2 (typ)

4: Backsplash (typ)

P4

Open

4'-0"4'-0"4'-0"4'-0"4'-0"1'-0" 1'-0"

1 7/8"

3'-0" 3'-1" 1'-3" 3'-7 3/8" 3'-0" 3'-7 3/8" 1'-3" 2'-2 1/8" 1'-3" 2'-1 3/4"

WSF2 (typ)

P4

4" backsplash (typ)

Open

2'-1 3/4" 1'-3" 2'-2 1/8" 1'-3" 3'-9 3/8" 3'-0" 3'-5 3/8" 1'-3" 3'-1" 3'-0"

1 7/8"

2'-6"

4'-0"4'-0" 4'-0" 4'-0"4'-0"1'-1" 11 3/8"

E018C

GL1

PL3

RB1

P1

P2

P1

RB1

3 3 3

P1

G2 G2

E019 Ch3 Ch2

WSF2

(typ)

P2 P2

FEC

4'-0" 4'-6" 3'-6" 3'-4"

3'-0"3'-0"3'-0"3'-0"3'-0"

2'-6" 3'-0 7/8" 1'-9" 3'-0 7/8" 2'-6"

RB1 RB1

P4 P4

P4

A650 Wood Veneer Bench PL3

A650

SIM

5'-0"5'-0"

(+ / - ) 14'-10"

Cushion

Cushion

Pendant Lights; RE: RCP

4 4 4

TVs by VA

RB1

GF1GF1

E002

A300

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

42-AdditionApproved: Associate Director

Approved: Chief of Staff

Approved: Chief Engineer

Approved: Infection Control

Approved: Safety Officer

Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Office of Facilities

ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032

Tel Fax

317.580.0402 317.582.0766

Structural

Asaturian Eaton & Assoc.

1440 Old West Main Carbondale, IL 62901

Tel Fax

618.529.3414 618.529.3423

Civil

John A Jurgiel & Assoc.

123 N. Main Street St. Charles, MO 63301

Tel 636.757.3060 636.757.3064

Industrial Hygenist

Heapy Engineering 1400 W. Dorothy Lane Dyton OH 45409

Tel 618.529.5262

Electrical

11/7/2019 15:38:47

Interior Elevations Expand & Upgrade Building 42 for Laboratory

A600

657-502

Marion, IL

11-08-2019

Bid Documents

RD AJS

1/4" = 1'-0"2 Elevation - Waiting 001 - West

1/4" = 1'-0"5 Lab - Main - East 1/4" = 1'-0"6 Lab - Main - Island

1/4" = 1'-0"7 Lab - Main - West 1/4" = 1'-0"8 Lab - Main - Island 2

1/4" = 1'-0"11 Lab - Main - South

1/4" = 1'-0"10 Lab - Main - Island 4 1/4" = 1'-0"9 Lab - Main - Island 3

1/4" = 1'-0"1 Public Corridor - East

1/4" = 1'-0"12 Lab - Main - North

1/4" = 1'-0"4 Elevation - Waiting 001 - North

To Room Beyond

GL1

PL3

TO CORRIDOR

BEYOND

KEYED NOTES - ELEVATIONS

1/4" = 1'-0"3 Elevation - Waiting 001 - East

Metal casework and counters by G.C.1

Provide blocking2

CG23

RS1; Field Verify Dimensions4

G1

WSF2

4" Backsplash

P4

3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"

3'-6" 3'-6" 3'-6" 3'-6" 3'-6"

Hi8

Hi7

Hi9

Hi1.2

Hi5

Hi2

1'-6" 1'-6" 2'-0" 2'-5 1/2"3'-6" 2'-3 3/8"

Hi5 Hi9

Hi11

4" Backsplash

WSF2 (typ)

P4

8" Wiremold

1'-11 7/8"3'-7 7/8"3'-0"3'-0"3'-0"4'-9 5/8"2'-5 1/2"

3 3 3

P4

E023A

Hi1.1

Hi6 Hi6

Hi1 Hi2 Hi5 Hi3

Hi1.2

WSF2 (typ)

4" backsplash

P4

2'-0" 3'-0" 3'-6" 1'-6" 3'-5 1/4" 1'-6" 3'-5 1/8" 1'-4" 2'-4 7/8"

M5 G2

M8

M9

M6

WSF2 (typ)

P4

4" Backsplash 1

2'-5 1/8" 3'-6" 3'-6" 3'-6"1'-0 3/8"

E019A

M12 M4

M11

C6

Open

3'-0" 3'-0" 3'-0"

2'-0" 2'-0" 3'-0" 3'-4 5/8" 1'-6"

P4

WSF2 (typ)

M11 M12

M4

P4

WSF2 typ.

3'-0" 1'-6" 3'-4 5/8" 3'-0" 2'-0" 2'-1 1/2"

3'-0" 3'-0" 3'-0"

OPEN

4" Backsplash

G2

P4

WSF2

4" Backsplash1

3'-0"3'-0"3'-0"3'-0"3'-0"3'-0"3'-0"

3'-6" 3'-6" 1'-6" 3'-6" 3'-6" 3'-6" 1'-6"

E019B M14 M3 M2

G2 4" Backsplash

WSF2 (typ)

2'-0" 3'-0" 3'-0" 1'-6"

P2

2'-5 1/8"

Hi11 Hi11 Hi9

Hi7

Hi8

Hi1.3

Hi10 H134" Backsplash

WSF2 (typ)

P2

3'-6" 1'-6" 1'-6" 3'-6" 3'-6" 3'-6" 3'-6" 4'-0" 1'-6"

3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"

2'-4 7/8"

4 3/8"

1'-6" 4 3/4"

P2

G1

Ch1a

P4

WSF2

4" Backsplash

3'-0" 7'-2 3/8" 3'-0" 1/2"

OPEN

Ch1a

P4

4" backsplash (typ)

WSF2

3'-0" 3'-0"

OPEN

E018B

G7

P4P4

P4

P4

P4

WSF5 (typ)

3/4" Max. Scribe typ.

A650

A650

A650

3'-0"3'-0"3'-0" 3'-0"3'-0"3'-0"EQ EQ

1'-6"3'-6"1'-6"2'-6"1'-6"5'-0"2'-6"

A650

A650

A650

A650

PL2 Base Cabinets (typ)

PL1 PL1

PL2 Base Cabinets (typ)

SS1

SS1

G2 G2…